2.5 CONSTANT-IMPEDANCE REPRESENTATION OF LOADS Usually, the power system loads are represented by their real and reactive powers, as shown in Figure 2.5(a). However, ible to represent the same load in terms of series or parallel combinations of its equivalent constant-load resistance and reactance values, as shown in Figures 2.5(b) and 2.5(c), respectively [4]. In the event that the load is represented by the series connection, the equivalent constant impedance can be expressed as R,+iX, 0 (2.91) where Mier Pag (2.92) Rp ie P+iQ Xp @ ro) @ Figure 2.5. Load representations as: (a) real and reactive powers; (b) constant impedance in terms of series combination; (c) constant impedance in terms of parallel combination. CONSTANT-MPEDANCE REPRESENTATION OF LOADS 49. lvl: (2.93) P+Q where R, = load resistance in series connection in ohms X,=load reactance in series connection in ohms Z, = constant-load impedance in ohms V = load voltage in volts P= real, or average, load power in watts Q = reactive load power in vars The constant impedance in per units can be expressed as Zoucey = Roacey + IX pao) PU (2.94) where Saou)? Ryuwy = Ponsa) Beg? PU (2.95) Sol¥ou)? oun (Qonanics) Beg GE PU (2.96) In the event that the load is represented by the parallel connection, the equivalent constant impedance can be expressed as 97 where where R, ~load resistance in parallel connection in ohms = load reactance in parallel connection in ohms 7), = constant-load impedance in ohms ‘The constant impedance in per units can be expressed as Rosen X puter“ Xoutpy Zou ra 2.98) eet Roucay * Xpuco) where Sa (VV Ren = 8 x) pu (2.99) or vi m0 Roupy= Bo PU (2.100) pe and Kun (EY pw @.101) or Vou Xucey = os fy (2.102) 2.6 THREE-WINDING TRANSFORMERS Figure 2.6(a) shows a single-phase three-winding transformer. They are usually used in the bulk power (transmission) substations to reduce the transmission voltage to the subtransmission voltage level. If excitation impedance is neglected, the equivalent circuit of a three-winding transfor- mer can be represented by a wye of impedances, as shown in Figure 2.6(b), where the primary, secondary, and tertiary windings are denoted by P, S, and T, respectively. Note that the common point 0 is fictitious and is not related to the neutral of the system. The tertiary windings of a three-phase and three-winding transformer bank is usually connected in delta and may be used for (1) providing a path for zero-sequence currents, (2) in-plant power distribution, and (3) application of power-factor-correcting capacitors or reactors. The impedance of any of the branches shown in Figure 2.6(b) can be determined by considering the short-circuit impedance between pairs of windings with the third open. Therefore, 22. Ze (2.103a) Ze 2 oe (2.103b) Zpr= Zp+Zy (2.103c) Zp= MZ ps + Zpy — Zs) (2.104a) Zs= MZps + Zrs~ Zpr) (2.1046) p= Zor + Zrs~ Zs) (2.1046) THREE-WINDING TRANSFORMERS 51 Yy N, Pamary @ Vs 0 Figure 2.6. A single-phase three-winding transformer: (a) winding diagram; (6) equivalent circuit where Z,,= leakage impedance measured in primary with secondary short- circuited and tertiary open Zp; = leakage impedance measured in primary with tertiary short- circuited and secondary open Zr = leakage impedance measured in secondary with tertiary short- circuited and primary open Z, = impedance of primary winding impedance of secondary winding impedance of tertiary winding 52 _ STEADY-STATE PERFORMANCE OF TRANSMISSION LINES In most large transformers the value of Z, is very small and can be negative Contrary to the situation with a two-winding transformer, the kilovoltam- pere ratings of the three windings of a three-winding transformer bank are not usually equal. Therefore, all impedances, as defined above, should be expressed on the same kilovoltampere base. For three-winding three-phase transformer banks with delta- or wye-connected windings, the positive- and negative-sequence diagrams are always the same. The corresponding zero- sequence diagrams are shown in Figure 3.10. 2.7 AUTOTRANSFORMERS Figure 2.7(a) shows a two-winding transformer. Viewed from the terminals, the same transformation of voltages, currents, and impedances can be obtained with the connection shown in Figure 2.7(b). Therefore, in the autotransformer, only one winding is used per phase, the secondary voltage being tapped off the primary winding, as shown in Figure 2.7(b). The common winding is the winding between the low-voltage terminals, whereas the remainder of the winding, belonging exclusively to the high-voltage Circuit, is called the series winding and, combined with the common winding, forms the series-common winding between the high-voltage terminals. In a sense, an autotransformer is just a normal two-winding transformer connec- ted in a special way. The only structural difference is that the series winding must have extra insulation. In a variable autotransformer the tap is movable. Autotransformers are increasingly used to interconnect two high-voltage transmission lines operating at different voltages. An autotransformer has two separate sets of ratios, namely, circuit ratios and winding ratios. For 4 Series winding a bh Common winding @ o Figure 2.7. Schematic diagram of ideal (stepdown) transformer connected as: (a) two-winding transformer; (6) autotransformer. AUTOTRANSFORMERS 53 circuit ratios, consider the equivalent circuit of an ideal autotransformer (neglecting losses) shown in Figure 2.7(b). Viewed from the terminals, the voltage and current ratios can be expressed as (2.105a) (2.105) (2.105¢) and a= : (2.106) From equation (2.105c), it can be observed that the ratio a is always larger than 1 For winding ratios, consider the voltages and currents of the series and common windings, as shown in Figure 2.7(b). Therefore, the voltage and current ratios can be expressed as (2.107) and fe 2.108: : (2.108a) (2.108b) From equation (2.105¢), (2.109) Therefore, substituting equation (2.109) into equation (2.107) yields =a-1 (2.110) Similarly, substituting equations (2.106) and (2.109) into equation (2.108) simultaneously yields pret (2am) 54 STEADY-STATE PERFORMANCE OF TRANSMISSION LINES For an ideal autotransformer, the voltampere ratings of circuits and wind- ings can be expressed, respectively, as (2.112) and s. = ‘windings = (2.113) ‘The advantages of autotransformers are lower leakage reactances, lower losses, smaller exciting currents, and less cost than two-winding transformers when the voltage ratio does not vary too greatly from 1 to 1. For example, if the same core and coils are used as a two-winding transformer and as an autotransformer, the ratio of the capacity as an autotransformer to the capacity as a two-winding transformer can be expressed as ___ Capacity as autotransformer _ Vid, VL, Capacity as two-winding transformer VI, (V, — V,)h, (2.114) a-1 Therefore, maximum advantage is obtained with relatively small difference between the voltages on the two sides (e.g., 161 kV/138 kV, 500 kV/700 kV, and 500 kV/345 kV). Therefore, a large saving in size, weight, the cost can be achieved over a two-windings per-phase transformer, The disadvantages of an autotransformer are that there is no electrical isolation between the primary and secondary circuits and there is a greater short-circuit current than the one for the two-winding transformer. Three-phase autotransformer banks generally have wye-connected main windings, the neutral of which is normally connected solidly to the earth. In addition, it is common practice to include a third winding connected in delta, called the tertiary winding. 2.8 DELTA-WYE AND WYE-DELTA TRANSFORMATIONS The three-terminal circuits encountered so often in networks are the delta and wye’ configurations, as shown in Figure 2.8. In some problems it is hecessary to convert delta to wye or vice versa If the impedances Z,,,, Z,,, and Z., are connected in delta, the equivalent wye impedances Z,, Z,, and Z, are “In Europe it is called the star configuration DELTA-WYE AND WYE-DELTA TRANSFORMATIONS 55 a Zeb 6 Figure 2.8. Delta-to-wye or wye-to-delta transformations. = Devbea ~ Lat Let Lea oe = Lup Lire Z,= Toeteeie (2.116) ee Ly Lice Be rene rae (2.117) Of course, if Z,, (2.118) On the other hand, if the impedances Z,, Z,, and Z, are connected in wye, the equivalent delta impedances Z,,, Z,., and Z,, are Dgy =Z, +2, + Be (2.119) Z, Zy.= Dy +L, + (2.120) Deg =D, +0, + oe (2.121) 56 STEADY-STATE PERFORMANCE OF TRANSMISSION LINES Of course, if Z, = Z, = Zz, ap = Dge = Dyg = BL (2.122) 2.9 FACTORS AFFECTING LINE DESIGN The function of the overhead three-phase electric power transmission line is to transmit bulk power to load centers and large industrial users beyond the primary distribution lines. A given transmission system comprises all land, conversion structures, and equipment at a primary source of supply, includ- ing lines, switching, and conversion stations, between a generating or receiving point, and a load center or wholesale point. It includes all lines and equipment whose main function is to increase, integrate, or tie together power supply sources. The decision to build a transmission system results from system planning studies to determine how best to meet the system requirements. At this stage, the following factors need to be considered and established: 4. Voltage level. 2. Conductor type and size. 3. Line regulation and voltage control. 4. Corona and losses. 5. Proper load-flow and system stability. 6. System protection. 7. Grounding. 8. Insulation coordination. 9. Mechanical design: (a) Sag and stress calculations. (b) Conductor composition (©) Conductor spacing (4) Insulator and conductor hardware selection. 10. Structural design: (a) Structure types. (b) Stress calculations. The basic configuration selection depends on many interrelated factors, including esthetic considerations, economics, performance criteria, company policies and practice, line profile, right-of-way restrictions, preferred materi als, and construction techniques. Figure 2.9 shows typical compact configu- rations. Figures 2.10~2.13 show typical structures used for EHV transmis- sion systems, Figure 2.14 shows a 345-KV line with a single circuit and wood H-frame, whereas Figure 2.15 shows a 345-kV kine with a double circuit and steel tower veces = | au farevs\ ove ; =| VI + : 1 | WR | eee eile Figure 2.10. Typical pole- and lattwe-type structures for M5-kV transmission sys- tems. (Used by permission. © 1979 Electric Power Research Institute.) 58 = Tame Figure 2.11. Typical wood H-frame-type structures for 345-KV system (From Ref. 14, Used by permission. © 1979 Electric Power Research Institute.) ao 59 1s Ea Figure 2.12. lypical 500-kY lattice. pole, guyed V- and Y-type structures (From Ref. 14. Used by permission. © 1979 Electric Power Research Institute.) 60 ovate Par Figure 2.13. Typical 735-8¢ by permission: © 1979 Elec Power Research Institute.) V ac designy and de structures (Fiom Ref 14 Used 61 2.10 CONDUCTOR SIZE Conductor sizes are based on the circular mil. A circular mil is the area of a circle that has a diameter of 1mil. A mil is equal to 1x 10~*in. The cross-sectional area of a wire in square inches equals its area in circular mils multiplied by 0.7854 x 10% For the smaller conductors, up to 211,600 circular mils, the size is usually given by a gage number according to the American Wire Gauge (AWG) standard, formerly known as the Brown and Sharpe Wire Gauge (B&S). Gage sizes decrease as the wire increases in size. The larger the gage size, the smaller the wire. These numbers start at 40, the smallest, which is assigned to a wire with a diameter of 3.145 mils. The largest size is number 0000, written as 4/0, and read as four odds. Above 4/0, the size is determined by cross-sectional area in circular mils. In summary, 1 linear mil = 0,001 inch = 0.0254 millimeter 1 circular mil = area of circle 1 lincar mil in diameter = ta square mils 4a x 10° = 0.7854 x 107° square inch One thousand circular mils is often used as a unit, for exampler, a size given as 250 kemil or MCM refers to 250,000 circular mils, or 250,000 emil. A given conductor may consist of a single strand or several strands. If a single strand, it is solid; if of more than one strand, it is stranded. A solid conductor is often called a wire, whereas a stranded conductor is called a cable. A general formula for the total number of strands in concentrically stranded cables is Number of strands = 3n? - 3n +1 (2.123) where 7 is the number of layers, including the single center strand. In general, distribution conductors larger than 2 AWG are stranded. Insulated conductors for underground distribution or aerial cable lines are classified as cables and usually are stranded. Table 2.3 gives standard conductor sizes. Conductors may be selected based on Kelvin’s law. According to Kelvin’s law,’ “the most economical area of conductor is that for which the annual cost of the energy wasted is equal to the interest on that portion of the capital expense which may be considered as proportional to the weight of the conductor” [5]. Therefore, 3CPR | pwa 1000" 100 Annual cost = (2.124) TABLE 2.3 Standard Conductor Sizes Number Solid Size (Cireular of or (AWG or kemil) mils) wires stranded 18 1,620 1 Solid 16 2,580 1 Solid “4 4,110 1 Solid 2 6,530 1 Solid 10 10,380 1 Solid 8 16.510 1 Solid 7 20.820 1 Solid 6 26,250 1 Solid 6 26,250 3 Stranded 5 33,100 3 Stranded 5 33,100 1 Solid 4 41,740 1 Solid 4 41,740 3 Stranded 3 630 3 Stranded 3 52.030 7 Standed 3 52.680 1 Solid 2 66,370 1 Solid 2 66,370 3 Stranded 2 66,370 7 Stranded i 83,690 3 Stranded 1 83,690 7 Stranded 0 (or 1/0) 105,500 7 Stranded 00 (or 2/0) 133,100 7 Stranded 000 (or 3/0) 167,800 1 Stranded 000 (or 3/0) 167,800 2 Stranded 0000 (or 4/0) 211,600 1 Stranded 0000 (or 4/0) 211,600 2 Stranded (0000 (or 4/0) 211,600 19 Stranded 250 250,000 12 Stranded 250 250,000 19 Stranded 300 300,000 12 Stranded 300 300,000 0 Stranded 350 350.000 12 Stranded 350 350.0001 » Stranded 400 400,000 v0 Stranded 450 430,000 19 Stranded 500 500,000 19 Stranded 500 500,000 37 Stranded 600 600,000 37 Stranded 700 700,000 37 Stranded 750 750,000 37 Stranded 800 800,000 37 Stranded 900 900,000 37 Stranded 1,000 1,000,000 37 Stranded 66 STEADY-STATE PERFORMANCE OF TRANSMISSION LINES cost of energy wasted in dollars per kilowatt-year™ current per wire R= resistance per mile per conductor cost per pound of conductor w= weight per mile of all conductors percent annual cost of money where C Here, the minimum cost is obtained when 3CPR _ pwa 1000 ~ 100 (2.125) However, in practice, Kelvin's law is seldom used. Instead, the /°R losses are calculated for the total time horizon. ‘The conductors used in the modern overhead power transmission lines are bare aluminum conductors, which are classified as follow: AAC: all-aluminum conductor. AAAC: all-aluminum-alloy conductor. ACSR: aluminum conductor steel reinforced ACAR: aluminum conductor alloy reinforced. 2.11 TRANSMISSION LINE CONSTANTS can be For the purpose of system analysis, a given transmission line represented by its resistance, inductance or inductive reactance, capacitance or capacitive reactance, and leakage resistance (which is usually negligible). 2.12 RESISTANCE The direct-current resistance of a conductor is pl R= Fo (2.126) where p = conductor resistivity conductor length conductor cross-sectional area A In practice, several different sets of units are used in the calculation of the resistance. For example, in the International System of Units (SI units), Jis in meters, A is in square meters, and p is in ohm-meters. Whereas in power systems in the United States, p is in ohm-circular-mils per foot, /is in feet, and A is in circular mils. The resistance of a conductor at any temperature may be determined by at ieee RT) +t, (2.127) where R, = conductor resistance at temperature f, . R, = conductor resistance at temperature t, 1,, (= conductor temperatures in degrees Celsius T)= constant varying with conductor material 234.5 for annealed copper = 241 for hard-drawn copper = 228 for hard-drawn aluminum ‘The phenomenon by which alternating current tends to flow in the outer layer of a conductor is called skin effect. Skin effect is a function of conductor size, frequency, and the relative resistance of the conductor material. Tables given in Appendix A provide the de and ac resistance values for various conductors. The resistances to be used in the positive- and negative- sequence networks are the ac resistances of the conductors. 2.13 INDUCTANCE AND INDUCTIVE REACTANCE 2.13.1 Single-Phase Overhead Lines Figure 2.16 shows a single-phase overhead line. Assume that a current flows out in conductor a and returns in conductor 6. These currents cause magnetic field lines that link between the conductors. A change in current causes a change in flux, which in turn results in an induced voltage in the circuit. In an ac citeuit, this induced voltage is called the LX drop. In going around the loop, if R is the resistance of each conductor, the total loss in voltage due to resistance is 2/R. Therefore, the voltage drop in the single-phase line due to loop impedance at 60 Hz is D, v= air + 0.2794 log, Fe) v (2.128) where VD = voltage drop due to line impedance in volts [=line length in miles R= resistance of each conductor in ohms per mile Equipotential lines Magnetic flux lines Figure 2.16. Magnetic field of single-phase line. D,, = equivalent or geometric mean distance (GMD) between con- ductor centers in inches D, = geometric mean radius (GMR) or self-GMD of one conductor in inches, 0.77887 for cylindrical conductor r= radius of cylindrical conductor in inches (see Figure 2.16) I= phase current in amperes Therefore, the inductance of the conductor is expressed as >, D, L=2x107 In? Him (2.129) or L=0.7411 log, 2. mH/mi (2.130) With the inductance known, the inductive reactance’ can be found as D, X, = 2afl = 2.02 x 10-F In" (2.131) or 3, Dn, X= 4.657 x 10-*f logo F (2.132) "Ieis also the same as the positive and negative-sequence of a line or, at 60 Hz, Dy ‘| X= 0.2794 log, BE O/mi (2.133) D : X, = 0.1213 In 5" Omi (2.134) By using the geometric mean radius of a conductor, D,, the calculation of inductance and inductive reactance can be done easily. Tables give the geometric mean radius of various conductors readily. 2.13.2 Three-Phase Overhead Lines In general, the spacings D,,, D,., and D,, between the conductors of three-phase transmission lines are not equal. For any given conductor configuration, the average values of inductance and capacitance can be found by representing the system by one with equivalent equilateral spacing. The “equivalent spacing” is calculated as D, (Das X Dye X De)? (2.135) In practice, the conductors of a transmission line are transposed, as shown in Figure 2.17. The transposition operation, that is, exchanging the conductor positions, is usually carried out at switching stations. Therefore, the average inductance per phase is 1 Dec L,=2x10-"In i H/m (2.136) 1” De, £, = 0.7411 logo zs mH /mi (2.137) Position 1 Conductor a Conductor ¢ Conductor 6 — \ Position 2 Conductor b Conductor ¢ Lb Conductor a Position 3. Conductor ¢ — Conductor « Figure 2.17. Transposition cycle of three-phase line. and the inductive reactance is Dd, X= 0.1213 In" Omi (2.138) or De =0.2794 log, > Omi (2.139) 2.14 CAPACITANCE AND CAPACITIVE REACTANCE 2.14.1 Single-Phase Overhead Lines Figure 2.18 shows a single-phase line with two identical parallel conductors @ and b of radius r separated by a distance D, center to center, and with a potential difference of V,, volts. Let conductors a and b carry charges of +, and ~q, farads per meter, respectively. The capacitance between conductors can be found as (2.140) "Que Co 3 In(D/r) Fim (2.141) D Figure 2.18. Capacitance of single-phase line. Since eF ee where 1 =12 6° seq scqor 78:85 10° F/m and 1 for air equation (2.141) becomes 0.0388 © = Flog, (pi) HF (2.142) or eee os F/mi 2.143 ZinDin, BF/mi (2.143) or 0.0241 °°” Tog ¢bin KEIM (2.144) Stevenson [3] explains that the capacitance to neutral or capacitance to ground for the two-wire line is twice the line-to-line capacitance or cap: tance between conductors, as shown in Figures 2.19 and 2.20. Therefore, the line-to-neutral capacitance is 0.0388 oY jog, (Din) HE/mito neutral (2.145) This can easily be verified since Cy must equal 2C,, so that the total capacitance between the conductors can be «es 3 Figure 2.19. Line-to-line capacitance. 2 Con = 26a lw Con = 2Cob 7 Figure 2.20. Line-to-neutral capacitance. GiuGy Cyt Cy ic 2 as before (2.146) With the capacitance known, the capacitive reactance between one conductor and neutral can be found as 1 Xi (2.147) or, for 60 Hz, D X, = 0.06836 log; — M{/mi to neutral (2.148) and the line-to-neutral susceptance is or 1 bas (2.149) or 14.6272 ~ bgp MS/mi to neutral (2.150) The charging current of the line is 1, =joCyVip Alm (2.151) 2.14.2 Three-Phase Overhead Lines Figure 2.21 shows the cross section of a three-phase line with equilateral spacing D. The line-to-neutral capacitance can be found as’ 0.0388 © logy(Dir) BF/mi to neutral (2.152) which is identical to equation (2.145). On the other hand, if the spacings between the conductors of the three-phase line are not equal, the line-to-neutral capacitance is* 0.0388 = uF 33 «= Tog(D.gy ME /i to neutral (2.153) where aa = Dy = (Day X Dye X Dea) fz N - a a cw | | | cy i cy Figure 2.21. Three-phase line with equilateral spacing. * See Stevenson [3] and Anderson [4] for the derivations. ‘The charging current per phase is 1.=jWC,Vaq Ali (2.154) 2.15 TABLES OF LINE CONSTANTS Tables provide the line constants directly without using equations for calculation. This concept was suggested by W. A. Lewis [6]. According to this concept, equation (2.134) for inductive reactance at 60 Hz, that is, X, = 0.1213 In can be broken down to X, = 0.1213 in 4 +0.1213In D,, Q/mi (2.155) where D,=GMER, which can be found from the tables for a given con- ductor D,, = GMD between conductor centers Therefore, equation (2.155) can be rewritten as Xp =x, +44 Umi (2.156) where x, = inductive reactance at 1-ft spacing = 0.1213 In z Dimi (2.157) x, = inductive reactance spacing factor =0.1213In D,, Q/mi (2.158) For a given frequency, the value of x, depends only on the GMR, which is a function of the conductor type. Whereas x, depends only on the spacing D,, If the spacing is greater than 1 ft, x, has a positive value that is added to x, On the other hand, if the spacing is less than 1 ft, x, has a negative value that is subtracted from x,. Tables given in Appendix A give x, and x, directly Similarly, equation (2.148) for shunt capacitive reactance at 60 Hz, that is, x, = 0.06836 log jg 2 MQ/mi can be split into 0.06836 log, 4 + 0.06836 logy D MO/mi 2.159) 105 Bio or xi+ xy MOImi (2.160) where x! = capacitive reactance at 1-ft spacing = 0.06836 log, t MOImi (2.161) x1,= capacitive reactance spacing factor = 0.06836 log,, D- MQ/mi (2.162) Tables given in Appendix A provide x} and xj directly. The term X%, is added or subtracted from x; depending on the magnitude of D. 2.16 EQUIVALENT CIRCUITS FOR TRANSMISSION LINES An overhead line or a cable can be represented as a distributed constant circuit, as shown in Figure 2.22. The resistance, inductance, capacitance, and leakage conductance of a distributed constant circuit are distributed uniformly along the line length. In the figure, L represents the inductance of a line conductor to neutral per unit length, r represents the ac resistance of a line conductor per unit length, C is the capacitance of a line conductor to neutral per unit length, and G is the leakage conductance per unit length. Figure 2.22. Distributed constant equivalent circuit of line. 2.17 SHORT TRANSMISSION LINES (UP TO 50 mi, OR 80 km) In the case of a short transmission line, the capacitance and leakage resistance to the earth are usually neglected, as shown in Figure 2.23. ‘Therefore, the transmission line can be treated as a simple, lumped, and constant impedance, that is, ZL=R+jX, =al =r+jl 2 (2.163) where Z=total series impedance per phase in ohms z= series impedance of one conductor in ohms per unit length jotal inductive reactance of one conductor in ohms inductive reactance of one conductor in ohms per unit length length of line The current entering the line at the sending end of the line is equal to the current Ieaving at the receiving end. Figures 2.24 and 2.25 show vector (or phasor) diagrams for a short transmission line connected to an inductive load and a capacitive load, respectively. It can be observed from the figures that (2.164) (2.165) (2.166) Sending Receiving end end (source) (source) N w Figure 2.23. Equivalent circuit of short transmission SHORT TRANSMISSION LINES (UP TO 50mi, OR 80km) 77 Ws=ta=! Figure 2.24. Phasor diagram of short transmission line to inductive load. 1, = receiving-end phase current Z = total series impedance per phase Therefore, using V, as the reference, equation (2.164) can be written as V5 =Ve + Up 008 Pg + fly sin ®,)(R + JX) (2.167) where the plus or minus sign is determined by ®g, the power factor angle of the receiving end or load. If the power factor is lagging, the minus sign is employed. On the other hand, if it is leading, the plus sign is used. However, if equation (2.166) is used, it is convenient to use Vs as the reference. Therefore, Vp =Vs— (Is 608 ®, * jls sin )(R + jX) (2.168) where ©, is the sending-end power factor angle, that determines, as before, whether the plus or minus sign will be used. Also, from Figure 2.24, using Vg as the reference vector, VV_ + IR cos &y + IX sin By)’ + (IX cos &y + IR in Dy) (2.169) Ve Figure 2.25. Phasor diagram of short transmission line connected to capacitive load. and load angle b=, 0, (2.170) or IRsin®, V, + IR eos b, + IX sin b, 6 =tan (2.171) The generalized constants, or ABCD parameters, can be determined by inspection of Figure 2.23. Since Cel-[é oll] (2.172) and AD-~ BC = 1, where A=1 B=Z C=0 (2.173) then (el-[ the] @.174y and ae eG gw Tee Oe IJoto 1 dha, The transmission efficiency of the short line can be expressed as output input _ V3V ql 608 Pye V3V61 cos ®; _ Vx605 Py * vcuor (2.175) Equation (2.175) is applicable whether the line is single phase or three phase. The transmission efficiency can also be expressed as output output + losses For a single-phase line, Vel £08 Og eo ae 2.176 1 V.tcosb, +2PR (2.176) For a three-phase line, VY, V3V,1 cos Py eam 1” VAV,1 cos, +3PR 2.17.1 Steady-State Power Limit Assume that the impedance of a short transmission line i ‘Therefore, the real power delivered, at steady state, to the receiving end of the transmission line can be expressed as Vea asec — 3) — VA cos n= AZ * cos(e- 8) ~ FE cos 0 (2.178) and similarly, the reactive power delivered can be expressed as 2 * Va nga - 5)— UB sino 2.179) On = ZF sin(0 ~ 8) ~ FE sin (2.179) If V, and Vg are the line-to-neutral voltages, equations (2.178) and (2.179) give P, and Q values per phase. On the other hand, if the obtained Pg and Qp values are multiplied by 3 or the line-to-line values of Vs and Vi are employed, the equations give the three-phase real and reactive power delivered to a balanced load at the receiving end of the line. If, in equation (2.178), all variables are kept constant with the exception of 8, so that the real power delivered, Pg, is a function of 5 only, Py is maximum when 6 = @, and the maximum power’ obtainable at the receiving end for a given regulation can be expressed as Vi (V, Pa. a (GZ) (2.180) where V; and V, are the phase (line-to-neutral) voltages whether the system is single phase or three phase. The equation can also be expressed as Vex V, Pen = 5 eX cos 0 (2.181) * Also called the steady-state power limit. If Vs=Ve, Vie FZ (1 cos 8) (2.182) Praesmax or Pe (Ye) (Z-R) (2.183) and similarly, the corresponding reactive power delivered to the load is given by (2.184) As can be observed, both equations (2.183) and (2.184) are independent of V, voltage. The negative sign in equation (2.184) points out that the load is a sink of leading vars,’ that is, going to the load or a source of lagging vars (i.c., from the load to the supply). The total three-phase power transmitted on the three-phase line is three times the power calculated by using the above equations. If the voltages are given in volts, the power is expressed in watts or vars, Otherwise, if they are given in kilovolts, the power is expressed in megawatts or megavars. Ina similar manner, the real and reactive powers for the sending end of a transmission line can be expressed as Vy = cos(@ + 8) (2.185) and sin(@ + 5) (2.186) x Z If, in equation (2.185), as before, all variables are kept constant with the exception of 6, so that the real power at the sending end, Ps, is a function of 6 only, P, is a maximum when 0+ 5 = 180° ‘For many decades, the electrical utility industry has declined to recognize two different kinds of reactive power, leading and lagging vars. Only magneiizing vars ate recognized, printed on varmeter scals plates, bought, and sold. Therefore, in the following sections, the leading ot lagging vars will be referred to as magnetizing vars ‘Therefore, the maximum power at the sending end, the maximum input power, can be expressed as Psmax = YS con + Ys ate (2.187) or (2.188) However, if Vs = Ves Poa = (8) Z*R) (2.189) and similarly, the corresponding reactive power at the sending end, the maximum input vars, is given by v2 Qs= 7 sin 0 (2.190) ‘As can be observed, both equations (2.189) and (2.190) are independent of V, voltage, and equation (2.190) has a positive sign this time. 2.17.2 Percent Voltage Regulation The voltage regulation of the line is defined by the rise in voltage when full load is removed, that is, IVs1—1¥, Percentage of voltage regulation = Mle x 100 (2.191) A or [Vel = IVa.ec! Percentage of voltage regulation’ = x 100 Weer (2.192) where —_ [V,| = magnitude of sending-end phase (line-to-neutral) voltage at no load [Val = magnitude of receiving-end phase (line-to-neutral) voltage at full load ' For further information see Stevenson [3, p. 97] |Ve.nu = magnitude of receiving-end voltage at no load [Vir] = magnitude of receiving-end voltage at full load with con- stant |Vs1 ‘Therefore, if the load is connected at the receiving end of the line, IWsl= [Veal and Wel =[Veeu) An approximate expression for percentage of voltage regulation is (Reos,* Xsin®y) Percentage of voltage regulation = I, : ‘a 00 (2.193) EXxamPLe 2.5 A three-phase, 60-Hz overhead short transmission line has a line-to-line voltage of 23 kV at the receiving end, a total impedance of 2.48 + j6.570/ phase, and a load of 9MW with a receiving-end lagging power factor of 0.85. (a) Calculate line-to-neutral and line-to-line voltages at sending end, (b) Calculate load angle, Solution Method I: Using complex algebra: (a) The line-to-neutral reference voltage is Va LL) Vea = 23x 10° /0° _ : = caayiace = 13,294.8 /OV ‘The line current is _ 9x 10° V3 x23 x 10° X 0.85 = 266.1(0.85 ~ 0.527) = 226.19 — j140.24.A x (0.85 — j0.527) Therefore, IZ = (226.19 — j140.24)(2.48 + j6.57) = 266.1 /—31.8° x 7.02 /69.32° = 1868.95 /37.52° V ‘Thus, the line-to-neutral voltage at the sending end is Vecu-ny = Veen) +12 = 14,820 /4.4° V ‘The line-to-line voltage at the sending end is V, 1) = V3VeLxy = 25,640 V (b) The load angle is 4.4°, Method II. Using 1 as the reference: (a) Vp Cos p+ IR = 13,294.8 x 0.85 + 266.1 x 2.48 Vp Sin Dy + IX = 13,294.8 X 0.527 + 266.1 x 6.5: Then Veue-ny = (11,960.57 + 8754.67)" = 14,820 V/phase Vseu-ay * 25,640 V 7: (b) 0, = 0,4 3=tant WE 2 36.2" 6=0, ~ ©, =36.2-31.8=4.4° Method III. Using V, as the reference: (a) Vecu.ny =[(Vp + IR cos By + 1X sin ®y)” + (IX cos ®, — IR sin ®,)'] IR cos ®, = 266.1 x 2.48 X 0.85 = 560.9 IR sin ®y = 266.1 X 2.48 x 0.527 = 347.8 IX cos ®, = 266.1 x 6.57 x 0.85 = 1486.0 IX sin p= 266.1 x 6,57 X 0.527 = 921.0 12 Therefore, Veu-ny = [(13,294.8 + 560.9 + 921.0)? + (1486.0 — 347.8)°]"? = [14,776.7" + 1138.27]? 14,820 V Vous = VV) 25,640 V (b) = tan” 1138-2 _ 44 4,776.7 Method IV. Using power relationships: Power loss in the line is Ae Tg = 3 x 266.1? x 2.48 x 1076 = 0.527 MW Total input power to the line is i Pr= Pt Prog \ =9+0.527 = 9.527 MW Var loss in the line is Qian * 3X =3 x 266.1? x 6.57 x 10° = 1.396 Mvar lagging Total megavar input to the line is Psin®, Or= Sea," * ow 9x 0.527 = hae +1396 = 6.976 Mvar lageing Total megavoltampere input to the line is Sp=VP7+ QO; = V9.527" + 6.976" = 11.81 MVA Sr @) Vou = ay _ 1.81 x 10° V3 x 266.1 vz = 25,640 V set 14,820 V P, b) cos, = (0) cos®s = 5! 0.807 lagging Therefore, , = 36.2" 5= 36.2° — 31.8" = 4.4° Method V. Treating the three-phase line as a single-phase line and having V, and Vp represent line-to-line voltages, not line-to-neutral voltages: (a) Power delivered is 4.5 MW pau 10° tine “23 x 10° x 0.85, R gop = 2X 2-48 = 4.96.2 Xjoop = 2 * 6.57 = 13.14 0 = 230.18 A Vp cos By = 23 x 10° x 0.85 = 19,550 V Vp Sin &y = 23 x 10° x 0.527 = 12,121 V IR = 230.18 x 4,96 = 1141.7 IX = 230.18 x 13.14 = 3024.6 V Therefore, Veet = [(Vq C08 Py + IR)? + (Vp sin Dy + ixyy'? = [(19,550 + 1141.7)? + (12,121 + 3024.6)°]""7 = [20,691.77 + 15,145.67]! =25,640V 8 = 36:2°- 31.8°=4.4° 2.17.3 Representation of Mutual Impedance of Short Lines Figure 2.26(a) shows a circuit of two lines, x and y, that have self- impedances of Z,, and Z,, and mutual impedance of Z,,. Its equivalent circuit is shown in Figure 2.26(). Sometimes, it may be required to preserve the electrical identity of the two lines, as shown in Figure 2.27. The mutual impedance Z,, can be in either line and transferred to the other by means of a transformer that has a 1:1 turns ratio. This technique is also applicable for three-phase lines. EXampLe 2.7 Assume that the mutual impedance between two parallel feeders is 0.09 + j0.3Q/mi per phase, The self-impedances of the feeders are 0.604 /50.4° and 0.567 /52.9° 0/mi per phase, respectively. Represent the mutual impe- dance between the feeders as shown in Figure 2.26(b). © © la - by a by a) Figure 2.26, Representation of mutual impedance between two circuits © © by ~ bey Figure 2.27. Representation of mutual impedance between two circuits by means of 1:1 transformer. Solution Z,, = 0.09 + 0.3.0 Z...= 0.604 /50.4° = 3.85 + j0.465.0 Z,, = 0.567 /52.9° = 0.342 + j0.452.0 Therefore, Zigy ~ Ley = 0.295 + 0.1650 Z,, ~ Zu, = 0.252 + j0.152.0 Hence, the resulting equivalent circuit is shown in Figure 2.28. 0.295 + j0.165 2 © 0.09 + 0.30 @ 0.252 + 40.152 0 Figure 2.28

Das könnte Ihnen auch gefallen