Beruflich Dokumente
Kultur Dokumente
Chapter 2 Loads
The first step in designing an engineered Enclosed buildings can be designed by the
structure is to determine the loads that stiffness matrix method or the diaphragm
would be applied to the structure. The 1996 analysis method. The diaphragm analysis
Revision of the 1994 Standard Building method accounts for the diaphragm action
Code states in Section 1601.2.2: provided by the metal cladding on the
building. This method sometimes allows
Buildings and structural systems shall more economical post sizing, however, more
possess general structural integrity to detail is involved in making proper
reduce hazards associated with progressive connections to assure that the loads can be
collapse to levels consistent with good safely transferred through the cladding and
engineering practice. The structural system supporting structure. Additionally the
shall be able to sustain local damage or building must meet the following conditions:
failure with the overall structure
remaining stable. Compliance with the The maximum length to width ratio is 3
applicable provisions of ASCE 7 shall be (i.e., a 40 foot wide building can be no
considered as meeting the requirements of longer than 120 feet).
this section. (SBCCI, 1996)
The endwalls must be continuous from
ANSI/ASCE 7-95 Minimum Design Loads ground to eave and designed as a shear
for Buildings and Other Structures, wall to transfer the anticipated loads.
therefore, was used to determine loads in this Limited openings are allowable.
handbook. (ASCE, 1996)
The diaphragm design method is outlined by
Two types of buildings, partially open and ASAE Standard EP484 Diaphragm Design
enclosed, are commonly constructed as of Metal-Clad, Post-Frame Rectangular
composters and stacking sheds. An open Buildings. (ASAE, 1990)
building is defined by ASCE 7-95 as a
structure having all walls at least 80% open. For this handbook, the stiffness matrix
Due to the bin walls on most of the method was used to develop the member
sizing charts for the composters and stacking
sheds.
Dead Load + (Roof Live Load or Snow Figure 2.1 and Figure 2.2 on the following
Load) + Wind Load. page show free body diagrams of two typical
waste management buildings. These
Since it is not likely that a roof live load that diagrams demonstrate that the loads applied
is caused mainly from maintenance workers as a result of wind pressure are not always
and equipment will be applied while there is what one expects. The direction of wind
snow on the roof, the two loads would not loads on various structures is detailed in
be used in the same scenario. In South ASCE 7-95, Chapter 6.
Carolina, roof live load is greater than snow
load, so it would be used.
Figure 2.1 An example of a free body diagram showing the loads applied to a partially open composter.
Figure 2.2 An example of a free body diagram showing the loads applied to an enclosed stacking shed.
Figure 2.4 A partially open building used as a composter and a stacking shed.
Figure 2.5 Excerpt from FIG. 6-1. Basic Wind Speed ANSI/ASCE 7-95