Nominal Part Cv Shipping P
Description
Size Number
Friction Loss*
Factor Weight
Q= Cv
S
Flange/Flange
Flange Drilling Model H-2 Q= Flow
ANSI 3" 08366Q/B 22 ft (6.7 m) 200 73 lbs (33 kg) Cv = Flow Factor (GPM/1 PSI P)
ANSI 4" 08367Q/B 16 ft (4.9 m) 471 123 lbs (56 kg) P = Pressure Loss through Valve
ANSI 6" 08368Q/B 31 ft (9.4 m) 987 251 lbs (114 kg)
S= Specific Gravity of Fluid
PN10/16 DN80 08873Q/B 22 ft (6.7 m) 200 74 lbs (34 kg)
PN10/16 DN100 08874Q/B 16 ft (4.9 m) 471 120 lbs (54 kg)
PN10/16 DN150 08875Q/B 31 ft (9.4 m) 987 250 lbs (113 kg)
Flange/Groove
HALAR
Flange Drilling / Pipe O.D. Model H-2
ANSI / 89 mm 3" 11207Q/B 22 ft (6.7 m) 200 65 lbs (30 kg)
ANSI / 114 mm 4" 11208Q/B 16 ft (4.9 m) 471 111 lbs (54 kg)
ANSI / 168 mm 6" 11209Q/B 31 ft (9.4 m) 987 236 lbs (107 kg)
PN10/16 / 168 mm DN150 11209Q/B 31 ft (9.4 m) 987 236 lbs (107 kg)
* Expressed in equivalent length of pipe based on Hazen & Williams Formula C = 120.
Form No. F_051700 16.06.23 Rev 16.1 Revised page replaces page 504a-k, dated June 24, 2011.
(Removed On-Off statement from FM Approval.)
2 of 12
4. INSTALLATION
Note: For INSTALLATION instructions for using the Halar Coated Flow Control Valve as a Foam Concen-
trate Control Valve, refer to the Viking website.
When Valve Trim is used, to maintain listings and approvals, trim must be installed according to Viking Model H Flow Control Valve
Conventional Trim Charts specifically labeled Maximum 250 PSI (17 bar) Water Working Pressure. Refer to Form No. F_101594
and F_101694. Order 250 PSI (17.2 bar) trim separately. Where difficulty in performance is experienced, make sure that the valve is
trimmed properly. Contact Viking or Vikings authorized representative before any field adjustments are made.
A. General Instruction
1. Viking Flow Control Valves must be installed in an area not subject to freezing temperatures or physical damage.
2. The valve must be trimmed according to current Viking Trim Charts and appropriate instructions for the system used. Trim
Charts are available on the Viking website, and are provided with trim packages. When the Halar Coated Flow Control Valve
is used on Flow Control or preaction systems where standard trim is required and allowed, the valve must be trimmed accord-
ing to Viking Model H Trim Charts for the system used. For additional trim connections, refer to technical data describing the
system being installed.
3. The priming line must be connected upstream of the system water supply main control valve or to a constant source of water
at a pressure equal to the system water supply.
4. After the Flow Control Valve is set, operation of the Flow Control Valve requires the release of priming water from the priming
chamber. This may be by automatic or manual operation of the release system. Viking Flow Control Valves are compatible
with hydraulic, pneumatic, and electric release systems.
a. Hydraulic Release Systems: See Figures 3-6 for the maximum allowable elevation of hydraulic release piping above
the Flow Control Valve. If the maximum height of hydraulic release piping exceeds the limit shown in Figures 3-6, use a
Pneumatic or Electric Release System.
CAUTION
When releasing devices capable of automatically resetting are used on the pneumatic release system of a Flow Control Valve,
Viking Model E Deluge Valve Conventional Trim, complete with PORV, is required.
Note: This arrangement will not allow the Flow Control Valve to automatically reset.
c. Electric Release: Solenoid Valves, Release Control Panels, and Electrical Detectors must be compatible. Consult appro-
priate listings and/or approval guides.
5. The Viking Flow Control Valve can be trimmed to automatically reset electrically or manually. For specific Trim arrangements
refer to System Data describing the system being installed.
Note: DO NOT install any releasing device, or valve used to automatically reset the Flow Control Valve,
on pneumatic release piping.
For pneumatic release systems, any releasing valve or device used to automatically reset the Flow Control Valve must be installed in
the trim piping between the Pneumatic Actuator and the priming chamber outlet.
CAUTION
Operation of Viking Flow Control Valves by pressurizing the priming chamber with air or any other pressurized gas is not recom-
mended or approved.
6. When the Viking Halar Coated Flow Control Valve is used on systems supplied with brackish water, salt water, foam/water
(pre-mixed) solution, or any other corrosive water supply, consult Table 2 for trim material specifications. Check with manufac-
turer prior to using this valve with fluids other than fresh water and those listed in Table 2.
7. Fixed temperature hydraulic release systems must be used to operate Flow Control and preaction systems equipped with
Halar Coated Flow Control Valves supplied by sea water. Contact manufacturer for special trim considerations.
8. Use caution when using wrenches on or around Halar Coated Valves. Halar Coating may chip when struck with hard or
sharp objects. If the Halar coating becomes chipped, immediately repair the damaged area to inhibit the potential for corro-
sion. Refer to paragraph 6.C.I, Halar Coating Repair instructions.
9. Halar Coating is black in color. Due to its chemical resistance paint will not adhere to Halar Coating sufficiently to resist
abrasion.
B. Placing the Valve in Service (Refer to Figure 1.)
1. Verify:
a. The system Main Water Supply Control Valve (D.1) is closed and the Flow Control Valve is trimmed according to current
Viking Trim Charts and schematic drawings for the system used.
b. The system has been properly drained.
c. The Auxiliary Drain (B.6) is open.
d. The Emergency Release (B.10) is closed.
e. The system water supply piping is pressurized up to the closed Main Water Supply Control Valve (D.1) and the priming
line is pressurized up to closed Priming Valve (B.1).
2. For Systems equipped with:
a. Hydraulic Release System
i. Verify that all releasing devices are set and that any Inspectors Test Valve and/or auxiliary drain valves are closed.
ii. Open Priming Valve (B.1) Proceed to step 3.
b. Pneumatic Release Systems:
i. Set the release system.
ii. Opening Priming Valve (B.1). Proceed to step 3.
c. Electric Release Systems:
i. Open Priming Valve (B.1)
ii. Set the electric release system. Proceed to step 3.
3. Open Flow Test Valve (B.14).
4. Partially open Main Water Supply Control Valve (D.1).
5. When full flow develops from Flow Test Valve (B.14), close the Flow Test Valve. Verify that there is no flow from open Auxiliary
Drain (B.6).
6. Close Auxiliary Drain (B.6).
7. Fully open and secure the Main Water Supply Control Valve (D.1).
8. Verify that the Alarm Shut-off Valve (B.9) is open and that all other valves are in their normal operating position.
9. Depress the plunger of Drip Check (B.7). No water should flow from the Drip Check when the plunger is pushed.
10. Check for, and repair all leaks.
11. On new installations, those systems that have been placed out of service or where new equipment has been installed, trip test
the system to verify that all equipment functions properly. Refer to paragraph 6.B: Annual tests.
CAUTION
Performing a trip test results in operation of the Flow Control Valve. Water will flow into the sprinkler piping. Take necessary
precautions to prevent damage.
CAUTION
Resetting or closing releasing devices or valves on pneumatic release piping will NOT automatically cause the Flow Control
Valve to reset. Do NOT install any releasing device or valve used to automatically reset the Flow Control Valve, on pneumatic
release piping.
CAUTION
Performing this test results in operation of the Flow Control Valve. Water will flow into the sprinkler piping and from any open
sprinklers and/or nozzles. Take necessary precautions to prevent damage.
1. Notify the Authority Having Jurisdiction and those in the area affected by the test.
2. Fully open the Flow Test Valve (B.14) to flush away any accumulation of foreign material.
3. Close the Flow Test Valve (B.14).
4. Trip the system by operating the release system. Allow a full flow to pass through the Flow Control Valve. Water flow alarms
should operate.
When test is complete:
5. For Flow Control Valves equipped with:
a. Hydraulic or Electric Release:
i. Re-set the Release System. Pressure in the priming chamber should gradually be restored. Flow through the Flow
Control Valve should stop. Proceed to step 6.
b. Pneumatic Release Systems:
i. Close the Main Water Supply Control Valve (D.1) and Priming Valve (B.1).
ii. Open Auxiliary Drain Valve (B.6).
iii. Open all system main drains and auxiliary drains. Allow the system to drain completely Proceed to step 6.
6. Perform SEMI-ANNUAL maintenance. Refer to paragraph 6.C.III.
7. Place the system in service. Refer to paragraph 4.B.
Note: Flow Control Valves supplied by brackish water, salt water, foam, foam/water solution, or any oth-
er corrosive water supply, should be flushed with good quality fresh water before being returned to
service.
8. Notify the Authority Having Jurisdiction that the test is complete. Record and/or provide notification of test results as required
by the Authority Having Jurisdiction.
Where difficulty in performance is experienced, the valve manufacturer or his authorized representative shall be contacted if any field
adjustment is to be made.
WARNING
Any system maintenance which involves placing a control valve or detection system out of service may eliminate the Fire Pro-
tection capabilities of that system. Prior to proceeding, notify all Authorities Having Jurisdiction. Consideration should be given
to employment of a Fire Patrol in the affected areas.
I. Halar Coating Repair - If the Halar coating becomes chipped, immediately repair the damaged area to inhibit the potential for
corrosion. Follow instructions below:
1. Wipe clean and prepare the area to be repaired.
2. Using a hand held torch, gently heat the Halar coating around the area needing repair to the melting point of the Halar.
3. Allow the heated Halar to flow together.
4. Allow the coating to cool.
II. After Each Operation:
1. Sprinkler systems that have been subjected to a fire must be returned to service as soon as possible. The entire system must
be inspected for damage, and repaired or replaced as necessary.
2. Flow Control Valves and trim that have been subjected to brackish water, salt water, foam, foam/water solution, or any other
corrosive water supply, should be flushed with good quality fresh water before being returned to service.
3. Perform SEMI-ANNUAL maintenance after every operation.
III. Semi-Annual Maintenance:
1. Remove the system from service. (See release system description and technical data for additional information.)
a. Close the Main Water Supply Control Valve (D.1) and Priming Valve (B.1).
b. Open the Auxiliary Drain Valve (B.6). Allow the outlet chamber of the Flow Control Valve to drain completely.
c. Release pressure in the priming chamber by opening the Emergency Release Valve (B.10).
2. Inspect all trim for signs of corrosion and/or blockage. Clean and/or replace as required.
3. Clean and/or replace all strainer screens.
4. Refer to Item 4.B, INSTALLATION: PLACING THE VALVE IN SERVICE.
IV. Every Fifth Year
1. Internal inspection of Flow Control Valves is recommended every five years unless inspections and tests indicate more fre-
quent internal inspections are required. Refer to DISASSEMBLY instructions provided below.
2. Internal inspection of strainers, and restricted orifices is recommended every five years unless inspections and tests indicate
more frequent internal inspections are required.
3. Record and provide notification of inspection results as required by the Authority Having Jurisdiction.
V. Valve Disassembly (Refer to Figures 1 and 6.)
1. Remove the valve from service (see the release system description and Technical Data for additional information). Close
the main control valve, open the main drain valve. Release the pressure in the priming chamber by opening the Emergency
Release Valve.
2. Disconnect and remove necessary trim from the cover.
3. Remove the cover (3):
a. Remove each of the cap screws (7) and break the seal of the cover.
i. For 3 and 4 valves, use a Socket Wrench with a 3/4 socket.
ii. For 6 valves, use a Socket Wrench with a 15/16 socket.
b. Lift the cover (3) off the valve body (1) and gently set it aside.
VI. Installing Replacement Parts and Valve Reassembly (Refer to Figure 6.)
1. To replace the entire clapper assembly, which is ordered pre-assembled:
a. Remove the old clapper assembly (2, 4, 5, 6, 7, 8, and 10) by placing a flat head screwdriver between the body (1) and
the diaphragm rubber and then lifting the clapper assembly from valve body (1).
b. Inspect the seat (9).
7. AVAILABILITY
The Viking Flow Control Valve and accessories are available through a network of Domestic, Canadian, and International Distributors.
8. GUARANTEES
For details of warranty, refer to Vikings current list price schedule or contact Viking directly.
Table 2 - Trim Piping Materials Chart Note 1 - Standard Trim sets available from Viking consist of galvanized nip-
ples and fittings. Includes ACCESSORY PACKAGE.
VALVE CONTROLLING: TRIM PIPING MATERIAL
Note 2 - After operation, the valve & trim should be flushed with good quality
Fresh Water Only Standard - See Note 1 fresh water before being returned to service.
Sea Water Only Note 3 - Copper trim sets are not available from Viking. They may be manu-
AFFF/Sea Water Premix Solution 316 Stainless Steel or 400 Monel.
factured by installer. Refer to Model H-2 Flow Control Valve Trim Charts can
ARC/Sea Water Premix Solution See Notes 2 and 4.
be found on the Viking website for required configuration of trim, sizes and
llengths of nipples and components required.
Black Steel, Copper, Stainless Steel or
AFFF/Fresh Water Premix Solution Note 4 - Monel trim sets are not available from Viking. They may be manu-
400 Monel. See Notes 3 and 4.
factured by installer. Refer to Model H-2 Flow Control Valve Trim Charts can
Black Steel, Copper, Stainless Steel or be found on the Viking website for required configuration of trim, sizes and
AFFF/Fresh Water Premix Solution
400 Monel. See Notes 3 and 4. lengths of nipples and components required.
AFFF Foam Concentrate in pipes Black Steel, Copper, Stainless Steel or Note 5 - DO NOT allow ARC Foam Concentrate to enter the priming cham-
2 (DN50) and larger 400 Monel. See Notes 3 and 4. ber of the Flow Control Valve. When using the Halar Coated Flow Control
Valve as a Foam Concentrate Control Valve, refer to the Viking website for
AFFF Foam Concentrate in pipes Copper 316, Stainless Steel, or 400 Monel. trim charts, technical data and special instructions.
smaller than 2 (DN50) See Note 4.
Maximum Allowable Pilot Heights for Select Equivalent Lengths of Hydraulic Release Piping
Model H-2 Flow Control Valves with 1/8 (3.2 mm) Restricted Orifice
Graph is based on 1/2 (15 mm) pilot sprinklers installed on 1/2 (15 mm) schedule 40 galvanized release system piping.
If the maximum height of hydraulic release piping exceeds the limits shown on the graph, use Pneumatic or Electric Release System.
Figure 3 - 3 Valve
Figure 4 - 4 Valve
Maximum Allowable Pilot Heights for Select Equivalent Lengths of Hydraulic Release Piping
Model H-2 Flow Control Valves with 1/8 (3.2 mm) Restricted Orifice
Graph is based on 1/2 (15 mm) pilot sprinklers installed on 1/2 (15 mm) schedule 40 galvanized release system piping.
If the maximum height of hydraulic release piping exceeds the limits shown on the graph, use Pneumatic or Electric Release System.
Figure 5 - 4 Valve
Size A B C D E F*
3 7 5 4-1/4 5-3/8 7-1/2 3/4
(DN80) (178) (127) (108) (137) (190.5) (19.05)
4 9 6-1/2 5-1/4 7 9 15/16
(DN100) (229) (165) (133) (178) (228.6) (23.81)
6 12 8 7 9-1/8 11 1
(DN150) (304) (203) (178) (232) (279.4) (25.4)
Dimensions shown in parentheses are millimeter.
*4 & 6 valves manufactured with sculptured flanges.
Dimensions indicate thickness of flange at bolt holes.
Form No. F_051700 16.06.23 Rev 16.1 Revised page replaces page 504a-k, dated June 24, 2011.
(Removed On-Off statement from FM Approval.)