Beruflich Dokumente
Kultur Dokumente
Abstract In distribution systems the most critical voltage levels. This impact depends on size, type and location
disturbance is the interruption of the power service. However, of DG units [3].
the main concern for end-users is the mal-operation produced by
voltage sags. The presence of distributed generation (DG) Voltage sags are the most important power quality (PQ)
modifies the radial configuration of distribution systems and disturbance that many industrial, commercial and residential
imposes new challenges to be evaluated concerning to the users faced it [4]. They are short-duration reductions in RMS
assessment of voltage stability, the performance of protection voltage at power frequency between 10% and 90% of the
system, the active power generation and consequently the
nominal value with durations from half-cycle to a few
behavior of voltage sags. This paper shows the influence on
voltage sag characteristics by the presence of DG in the IEEE-13 seconds. These disturbances produce mal-operation or
bus test feeder. The analysis is performed by using a random interruption on sensitive equipment, in many occasions leads
generation of disturbances using a MATLAB routine and to complete interruptions of the industrial process and affect
simulated in ATP/EMTP software tool. Several case studies in the the proper operation of power and distribution systems [5].
test system taking into account different locations and sizes of DG
unit are presented. Study of sags has increased the interest on mitigation
methods to preventing or reducing their effects. Usually, DG
Index Terms voltage sags, distributed generation (DG), helps to mitigate voltage sags because increases the short
power quality, modeling, IEEE-13, ATP/EMTP. circuit power in distribution networks, increases voltage
profiles of nodes in fault condition and also helps to maintain
I. INTRODUCTION the voltages during the fault [2], [6]. In addition, a factor as the
Noviembre 2 7, 28 y 29
Medelln Colombia
2013
VII Simposio Internacional sobre
4.16/0.480 kV, one voltage regulator unit, two shunt capacitor system is proposed. This function is given by
banks, unbalanced spot and distributed loads [7]. On the other
(2)
hand, in steady-state the IEEE 13-bus system present three
types of disturbances: (a) voltage imbalances, (b) load Where, is the local function for each fault condition
unbalance and (c) reactive power flows. Fig. 1 shows the in the bus . Table 2 presents the overall functions of IEEE-13
scheme of the IEEE-13 bus test feeder. buses organized in descendent order.
TABLE I
FAULT TYPES
Fault code
Fault type Involved phases
(A)
A 1
single
B 2
line-to-ground (LG)
C 3
AB 4
line-to-line
BC 5
(LL)
AC 6
Double AB 7
line-to-ground BC 8
(2LG) AC 9
Three line
ABC 10
(3L)
Three line-to-ground
ABC to-ground 11
(3LG)
Noviembre 2 7, 28 y 29
Medelln Colombia
2013
VII Simposio Internacional sobre
IV. CASE STUDIES TABLE III
CASE STUDIES FOR DG UNIT IMPLEMENTATION
Voltage sags features at bus of interest are predicted
applying a method of stochastic generation of disturbances Fault Resistance Local
Case Fault Position
based on the distribution system model and statistical data of Type Value [] Function
faults [5]. This method selects different fault positions 1 N671 LG 1 0.19 9.396
(critical buses identified in section III), the fault type and the 2 50% Line 632-671 2LG 9 0.19 12.495
fault resistance taking into account statistical data about faults 3 N675 3L 10 0.38 10.067
in the electrical system. In addition, the method assumes that
sags are originated only by faults, and they are rectangular. V. ATP/EMTP MODEL OF THE DISTRIBUTED GENERATION
UNIT
Stochastic generation of disturbances is implemented using
a Matlab routine, generating random numbers with a density In this paper, only one distributed source is installed. This
of probability. The total of 200 voltage sag conditions are DG unit is a medium power synchronous generator, whose
simulated on the IEEE-13 bus test feeder. The parameters used ratings and electric parameters are shown in Table 4. In
in simulations are the following: simulations this generator will be connected to all buses of
Location of fault: the fault may occur at any critical node IEEE-13 system.
(632, 633, 671, 675 and 680) or at any line that connect TABLE IV
the critical nodes. This paper assumes that the fault ELECTRICAL PARAMETERS OF THE SYNCHRONOUS GENERATOR
position in each line may occur in three positions (25%, Parameter Value
50% and 75%). The density function for nodes and lines Rated Frequency 60 Hz
is 65% and 35%, respectively. Fig. 2 shows with a dashed Rated Voltage 4.16 kV
line the selected critical zones of IEEE-13 system. Number of poles 2
Probability of fault types: LG:75%, LL: 15%, 2LG: 6%, Armature resistance: Ra 0.0015 p.u.
3L and 3LG: 4% Armature leakage reactance: Xl 0.1300 p.u.
Zero-sequence reactance: Xo 0.1000 p.u.
Fault resistance: 8 different values between 0.19 and d-axis synchronous reactance: Xd 0.9500 p.u.
0.85 are established. The fault resistance is selected by d-axis transient reactance: Xd' 0.1400 p.u.
an uniform density function. d-axis sub-transient reactance: Xd'' 0.1350 p.u.
q-axis synchronous reactance: Xq 0.9200 p.u.
q-axis transient reactance: Xq' 0.2100 p.u.
q-axis sub-transient reactance: Xq'' 0.1400 p.u.
d-axis open circuit transient tine constant: Tdo' 4.300 s
d-axis open circuit sub-transient tine constant: Tdo'' 0.032 s
q-axis open circuit transient tine constant: Tqo' 0.850 s
q-axis open circuit sub-transient tine constant: Tqo'' 0.050 s
Noviembre 2 7, 28 y 29
Medelln Colombia
2013
VII Simposio Internacional sobre
TABLE V
SIMULATION RESULTS COMPARISON FOR IEEE-13 SYSTEM 6,9
PL 25%
VOLTAGE [p.u] VOLTAGE [p.u] 6,8 PL 50%
IEEE-13 REPORT IEEE-13 FROM ATP PL 100%
NODE
Local Function
A B C A B C
6,7
Noviembre 2 7, 28 y 29
Medelln Colombia
2013
VII Simposio Internacional sobre
TABLE VII influence on voltage sag severity by decreasing the local
VOLTAGE COMPARISON AT 50% OF LINE 632-671 FOR CASE 2
function slightly as seen in Fig. 3.
Voltage [p.u] With respect to the location of DG unit, if the new
Phase A Phase B Phase C generator is installed at any three-phase bus of the test
Without DG 0.241 1.281 0.233 system the voltage profiles can be improved. However,
With DG 0.489 1.199 0.517 downstream-installed DG can improve voltage profile of
system and reduce the voltage sag severity better than
3) Case 3: voltage sag at bus 675 upstream-installed DG.
Average voltage sag of 0.378 p.u due to a three line fault
(type 10) at bus 675 with a fault resistance of 0.38 is VII. CONCLUSIONS
presented. Fig. 5 shows the influence of location and DG In this paper, the influence of a distributed generation unit
penetration level on the local function. The best location of on voltage sags features caused by faults in the IEEE-13 test
DG unit using a high penetration level is bus 680. With this system has been analyzed. Also, in order to evaluate the
configuration LF is reduced from 10.067 to 6.379. impacts of its installation, the location and size of the new
synchronous generator have been taken into account. Besides,
8,00 a method to identify the critical buses based on random
PL 25%
7,75 generation of disturbances, the system model and statistical
PL 50%
7,50
data of faults was applied.
PL 100%
Local Function
7,25 For the cases studies, it was observed that the presence of
7,00
DG unit has a positive effect on the system, contributes to
reduce the voltage sags impact and improves the voltage
6,75
profiles in all system. Simulation results show that DG unit
6,50 should be installed closed to bus affected by voltage sag. The
6,25 new DG unit at a downstream location of principal generator
6,00
shows better performance than an upstream location. In case
N633 N632 N671 N680 N675 studies 2 and 3, the inclusion of a 1.25 MVA DG unit
improves the performance of voltage profile connecting this
DG Location
generator at buses 675 and 680, respectively. In addition,
under one-single voltage sag conditions the impact of DG unit
Figure 5. Local function vs. DG location and dispersion level for case 3
size is not significantly different.
The RMS voltage at bus affected by sag condition with and
Developed features and graphic advantages available in
without the DG unit is presented in Table 8. Note that the ATP/EMTP were used to conduct all aspects of the DG
voltage sag depth at bus 675 decrease about 23% with respect implementation, the IEEE-13 system modeling and to carry
the reference value (pre-fault voltage) connecting DG unit. out several simulation results. This work is still under
TABLE VIII development, the next steps in research should consider the
VOLTAGE COMPARISON AT BUS 675 FOR CASE 3 influence of protection schemes to find more accurate results
Voltage [p.u]
and the optimal location to connect the DG unit.
Phase A Phase B Phase C
Without DG 0.362 0.429 0.344
REFERENCES
With DG 0.591 0.635 0.579 [1] M. Bollen, Integration of Distributed Generation in the Power System,
1st Edition. New Jersey, USA: Wiley-IEEE Press, 2011, p. 524.
[2] J. Martinez-Velasco and J. Martin-Arnedo, EMTP model for analysis
C. Results analysis of distributed generation impact on voltage sags, IET Gener. Transm.
Distrib., vol. 1, no. 1, pp. 112119, 2007.
Results from simulations show that local function and [3] S. Surisunthon and T. Tayjasanant, Impacts of distributed generations
voltage profile of IEEE-13 bus test feeder are improved when locations, sizes, operation modes and transformer connections on
voltage sag assessment, in 2011 IEEE Region 10 Conference -
DG is installed. Impacts of DG on voltage sag assessment TENCON 2011, 2011, pp. 893897.
depend on characteristics of DG as follows: [4] R. C. Dugan, M. F. McGranaghan, and H. W. Beaty, Electrical Power
Systems Quality, 3rd Edition. India: McGraw-Hill, 2012, p. 580.
An increase of DG size in the test system leads to a [5] M. Bollen, Understanding power quality problems. Voltage Sags and
reduction voltage sags severity in almost all buses of Interruptions, 1st Edition. New York: Wiley-IEEE Press, 2013, p. 672.
[6] L. Zheng, Y. Zhang, and L. Lin, Studies on Voltage Sag in
system. In those cases where the voltage sag is occurred
Distribution Network Containing Distributed Generations, in Power
at system bus, the best results can be obtained with a and Energy Engineering Conference (APPEEC), 2012 Asia-Pacific,
medium or high penetration level. However, in general 2012, pp. 15.
terms when multiple-phase are involved in voltage sag [7] IEEE Distribution System Subcomitte, IEEE 13 Node Test Feeder
Report, 2001.
condition the size of DG decrease the local function and [8] J. Martinez and J. Martin-Arnedo, Voltage sag studies in distribution
voltage sag severity. By other hand, if the voltage Networks-part I: system modeling, IEEE Trans. Power Deliv., vol. 21,
condition involves a single-phase, the size of DG has no. 3, pp. 16701678, Jul. 2006.
Noviembre 2 7, 28 y 29
Medelln Colombia