Sie sind auf Seite 1von 203

REPUBLIC OF THE PHILIPPINES

TABLE OFFICE OF THE CITY/MUNICIPAL


ENGINEER/BUILDING OFFICIAL

OF
CONTENTS
DISTRICT/CITY/MUNICIPALITY

ARCHITECTURAL
LAND USE & ZONING
A-1 PERSPECTIVE VIEW, TABLE OF CONTENTS

A-2 FLOOR PLAN, ELEVATIONS, ROOF PLAN


SECTIONS, REFLECTED CEILING PLAN

A-3 SCHEDULE OF DOOR & WINDOWS, BAY


SECTION, DETAIL SECTION, LOUVER LINE & GRADE
BLOCK VENT., RAMP DETAIL

ARCHITECTURAL

1 PERSPECTIVE VIEW
A-1 SCALE: NTS

STRUCTURAL

S-1 FOUNDATION PLAN, ROOF FRAMING


PLAN FOOTING DETAIL, COLUMN DETAIL, STRUCTURAL
WF-1, RAMP DETAIL

S-2 ELEVATIONS TYPICAL CONNECTION


DETAIL

SANITARY

ELECTRICAL
E-1 ELECTRICAL LAYOUT PLAN, RISER
DIAGRAM, LOAD SCHEDULE, GEN. NOTES

ELECTRICAL

SANITARY

MECHANICAL

REPUBLIC OF THE PHILIPPINES PREPARED BY : CHECKED BY : RECOMMENDING APPROVAL : APPROVED BY : PROJECT TITLE : PROJECT NO: 0000009 OWNER : SHEET NO:

DESIGNED BY: NQM


EMEC
AMA
VDS II
ONE STOREY DEPARTMENT OF EDUCATION
ONE CLASSROOM ENCODED BY: Max C.
VDS DepED A -1
S
AN
D SCHO
OL
DEPARTMENT OF EDUCATION MAXIMO M. CALBANG NATHANIEL Q. MENDOZA LUIS G. PURISIMA JR. OLIVER R. HERNANDEZ 7x9m (MODIFIED) CHECKED BY: LGP
SHEET CONTENTS : FLOOR PLAN
S
IE

3
ENG
FAC IL IT

ELEVATIONS
PHYSICAL FACILITIES AND SCHOOLS ENGINEERING DIVISION
INEERING D

PDO - III ARCHITECT III HEAD, PLANNING AND DESIGN UNIT CHIEF, PFSED-OPS PERSPECTIVE VIEW TABLE OF CONTENTS
AL

SECTIONS
IC

IV

PFSED-DepED PFSED-DepED DepED


SI
I

YS

MERALCO AVENUE, PASIG CITY PFSED-DepED 01 01 2005


ON
LOCATION : DATE :
PH
De ED
p

DETAILS
NOTE:
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF PHYSICAL FACILITIES AND SCHOOLS ENGINEERING
DIVISION AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


C' B' A A B B B' CC' C
C B A GA.#26 CORR. G.I. ROOFING 1 1 1
SHEET (PAINT FINISH) 1
A-1 2
A-1 3
A-1
GA.#26 CORR. G.I. ROOFING
C B A 7000 1500
9000
APEX OF ROOF 1100 3500 3500
12x300mm FIBER CEMENT
SHEET (PAINT FINISH) 4500 4500
1500 7000 FASCIA BOARD (PAINT FINISH)
3500 3500 1100

2026
APEX OF ROOF
12x300mm FIBER CEMENT
300x300mm EXTERIOR CONC.
FASCIA BOARD (PAINT FINISH)

1100
TOP OF ROOF BEAM LOUVER BLOCKS

2026
VENT. (SEE DETAIL)
300x300mm EXTERIOR CONC. A
LOUVER BLOCKS TOP OF ROOF BEAM 12mm THK. FIBER CEMENT

2800
FASCIA BOARD (PAINT FIN.)
LIGHTING FIXTURE

3500
12mm THK. FIBER CEMENT 100mm THK. CHB WALL PLAIN 2 2 2
CLASSROOM

2800
FASCIA BOARD (PAINT FIN.) CEMENT PLASTER & PAINT FIN.
FIN. FLR. LINE

VAR.
12mm THK. FIBER
100mm THK. CHB WALL PLAIN
100mm THK. CHB WALL WITH

PLAIN CEMENT PLASTER (PAINT


FIN.)

FIN. GRD. LN. CEMENT FASCIA BOARD


CLASSROOM
CEMENT PLASTER & PAINT FIN. PAINT FINISH
FIN. FLR. LINE
LEFT ELEVATION B

VAR.

9600
100mm THK. CHB WALL WITH

PLAIN CEMENT PLASTER (PAINT


FIN.)
4
FIN. GRD. LN. 4.8mm THK. FIBER
A-2 SCALE: 1:100m
CEMENT EXTERIOR &
3 RIGHT ELEVATION INTERIOR CEILING

3500
2 2 2

A-2 SCALE: 1:100m BOARD ON METAL OR

3 2 1 SOLID WOOD CEILING


JOIST @600mm OC
9000 GA#26 G.I. PL. BW PAINT FINISH
400 4500 9400 4500 RIDGE ROLL
PAINT FIN. C A-1

1500
1 2 3 APEX OF ROOF

GA#26 G.I. PL. 9000 GA#26 G.I. CORR.


RIDGE ROLL

2026
400 4500 4500 400 SLOPE SHEET ROOFING
PAINT FIN.
PAINT FIN.
APEX OF ROOF
TOP OF
1 REFLECTED CEILING PLAN
GA#26 G.I. CORR. ROOF BEAM
100mm THK. A-2 SCALE: 1:100m
2026

SHEET ROOFING SLOPE


CHB WALL PLAIN
PAINT FIN.

2800
CEMENT PLASTER
TOP OF & PAINT FIN.
ROOF BEAM W W CLASSROOM
100mm THK. 1 1
FIN. FLR. LN.

150.
CHB WALL PLAIN
2800

CEMENT PLASTER FIN. GRD. LN.


& PAINT FIN.
D
5 REAR ELEVATION
CLASSROOM W
D
1 W

A-2
1 SCALE: 1:100m
FIN. FLR. LN. 2
150.

FIN. GRD. LN. GA#26 PLAIN GI RIDGE ROLL


C C C

2 FRONT ELEVATION C
A-1 B
A-1 A
A-1
PAINT FINISH

300x300mm EXT. CONCRETE


LOUVER BLOCKS
7000
A-2 SCALE: 1:100m
GA#26 CORR. GI ROOFING
1500 3500 3500 1100 1 1 1
APEX OF ROOF
SHEET PAINT FINISH
4.8mm THK. FIBER CEMENT CEILING BOARD
1
A-1 2
A-1 3
A-1
ON 50x50mm CEILING JOIST @600mm OC 9000
50
29 00 BOTHWAYS PAINT FINISH
54

2026
4500 4500
1 2 3 VENTILATION (SEE DETAIL)
RAFTER/PURLINS SEE DETAIL
TOP OF ROOF BEAM

9000 12x300mm FIBER CEMENT

1100
FASCIA BOARD PAINT FINISH
4500 4500
W 4.8mm THK. FIBER CEMENT CEILING
A

3000
BOARD ON 50x50mm CLG. JST.
D 1
@600mm OC BW PAINT FIN.
50-100mm RIVER STONE TRENCH
1 GA#26 CORR. G.I.
CLASSROOM 100mm THK CHB WALL w/PLAIN SHEET ROOFING PAINT
W

3500
W
1100

FIN. FLR. LN. CEMENT PLASTER PAINT FINISH FINISH


1 CLASSROOM
150
1 100mm THK. CONCRETE SLAB ON FILL

A
FIN. GRD. LN. 100mm THK. 50-100mm GRAVEL BED SLOPE
FROM SELECTED COMPACT
FILLING MATERIAL
GA#26 PLAIN G.I.
6 CROSS SECTION B

9600
SHEET RIDGE ROLL
3500

100mm THK. CHB WALL


SCALE : 1:100 m. PAINT FINISH
PLASTER & PAINT FINISH .

A-2
12mm THK. FIBER SLOPE

3500
CEMENT FASCIA BOARD
PAINT FINISH
7000

1 1 1
1 2 3
BLACKBOARD

B CLASSROOM
EL. 150mm
1
A-1 2
A-1 3
A-1
FIN.: PLAIN CEMENT FIN.
SEE STRUCTURAL 9000
DETAIL 400 4500 4500 400 C
3500

1500
7 4.8mm THK. FIBER CEMENT APEX OF ROOF
1
A-2 W W CEILING BOARD ON 50x50mm
2 2 CEILING JOIST @600mm OC BW
2026

PAINT FINISH
C CORRIDOR
VENT. SEE DETAIL
TOP OF BEAM
ROOF PLAN
1500

9
1200

EL. 125mm
RAMP UP
FIN.: PLAIN CEMENT FIN.
LIGHTING FIXRUE
150mm THK. CHB WALL A-2 SCALE: 1:100mm
2800
600

6 50-100mm RIVER STONE TRENCH w/PLAIN CEMENT PLASTER


1
A-2 & PAINT FIN.

W-1
FLOOR PLAN
W-1
150

1 100mm THK. CONCRETE FIN. FLOOR LINE


SCHED. OF FLOOR FIN.
SLAB
A-2 1:100m NGL
FL-1 PLAIN CEMENT 50-100mm GRAVEL
FLOOR FIN. BEDDING
7 LONGITUDINAL SECTION
PLAIN CEMENT FLR. FROM SELECTED FILLING
FL-2
FIN. W/ GROOVE (ROUGH) MATERIAL A-2 SCALE: 1:100m

REPUBLIC OF THE PHILIPPINES PREPARED BY : CHECKED BY : RECOMMENDING APPROVAL : APPROVED BY : PROJECT TITLE : PROJECT NO: 0000009 OWNER : SHEET NO:

DESIGNED BY: NQM


EMEC
AMA
VDS II
ONE STOREY DEPARTMENT OF EDUCATION
ONE CLASSROOM ENCODED BY: Max C.
VDS DepED A -2
S
AN
D SCHO
OL
DEPARTMENT OF EDUCATION MAXIMO M. CALBANG NATHANIEL Q. MENDOZA LUIS G. PURISIMA JR. OLIVER R. HERNANDEZ (Modified 7x9m) CHECKED BY: LGP
SHEET CONTENTS : FLOOR PLAN
S
IE

3
ENG
FAC IL IT

ELEVATIONS
FLOOR, REFLECTED CEILING, AND ROOF PLAN,
PHYSICAL FACILITIES AND SCHOOLS ENGINEERING DIVISION
INEERING D

PDO - III ARCHITECT III HEAD, PLANNING AND DESIGN UNIT CHIEF, PFSED-OPS
AL

SECTIONS
ELEVATIONS, SECTIONS
IC

IV

PFSED-DepED PFSED-DepED DepED


SI
I

YS

MERALCO AVENUE, PASIG CITY PFSED-DepED 01 01 2005


ON
LOCATION : DATE :
PH
De ED
p

DETAILS
NOTE:
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF PHYSICAL FACILITIES AND SCHOOLS ENGINEERING
DIVISION AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


2-16 BOLTS
6mm THK PLYWOOD w/6mm
GROOVE ON 50x50mm NAILERS

@600mm OC BW (PAINT FIN) GA#26 CORR. ROOFING SHEET


(PAINT FIN.)
SAG ROD (SEE DETAIL)

TECKSCREW
1000 4 EQ. PARTS= 2 EQUAL PARTS =
STL. PURLINS (SEE STRUCTURAL DET.)
2500 1250 10mm THICK PLATE
TECKSCREW
6mm GROOVE

300

300

300

275
300x150x10mm BASE
PLATE
25x25 mm WOOD VENT

(14-BLADES)

(14-BLADES)
PROVIDE INSECT SCREEN
4-16x300mm LONG VENTILLATION W/ WIRE

1230

1230
BENT ANCHOR BOLTS MESH

300
2400

2400

2400
12x300mm FIBER
2100

CEMENT FASCIA BOARD

300
FULLY WELD ON
RAFTER

875

875
ELEV 20x20x2mm ANGULAR
BAR FOR FASCIA BD.
FFL
5 EAVES DETAIL FRAME WELDED TO
RAFTERS AND PURLINS
575 575
SCALE: 1:20mts
D-1 W-1 W-2 A-3

HOLLOW CORE FLUSH TYPE HINGED DOOR


JALOUSIE WINDOW W/ CLEAR GLASS BLADES ON STD. ALUM. SAME AS W-1

ON 50x100mm WOOD JAMBS/FRAMES HOUSING & FIXED CLEAR GLASS TRANSOMS ON 50x100mm WD.

275
JAMBS/FRAMES

1 DOOR & WINDOW SCHEDULE


A-3 SCALE: 1:50m
25x25mm WOOD VENT
PLAN PROVIDE INSECT SCREEN

600

4 TYP. CLG. VENT. DETAILS 300

A A-3 SCALE: 1:10 mts.


GA#26 CORR. GI.
C GA#26 PLAIN
ROOF

GI. FLASHING 27

1100 123
1500 C-PURLIN SEE
STRUCTURAL DET.
5
LOUVER BLOCKS (CONCRETE)
A-3

600

150
23

4
GA 26 G.I. CORR. SHEET ROOFING
TOP OF ROOF BEAM
TOP OF ROOF BEAM PAINT FINISH

GA#26 CORR. G.I. SHT. LC 100x50x15x1.5mm STL


ROOF (PAINT FIN.)
400

CONC. C-PURLINS @750mm OC ON RAFTER SEE


BEAM 2-LC 150x65x20x2mm RAFTER STRUCTURAL DET.
6mm THK. ORD. PLYWOOD INSIDE
INT. CEILING w/6MM GROOVE ON
OUTSIDE
50x50mm CEILING JOIST @600mm
ELEVATION

300
OC BOTHWAYS
10mmSAG ROD
12x300mm FIBER CEMENT
RAFTER (SEE STRUCT'L DET.)
FASCIA BOARD ON 20x20x2mm

CEILING VENTILATION SEE


SECTION ANGLE BAR FRAME W/ VERT.
MEMBER @ 600mm OC
12x300mm FIBER CEMENT 6mm THK. ORDINARY PLYWOOD
FASCIA BOARD ON 25x25x6mm
DETAIL
CEILING w/6mm GROOVE ON
12x300mm FIBER CONCRETE FASCIA
BOARD ON 25x25x6mm L-BAR
6 LOUVER BLOCK DETAIL 400
THK L-BAR w/25x6mm THK 50x50mm CEILING JOIST @600mm
STIFF FLAT BAR @600mm OC OC BW (PAINT FINISH) W/25x6mm THK STIFFENER FLAT BAR @
EVERY 600mm OC
A-3 SCALE: 1:10 mts.

BW. PAINT FIN.


7 EAVES DETAIL
W-1

2800
2800

CEILING VENTILLATION (SEE A-3 SCALE : 1:20M


DETAIL)
100 mm THK. CHB WALL WITH

PLAIN CEMENT PLASTER (PAINT FIN.)

2216
D-1

CLASSROOM
EL. +175mm
PART OF 100
100
C
800

CLASSROOM
TYPICAL

PART OF CORRIDOR

6mm
6mm
CLASSROOM 6mm

1500

UP
1200
CORRIDOR

25
FIN. FLOOR LINE NON-SK
FL-2 ID PLAIN

RAMP
CEMENT
FLOOR
CEMEMN

VAR.
T FINISH
VAR.

150
FIN. GRADE LINE

LINE OF CORRIDOR
POLYETHYLENE SHEET DAMP POLYETHYLENE SHEET DAMP
PROOFING PROOFING 1800
100mm THK. REINF. CONC 100mm THK. REINF. CONC DETAIL SECTION
SLAB SLAB
1500 DETAIL PLAN SCALE 1:5 M
100mm THK 50-100mm 100mm THK 50-100mm SCALE 1:50 M
GRAVEL BED GRAVEL BED

FR. SELECTED FILLING


PLAN
FR. SELECTED FILLING
1 PLAN MATERIALS MATERIALS 2 8 RAMP DETAILS
A-3 SCALE: 1:100m
A-3 SCALE: 1:100m
A-3 SCALE: AS SHOWN

REPUBLIC OF THE PHILIPPINES PREPARED BY : CHECKED BY : RECOMMENDING APPROVAL : APPROVED BY : PROJECT TITLE : PROJECT NO: 0000009 OWNER : SHEET NO:

DESIGNED BY: NQM


EMEC
AMA
VDS II
ONE STOREY DEPARTMENT OF EDUCATION
ONE CLASSROOM ENCODED BY: Max C.
VDS DepED A -3
S
AN
D SCHO
OL
DEPARTMENT OF EDUCATION MAXIMO M. CALBANG NATHANIEL Q. MENDOZA LUIS G. PURISIMA JR. OLIVER R. HERNANDEZ (Modified 7x9m) CHECKED BY: LGP
SHEET CONTENTS : FLOOR PLAN
S
IE

3
DOOR AND WINDOW SCHEDULE, BAY SECTION,
ENG
FAC IL IT

ELEVATIONS
PHYSICAL FACILITIES AND SCHOOLS ENGINEERING DIVISION
INEERING D

PDO - III ARCHITECT III HEAD, PLANNING AND DESIGN UNIT CHIEF, PFSED-OPS VENT, EAVES AND RAMP DETAIL
AL

SECTIONS
IC

IV

PFSED-DepED PFSED-DepED DepED


SI
I

YS

MERALCO AVENUE, PASIG CITY PFSED-DepED 01 01 2005


ON
LOCATION : DATE :
PH
De ED
p

DETAILS
NOTE:
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF PHYSICAL FACILITIES AND SCHOOLS ENGINEERING
DIVISION AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


1 2 3
9000

4500 4500
1 2 3
9000

1100
4500 4500
RG-1 RG-1
F-1
C-1
F-2
C-2
F-1 A
C-1

A WF-1 WF-1
10mm SAG ROD

w/STANDARD NUTS &

3500

RG-2

RG-2
EB-1

EB-1
WASHERS @ END
3500

WF-1
WF-1

R - 1

R - 1
R - 2

R - 2
7000
F-1 F-1 B
C-1 C-1
7000

100mm THK. SLAB ON FILL ON


B 100mm THK. GRAVEL FILL
50x100x15x1.5mm
COMPACTED 95w/SELECTED

3500

RG-2

RG-2
STEEL PURLINS

EB-1

EB-1
FILLING MATERIALS
@750 O.C.
3500

WF-1
WF-1

RG-1 RG-1

F-1
C-1
F-2
C-2
F-1
C-1
C

1500
C
RAMP UP

WF-1 WF-1
1500

1200

1800
B ROOF FRAMING PLAN
A FOUNDATION PLAN S-1 SCALE: 1:100m

S-1 SCALE: 1:100m

100mm THK.
CHB

10@600
L
HOR. BARS

NGL NATURAL GRADE LINE


1

10@600
VERT. BARS 1800

600
D
Y-BARS 10 300mm TEMP
X-BARS BARS BOTHWAYS
W

150
t

250
Y-BARS

10mm

100
X-BARS

C O L U M N S C H E D U L E L 100 mm THICK
GRAVEL BEDDING
G-20mm GRAVEL 3-10mm
BEDDING 10mm @300 CUT BARS
PLAN SECTION 400

LEVEL C-1 C-2 C TYP. FOOTING DETAIL E DETAIL OF RAMP


D DETAIL OF WF-1
SCALE 1 : 50M
S-1 SCALE : NTS
S-1 SCALE : NTS. S-1
300 400

DESIGN CRITERIA :
200

200

S C H E D U L E O F F O O T I N G S
A. CONCRETE
FOUNDATION LEVEL
LEVEL

fc' = 20.685 Mpa ( 3,000 Psi ), minimum compressive strength of concrete


FOOTING
FOOTING DIMENSIONS (mm) REINFORCEMENT
a 28 days unless otherwise specified.
MAIN BAR: MAIN BAR: REMARKS
MARK LENGTH WIDTH DEPTH THICKNESS B. REBAR
4-%16mm 6-%16mm BAR X BAR Y
(L) (W) (D) (t)
fy = 275.8 Mpa ( 40,000 Psi ), minimum yield strength of reinforcing bars
ROOF

TIES : 10 mm TIES : 10 mm
1@50, 8@75, REST @ 1@50, 8@75, REST @ F-1 800 800 1200 250 4 - 16mm% 4 - 16mm% SQUARE FOOTING unless otherwise specified.
150mm TO CENTER 150mm TO CENTER C. STRUCTURAL STEEL

F-2 1000 1000 1200 250 4 - 16mm% 4 - 16mm% SQUARE FOOTING


Fy = 248 Mpa ( 36 Ksi ), specified minimum yield strength
TO

unless otherwise specified.


D. FOUNDATION

SBP = 95.706 Kpa ( 2,000 Psf ), was used in the design for all footings.
No footing shall rest on fill.

REPUBLIC OF THE PHILIPPINES PREPARED BY : CHECKED BY : RECOMMENDING APPROVAL : APPROVED BY : PROJECT TITLE : PROJECT NO: 0000009 OWNER : SHEET NO:

DESIGNED BY: NQM


EMEC
AMA
VDS II
ONE STOREY DEPARTMENT OF EDUCATION
ONE CLASSROOM ENCODED BY: Max C.
VDS DepED S -1
S
AN
D SCHO
OL
DEPARTMENT OF EDUCATION MAXIMO M. CALBANG ANTONIA M. ALHAMBRA LUIS G. PURISIMA JR. OLIVER R. HERNANDEZ 7x9m (MODIFIED) CHECKED BY: LGP
SHEET CONTENTS : FLOOR PLAN
S
IE

FOUNDATION PLAN, ROOF FRAMING PLAN


2
ENG
FAC IL IT

ELEVATIONS
PHYSICAL FACILITIES AND SCHOOLS ENGINEERING DIVISION
INEERING D

PDO - III
CIVIL ENGINEER/MASTER PLUMBER HEAD, PLANNING AND DESIGN UNIT CHIEF, PFSED-OPS
FOOTING DETAIL, COLUMN DETAIL, WF-1,
AL

SECTIONS
IC

IV

PFSED-DepED PFSED-DepED DepED


SI
I

YS

MERALCO AVENUE, PASIG CITY PFSED-DepED 01 01 2005


ON
LOCATION : DATE :
PH
De ED
p
RAMP DET.
DETAILS
NOTE:
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF PHYSICAL FACILITIES AND SCHOOLS ENGINEERING
DIVISION AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


4-%16x300mm LONG
BENT ANCHOR BOLTS
65 65

20

20
300x150x10mm
300 BASE PLATE
50 50
100mm THK.

37.5
CHB

150

150
50

37.5
10@600

15
HOR. BARS

1 2LC-150x65x20x3 LC-150x65x20x3
NATURAL GRADE LINE
LINE OF R-1/R-2

100
R-1 R-2
10@600 10mm THICK PLATE
PLAN
VERT. BARS 1800

E DETAIL OF RAfTER
600

10 300mm TEMP
BARS BOTHWAYS
SCALE NTS LC-100x50x15x1.5
S-2

150
F DETAIL OF PURLINS
250

10mm SCALE NTS


S-2
G-20mm GRAVEL 3-10mm
BEDDING 10mm @300 CUT BARS
400

D DETAIL OF WF-1 E DETAIL OF RAMP


2-%16
SCALE 1 : 50M
S-1 SCALE : NTS. S-1 BOLTS 100x50x15x1.5mm
2-%16 STEEL C-PURLINS
BOLTS 750mm O.C.

R-2
4-%16x300mm
L
LONG BENT R-1/R-2 10mm THICK PLATE
ANCHOR BOLTS 1-%10mm A-307

10mm X 150mm ANCHOR BOLT


NGL 4-%16x300mm LONG EB-1
ANCHOR BOLTS
300x150x10mm BENT ANCHOR BOLTS (SEE SCHED)
BASE PLATE
R- SPACED @ 800mm O.C. L-50x50x4.5

10mm THICK PLATE 1/


300x150x10mm R- 1:20 M
2
BASE PLATE

1 SECTION DETAIL
D

Y-BARS

X-BARS
W

SCALE NTS
S-2
t

Y-BARS

RC BEAM/COLUMN
100

X-BARS

PURLIN CONNECTION DET


100 mm THICK
G
L
GRAVEL BEDDING
ELEVATION
PLAN SECTION SCALE 1 : 5 M

ELEVATION
S-2
C TYP. FOOTING DETAIL
S-1 SCALE :
D TYPICAL RAFTER ANCHORAGE DETAIL
SCALE
S-2

L1 L2
NTS

2D LAP SPLICES ARE ALLOWED 2D 2D LAP SPLICES ARE ALLOWED 2D

ONLY IN THIS PORTION ONLY IN THIS PORTION

100x50x15x1.5mm
STEEL C-PURLINS
750mm O.C.

10mm% SAG ROD WITH


2-10mm SIDE BARS
STANDARD NUTS &
TOP OF RAFTER WASHERS @ EACH END

10mm TIE ROD WITH


STANDARD NUTS &
WASHERS @ EACH END
C TYPICAL BEAM ELEVATION CL.
50x100x15x1.5mm
S-2 STEEL C-PURLINS
150
150
750mm O.C. R-
1/
R-
2
10mm SAG ROD
B E A M S C H E D U L E

BEAM S T E E L R E I N F O R C E M E N T S
FLOOR BEAM DIMENSIONS S T I R R U P S
( in / mm ) LEFT MID SPAN RIGHT
LEVEL MARK REBAR 10mm

(mm ) (UNLESS NOTED OTHERWISE)


b h TOP BOTTOM TOP BOTTOM TOP BOTTOM

RG-1 150 400 12mm 2 2 2 2 2 2 1@50, 8@100, REST@200


LEVEL

RG-2 150 400 12mm 2 2 2 2 2 2 1@50, 6@100, REST@200 I SAG ROD CONNECTION DET.
H TIE ROD CONNECTION DET. SCALE 1 : 10 M
SCALE 1 : 10 M S-2
S-2
ROOF

EB-1 150 250 10mm 2 2 2 2 2 2 1@50, REST@200

REPUBLIC OF THE PHILIPPINES PREPARED BY : CHECKED BY : RECOMMENDING APPROVAL : APPROVED BY : PROJECT TITLE : PROJECT NO: 0000009 OWNER : SHEET NO:

DESIGNED BY: NQM


EMEC
AMA
VDS II
ONE STOREY DEPARTMENT OF EDUCATION
ONE CLASSROOM ENCODED BY: Max C.
VDS DepED S -2
S
AN
D SCHO
OL
DEPARTMENT OF EDUCATION MAXIMO M. CALBANG ANTONIA M. ALHAMBRA LUIS G. PURISIMA JR. OLIVER R. HERNANDEZ 7x9m (MODIFIED) CHECKED BY: LGP
SHEET CONTENTS : FLOOR PLAN
S
IE

2
ENG
FAC IL IT

ELEVATIONS
PHYSICAL FACILITIES AND SCHOOLS ENGINEERING DIVISION
INEERING D

PDO - III
CIVIL ENGINEER/MASTER PLUMBER HEAD, PLANNING AND DESIGN UNIT CHIEF, PFSED-OPS
ELEVATIONS, BEAM DETAIL & SCHED.
AL

SECTIONS
IC

IV

PFSED-DepED PFSED-DepED DepED


SI
I

YS

MERALCO AVENUE, PASIG CITY PFSED-DepED 01 01 2005 TYPICAL CONNECTION DETAIL


ON
LOCATION : DATE :
PH
De ED
p

DETAILS
NOTE:
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF PHYSICAL FACILITIES AND SCHOOLS ENGINEERING
DIVISION AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


GENERAL NOTES CALCULATIONS

1. ALL ELECTRICAL WORKS SHALL COMPLY IN ACCORDANCE WITH THIS PLAN


AND SPECIFICATIONS. THE APPLICABLE PROVISIONS OF THE LATEST EDITION 1. TOTAL LOAD:
5. SCHEMATIC DIAGRAM OF SAFETY SWITCH:
OF THE PHILIPPINE ELECTRICAL CODE (PEC). THE RULES AND REGULATION OF A. LIGHTING OUTLET 7 x 100 W = 700 W
THE LOCAL ENFORCING AUTHORITY AND THE REQUIREMENTS OF THE LOCAL
POWER COMPANY. ALL ELECTRICAL WORKS SHALL BE UNDER THE B. FAN OUTLET 1 x 100 W = 100 W
3.5mmTHW WIRE
IMMEDIATE SUPERVISION OF A DULY REGISTERED ELECTRICAL ENGINEER.
C. CONVENIENCE OUTLET 2 x 180 W = 360 W

2. THE ELECTRICAL SERVICE POWER IS 1-PHASE, 2-WIRE, 230 V AC, 60 Hz.


TOTAL LOAD = 1160 W
3. WIRING METHOD SHALL BE AS FOLLOWS :
a. FEEDERS AND RISERS - RIGID METALLIC CONDUIT
I LOAD 1160 / 230 = 5.04 A
b.LIGHTING, POWER RECEPTACLE - POLYVINYL CHLORIDE CONDUIT
BRANCH CKT., & AUXILIARY SCH. 40

4. ALL WIRES SHALL BE COPPER AND THERMOPLASTIC INSULATED TYPE "THW" UNLESS 2. CIRCUIT REQUIREMENT:
OTHERWISE INDICATED IN THE PLAN. THE MINIMUM SIZE OF WIRE FOR POWER AND LIGHTING
CIRCUIT HOMERUN SHALL BE 3.5mm AND INSULATED FOR 600 VOLTS. SMALLEST
USE 20 A 2-WIRE CIRCUIT 3.5mmTHW COPPER WIRE
RACEWAY SHALL BE 15mm TRADE/NOMINAL SIZE.

5. ALL OUTLET BOXES SHALL BE GALVANIZED GAUGE NO. 16 DEEP TYPE WITH
3. SERVICE ENTRANCE CONDUCTORS:
FACTORY KNOCKOUTS.

6. ALL MATERIALS TO BE USED SHALL BE BRAND NEW AND APPROVED TYPE FOR THE USE 2-3.5mm THW COPPER WIRES

PARTICULAR LOCATION AND PURPOSE.

7. GROUNDING SYSTEM SHALL BE PROVIDED TO ALL LIGHTING AND POWER CIRCUIT AS PER 4. SERVICE EQUIPMENT:
PHILIPPINE ELECTRICAL CODE REQUIREMENT.
USE 1-30 A, 2PST, 250V SAFETY SWITCH WITH 2-20 A, RENEWABLE FUSES
8. MOUNTING HEIGHT OF WIRING DEVICES SHALL BE AS FOLLOWS :

a. LIGHT SWITCH - 1.20 M ABOVE FINISH FLOOR

b. CONVENIENCE OUTLET - 0.30 M ABOVE FINISH FLOOR.

c. SAFETY SWITCH - 1.80 M ABOVE FINISH FLOOR

OVERHEAD SERVICE ENTRANCE


CONNECTED TO 220V AC, 1O,
2 WIRE, 60 Hz FITTED WITH
20mm O TYPE "F" CONDULET

1 2 3

LEGEND
A
SYMBOL DESCRIPTION
- CEILING LIGHT OUTLET CEILING LINE aa a ba
222 22
BUILDING WALL
2
- 2 x 40 WATTS FLUORESCENT LAMP a a

2 2
METERING CONDUIT

F - CEILING FAN OUTLET 2-3.5mm THW


2 CLASSROOM
KWHR METER IN 20mmORSC

- ONE GANG DEVICE SWITCH B


a
2 F 2
S/Sa 2

3500 mm
a
S ab - TWO GANG DEVICE SWITCH

S cde - THREE GANG DEVICE SWITCH aaa

222
b
2

1800 mm

1800 mm
1
- 1 x 40 WATTS FLUORESCENT LAMP a

Sf - FAN CONTROL SWITCH LP SabcSf


22

- RACEWAY CONDUIT CONCEALED IN CEILING GROUND FLOOR LINE


C
Sab M
Sabc
b
c

- RACEWAY CONDUIT CONCEALED UNDER FLOOR FIN. GRADE LINE

2 OVERHEAD SERVICE ENTRANCE

ELECTRICAL LAYOUT
1-3.5mm THW COPPER WIRE
REFER TO RISER DIAGRAM

1
IN 15mmO C

- SAFETY SWITCH 16MMO x 2400mm LENGTH


GROUNDING ROD COPPERWELD

E-1 SCALE: 1:100m

- DUPLEX CONVENIENCE OUTLET, GROUNDING TYPE


10 AMPS, 250 VOLT WITH MODERN PLATE COVER

M
- ELECTRIC SERVICE METER

- SERVICE ENTRANCE
ELECTRICAL RISER DIAGRAM
NOT TO SCALE

REPUBLIC OF THE PHILIPPINES PREPARED BY : CHECKED BY : RECOMMENDING APPROVAL : APPROVED BY : PROJECT TITLE : PROJECT NO: 0000009 OWNER : SHEET NO:

DESIGNED BY: NQM


EMEC
AMA
VDS II
ONE STOREY DEPARTMENT OF EDUCATION
ONE CLASSROOM ENCODED BY: Max C.
VDS DepED E -1
S
AN
D SCHO
OL
DEPARTMENT OF EDUCATION MAXIMO M. CALBANG VENERANDO D. SAHAGUN LUIS G. PURISIMA JR. OLIVER R. HERNANDEZ 7x9m (MODIFIED) CHECKED BY: LGP
SHEET CONTENTS : FLOOR PLAN
CALCULATIONS
S
IE

1
ENG
FAC IL IT

ELEVATIONS
PHYSICAL FACILITIES AND SCHOOLS ENGINEERING DIVISION
INEERING D

PDO - III ENGINEER III HEAD, PLANNING AND DESIGN UNIT CHIEF, PFSED-OPS GENERAL NOTES LEGEND
AL

SECTIONS
IC

IV

PFSED-DepED PFSED-DepED DepED


SI
I

YS

MERALCO AVENUE, PASIG CITY PFSED-DepED 01 01 2005 ELECTRICAL LAYOUT RISER DIAGRAM
ON
LOCATION : DATE :
PH
De ED
p

DETAILS
NOTE:
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF PHYSICAL FACILITIES AND SCHOOLS ENGINEERING
DIVISION AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


REPUBLIC OF THE PHILIPPINES

TABLE OFFICE OF THE CITY/MUNICIPAL


ENGINEER/BUILDING OFFICIAL

OF
CONTENTS
DISTRICT/CITY/MUNICIPALITY

ARCHITECTURAL
LAND USE & ZONING
A-1 PERSPECTIVE VIEW, TABLE OF CONTENTS

A-2 FLOOR PLAN, ELEVATIONS, ROOF PLAN


SECTIONS, REFLECTED CEILING PLAN, RAMP
DET.

A-3 SCHEDULE OF DOOR & WINDOWS, BAY


SECTION, DETAIL SECTION, DECO BLOCK LINE & GRADE
VENT., DAMP PROOFING DETAIL

ARCHITECTURAL

1 PERSPECTIVE VIEW STRUCTURAL


A-1 SCALE: NTS

S-1 FOUNDATION PLAN, ROOF FRAMING PLAN


FOOTING DETAIL, COLUMN DETAIL, WF-1
STRUCTURAL

S-2 ELEVATIONS TYPICAL CONNECTION DETAIL

SANITARY

ELECTRICAL
E-1 ELECTRICAL LAYOUT PLAN, RISER
DIAGRAM, LOAD SCHEDULE, GEN. NOTES

ELECTRICAL

SANITARY

MECHANICAL

REPUBLIC OF THE PHILIPPINES PREPARED BY : CHECKED BY : RECOMMENDING APPROVAL : APPROVED BY : PROJECT TITLE : PROJECT NO: 00200511 OWNER : SHEET NO:

ONE STOREY DESIGNED BY: NQM


EMEC
AMA
VDS II
DEPARTMENT OF EDUCATION
ONE CLASSROOM w/TOILET ENCODED BY: Max C.
VDS DepED A-1
1
AN
D SCHO
OL
DEPARTMENT OF EDUCATION MAXIMO M. CALBANG NATHANIEL Q. MENDOZA LUIS G. PURISIMA JR. OLIVER R. HERNANDEZ 7x9m (MODIFIED) SHEET CONTENTS : FLOOR PLAN

4
S
CHECKED BY: LGP
S
IE

4
ENG
FAC IL IT

ELEVATIONS
PHYSICAL FACILITIES AND SCHOOLS ENGINEERING DIVISION
INEERING D

PDO - III ARCHITECT III HEAD, PLANNING AND DESIGN UNIT CHIEF, PFSED-OPS PERSPECTIVE VIEW, TABLE OF CONTENTS
AL

SECTIONS
IC

IV

PFSED-DepED PFSED-DepED DepED


SI
I

YS

MERALCO AVENUE, PASIG CITY PFSED-DepED 01 01 2005


ON
LOCATION : DATE :
PH
De ED
p

DETAILS
NOTE:
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF PHYSICAL FACILITIES AND SCHOOLS ENGINEERING
DIVISION AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


1 1
1 2 3
C B A A B B'
A-1 C'
A-1
C 9000
GA.#26 CORR. G.I. ROOFING GA.#26 CORR. G.I. ROOFING
SHEET (PAINT FINISH) SHEET (PAINT FINISH) 400 4500 4500 400
1500 7000 7000 1500 400 1800 6mm THK. MARINE PLYWOOD
3500 3500 1100 APEX OF ROOF APEX OF ROOF 1100 3500 3500 ON 50x50mm CEILING JOIST
12x300mm FIBER CEMENT 12x300mm FIBER CEMENT
@600mm O.C. BOTH WAYS

1100
FASCIA BOARD (PAINT FINISH) FASCIA BOARD (PAINT FINISH)

2026

2026
300x300mm EXTERIOR CONC. 300x300mm EXTERIOR CONC. 12x300mm FIBER CEMENT
LOUVER BLOCKS TOP OF ROOF BEAM TOP OF ROOF BEAM LOUVER BLOCKS FASCIA BOARD PAINT FIN. FR

LIGHTING
12mm THK. FIBER CEMENT 12mm THK. FIBER CEMENT FIXTURES

2800

2800
FASCIA BOARD (PAINT FIN.) FASCIA BOARD (PAINT FIN.)
150mm THK. CHB WALL PLAIN 150mm THK. CHB WALL PLAIN
CLASSROOM CLASSROOM

7000
CEMENT PLASTER & PAINT FIN.
FIN. FLR. LINE FIN. FLR. LINE
CEMENT PLASTER & PAINT FIN.
B CLASSROOM-1

VAR.

VAR.
FIN. GRD. LN. FIN. GRD. LN.

650
6mm THK. ORD. PLYWOOD CEILING

3 RIGHT ELEVATION 4 LEFT ELEVATION w/6mm GROOVE ON 50x50mm


CEILING JOIST @600mm O.C. BOTH

A-2 A-2 WAYS

2000
SCALE: 1:100m SCALE: 1:100m

3 2 1 1'

300
9000 GA#26 G.I. PL.
C

1500
RIDGE ROLL
4500 9400 4500 2000 400
1' 1 2 3 PAINT FIN.

GA#26 G.I. PL. 9000 APEX OF ROOF


RIDGE ROLL
400 2000 4500 4500 400
PAINT FIN. GA#26 G.I. CORR.

2026
SLOPE SHEET ROOFING

REFLECTED CEILING PLAN


APEX OF ROOF PAINT FIN.
8
GA#26 G.I. CORR. TOP OF
A-2
2026

SHEET ROOFING SLOPE ROOF BEAM SCALE: 1:100 M

PAINT FIN. 150mm THK.


CHB WALL PLAIN

2800
TOP OF
CEMENT PLASTER
ROOF BEAM
& PAINT FIN.
150mm THK.
W W CLASSROOM
CHB WALL PLAIN
2800

1 1 FIN. FLR. LN.

150.
CEMENT PLASTER
& PAINT FIN. D
FIN. GRD. LN.
2 D
CLASSROOM D

FIN. FLR. LN.


1
W

2
W
1 5 REAR ELEVATION
150.

FIN. GRD. LN. A-2 SCALE: 1:100m

2 FRONT ELEVATION GA#26 PLAIN GI RIDGE ROLL


C C' B' B A (PAINT FIN.)
A-2 SCALE: 1:100m
300x300mm EXT. CONC.
LOUVER BLOCKS
7000
1500 3500 3500 1100 GA.#26 CORR. G.I. ROOFING SHEET
(PAINT FINISH)
TOP OF TRUSS 300 2200 1000 1 2 3
6mm THK. PLYWOOD CEILING ON
1' 1 2 3 16
50
00 50X50mm CEILING JOIST SP. @600mm
9000
53

1780
O.C. BOTHWAYS (PAINT FINISH)
4500 4500
9000
2000 TOP OF ROOF BEAM

4500 4500 400 400


12x300mm FIBER CEMENT FASCIA

BOARD (PAINT FIN.)


2800
50-100mm RIVER STONE TRENCH W-1 6mm THK MARINE PLYWOOD ON
50x50mm CEILING JOIST

1100
W D-1
W @600mm O.C. BW.
1 CLASSROOM
1
A
A
FIN. FLR. LN. CLASSROOM
VAR.

SUSPENDED LIGHTING FIXTURES

FIN. GRD. LN. 12x300mm CEMENT FIBER

150mm THK. CHB WALL


100 mm THK. CHB WALL FASCIA BOARD w/#26 G.I.
PLASTER & PAINT FINISH 6 CROSS SECTION WITH PLAIN CEMENT FLASHING PAINT FINISH

3500
.
3500

PLASTER (PAINT FIN.) SLOPE


A-2 SCALE: 1:100 M
2

A-4

7000
200x200mm VITRIFIED
1' 1 2 3
7000

BLACKBOARD

B UNGLAZED FLOOR TILES CLASSROOM

500
W EL. 150mm

B'
3 FIN.: PLAIN CEMENT FIN. 1800 9000
B' 200x200mm VITRIFIED WALL

TILES (GLAZED) 400 4500 4500 400


GA.#26 CORR. G.I. SHEET
ROOF (PAINT FINISH) GA.#26 G.I. PLAIN SHT.

3500
SLOPE
3500

RIDGE ROLL

2200
7
2200

TOP OF TRUSS
1 C'
C' A-2
D
W W
GA.#26 CORR. G.I. SHEET
2150

2 2

300
1 ROOF (PAINT FINISH)
300

SEE STRUCTURAL DETAILS

C
25mm
DEP.
d

1500
C
25mm 25mm

CORRIDOR
1500

DEP. DEP. TOP OF ROOF BEAM


1200

2 6mm THK. PLYWOOD CEILING


EL. 125mm
RAMP UP W-3
6 FIN.: PLAIN CEMENT FIN. ON 50X50 WD. NAILERS SP. @

A-2 1 600X600 ON CENTER BOTH

WAYS (PAINT FINISH)


600

2800

50-100mm RIVER STONE TRENCH

9 ROOF PLAN
FLOOR PLAN
WC

1 W-1 W-1 100mm THK. CHB WALL


25

FIN. FLR. LN. CLASSROOM


w/PALIN CEMENT PLASTER & A-2 SCALE: 1:100 M
175

SCHED. OF FLOOR FIN.


A-2 SCALE: 1:100m PAINT FIN.
150

FIN. GRD. LN.


PLAIN CEMENT
LONGITUDINAL SECTION
FL-1
FLOOR FIN.
7
PLAIN CEMENT FLR.
FL-2
FIN. W/ GROOVE (ROUGH)
A-2 SCALE: 1:100 M

REPUBLIC OF THE PHILIPPINES PREPARED BY : CHECKED BY : RECOMMENDING APPROVAL : APPROVED BY : PROJECT TITLE : PROJECT NO: 00200511 OWNER : SHEET NO:

ONE STOREY DESIGNED BY: NQM


EMEC
AMA
VDS II
DEPARTMENT OF EDUCATION
ONE CLASSROOM w/TOILET ENCODED BY: Max C.
VDS DepED A-22
NATHANIEL Q. MENDOZA LUIS G. PURISIMA JR. OLIVER R. HERNANDEZ 7x9m (MODIFIED)
MAXIMO M. CALBANG
4
S
AN
D SCHO
OL
DEPARTMENT OF EDUCATION LGP
SHEET CONTENTS : FLOOR PLAN
CHECKED BY:
S
IE

4
ENG
FAC IL IT

ELEVATIONS
PHYSICAL FACILITIES AND SCHOOLS ENGINEERING DIVISION
INEERING D

PDO - III ARCHITECT III HEAD, PLANNING AND DESIGN UNIT CHIEF, PFSED-OPS FLOOR PLAN, ELEVATIONS, ROOF PLAN
AL

SECTIONS
IC

IV

PFSED-DepED PFSED-DepED DepED


SI
I

YS

MERALCO AVENUE, PASIG CITY PFSED-DepED 01 01 2005


ON
LOCATION : DATE :
PH
De ED
p SECTIONS, REFLECTED CEILING PLAN
DETAILS
NOTE:
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF PHYSICAL FACILITIES AND SCHOOLS ENGINEERING
DIVISION AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


25x25 mm WOOD VENT
50 325 50 PROVIDE INSECT SCREEN

GA#26 G.I. CORR. SHT


ROOFING (PAINT FIN.)

SAG ROD (SEE DETAIL)


2-16
BOLTS
275 STL. PURLINS (SEE
6mm THK. ORD. CLNG. PLY
STRUCTURAL DET.)
CEILING ON 50X50 CLNG.
. 25x75mm WD.FRAME TECK SCREW
JOISTS SP. @ 600 X 600 4.8mm THK. FIBER CEMENT CEILING

SECTION
S4S KD TANG.
O.C. B/W ( PAINT BOARD ON 50x50mm CLG. JST. @600mm

SEMI-GLOSS ) OC BW (PAINT FIN) 20x20x5mm ANGULAR BAR


575 575 @600mm OC VERT.
MEMBER FOR FRAME OF
6mm CONC. FIBER FASCIA
BOARD

10mm THICK
PLATE

6mm GROOVE

300x150x10mm BASE PLATE


275

4-16x300mm LONG BENT


ANCHOR BOLTS

300
PLAN 25x25mm WOOD VENT 12x300mm FIBER
CEMENT FASCIA BOARD
4 CEILING VENT DETAIL PROVIDE INSECT SCREEN
(PAINT FIN.)

A-6 SCALE : 1 : 5 M

FULLY WELD ON RAFTER


GA#26 CORR. G.I. SHT.

20
ROOF (PAINT FIN.)
A RIVET @400mm OC
LONGITUDINAL
10mm SAG RODS

1500 4.8mm THK. FIBER CEMENT CEILING


1100 BOARD ON 50x50mm CLG. JST. @600mm

OC BW (PAINT FIN)
GA#26 CORR. G.I. SHT.
ROOF (PAINT FIN.)
25x25mm S4S KD TANG. PAINT
LC 100x50x15x1.5mm STL FOR VENT. W/ WIRE MESH
C-PURLINS @750mm OC (VENTILLATION)
ON 2-LC 150x65x20x30mm
RAFTER

VENT. WITH
WIRE MESH INSECT
5 EAVES, VENT. & INT CEILING DETAIL

23
SCREEN (SEE DETAIL)
SEE STRUCTURAL DETAIL A-3 SCALE : AS SHOWN
TOP OF ROOF BEAM TOP OF ROOF BEAM

6mm THK. ORD. PLYWOOD


400

CONC.
BEAM INT. CEILING ON50x50mm
FR 25x300 S4S KD TANG OR 12mm THK
CEILING JOIST @600mm OC (150X400)
FIBER CONCRETE FASCIA
BOTHWAYS
BOARD ON 25x25x6 L-BAR W/
25x6mm THK STIFFENER FLAT 12mm FIBER CONCRETE FASCIA
BAR @ EVERY 1200mm OC

300
BOARD ON 25x25x6 L-BAR W/25x6mm
THK STIFFENER FLAT BAR @ EVERY
1200mm OC
6mm THK. MARINE PLYWOOD

INT. CEILING w/6MM GROOVE ON 50x50mm


CEILING JOIST @600mm OC BOTHWAYS

6mm THK. ORD. PLYWOOD

INT. CEILING w/6MM GROOVE ON 50x50mm 600


CEILING JOIST @600mm OC BOTHWAYS
W-1
2800

2800 300

2216
150mm THK. CHB WALL

PLAIN CEM. PLASTER (PAINT FIN.)

6
D-1
LOUVER BLOCKS (CONCRETE)
6

150 mm THK. CHB WALL WITH

PLAIN CEMENT PLASTER (PAINT FIN.)

600
PART OF PART OF CORRIDOR
800

CLASSROOM CLASSROOM

25
FIN. FLOOR LINE FIN. FLOOR LINE FIN. FLOOR LINE
FIN. FLOOR LINE INSIDE
175

175

150
OUTSIDE
FIN. GRADE LINE FIN. GRADE LINE FIN. GRADE LINE
ELEVATION

1500

BAY SECTION SECTION


1
DETAIL SECTION 3 LOUVER BLOCKS DETAIL
A-3 SCALE: 1 : 20 M
2
A-3 SCALE: 1:20 mts. A-3 SCALE : 1:20M

REPUBLIC OF THE PHILIPPINES PREPARED BY : CHECKED BY : RECOMMENDING APPROVAL : APPROVED BY : PROJECT TITLE : PROJECT NO: 00200511 OWNER : SHEET NO:

ONE STOREY DESIGNED BY: NQM


EMEC
AMA
VDS II
DEPARTMENT OF EDUCATION
ONE CLASSROOM w/TOILET ENCODED BY: Max C.
VDS DepED A-34
NATHANIEL Q. MENDOZA LUIS G. PURISIMA JR. OLIVER R. HERNANDEZ 7x9m (MODIFIED)
MAXIMO M. CALBANG
4
S
AN
D SCHO
OL
DEPARTMENT OF EDUCATION LGP
SHEET CONTENTS : FLOOR PLAN
CHECKED BY:
BAY SECTION, DETAIL SECTION, DECO
S
IE

4
ENG
FAC IL IT

ELEVATIONS
PHYSICAL FACILITIES AND SCHOOLS ENGINEERING DIVISION
INEERING D

PDO - III ARCHITECT III HEAD, PLANNING AND DESIGN UNIT CHIEF, PFSED-OPS BLOCK VENT., DAMP PROOFING DETAIL
AL

SECTIONS
IC

IV

PFSED-DepED PFSED-DepED DepED


SI
I

YS

MERALCO AVENUE, PASIG CITY PFSED-DepED 01 01 2005


ON
LOCATION : DATE :
PH
De ED
p

DETAILS
NOTE:
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF PHYSICAL FACILITIES AND SCHOOLS ENGINEERING
DIVISION AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


OF THE SAME DUE TO FAULTY DESIGN.

C B'
4.5mm THK. FIBER

1 2 4.5mm THK. FIBER


CEMENT CLG. BD. ON

1 2 1800
CEMENT CLG. BD. ON
2000 50x50mm CLG. JOIST
@600mm O.C.
50x50mm CLG. JOIST
@600mm O.C.
1800
TOP OF ROOF BEAM
600 950 450
TOP OF ROOF BEAM
R.C. BEAM (SEE
6 R.C. BEAM (SEE STRUCTURAL DETAIL)
A-3 STRUCTURAL DETAIL)
FIN CLNG. LN. FIN CLNG. LN.
850

W-3

100mm THK. CHB


PLASTER & PAINT FIN.
100mm THK. CHB
W-3 PLASTER & PAINT FIN.

38mm TEXTURED
STAINLESS STEEL GRAB

1000
BAR (HT. = 850mm)

2800

2800
2400

2400
PART OF
2000

CLASSROOM 38mm TEXTURED STAINLESS


STEEL GRAB RAIL
5
LAV 38mm TEXTURED STAINLESS
A-3 STEEL GRAB RAIL (HT.=850mm)

1500

1500
200x200mm VITRIFIED
CERAMIC GLAZED WALL (HT.=850mm)
TILES 200x200mm VITRIFIED

850
CERAMIC GLAZED WALL

800
200x200mm VITRIFIED
TILES
D-2
CERAMIC GLAZED WALL
TILES

FFL FFL
B'

VAR.

VAR.
NGL NGL
25MM

1 DET. PLAN OF TOILET 2 DET. SECTION OF TOILET


A-4 SCALE: 1 : 250 M
A-4 SCALE: 1 : 100 M 3 DET. SECTION OF TOILET
A-4 SCALE: 1 : 100 M

900 4 EQ. PARTS= 2 EQUAL PARTS =


900 2500 1260
1228
300

336

336

6-BLDS.
574
(CLEAR)

(CLEAR)
1225
1264
2400

2400

2400
2100

2100

1600
800

800
300

STAINLESS STEEL
KICKING PLATE 100

D-1 D-2
W-1 W-2 W-3 C' CLASSROOM TYPICAL
100

SAME AS W-1 SAME AS W-1


D EL. +175mm
JALOUSIE WINDOW W/ CLEAR GLASS

6mm
6mm
C
HOLLOW CORE FLUSH TYPE
6mm
PANEL DOOR
DOOR
TYPE HINGED
& FIXED GLASS TRANSOM HINGED DOOR ON
BLADES ON STD. ALUM. HOUSING & FIXED
CLEAR GLASS TRANSOMS ON 50x150mm
2
50x150mm WOOD NON-SK
ON 50x150mm WOOD ID PLAIN
WD. JAMBS/FRAMES CEMENT

RAMP UP
FLOOR
JAMBS/FRAMES JAMBS/FRAMES PROVIDE CEMEMN
T FINISH

1200
FL-2

RAMP UP
1500
1500
KICKPLATE

1200
CORRIDOR
DETAIL SECTION
SCALE 1:5 M

LINE OF ROOF
1800
1800 LINE OF CORRIDOR

DETAIL PLAN
SCALE 1:50 M

SCHEDULE OF DOORS & WINDOWS 10 RAMP DETAIL


1
A-4 SCALE: 1 : 100 M A-2 AS SHOWN

REPUBLIC OF THE PHILIPPINES PREPARED BY : CHECKED BY : RECOMMENDING APPROVAL : APPROVED BY : PROJECT TITLE : PROJECT NO: 00200511 OWNER : SHEET NO:

ONE STOREY DESIGNED BY: NQM


EMEC
AMA
VDS II
DEPARTMENT OF EDUCATION
ONE CLASSROOM w/TOILET ENCODED BY: Max C.
VDS DepED A -3
4
NATHANIEL Q. MENDOZA LUIS G. PURISIMA JR. OLIVER R. HERNANDEZ 7x9m (MODIFIED)
MAXIMO M. CALBANG
4
S
AN
D SCHO
OL
DEPARTMENT OF EDUCATION LGP
SHEET CONTENTS : FLOOR PLAN
CHECKED BY:
S
IE

4
ENG
FAC IL IT

ELEVATIONS
PHYSICAL FACILITIES AND SCHOOLS ENGINEERING DIVISION
INEERING D

PDO - III ARCHITECT III HEAD, PLANNING AND DESIGN UNIT CHIEF, PFSED-OPS
AL

DETAIL SECTIONS
PLAN OF TOILET, DETAIL SECTION OF
IC

IV

PFSED-DepED PFSED-DepED DepED


SI
I

YS

MERALCO AVENUE, PASIG CITY PFSED-DepED 01 01 2005


ON
LOCATION : DATE :
PH
De ED
p
TOILET, DOOR & WINDOW SCHEDULE, RAMP DET.
DETAILS
NOTE:
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF PHYSICAL FACILITIES AND SCHOOLS ENGINEERING
DIVISION AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


1' 1 2 3
1' 1 2 3
2000 9000
9000 50x100x15x1.5mm
STEEL C-PURLINS
2000 4500 4500 400 4000 4500 400
750mm O.C.

F-2

1000
F-1 F-1
C-1 C-2 C-1
A
RG-1 RG-1
A 10mm% SAG ROD WITH
STANDARD NUTS &
WF-1 WF-1
WASHERS @ EACH END

3500

3500
WF-1
WF-1

RG-2

RG-2
EB-1

EB-1
F-1 F-1

R - 2

R - 1

R - 1

R - 2
C-1 C-1

7000

7000
B F-1
B
100mm THICK

600
C-1 WF-1 SLAB ON FILL RG-3
WITH 10mm
SPACED AT 400

3500

3500
WF-1
WF-1

RG-2

RG-2
EB-1

EB-1
BOTHWAYS

2200
B' B'

WF-1
2200

R - 2
RG-3
F-1
C-1 F-2 F-1
F-1
C-1 C-2 C-1 RG - 1 RG - 1

300

300
C C RG-1

WF-1 WF-1

1500
RAMP UP

A FOUNDATION PLAN B ROOF FRAMING PLAN


S-1 SCALE 1:100 M. S-1 SCALE 1:100 M.

150MM THK.
CHB

10@600
L
HOR. BARS

NGL NATURAL GRADE LINE


1

10@600
VERT. BARS 1800

600
D
Y-BARS 10 300mm TEMP
X-BARS BARS BOTHWAYS
W

150
t

250
Y-BARS

10mm

100
X-BARS

C O L U M N S C H E D U L E L 100 mm THICK
GRAVEL BEDDING
G-20mm GRAVEL 3-10mm
BEDDING 10mm @300 CUT BARS
PLAN SECTION 400

LEVEL C-1 C-2 C TYP. FOOTING DETAIL E DETAIL OF RAMP


D DETAIL OF WF-1
SCALE 1 : 50M
S-1 SCALE : NTS
S-1 SCALE : NTS. S-1
300 300

DESIGN CRITERIA :
200

200

S C H E D U L E O F F O O T I N G S
A. CONCRETE
FOUNDATION LEVEL
LEVEL

fc' = 20.685 Mpa ( 3,000 Psi ), minimum compressive strength of concrete


FOOTING
FOOTING DIMENSIONS (mm) REINFORCEMENT
a 28 days unless otherwise specified.
MAIN BAR: MAIN BAR: REMARKS
MARK LENGTH WIDTH DEPTH THICKNESS B. REBAR
4-%16mm 6-%16mm BAR X BAR Y
(L) (W) (D) (t)
fy = 275.8 Mpa ( 40,000 Psi ), minimum yield strength of reinforcing bars
ROOF

TIES : 10 mm TIES : 10 mm
1@50, 8@75, REST @ 1@50, 8@75, REST @ F-1 800 800 1200 250 4 - 16mm% 4 - 16mm% SQUARE FOOTING unless otherwise specified.
150mm TO CENTER 150mm TO CENTER C. STRUCTURAL STEEL

F-2 1000 1000 1200 250 4 - 16mm% 4 - 16mm% SQUARE FOOTING


Fy = 248 Mpa ( 36 Ksi ), specified minimum yield strength
TO

unless otherwise specified.


D. FOUNDATION

SBP = 95.706 Kpa ( 2,000 Psf ), was used in the design for all footings.
No footing shall rest on fill.

REPUBLIC OF THE PHILIPPINES PREPARED BY : CHECKED BY : RECOMMENDING APPROVAL : APPROVED BY : PROJECT TITLE : PROJECT NO: 00200511 OWNER : SHEET NO:

ONE STOREY DESIGNED BY: NQM


EMEC
AMA
VDS II
DEPARTMENT OF EDUCATION
ONE CLASSROOM w/TOILET ENCODED BY: Max C.
VDS DepED S - 11
MAXIMO M. CALBANG ANTONIA M. ALHAMBRA LUIS G. PURISIMA JR. OLIVER R. HERNANDEZ 7x9m (MODIFIED) 2
S
AN
D SCHO
OL
DEPARTMENT OF EDUCATION LGP
SHEET CONTENTS : FLOOR PLAN
CHECKED BY:
S
IE

2
ENG
FAC IL IT

ELEVATIONS
PHYSICAL FACILITIES AND SCHOOLS ENGINEERING DIVISION
INEERING D

PDO - III
CIVIL ENGINEER/MASTER PLUMBER HEAD, PLANNING AND DESIGN UNIT CHIEF, PFSED-OPS GENERAL NOTES LEGEND
AL

SECTIONS
IC

IV

PFSED-DepED PFSED-DepED DepED


SI
I

YS

MERALCO AVENUE, PASIG CITY PFSED-DepED 01 01 2005 ELECTRICAL LAYOUT RISER DIAGRAM
ON
LOCATION : DATE :
PH
De ED
p

DETAILS
NOTE:
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF PHYSICAL FACILITIES AND SCHOOLS ENGINEERING
DIVISION AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


B 1 A
S-
2

4-%16x300mm LONG
R- BENT ANCHOR BOLTS 65 65
2 1 2
-
R-

20

20
EB EB
- 300x150x10mm 50
1
300

15
ALUM. STEEL KICKING 50 50 BASE PLATE
PLATE

37.5

150

150
RG-1 RG-2 RG-2 RG-1

100
D-2

37.5
HOLLOW CORE FLUSH TYPE
HINGED DOOR ON WOOD

JAMBS/FRAMES PROVIDE 2LC-150x65x20x3 LC-150x65x20x3


LINE OF R-1/R-2
KICKPLATE
R-1 R-2 LC-100x50x15x1.5
10mm THICK PLATE
PLAN

F DETAIL OF RAfTER G DETAIL OF PURLINS


A ELEV @ GRID 1 & 3 2-%16

BOLTS 2-%16
S-2
SCALE NTS
S-2
SCALE NTS

BOLTS
S-2 SCALE: 1:100 M
4-%16x300mm
LONG BENT R-1/R-2
ANCHOR BOLTS

300x150x10mm 10mm THICK PLATE

C B A BASE PLATE
10mm THICK PLATE 4-%16x300mm LONG 100x50x15x1.5mm

BENT ANCHOR BOLTS STEEL C-PURLINS


R- 750mm O.C.
1/
300x150x10mm R-
2
BASE PLATE
R-
1 1
R- 1-%10mm A-307
ANCHOR BOLT

L-50x50x4.5
RC BEAM/COLUMN
RG-1 RG-1

R-2

ELEVATION
ELEVATION
EB-1 10mm X 150mm

TYPICAL RAFTER ANCHORAGE DETAIL


ANCHOR BOLTS
(SEE SCHED)
E SPACED @ 800mm O.C.

B ELEV @ GRID 2 S-2 SCALE 1:20 M

S-2 SCALE: 1:100 M


1 SECTION DETAIL H PURLIN CONNECTION DET
SCALE 1 : 5 M
SCALE NTS S-2
S-2

L1 L2

2D LAP SPLICES ARE ALLOWED 2D 2D LAP SPLICES ARE ALLOWED 2D

ONLY IN THIS PORTION ONLY IN THIS PORTION

B'

100x50x15x1.5mm
2-10mm SIDE BARS
2
R- STEEL C-PURLINS
750mm O.C.

RG-3 10mm% SAG ROD WITH


RG-1
RG-3
STANDARD NUTS &

100mm
D TYPICAL BEAM ELEVATION TOP OF RAFTER WASHERS @ EACH END

CIRCULAR TUBE 10mm TIE ROD WITH


SCHED 40 S-2 STANDARD NUTS &
WASHERS @ EACH END
CL.
50x100x15x1.5mm
STEEL C-PURLINS
B E A M S C H E D U L E 150
150
750mm O.C. R-
1/
C ELEV @ GRID 1 BEAM S T E E L R E I N F O R C E M E N T S 10mm SAG ROD
R-
2
DIMENSIONS
S-2 SCALE: 1 : 100 M FLOOR BEAM
LEFT MID SPAN RIGHT
S T I R R U P S
LEVEL MARK ( in / mm ) REBAR 10mm

(mm ) (UNLESS NOTED OTHERWISE)


b h TOP BOTTOM TOP BOTTOM TOP BOTTOM

RG-1 150 400 12mm 2 2 2 2 2 2 1@50, 8@100, REST@200


LEVEL

RG-2 150 400 12mm 2 2 2 2 2 2 1@50, 6@100, REST@200

1@50, 6@100, REST@200


ROOF

J SAG ROD CONNECTION DET.


EB-1 150 250 10mm 2 2 2 2 2 2 1@50, REST@200 I TIE ROD CONNECTION DET. SCALE 1 : 10 M
SCALE 1 : 10 M S-2
S-2

REPUBLIC OF THE PHILIPPINES PREPARED BY : CHECKED BY : RECOMMENDING APPROVAL : APPROVED BY : PROJECT TITLE : PROJECT NO: 00200511 OWNER : SHEET NO:

ONE STOREY DESIGNED BY: NQM


EMEC
AMA
VDS II
DEPARTMENT OF EDUCATION
ONE CLASSROOM w/TOILET ENCODED BY: Max C.
VDS DepED S-22
MAXIMO M. CALBANG ANTONIA M. ALHAMBRA LUIS G. PURISIMA JR. OLIVER R. HERNANDEZ 7x9m (MODIFIED) 2
S
AN
D SCHO
OL
DEPARTMENT OF EDUCATION LGP
SHEET CONTENTS : FLOOR PLAN
CHECKED BY:
S
IE

2
ENG
FAC IL IT

ELEVATIONS
PHYSICAL FACILITIES AND SCHOOLS ENGINEERING DIVISION
INEERING D

PDO - III
CIVIL ENGINEER/MASTER PLUMBER HEAD, PLANNING AND DESIGN UNIT CHIEF, PFSED-OPS ELEVATIONS
AL

SECTIONS
IC

IV

PFSED-DepED PFSED-DepED DepED


SI
I

YS

MERALCO AVENUE, PASIG CITY PFSED-DepED 01 01 2005 TYPICAL CONNECTION DETAIL


ON
LOCATION : DATE :
PH
De ED
p

DETAILS
NOTE:
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF PHYSICAL FACILITIES AND SCHOOLS ENGINEERING
DIVISION AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


GENERAL NOTES CALCULATIONS

1. ALL ELECTRICAL WORKS SHALL COMPLY IN ACCORDANCE WITH THIS PLAN


AND SPECIFICATIONS. THE APPLICABLE PROVISIONS OF THE LATEST EDITION 1. TOTAL LOAD: 5. SCHEMATIC DIAGRAM OF SAFETY SWITCH:
OF THE PHILIPPINE ELECTRICAL CODE (PEC). THE RULES AND REGULATION OF A. LIGHTING OUTLET 7 x 100 W = 700 W
THE LOCAL ENFORCING AUTHORITY AND THE REQUIREMENTS OF THE LOCAL
POWER COMPANY. ALL ELECTRICAL WORKS SHALL BE UNDER THE 3.5mmTHW WIRE
B. FAN OUTLET 1 x 100 W = 100 W
IMMEDIATE SUPERVISION OF A DULY REGISTERED ELECTRICAL ENGINEER.
C. CONVENIENCE OUTLET 2 x 180 W = 360 W

2. THE ELECTRICAL SERVICE POWER IS 1-PHASE, 2-WIRE, 230 V AC, 60 Hz.


TOTAL LOAD = 1160 W
3. WIRING METHOD SHALL BE AS FOLLOWS :
a. FEEDERS AND RISERS - RIGID METALLIC CONDUIT
I LOAD 1160 / 230 = 5.04 A
b.LIGHTING, POWER RECEPTACLE - POLYVINYL CHLORIDE CONDUIT
BRANCH CKT., & AUXILIARY SCH. 40

4. ALL WIRES SHALL BE COPPER AND THERMOPLASTIC INSULATED TYPE "THW" UNLESS 2. CIRCUIT REQUIREMENT:
OTHERWISE INDICATED IN THE PLAN. THE MINIMUM SIZE OF WIRE FOR POWER AND LIGHTING
CIRCUIT HOMERUN SHALL BE 3.5mm AND INSULATED FOR 600 VOLTS. SMALLEST 3.5mmTHW COPPER WIRE
USE 20 A 2-WIRE CIRCUIT
RACEWAY SHALL BE 15mm TRADE/NOMINAL SIZE.

5. ALL OUTLET BOXES SHALL BE GALVANIZED GAUGE NO. 16 DEEP TYPE WITH
3. SERVICE ENTRANCE CONDUCTORS:
FACTORY KNOCKOUTS.

6. ALL MATERIALS TO BE USED SHALL BE BRAND NEW AND APPROVED TYPE FOR THE USE 2-3.5mm THW COPPER WIRES

PARTICULAR LOCATION AND PURPOSE.

7. GROUNDING SYSTEM SHALL BE PROVIDED TO ALL LIGHTING AND POWER CIRCUIT AS PER 4. SERVICE EQUIPMENT:
PHILIPPINE ELECTRICAL CODE REQUIREMENT.
USE 1-30 A, 2PST, 250V SAFETY SWITCH WITH 2-20 A, RENEWABLE FUSES
8. MOUNTING HEIGHT OF WIRING DEVICES SHALL BE AS FOLLOWS :

a. LIGHT SWITCH - 1.20 M ABOVE FINISH FLOOR

b. CONVENIENCE OUTLET - 0.30 M ABOVE FINISH FLOOR.

c. SAFETY SWITCH - 1.80 M ABOVE FINISH FLOOR

OVERHEAD SERVICE ENTRANCE


CONNECTED TO 220V AC, 1,
2 WIRE, 60 Hz FITTED WITH
20mm TYPE "F" CONDULET
1 2 3

LEGEND A
SYMBOL DESCRIPTION
aa a ba
CEILING LINE
- CEILING LIGHT OUTLET 222 22

BUILDING WALL a a

2
- 2 x 40 WATTS FLUORESCENT LAMP 2 2

METERING CONDUIT CLASSROOM


F - CEILING FAN OUTLET KWHR METER
2-3.5mm THW IN 20mm RSC

B
a
2 F 2
2

S/Sa - ONE GANG DEVICE SWITCH a

3500 mm
S ab - TWO GANG DEVICE SWITCH
aaa b
222 2
S cde - THREE GANG DEVICE SWITCH

1800 mm

1800 mm

1800 mm
a
1
- 1 x 40 WATTS FLUORESCENT LAMP
LP
Sf - FAN CONTROL SWITCH SabcSf

C
22

Sab M
Sabc
GROUND FLOOR LINE
- RACEWAY CONDUIT CONCEALED IN CEILING b
c

- RACEWAY CONDUIT CONCEALED UNDER FLOOR FIN. GRADE LINE OVERHEAD SERVICE ENTRANCE

ELECTRICAL LAYOUT
REFER TO RISER DIAGRAM

1-3.5mm THW COPPER WIRE


IN 15mm C
16mmx2400mm LENGTH
- SAFETY SWITCH
GROUNDING ROD COPPERWELD
E-1 SCALE: 1:100m

- DUPLEX CONVENIENCE OUTLET, GROUNDING TYPE


10 AMPS, 250 VOLT WITH MODERN PLATE COVER

M
- ELECTRIC SERVICE METER

- SERVICE ENTRANCE
ELECTRICAL RISER DIAGRAM
NOT TO SCALE

REPUBLIC OF THE PHILIPPINES PREPARED BY : CHECKED BY : RECOMMENDING APPROVAL : APPROVED BY : PROJECT TITLE : PROJECT NO: 00200511 OWNER : SHEET NO:

ONE STOREY DESIGNED BY: NQM


EMEC
AMA
VDS II
DEPARTMENT OF EDUCATION
ONE CLASSROOM w/TOILET ENCODED BY: Max C.
VDS DepED E -3
1
VENERANDO D. SAHAGUN LUIS G. PURISIMA JR. OLIVER R. HERNANDEZ 7x9m (MODIFIED)
MAXIMO M. CALBANG
1
AN
D SCHO
OL
DEPARTMENT OF EDUCATION SHEET CONTENTS : FLOOR PLAN
LGP CALCULATIONS
S
CHECKED BY:
S
IE

4
ENG
FAC IL IT

ELEVATIONS
PHYSICAL FACILITIES AND SCHOOLS ENGINEERING DIVISION
INEERING D

PDO - III ENGINEER III HEAD, PLANNING AND DESIGN UNIT CHIEF, PFSED-OPS GENERAL NOTES LEGEND
AL

SECTIONS
IC

IV

PFSED-DepED PFSED-DepED DepED


SI
I

YS

MERALCO AVENUE, PASIG CITY PFSED-DepED 01 01 2005 ELECTRICAL LAYOUT RISER DIAGRAM
ON
LOCATION : DATE :
PH
De ED
p

DETAILS
NOTE:
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF PHYSICAL FACILITIES AND SCHOOLS ENGINEERING
DIVISION AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


LEGEND:
3450
CB CATCH BASIN
100mm THK. + FIN. SLAB W/
10mm REBARS AT 200mm O.C. 100mm THK. + FIN. SLAB w/
150X300mm RC BEAM W/2-16mm 10mm BENT UP 2 OUT OF 3 CDP CONCRETE DRAIN PIPE
BENT UP 2 OUT OF 3 AT L/4 TOP AND BOT. REBARS & 10mm
FROM FACE SUPPORT. BOTH WAYS @L/4 FROM FACE SUPPORT BW
STIRRUPS
CO CLEAN OUT
1@50,3@100, REST @300mm O.C.
3450
AIR SPACE CV CHECK VALVE
150 1000 150 2000 150 NGL
S-1a 100mm THK. + FIN. SLAB w/

100
PLASTER
100mm REBARS @300mm BW. FROM
w/WATERPROOFING HB HOSE BIBB

(MAX)
MANHOLE

150
FACE OF SUPPORT MANHOLE

750
OUTLET COMPOUND OR APPLY

300
ONE FACE BITUMIN TAR FD FLOOR DRAIN
0.60

100
250 WATER LEVEL
250

300
PLASTER W/WATERPROOFING
GICWL GALVANIZED IRON COLD WATER LINE (SCH. 40)

50
COMPOUND OR APPLY ONE FACE

2100
WALLS REINFORCEMENT 10mm REINF. VERT & HOR.
BITUMIN TAR
2300

2000

1600
MANHOLE MANHOLE WATER LEVEL 10mm VERT. & HOR. BAR BAR @ 200mm OC BW GICWR GALVANIZED IRON COLD WATER RISER (SCH. 40)
LEACHING @200mm O.C. E.W.

2100

1900
GV GATE VALVE
50 (TYP.) S-2 100mm THK. + FIN. SLAB w/10mm CHAMBER DIGESTIVE CHAMBER
REBARS @300mm OC BW. bENT 2 OUT OF

3 @L/4 FR. FACE SUPPORT & SHORT SPAN GRAVEL BED MH MANHOLE

100
10mm TEMP. BARS @300mm EW
150

PVCDS POLYVINYL CHLORIDE DOWNSPOUT


2000
1SLOPE

100
2300
PLAN 100mm THK. + FIN. SLAB w/
PVCDP POLYVINYL CHLORIDE DRAIN PIPE

100mm THK SLAB W/ 10mm REBARS 10mm REBARS @300mm OC


BW PVCDS POLYVINYL CHLORIDE DOWNSPOUT
@300mm BOTH WAYS

SEPTIC TANK DETAILS CROSS SECTION PVCSP POLYVINYL CHLORIDE SOIL PIPE
3 LONGITUDINAL SECTION
P-1 SCALE: 1 : 50 M PVCVAC POLYVINYL CHLORIDE VENT. ACROSS CEILING

PVCVP POLYVINYL CHLORIDE VENT. PIPE

PVCVS POLYVINYL CHLORIDE VENT STACK

PVCVTR/W POLYVINYL CHLORIDE VENT TROUGH ROOF/WALL

PVCWP POLYVINYL CHLORIDE WASTE PIPE

PVCWS POLYVINYL CHLORIDE WASTE STACK

RD ROOF DRAIN

UD URINAL DRAIN

WC WATER CLOSET

LAV LAVATORY

CS COUNTER SINK

PLUMBING NOTES:

GRADES OF HORIZONTAL PIPINGS


RUN ALL HORIZONTAL PIPINGS IN PERPECT ALIGNMENT AND AT
SEPTIC TANK 1. A FORM GRADE NOT LESS THAN TWO PERCENT (2
75mm PVCVTW
2. CHANGE IN DIRECTION
ALL CHANGE IN DIRECTION SHALL BE MADE BY APPROPRIATE USE OF

CLASSROOM
T

R
100mm PVCSP FORTY-FIVE DEGREES (45) WYES, LONG SWEEP QUARTER BEND,

V
C
V

M
P
O SIXTH-EIIGHT OR SIXTEENTH BEND. WHEN THE CHANGE OF FLOW IS FROM

m
75

m
O HORIZONTAL TO VERTICAL A SINGLE 1/8 BEND COMBINATION MAYBE USED

R
ON VERTICAL STACKS AND SHORT QUARTER BENDS MAYBE USED ON WASTE

S
LA
75mm PVCVTR

S
LINE, TEE AND CROSSES MAYBE USED IN BENT PIPES.
CV 20mm GICWL

C
3. PROHIBITED FITTINGS
50mm NO DOUBLE HUB OR TEE BRANCH SHALL BE USED ON HORIZONTAL SOIL
F AND WASTE LINES, THE DRILLINGS AND TAPPING OF HOUSE DRAIN, WASTE
PVC CO LAV
O
PVCWP

WC O OR VENT PIPES AND USED OF SADDLE HUB AND BEND ARE PROHIBITED.

R
1.
4. PIPE CLEAN-OUTS

R
FD
O CLEAN-OUTS ARE REQUIRED UNDER THE F0LLOWING CONDITIONS:

ID
50mm

TW a) EVERY CHANGE OF HORIZONTAL DIRECTION EXCEEDING TWENTY TWOAND

R
V
C
ONE-HALF DEGREES (22 1/2).

R
O

V
P
m
75

m
b) ONE AND ONE-HALF METERS (1.50m.) INSIDE THE PROPERTY LINES

C
E

K
BEFORE THE HOUSE DRAINAGE CONNECTION.

N
T

A
T
N

IC
SE c) EVERY FIFTEEN METERS (15.00m) IN HORIZONTAL RUN OF PIPES.
L

I
WL
d) AT THE END OF ANY HORIZONTAL PIPE LINES.

C
IC

W
G

P
W

R
O

C
20

m
V
V

P
V LA 5. THE DIGESTION CHAMBER OF SEPTIC VAULT MUST BE WATERPROOFED.

ID
m
C
F

m
D

R
0
S

5
m
P

O
50

R
6.
O

C
C
V
NOT LESS THAN 0.30 METER OF AIR SPACE MUST BE LEFT BETWEEN

C
P

V
P
m
RAMP UP

0
m

C
10 THE TOP OF THE SEWAGE AND THE UNDER PART OF VAULT ROOF SLAB.

7.
NO SEPTIC VAULT SHALL BE CONSTRUCTED UNDER THE BUILDING.

GV CORRIDOR 8.
ALL PLUMBING WORKS SHALL BE UNDER THE SUPRVISION OF A
LICENSED MASTER PLUMBER AND A LICENCED PLUMBING CONTRACTOR.
V

G
DESIGN CRITERIA
M

M
T

O
WL
100mm PVCSP TE

R
G
V
W

IN m

A
G
20

m
TO MAIN SEWER EM
ST

P
M

A
U
S E S
i. LIVE LOAD_________________ 1000Pa

P
GV

Y
SYSTEM

R
W

C
SE

IN PV
P
CORRIDOR LINE ROOF LINE

m
20mm GIWL TO AM 00 ii ALLOWABLE STRESSES

m
M

A
1 EM

R
MAIN WATER T ST

O
S

Y
SYSTEM 1. CONCRETE

a. FOR FOOTING, BEAMS AND SLABS


fc'' = 20 MPa
2. CONCRETE MASONRY UNITS (LOAD BEARING CHB)
fm' =6.90 MPa, fm = 2.41 MPa
3. REINFORCING STEEL BARS
FOR BARS SMALLER THAN 16mm

fy = 230 MPa
1 PLUMBING RO-IN LAYOUT 2 ISOMETRIC VIEW 4. ASSUMED ALLOWABLE BEARING CAPACITY Y = 100KPa

P-1 SCALE: 1:100m


P-1 SCALE: NTS

NOTE:
WATER TABLE IS 1500 BELOW GROUND LEVEL.

REPUBLIC OF THE PHILIPPINES PREPARED BY : CHECKED BY : RECOMMENDING APPROVAL : APPROVED BY : PROJECT TITLE : PROJECT NO: 00200511 OWNER : SHEET NO:

ONE STOREY DESIGNED BY: EMEC


AMA
NQM
VDS II
DEPARTMENT OF EDUCATION
ONE CLASSROOM w/TOILET ENCODED BY: Max C.
VDS DepED P -1
3
E. MELQUIADES EMEL CUBA II LUIS G. PURISIMA JR. OLIVER R. HERNANDEZ 7x9m (MODIFIED)
MAXIMO M. CALBANG
1
S
AN
D SCHO
OL
DEPARTMENT OF EDUCATION LGP
SHEET CONTENTS : FLOOR PLAN PLUMBING RO-IN LAYOUT,
CHECKED BY:
S
IE

4
ENG

ISOMETRIC VIEW, SEPTIC TANK, CATCH BASIN, DRAIN PIT, STORM


FAC IL IT

ELEVATIONS
PHYSICAL FACILITIES AND SCHOOLS ENGINEERING DIVISION
INEERING D

PDO - III
CIVIL ENGINEER/MASTER PLUMBER HEAD, PLANNING AND DESIGN UNIT CHIEF, PFSED-OPS
DRAIN, LEACHING FIELD DET., LEGEND, NOTES & DESIGN
AL

SECTIONS
IC

IV

PFSED-DepED PFSED-DepED DepED


SI
I

YS

MERALCO AVENUE, PASIG CITY PFSED-DepED 01 01 2005


ON
LOCATION : DATE :
PH
De ED
p CRITERIA
DETAILS
NOTE:
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF PHYSICAL FACILITIES AND SCHOOLS ENGINEERING
DIVISION AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


REPUBLIC OF THE PHILIPPINES

OFFICE OF THE CITY/MUNICIPAL


ENGINEER/BUILDING OFFICIAL

DISTRICT/CITY/MUNICIPALITY

ARCHITECTURAL
LAND USE & ZONING
A-1 PERSPECTIVE VIEW, TABLE OF
CONTENTS

A-2 FLOOR PLAN, ELEVATIONS, ROOF


PLAN SECTIONS, REFLECTED
CEILING PLAN

A-3 SCHEDULE OF DOOR & WINDOWS,


BAY SECTION, DETAIL SECTION, LINE & GRADE
LOUVER BLOCK VENT., RAMP
DETAIL

ARCHITECTURAL

1 PERSPECTIVE VIEW
A-1 SCALE: NTS

STRUCTURAL

S-1 FOUNDATION PLAN, ROOF


FRAMING PLAN FOOTING DETAIL, STRUCTURAL
COLUMN DETAIL, WF-1, RAMP
DETAIL

S-2 ELEVATIONS TYPICAL


CONNECTION DETAIL

SANITARY

ELECTRICAL
E-1 ELECTRICAL LAYOUT PLAN, RISER
DIAGRAM, LOAD SCHEDULE, GEN.
NOTES

ELECTRICAL

SANITARY

MECHANICAL

CONSULTANT / DESIGNER REVIEWED BY: RECOMMENDING APPROVAL : APPROVED FOR ACCREDITATION : CONCURRED : PROJECT TITLE : PROJECT NO: 01-002 OWNER : SHEET NO:

REPUBLIC OF THE PHILIPPINES DESIGNED BY: AZB


E

ONE STOREY DEPARTMENT OF EDUCATION


A-1
t he PH F A
f
o IL
IC I

DEPARTMENT OF EDUCATION (DepED) A-1


T
M
L

P
B

TA
PU

I TO R I NG
IN

SK

EMMANUEL P. CUNTAPAY
RE

ES

SOFIA T. SANTIAGO GILBERTO S. REYES RAMON C. BACANI


DepED
F O RC E

ALBERT Z. DE BELEN
ONE CLASSROOM
ON

ENCODED BY: Max C


D

TASK FORCE ENGINEERING, ASSESSMENT AND MONITORING


M
PE

NO

EN

MCMXCIX
&

IN
G
I

T
A

E N
E
R

ER
T

IN SM
A

A S SE S
T C
M U G ,

7x9m (STANDARD)
E

CHIEF, ARCHITECTURAL DIVISION


DE
TN

OIC, DIRECTOR III OIC, DIRECTOR IV


F O

UNDERSECRETARY

3
MERALCO AVENUE, PASIG CITY ARCHITECT IV
SHEET CONTENTS :
BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH CHECKED BY: PERSPECTIVE VIEW
8
0010990 149 460 161 DEPATMENT OF EDUCATION (DepED)
PRC NO. : TIN :
TABLE
PERSPECTIVE OF CONTENTS
VIEW
27 OCT. 2002
PTR NO. : DATE : LOCATION : DATE : TABLE OF CONTENTS
01 03

NOTE:
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF TASK FORCE ENGINEERING, ASSESSMENT AND
MONITORING AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


SUSPENDED
LIGHTING FIXTURES

6mm THK. PLYWOOD GA.#26 CORR. G.I.


12mm GI. PIPE HANGERS
CEILING ON 50X50mm ROOFING SHEET

CEILING JOIST SP. 1 (PAINT FINISH) 2 3


@600mm O.C.
GA.#26 CORR. G.I. ROOFING
C B A BOTHWAYS (PAINT
400 9000 400
SHEET (PAINT FINISH) FINISH)
1500 7000 4500 4500
TOP OF TRUSS
12x300mm FIBER CEMENT 3500 3500 1100

FASCIA BOARD (PAINT TOP OF TRUSS


FINISH)

1780
1780
300x300mm EXTERIOR
CONC. LOUVER BLOCKS
A B C GA#26 CORR. G.I.
ROOFING SHEET
TOP OF ROOF
BEAM
TOP OF ROOF BEAM
(PAINT FIN.)
7000 1500
GA#26 PLAIN G.I. 150mm THK. CHB

2800
1100 3500 3500 WALL PLASTER
12mm THK. FIBER CEMENT FLASHING (PAINT

2800
FIN.) PAINT FIN.
FASCIA BOARD (PAINT FIN.) TOP OF TRUSS

150 mm THK. CHB WALL WITH CLASSROOM W-1 W-1


CLASSROOM 1
FIN. FLR. LN.

VAR
CLASSROOM

1780
PLAIN CEMENT PLASTER
FIN. FLR. LINE
(PAINT FIN.) 300x300mm EXT.

VAR.
FIN. GRD. LN.
CONC. LOUVER
FIN. GRD. LN. TOP OF ROOF BLOCKS
BEAM
3 RIGHT ELEVATION 12x300mm FIBER CEMENT
7 LONGITUDINAL SECTION
FASCIA BOARD (PAINT FIN.)
A-2 SCALE: 1:100m
A-2

2800
SCALE: 1:100 M

CLASSROOM 150 mm THK. CHB WALL 1 2 3


FIN. FLR. LN. WITH PLAIN CEMENT

VAR.
1 2 3 PLASTER (PAINT FIN.) 9000
FIN. GRD. LN.
GA#26 G.I. PL. RIDGE 12x300mm FIBER
400 4500 4500
ROLL (PAINT FIN.) 9000 CEMENT FASCIA

GA#26 G.I. CORR. 400 4500 4500 400


4 LEFT ELEVATION BOARD (PAINT FIN.)
SHEET ROOFING
A-2

1100
SCALE: 1:100m
(PAINT FIN.)
TOP OF TRUSS
A
SUSPENDED
GA#26 G.I. PLAIN
LIGHTING
FLASHING (PAINT SLOPE
1780

FIXTURES
FIN.)

TOP OF ROOF BEAM 6mm THK. ORD. PLYWOOD


CEILING w/6mm GROOVE
1 2 3 ON 50x50mm CEILING
JOIST @600mm O.C. BOTH
WAYS
2800

6mm THK. CHB 9000


B

7000
PLASTER PAINT FIN.
400 4500 4500 400

D-1 D-1 GA#26 PL. GI. SHT.


CLASSROOM W-2 W-2 6mm THK. MARINE
RIDGE ROLL PAINT
VAR.

FIN. FLR. LN. TOP OF TRUSS PLYWOOD EXT. CLG. ON


FIN.
FIN. GRD. LN.
50x50mm @600mm OC
BW.
GA#26 G.I. CORR.

1780
SLOPE
SHT. ROOFING PAINT VENT.

2 FRONT ELEVATION TOP OF ROOF BEAM


FIN. (SEE DETAIL)
GA.#26 PL. G.I.

A-2 SCALE: 1:100 M FLASHING ON


12x300mm FIBER
C

1500
CEMENT FASCIA

2800
BOARD (PAINT FIN.)

1 2 3 CLASSROOM
W-1 W-1
150 mm THK. CHB

VAR.
FIN. FLR. LN. WALL WITH PLAIN
CEMENT PLASTER

400 4500
9000

4500
FIN. GRD. LN.
(PAINT FIN.) 8 REFLECTED CEILING PLAN
5 REAR ELEVATION A-2 SCALE: 1:100m

A-2 SCALE: 1:100 M


600

GRAVEL BED (RIVER STONE)


ROOF LINE ABOVE
1 2 GA#26 CORR. G.I.
3 GA#26 PLAIN G.I.
1100

ROOFING SHEET
RIDGE ROLL (PAINT
W-1 W-1
(PAINT FIN) FIN.)
A 9000

400 4500 4500 400


ROOF LINE
3500

1100
150mm THK. CHB
W/PLAIN CEMENT
A
BLACKBOARD

PLASTER (PAINT GA#26 PLAIN GI RIDGE

FIN.) CLASSROOM C B A ROLL (PAINT FIN.)


B
7000

FL-1 300x300mm EXT. CONC.


LOUVER BLOCKS

3500
7000
GA.#26 CORR. G.I. ROOFING
1500 3500 3500 1100
SHEET (PAINT FINISH)
SLOPE
TOP OF TRUSS
3500

6mm THK. PLYWOOD CEILING


7 50
00

7000
ON 50X50mm CEILING JOIST SP.
A-2 53
16
B
1780

@600mm O.C. BOTHWAYS (PAINT


D-1 D-1 FINISH)
W-2 W-2

C
TOP OF ROOF BEAM
SLOPE
25mm 25mm

3500
1200
1500

DEP.
6 CORRIDOR DEP.
12x300mm FIBER CEMENT
FL-1
A-2 LINE OF ROOF FASCIA BOARD (PAINT FIN.)
2800

W-1
200
600

GRAVEL BED (RIVER STONE) D-1 6mm THK MARINE PLYWOOD


CLASSROOM
C
ON 50x50mm CEILING JOIST
LINE OF CORRIDOR FIN. FLR. LN.
CLASSROOM @600mm O.C. BW.
VAR.

BUILDING LINE
(OPTIONAL)

1500
FIN. GRD. LN.
SCHEDULE OF FLOOR FIN. 150 mm THK. CHB WALL
1 FLOOR PLAN 6 CROSS SECTION WITH PLAIN CEMENT
PLAIN GREEN CEMENT FIN.
FL-1 PLASTER (PAINT FIN.)
A-2 SCALE: 1:100m
A-2 SCALE: 1:100 M
GA#26 PLAIN G.I. FLASHING

FL-2
PLAIN CEMENT FLR. ON 12x300mm FIBER CEMENT
9 ROOF PLAN
FIN. W/ GROOVE (ROUGH) FASCIA BOARD (PAINT FIN.)
A-2 SCALE: 1:100 M

CONSULTANT / DESIGNER REVIEWED BY: RECOMMENDING APPROVAL : APPROVED FOR ACCREDITATION : CONCURRED : PROJECT TITLE : PROJECT NO: 01-002 OWNER : SHEET NO:

REPUBLIC OF THE PHILIPPINES DESIGNED BY: AZB


E

ONE STOREY DEPARTMENT OF EDUCATION


A-2
t he PH F A
f
o IL
IC I

DEPARTMENT OF EDUCATION (DepED) A-1


T
M
L

P
B

TA
PU

I TO R I NG
IN

SK

EMMANUEL P. CUNTAPAY
RE

ES

SOFIA T. SANTIAGO GILBERTO S. REYES RAMON C. BACANI


DepED
F O RC E

ALBERT Z. DE BELEN
ONE CLASSROOM
ON

ENCODED BY: Max C


D

TASK FORCE ENGINEERING, ASSESSMENT AND MONITORING


M
PE

NO

EN

MCMXCIX
&

IN
G
I

T
A

E N
E
R

ER
T

IN SM
A

A S SE S
T C
M U G ,

7x9m (STANDARD)
E

CHIEF, ARCHITECTURAL DIVISION


DE
TN

OIC, DIRECTOR III OIC, DIRECTOR IV


F O

UNDERSECRETARY

3
MERALCO AVENUE, PASIG CITY ARCHITECT IV
SHEET CONTENTS :
BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH CHECKED BY: PERSPECTIVE VIEW
8
0010990 149 460 161 DEPATMENT OF EDUCATION (DepED)
PRC NO. : TIN :
TABLE
FLOOR, CEILING OF
& ROOF CONTENTS
PLANS
27 OCT. 2002
PTR NO. : DATE : LOCATION : DATE : ELEVATIONS & SECTIONS
01 03

NOTE:
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF TASK FORCE ENGINEERING, ASSESSMENT AND
MONITORING AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


20x20x5mm ANGULAR BAR @600mm OC NOTE:
2-16 BOLTS
VERT. MEMBER FOR FRAME OF 12x300mm 6mm THK PLYWOOD w/6mm 1. IF THERE'S EXTERIOR CEILING PROVIDE
900 FIBER CEMENT FASCIA BOARD GROOVE ON 50x50mm CEILING VENT
4 EQ. PARTS= 2 EQUAL PARTS = 600 V2.
1000 2500 NAILERS @600mm OC BW (SEE DETAIL)
1250 GA#26 CORR. ROOFING SHEET
25x25mm WOOD (PAINT FIN) 2. IF THERE'S NO EXTERIOR CEILING
VENT PROVIDE (PAINT FIN.)
PROVIDE V1.

300
INSECT SCREEN

1230 300

1230 300
SAG ROD (SEE DETAIL)

138
(14-BLADES)

(14-BLADES)
325 50
V1 TECK SCREW

555

25
275
STL. PURLINS (SEE STRUCTURAL
STAINLESS
10mm THICK PLATE
DET.)
STEEL 25x25 mm WOOD VENT
2400

2400

2400
KICKING PROVIDE INSECT SCREEN TECK SCREW
2100

2100

275
PALTE 6mm GROOVE
300x150x10mm BASE

1500
V2
PLATE

875

875
4-16x300mm LONG

300
6mm THK. ORD. CLNG. PLY BENT ANCHOR
FR. 25x75mm WD.FRAME CEILING ON 50X50 CLNG. BOLTS

300
50 25 25 25
S4S KD TANG. JOISTS SP. @600mm O.C. BW ( 425 12x300mm FIBER
PAINT FIN. ) VENTILLATION W/ CEMENT FASCIA

300
WIRE MESH 6mm THK. MARINE FULLY WELD BOARD
W-1 W-2 W-3 25
(OPTIONAL) PLYWOOD ON ON RAFTER
D-1 D-2
SECTION (V2)
50x50mm CLG. JST.

PANEL DOOR TYPE HINGED HOLLOW CORE FLUSH


JALOUSIE WINDOW W/ CLEAR GLASS
BLADES ON STD. ALUM. HOUSING &
SAME AS W-1 SAME AS W-1
/NO FIX
SECTION (V1) @600mm O.C. BW.
(OPTIONAL)
20x20x2mm ANGULAR
BAR FOR FASCIA BD.
DOOR & FIXED CLEAR TYPE HINGED DOOR FIXED CLEAR GLASS TRANSOMS ON GLASS FRAME WELDED TO
GLASS TRANSOM ON ON WOOD JAMBS/FRAMES 50x150mm WD. JAMBS/FRAMES 575 575 RAFTERS AND
50x150mm WOOD
JAMBS/FRAMES
PROVIDE KICKPLATE
6 EAVES, VENT. & INT CEILING DETAIL PURLINS

A-3 SCALE : AS SHOWN


DETAIL
2 SCHEDULE OF DOORS & WINDOWS

275
SCALE : 1:10MTS

A-3 SCALE: 1 : 100 M

25x25mm WOOD VENT


PLAN PROVIDE INSECT SCREEN

GA#26 CORR. G.I. 3 TYP. CLG. VENT PLAN DETAIL 600

ROOFING SHEET 300


A (PAINT FIN.) A-3 SCALE : 1 : 10 M

1242 GA#26 CORR. GI.


10mm SAG RODS
ROOF
GA#26 PLAIN
GI. FLASHING 27
1100

123
C-PURLIN SEE
LOUVER BLOCKS STRUCTURAL
(CONCRETE) DET.
C-PURLINS (SEE

600
STRUCTURAL DET.)

150
1500

4
GA#26 CORR. G.I. 7
ROOFING SHEET A-3
VENT. WITH
(PAINT FIN.)
WIRE MESH INSECT

23
SCREEN (SEE DETAIL) RAFTER SEE
SEE STRUCTURAL DETAIL
STRUCTURAL
TOP OF ROOF BEAM TOP OF ROOF BEAM INSIDE DET.

OUTSIDE
CONC. 6mm THK. ORD. PLYWOOD
ELEVATION
400

BEAM INT. CEILING ON50x50mm


12x300mm FIBER CEMENT
CEILING JOIST @600mm OC 20x20x5mm ANGULAR
FASCIA BOARD (PAINT (150X400)
BOTHWAYS (PAINT FIN.) BAR @600mm OC VERT.
FIN.) (OPTIONAL) (OPTIONAL)

SECTION MEMBER FOR FRAME OF

300
12x300mm FIBER
5 LOUVER BLOCKS DETAIL CEMENT FASCIA BOARD
400
6mm THK. MARINE 6mm THK. MARINE PLYWOOD
PLYWOOD ON 50x50mm CLG. JST. @600mm A-3 SCALE : 1:10M

O.C. BW. (OPTIONAL)


EAVES DETAIL
INT. CEILING w/6MM
GROOVE ON 50x50mm
12x300mm FIBER
7
CEILING JOIST @600mm CEMENT FASCIA
OC BOTHWAYS (PAINT BOARD (PAINT A-3 SCALE : 1:20M
FIN.) (OPTIONAL) FIN.)

W-1
2800

2800
2216
150mm THK. CHB WALL
PLAIN CEM. PLASTER (PAINT FIN.)
CLASSROOM
D-1 EL. +175mm 100
150 mm THK. CHB WALL WITH 100
TYPICAL
PLAIN CEMENT PLASTER (PAINT
FIN.)

RAMP UP

6mm
6mm

PART OF

1200
6mm
900

1500
CORRIDOR CORRIDOR NON-SKID

PART OF CLASSROOM PLAIN CE


MENT FL
OOR CEM
EMNT FINISH

CLASSROOM LINE OF ROOF


20x20x3mm THK ANGULAR

25
1800
FIN. FLOOR LINE FRAME FOR VENT. WELDED
FIN. FLOOR LINE LINE OF CORRIDOR
TO PURLINS
VAR.

VAR.
FIN. GRADE LINE
FIN. GRADE LINE
DETAIL SECTION
DETAIL PLAN SCALE 1:5 M

1500 SCALE 1:50 M

DETAIL SECTION 8 RAMP DETAILS


1 BAY SECTION 4
A-3 SCALE: 1:20 mts.
A-3 SCALE: AS SHOWN

A-3 SCALE: 1 : 20 M

CONSULTANT / DESIGNER REVIEWED BY: RECOMMENDING APPROVAL : APPROVED FOR ACCREDITATION : CONCURRED : PROJECT TITLE : PROJECT NO: 01-002 OWNER : SHEET NO:

REPUBLIC OF THE PHILIPPINES DESIGNED BY: AZB


E

ONE STOREY DEPARTMENT OF EDUCATION


A-3
t he PH F A
f
o IL
IC I

DEPARTMENT OF EDUCATION (DepED) A-1


T
M
L

P
B

TA
PU

I TO R I NG
IN

SK

EMMANUEL P. CUNTAPAY
RE

ES

SOFIA T. SANTIAGO GILBERTO S. REYES RAMON C. BACANI


DepED
F O RC E

ALBERT Z. DE BELEN
ONE CLASSROOM
ON

ENCODED BY: Max C


D

TASK FORCE ENGINEERING, ASSESSMENT AND MONITORING


M
PE

NO

EN

MCMXCIX
&

IN
G
I

T
A

E N
E
R

ER
T

IN SM
A

A S SE S
T C
M U G ,

7x9m (STANDARD)
E

CHIEF, ARCHITECTURAL DIVISION


DE
TN

OIC, DIRECTOR III OIC, DIRECTOR IV


F O

UNDERSECRETARY

3
MERALCO AVENUE, PASIG CITY ARCHITECT IV
SHEET CONTENTS :
BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH CHECKED BY: PERSPECTIVE VIEW
8
0010990 149 460 161 DEPATMENT OF EDUCATION (DepED)
PRC NO. : TIN :
TABLE
SCH. OF DOORS OF CONTENTS
& WINDOWS
27 OCT. 2002
PTR NO. : DATE : LOCATION : DATE : BAY & DETAIL SECTION, EAVES,
01 03
LOUVER BLK, VENT, RAMP DET.

NOTE:
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF TASK FORCE ENGINEERING, ASSESSMENT AND
MONITORING AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


1 2 3
1 2 3
9000

9000 50x100x15x1.5mm
400 4500 4500 400 STEEL C-PURLINS
750mm O.C.
4500 4500

1100
F-1 F-2 F-1
C-1 C-2 C-1
A
RG-1 RG-1
10mm% SAG ROD WITH
A STANDARD NUTS &
WF-1 WF-1
WASHERS @ EACH END

3500
3500

RG-2

RG-2
EB-1

EB-1
WF-1
WF-1
F-1 F-1

R - 1

R - 1
R - 2

R - 2
7000
C-1 C-1
B
7000
B 100mm THICK
SLAB ON FILL
WITH 10mm
SPACED AT 400

3500
WF-1
WF-1
3500

RG-2

RG-2
EB-1

EB-1
BOTHWAYS

F-1 F-2 F-1


C-2 C-1 RG-1 RG-1
C-1
C C
WF-1 WF-1

1500
1500

1200

RAMP UP

1800

A FOUNDATION PLAN B ROOF FRAMING PLAN


S-1 SCALE 1:100 M. S-1 SCALE 1:100 M.

150MM THK.
CHB

10@600
L
HOR. BARS

NGL NATURAL GRADE LINE


1

10@600
1800
VERT. BARS

600
D
Y-BARS 10 300mm TEMP
X-BARS BARS BOTHWAYS
W

150
t

250
Y-BARS

10mm

100
X-BARS

C O L U M N S C H E D U L E L 100 mm THICK
GRAVEL BEDDING
G-20mm GRAVEL 3-10mm

PLAN
BEDDING 10mm @300 CUT BARS
SECTION 400

LEVEL C-1 C-2 C TYP. FOOTING DETAIL E DETAIL OF RAMP


D DETAIL OF WF-1
SCALE 1 : 50M
S-1 SCALE : NTS
S-1 SCALE : NTS. S-1
400 400
160

160

DESIGN CRITERIA :

SCHEDULE OF FOOTINGS
A. CONCRETE
FOUNDATION LEVEL
LEVEL

fc' = 20.685 Mpa ( 3,000 Psi ), minimum compressive strength of concrete


FOOTING
FOOTING DIMENSIONS (mm) REINFORCEMENT
a 28 days unless otherwise specified.
MAIN BAR: MAIN BAR: REMARKS
MARK LENGTH WIDTH DEPTH THICKNESS B. REBAR
4-%16mm 6-%16mm BAR X BAR Y
(L) (W) (D) (t)
fy = 275.8 Mpa ( 40,000 Psi ), minimum yield strength of reinforcing bars
ROOF

TIES : 10 mm TIES : 10 mm
SQUARE FOOTING
unless otherwise specified.
1@50, 8@75, REST @ 1@50, 8@75, REST @ F-1 800 800 1200 250 4 - 16mm% 4 - 16mm%
150mm TO CENTER 150mm TO CENTER C. STRUCTURAL STEEL

F-2 1000 1000 1200 250 4 - 16mm% 4 - 16mm% SQUARE FOOTING


Fy = 248 Mpa ( 36 Ksi ), specified minimum yield strength
TO

unless otherwise specified.


D. FOUNDATION

SBP = 95.706 Kpa ( 2,000 Psf ), was used in the design for all footings.
No footing shall rest on fill.

CONSULTANT / DESIGNER REVIEWED BY: RECOMMENDING APPROVAL : APPROVED FOR ACCREDITATION : CONCURRED : PROJECT TITLE : PROJECT NO: 01-002 OWNER : SHEET NO:

REPUBLIC OF THE PHILIPPINES DESIGNED BY: AZB


IC
o
f t he PH
IL
I
F
E A

ONE STOREY DEPARTMENT OF EDUCATION


DEPARTMENT OF EDUCATION (DepED) A-1
T
M
L

P
B

TA
PU

I TO R I NG
IN

SK

EMMANUEL P. CUNTAPAY
RE

ES

SOFIA T. SANTIAGO GILBERTO S. REYES RAMON C. BACANI


DepED
F O RC E

ALBERT Z. DE BELEN
ONE CLASSROOM S-1
ON

ENCODED BY: Max C


D

TASK FORCE ENGINEERING, ASSESSMENT AND MONITORING


M
PE

NO

EN

MCMXCIX
&

IN
G
I

T
A

E N
E
R

ER
T

IN SM
A

A S SE S
T C
M U G ,

7x9m (STANDARD)
E

CHIEF, ARCHITECTURAL DIVISION


DE
TN

OIC, DIRECTOR III OIC, DIRECTOR IV


F O

ARCHITECT IV UNDERSECRETARY
MERALCO AVENUE, PASIG CITY SHEET CONTENTS :
BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH CHECKED BY: PERSPECTIVE VIEW 2
8
0010990 149 460 161 DEPATMENT OF EDUCATION (DepED)
PRC NO. : TIN : FOUNDATIONTABLE
PLAN, ROOF FRAMING PLAN
OF CONTENTS
PTR NO. : DATE :
27 OCT. 2002
LOCATION : DATE : 01 03
FOOTING DETAIL, COLUMN DETAIL, WF-1,
RAMP DET.
NOTE:
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF TASK FORCE ENGINEERING, ASSESSMENT AND
MONITORING AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


C B 1 A
S-
2

4-%16x300mm LONG
R- BENT ANCHOR BOLTS 65 65
2 1 2
R- E B- EB

20

20
-1 300x150x10mm 50
300

15
BASE PLATE

50 50

150

150
37.5
RG-1 RG-2 RG-2 RG-1

100
37.5
LINE OF R-1/R-2
2LC-150x65x20x3 LC-150x65x20x3
R-1 R-2 LC-100x50x15x1.5
10mm THICK PLATE
PLAN

E DETAIL OF RAfTER F DETAIL OF PURLINS


A ELEV @ GRID 1 & 3 2-%16
BOLTS 2-%16
S-2
SCALE NTS
S-2
SCALE NTS

BOLTS
S-2 SCALE: 1:100 M
4-%16x300mm
LONG BENT R-1/R-2
ANCHOR BOLTS

300x150x10mm 10mm THICK PLATE

C B A BASE PLATE
10mm THICK PLATE 4-%16x300mm LONG 100x50x15x1.5mm

BENT ANCHOR BOLTS STEEL C-PURLINS


750mm O.C.
R
-1
300x150x10mm /R
-2
BASE PLATE
R-
1 1
R- 1-%10mm A-307
ANCHOR BOLT

L-50x50x4.5
RC BEAM/COLUMN
RG-1 RG-1

R-2

ELEVATION
ELEVATION
EB-1 10mm X 150mm

TYPICAL RAFTER ANCHORAGE DETAIL (SEE SCHED) ANCHOR BOLTS


D SPACED @ 800mm O.C.

B ELEV BETWEEN GRIDLINES S-2 SCALE 1:20 M

S-2 SCALE: 1:100 M


1 SECTION DETAIL G PURLIN CONNECTION DET
SCALE 1:5M
SCALE NTS S-2
S-2

L1 L2

2D LAP SPLICES ARE ALLOWED 2D 2D LAP SPLICES ARE ALLOWED 2D

ONLY IN THIS PORTION ONLY IN THIS PORTION

100x50x15x1.5mm
2-10mm SIDE BARS
STEEL C-PURLINS
750mm O.C.

10mm% SAG ROD WITH


STANDARD NUTS &

C TYPICAL BEAM ELEVATION TOP OF RAFTER WASHERS @ EACH END

10mm TIE ROD WITH


S-2 STANDARD NUTS &
WASHERS @ EACH END
CL.
50x100x15x1.5mm
STEEL C-PURLINS
B E A M S C H E D U L E 150
150
750mm O.C.
R
-1
/R
-2
BEAM STEEL REINFORCEMENTS 10mm SAG ROD
FLOOR BEAM DIMENSIONS STIRRUPS
LEVEL MARK ( in / mm ) REBAR
LEFT MID SPAN RIGHT 10mm

(mm ) (UNLESS NOTED OTHERWISE)


b h TOP BOTTOM TOP BOTTOM TOP BOTTOM

RG-1 150 400 12mm 2 2 2 2 2 2 1@50, 8@100, REST@200


LEVEL

RG-2 150 400 12mm 2 2 2 2 2 2 1@50, 6@100, REST@200


ROOF

I SAG ROD CONNECTION DET.


EB-1 150 250 10mm 2 2 2 2 2 2 1@50, REST@200 H TIE ROD CONNECTION DET. SCALE 1 : 10 M
SCALE 1 : 10 M S-2
S-2

CONSULTANT / DESIGNER REVIEWED BY: RECOMMENDING APPROVAL : APPROVED FOR ACCREDITATION : CONCURRED : PROJECT TITLE : PROJECT NO: 01-002 OWNER : SHEET NO:

REPUBLIC OF THE PHILIPPINES DESIGNED BY: AZB


IC
o
f t he PH
IL
I
F
E A

ONE STOREY DEPARTMENT OF EDUCATION


DEPARTMENT OF EDUCATION (DepED) A-1
T
M
L

P
B

TA
PU

I TO R I NG
IN

SK

EMMANUEL P. CUNTAPAY
RE

ES

SOFIA T. SANTIAGO GILBERTO S. REYES RAMON C. BACANI


DepED
F O RC E

ALBERT Z. DE BELEN
ONE CLASSROOM S-2
ON

ENCODED BY: Max C


D

TASK FORCE ENGINEERING, ASSESSMENT AND MONITORING


M
PE

NO

EN

MCMXCIX
&

IN
G
I

T
A

E N
E
R

ER
T

IN SM
A

A S SE S
T C
M U G ,

7x9m (STANDARD)
E

CHIEF, ARCHITECTURAL DIVISION


DE
TN

OIC, DIRECTOR III OIC, DIRECTOR IV


F O

UNDERSECRETARY
2
MERALCO AVENUE, PASIG CITY ARCHITECT IV
SHEET CONTENTS :
BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH CHECKED BY: PERSPECTIVE VIEW
8
0010990 149 460 161 DEPATMENT OF EDUCATION (DepED)
PRC NO. : TIN :
TABLE OF CONTENTS
27 OCT. 2002 ELEVATIONS, BEAM DETAIL & SCHED.
PTR NO. : DATE : LOCATION : DATE : 01 03 TYPICAL CONNECTION DETAIL

NOTE:
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF TASK FORCE ENGINEERING, ASSESSMENT AND
MONITORING AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


GENERAL NOTES CALCULATIONS

1. ALL ELECTRICAL WORKS SHALL COMPLY IN ACCORDANCE WITH


1. TOTAL LOAD: 5. SCHEMATIC DIAGRAM OF SAFETY SWITCH:
THESE PLANS AND SPECIFICATIONS. THE APPLICABLE PROVISIONS

OF THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL CODE (PEC). A. LIGHTING OUTLET 5 x 100 W = 500 W
2

THE RULES AND REGULATION OF THE LOCAL ENFORCING AUTHORITY 3.5 mm THW WIRE
B. FAN OUTLET 1 x 100 W = 100 W
AND THE REQUIREMENTS OF THE LOCAL POWER COMPANY.

ALL ELECTRICAL WORKS SHALL BE UNDER THE IMMEDIATE SUPERVISION C. CONVENIENCE OUTLET 2 x 180 W = 360 W

OF A DULY REGISTERED ELECTRICAL ENGINEER.

TOTAL LOAD = 960 W


2. THE ELECTRICAL SERVICE POWER IS 1-PHASE, 2-WIRE,
230 V AC, 60 Hz.
I LOAD 960 / 230 = 4.17 A
3. WIRING METHOD SHALL BE AS FOLLOWS :

a. FEEDERS AND RISERS - RIGID METALLIC CONDUIT

b. LIGHTING, POWER RECEPTACLE - POLYVINYL CHLORIDE CONDUIT


2. CIRCUIT REQUIREMENT:
BRANCH CKT., & AUXILIARY SCH. 40
2

3.5 mm THW COPPER WIRE


4. ALL WIRES SHALL BE COPPER AND THERMOPLASTIC INSULATED TYPE USE 20 A 2-WIRE CIRCUIT

"THW" UNLESS OTHERWISE INDICATED IN THE PLAN. THE MINIMUM

SIZE OF WIRE FOR POWER AND LIGHTING CIRCUIT HOMERUN SHALL BE


3. SERVICE ENTRANCE CONDUCTORS:
2
3.5mm AND INSULATED FOR 600 VOLTS. SMALLEST RACEWAY SHALL

BE 15mmO TRADE/NOMINAL SIZE. USE 2-3.5 mm


2

THW COPPER WIRES


I

5. ALL OUTLET BOXES SHALL BE GALVANIZED GAGE NO. 16 DEEP


TYPE WITH FACTORY KNOCKOUTS.
4. SERVICE EQUIPMENT:

6. ALL MATERIALS TO BE USED SHALL BE BRAND NEW AND APPROVED


TYPE FOR THE PARTICULAR LOCATION AND PURPOSE. USE 1-30 A, 2PST, 250V SAFETY SWITCH WITH 2-20 A, RENEWABLE FUSES

7. GROUNDING SYSTEM SHALL BE PROVIDED TO ALL LIGHTING AND


POWER CIRCUIT AS PER PHILIPPINE ELECTRICAL CODE REQUIREMENT.

8. MOUNTING HEIGHT OF WIRING DEVICES SHALL BE AS FOLLOWS :

a. LIGHT SWITCH - 1.20 M ABOVE FINISH FLOOR

b. CONVENIENCE OUTLET - 0.30 M ABOVE FINISH FLOOR.

c. SAFETY SWITCH - 1.80 M ABOVE FINISH FLOOR

1 2 3
OVERHEAD SERVICE ENTRANCE
CONNECTED TO 220V AC, 1O,
2 WIRE, 60 Hz FITTED WITH
20mm O TYPE "F" CONDULET

LEGEND
SYMBOL DESCRIPTION
C
- CEILING LIGHT OUTLET CEILING LINE

BUILDING WALL
2
- 2 x 40 WATTS FLUORESCENT LAMP a b
METERING CONDUIT

- CEILING FAN OUTLET


2
F 2-3.5mm THW
2 2
KWHR METER IN 20mmORSC

S/Sa - ONE GANG DEVICE SWITCH CLASSROOM

3500 mm
S ab - TWO GANG DEVICE SWITCH B F

S cde - THREE GANG DEVICE SWITCH

1800 mm

1800 mm
a b
S
3W - THREE WAY DEVICE SWITCH
2 2

Sf - FAN CONTROL SWITCH

GROUND FLOOR LINE

- RACEWAY CONDUIT CONCEALED IN CEILING Sf

A
Sabc
M
FIN. GRADE LINE
- RACEWAY CONDUIT CONCEALED UNDER FLOOR
2
1-3.5mm THW COPPER WIRE
IN 15mmO C

c
16MMO x 2400mm LENGTH

- SAFETY SWITCH
GROUNDING ROD COPPERWELD

OVERHEAD SERVICE ENTRANCE


REFER TO RISER DIAGRAM

- DUPLEX CONVENIENCE OUTLET, GROUNDING TYPE

10 AMPS, 250 VOLT WITH MODERN PLATE COVER

M
- ELECTRIC SERVICE METER

- SERVICE ENTRANCE
ELECTRICAL RISER DIAGRAM ELECTRICAL LAYOUT
NOT TO SCALE SCALE 1:100 M

CONSULTANT / DESIGNER REVIEWED BY: RECOMMENDING APPROVAL : APPROVED FOR ACCREDITATION : CONCURRED : PROJECT TITLE : PROJECT NO: 99-001 OWNER : SHEET NO:

REPUBLIC OF THE PHILIPPINES DESIGNED BY: RDS


IC
o
f t he PH
IL
I
F
E A

ONE STOREY DEPARTMENT OF EDUCATION


DEPARTMENT OF EDUCATION (DepED) A-1
T
M
L

P
B

TA
PU

I TO R I NG
IN

SK

EMMANUEL P. CUNTAPAY
RE

ES

SOFIA T. SANTIAGO GILBERTO S. REYES RAMON C. BACANI


DepED
F O RC E

ALBERT Z. DE BELEN
ONE CLASSROOM E-1
ON

ENCODED BY: RDS


D

TASK FORCE ENGINEERING, ASSESSMENT AND MONITORING


M
PE

NO

EN

MCMXCIX
&

IN
G
I

T
A

E N
E
R

ER
T

IN SM
A

A S SE S
T C
M U G ,

7x9m (STANDARD)
E

CHIEF, ARCHITECTURAL DIVISION


DE
TN

OIC, DIRECTOR III OIC, DIRECTOR IV


F O

ARCHITECT IV UNDERSECRETARY
MERALCO AVENUE, PASIG CITY SHEET CONTENTS :
BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH CHECKED BY: CALCULATIONS
PERSPECTIVE VIEW 1
8
0010990 149 460 161 DEPATMENT OF EDUCATION (DepED)
PRC NO. : TIN :
TABLE OF
GENERAL NOTES CONTENTS
LEGEND
27 OCT. 2002
PTR NO. : DATE : LOCATION : DATE : 5-5-00 ELECTRICAL LAYOUT RISER DIAGRAM

NOTE:
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF TASK FORCE ENGINEERING, ASSESSMENT AND
MONITORING AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


REPUBLIC OF THE PHILIPPINES

TABLE OFFICE OF THE CITY/MUNICIPAL


ENGINEER/BUILDING OFFICIAL

OF
CONTENTS
DISTRICT/CITY/MUNICIPALITY

ARCHITECTURAL
LAND USE & ZONING
A-1 PERSPECTIVE VIEW, TABLE OF CONTENTS

A-2 FLOOR PLAN, ELEVATIONS, ROOF PLAN


SECTIONS, REFLECTED CEILING PLAN

A-3 SCHEDULE OF DOOR & WINDOWS, BAY


SECTION, DETAIL SECTION, LOUVER LINE & GRADE
BLOCK VENT., RAMP DETAIL

ARCHITECTURAL

1 PERSPECTIVE VIEW
A-1 SCALE: NTS

STRUCTURAL

S-1 FOUNDATION PLAN, ROOF FRAMING


PLAN FOOTING DETAIL, COLUMN DETAIL, STRUCTURAL
WF-1, RAMP DETAIL

S-2 ELEVATIONS TYPICAL CONNECTION


DETAIL

SANITARY

ELECTRICAL
E-1 ELECTRICAL LAYOUT PLAN, RISER
DIAGRAM, LOAD SCHEDULE, GEN. NOTES

ELECTRICAL

SANITARY

MECHANICAL

REPUBLIC OF THE PHILIPPINES PREPARED BY : CHECKED BY : RECOMMENDING APPROVAL : APPROVED BY : PROJECT TITLE : PROJECT NO: 00200511 OWNER : SHEET NO:

DESIGNED BY: NQM


EMEC
AMA
VDS II
ONE STOREY DEPARTMENT OF EDUCATION
TWO CLASSROOM ENCODED BY: Max C.
VDS DepED A -1
S
AN
D SCHO
OL
DEPARTMENT OF EDUCATION MAXIMO M. CALBANG NATHANIEL Q. MENDOZA LUIS G. PURISIMA JR. OLIVER R. HERNANDEZ 7x9m (MODIFIED) CHECKED BY: LGP
SHEET CONTENTS :
S
IE

3
ENG
FAC IL IT

PERSPECTIVE VIEW
PHYSICAL FACILITIES AND SCHOOLS ENGINEERING DIVISION
INEERING D

PDO - III ARCHITECT III HEAD, PLANNING AND DESIGN UNIT CHIEF, PFSED-OPS
AL

TABLE OF CONTENTS
IC

IV

PFSED-DepED PFSED-DepED DepED


SI
I

YS

MERALCO AVENUE, PASIG CITY PFSED-DepED 01 01 2005


ON
LOCATION : DATE :
PH
De ED
p

NOTE:
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF PHYSICAL FACILITIES AND SCHOOLS ENGINEERING
DIVISION AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


GA.#26 CORR. G.I. ROOFING
C B A 1
5 4
1
3 2 1 1
1
1
2
1
2 3
1
3 4
1
5
1
A-1 A-1 A-1 A-1 A-1 A-1 A-1
SHEET (PAINT FINISH) GA#26 G.I. PL. 18000
SEE STRUCTURAL 18000
1500 7000 RIDGE ROLL
400 4500 4500 4500 4500 400
3500 3500 1100 APEX OF ROOF PAINT FIN. DETAIL 400 4500 4500 4500 4500 400
12x300mm FIBER CEMENT
FASCIA BOARD (PAINT FINISH) APEX OF ROOF 4.8mm THK. FIBER CEMENT APEX OF ROOF
CEILING BOARD ON 50x50mm

2026
GA#26 G.I. CORR.
CEILING JOIST @600mm OC BW

2026
300x300mm EXTERIOR CONC.

2026
SHEET ROOFING SLOPE
LOUVER BLOCKS PAINT FINISH
TOP OF ROOF BEAM PAINT FIN.
VENT. SEE DETAIL
TOP OF TOP OF BEAM

12mm THK. FIBER CEMENT ROOF BEAM


100mm THK.

2800
FASCIA BOARD (PAINT FIN.) CHB WALL PLAIN
150mm THK. CHB WALL

2800
2800
100mm THK. CHB WALL PLAIN CEMENT PLASTER w/PLAIN CEMENT PLASTER
CLASSROOM & PAINT FIN.
CEMENT PLASTER & PAINT FIN. & PAINT FIN.
FIN. FLR. LINE

VAR.
CLASSROOM W W W W W-1 W-1 W-1 W-1

150
100mm THK. CONCRETE FIN. FLOOR LINE
100mm THK. CHB WALL WITH

PLAIN CEMENT PLASTER (PAINT

FIN. FLR. LN.


FIN.)

FIN. GRD. LN. 1 1 1 1

150.
SLAB
NGL
3 RIGHT ELEVATION FIN. GRD. LN.
50-100mm GRAVEL
2 FRONT ELEVATION BEDDING LONGITUDINAL SECTION
A-2 SCALE: 1:100m
7
FROM SELECTED FILLING
A-2 SCALE: 1:100m
A-2 SCALE: 1:100m
MATERIAL

1 1 1 1 1

1 1
1
A-1 2
A-1 3
A-1 4
A-1 5
A-1

1 2 3 4
A-1 5
A-1 A B C 18000
GA.#26 CORR. G.I. ROOFING
GA#26 G.I. PL. 18000 4500 4500 4500 4500
RIDGE ROLL SHEET (PAINT FINISH)
400 4500 4500 4500 4500 400
7000 1500
PAINT FIN.
APEX OF ROOF 1100 3500 3500
APEX OF ROOF
12x300mm FIBER CEMENT

1100
FASCIA BOARD (PAINT FINISH)
GA#26 G.I. CORR.
A

2026
2026

SHEET ROOFING SLOPE


300x300mm EXTERIOR CONC.
PAINT FIN.
TOP OF ROOF BEAM LOUVER BLOCKS GA#26 CORR. G.I.
TOP OF SHEET ROOFING PAINT

3500
ROOF BEAM FINISH
100mm THK. 12mm THK. FIBER CEMENT

2800
CHB WALL PLAIN
FASCIA BOARD (PAINT FIN.) SLOPE
2800

CEMENT PLASTER
& PAINT FIN. CLASSROOM
100mm THK. CHB WALL PLAIN GA#26 PLAIN G.I.
B

9600
CLASSROOM D
W
D D
W
D CEMENT PLASTER & PAINT FIN. SHEET RIDGE ROLL
W W FIN. FLR. LINE

VAR.
1 1 1 1
FIN. FLR. LN. 2 2 PAINT FINISH
150.

2 2
100mm THK. CHB WALL WITH

PLAIN CEMENT PLASTER (PAINT


FIN.)

FIN. GRD. LN.


FIN. GRD. LN. 12mm THK. FIBER SLOPE

FRONT ELEVATION 4 LEFT ELEVATION

3500
CEMENT FASCIA BOARD
2 PAINT FINISH
A-2 SCALE: 1:100m
A-2 SCALE: 1:100m

1500
2 2 2 2
1 2
A-1 3
A-1 4
A-1 5
A-1

18000 9 ROOF PLAN


4500 4500 4500 4500 A-2 SCALE: 1:100mm

1 1 1 1 1

W
50-100mm RIVER STONE TRENCH

W
1
A-1 2
A-1 3
A-1 4
A-1 5
A-1
W W
1100

GA#26 PLAIN GI RIDGE ROLL


1 1 C C C
1 1
C
A-1 B
A-1 A
A-1
PAINT FINISH 18000

A 300x300mm EXT. CONCRETE


LOUVER BLOCKS
4500 4500 4500 4500

7000
GA#26 CORR. GI ROOFING
1500 3500 3500 1100
SHEET PAINT FINISH
APEX OF ROOF

1100
3500

100mm THK. CHB WALL 4.8mm THK. FIBER CEMENT CEILING BOARD
PLASTER & PAINT FINISH
50 ON 50x50mm CEILING JOIST @600mm OC VENT. (SEE DETAIL)
A
.

29 00 BOTHWAYS PAINT FINISH


54
2026

VENTILATION (SEE DETAIL)


RAFTER/PURLINS SEE DETAIL
7000

BLACKBOARD

BLACKBOARD

TOP OF ROOF BEAM

B CLASSROOM CLASSROOM LIGHTING FIXTURE

3500
12x300mm FIBER CEMENT
EL. 150mm EL. 150mm 2 2 2 2 2 2

FIN.: PLAIN CEMENT FIN. FIN.: PLAIN CEMENT FIN. FASCIA BOARD PAINT FINISH

W 4.8mm THK. FIBER CEMENT CEILING 12mm THK. FIBER


3000

BOARD ON 50x50mm CLG. JST. CEMENT FASCIA BOARD


3500

D 1
@600mm OC BW PAINT FIN. PAINT FINISH
7 1

1 B

9600
A-2 CLASSROOM 100mm THK CHB WALL w/PLAIN
W W W W CEMENT PLASTER PAINT FINISH
FIN. FLR. LN. 4.8mm THK. FIBER
2 2 2 2 CLASSROOM
150

100mm THK. CONCRETE SLAB ON FILL CEMENT EXTERIOR &


FIN. GRD. LN.
C
100mm THK. 50-100mm GRAVEL BED INTERIOR CEILING

3500
FROM SELECTED COMPACT 2 2 2 2 2 2
CORRIDOR BOARD ON METAL OR
1500
1200

EL. 125mm FILLING MATERIAL


RAMP UP SOLID WOOD CEILING
FIN.: PLAIN CEMENT FIN. 6 CROSS SECTION JOIST @600mm OC
SCALE : 1:100 m. BW PAINT FINISH
600

6 50-100mm RIVER STONE TRENCH A-2


1
A-2
C A-1

1500
1 FLOOR PLAN
SCHED. OF FLOOR FIN.
A-2 1:100m

FL-1 PLAIN CEMENT


FLOOR FIN.

FL-2
PLAIN CEMENT FLR. 1 REFLECTED CEILING PLAN
FIN. W/ GROOVE (ROUGH)
A-2 SCALE: 1:100m

REPUBLIC OF THE PHILIPPINES PREPARED BY : CHECKED BY : RECOMMENDING APPROVAL : APPROVED BY : PROJECT TITLE : PROJECT NO: 00200511 OWNER : SHEET NO:

DESIGNED BY: NQM


EMEC
AMA
VDS II
ONE STOREY DEPARTMENT OF EDUCATION
TWO CLASSROOM ENCODED BY: Max C.
VDS DepED A -2
S
AN
D SCHO
OL
DEPARTMENT OF EDUCATION MAXIMO M. CALBANG NATHANIEL Q. MENDOZA LUIS G. PURISIMA JR. OLIVER R. HERNANDEZ 7x9m (MODIFIED) CHECKED BY: LGP
SHEET CONTENTS : FLOOR, REFLECTED CLG., ROOF
S
IE

3
ENG
FAC IL IT

PHYSICAL FACILITIES AND SCHOOLS ENGINEERING DIVISION PLANS,FRONT, RIGHT, REAR,


INEERING D

PDO - III ARCHITECT III HEAD, PLANNING AND DESIGN UNIT CHIEF, PFSED-OPS
AL

LEFT ELEVATIONS, CROSS,


IC

IV

PFSED-DepED PFSED-DepED DepED


SI
I

YS

MERALCO AVENUE, PASIG CITY PFSED-DepED 01 01 2005


ON
LOCATION : DATE :
PH
De ED
p

LONGITUDINAL SECTIONS
NOTE:
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF PHYSICAL FACILITIES AND SCHOOLS ENGINEERING
DIVISION AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


2-16 BOLTS
6mm THK PLYWOOD w/6mm
GROOVE ON 50x50mm NAILERS

@600mm OC BW (PAINT FIN) GA#26 CORR. ROOFING SHEET


(PAINT FIN.)
SAG ROD (SEE DETAIL)

TECKSCREW
1000 4 EQ. PARTS= 2 EQUAL PARTS =
STL. PURLINS (SEE STRUCTURAL DET.)
2500 1250 10mm THICK PLATE
TECKSCREW
6mm GROOVE

300

300

300

275
300x150x10mm BASE
PLATE
25x25 mm WOOD VENT

(14-BLADES)

(14-BLADES)
PROVIDE INSECT SCREEN
4-16x300mm LONG VENTILLATION W/ WIRE

1230

1230
BENT ANCHOR BOLTS MESH

300
2400

2400

2400
12x300mm FIBER
2100

CEMENT FASCIA BOARD

300
FULLY WELD ON
RAFTER

875

875
ELEV 20x20x2mm ANGULAR
BAR FOR FASCIA BD.
FFL
5 EAVES DETAIL FRAME WELDED TO
RAFTERS AND PURLINS
575 575
SCALE: 1:20mts
D-1 W-1 W-2 A-3

HOLLOW CORE FLUSH TYPE HINGED DOOR


JALOUSIE WINDOW W/ CLEAR GLASS BLADES ON STD. ALUM. SAME AS W-1

ON 50x100mm WOOD JAMBS/FRAMES HOUSING & FIXED CLEAR GLASS TRANSOMS ON 50x100mm WD.

275
JAMBS/FRAMES

1 DOOR & WINDOW SCHEDULE


A-3 SCALE: 1:50m
25x25mm WOOD VENT
PLAN PROVIDE INSECT SCREEN

600

4 TYP. CLG. VENT. DETAILS 300

A A-3 SCALE: 1:10 mts.


GA#26 CORR. GI.
C GA#26 PLAIN
ROOF

GI. FLASHING 27

1100 123
1500 C-PURLIN SEE
STRUCTURAL DET.
5
LOUVER BLOCKS (CONCRETE)
A-3

600

150
23

4
GA 26 G.I. CORR. SHEET ROOFING
TOP OF ROOF BEAM
TOP OF ROOF BEAM PAINT FINISH

GA#26 CORR. G.I. SHT. LC 100x50x15x1.5mm STL


ROOF (PAINT FIN.)
400

CONC. C-PURLINS @750mm OC ON RAFTER SEE


BEAM 2-LC 150x65x20x2mm RAFTER STRUCTURAL DET.
6mm THK. ORD. PLYWOOD INSIDE
INT. CEILING w/6MM GROOVE ON
OUTSIDE
50x50mm CEILING JOIST @600mm
ELEVATION

300
OC BOTHWAYS
10mmSAG ROD
12x300mm FIBER CEMENT
RAFTER (SEE STRUCT'L DET.)
FASCIA BOARD ON 20x20x2mm

CEILING VENTILATION SEE


SECTION ANGLE BAR FRAME W/ VERT.
MEMBER @ 600mm OC
12x300mm FIBER CEMENT 6mm THK. ORDINARY PLYWOOD
FASCIA BOARD ON 25x25x6mm
DETAIL
CEILING w/6mm GROOVE ON
12x300mm FIBER CONCRETE FASCIA
BOARD ON 25x25x6mm L-BAR
6 LOUVER BLOCK DETAIL 400
THK L-BAR w/25x6mm THK 50x50mm CEILING JOIST @600mm
STIFF FLAT BAR @600mm OC OC BW (PAINT FINISH) W/25x6mm THK STIFFENER FLAT BAR @
EVERY 600mm OC
A-3 SCALE: 1:10 mts.

BW. PAINT FIN.


7 EAVES DETAIL
W-1

2800
2800

CEILING VENTILLATION (SEE A-3 SCALE : 1:20M


DETAIL)
100 mm THK. CHB WALL WITH

PLAIN CEMENT PLASTER (PAINT FIN.)

2216
D-1

CLASSROOM
EL. +175mm
PART OF 100
100
C
800

CLASSROOM
TYPICAL

PART OF CORRIDOR

6mm
6mm
CLASSROOM 6mm

1500

UP
1200
CORRIDOR

25
FIN. FLOOR LINE NON-SK
FL-2 ID PLAIN

RAMP
CEMENT
FLOOR
CEMEMN

VAR.
T FINISH
VAR.

150
FIN. GRADE LINE

LINE OF CORRIDOR
POLYETHYLENE SHEET DAMP POLYETHYLENE SHEET DAMP
PROOFING PROOFING 1800
100mm THK. REINF. CONC 100mm THK. REINF. CONC DETAIL SECTION
SLAB SLAB
1500 DETAIL PLAN SCALE 1:5 M
100mm THK 50-100mm 100mm THK 50-100mm SCALE 1:50 M
GRAVEL BED GRAVEL BED

FR. SELECTED FILLING


PLAN
FR. SELECTED FILLING
1 PLAN MATERIALS MATERIALS 2 8 RAMP DETAILS
A-3 SCALE: 1:100m
A-3 SCALE: 1:100m
A-3 SCALE: AS SHOWN

REPUBLIC OF THE PHILIPPINES PREPARED BY : CHECKED BY : RECOMMENDING APPROVAL : APPROVED BY : PROJECT TITLE : PROJECT NO: 00200511 OWNER : SHEET NO:

DESIGNED BY: NQM


EMEC
AMA
VDS II
ONE STOREY DEPARTMENT OF EDUCATION
TWO CLASSROOM ENCODED BY: Max C.
VDS DepED A -3
S
AN
D SCHO
OL
DEPARTMENT OF EDUCATION MAXIMO M. CALBANG NATHANIEL Q. MENDOZA LUIS G. PURISIMA JR. OLIVER R. HERNANDEZ 7x9m (MODIFIED) CHECKED BY: LGP
SHEET CONTENTS : DOOR & WINDOW SCHEDULE
S
IE

3
ENG
FAC IL IT

DETAILS
PHYSICAL FACILITIES AND SCHOOLS ENGINEERING DIVISION
INEERING D

PDO - III ARCHITECT III HEAD, PLANNING AND DESIGN UNIT CHIEF, PFSED-OPS
AL
IC

IV

PFSED-DepED PFSED-DepED DepED


SI
I

YS

MERALCO AVENUE, PASIG CITY PFSED-DepED 01 01 2005


ON
LOCATION : DATE :
PH
De ED
p

NOTE:
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF PHYSICAL FACILITIES AND SCHOOLS ENGINEERING
DIVISION AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


1 2 3
18000

4500 13500
4500 4500
1 2 3
9000 9000

1100
4500 4500 4500 4500
RG-1 RG-1 RG-1 RG-1
F-1
C-1
F-2
C-2
F-1
C-1
F-2
C-2
F-1 A
C-1

A WF-1 WF-1 WF-1 WF-1


10mm SAG ROD

w/STANDARD NUTS &

3500

RG-2

RG-2

RG-2
EB-1

EB-1

EB-1
WASHERS @ END
3500

WF-1
WF-1

WF-1

R - 1

R - 1

R - 1

R - 1
R - 2

R - 2

R - 2
7000
F-1 F-1 F-1 B
C-1 C-1 C-1
7000

100mm THK. SLAB ON FILL ON


B 100mm THK. GRAVEL FILL
50x100x15x1.5mm
COMPACTED 95w/SELECTED

3500

RG-2

RG-2

RG-2
STEEL PURLINS

EB-1

EB-1

EB-1
FILLING MATERIALS
@750 O.C.
3500

WF-1
WF-1

WF-1
RG-1 RG-1 RG-1 RG-1

F-1
C-1
F-2
C-2
F-1
C-1
F-2
C-2
F-1
C-1
C

1500
C
RAMP UP

WF-1 WF-1 WF-1 WF-1


1500

1200

1800
B ROOF FRAMING PLAN
A FOUNDATION PLAN S-1 SCALE: 1:100m

S-1 SCALE: 1:100m

C B 1 A C B 2 A C B A
S- S-
2 3

R- R- R-
2 1 2 2 1 2 1 1
R- EB
- EB R- EB
- EB R-
- -
1 1

RG-1 RG-2 RG-2 RG-1 RG-1 RG-2 RG-2 RG-1 RG-1 RG-1

C O L U M N S C H E D U L E

LEVEL C-1 C-2 C ELEV END GRID D ELEV PARTITION GRID E ELEV BETWEEN GRID
S-1 SCALE: 1:100m
S-1 SCALE: 1:100m
S-1 SCALE: 1:100m

300 400

DESIGN CRITERIA :
200

200

S C H E D U L E O F F O O T I N G S
A. CONCRETE
FOUNDATION LEVEL
LEVEL

fc' = 20.685 Mpa ( 3,000 Psi ), minimum compressive strength of concrete


FOOTING
FOOTING DIMENSIONS (mm) REINFORCEMENT
a 28 days unless otherwise specified.
MAIN BAR: MAIN BAR: REMARKS
MARK LENGTH WIDTH DEPTH THICKNESS B. REBAR
4-%16mm 6-%16mm BAR X BAR Y
(L) (W) (D) (t)
fy = 275.8 Mpa ( 40,000 Psi ), minimum yield strength of reinforcing bars
ROOF

TIES : 10 mm TIES : 10 mm
1@50, 8@75, REST @ 1@50, 8@75, REST @ F-1 800 800 1200 250 4 - 16mm% 4 - 16mm% SQUARE FOOTING unless otherwise specified.
150mm TO CENTER 150mm TO CENTER C. STRUCTURAL STEEL

F-2 1000 1000 1200 250 4 - 16mm% 4 - 16mm% SQUARE FOOTING


Fy = 248 Mpa ( 36 Ksi ), specified minimum yield strength
TO

unless otherwise specified.


D. FOUNDATION

SBP = 95.706 Kpa ( 2,000 Psf ), was used in the design for all footings.
No footing shall rest on fill.

REPUBLIC OF THE PHILIPPINES PREPARED BY : CHECKED BY : RECOMMENDING APPROVAL : APPROVED BY : PROJECT TITLE : PROJECT NO: 00200511 OWNER : SHEET NO:

DESIGNED BY: NQM


EMEC
AMA
VDS II
ONE STOREY DEPARTMENT OF EDUCATION
TWO CLASSROOM ENCODED BY: Max C.
VDS DepED S -1
S
AN
D SCHO
OL
DEPARTMENT OF EDUCATION MAXIMO M. CALBANG ANTONIA M. ALHAMBRA LUIS G. PURISIMA JR. OLIVER R. HERNANDEZ 7x9m (MODIFIED) CHECKED BY: LGP
SHEET CONTENTS :
S
IE

FOUNDATION PLAN, ROOF FRAMING PLAN


2
ENG
FAC IL IT

PHYSICAL FACILITIES AND SCHOOLS ENGINEERING DIVISION


INEERING D

PDO - III
CIVIL ENGINEER/MASTER PLUMBER HEAD, PLANNING AND DESIGN UNIT CHIEF, PFSED-OPS
FOOTING DETAIL, COLUMN DETAIL, WF-1,
AL
IC

IV

PFSED-DepED PFSED-DepED DepED


SI
I

YS

MERALCO AVENUE, PASIG CITY PFSED-DepED 01 01 2005


ON
LOCATION : DATE :
PH
De ED
p
RAMP DET.
NOTE:
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF PHYSICAL FACILITIES AND SCHOOLS ENGINEERING
DIVISION AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


4-%16x300mm LONG
BENT ANCHOR BOLTS
65 65

20

20
300x150x10mm
300 BASE PLATE
50 50
100mm THK.

37.5
CHB

150

150
50

37.5
10@600

15
HOR. BARS

1 2LC-150x65x20x3 LC-150x65x20x3
NATURAL GRADE LINE
LINE OF R-1/R-2

100
R-1 R-2
10@600 10mm THICK PLATE
PLAN
VERT. BARS 1800

E DETAIL OF RAfTER
600

10 300mm TEMP
BARS BOTHWAYS
SCALE NTS LC-100x50x15x1.5
S-2

150
F DETAIL OF PURLINS
250

10mm SCALE NTS


S-2
G-20mm GRAVEL 3-10mm
BEDDING 10mm @300 CUT BARS
400

D DETAIL OF WF-1 E DETAIL OF RAMP


2-%16
SCALE 1 : 50M
S-1 SCALE : NTS. S-1 BOLTS 100x50x15x1.5mm
2-%16 STEEL C-PURLINS
BOLTS 750mm O.C.

R-2
4-%16x300mm
L
LONG BENT R-1/R-2 10mm THICK PLATE
ANCHOR BOLTS 1-%10mm A-307

10mm X 150mm ANCHOR BOLT


NGL 4-%16x300mm LONG EB-1
ANCHOR BOLTS
300x150x10mm BENT ANCHOR BOLTS (SEE SCHED)
BASE PLATE
R- SPACED @ 800mm O.C. L-50x50x4.5

10mm THICK PLATE 1/


300x150x10mm R- 1:20 M
2
BASE PLATE

1 SECTION DETAIL
D

Y-BARS

X-BARS
W

SCALE NTS
S-2
t

Y-BARS

RC BEAM/COLUMN
100

X-BARS

PURLIN CONNECTION DET


100 mm THICK
G
L
GRAVEL BEDDING
ELEVATION
PLAN SECTION SCALE 1 : 5 M

ELEVATION
S-2
C TYP. FOOTING DETAIL
S-1 SCALE :
D TYPICAL RAFTER ANCHORAGE DETAIL
SCALE
S-2

L1 L2
NTS

2D LAP SPLICES ARE ALLOWED 2D 2D LAP SPLICES ARE ALLOWED 2D

ONLY IN THIS PORTION ONLY IN THIS PORTION

100x50x15x1.5mm
STEEL C-PURLINS
750mm O.C.

10mm% SAG ROD WITH


2-10mm SIDE BARS
STANDARD NUTS &
TOP OF RAFTER WASHERS @ EACH END

10mm TIE ROD WITH


STANDARD NUTS &
WASHERS @ EACH END
C TYPICAL BEAM ELEVATION CL.
50x100x15x1.5mm
S-2 STEEL C-PURLINS
150
150
750mm O.C. R-
1/
R-
2
10mm SAG ROD
B E A M S C H E D U L E

BEAM S T E E L R E I N F O R C E M E N T S
FLOOR BEAM DIMENSIONS S T I R R U P S
( in / mm ) LEFT MID SPAN RIGHT
LEVEL MARK REBAR 10mm

(mm ) (UNLESS NOTED OTHERWISE)


b h TOP BOTTOM TOP BOTTOM TOP BOTTOM

RG-1 150 400 12mm 2 2 2 2 2 2 1@50, 8@100, REST@200


LEVEL

RG-2 150 400 12mm 2 2 2 2 2 2 1@50, 6@100, REST@200 I SAG ROD CONNECTION DET.
H TIE ROD CONNECTION DET. SCALE 1 : 10 M
SCALE 1 : 10 M S-2
S-2
ROOF

EB-1 150 250 10mm 2 2 2 2 2 2 1@50, REST@200

REPUBLIC OF THE PHILIPPINES PREPARED BY : CHECKED BY : RECOMMENDING APPROVAL : APPROVED BY : PROJECT TITLE : PROJECT NO: 00200511 OWNER : SHEET NO:

ONE STOREY DESIGNED BY: NQM


EMEC
AMA
VDS II
DEPARTMENT OF EDUCATION
TWO CLASSROOM ENCODED BY: Max C.
VDS DepED S -2
S
AN
D SCHO
OL
DEPARTMENT OF EDUCATION MAXIMO M. CALBANG ANTONIA M. ALHAMBRA LUIS G. PURISIMA JR. OLIVER R. HERNANDEZ 7x9m (MODIFIED) CHECKED BY: LGP
SHEET CONTENTS :
S
IE

2
ENG
FAC IL IT

PHYSICAL FACILITIES AND SCHOOLS ENGINEERING DIVISION


INEERING D

PDO - III
CIVIL ENGINEER/MASTER PLUMBER HEAD, PLANNING AND DESIGN UNIT CHIEF, PFSED-OPS
ELEVATIONS, BEAM DETAIL & SCHED.
AL
IC

IV

PFSED-DepED PFSED-DepED DepED


SI
I

YS

MERALCO AVENUE, PASIG CITY PFSED-DepED 01 01 2005 TYPICAL CONNECTION DETAIL


ON
LOCATION : DATE :
PH
De ED
p

NOTE:
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF PHYSICAL FACILITIES AND SCHOOLS ENGINEERING
DIVISION AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


GENERAL NOTES LEGEND
SYMBOL DESCRIPTION
1. ALL ELECTRICAL WORKS SHALL COMPLY IN ACCORDANCE WITH
OVERHEAD SERVICE ENTRANCE
- CEILING LIGHT OUTLET CONNECTED TO 220V AC, 1O,
THESE PLANS AND SPECIFICATIONS. THE APPLICABLE PROVISIONS
2 WIRE, 60 Hz FITTED WITH
2
- 2 x 40 WATTS FLUORESCENT LAMP
OF THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL CODE (PEC). 20mm O TYPE "F" CONDULET

THE RULES AND REGULATION OF THE LOCAL ENFORCING AUTHORITY F - CEILING FAN OUTLET

AND THE REQUIREMENTS OF THE LOCAL POWER COMPANY. - ONE GANG DEVICE SWITCH
S/Sa
THE ELECTRICAL WORKS SHALL BE UNDER IMMEDIATE SUPERVISION
S ab - TWO GANG DEVICE SWITCH CEILING LINE
OF A DULY REGISTERED ELECTRICAL ENGINEER.
BUILDING WALL
S cde - THREE GANG DEVICE SWITCH
2. THE ELECTRICAL SERVICE POWER IS 1-PHASE, 2-WIRE,
- THREE WAY DEVICE SWITCH METERING CONDUIT
230 V AC, 60 Hz. S 3W
2
2-5.5mm THW
KWHR METER
Sf - FAN CONTROL SWITCH IN 20mmORSC
3. WIRING METHOD SHALL BE AS FOLLOWS :

a. FEEDERS AND RISERS - INTERMEDIATE METALLIC CONDUIT - RACEWAY CONDUIT CONCEALED IN CEILING

3500 mm
b. LIGHTING, POWER RECEPTACLE - POLYVINYL CHLORIDE CONDUIT - RACEWAY CONDUIT CONCEALED UNDER FLOOR
BRANCH CKT., & AUXILIARY SCH. 40
- PANELBOARD
4. ALL WIRES SHALL BE COPPER AND THERMOPLASTIC INSULATED TYPE

1800 mm

1800 mm
- DUPLEX CONVENIENCE OUTLET, GROUNDING TYPE
"THW" UNLESS OTHERWISE INDICATED IN THE PLAN. THE MINIMUM
10 AMPS, 250 VOLT WITH MODERN PLATE COVER
SIZE OF WIRE FOR POWER AND LIGHTING CIRCUIT HOMERUN SHALL BE
2
3.5mm AND INSULATED FOR 600 VOLTS. SMALLEST RACEWAY SHALL - WEATHERPROOF TYPE

BE 15mm O TRADE/NOMINAL SIZE. WP


DUPLEX CONVENIENCE OUTLET, GROUNDING TYPE GROUND FLOOR LINE
I

5. ALL OUTLET BOXES SHALL BE GALVANIZED GAUGE NO. 16 DEEP


10 AMPS, 250 VOLT WITH MODERN PLATE COVER
TYPE WITH FACTORY KNOCKOUTS. LP
FIN. GRADE LINE
1 - HOMERUN DIRECT TO PANELBOARD
2
1-5.5mm THW COPPER WIRE

6. ALL MATERIALS TO BE USED SHALL BE BRAND NEW AND APPROVED 20


- CIRCUIT BREAKER, RATING AS INDICATED IN 15mmO C

TYPE FOR THE PARTICULAR LOCATION AND PURPOSE OF USAGE. 16MMO x 2400mm LENGTH
M
- ELECTRIC SERVICE METER GROUNDING ROD COPPERWELD

7. GROUNDING SYSTEM SHALL BE PROVIDED TO ALL LIGHTING AND


- SERVICE ENTRANCE
POWER CIRCUIT AS PER PHILIPPINE ELECTRICAL CODE REQUIREMENT.

8. MOUNTING HEIGHT OF WIRING DEVICES SHALL BE AS FOLLOWS :


ELECTRICAL RISER DIAGRAM
a. LIGHT SWITCH - 1.20 M ABOVE FINISH FLOOR NOT TO SCALE

b. CONVENIENCE OUTLET - 0.30 M ABOVE FINISH FLOOR.

c. PANELBOARD - 1.80 M ABOVE FINISH FLOOR

1 2 3 4 5
LOAD SCHEDULE

PANELBOARD: LP MAIN : A
40AT, 100AF, 2P, 240V

CIRCUIT BREAKER a a
e
d
CKT. VA
DESCRIPTION WIRE & CONDUIT SIZE 2 2 2 2

NO. LOAD
VOLT POLE AT AF CLASSROOM CLASSROOM

CONVENIENCE OUTLET 2 B F F
1 720 230 2 20 50 3-3.5mm THW IN 15mm C
LP1 e d
2 a
1200
a

2 LIGHTS & FAN 230 2 20 50 3-3.5mm THW IN 15mm C


2 2 2 2

LP2
3 SPARE 1500 230 2 20 50
Sabc Sf Sf Sdef

TOTAL 3420 C M

UP
c f

RAMP
2 2

2
IL = 3420 = 15 A FEEDER: 2-5.5mm THW IN 20mm RSC OVERHEAD SERVICE ENTRANCE
REFER TO RISER DIAGRAM

230 V PROTECTION: 40 AT, 50 AF, 2P, 240 V

ELECTRICAL LAYOUT
SCALE 1:100 M

REPUBLIC OF THE PHILIPPINES PREPARED BY : CHECKED BY : RECOMMENDING APPROVAL : APPROVED BY : PROJECT TITLE : PROJECT NO: 00200511 PROJECT NO:
OWNER
99-005
: SHEET NO:

DESIGNED BY: NQM


EMEC
AMA
VDS II
ONE STOREY DEPARTMENT OF EDUCATION
TWO CLASSROOM ENCODED BY: Max C.
VDS DepED E -1
S
AN
D SCHO
OL
DEPARTMENT OF EDUCATION MAXIMO M. CALBANG VENERANDO D. SAHAGUN LUIS G. PURISIMA JR. OLIVER R. HERNANDEZ 7x9m (MODIFIED) CHECKED BY: LGP
SHEET CONTENTS :
CALCULATIONS
S
IE

1
ENG
FAC IL IT

PHYSICAL FACILITIES AND SCHOOLS ENGINEERING DIVISION


INEERING D

PDO - III ENGINEER III HEAD, PLANNING AND DESIGN UNIT CHIEF, PFSED-OPS GENERAL NOTES LEGEND
AL
IC

IV

PFSED-DepED PFSED-DepED DepED


SI
I

YS

MERALCO AVENUE, PASIG CITY PFSED-DepED 01 01 2005 ELECTRICAL LAYOUT RISER DIAGRAM
ON
LOCATION : DATE :
PH
De ED
p

NOTE:
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF PHYSICAL FACILITIES AND SCHOOLS ENGINEERING
DIVISION AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


REPUBLIC OF THE PHILIPPINES

TABLE OFFICE OF THE CITY/MUNICIPAL


ENGINEER/BUILDING OFFICIAL

OF
CONTENTS
DISTRICT/CITY/MUNICIPALITY

ARCHITECTURAL
LAND USE & ZONING
A-1 PERSPECTIVE VIEW, TABLE OF CONTENTS

A-2 FLOOR PLAN, ELEVATIONS, ROOF PLAN


SECTIONS, REFLECTED CEILING PLAN

A-3 SCHEDULE OF DOOR & WINDOWS, BAY


SECTION, DETAIL SECTION, LOUVER LINE & GRADE
BLOCK VENT., RAMP DETAIL

ARCHITECTURAL

1 PERSPECTIVE VIEW
A-1 SCALE: NTS

STRUCTURAL

S-1 FOUNDATION PLAN, ROOF FRAMING


PLAN FOOTING DETAIL, COLUMN DETAIL, STRUCTURAL
WF-1, RAMP DETAIL

S-2 ELEVATIONS TYPICAL CONNECTION


DETAIL

SANITARY

ELECTRICAL
E-1 ELECTRICAL LAYOUT PLAN, RISER
DIAGRAM, LOAD SCHEDULE, GEN. NOTES

ELECTRICAL

SANITARY

MECHANICAL

REPUBLIC OF THE PHILIPPINES PREPARED BY : CHECKED BY : RECOMMENDING APPROVAL : APPROVED BY : PROJECT TITLE : PROJECT NO: 00200511 OWNER : SHEET NO:

DESIGNED BY: NQM


EMEC
AMA
VDS II
ONE STOREY DEPARTMENT OF EDUCATION
THREE CLASSROOM ENCODED BY: Max C.
VDS DepED A -1
S
AN
D SCHO
OL
DEPARTMENT OF EDUCATION MAXIMO M. CALBANG NATHANIEL Q. MENDOZA LUIS G. PURISIMA JR. OLIVER R. HERNANDEZ 7x9m (MODIFIED) CHECKED BY: LGP
SHEET CONTENTS :
S
IE

3
ENG
FAC IL IT

PERSPECTIVE VIEW
PHYSICAL FACILITIES AND SCHOOLS ENGINEERING DIVISION
INEERING D

PDO - III ARCHITECT III HEAD, PLANNING AND DESIGN UNIT CHIEF, PFSED-OPS PERSPECTIVE VIEW
AL

TABLE OF CONTENTS
IC

IV

PFSED-DepED PFSED-DepED DepED


SI
TABLE OF CONTENTS
I

YS

MERALCO AVENUE, PASIG CITY PFSED-DepED 01 01 2005


ON
LOCATION : DATE :
PH
De ED
p

NOTE:
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF PHYSICAL FACILITIES AND SCHOOLS ENGINEERING
DIVISION AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


GA.#26 CORR. G.I. ROOFING
C B A 7
1
6
1 1
5
1
4 3 2 1
A-1 A-1 A-1 A-1
SHEET (PAINT FINISH) GA#26 G.I. PL. 27000
1500 7000 RIDGE ROLL
400 4500 4500 4500 4500 4500 4500 400
3500 3500 1100 APEX OF ROOF PAINT FIN.
12x300mm FIBER CEMENT
FASCIA BOARD (PAINT FINISH) APEX OF ROOF

2026
GA#26 G.I. CORR.

2026
300x300mm EXTERIOR CONC. SHEET ROOFING SLOPE
LOUVER BLOCKS TOP OF ROOF BEAM PAINT FIN.

TOP OF

12mm THK. FIBER CEMENT ROOF BEAM


100mm THK.

2800
FASCIA BOARD (PAINT FIN.) CHB WALL PLAIN

2800
100mm THK. CHB WALL PLAIN CEMENT PLASTER
CLASSROOM
CEMENT PLASTER & PAINT FIN. & PAINT FIN.
FIN. FLR. LINE

VAR.
CLASSROOM W W W W W W
100mm THK. CHB WALL WITH

PLAIN CEMENT PLASTER (PAINT

FIN. FLR. LN.


FIN.)

FIN. GRD. LN. 1 1 1 1 1 1

150.
3 RIGHT ELEVATION FIN. GRD. LN.

4 FRONT ELEVATION
A-2 SCALE: 1:100m

A-2 SCALE: 1:100m

2 2

1 2 4
1
5
1
6 7
3 A-1 A-1
A-1 A-1
A B C GA.#26 CORR. G.I. ROOFING
GA#26 G.I. PL. 27000
RIDGE ROLL SHEET (PAINT FINISH)
400 4500 4500 4500 4500 4500 4500 400
7000 1500
PAINT FIN.
APEX OF ROOF 1100 3500 3500
APEX OF ROOF
12x300mm FIBER CEMENT
FASCIA BOARD (PAINT FINISH)
GA#26 G.I. CORR.

2026
2026

SHEET ROOFING SLOPE


300x300mm EXTERIOR CONC.
PAINT FIN.
TOP OF ROOF BEAM LOUVER BLOCKS
TOP OF
ROOF BEAM
100mm THK. 12mm THK. FIBER CEMENT

2800
CHB WALL PLAIN
FASCIA BOARD (PAINT FIN.)
2800

CEMENT PLASTER
& PAINT FIN. 100mm THK. CHB WALL PLAIN
CLASSROOM
CLASSROOM D
W
D D
W
D D
W
D CEMENT PLASTER & PAINT FIN.
W W W FIN. FLR. LINE

VAR.
1 1 1 1 1 1
FIN. FLR. LN. 2 2 2
150.

2 2 2
100mm THK. CHB WALL WITH

PLAIN CEMENT PLASTER (PAINT


FIN.)

FIN. GRD. LN.


FIN. GRD. LN.

2 FRONT ELEVATION 5 LEFT ELEVATION


A-2 SCALE: 1:100m
A-2 SCALE: 1:100m

2 2 2 2 2 2
1 2
A-1 3
A-1 4
A-1 5
A-1 6
A-1 7
A-1

27000

4500 4500 4500 4500 4500 4500

GA#26 PLAIN GI RIDGE ROLL


C C C
50-100mm RIVER STONE TRENCH C
A-1 B
A-1 A
A-1
PAINT FINISH

300x300mm EXT. CONCRETE


W W W LOUVER BLOCKS
W W W
1100

7000
1 1 1
1 1 1 GA#26 CORR. GI ROOFING
1500 3500 3500 1100
A
SHEET PAINT FINISH
APEX OF ROOF
4.8mm THK. FIBER CEMENT CEILING BOARD
ON 50x50mm CEILING JOIST @600mm OC
50
29 00 BOTHWAYS PAINT FINISH
54

2026
3500

100mm THK. CHB WALL VENTILATION (SEE DETAIL)


PLASTER & PAINT FINISH RAFTER/PURLINS SEE DETAIL
TOP OF ROOF BEAM
.

12x300mm FIBER CEMENT


FASCIA BOARD PAINT FINISH
7000

BLACKBOARD

BLACKBOARD

BLACKBOARD
W 4.8mm THK. FIBER CEMENT CEILING
B CLASSROOM CLASSROOM CLASSROOM

3000
BOARD ON 50x50mm CLG. JST.
EL. 150mm EL. 150mm EL. 150mm D 1
1
@600mm OC BW PAINT FIN.
FIN.: PLAIN CEMENT FIN. FIN.: PLAIN CEMENT FIN. FIN.: PLAIN CEMENT FIN.

CLASSROOM 100mm THK CHB WALL w/PLAIN


FIN. FLR. LN. CEMENT PLASTER PAINT FINISH
3500

CLASSROOM

150
7 100mm THK. CONCRETE SLAB ON FILL

1
A-2 W W W W W W
FIN. GRD. LN. 100mm THK. 50-100mm GRAVEL BED
FROM SELECTED COMPACT
2 2 2 2 2 2 FILLING MATERIAL

6 CROSS SECTION
C CORRIDOR SCALE : 1:100 m.
1500

A-2
1200

EL. 125mm
RAMP UP
FIN.: PLAIN CEMENT FIN.
600

6 50-100mm RIVER STONE TRENCH

1
A-2

1 FLOOR PLAN
SCHED. OF FLOOR FIN.
A-2 1:100m

FL-1 PLAIN CEMENT


FLOOR FIN.

PLAIN CEMENT FLR.


FL-2
FIN. W/ GROOVE (ROUGH)

REPUBLIC OF THE PHILIPPINES PREPARED BY : CHECKED BY : RECOMMENDING APPROVAL : APPROVED BY : PROJECT TITLE : PROJECT NO: 00200511 OWNER : SHEET NO:

DESIGNED BY: NQM


EMEC
AMA
VDS II
ONE STOREY DEPARTMENT OF EDUCATION
THREE CLASSROOM ENCODED BY: Max C.
VDS DepED A -2
S
AN
D SCHO
OL
DEPARTMENT OF EDUCATION MAXIMO M. CALBANG NATHANIEL Q. MENDOZA LUIS G. PURISIMA JR. OLIVER R. HERNANDEZ 7x9m (MODIFIED) CHECKED BY: LGP
SHEET CONTENTS : FLOOR, REFLECTED CLG., ROOF
S
IE

3
ENG
FAC IL IT

PHYSICAL FACILITIES AND SCHOOLS ENGINEERING DIVISION PLANS,FRONT, RIGHT, REAR,


INEERING D

PDO - III ARCHITECT III HEAD, PLANNING AND DESIGN UNIT CHIEF, PFSED-OPS FLOOR PLAN, ELEVATIONS, ROOF PLAN
AL

LEFT ELEVATIONS, CROSS,


IC

IV

PFSED-DepED PFSED-DepED DepED


SI
I

YS

MERALCO AVENUE, PASIG CITY PFSED-DepED 01 01 2005


ON
LOCATION : DATE :
PH
De ED
p SECTIONS, REFLECTED CEILING PLAN
LONGITUDINAL SECTIONS
NOTE:
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF PHYSICAL FACILITIES AND SCHOOLS ENGINEERING
DIVISION AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


1 1 1 1 1 1 1
1
1
A-1
2 2
A-1
3 3
A-1 4
A-1 5
A-1 6
A-1 7
A-1

SEE STRUCTURAL 27000


DETAIL 400 4500 4500 4500 4500 4500 4500 400

4.8mm THK. FIBER CEMENT APEX OF ROOF


CEILING BOARD ON 50x50mm
CEILING JOIST @600mm OC BW

2026
PAINT FINISH
VENT. SEE DETAIL
TOP OF BEAM

150mm THK. CHB WALL

2800
w/PLAIN CEMENT PLASTER
& PAINT FIN.

W-1 W-1 W-1 W-1 W-1 W-1

150
100mm THK. CONCRETE FIN. FLOOR LINE
SLAB
NGL
50-100mm GRAVEL
BEDDING
3 LONGITUDINAL SECTION
FROM SELECTED FILLING
MATERIAL A-3 SCALE: 1:100m

1 1 1 1 1 1 1
1
A-1 2
A-1 3
A-1 4
A-1 5
A-1 6
A-1 7
A-1

27000
4500 4500 4500 4500 4500 4500

1100
A
GA#26 CORR. G.I.
SHEET ROOFING PAINT

3500
FINISH

SLOPE

GA#26 PLAIN G.I.


B

9600
SHEET RIDGE ROLL
PAINT FINISH

12mm THK. FIBER SLOPE

3500
CEMENT FASCIA BOARD
PAINT FINISH

1500

2 ROOF PLAN
A-3 SCALE: 1:100mm

1 1 1 1 1 1 1
1
A-1 2
A-1 3
1
A-1 4
A-1 5
A-1 6
A-1 7
A-1

27000
4500 4500 4500 4500 4500 4500
1100

VENT. (SEE DETAIL)


A

LIGHTING FIXTURE
3500

2 2 2 2 2 2 2 2 2

12mm THK. FIBER


CEMENT FASCIA BOARD
PAINT FINISH
B
9600

4.8mm THK. FIBER


CEMENT EXTERIOR &
INTERIOR CEILING
3500

2 2 2 2 2 2 2 2 2
BOARD ON METAL OR
SOLID WOOD CEILING
JOIST @600mm OC
BW PAINT FINISH

C A-1
1500

1 REFLECTED CEILING PLAN


A-3 SCALE: 1:100m

REPUBLIC OF THE PHILIPPINES PREPARED BY : CHECKED BY : RECOMMENDING APPROVAL : APPROVED BY : PROJECT TITLE : PROJECT NO: 00200511 OWNER : SHEET NO:

DESIGNED BY: NQM


EMEC
AMA
VDS II
ONE STOREY DEPARTMENT OF EDUCATION
THREE CLASSROOM ENCODED BY: Max C.
VDS DepED A -3
S
AN
D SCHO
OL
DEPARTMENT OF EDUCATION MAXIMO M. CALBANG NATHANIEL Q. MENDOZA LUIS G. PURISIMA JR. OLIVER R. HERNANDEZ 7x9m (MODIFIED) CHECKED BY: LGP
SHEET CONTENTS : DOOR & WINDOW SCHEDULE
S
IE

3
ENG
FAC IL IT

DETAILS
PHYSICAL FACILITIES AND SCHOOLS ENGINEERING DIVISION
INEERING D

PDO - III ARCHITECT III HEAD, PLANNING AND DESIGN UNIT CHIEF, PFSED-OPS
AL
IC

IV

PFSED-DepED PFSED-DepED DepED


SI
I

YS

MERALCO AVENUE, PASIG CITY PFSED-DepED 01 01 2005


ON
LOCATION : DATE :
PH
De ED
p

NOTE:
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF PHYSICAL FACILITIES AND SCHOOLS ENGINEERING
DIVISION AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


2-16 BOLTS
6mm THK PLYWOOD w/6mm
GROOVE ON 50x50mm NAILERS

@600mm OC BW (PAINT FIN) GA#26 CORR. ROOFING SHEET


(PAINT FIN.)
SAG ROD (SEE DETAIL)

TECKSCREW
1000 4 EQ. PARTS= 2 EQUAL PARTS =
STL. PURLINS (SEE STRUCTURAL DET.)
2500 1250 10mm THICK PLATE
TECKSCREW
6mm GROOVE

300

300

300

275
300x150x10mm BASE
PLATE
25x25 mm WOOD VENT

(14-BLADES)

(14-BLADES)
PROVIDE INSECT SCREEN
4-16x300mm LONG VENTILLATION W/ WIRE

1230

1230
BENT ANCHOR BOLTS MESH

300
2400

2400

2400
12x300mm FIBER
2100

CEMENT FASCIA BOARD

300
FULLY WELD ON
RAFTER

875

875
ELEV 20x20x2mm ANGULAR
BAR FOR FASCIA BD.
FFL
5 EAVES DETAIL FRAME WELDED TO
RAFTERS AND PURLINS
575 575
SCALE: 1:20mts
D-1 W-1 W-2 A-4

HOLLOW CORE FLUSH TYPE HINGED DOOR


JALOUSIE WINDOW W/ CLEAR GLASS BLADES ON STD. ALUM. SAME AS W-1

ON 50x100mm WOOD JAMBS/FRAMES HOUSING & FIXED CLEAR GLASS TRANSOMS ON 50x100mm WD.

275
JAMBS/FRAMES

1 DOOR & WINDOW SCHEDULE


A-3 SCALE: 1:50m
25x25mm WOOD VENT
PLAN PROVIDE INSECT SCREEN

600

4 TYP. CLG. VENT. DETAILS 300

A A-4 SCALE: 1:10 mts.


GA#26 CORR. GI.
C GA#26 PLAIN
ROOF

GI. FLASHING 27

1100 123
1500 C-PURLIN SEE
STRUCTURAL DET.
5
LOUVER BLOCKS (CONCRETE)
A-4

600

150
23

4
GA 26 G.I. CORR. SHEET ROOFING
TOP OF ROOF BEAM
TOP OF ROOF BEAM PAINT FINISH

GA#26 CORR. G.I. SHT. LC 100x50x15x1.5mm STL


ROOF (PAINT FIN.)
400

CONC. C-PURLINS @750mm OC ON RAFTER SEE


BEAM 2-LC 150x65x20x2mm RAFTER STRUCTURAL DET.
6mm THK. ORD. PLYWOOD INSIDE
INT. CEILING w/6MM GROOVE ON
OUTSIDE
50x50mm CEILING JOIST @600mm
ELEVATION

300
OC BOTHWAYS
10mmSAG ROD
12x300mm FIBER CEMENT
RAFTER (SEE STRUCT'L DET.)
FASCIA BOARD ON 20x20x2mm

CEILING VENTILATION SEE


SECTION ANGLE BAR FRAME W/ VERT.
MEMBER @ 600mm OC
12x300mm FIBER CEMENT 6mm THK. ORDINARY PLYWOOD
FASCIA BOARD ON 25x25x6mm
DETAIL
CEILING w/6mm GROOVE ON
12x300mm FIBER CONCRETE FASCIA
BOARD ON 25x25x6mm L-BAR
6 LOUVER BLOCK DETAIL 400
THK L-BAR w/25x6mm THK 50x50mm CEILING JOIST @600mm
STIFF FLAT BAR @600mm OC OC BW (PAINT FINISH) W/25x6mm THK STIFFENER FLAT BAR @
EVERY 600mm OC
A-4 SCALE: 1:10 mts.

BW. PAINT FIN.


7 EAVES DETAIL
W-1

2800
2800

CEILING VENTILLATION (SEE A-4 SCALE : 1:20M


DETAIL)
100 mm THK. CHB WALL WITH

PLAIN CEMENT PLASTER (PAINT FIN.)

2216
D-1

CLASSROOM
EL. +175mm
PART OF 100
100
C
800

CLASSROOM
TYPICAL

PART OF CORRIDOR

6mm
6mm
CLASSROOM 6mm

1500

UP
1200
CORRIDOR

25
FIN. FLOOR LINE NON-SK
FL-2 ID PLAIN

RAMP
CEMENT
FLOOR
CEMEMN

VAR.
T FINISH
VAR.

150
FIN. GRADE LINE

LINE OF CORRIDOR
POLYETHYLENE SHEET DAMP POLYETHYLENE SHEET DAMP
PROOFING PROOFING 1800
100mm THK. REINF. CONC 100mm THK. REINF. CONC DETAIL SECTION
SLAB SLAB
1500 DETAIL PLAN SCALE 1:5 M
100mm THK 50-100mm 100mm THK 50-100mm SCALE 1:50 M
GRAVEL BED GRAVEL BED

FR. SELECTED FILLING


PLAN
FR. SELECTED FILLING
1 PLAN MATERIALS MATERIALS 2 8 RAMP DETAILS
A-4 SCALE: 1:100m
A-4 SCALE: 1:100m
A-4 SCALE: AS SHOWN

REPUBLIC OF THE PHILIPPINES PREPARED BY : CHECKED BY : RECOMMENDING APPROVAL : APPROVED BY : PROJECT TITLE : PROJECT NO: 00200511 OWNER : SHEET NO:

DESIGNED BY: NQM


EMEC
AMA
VDS II
ONE STOREY DEPARTMENT OF EDUCATION
THREE CLASSROOM ENCODED BY: Max C.
VDS DepED A -4
S
AN
D SCHO
OL
DEPARTMENT OF EDUCATION MAXIMO M. CALBANG NATHANIEL Q. MENDOZA LUIS G. PURISIMA JR. OLIVER R. HERNANDEZ 7x9m (MODIFIED) CHECKED BY: LGP
SHEET CONTENTS : FLOOR PLAN
S
IE

4
ENG
FAC IL IT

ELEVATIONS
PHYSICAL FACILITIES AND SCHOOLS ENGINEERING DIVISION
INEERING D

PDO - III ARCHITECT III HEAD, PLANNING AND DESIGN UNIT CHIEF, PFSED-OPS
AL

SECTIONS
IC

IV

PFSED-DepED PFSED-DepED DepED


SI
I

YS

MERALCO AVENUE, PASIG CITY PFSED-DepED 01 01 2005


ON
LOCATION : DATE :
PH
De ED
p

DETAILS
NOTE:
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF PHYSICAL FACILITIES AND SCHOOLS ENGINEERING
DIVISION AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


4 4 4 4
1 2 3 4
A-1 5
A-1 6
A-1 7
A-1
27000

4 4 4 4 4500 4500 22500


4500 4500 4500
1 2 3 4
A-1 5
A-1 6
A-1 7
A-1

9000 9000 9000

1100
4500 4500 4500 4500 4500 4500
RG-1 RG-1 RG-1 RG-1 RG-1 RG-1
F-1
C-1
F-2
C-2
F-1
C-1
F-2
C-2
F-1
C-1
F-2
C-2
F-1 A
C-1

A WF-1 WF-1 WF-1 WF-1 WF-1 WF-1


10mm SAG ROD

w/STANDARD NUTS &

3500

RG-2

RG-2

RG-2

RG-2
EB-1

EB-1

EB-1

EB-1
WASHERS @ END
3500

WF-1
WF-1

WF-1

WF-1

R - 1

R - 1

R - 1

R - 1

R - 1

R - 1
R - 2

R - 2

R - 2

R - 2
7000
F-1 F-1 F-1 F-1 B
C-1 C-1 C-1 C-1
7000

100mm THK. SLAB ON FILL ON


B 100mm THK. GRAVEL FILL
50x100x15x1.5mm
COMPACTED 95w/SELECTED

3500

RG-2

RG-2

RG-2

RG-2
STEEL PURLINS

EB-1

EB-1

EB-1

EB-1
FILLING MATERIALS
@750 O.C.
3500

WF-1
WF-1

WF-1

WF-1
RG-1 RG-1 RG-1 RG-1 RG-1 RG-1

F-1
C-1
F-2
C-2
F-1
C-1
F-2
C-2
F-1
C-1
F-2
C-2
F-1
C-1
C

1500
C
RAMP UP

WF-1 WF-1 WF-1 WF-1 WF-1 WF-1


1500

1200

1800
B ROOF FRAMING PLAN
A FOUNDATION PLAN S-1 SCALE: 1:100m

S-1 SCALE: 1:100m

C B 1 A C B 2 A C B A
S- S-
2 3

R- R- R-
2 1 2 2 1 2 1 1
R- EB
- EB R- EB
- EB R-
- -
1 1

RG-1 RG-2 RG-2 RG-1 RG-1 RG-2 RG-2 RG-1 RG-1 RG-1

C O L U M N S C H E D U L E

LEVEL C-1 C-2 C ELEV END GRID D ELEV PARTITION GRID E ELEV BETWEEN GRID
S-1 SCALE: 1:100m
S-1 SCALE: 1:100m
S-1 SCALE: 1:100m

300 400

DESIGN CRITERIA :
200

200

S C H E D U L E O F F O O T I N G S
A. CONCRETE
FOUNDATION LEVEL
LEVEL

fc' = 20.685 Mpa ( 3,000 Psi ), minimum compressive strength of concrete


FOOTING
FOOTING DIMENSIONS (mm) REINFORCEMENT
a 28 days unless otherwise specified.
MAIN BAR: MAIN BAR: REMARKS
MARK LENGTH WIDTH DEPTH THICKNESS B. REBAR
4-%16mm 6-%16mm BAR X BAR Y
(L) (W) (D) (t)
fy = 275.8 Mpa ( 40,000 Psi ), minimum yield strength of reinforcing bars
ROOF

TIES : 10 mm TIES : 10 mm
1@50, 8@75, REST @ 1@50, 8@75, REST @ F-1 800 800 1200 250 4 - 16mm% 4 - 16mm% SQUARE FOOTING unless otherwise specified.
150mm TO CENTER 150mm TO CENTER C. STRUCTURAL STEEL

F-2 1000 1000 1200 250 4 - 16mm% 4 - 16mm% SQUARE FOOTING


Fy = 248 Mpa ( 36 Ksi ), specified minimum yield strength
TO

unless otherwise specified.


D. FOUNDATION

SBP = 95.706 Kpa ( 2,000 Psf ), was used in the design for all footings.
No footing shall rest on fill.

REPUBLIC OF THE PHILIPPINES PREPARED BY : CHECKED BY : RECOMMENDING APPROVAL : APPROVED BY : PROJECT TITLE : PROJECT NO: 00200511 OWNER : SHEET NO:

DESIGNED BY: NQM


EMEC
AMA
VDS II
ONE STOREY DEPARTMENT OF EDUCATION
THREE CLASSROOM ENCODED BY: Max C.
VDS DepED S -1
S
AN
D SCHO
OL
DEPARTMENT OF EDUCATION MAXIMO M. CALBANG ANTONIA M. ALHAMBRA LUIS G. PURISIMA JR. OLIVER R. HERNANDEZ 7x9m (MODIFIED) CHECKED BY: LGP
SHEET CONTENTS :
S
IE

FOUNDATION PLAN, ROOF FRAMING PLAN


2
ENG
FAC IL IT

PHYSICAL FACILITIES AND SCHOOLS ENGINEERING DIVISION


INEERING D

PDO - III
CIVIL ENGINEER/MASTER PLUMBER HEAD, PLANNING AND DESIGN UNIT CHIEF, PFSED-OPS
FOOTING DETAIL, COLUMN DETAIL, WF-1,
AL
IC

IV

PFSED-DepED PFSED-DepED DepED


SI
I

YS

MERALCO AVENUE, PASIG CITY PFSED-DepED 01 01 2005


ON
LOCATION : DATE :
PH
De ED
p
RAMP DET.
NOTE:
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF PHYSICAL FACILITIES AND SCHOOLS ENGINEERING
DIVISION AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


4-%16x300mm LONG
BENT ANCHOR BOLTS
65 65

20

20
300x150x10mm
300 BASE PLATE
50 50
100mm THK.

37.5
CHB

150

150
50

37.5
10@600

15
HOR. BARS

1 2LC-150x65x20x3 LC-150x65x20x3
NATURAL GRADE LINE
LINE OF R-1/R-2

100
R-1 R-2
10@600 10mm THICK PLATE
PLAN
VERT. BARS 1800

E DETAIL OF RAfTER
600

10 300mm TEMP
BARS BOTHWAYS
SCALE NTS LC-100x50x15x1.5
S-2

150
F DETAIL OF PURLINS
250

10mm SCALE NTS


S-2
G-20mm GRAVEL 3-10mm
BEDDING 10mm @300 CUT BARS
400

D DETAIL OF WF-1 E DETAIL OF RAMP


2-%16
SCALE 1 : 50M
S-1 SCALE : NTS. S-1 BOLTS 100x50x15x1.5mm
2-%16 STEEL C-PURLINS
BOLTS 750mm O.C.

R-2
4-%16x300mm
L
LONG BENT R-1/R-2 10mm THICK PLATE
ANCHOR BOLTS 1-%10mm A-307

10mm X 150mm ANCHOR BOLT


NGL 4-%16x300mm LONG EB-1
ANCHOR BOLTS
300x150x10mm BENT ANCHOR BOLTS (SEE SCHED)
BASE PLATE
R- SPACED @ 800mm O.C. L-50x50x4.5

10mm THICK PLATE 1/


300x150x10mm R- 1:20 M
2
BASE PLATE

1 SECTION DETAIL
D

Y-BARS

X-BARS
W

SCALE NTS
S-2
t

Y-BARS

RC BEAM/COLUMN
100

X-BARS

PURLIN CONNECTION DET


100 mm THICK
G
L
GRAVEL BEDDING
ELEVATION
PLAN SECTION SCALE 1 : 5 M

ELEVATION
S-2
C TYP. FOOTING DETAIL
S-1 SCALE :
D TYPICAL RAFTER ANCHORAGE DETAIL
SCALE
S-2

L1 L2
NTS

2D LAP SPLICES ARE ALLOWED 2D 2D LAP SPLICES ARE ALLOWED 2D

ONLY IN THIS PORTION ONLY IN THIS PORTION

100x50x15x1.5mm
STEEL C-PURLINS
750mm O.C.

10mm% SAG ROD WITH


2-10mm SIDE BARS
STANDARD NUTS &
TOP OF RAFTER WASHERS @ EACH END

10mm TIE ROD WITH


STANDARD NUTS &
WASHERS @ EACH END
C TYPICAL BEAM ELEVATION CL.
50x100x15x1.5mm
S-2 STEEL C-PURLINS
150
150
750mm O.C. R-
1/
R-
2
10mm SAG ROD
B E A M S C H E D U L E

BEAM S T E E L R E I N F O R C E M E N T S
FLOOR BEAM DIMENSIONS S T I R R U P S
( in / mm ) LEFT MID SPAN RIGHT
LEVEL MARK REBAR 10mm

(mm ) (UNLESS NOTED OTHERWISE)


b h TOP BOTTOM TOP BOTTOM TOP BOTTOM

RG-1 150 400 12mm 2 2 2 2 2 2 1@50, 8@100, REST@200


LEVEL

RG-2 150 400 12mm 2 2 2 2 2 2 1@50, 6@100, REST@200 I SAG ROD CONNECTION DET.
H TIE ROD CONNECTION DET. SCALE 1 : 10 M
SCALE 1 : 10 M S-2
S-2
ROOF

EB-1 150 250 10mm 2 2 2 2 2 2 1@50, REST@200

REPUBLIC OF THE PHILIPPINES PREPARED BY : CHECKED BY : RECOMMENDING APPROVAL : APPROVED BY : PROJECT TITLE : PROJECT NO: 00200511 OWNER : SHEET NO:

ONE STOREY DESIGNED BY: NQM


EMEC
AMA
VDS II
DEPARTMENT OF EDUCATION
THREE CLASSROOM ENCODED BY: Max C.
VDS DepED S -2
S
AN
D SCHO
OL
DEPARTMENT OF EDUCATION MAXIMO M. CALBANG ANTONIA M. ALHAMBRA LUIS G. PURISIMA JR. OLIVER R. HERNANDEZ 7x9m (MODIFIED) CHECKED BY: LGP
SHEET CONTENTS :
S
IE

2
ENG
FAC IL IT

PHYSICAL FACILITIES AND SCHOOLS ENGINEERING DIVISION


INEERING D

PDO - III
CIVIL ENGINEER/MASTER PLUMBER HEAD, PLANNING AND DESIGN UNIT CHIEF, PFSED-OPS
ELEVATIONS, BEAM DETAIL & SCHED.
AL
IC

IV

PFSED-DepED PFSED-DepED DepED


SI
I

YS

MERALCO AVENUE, PASIG CITY PFSED-DepED 01 01 2005 TYPICAL CONNECTION DETAIL


ON
LOCATION : DATE :
PH
De ED
p

NOTE:
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF PHYSICAL FACILITIES AND SCHOOLS ENGINEERING
DIVISION AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


GENERAL NOTES LEGEND 1 2 3 4 5 6 7

SYMBOL DESCRIPTION
1. ALL ELECTRICAL WORKS SHALL COMPLY IN ACCORDANCE WITH

THESE PLANS AND SPECIFICATIONS. THE APPLICABLE PROVISIONS - CEILING LIGHT OUTLET

OF THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL CODE (PEC). 2


- 2 x 40 WATTS FLUORESCENT LAMP

THE RULES AND REGULATION OF THE LOCAL ENFORCING AUTHORITY F - CEILING FAN OUTLET
AND THE REQUIREMENTS OF THE LOCAL POWER COMPANY.

THE ELECTRICAL WORKS SHALL BE UNDER IMMEDIATE SUPERVISION


S/Sa - ONE GANG DEVICE SWITCH
A
S ab - TWO GANG DEVICE SWITCH
OF A DULY REGISTERED ELECTRICAL ENGINEER.

S cde - THREE GANG DEVICE SWITCH


2. THE ELECTRICAL SERVICE POWER IS 1-PHASE, 2-WIRE,
230 V AC, 60 Hz. S 3W - THREE WAY DEVICE SWITCH

3. WIRING METHOD SHALL BE AS FOLLOWS : - FAN CONTROL SWITCH CLASSROOM CLASSROOM CLASSROOM
Sf

a. FEEDERS AND RISERS - INTERMEDIATE METALLIC CONDUIT


- RACEWAY CONDUIT CONCEALED IN CEILING
B
b. LIGHTING, POWER RECEPTACLE - POLYVINYL CHLORIDE CONDUIT
- RACEWAY CONDUIT CONCEALED UNDER FLOOR
BRANCH CKT., & AUXILIARY SCH. 40

- PANELBOARD
LP
4. ALL WIRES SHALL BE COPPER AND THERMOPLASTIC INSULATED TYPE 1

"THW" UNLESS OTHERWISE INDICATED IN THE PLAN. THE MINIMUM - DUPLEX CONVENIENCE OUTLET, GROUNDING TYPE
LP

SIZE OF WIRE FOR POWER AND LIGHTING CIRCUIT HOMERUN SHALL BE 10 AMPS, 250 VOLT WITH MODERN PLATE COVER

3.5mm
2
AND INSULATED FOR 600 VOLTS. SMALLEST RACEWAY SHALL
C M

UP

UP
- WEATHERPROOF TYPE WP WP

BE 15mmO TRADE/NOMINAL SIZE.

RAMP

RAMP
WP
DUPLEX CONVENIENCE OUTLET, GROUNDING TYPE
I

OVERHEAD SERVICE ENTRANCE

5. ALL OUTLET BOXES SHALL BE GALVANIZED GAUGE NO. 16 DEEP 10 AMPS, 250 VOLT WITH MODERN PLATE COVER
REFER TO RISER DIAGRAM

TYPE WITH FACTORY KNOCKOUTS. LP

1 - HOMERUN DIRECT TO PANELBOARD

6. ALL MATERIALS TO BE USED SHALL BE BRAND NEW AND APPROVED


20
- CIRCUIT BREAKER, RATING AS INDICATED
TYPE FOR THE PARTICULAR LOCATION AND PURPOSE OF USAGE.

POWER LAYOUT
M
- ELECTRIC SERVICE METER
7. GROUNDING SYSTEM SHALL BE PROVIDED TO ALL LIGHTING AND
- SERVICE ENTRANCE
POWER CIRCUIT AS PER PHILIPPINE ELECTRICAL CODE REQUIREMENT.
SCALE 1:100 M

8. MOUNTING HEIGHT OF WIRING DEVICES SHALL BE AS FOLLOWS :

a. LIGHT SWITCH - 1.20 M ABOVE FINISH FLOOR

b. CONVENIENCE OUTLET - 0.30 M ABOVE FINISH FLOOR.

c. PANELBOARD - 1.80 M ABOVE FINISH FLOOR

1 2 3 4 5 6 7

LOAD SCHEDULE

OVERHEAD SERVICE ENTRANCE


CONNECTED TO 220V AC, 1O,
2 WIRE, 60 Hz FITTED WITH
25mm O TYPE "F" CONDULET

A
PANELBOARD: LP MAIN : 60AT, 100AF, 2P, 230V
CEILING LINE
a b c d e f
BUILDING WALL
CIRCUIT BREAKER
CKT. VA
DESCRIPTION WIRE & CONDUIT SIZE METERING CONDUIT
2 2 2 2 2 2

NO. LOAD
VOLT POLE AT AF 2-14mm THW
2

KWHR METER
IN 25mmORSC

2
CONV. OUTLET - 8 x 180W
1 1440 230 2 20 50 3-3.5mm THW IN 15mm C
B F F F

3500 mm
2
2 LIGHTING OUTLET - 8 x 100W 800 230 2 20 50 3-3.5mm THW IN 15mm C

1000
2
3-3.5mm THW IN 15mm C
a b c d e f
3 LIGHTING OUTLET - 10 x 100W 230 2 20 50
1800 mm

1800 mm

2 2 2 2 2 2

4 SPARE 1500 230 2 20 50

TOTAL 4740 LP LP

Sab Sf Scd Sf 3
Sef Sf 2

GROUND FLOOR LINE


C
Sg Shi

UP

UP
2
IL = 4740 = 20.6 A FEEDER: 2-14mm THW IN 25mm C
FIN. GRADE LINE
g h i

RAMP

RAMP
2

PROTECTION: 60 AT, 100 AF, 2P, 230 V


2
2 2
230 V 1-5.5mm THW COPPER WIRE
IN 15mmO C

16MMO x 2400mm LENGTH


GROUNDING ROD COPPERWELD

ELECTRICAL RISER DIAGRAM LIGHTING LAYOUT


NOT TO SCALE SCALE 1:100 M

REPUBLIC OF THE PHILIPPINES PREPARED BY : CHECKED BY : RECOMMENDING APPROVAL : APPROVED BY : PROJECT TITLE : PROJECT NO: 00200511 OWNER : SHEET NO:

DESIGNED BY: NQM


EMEC
AMA
VDS II
ONE STOREY DEPARTMENT OF EDUCATION
THREE CLASSROOM ENCODED BY: Max C.
VDS DepED E -1
S
AN
D SCHO
OL
DEPARTMENT OF EDUCATION MAXIMO M. CALBANG VENERANDO D. SAHAGUN LUIS G. PURISIMA JR. OLIVER R. HERNANDEZ 7x9m (MODIFIED) CHECKED BY: LGP
SHEET CONTENTS :
LEGEND POWER LAYOUT
S
IE

1
ENG
FAC IL IT

PHYSICAL FACILITIES AND SCHOOLS ENGINEERING DIVISION


INEERING D

PDO - III ENGINEER III HEAD, PLANNING AND DESIGN UNIT CHIEF, PFSED-OPS GENERAL NOTES LOAD SCHEDULE
AL
IC

IV

PFSED-DepED PFSED-DepED DepED


SI
I

YS

MERALCO AVENUE, PASIG CITY PFSED-DepED 01 01 2005 LIGHTING LAYOUT RISER DIAGRAM
ON
LOCATION : DATE :
PH
De ED
p

NOTE:
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF PHYSICAL FACILITIES AND SCHOOLS ENGINEERING
DIVISION AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


REPUBLIC OF THE PHILIPPINES

OFFICE OF THE CITY/MUNICIPAL


ENGINEER/BUILDING OFFICIAL

DISTRICT/CITY/MUNICIPALITY

ARCHITECTURAL
LAND USE & ZONING
A-1 PERSPECTIVE VIEW, TABLE OF
CONTENTS

A-2 FLOOR PLAN, ELEVATIONS, CROSS


SECTION

A-3 CEILING & ROOF PLANS,


LONGITUDINAL SECTION LINE & GRADE

A-4 SCHEDULE OF DOOR & WINDOWS,


BAY SECTION, DETAIL SECTION,
LOUVER BLOCK VENT., RAMP
DETAIL

ARCHITECTURAL

1 PERSPECTIVE VIEW
A-1 SCALE: NTS

STRUCTURAL
S-1 FOUNDATION PLAN, ROOF
FRAMING PLAN FOOTING DETAIL,
COLUMN DETAIL, WF-1, RAMP STRUCTURAL
DETAIL

S-2 ELEVATIONS TYPICAL


CONNECTION DETAIL

SANITARY

ELECTRICAL
E-1 ELECTRICAL LAYOUT PLAN, RISER
DIAGRAM, LOAD SCHEDULE, GEN.
NOTES

ELECTRICAL

SANITARY

MECHANICAL

CONSULTANT / DESIGNER REVIEWED BY: RECOMMENDING APPROVAL : APPROVED FOR ACCREDITATION : CONCURRED : PROJECT TITLE : PROJECT NO: 01-002 OWNER : SHEET NO:

REPUBLIC OF THE PHILIPPINES DESIGNED BY: AZB


E

ONE STOREY DEPARTMENT OF EDUCATION


A-1
t h e PH F A
f
o IL
IC I

DEPARTMENT OF EDUCATION (DepED) A-1


T
M
L

P
B

TA
PU

I TO R I NG
IN

SK

EMMANUEL P. CUNTAPAY
RE

ES

SOFIA T. SANTIAGO GILBERTO S. REYES RAMON C. BACANI


DepED
F O RC E

ALBERT Z. DE BELEN
THREE CLASSROOM
ON

ENCODED BY: Max C


D

TASK FORCE ENGINEERING, ASSESSMENT AND MONITORING


M
PE

NO

EN

MCMXCIX
&

IN
G
I
A

E N
E
R

ER
T

IN SM
A

A S SE S
T C
M U G ,

7x9m (STANDARD)
E

CHIEF, ARCHITECTURAL DIVISION


DE
TN

OIC, DIRECTOR III OIC, DIRECTOR IV


F O

UNDERSECRETARY

3
MERALCO AVENUE, PASIG CITY ARCHITECT IV
SHEET CONTENTS :
BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH CHECKED BY: PERSPECTIVE VIEW
8
0010990 149 460 161 DEPATMENT OF EDUCATION (DepED)
PRC NO. : TIN :
TABLE
PERSPECTIVE OF CONTENTS
VIEW
27 OCT. 2002
PTR NO. : DATE : LOCATION : DATE : TABLE OF CONTENTS
01 03

NOTE:
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF TASK FORCE ENGINEERING, ASSESSMENT AND
MONITORING AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


7 6 5 4 3 2 1 A B C GA#26 CORR. G.I.
GA.#26 CORR. G.I. ROOFING
C B A ROOFING SHEET

SHEET (PAINT FINISH) (PAINT FIN.)


9000 9000 9000
7000 1500
1500 7000 GA#26 PLAIN G.I.
4500 4500 4500 4500 4500 4500 GA#26 PL. GI. SHT. 1100 3500 3500
12x300mm FIBER CEMENT 3500 3500 1100 FLASHING (PAINT
RIDGE ROLL PAINT
FASCIA BOARD (PAINT TOP OF TRUSS TOP OF TRUSS FIN.)
FIN.
FINISH)
GA#26 G.I. CORR.

1780
SLOPE SLOPE SLOPE

1780
SHT. ROOFING PAINT 300x300mm EXT.
300x300mm EXTERIOR
FIN. CONC. LOUVER
CONC. LOUVER BLOCKS TOP OF ROOF BEAM GA.#26 PL. G.I. TOP OF ROOF BLOCKS
FLASHING ON BEAM
12x300mm FIBER 12x300mm FIBER CEMENT
CEMENT FASCIA FASCIA BOARD (PAINT FIN.)
12mm THK. FIBER CEMENT

2800
BOARD (PAINT FIN.)

2800
FASCIA BOARD (PAINT FIN.)
150 mm THK. CHB WALL WITH
PLAIN CEMENT PLASTER CLASSROOM CLASSROOM 150 mm THK. CHB WALL
150 mm THK. CHB
FIN. FLR. LINE W-1 W-1 W-1 W-1 W-1 W-1 FIN. FLR. LN. WITH PLAIN CEMENT
(PAINT FIN.)

VAR.
WALL WITH PLAIN

VAR.
CEMENT PLASTER
PLASTER (PAINT FIN.)
FIN. GRD. LN. FIN. GRD. LN.
(PAINT FIN.)
3 RIGHT ELEVATION
4 REAR ELEVATION 5 LEFT ELEVATION
A-2 SCALE: 1:100m

A-2 SCALE: 1:100m A-2 SCALE: 1:100m

SUSPENDED
LIGHTING FIXTURES

1 2 3 4 5 6 7 6mm THK. PLYWOOD GA.#26 CORR. G.I.


ROOFING SHEET
12mm GI. PIPE HANGERS
CEILING ON 50X50mm
1 2 3 4 5 6 7
GA#26 G.I. PL. RIDGE
CEILING JOIST SP. (PAINT FINISH)
ROLL (PAINT FIN.) 9000 9000 9000
@600mm O.C.
GA#26 G.I. CORR. 400 4500 4500 4500 4500 4500 4500 BOTHWAYS (PAINT
400 9000 9000 9000 400
SHEET ROOFING FINISH)
(PAINT FIN.) 4500 4500 4500 4500 4500 4500
TOP OF TRUSS TOP OF TRUSS

GA#26 G.I. PLAIN


FLASHING (PAINT SLOPE SLOPE SLOPE

1780
1780

FIN.)

TOP OF ROOF BEAM TOP OF ROOF


BEAM

150mm THK. CHB


PAINT FIN.

2800
2800

6mm THK. CHB


PLASTER PAINT FIN.

CLASSROOM D-1 D-1 D-1 D-1 D-1 D-1 CLASSROOM W-1 W-1 W-1
W-2 W-2 W-2 W-2 W-2 W-2 W-1 W-1 W-1
CLASSROOM 1 CLASSROOM 2 CLASSROOM 3
VAR.

FIN. FLR. LN. FIN. FLR. LN.

VAR
FIN. GRD. LN. FIN. GRD. LN.

6 LONGITUDINAL SECTION
2 FRONT ELEVATION
A-2 SCALE: 1:100m

A-2 SCALE: 1:100m

1 2 3 4 5 6 7
9000 9000 9000
1 2 3 4 5 6 7
400 4500 4500 4500 4500 4500 4500 400

9000 9000 9000


600

GRAVEL BED (RIVER STONE) 12x300mm FIBER


400 4500 4500 4500 4500 4500 4500 400
ROOF LINE ABOVE CEMENT FASCIA
BOARD (PAINT FIN.)
1100

W-1 W-1 W-1 W-1 W-1 W-1


ROOF LINE

1100
A

ROOF LINE
SUSPENDED
LIGHTING
3500

150mm THK. FIXTURES


CHB W/PLAIN
CEMENT 6mm THK. ORD. PLYWOOD
PLASTER CEILING w/6mm GROOVE
ON 50x50mm CEILING
BLACKBOARD

BLACKBOARD

BLACKBOARD
(PAINT FIN.) CLASSROOM 1 CLASSROOM 2 CLASSROOM 3

B
7000

JOIST @600mm O.C. BOTH


FL-1 FL-1 FL-1 WAYS

7000
CLASSROOM 1 CLASSROOM 2 CLASSROOM 3

FL-1 FL-1 FL-1


6mm THK. MARINE
3500

PLYWOOD EXT. CLG. ON


6
50x50mm @600mm OC
A-2 BW.

D-1 D-1 D-1 D-1 D-1 D-1 VENT.


W-2 W-2 W-2 W-2 W-2 W-2
(SEE DETAIL)
C
RAMP UP

C
25mm 25mm 25mm 25mm 25mm 25mm
1200
1500

DEP.
CORRIDOR DEP.
CORRIDOR DEP.
CORRIDOR DEP.

FL-1 LINE OF ROOF FL-1 FL-1


2

1500
A-3
600

GRAVEL BED (RIVER STONE)


200

1800 LINE OF CORRIDOR

SCHED. OF FLOOR FIN.


1 FLOOR PLAN 7 REFLECTED CEILING PLAN
FL-1 PLAIN CEMENT FIN. GREEN
(EPOXY PAINT, A-2 SCALE: 1:100m A-2 SCALE: 1:100m

GREEN)/OPTIONAL
PLAIN CEMENT FLR.
FL-2
FIN. W/ GROOVE (ROUGH)

CONSULTANT / DESIGNER REVIEWED BY: RECOMMENDING APPROVAL : APPROVED FOR ACCREDITATION : CONCURRED : PROJECT TITLE : PROJECT NO: 01-002 OWNER : SHEET NO:

REPUBLIC OF THE PHILIPPINES DESIGNED BY: AZB


E

ONE STOREY DEPARTMENT OF EDUCATION


A-2
t h e PH F A
f
o IL
IC I

DEPARTMENT OF EDUCATION (DepED) A-1


T
M
L

P
B

TA
PU

I TO R I NG
IN

SK

EMMANUEL P. CUNTAPAY
RE

ES

SOFIA T. SANTIAGO GILBERTO S. REYES RAMON C. BACANI


DepED
F O RC E

ALBERT Z. DE BELEN
THREE CLASSROOM
ON

ENCODED BY: Max C


D

TASK FORCE ENGINEERING, ASSESSMENT AND MONITORING


M
PE

NO

EN

MCMXCIX
&

IN
G
I
A

E N
E
R

ER
T

IN SM
A

A S SE S
T C
M U G ,

7x9m (STANDARD)
E

CHIEF, ARCHITECTURAL DIVISION


DE
TN

OIC, DIRECTOR III OIC, DIRECTOR IV


F O

UNDERSECRETARY

3
MERALCO AVENUE, PASIG CITY ARCHITECT IV
SHEET CONTENTS :
BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH CHECKED BY: PERSPECTIVE VIEW
8
0010990 149 460 161 DEPATMENT OF EDUCATION (DepED)
PRC NO. : TIN :
TABLE
FLOOR, CEILING OF
PLANS, CONTENTS
ELEVATIONS
27 OCT. 2002
PTR NO. : DATE : LOCATION : DATE : LONGITUDINAL SECTION
01 03

NOTE:
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF TASK FORCE ENGINEERING, ASSESSMENT AND
MONITORING AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


4 EQ. PARTS= 2 EQUAL PARTS =
1000 2500 2-16 BOLTS
1250
A
6mm THK PLYWOOD w/6mm
GROOVE ON 50x50mm CEILING VENT
1242 (SEE DETAIL)
NAILERS @600mm OC BW

300

1230 300

1230 300
GA#26 CORR. ROOFING SHEET

(14-BLADES)

(14-BLADES)
1100 (PAINT FIN)
(PAINT FIN.)
GA#26 CORR. G.I. ROOFING SHEET SAG ROD (SEE DETAIL)

138
(PAINT FIN.)
SEE STRUCTURAL DETAIL TOP OF V2

2400

2400

2400
ROOF BEAM
STL. PURLINS (SEE STRUCTURAL

400
2100
CONC.
BEAM
12x300mm FIBER CEMENT FASCIA DET.)
10mm THICK PLATE
BOARD (PAINT FIN.) TECK SCREW
TECK SCREW 6mm GROOVE

875

875
6mm THK. MARINE PLYWOOD 300x150x10mm BASE
V1
INT. CEILING w/6MM GROOVE ON PLATE

50x50mm CEILING JOIST @600mm OC 4-16x300mm LONG


BOTHWAYS (PAINT FIN.) PROVIDE VENT BENT ANCHOR
AS SHOWN

2800
W-1 BOLTS

300
50 25 25 25
425
W-1 W-2
D-1 VENTILLATION W/
6mm THK. MARINE FULLY WELD
JALOUSIE WINDOW W/ CLEAR GLASS SAME AS W-1 WIRE MESH
PLYWOOD ON ON RAFTER
PANEL DOOR TYPE HINGED BLADES ON STD. ALUM. HOUSING & 150 mm THK. CHB WALL WITH PLAIN 50x50mm CLG. JST.
DOOR & FIXED CLEAR FIXED CLEAR GLASS TRANSOMS ON CEMENT PLASTER (PAINT FIN.) 12x300mm FIBER @600mm O.C. BW.

900
GLASS TRANSOM ON 50x150mm WD. JAMBS/FRAMES CEMENT FASCIA (OPTIONAL) 9

300
50x150mm WOOD PART OF BOARD
JAMBS/FRAMES CLASSROOM A-3
FIN. FLOOR LINE
SCHEDULE OF DOORS & WINDOWS

VAR.
3 FIN. GRADE LINE
20x20x2mm ANGULAR
BAR FOR FASCIA BD.
A-3
EAVES, VENT. & INT CEILING DETAIL
SCALE: 1 : 100 M
FRAME WELDED TO
RAFTERS AND
8
4 BAY SECTION PURLINS
A-3 SCALE : 1:10mts
C
GA#26 CORR. G.I. A-3 SCALE: 1 : 20 M

ROOFING SHEET (PAINT


FIN.)
9 DETAIL
1500
10mm SAG RODS
7
A-3 SCALE : 1:10mts NOTE:
C-PURLINS (SEE A-4 1. IF THERE'S EXTERIOR CEILING PROVIDE

23
GA#26 PLAIN GI RIDGE STRUCTURAL DET.) TOP OF ROOF BEAM V2.

C B A ROLL (PAINT FIN.)


6mm THK. ORD. PLYWOOD 2. IF THERE'S NO EXTERIOR CEILING
300x300mm EXT. CONC. PROVIDE V1.
INT. CEILING ON 50x50mm
LOUVER BLOCKS (150X400)
7000 CEILING JOIST @600mm OC

300
GA.#26 CORR. G.I. ROOFING BOTHWAYS (PAINT FIN.)
1500 3500 3500 1100 325 50
SHEET (PAINT FINISH)
TOP OF TRUSS VENT. WITH 275
6mm THK. PLYWOOD CEILING WIRE MESH INSECT 12x300mm FIBER
50
00 ON 50X50mm CEILING JOIST SP. CEMENT FASCIA 25x25 mm WOOD VENT
16 SCREEN (SEE DETAIL) 6mm THK. MARINE
53
1780

@600mm O.C. BOTHWAYS (PAINT BOARD (PAINT PROVIDE INSECT SCREEN

2800
PLYWOOD ON
FINISH) FIN.)
50x50mm CLG. JST.
TOP OF ROOF BEAM
@600mm O.C. BW.

2216
150mm THK. CHB WALL
GA#26 PLAIN GI. GA#26 CORR. GI. ROOF
PLAIN CEM. PLASTER (PAINT FIN.) 13
12x300mm FIBER CEMENT FLASHING
D-1
6mm THK. ORD. CLNG. PLY CEILING 62
FASCIA BOARD (PAINT FIN.) C-PURLIN SEE
2800

FR. 25x75mm WD.FRAME ON 50X50 CLNG. JOISTS SP.


W-1
S4S KD TANG. STRUCTURAL DET.
PART OF @600mm O.C. BW ( PAINT FIN. )
CORRIDOR

75
D-1 6mm THK MARINE PLYWOOD
CLASSROOM CLASSROOM
ON 50x50mm CEILING JOIST

2
FIN. FLR. LN.
CLASSROOM @600mm O.C. BW. FIN. FLOOR LINE

25
VAR.

VAR.
(OPTIONAL) RAFTER SEE

SECTION (V1)
FIN. GRD. LN. FIN. GRADE LINE
STRUCTURAL DET.
150 mm THK. CHB WALL

25
CROSS SECTION
20x20x5mm ANGULAR BAR
2 WITH PLAIN CEMENT 1500
25x25mm WOOD @600mm OC VERT.
PLASTER (PAINT FIN.) VENT PROVIDE MEMBER FOR FRAME OF
A-3 SCALE: 1:100 M
5 DETAIL SECTION 575 575 INSECT SCREEN 12x300mm FIBER CEMENT
200

275
FASCIA BOARD

A-3 SCALE: 1:20 mts.

10 EAVES DETAIL
1 2 GA#26 CORR. G.I.
3 GA#26 PLAIN G.I.
4 5 6 7

275
ROOFING SHEET
RIDGE ROLL (PAINT
(PAINT FIN) FIN.) A-3 SCALE : 1:20M
9000 9000 9000

400 4500 4500 4500 4500 4500 4500 400


25
25x25mm WOOD VENT
PLAN PROVIDE INSECT SCREEN
SECTION (V2)
1100

A 7 TYP. CLG. VENT PLAN DETAIL


A-3 SCALE : 1 : 10 M
3500

CLASSROOM
SLOPE SLOPE SLOPE EL. +175mm 100
100
TYPICAL

B
7000

RAMP UP

6mm
600 6mm

1200
6mm
300

1500
SLOPE SLOPE SLOPE CORRIDOR NON-SKID
PLAIN CE
MENT FL
OOR CEM
3500

EMNT FINISH
LOUVER
LINE OF ROOF
BLOCKS 20x20x3mm THK ANGULAR
1800

600
(CONCRETE) FRAME FOR VENT. WELDED
LINE OF CORRIDOR
TO PURLINS

C BUILDING LINE BUILDING LINE BUILDING LINE


INSIDE DETAIL SECTION
1500

OUTSIDE DETAIL PLAN SCALE 1:5 M


ELEVATION
SCALE 1:50 M

SECTION
GA#26 PLAIN G.I. FLASHING
ON 12x300mm FIBER CEMENT
1 ROOF PLAN 6 LOUVER BLOCKS DETAIL 11 RAMP DETAILS
FASCIA BOARD (PAINT FIN.)
A-3 SCALE: AS SHOWN
A-3 SCALE: 1:100 M
A-3 SCALE : 1:20M

CONSULTANT / DESIGNER REVIEWED BY: RECOMMENDING APPROVAL : APPROVED FOR ACCREDITATION : CONCURRED : PROJECT TITLE : PROJECT NO: 01-002 OWNER : SHEET NO:

REPUBLIC OF THE PHILIPPINES DESIGNED BY: AZB


E

ONE STOREY DEPARTMENT OF EDUCATION


A-3
t h e PH F A
f
o IL
IC I

DEPARTMENT OF EDUCATION (DepED) A-1


T
M
L

P
B

TA
PU

I TO R I NG
IN

SK

EMMANUEL P. CUNTAPAY
RE

ES

SOFIA T. SANTIAGO GILBERTO S. REYES RAMON C. BACANI


DepED
F O RC E

ALBERT Z. DE BELEN
THREE CLASSROOM
ON

ENCODED BY: Max C


D

TASK FORCE ENGINEERING, ASSESSMENT AND MONITORING


M
PE

NO

EN

MCMXCIX
&

IN
G
I
A

E N
E
R

ER
T

IN SM
A

A S SE S
T C
M U G ,

7x9m (STANDARD)
E

CHIEF, ARCHITECTURAL DIVISION


DE
TN

OIC, DIRECTOR III OIC, DIRECTOR IV


F O

UNDERSECRETARY

3
MERALCO AVENUE, PASIG CITY ARCHITECT IV
SHEET CONTENTS :
BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH CHECKED BY: PERSPECTIVE VIEW
8
0010990 149 460 161 DEPATMENT OF EDUCATION (DepED)
PRC NO. : TIN :
TABLE
ROOF PLAN, OF CONTENTS
SCH. OF DOORS & WINDOWS
27 OCT. 2002
PTR NO. : DATE : LOCATION : DATE : BAY & DETAIL SECTION, EAVES,
01 03
LOUVER BLK, VENT, RAMP DET.

NOTE:
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF TASK FORCE ENGINEERING, ASSESSMENT AND
MONITORING AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


1 2 3 4 5 6 7
9000 9000 9000

4500 4500 4500 4500 4500 4500

F-1 F-2 F-3 F-2 F-3 F-2 F-1


C-1 C-2 C-1 C-2 C-1 C-2 C-1

A
WF-1 WF-1 WF-1 WF-1 WF-1 WF-1

3500

WF-1
WF-1

WF-1

WF-1
F-1 F-1 F-1 F-1
C-1 C-1 C-1 C-1

7000
B
100mm THICK SLAB ON FILL WITH
10mm SPACED AT 400
BOTHWAYS

WF-1
WF-1

WF-1

WF-1
3500
F-1 F-2 F-3 F-2 F-3 F-2 F-1
C-1 C-2 C-1 C-2 C-1 C-2 C-1
C
WF-1 WF-1 WF-1 WF-1 WF-1 WF-1

1500
RAMP UP

1200
1800

A FOUNDATION PLAN
S-1 SCALE 1:100 M.

1 2 3 4 5 6 7
9000 9000 9000 50x100x15x1.5mm
400 4500 4500 4500 4500 4500 4500 400 STEEL C-PURLINS
750mm O.C.
1100

A
RG-1 RG-1 RG-1 RG-1 RG-1 RG-1
10mm SAG ROD
WITH STANDARD
NUTS & WASHERS
@ EACH END
3500

RG-2

RG-2

RG-2
RG-2
EB-1

EB-1

EB-1

EB-1
R - 1

R - 1

R - 1

R - 1

R - 1

R - 1
R - 2

R - 2

R - 2
R - 2
7000

B
3500

RG-2

RG-2

RG-2

RG-2
EB-1

EB-1

EB-1

EB-1
RG-1 RG-1 RG-1 RG-1 RG-1 RG-1

C
1500

B ROOF FRAMING PLAN


S-1 SCALE 1:100 M.

CONSULTANT / DESIGNER REVIEWED BY: RECOMMENDING APPROVAL : APPROVED FOR ACCREDITATION : CONCURRED : PROJECT TITLE : PROJECT NO: 01-002 OWNER : SHEET NO:

REPUBLIC OF THE PHILIPPINES DESIGNED BY: AZB


IC
o
f t h e PH
IL
I
F
E A

THREE STOREY DEPARTMENT OF EDUCATION


DEPARTMENT OF EDUCATION (DepED) A-1
T
M
L

P
B

TA
PU

I TO R I NG
IN

SK

EMMANUEL P. CUNTAPAY
RE

ES

SOFIA T. SANTIAGO GILBERTO S. REYES RAMON C. BACANI


DepED S-1
F O RC E

ALBERT Z. DE BELEN
TWO CLASSROOM
ON

ENCODED BY: Max C


D

TASK FORCE ENGINEERING, ASSESSMENT AND MONITORING


M
PE

NO

EN

MCMXCIX
&

IN
G
I
A

E N
E
R

ER
T

IN SM
A

A S SE S
T C
M U G ,

7x9m (STANDARD)
E

CHIEF, ARCHITECTURAL DIVISION


DE
TN

OIC, DIRECTOR III OIC, DIRECTOR IV


F O

ARCHITECT IV UNDERSECRETARY
MERALCO AVENUE, PASIG CITY
3
SHEET CONTENTS :
BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH CHECKED BY: PERSPECTIVE VIEW
8
0010990 149 460 161 DEPATMENT OF EDUCATION (DepED) FOUNDATION PLAN
PRC NO. : TIN :
TABLE OF CONTENTS
PTR NO. : DATE :
27 OCT. 2002 ROOF FRAMING PLAN
LOCATION : DATE : 01 03

NOTE:
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF TASK FORCE ENGINEERING, ASSESSMENT AND
MONITORING AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


L1 L2

2D LAP SPLICES ARE ALLOWED 2D 2D LAP SPLICES ARE ALLOWED 2D

ONLY IN THIS PORTION ONLY IN THIS PORTION

COLUMN SCHEDULE

2-10mm SIDE BARS


LEVEL C-1 C-2

400 400
A TYPICAL BEAM ELEVATION
S-2

160

160
FOUNDATION LEVEL
B E A M S C H E D U L E

TO ROOF LEVEL
BEAM STEEL REINFORCEMENTS MAIN BAR: MAIN BAR:
FLOOR BEAM DIMENSIONS STIRRUPS
( in / mm ) LEFT MID SPAN RIGHT 4-%16mm 6-%16mm
LEVEL MARK REBAR 10mm

(mm ) (UNLESS NOTED OTHERWISE) TIES : 10 mm TIES : 10 mm


b h TOP BOTTOM TOP BOTTOM TOP BOTTOM

1@50, 8@75, REST @ 1@50, 8@75, REST @


RG-1 150 400 12mm 2 2 2 2 2 2 1@50, 8@100, REST@200 150mm TO CENTER 150mm TO CENTER
ROOF LEVEL

RG-2 150 400 12mm 2 2 2 2 2 2 1@50, 6@100, REST@200

1@50, 6@100, REST@200

EB-1 150 250 10mm 2 2 2 2 2 2 1@50, REST@200

1
L

NGL
1800

10 300mm TEMP
BARS BOTHWAYS

150
Y-BARS
D

X-BARS
W

10mm
t

Y-BARS
100

X-BARS

L 100mm THK.

PLAN SECTION
GRAVEL BEDDING
D DETAIL OF RAMP
SCALE 1 : 50M
S-2
B TYP. FOOTING DETAIL 150MM THK.
CHB
SCALE : NTS
S-2
10@600
HOR. BARS

NATURAL GRADE LINE

DESIGN CRITERIA :
10@600
SCHEDULE OF FOOTINGS VERT. BARS

A. CONCRETE

600
fc' = 20.685 Mpa ( 3,000 Psi ), minimum compressive strength of concrete
FOOTING
FOOTING DIMENSIONS (mm) REINFORCEMENT
a 28 days unless otherwise specified.
REMARKS
MARK LENGTH WIDTH DEPTH THICKNESS B. REBAR

250
BAR X BAR Y
(L) (W) (D) (t)
fy = 275.8 Mpa ( 40,000 Psi ), minimum yield strength of reinforcing bars
SQUARE FOOTING G-20mm GRAVEL 3-10mm unless otherwise specified.
F-1 800 800 1200 250 4 - 16mm% 4 - 16mm%
BEDDING 10mm @300 CUT BARS C. STRUCTURAL STEEL
400
F-2 1000 1000 1200 250 4 - 16mm% 4 - 16mm% SQUARE FOOTING
Fy = 248 Mpa ( 36 Ksi ), specified minimum yield strength

F-3 900 900 1200 250 4 - 16mm% 4 - 16mm% SQUARE FOOTING


C DETAIL OF WF-1 D. FOUNDATION
unless otherwise specified.

SCALE : NTS.
S-2 SBP = 95.706 Kpa ( 2,000 Psf ), was used in the design for all footings.
No footing shall rest on fill.

CONSULTANT / DESIGNER REVIEWED BY: RECOMMENDING APPROVAL : APPROVED FOR ACCREDITATION : CONCURRED : PROJECT TITLE : PROJECT NO: 01-002 OWNER : SHEET NO:

REPUBLIC OF THE PHILIPPINES DESIGNED BY: AZB


IC
o
f t h e PH
IL
I
F
E A

ONE STOREY DEPARTMENT OF EDUCATION


DEPARTMENT OF EDUCATION (DepED) A-1
T
M
L

P
B

TA
PU

I TO R I NG
IN

SK

EMMANUEL P. CUNTAPAY
RE

ES

SOFIA T. SANTIAGO GILBERTO S. REYES RAMON C. BACANI


DepED
F O RC E

ALBERT Z. DE BELEN
THREE CLASSROOM S-2
ON

ENCODED BY: Max C


D

TASK FORCE ENGINEERING, ASSESSMENT AND MONITORING


M
PE

NO

EN

MCMXCIX
&

IN
G
I
A

E N
E
R

ER
T

IN SM
A

A S SE S
T C
M U G ,

7x9m (STANDARD)
E

CHIEF, ARCHITECTURAL DIVISION


DE
TN

OIC, DIRECTOR III OIC, DIRECTOR IV


F O

ARCHITECT IV UNDERSECRETARY
MERALCO AVENUE, PASIG CITY SHEET CONTENTS :
BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH CHECKED BY: PERSPECTIVE VIEW 3
8
0010990 149 460 161 DEPATMENT OF EDUCATION (DepED)
PRC NO. : TIN : TYPICAL BEAM DETAIL, BEAM SCHEDULE,
TABLE OF CONTENTS
PTR NO. : DATE :
27 OCT. 2002
LOCATION : DATE : 01 03
FOOTING DETAIL, COLUMN DETAIL, WF-1,
RAMP DET.
NOTE:
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF TASK FORCE ENGINEERING, ASSESSMENT AND
MONITORING AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


C B 1 A
S-
2

4-%16x300mm LONG
R- BENT ANCHOR BOLTS 65 65
2 1 2
R- B-

20

20
E EB 50
-1 300x150x10mm

15
300 BASE PLATE
50 50

37.5

150

150
RG-1 RG-2 RG-2 RG-1

100
37.5
LINE OF R-1/R-2
2LC-150x65x20x3 LC-150x65x20x3
R-1 R-2 LC-100x50x15x1.5
10mm THICK PLATE
PLAN

E DETAIL OF RAfTER F DETAIL OF PURLINS


A ELEV @ GRID 1&7 2-%16
BOLTS 2-%16
S-3
SCALE NTS
S-3
SCALE NTS

BOLTS
S-3 SCALE: 1:100 M
4-%16x300mm
LONG BENT R-1/R-2
ANCHOR BOLTS

300x150x10mm 10mm THICK PLATE

BASE PLATE
10mm THICK PLATE 4-%16x300mm LONG
BENT ANCHOR BOLTS
R
-1
300x150x10mm /R
-2
BASE PLATE

C B 2 A
S-
2
RC BEAM/COLUMN

R-1

R-
2 -1 2
R- EB EB R-2
-1
ELEVATION
ELEVATION
EB-1 10mm X 150mm EB-1 10mm X 150mm
RG-1 RG-2 RG-2 RG-1
TYPICAL RAFTER ANCHORAGE DETAIL (SEE SCHED) ANCHOR BOLTS ANCHOR BOLTS
(SEE SCHED)
D SPACED @ 800mm O.C. SPACED @ 1000mm O.C.

SCALE 1:20 M
S-3
1 SECTION DETAIL 2 SECTION DETAIL
SCALE NTS SCALE NTS
S-2 S-2

B ELEV @ GRID 3 & 5


S-3 SCALE: 1:100 M

100x50x15x1.5mm
STEEL C-PURLINS
750mm O.C.

10mm% SAG ROD WITH


STANDARD NUTS &

C B A 100x50x15x1.5mm
TOP OF RAFTER WASHERS @ EACH END
STEEL C-PURLINS
10mm TIE ROD WITH
750mm O.C.
STANDARD NUTS &
WASHERS @ EACH END
R-
CL.
1 1
R-
1-%10mm A-307 50x100x15x1.5mm
150 STEEL C-PURLINS
150
ANCHOR BOLT
750mm O.C.
L-50x50x4.5 R
-1
RG-1 /R
RG-1 -2
10mm SAG ROD

C ELEV BET GRIDLINES


S-3 SCALE: 1:100 M
G PURLIN CONNECTION DET
I SAG ROD CONNECTION DET.
S-3
SCALE 1:5M
H TIE ROD CONNECTION DET. SCALE 1 : 10 M
SCALE 1 : 10 M S-3
S-3

CONSULTANT / DESIGNER REVIEWED BY: RECOMMENDING APPROVAL : APPROVED FOR ACCREDITATION : CONCURRED : PROJECT TITLE : PROJECT NO: 01-002 OWNER : SHEET NO:

REPUBLIC OF THE PHILIPPINES DESIGNED BY: AZB


IC
o
f t h e PH
IL
I
F
E A

ONE STOREY DEPARTMENT OF EDUCATION


DEPARTMENT OF EDUCATION (DepED) A-1
T
M
L

P
B

TA
PU

I TO R I NG
IN

SK

EMMANUEL P. CUNTAPAY
RE

ES

SOFIA T. SANTIAGO GILBERTO S. REYES RAMON C. BACANI


DepED
F O RC E

ALBERT Z. DE BELEN
THREE CLASSROOM S-3
ON

ENCODED BY: Max C


D

TASK FORCE ENGINEERING, ASSESSMENT AND MONITORING


M
PE

NO

EN

MCMXCIX
&

IN
G
I
A

E N
E
R

ER
T

IN SM
A

A S SE S
T C
M U G ,

7x9m (STANDARD)
E

CHIEF, ARCHITECTURAL DIVISION


DE
TN

OIC, DIRECTOR III OIC, DIRECTOR IV


F O

UNDERSECRETARY
3
MERALCO AVENUE, PASIG CITY ARCHITECT IV
SHEET CONTENTS :
BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH CHECKED BY: PERSPECTIVE VIEW
8
0010990 149 460 161 DEPATMENT OF EDUCATION (DepED)
PRC NO. : TIN :
TABLE OF CONTENTS
ELEVATIONS
27 OCT. 2002
PTR NO. : DATE : LOCATION : DATE : 01 03 TYPICAL CONNECTION DETAIL

NOTE:
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF TASK FORCE ENGINEERING, ASSESSMENT AND
MONITORING AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


GENERAL NOTES LEGEND 1 2 3 4 5 6 7

SYMBOL DESCRIPTION
1. ALL ELECTRICAL WORKS SHALL COMPLY IN ACCORDANCE WITH
- CEILING LIGHT OUTLET
THESE PLANS AND SPECIFICATIONS. THE APPLICABLE PROVISIONS
2
- 2 x 40 WATTS FLUORESCENT LAMP
OF THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL CODE (PEC).
THE RULES AND REGULATION OF THE LOCAL ENFORCING AUTHORITY F - CEILING FAN OUTLET

AND THE REQUIREMENTS OF THE LOCAL POWER COMPANY. S/Sa - ONE GANG DEVICE SWITCH
A
THE ELECTRICAL WORKS SHALL BE UNDER IMMEDIATE SUPERVISION
S ab - TWO GANG DEVICE SWITCH
OF A DULY REGISTERED ELECTRICAL ENGINEER.
S cde - THREE GANG DEVICE SWITCH
2. THE ELECTRICAL SERVICE POWER IS 1-PHASE, 2-WIRE,
S
3W - THREE WAY DEVICE SWITCH
230 V AC, 60 Hz.

- FAN CONTROL SWITCH CLASSROOM CLASSROOM CLASSROOM


Sf
3. WIRING METHOD SHALL BE AS FOLLOWS :

a. FEEDERS AND RISERS - INTERMEDIATE METALLIC CONDUIT - RACEWAY CONDUIT CONCEALED IN CEILING B
b. LIGHTING, POWER RECEPTACLE - POLYVINYL CHLORIDE CONDUIT - RACEWAY CONDUIT CONCEALED UNDER FLOOR
BRANCH CKT., & AUXILIARY SCH. 40
- PANELBOARD LP

4. ALL WIRES SHALL BE COPPER AND THERMOPLASTIC INSULATED TYPE


- DUPLEX CONVENIENCE OUTLET, GROUNDING TYPE
"THW" UNLESS OTHERWISE INDICATED IN THE PLAN. THE MINIMUM LP

10 AMPS, 250 VOLT WITH MODERN PLATE COVER


SIZE OF WIRE FOR POWER AND LIGHTING CIRCUIT HOMERUN SHALL BE
C M

3.5mm AND INSULATED FOR 600 VOLTS. SMALLEST RACEWAY SHALL

RAMP UP

RAMP UP
- WEATHERPROOF TYPE WP WP

BE 15mm TRADE/NOMINAL SIZE. WP


DUPLEX CONVENIENCE OUTLET, GROUNDING TYPE
OVERHEAD SERVICE ENTRANCE

10 AMPS, 250 VOLT WITH MODERN PLATE COVER REFER TO RISER DIAGRAM

5. ALL OUTLET BOXES SHALL BE GALVANIZED GAGE NO. 16 DEEP


LP
TYPE WITH FACTORY KNOCKOUTS.
1 - HOMERUN DIRECT TO PANELBOARD

6. ALL MATERIALS TO BE USED SHALL BE BRAND NEW AND APPROVED 20


- CIRCUIT BREAKER, RATING AS INDICATED
TYPE FOR THE PARTICULAR LOCATION AND PURPOSE OF USAGE.
- ELECTRIC SERVICE METER
POWER LAYOUT
M

7. GROUNDING SYSTEM SHALL BE PROVIDED TO ALL LIGHTING AND - SERVICE ENTRANCE


POWER CIRCUIT AS PER PHILIPPINE ELECTRICAL CODE REQUIREMENT. SCALE 1:100 M

8. MOUNTING HEIGHT OF WIRING DEVICES SHALL BE AS FOLLOWS :

a. LIGHT SWITCH - 1.20 M ABOVE FINISH FLOOR

b. CONVENIENCE OUTLET - 0.30 M ABOVE FINISH FLOOR.

c. PANELBOARD - 1.80 M ABOVE FINISH FLOOR

1 2 3 4 5 6 7

LOAD SCHEDULE

OVERHEAD SERVICE ENTRANCE


CONNECTED TO 220V AC, 1%,
2 WIRE, 60 Hz FITTED WITH
25mm O TYPE "F" CONDULET

A
PANELBOARD: LP MAIN : 60AT, 100AF, 2P, 230V
CEILING LINE
a b c d e f
BUILDING WALL
CIRCUIT BREAKER
CKT. VA
DESCRIPTION WIRE & CONDUIT SIZE METERING CONDUIT
2 2 2 2 2 2

NO. LOAD
VOLT POLE AT AF 2-14mm THW
KWHR METER
IN 25mmRSC

CONV. OUTLET - 8 x 180W


1 1440 230 2 20 50 3-3.5mm THW IN 15mm% C
B F F F

3500 mm
2 LIGHTING OUTLET - 8 x 100W 800 230 2 20 50 3-3.5mm THW IN 15mm% C

a b c d e f
3 LIGHTING OUTLET - 10 x 100W 1000 230 2 20 50 3-3.5mm THW IN 15mm% C
1800 mm

1800 mm

2 2 2 2 2 2

4 SPARE 1500 230 2 20 50

TOTAL 4740 LP LP

Sab Sf Scd Sf 3
Sef Sf 2

GROUND FLOOR LINE


C
Sg Shi

RAMP UP

RAMP UP
IL = 4740 = 20.6 A FEEDER: 2-14mm THW IN 25mm C
FIN. GRADE LINE
g h i
2

PROTECTION: 60 AT, 100 AF, 2P, 230 V


2 2
230 V 1-5.5mm THW COPPER WIRE
IN 15mm% C

16MM% x 2400mm LENGTH


GROUNDING ROD COPPERWELD

ELECTRICAL RISER DIAGRAM LIGHTING LAYOUT


NOT TO SCALE SCALE 1:100 M

CONSULTANT / DESIGNER REVIEWED BY: RECOMMENDING APPROVAL : APPROVED FOR ACCREDITATION : CONCURRED : PROJECT TITLE : PROJECT NO: 99-009
99-001 OWNER : SHEET NO:

REPUBLIC OF THE PHILIPPINES RDS


DESIGNED BY: RDS
IC
o
f t h e PH
IL
I
F
E A

ONE STOREY DEPARTMENT OF EDUCATION


DEPARTMENT OF EDUCATION (DepED) A-1
T
M

E-1
L

P
B

TA
PU

I TO R I NG
IN

SK

EMMANUEL P. CUNTAPAY
RE

ES

SOFIA T. SANTIAGO GILBERTO S. REYES RAMON C. BACANI


DepED
F O RC E

ALBERT Z. DE BELEN
THREE CLASSROOM
ON

RDS
ENCODED BY: RDS
D

TASK FORCE ENGINEERING, ASSESSMENT AND MONITORING


M
PE

NO

EN

MCMXCIX
&

IN
G
I
A

E N
E
R

ER
T

IN SM
A

A S SE S
T C
M U G ,

7x9m (STANDARD)
E

CHIEF, ARCHITECTURAL DIVISION


DE
TN

OIC, DIRECTOR III OIC, DIRECTOR IV


F O

ARCHITECT IV UNDERSECRETARY
MERALCO AVENUE, PASIG CITY SHEET CONTENTS :
BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH CHECKED BY: LEGEND
PERSPECTIVE POWER
VIEW LAYOUT
8
DEPATMENT OF EDUCATION (DepED)
1
0010990 149 460 161
PRC NO. : TIN :
GENERAL NOTESOF CONTENTS
TABLE LOAD SCHEDULE
27 OCT. 2002
PTR NO. : DATE : LOCATION : DATE :5-5-00
: 5-5-00 LIGHTING LAYOUT RISER DIAGRAM

NOTE:
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF TASK FORCE ENGINEERING, ASSESSMENT AND
MONITORING AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


REPUBLIC OF THE PHILIPPINES

TABLE OFFICE OF THE CITY/MUNICIPAL


ENGINEER/BUILDING OFFICIAL
OF
CONTENTS
DISTRICT/CITY/MUNICIPALITY

LAND USE & ZONING


ARCHITECTURAL

A-1 PERSPECTIVE VIEW & TABLE OF


CONTENTS

A-2 GROUND, SECOND FLOOR, ROOF,


REFLECTED CEILING PLANS

A-3 LONGITUDINAL, CROSS SECTION,


FRONT, REAR, RIGHT, LEFT SIDE
ELEV.

A-4 LEFT SIDE ELEV., SCHED. OF LINE & GRADE


DOORS & WINDOWS, BALCONY
RAILING, EAVES,
VENT., & RAMP DETAILS

A-6 STAIR, HANDRAIL DETAILS

A-5 TOILET, CONC. COUNTER,


SUN BREAKER DETAILS

ARCHITECTURAL

STRUCTURAL

S-1 FOUNDATION, SCHEDULE OF SLAB STRUCTURAL


2ND FLOOR & ROOF FRAMING PLAN

1 PERSPECTIVE VIEW S-2 DET. STAIR ON GRADE, RAMP &


BEAM, FOOTING/TIE BEAM/COLUMN
A-1 SCALE : N T S
DETAIL
S-3 TRUSS DIAGRAM, STAIR DET.
DETAILS OF STEEL CONNECTION

SANITARY

ELECTRICAL

E-1 GEN. NOTES, LEGEND, LOAD


SCHEDULE, RISER DIAGRAM, SINGLE
LINE DIAGRAM

E-2 POWER LAYOUTS(GRND & 2ND FLR)


LIGHT'G LAYOUTS(GRND & 2ND FLR)
ELECTRICAL

SANITARY

P-1 PLUMBING RO-IN LAYOUT, ROOF MECHANICAL


DRAIN LAYOUT & ISOMETRIC VIEW

P-2 SEPTIC TANK, CATCH BASIN DETAILS


LEGEND, NOTES & DESIGN CRITERIA

CONSULTANT / DESIGNER REVIEWED BY: RECOMMENDING APPROVAL : APPROVED FOR ACCREDITATION : CONCURRED : PROJECT TITLE : PROJECT NO: OWNER : SHEET NO:

REPUBLIC OF THE PHILIPPINES DESIGNED BY:


IC
o
f t h e PH
IL
I
F
E A

TWO STOREY DEPARTMENT OF EDUCATION


DEPARTMENT OF EDUCATION (DepED) A-1
T
M
L

P
B

TA
PU

I TO R I NG
IN

SK
RE

EMMANUEL P. CUNTAPAY
ES

SOFIA T. SANTIAGO GILBERTO S. REYES RAMON C. BACANI


DepED
F O RC E

ALBERT Z. DE BELEN
FOUR CLASSROOM
ON

ENCODED BY: Max C


D

TASK FORCE ENGINEERING, ASSESSMENT AND MONITORING


M
PE

NO

EN

MCMXCIX
&

IN
G
I
A

E N
E
R

ER
T

IN SM
A

A S SE S
T C
M U G ,

SCHOOL BUILDING
E DE

CHIEF, ARCHITECTURAL DIVISION


TN

OIC, DIRECTOR III OIC, DIRECTOR IV


F O

ARCHITECT IV UNDERSECRETARY
MERALCO AVENUE, PASIG CITY SHEET CONTENTS :
BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH DEPATMENT OF EDUCATION (DepED) CHECKED BY: PERSPECTIVE VIEW
6
0010990 149 460 161
PRC NO. : TIN :
TABLE OF CONTENTS
27 OCT. 2002
PTR NO. : DATE : LOCATION : DATE :

THE REVIEW & APPROVAL OF THIS PLANS BY THE DPWH DOES NOT RELIEVE THE DESIGNER/CONSULTANT NOTE:
FROM RESPONSIBILTY FOR THE SAFETY OF THE COMPLETED FACILITIES AS WELL AS FOR THE FAILURE THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF TASK FORCE ENGINEERING, ASSESSMENT AND
OF THE SAME DUE TO FAULTY DESIGN. MONITORING AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


CONCRETE SUNBREAKER
1 2 3 4 5 6 1 2 3 4 5 8 6mm THK. MARINE PLYWOOD CEILING

w/GROOVE ON 50x50mm CEILING


9000 9000 4500 600 9000 9000 4500 600
JOISTS (PAINT FIN.)
150mm THK. CHB WALL 4500 4500 4500 4500 600 4500 4500 4500 4500
PLASTER AND PAINT FIN. CONCRETE CEILING VENT. (SEE
SUNBREAKER (SEE DETAIL)
DETAIL) GA.24 PLAIN G.I. GUTTER
1 ON 12x300mm THK.

A-3 FIBER CEMENT FASCIA

675

1000
BOARD
A
W-1
WF1
A
W-1 W-1 W-1 W-1

LANDING LIGHTING FIXTURE


WF1 WF1

6mm THK. ORD PLYWOOD CEILING

dn. w/6mm GROOVE ON 50x50mm


CLEILING JOISTS (PAINT FIN.)
7000

CLASSROOM-3 CLASSROOM-4

7000
FL-1 FL-1

CHALKBOARD

CHALKBOARD
WF1

W-2 W-2 W-2 W-2


D-1 D-1 D-1 D-1

B
b
25mm 25mm 25mm 25mm
DEP. DEP. DEP. DEP.
2500

2500
FL1 C O R R I D O R

FD FD FD FD FD
FD FD

C
c

1000
RAILING (SEE DETAIL) ROOF LINE

SECOND FLOOR PLAN


A-3
1

A-2 SCALE : 1 : 100 METERS

4 SECOND FLOOR REFLECTED CEILING PLAN


A-2 SCALE : 1 : 100 METERS

1 2 3 4 5 6
9000 9000 4500

4500 4500 4500 4500


1 2 3 4 5 8
150mm THK. CHB WALL
1
PLASTER AND PAINT FIN.
A-3 9000 9000

600 4500 4500 4500 4500 4500 600

LN. OF SUNBREAKER
W-3 W-4
675

800
850
WF1 1100 WF1
SHE 1
W-1 W-1 W-1 W-1 HE RD RD RD RD RD RD
D-4 D-4 A-3

1000
D-3

1100
800

D-3

A
D-2

7000
7000

CLASSROOM CLASSROOM HCR

1 1

4776
9500

FL1 FL1 GA.26 CORR. G.I.


SHEET ROOFING

7000
WF1
PAINT FINISH

W-2 W-2 W-2 W-2


D-1 D-1 D-1 D-1 GA. 26 PLAIN G.I. SHT.

B
RIDGE ROLL PAINT FIN.
25mm 25mm
25mm 25mm
DEP. DEP.
DEP. DEP. UP
2500

FL1 C O R R I D O R

FD FD FD FD FD FD FD
B GA.26 PLAIN.
SHEET FLASHING
G.I.
ON
C 12x300mm FIBER

2500
CEMENT FASCIA BOARD
UP RAMP PAINT FINISH
RAILING (SEE DETAIL) UP

2
ENTRY A-4 C 1000
LN. OF STRUCTURE

GA.26 PLAIN. G.I.


RD RD RD RD RD RD SHEET GUTTER

2 GROUND FLOOR PLAN 7


PAINT FINISH

A-2 SCALE : 1 : 100 METERS


A-4
3 ROOF PLAN
A-2 1
SCALE : : 100 METERS

CONSULTANT / DESIGNER REVIEWED BY: RECOMMENDING APPROVAL : APPROVED FOR ACCREDITATION : CONCURRED : PROJECT TITLE : PROJECT NO: OWNER : SHEET NO:

REPUBLIC OF THE PHILIPPINES DESIGNED BY:


IC
o
f t h e PH
IL
I
F
E A

TWO STOREY DEPARTMENT OF EDUCATION


DEPARTMENT OF EDUCATION (DepED) A-2
T
M
L

P
B

TA
PU

I TO R I NG
IN

SK
RE

EMMANUEL P. CUNTAPAY
ES

SOFIA T. SANTIAGO GILBERTO S. REYES RAMON C. BACANI


DepED
F O RC E

ALBERT Z. DE BELEN
FOUR CLASSROOM
ON

ENCODED BY: Max C


D

TASK FORCE ENGINEERING, ASSESSMENT AND MONITORING


M
PE

NO

EN

MCMXCIX
&

IN
G
I
A

E N
E
R

ER
T

IN SM
A

A S SE S
T C
M U G ,

SCHOOL BUILDING
E DE

CHIEF, ARCHITECTURAL DIVISION


TN

OIC, DIRECTOR III OIC, DIRECTOR IV


F O

ARCHITECT IV UNDERSECRETARY
MERALCO AVENUE, PASIG CITY SHEET CONTENTS :
BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH DEPATMENT OF EDUCATION (DepED) CHECKED BY:
GROUND, SECOND,
6
0010990 149 460 161
PRC NO. : TIN :
REFLECTED CEILING,
27 OCT. 2002
PTR NO. : DATE : LOCATION : DATE : & ROOF PLAN

THE REVIEW & APPROVAL OF THIS PLANS BY THE DPWH DOES NOT RELIEVE THE DESIGNER/CONSULTANT NOTE:
FROM RESPONSIBILTY FOR THE SAFETY OF THE COMPLETED FACILITIES AS WELL AS FOR THE FAILURE THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF TASK FORCE ENGINEERING, ASSESSMENT AND
OF THE SAME DUE TO FAULTY DESIGN. MONITORING AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


1 2 3 4 5 6

600 9000 9000

4500 4500 4500 4500 4500 600

APEX OF TRUSS

2500
SEE TRUSS DETAILS

TOP OF ROOF BEAM

3200
10200
W-1 CLASSROOM 3 W-1 W-1 CLASSROOM 4 W-1 W-1
SECOND FLOOR LEVEL
3 LONGITUDINAL SECTION
LANDING

A-3 SCALE : 100

W-3

3200
200x200mm
GLAZED WALL
TILES
A B C
A C
W-1 W-1 W-1 W-1
B
CLASSROOM 1 CLASSROOM 2
GROUND FLOOR LEVEL HE SHE

325
9500
NAT. GRD. LN.
9500 1000 7000 2500 1000
1000 7000 2500 1000
TOP OF TRUSS
EXPOSED CEILING UNDER
APEX LINE OF TRUSS
SLAB PAINT FIN.

GA. 26 CORR. G.I.


C B A

2500
9500
2500

SHEET ROOFING
SEE TRUSS DETAIL
(PAINT FINISH) 1000 2500 7000 1000

APEX LINE OF TRUSS


TOP OF ROOF BEAM
TOP OF ROOF BEAM

538
GA. 26 PLAIN G.I. SHEET GA. 26 CORR. G.I.
GUTTER ON 12x300mm SHEET ROOFING (PAINT

2500
FIBER CEMENT FASCIA BOARD FINISH)
(PAINT FINISH)

3200
3200

10
W-1 W-2
TOP OF ROOF BEAM GA. 26 PLAIN G.I.
A-5
SHEET GUTTER ON
12x300mm FIBER
150mm THK. CHB CLASSROOM
CEMENT FASCIA BOARD SECOND FLOOR LEVEL 3
CORRIDOR

6725
PLAIN PLASTER
SECOND FLR. LVL.
(PAINT FINISH)
6725

PAINTED FIN.

3200
50mm GA# 40
150mm THK. CHB PLAIN G.I. PIPE

3200
PLASTER PAINT FIN. HANDRAIL
12
3200

W-1 W-2
32mm G.I. PIPE SECOND FLR. LVL.
A-4

6725
HANDRAIL WITH 32mm 150mm THK.
VERT. SUPPORT CLASSROOM
GROUND FLOOR LEVEL 1 CHB WALL
@300mm O.C. (PAINT PLASTER PAINT

325
GROUND FLR. LVL.
FIN. GRD. LN.
325

FINISH) FIN.

3200
NAT. GRD. LN.
EXPOSE CEILING
32mm G.I. PIPE
UNDERSLAB PAINT FINISH
2 LEFT SIDE ELEVATION HANDRAIL
VERT.
WITH 32mm
SUPPORT 6 CROSS SECTION
GROUND FLR. LVL. @300mm O.C. (PAINT
A-3 SCALE : 1 : 100 METERS
A-3 SCALE : 1 : 100 METERS

325
NAT. GRD. LN. FINISH)

4 RIGHT SIDE ELEVATION


1 2 3 4 5 6 6 3 4 3 2 1
A-3 SCALE : 1 : 100 METERS

9000 9000 9000 9000 600


600 4500 4500 4500 4500 4500 600
600 4500 4500 4500 4500 4500

APEX LINE OF TRUSS APEX LINE OF TRUSS


GA.26 CORR. G.I.
GA.26 CORR G.I. SHEET
SHEET ROOFING
ROOFING (PAINT FIN.)
(PAINT FINISH)
2500

2500
GA.26 PLAIN G.I.
GA.26 PLAIN G.I.SHT. SHEET GUTTER ON
TOP OF ROOF BEAM TOP OF ROOF BEAM
GUTTER ON 12x300mm 12x300mm FIBER
THK FIBER CEMENT CEMENT FASCIA BD.
FASCIA BOARD (PAINT (PAINT FINISH)
FIN.)
3200

3200
D-1 D-1 D-1 D-1
PLAIN CEMENT
PLASTER PAINT WALL
100mm THK. CHB RAILING
FINISH

W-2 W-2 W-2 W-2


w/50mm G.I. PIPE HANDRAIL W-1 W-1 W-1 W-1 W-1
W-1
SECOND FLOOR LEVEL (PAINT FINISH) SECOND FLOOR LEVEL
6725

6725
GA. 26 CORR. G.I.
SHEET SUN BREAKER
ON STEEL FRAMING
3200

3200
D-1 D-1 D-1 D-1
(SEE DETAIL)
32mm G.I. PIPE W-4 W-3
HANDRAIL w/32mm
VERT. SUPPORT @300mm
D-1
W-2 W-2 W-2 W-2 O.C. (PAINT FIN.) W-1 W-1 W-1 W-1
GROUND FLOOR LEVEL GROUND FLOOR LEVEL
325

325
NAT. GRD. LN. FIN. GRD. LN.

1 FRONT ELEVATION 5 REAR ELEVATION


A-4 SCALE : 1 : 100 METERS
A-3 SCALE : 1 : 100 METERS

CONSULTANT / DESIGNER REVIEWED BY: RECOMMENDING APPROVAL : APPROVED FOR ACCREDITATION : CONCURRED : PROJECT TITLE : PROJECT NO: OWNER : SHEET NO:

REPUBLIC OF THE PHILIPPINES DESIGNED BY:


IC
o
f t h e PH
IL
I
F
E A

TWO STOREY DEPARTMENT OF EDUCATION


DEPARTMENT OF EDUCATION (DepED) A-3
T
M
L

P
B

TA
PU

I TO R I NG
IN

SK
RE

EMMANUEL P. CUNTAPAY
ES

SOFIA T. SANTIAGO GILBERTO S. REYES RAMON C. BACANI


DepED
F O RC E

ALBERT Z. DE BELEN
FOUR CLASSROOM
ON

ENCODED BY: Max C


D

TASK FORCE ENGINEERING, ASSESSMENT AND MONITORING


M
PE

NO

EN

MCMXCIX
&

IN
G
I
A

E N
E
R

ER
T

IN SM
A

A S SE S
T C
M U G ,

SCHOOL BUILDING
E DE

CHIEF, ARCHITECTURAL DIVISION


TN

OIC, DIRECTOR III OIC, DIRECTOR IV


F O

ARCHITECT IV UNDERSECRETARY
MERALCO AVENUE, PASIG CITY SHEET CONTENTS :
BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH DEPATMENT OF EDUCATION (DepED) CHECKED BY:
FRONT, REAR, RIGHT
6
0010990 149 460 161
PRC NO. : TIN :
ELEVATIONS
27 OCT. 2002
PTR NO. : DATE : LOCATION : DATE : SECTIONS

THE REVIEW & APPROVAL OF THIS PLANS BY THE DPWH DOES NOT RELIEVE THE DESIGNER/CONSULTANT NOTE:
FROM RESPONSIBILTY FOR THE SAFETY OF THE COMPLETED FACILITIES AS WELL AS FOR THE FAILURE THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF TASK FORCE ENGINEERING, ASSESSMENT AND
OF THE SAME DUE TO FAULTY DESIGN. MONITORING AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


1000 4 EQUAL PARTS = 2500 2 EQUAL PARTS = 1400 4 EQUAL PARTS = 2500
4 EQUAL PARTS = 600
700
900

7-BLADES

7-BLADES
300
300

300

635

635
600

14-BLADES

14-BLADES
1200

1200
2400
2400

2400

2400

2400
2100

2100
2054
STAINLESS STEEL

1200

1765

1765
KICKING PLATE
800

1500

900
900
300

300
FFL FFL

CLASSROOM TOILET (DISABLED) TOILET TOILET (CUBICLE)


JALOUSIE WINDOWS WITH CLEAR GLASS
BLADES ON STANDARD ALUMINUM
TANGUILE PANEL DOOR ON 50X150 MM HOLLOW CORE FLUSH TYPE SWING HOLLOW CORE FLUSH TYPE SWING DOOR SWING DOOR ON 50X100 JALOUSIE WINDOWS WITH CLEAR GLASS JALOUSIE WINDOWS WITH CLEAR GLASS BLADES JALOUSIE WINDOWS WITH CLEAR GLASS

THK. YACAL/GUIJO JAMB W/ FIXED DOOR W/ MARINE PLYWOOD FACING W/ MARINE PLYWOOD FACING INSIDE AND YACAL/GUIJO DOOR JAMB BLADES ON STANDARD ALUMINUM CASING ON STANDARD ALUMINUM CASING AND FIXED BLADES ON STANDARD ALUMINUM CASING W-4 CASING ON 50X150 YACAL/GUIJO
D-1 D-2 D-3 D-4
AND FIXED CLEAR GLASS TRANSOM ON CLEAR GLASS TRANSOM ON 50X150 JAMB COMPLETE WITH HARDWARES
CLEAR GLASS TRANSOM COMPLETE INSIDE AND ORDINARY OUTSIDE
ORDINARY OUTSIDE COMPLETE W/ COMPLETE WITH HARDWARES
W-1 W-2 W-3 ON 50X150 YACAL/GUIJO JAMB COMPLETE AND ACCESSORIES
WITH HARDWARES AND ACCESSORIES
COMPLETE W/ HARDWARES AND HARDWARES AND ACCESSORIES ACCESSORIES 50X150 YACAL/GUIJO JAMB COMPLETE WITH YACAL/GUIJO JAMB COMPLETE WITH WITH HARDWARES AND ACCESSORIES
ACCESSORIES PROVIDE KICK PLATE HARDWARES AND ACCESSORIES HARDWARES AND ACCESSORIES

1 FPLAN
CONCRETE HOLLOW GA#26 CORR. G.I.
BLOCKS
A-1 SCALE : 1:100 ROOFING SHT. PAINT FIN.

CONCRETE SLAB 1000


6mm THK. MARINE PLYWOOD
POLYETHYLENE SHEET DAMP PROOFING
TOP CHORD SEE STRUCTURAL DETAIL CEILING ON 50x50mm CEILING

GRAVEL BEDDING JOIST @600mm BW

38mm TEKSCREW 38mm TEKSCREW


2-32mm G.I. PIPE
C-PURLIN (SEE STRUC'L DETAIL) GA#26 GI STRAP

200
HANDRAIL w/32mm COPPER RIVET
VERT. SUPPORT @300mm SAG ROD SEE STRUCTURAL DETAIL
12x300mm FIBER CEMENT
OC (PAINT FIN.)
6mm THK. MARINE PLYWOOD CEILING
FASCIA BOARD FIX W/METAL
SCREW ON STL. FRAME PAINT
6 DAMP PROOFING DET. ON 50x50mm CEILING JOIST
FINISH

900
@600mm BW

NOT TO SCALE
GA#26 GI GUTTER PAINT FIN.
A-4 6mm THK. ORD. GA#26 GI STRAP
12mM STEEL DOWEL
PLYWOOD CEILING W/ ROOF

700
20x20X2mm ANGULAR BAR
EMBEDD IN CONC. 6mm GROOVE ON
9
BEAM GA#26 G.I. GUTTER ON 12x300mm FOR FASCIA BOARD FRAME
A-4 FIBER CEMENT FASCIA BOARD PAINT
NON-SKID PLAIN CEMENT 50x50mm CEILING COATED WITH PRIMER
32mm G.I. PIPE HANDRAIL FIN.
JOIST @600mm BW
w/32mm VERT. SUPPORT FLOOR FIN. w/ GROOVE
BASKET STRAINER
LINES (PAINT FIN.)
@1200mm O.C.(PAINT FIN.)

100
BASKET STRAINER

NON-SKID PLAIN
75mm PVC DOWNSPOUT PAINT
CEMENT FLOOR FINISH 8
2 FINISH
w/GROOVE LINES A-4
200

75mm PVC
A-4
DOWNSPOUT PAINT
CEILING VENT (SEE DETAIL)
200

900

FINISH
700

1200
900

7 8
SECTION DETAIL (EAVES) SPOT DETAIL (EAVES)
700

2A DETAIL SECTION
300

A-1 SCALE 1:10 M


A-4 SCALE : 1 : 40 m.
A-4 SCALE : 1:10 m.

SEE TRUSS DET.


3 DET. ELEVATION OF RAMP 100

A-4 SCALE 1:50 M


100X100 CONCRETE
SKIRTING
5 6
4500

6mm THK. ORD.


100

PLYWD. CEILING
32 mm G.I PIPE
(PAINTED) ON
150

VERTICAL SUPPORT
CONC. BEAM
@ 600mm ON CENTER 50x50mm CLG. JST.
PROVIDE 12mm STEEL @600mm OC BW
DOWELS (PAINTED FIN.)
B 10mm @250mm
ON CENTER

100
6mm THK. MARINE
FR. QUARTER-C
PLYWD. CEILING
MOULDING CEILING
CONTACT TO CONC. (PAINTED) ON

100
2500

50x50mm CLG. JST.


C O R R I D O R WALL
@600mm OC BW

5 SPOT DETAIL 9
1200
A-4 SCALE 1:5 M SPOT DETAIL (CORNER CLG) 12x12mm GROOVE

11 A-4 SCALE : 1 : 10 m.
BEAM REBARS SEE
STRUCTURAL DETAIL
25x25mm WOOD VENT.
A-4
C FR. 25x75mm WOOD PROVIDE INSECT SCREEN
175

FRAMEPAINT FIN.
50 12 325 12 50
675
1400
1400

RAMP UP

3
300

A-4

3600 12 CONCRETE SUNBREAKER DET.


NON-SKID PLAIN
CEMENT FLOOR
5150
1175 6 25 300
6mm THK PLYWOOD
A-4 SCALE: 1:10 mts.

FINISH w/GROOVE TOTAL RUN OF RAMP 32mm G.I. PIPE


25x25mm WOOD VENT FR.25x75mm CEILING ON 50x50mm
LINES
4 HANDRAIL w/32mm PROVIDE INSECT SCREEN VENT FRAME CEILING JOIST @600mm
VERT. SUPPORT @300mm
A-4 (PAINT FIN.) OC. BW (PAINT FIN.)
O.C. (PAINT FIN.)
11
2 DET. PLAN OF RAMP
10
DETAIL PLAN (VENT.) SECTION DETAIL (VENT.)
A-4 SCALE 1:50 M
A-4 SCALE : 1 : 10 m.
A-4 SCALE : 1 : 5 m

CONSULTANT / DESIGNER REVIEWED BY: RECOMMENDING APPROVAL : APPROVED FOR ACCREDITATION : CONCURRED : PROJECT TITLE : PROJECT NO: OWNER : SHEET NO:

REPUBLIC OF THE PHILIPPINES DESIGNED BY:


IC
o
f t h e PH
IL
I
F
E A

TWO STOREY DEPARTMENT OF EDUCATION


DEPARTMENT OF EDUCATION (DepED) A-4
T
M
L

P
B

TA
PU

I TO R I NG
IN

SK
RE

EMMANUEL P. CUNTAPAY
ES

SOFIA T. SANTIAGO GILBERTO S. REYES RAMON C. BACANI


DepED
F O RC E

ALBERT Z. DE BELEN
FOUR CLASSROOM
ON

ENCODED BY: Max C


D

TASK FORCE ENGINEERING, ASSESSMENT AND MONITORING


M
PE

NO

EN

MCMXCIX
&

IN
G
I
A

E N
E
R

ER
T

IN SM
A

A S SE S
T C
M U G ,

SCHOOL BUILDING
E DE

CHIEF, ARCHITECTURAL DIVISION


TN

OIC, DIRECTOR III OIC, DIRECTOR IV


F O

ARCHITECT IV UNDERSECRETARY
MERALCO AVENUE, PASIG CITY SHEET CONTENTS :
BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH DEPATMENT OF EDUCATION (DepED) CHECKED BY: DOOR AND WINDOW SCHEDULE
6
0010990 149 460 161
PRC NO. : TIN :
RAMP, EAVES, DETAILS
27 OCT. 2002
PTR NO. : DATE : LOCATION : DATE : SUN BREAKEER DETAIL

THE REVIEW & APPROVAL OF THIS PLANS BY THE DPWH DOES NOT RELIEVE THE DESIGNER/CONSULTANT NOTE:
FROM RESPONSIBILTY FOR THE SAFETY OF THE COMPLETED FACILITIES AS WELL AS FOR THE FAILURE THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF TASK FORCE ENGINEERING, ASSESSMENT AND
OF THE SAME DUE TO FAULTY DESIGN. MONITORING AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


3
5 A-5
6
5 50mm G.I. PIPE SCH.
50mm G.I. PIPE SCH. 250
40 PAINT FIN.
4500 A-5 40 PAINT FIN.
2200 2200 50mmG.I. PIPE SCH.
100 146 40 PAINT FIN.
100
50mm G.I. PIPE

50
SCHEDULE 40
19mm sQUARE BAR WELD (PAINT FINISH)
19mm SQUARE BAR
TO G.I. PIPE HANDRAIL
W-1 WELDED TO G.I. PIPE
@146mm O.C.
HANDRAIL @146mm O.C.

PLAIN CEMENT STEEL


19mm SQUARE BAR
TROWELL FIN.

900
WELDED TO G.I. PIPE
19mm SQUARE BAR
2500

LANDING HANDRAIL @146mm O.C.


WELDED TO G.I. PIPE

TYPICAL

W A L L
HANDRAIL @146mm O.C.
9

900
50
8
A-5

900

850
A-5 6 SECOND F.F.L.
5 HANDRAIL DETAIL

TYPICAL
A-5

168
18 17

146
ANCHOR @R.C. STAIR

19 16
A-5 SCALE : 1:20 mts

50
LANDING ANCHORED @R.C. STAIR
TREAD
15 50mm G.I. PIPE SCH.
DN
40 w/19mm SQ. BAR
@ 292mm EACH = 4672mm

14
@146mm ON CENTER 146
25x25x2mm ANGULAR
7000

13 PAINT FIN.
BAR NOSING
7 9 SPOT DETAIL
12 292
25
CRASH RAILING
TYPICAL
11
A-5 SCALE : 1:20 mts A-5 SCALE : 1:20 MTS

10
4 SECTION DETAIL

25
2x25x25mm
4672

A-5 SCALE : 1:20 mts


ANGULAR BAR

168
NOSING @STEP

12x12x2mm FLAT
16 TREADS

BAR STRAP
@600mm O.C.

175
50mm SCH. 40 G.I.
175 50mm G.I. PIPE
PIPE PAINT FIN. 50
SCHEDULE 40
50 50
6 NOSING DETAIL (PAINT FINISH)
19mm SQ. BAR

B A-5 SCALE : 1:10 mts ANCHORED TO THE WALL

(PAINT FIN.)

TREAD
(SECOND FLOOR TO GROUND FLOOR)

100

50
900mm FROM
2 DETAIL PLAN OF STAIR 19 mm SQUARE
BAR ANCHORED
TO THE WALL
1:50 mts
A-5 SCALE :
(PAINT FINISH)

5 6
7000 2500

8 SPOT DETAIL
ROOF LINE 2460 4540
4500

2200 A-5 SCALE : 1:5 MTS

2067

A 10 SPOT DETAIL
W-3 W-4
11 A-5 SCALE : 1:5 MTS
3200
1100

W-1 A-5
TOILET 4 146
2328
100

A-6

200
100 650 100
@168
850

900
700
SECOND FLOOR LINE CORRIDOR
2 RISERS

19 50mm G.I.PIPE SCH. 40


17
C HANDRAIL w/25mm SQ.
337

18
18 16
LANDING 17
50mm SCH. 40 G.I. BRACKECT @600mm O.C. C
16 PAINT FIN.
19 15 15
PIPE HANDRAIL w/19mm
SQ. BAR @146mm O.C
14
14 38mm STAINLESS
13
= 2856
292mm EACH = 4672mm

STEEL GRAB BAR 1


12 5

200
13
7000

W-3 0
5mm THK.

0
11

20
12 PLASTER PAINT FIN. FACIAL MIRROR 700 400 10
3200

100mm THK CHB RAILING

700
9
2863

@168

PLASTER AND PAINT FIN.


2763

11 8

600
7 SECOND FLOOR LEVEL

50
200x200mm VITRIFIED
10 50mm G.I. PIPE SCH.
GLAZED WALL TILES 6
RISERS

40 w/19mm SQ. BAR


295

300
5

1726
1625
4672

200
9 @146mm ON CENTER 292 4
PAINT FIN. CS LAV 3
8 342

168
WC

900

900
WC 2 ELEV.
787

700
17

7 1 DETAIL
GROUND FLOOR LINE SHE HCR CORRIDOR SCALE: 1:50m
@

SCALE: 1:20m
6
325

9 NATURAL GRADE LINE


16TREADS

BALCONY RAILING DET.


5
A-5 11
4
2460 4672
A-5 SCALE: AS SHOWN
292

3
16 TREADS @ 292 = 4672
50

B 1

UP 3 DETAIL SECTION OF STAIR


(GRD FLOOR TO SECOND FLOOR)
1 A-6 SCALE : 1:50 mts.

DETAIL PLAN OF STAIR


A-5 SCALE : 1:100 mts

CONSULTANT / DESIGNER REVIEWED BY: RECOMMENDING APPROVAL : APPROVED FOR ACCREDITATION : CONCURRED : PROJECT TITLE : PROJECT NO: OWNER : SHEET NO:

REPUBLIC OF THE PHILIPPINES DESIGNED BY:


IC
o
f t h e PH
IL
I
F
E A

TWO STOREY DEPARTMENT OF EDUCATION


DEPARTMENT OF EDUCATION (DepED) A-5
T
M
L

P
B

TA
PU

I TO R I NG
IN

SK
RE

EMMANUEL P. CUNTAPAY
ES

SOFIA T. SANTIAGO GILBERTO S. REYES RAMON C. BACANI


DepED
F O RC E

ALBERT Z. DE BELEN
FOUR CLASSROOM
ON

ENCODED BY: Max C


D

TASK FORCE ENGINEERING, ASSESSMENT AND MONITORING


M
PE

NO

EN

MCMXCIX
&

IN
G
I
A

E N
E
R

ER
T

IN SM
A

A S SE S
T C
M U G ,

SCHOOL BUILDING
E DE

CHIEF, ARCHITECTURAL DIVISION


TN

OIC, DIRECTOR III OIC, DIRECTOR IV


F O

ARCHITECT IV UNDERSECRETARY
MERALCO AVENUE, PASIG CITY SHEET CONTENTS :
BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH DEPATMENT OF EDUCATION (DepED) CHECKED BY:
STAIR, BALCONY RAILING
6
0010990 149 460 161
PRC NO. : TIN :

27 OCT. 2002
PTR NO. : DATE : LOCATION : DATE : DETAILS

THE REVIEW & APPROVAL OF THIS PLANS BY THE DPWH DOES NOT RELIEVE THE DESIGNER/CONSULTANT NOTE:
FROM RESPONSIBILTY FOR THE SAFETY OF THE COMPLETED FACILITIES AS WELL AS FOR THE FAILURE THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF TASK FORCE ENGINEERING, ASSESSMENT AND
OF THE SAME DUE TO FAULTY DESIGN. MONITORING AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


7 8 200x200mm GLAZED
WALL TILES
PLAIN CEM. PLASTERED 3mm THK. FACIAL
PAINT FIN. MIRROR ON AL. FRAMING
4500
PLAIN CEM. PLASTERED 1100
PAINT FIN.
PLAIN CEMENT PLASTER 700
PAINT WALL FINISH

100 1700 200X200 VITRIFIED 200x200mm VITRIFIED


CERAMIC WALL 1100
2ND FLR. LVL. WALL TILES (GLAZED)
TILES ( GLAZED ) W-3
350 400 350
4
512

600
LANDING LVL. A-7 LANDING

200

1710
3200

600
W-3 W-4 COUNTER SINK

300
2688

2738
2613

100

800
CONC. COUNTER

1600
SINK

300
800

WC
6

800
MALE A-7
CLASSROOM LVL. TOILET
50

300
TOILET LVL.

600 URINAL

5 DET.PLAN OF C. SINK 6 DETAIL ELEVATION


2 DETAIL SECTION OF TOILET
A-6 SCALE : 1:20 M
A-6 SCALE : 1:20 m.

A-6 SCALE : 1:40 m.

DET. SECTION
2680 1820

4 SPOT DETAIL
3
W-3 W-4 A-6 A-6 SCALE : 1:20 m.

8
A-5

850
SHE
1100

SECOND FLOOR LINE


HE
2
A-6 LANDING FLOOR LINE 17
D-4
2074

D-4
16
D-3 50mm SCH. 40 G.I.

PLASTER PAINT FIN.


15 PIPE HANDRAIL w/19mm
SQ. BAR @600mm OC.
UNDER SLAB 14
1100

9
13
850

D-3 38mm STAINLESS A-5


12
STEEL GRAB BAR
W-4
5mm THK. FACIAL 11

0
20
MIRROR 150mm THK CHB WALL
700 400 10 PLASTER PAINT FIN.

3200
9

2856
8

2763

600
7
200x200mm VITRIFIED
D-2
GLAZED WALL TILES 6

2100

2100
5

200
1700

300
1625
292 4
3
342
HCR

920
2

168
1
SHE HCR
GROUND FLOOR LINE

NATURAL GRADE LINE


1609 1074

1 DET. PLAN OF TOILET


A-6 SCALE : 1:30 m.
3 DET. SECTION OF TOILET/STAIR
A-6 SCALE : 1 : 30 m.

CONSULTANT / DESIGNER REVIEWED BY: RECOMMENDING APPROVAL : APPROVED FOR ACCREDITATION : CONCURRED : PROJECT TITLE : PROJECT NO: OWNER : SHEET NO:

REPUBLIC OF THE PHILIPPINES DESIGNED BY:


IC
o
f t h e PH
IL
I
F
E A

TWO STOREY DEPARTMENT OF EDUCATION


DEPARTMENT OF EDUCATION (DepED) A-6
T
M
L

P
B

TA
PU

I TO R I NG
IN

SK
RE

EMMANUEL P. CUNTAPAY
ES

SOFIA T. SANTIAGO GILBERTO S. REYES RAMON C. BACANI


DepED
F O RC E

ALBERT Z. DE BELEN
FOUR CLASSROOM
ON

ENCODED BY: Max C


D

TASK FORCE ENGINEERING, ASSESSMENT AND MONITORING


M
PE

NO

EN

MCMXCIX
&

IN
G
I
A

E N
E
R

ER
T

IN SM
A

A S SE S
T C
M U G ,

SCHOOL BUILDING
E DE

CHIEF, ARCHITECTURAL DIVISION


TN

OIC, DIRECTOR III OIC, DIRECTOR IV


F O

ARCHITECT IV UNDERSECRETARY
MERALCO AVENUE, PASIG CITY SHEET CONTENTS :
BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH DEPATMENT OF EDUCATION (DepED) CHECKED BY:

6
0010990 149 460 161
PRC NO. : TIN :
TOILET DETAILS
27 OCT. 2002
PTR NO. : DATE : LOCATION : DATE :

THE REVIEW & APPROVAL OF THIS PLANS BY THE DPWH DOES NOT RELIEVE THE DESIGNER/CONSULTANT NOTE:
FROM RESPONSIBILTY FOR THE SAFETY OF THE COMPLETED FACILITIES AS WELL AS FOR THE FAILURE THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF TASK FORCE ENGINEERING, ASSESSMENT AND
OF THE SAME DUE TO FAULTY DESIGN. MONITORING AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


1 2 3 4 5 6 1 2 3 4 5 6
4500 4500 4500 4500 4500

4500 4500 4500 4500 4500

F-3 F-3 F-3 F-3 F-3 F-3


C-3 C-3 C-3 C-3 C-3 C-3 RG-1 RG-1 RG-1 RG-1 RG-1
A TG-3 TG-3 TG-3 TG-3 TG-3
A

RG-2

RG-2

RG-2

RG-2

RG-2

RG-2
TG-2

TG-2

TG-2

TG-2

T-1

T-1

T-1

T-1

T-1

T-1
7000

7000
100mm THICK
SLAB ON FILL
WITH 10mm
SPACED AT 400
BOTHWAYS

F-2 F-2 F-2 F-2 F-2 F-2


C-2 C-2 C-2 C-2 C-2 C-2

B TG-3 TG-3 TG-3 TG-3 TG-3


B
RG-1 RG-1 RG-1 RG-1 RG-1
2500

2500

RG-1

RG-1
RG-1

RG-1

RG-1

RG-1
TG-1

TG-1

TG-1

TG-1
B

S-2

F-1 F-1 F-1 F-1 F-1 F-1 RG-1 RG-1 RG-1 RG-1 RG-1
C C-1
TG-3
C-1
TG-3
C-1
TG-3
C-1
TG-3
C-1
TG-3
C-1
C

LC-120x40x20x2.0 PURLINS
12mm CROSS
SPACED @ 750 mm O.C
BRACINGS
WITH %10 SAGRODS @ MIDSPAN

C ROOF DECK FRAMING PLAN


A FOUNDATION PLAN
S-1 SCALE : 1:100 M.

S-1 SCALE : 1:100 M.

L1 L2

1 2 3 4 5 6 L1/3 TOP BAR


L1/3 L2/3 TOP BAR

4500 4500 4500 4500 4500

L1/6 BOTTOM BAR L1/5 L2/5 BOTTOM BAR

G-3 G-3 G-3 G-3 G-3a


A

S-1 S-1 S-1 S-1


STAIR WELL
D TYPICAL SLAB ELEVATION

G-5
S-1
7

B-1 B-1 B-1 B-1 CB-1


7000

G-5

G -

G -

G -

G -

B-2

S-2
S-1 S-1 S-1 S-1
SCHEDULE OF SLABS
REBAR SPACING ALONG SHORT DIRECTION REBAR SPACING ALONG LONG DIRECTION
in mm in mm
G-2 G-2 G-2 G-2 G-2
THICK-
B FLOOR
LEVEL
SLAB
MARK
NESS
REBAR
LEFT SUPPORT MIDSPAN RIGHT SUPPORT
REBAR
LEFT SUPPORT MIDSPAN RIGHT SUPPORT REMARKS

in mm SIZE SIZE
S-2 S-2 S-2 S-2 S-2 BOTT. BOTT. BOTT. TOP BOTT. TOP BOTT. TOP BOTT.
2500

TOP TOP TOP


G-4

G-6

G-6

G-6

G-6

G-4

LEVEL
SECOND
G-1 G-1 G-1 G-1 G-1 S-1 100 10 200 300 300 200 300 10 250 300 300 250 300 TWO-WAY
C
- -

S-2 100 10 300 300 - 300 300 300 10 300 300 - 300 300 300 TWO-WAY

B 2ND FLOOR FRAMING PLAN


S-1 SCALE : 1:100 M.

CONSULTANT / DESIGNER REVIEWED BY: RECOMMENDING APPROVAL : APPROVED FOR ACCREDITATION : CONCURRED : PROJECT TITLE : PROJECT NO: OWNER : SHEET NO:

REPUBLIC OF THE PHILIPPINES DESIGNED BY:


IC
o
f t h e PH
IL
F
E A

TWO STOREY DEPARTMENT OF EDUCATION


S-1
I

DEPARTMENT OF EDUCATION (DepED)


T
M
L

P
B

TA
PU

I TO R I NG
IN

SK
RE

ES

SOFIA T. SANTIAGO GILBERTO S. REYES RAMON C. BACANI


DepED
F O RC E

BERNADETTE N. AQUINO WILFREDO S. LOPEZ


FOUR CLASSROOM
ON

ENCODED BY: Max C


D

TASK FORCE ENGINEERING, ASSESSMENT AND MONITORING


M
PE

NO

EN

MCMXCIX
&

IN
G
I
A

E N
E
R

ER
T

IN SM
A

A S SE S
T C
M U G ,

SCHOOL BUILDING
E DE
TN

OIC, DIRECTOR III OIC, DIRECTOR IV


F O

ENGINEER III OIC, STRUCTURAL DIVISION UNDERSECRETARY


MERALCO AVENUE, PASIG CITY SHEET CONTENTS :
BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH DEPATMENT OF EDUCATION (DepED) CHECKED BY:
FOUNDATION, SECONF FLOOR
3
PRC NO. :
0074495
TIN :
199-674-196 BUREAU OF DESIGN, DPWH
ROOF FRAMING PLAN
PTR NO. : DATE : LOCATION : DATE : SCHEDULE OF SLAB
BEAM TYP. DETAIL
THEREVIEW
THE REVIEW& &APPROVAL
APPROVALOFOFTHIS
THISPLANS
PLANSBYBYTHE
THEDPWH
DPWHDOES
DOESNOT
NOTRELIEVE
RELIEVETHE
THEDESIGNER/CONSULTANT
DESIGNER/CONSULTANT NOTE:
FROMRESPONSIBILTY
FROM RESPONSIBILTYFOR
FORTHE
THESAFETY
SAFETYOFOFTHE
THECOMPLETED
COMPLETEDFACILITIES
FACILITIESASASWELL
WELLASASFOR
FORTHE
THEFAILURE
FAILURE THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF TASK FORCE ENGINEERING, ASSESSMENT AND
OFOFTHE
THESAME
SAMEDUE
DUETOTOFAULTY
FAULTYDESIGN.
DESIGN. MONITORING AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


COLUMN SCHEDULE AS SHOWN
%10 SPACED

6
MAIN BARS
%10 @250 10 @250
CUT BARS
5
LEVEL C-1 C-2 C-3 1-10
NOSING BAR
NGL

100
350 350 350

125
5
TIE BEAM

12
10 300mm TEMP
(SEE SCHEDULE)
BARS BOTHWAYS

100
400

350

350

350
4-10 CONT. BARS

125
10 @250
10mm
CUT BARS
TO
2ND FLOOR LEVEL

DECKLEVEL

DETAIL OF TIE BEAM DETAIL OF STAIR ON GRADE DETAIL OF RAMP


MAIN BAR: MAIN BAR: MAIN BAR:

6-%16mm 8-%20mm 8-%20mm


A B C
SCALE NTS SCALE 1 : 25M SCALE 1 : 50M
TIES : 10 mm TIES : 10 mm TIES : 10 mm S-2 S-2 S-2
1@50, 8@75, REST @ 1@50, 8@75, REST @ 1@50, 8@75, REST @
ROOF

150mm TO CENTER 150mm TO CENTER 150mm TO CENTER

L1 L2 L3

350 350 350


L2/3 L2/3 L3/3 L3/3

2D 2D LAP SPLICES ARE ALLOWED 2D 2D LAP SPLICES ARE ALLOWED 2D


ONLY IN THIS PORTION ONLY IN THIS PORTION

D
350

350

350
L2/5 L2/5 L2/5 L3/6
TO

2-12mm SIDE BARS


LEVEL

FLOOR LEVEL

MAIN BAR:

8-%16mm
MAIN BAR:

14-%20mm
MAIN BAR:

12-%20mm
D TYPICAL BEAM ELEVATION
FOUNDATION

TIES : 10 mm TIES : 10 mm TIES : 10 mm


S-2
1@50, 8@75, REST @ 1@50, 8@75, REST @ 1@50, 8@75, REST @
150mm TO CENTER 150mm TO CENTER 150mm TO CENTER
2ND

B E A M S C H E D U L E

BEAM S T E E L R E I N F O R C E M E N T S
DIMENSIONS S T I R R U P S
FLOOR BEAM
LEVEL MARK ( in / mm ) REBAR
LEFT MID SPAN RIGHT
10mm
L
(mm ) (UNLESS NOTED OTHERWISE)
b h TOP BOTTOM TOP BOTTOM TOP BOTTOM

NGL
G-1 200 400 20mm 2 2 2 2 2 2 1@50, 6@100, REST@200

G-2 200 400 20mm 4 3 2 2 4 3 1@50, 6@100, REST@200

G-3 200 400 20mm 3 2 2 2 3 2 1@50, 6@100, REST@200


D

Y-BARS
X-BARS G-3a 200 800 20mm 3 2 2 2 3 2 1@50, 8@175, REST@300
W

G-4 200 400 20mm 3 2 2 2 3 3 1@50, 6@100, REST@200

LEVEL
t

Y-BARS G-5 250 500 20mm 5 3 2 4 5 3 1@50, 8@100, REST@200


100

X-BARS

2ND FLOOR
G-6 200 400 20mm 3 2 2 2 3 3 1@50, 6@100, REST@200
100 mm THICK
L G-7 250 500 20mm 5 3 2 6 5 3 1@50, 8@100, REST@200
GRAVEL BEDDING

PLAN SECTION B-1 200 400 16mm 4 2 2 2 4 2 1@50, 6@100, REST@200

B-2 200 400 16mm 2 2 2 4 2 2 1@50, 6@100, REST@200

E TYP. FOOTING DETAIL CB-1 200 400 16mm 4 2 4 2 4 2 1@50, 6@100, REST@200

SCALE NTS
S-2
RG-1 200 400 16mm 2 2 2 2 2 2 1@50, 6@100, REST@200

ROOF
LEVEL
RG-2 200 500 16mm 3 3 2
3 3 3 3 1@50, 8@100, REST@200

SCHEDULE OF FOOTING
TG-1 300 500 20mm 3 2 2 2 4 3 1@50, 8@100, REST@200

BEAM
FOOTING DIMENSIONS (mm)

TIE
REINFORCEMENT REMARKS
FOOTING TG-2 300 500 20mm 4 3 2 2 4 3 1@50, 8@100, REST@200

MARK LENGTH WIDTH DEPTH Thickness


BAR X BAR Y TG-3 300 500 20mm 3 3 2 2 3 3 1@50, 6@100, REST@200
(L) (W) (D) (t)

F-1 1100 1100 1500 250 5 - 16mm% 5 - 16mm% SQUARE FOOTING


STB-1 200 400 16mm 3 2 2 4 3 2 1@50, 6@100, REST@200

BEAM
STAIR STB-2 200 500 16mm 4 2 2 4 4 2
F-2 2200 2200 1500 300 12 - 16mm% 12- 16mm% SQUARE FOOTING 1@50, 8@100, REST@200

F-3 1900 1900 1500 300 11 - 16mm% 11 - 16mm% SQUARE FOOTING

CONSULTANT / DESIGNER REVIEWED BY: RECOMMENDING APPROVAL : APPROVED FOR ACCREDITATION : CONCURRED : PROJECT TITLE : PROJECT NO: OWNER : SHEET NO:

REPUBLIC OF THE PHILIPPINES DESIGNED BY:


IC
o
f t h e PH
IL
F
E A

TWO STOREY DEPARTMENT OF EDUCATION


S-2
I

DEPARTMENT OF EDUCATION (DepED)


T
M
L

P
B

TA
PU

I TO R I NG
IN

SK
RE

ES

SOFIA T. SANTIAGO GILBERTO S. REYES RAMON C. BACANI


DepED
F O RC E

BERNADETTE N. AQUINO WILFREDO S. LOPEZ


FOUR CLASSROOM
ON

ENCODED BY: Max C


D

TASK FORCE ENGINEERING, ASSESSMENT AND MONITORING


M
PE

NO

EN

MCMXCIX
&

IN
G
I
A

E N
E
R

ER
T

IN SM
A

A S SE S
T C
M U G ,

SCHOOL BUILDING
E DE
TN

OIC, DIRECTOR III OIC, DIRECTOR IV


F O

ENGINEER III OIC, STRUCTURAL DIVISION UNDERSECRETARY


MERALCO AVENUE, PASIG CITY SHEET CONTENTS :
BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH DEPATMENT OF EDUCATION (DepED) CHECKED BY:
COLUMN, BEAM, & FOOTING
3
PRC NO. :
0074495
TIN :
199-674-196 BUREAU OF DESIGN, DPWH
SCHEDULES, RAMP, FOOTING
PTR NO. : DATE : LOCATION : DATE : BEAM TYP. DETAILS

THEREVIEW
THE REVIEW& &APPROVAL
APPROVALOFOFTHIS
THISPLANS
PLANSBYBYTHE
THEDPWH
DPWHDOES
DOESNOT
NOTRELIEVE
RELIEVETHE
THEDESIGNER/CONSULTANT
DESIGNER/CONSULTANT NOTE:
FROMRESPONSIBILTY
FROM RESPONSIBILTYFOR
FORTHE
THESAFETY
SAFETYOFOFTHE
THECOMPLETED
COMPLETEDFACILITIES
FACILITIESASASWELL
WELLASASFOR
FORTHE
THEFAILURE
FAILURE THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF TASK FORCE ENGINEERING, ASSESSMENT AND
OFOFTHE
THESAME
SAMEDUE
DUETOTOFAULTY
FAULTYDESIGN.
DESIGN. MONITORING AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


S-4
L

5 S-3
6
C
250 4500
S-4

29 30 25 38 38 25 30 29 2200 2200

6mm GUSSET PLATE

BOTTOM CHORD A
2500

W-2
1
W
- 4-12x300mm LONG A

W
1

2
-

W-2

W-2
W

-
-
BENT ANCHOR BOLTS

W
2
2

2
F

W-2
-
S-2

W-2
-

-
W

W
S-4

50

2442
2

W-2
- 250x200x10mm BASE

W-2
W

2834
PLATE

1188
W-1
W-2

W-2

200

100
STB-2
E
W-2 S-4
2L-2x2x1/4 STRUT W-2

1000 2-SPAN @1250 2-SPAN @1125 4-SPAN @1187.5 1000 DC-1


DC-1 P
2500 2250 4750

50
9500 S-3
SEE SCHEDULE OF

300mm EACH = 4500mm


2ND FLOOR LEVEL
DN S-2 (2ND/3RD LVL)
CB-1 FOR DETAIL OF REIN.
CB-1

PLAN

7000
A DETAIL OF T-1 G-3a
STB-2 M
G-2

SCALE 1 : 25 M S-3
S-3 2150
N

4500

3200
S-3

2856
6mm GUSSET PLATE
292
250

SCHEDULE OF TRUSS MEMBERS

0
BOTTOM CHORD (FULLY

20
29 30 25 38 38 25 30 29
WELDED TO BASE PLATED)

B-2
TO 6mm GUSSET PLATE (TYP.)

15 TREADS

168
P
RD CH
O O
CH RD
MARK DESCRIPTION
P QTY SIZE 4-12x300mm LONG
TO
BENT ANCHOR BOLTS

W-1 TOP & BOT. CHORDS 2L 2"x2"x1/4" GROUND FLOOR LEVEL


250x200x10mm BASE
PLATE
W-2 WEB MEMBERS 2L 2"x2"x3/16"

FULL WELD
COLUMN OR BEAM
B S-3
TG-3

O
KING POST

D CONNECTION DETAIL K STAIR FRAMING PLAN (TYP) L STAIR SECTION DETAIL


1 : 5 M
S-3
SCALE
O
RD S-3 SCALE 1:50 M
S-3 SCALE 1:50 M

CH
TO
P 6mm GUSSET PLATE (TYP.)

16 @200 10 @300
FULL WELD
TEMP BARS

12@ 125 TOP 12@ 125


MAIN BARS STEP BARS 2-10

SECTION STEP BAR

200mm 200

200
12 @120

TYPICAL TRUSS

200
H ANCHORAGE DETAIL 16 @ 200
MAIN BAR:
MAIN BAR
FULL WELD SCALE 1:5 M 4-16mm
S-3

0
CONNECTION DETAIL

0
F M SECTION OF STAIR SLAB

2
6mm GUSSET PLATE (TYP.) %12 @300
TIES : 10 mm

SCALE 1 : 5 M 1@50, 8@75, REST @


S-3 S-3 SCALE 1:25 M
150mm TO CENTER

N SPOT DETAIL DC-1


BOTTOM CHORD SCALE 1 : 25 M
SEE TRUSS ANCHORAGE DETAIL
S-3 (FROM LANDING TO
2ND/3RD FLOOR LEVEL)
CONNECTION DETAIL
W 10 @300
-
E 1

SCALE 1 : 5 M 120x40x20x2.0mm
S-3 STEEL C-PURLINS
2-10
750mm O.C.
STEP BAR
10mm% SAG ROD WITH 200mm
STANDARD NUTS & 10 @300
75

W-2
WASHERS @ EACH END
7
5 0
LC-120x40x20x2.0 6-%10x200mm LONG
2-10
PURLINS
STEP BAR
75

1-%10mm A-307
ANCHOR BOLT
L-2.5x2.5x1/4

100
100
100 100
100
CB-1
W-2
10mm @
TG-3
300mm o.c.

3-10mm STB-2

HALF TRUSS O SPOT DETAIL P SPOT DETAIL


G PURLIN CONNECTION DETAIL I SAG ROD CONNECTION DETAIL J CONNECTION DETAIL S-3
SCALE 1 : 25 M
S-3
SCALE 1 : 25 M

SCALE 1 : 5 M SCALE 1 : 10 M SCALE 1 : 10 M


S-3 S-3 S-3

CONSULTANT / DESIGNER REVIEWED BY: RECOMMENDING APPROVAL : APPROVED FOR ACCREDITATION : CONCURRED : PROJECT TITLE : PROJECT NO: OWNER : SHEET NO:

REPUBLIC OF THE PHILIPPINES DESIGNED BY:


IC
o
f t h e PH
IL
F
E A

TWO STOREY DEPARTMENT OF EDUCATION


S-3
I

DEPARTMENT OF EDUCATION (DepED)


T
M
L

P
B

TA
PU

I TO R I NG
IN

SK
RE

ES

SOFIA T. SANTIAGO GILBERTO S. REYES RAMON C. BACANI


DepED
F O RC E

BERNADETTE N. AQUINO WILFREDO S. LOPEZ


FOUR CLASSROOM
ON

ENCODED BY: Max C


D

TASK FORCE ENGINEERING, ASSESSMENT AND MONITORING


M
PE

NO

EN

MCMXCIX
&

IN
G
I
A

E N
E
R

ER
T

IN SM
A

A S SE S
T C
M U G ,

SCHOOL BUILDING
E DE
TN

OIC, DIRECTOR III OIC, DIRECTOR IV


F O

ENGINEER III OIC, STRUCTURAL DIVISION UNDERSECRETARY


MERALCO AVENUE, PASIG CITY SHEET CONTENTS :
BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH DEPATMENT OF EDUCATION (DepED) CHECKED BY:
TRAUSS DIAGRAM, CONNECTION
3
PRC NO. :
0074495
TIN :
199-674-196 BUREAU OF DESIGN, DPWH
STAIR, DETAILS
PTR NO. : DATE : LOCATION : DATE :

THEREVIEW
THE REVIEW& &APPROVAL
APPROVALOFOFTHIS
THISPLANS
PLANSBYBYTHE
THEDPWH
DPWHDOES
DOESNOT
NOTRELIEVE
RELIEVETHE
THEDESIGNER/CONSULTANT
DESIGNER/CONSULTANT NOTE:
FROMRESPONSIBILTY
FROM RESPONSIBILTYFOR
FORTHE
THESAFETY
SAFETYOFOFTHE
THECOMPLETED
COMPLETEDFACILITIES
FACILITIESASASWELL
WELLASASFOR
FORTHE
THEFAILURE
FAILURE THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF TASK FORCE ENGINEERING, ASSESSMENT AND
OFOFTHE
THESAME
SAMEDUE
DUETOTOFAULTY
FAULTYDESIGN.
DESIGN. MONITORING AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


LEGEND LOAD SCHEDULE
GENERAL NOTES
SYMBOL DESCRIPTION
1. ALL ELECTRICAL WORKS SHALL COMPLY IN ACCORDANCE WITH

THESE PLANS AND SPECIFICATIONS. THE APPLICABLE PROVISIONS - CEILING LIGHT OUTLET

OF THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL CODE (PEC). 2


- 2 x 40 WATTS FLUORESCENT LAMP
PANELBOARD: LP MAIN : 60AT, 100AF, 2P, 230V
THE RULES AND REGULATION OF THE LOCAL ENFORCING AUTHORITY F - CEILING FAN OUTLET

AND THE REQUIREMENTS OF THE LOCAL POWER COMPANY. CIRCUIT BREAKER


S/Sa - ONE GANG DEVICE SWITCH CKT. VA
DESCRIPTION WIRE & CONDUIT SIZE
THE ELECTRICAL WORKS SHALL BE UNDER IMMEDIATE SUPERVISION NO. LOAD
S ab - TWO GANG DEVICE SWITCH VOLT POLE AT AF
OF A DULY REGISTERED ELECTRICAL ENGINEER.

S cde - THREE GANG DEVICE SWITCH 2


CONV. OUTLET - 6 x 180W 1080 230 2 50
2. THE ELECTRICAL SERVICE POWER IS 1-PHASE, 2-WIRE,
1 20 3-3.5mm THW IN 15mm C
230 V AC, 60 Hz. S 3W - THREE WAY DEVICE SWITCH
2
2 CONV. OUTLET - 6 x 180W 1080 230 2 20 50 3-3.5mm THW IN 15mm C
3. WIRING METHOD SHALL BE AS FOLLOWS : Sf - FAN CONTROL SWITCH
LIGHT OUTLET - 6 x 100W 2
3 780 230 2 20 50 3-3.5mm THW IN 15mm C
a. FEEDERS AND RISERS - INTERMEDIATE METALLIC CONDUIT - EXHAUST FAN SWITCH EXHAUST FAN OUTLET - 1 x 180W
S EF
2
b. LIGHTING, POWER RECEPTACLE - POLYVINYL CHLORIDE CONDUIT 4 LIGHT OUTLET - 10 x 100W 1000 230 2 20 50 3-3.5mm THW IN 15mm C
- RACEWAY CONDUIT CONCEALED IN CEILING
BRANCH CKT., & AUXILIARY SCH. 40
2
- RACEWAY CONDUIT CONCEALED UNDER FLOOR 5 LIGHT OUTLET - 14 x 100W 1400 230 2 20 50 3-3.5mm THW IN 15mm C
4. ALL WIRES SHALL BE COPPER AND THERMOPLASTIC INSULATED TYPE
6 1500 230 2 20
"THW" UNLESS OTHERWISE INDICATED IN THE PLAN. THE MINIMUM S P A R E 50
- PANELBOARD
SIZE OF WIRE FOR POWER AND LIGHTING CIRCUIT HOMERUN SHALL BE
- CKT. BREAKER, RATING AS INDICATED TOTAL 6840
2
3.5mm AND INSULATED FOR 600 VOLTS. SMALLEST RACEWAY SHALL
- DUPLEX CONVENIENCE OUTLET, GROUNDING TYPE
BE 15mmO
I TRADE/NOMINAL SIZE.
10 AMPS, 250 VOLT WITH MODERN PLATE COVER
5. ALL OUTLET BOXES SHALL BE GALVANIZED GAUGE NO. 16 DEEP 2
- EXHAUST FAN OUTLET, SINGLE, GROUNDING TYPE IL = 6840 = 29.7 A FEEDER: 2-14mm THW IN 25mm C
TYPE WITH FACTORY KNOCKOUTS. EF
10 AMPS, 250 VOLT WITH MODERN PLATE COVER
230 V PROTECTION: 60 AT, 100 AF, 2P, 230 V
6. ALL MATERIALS TO BE USED SHALL BE BRAND NEW AND APPROVED LP
- HOMERUN DIRECT TO PANELBOARD
TYPE FOR THE PARTICULAR LOCATION AND PURPOSE OF USAGE.

- PUSH BUTTON
7. GROUNDING SYSTEM SHALL BE PROVIDED TO ALL LIGHTING AND
POWER CIRCUIT AS PER PHILIPPINE ELECTRICAL CODE REQUIREMENT. - ENCLOSED AIR CIRCUIT BREAKER

FA - FIRE ALARM CONTROL PANEL


8. MOUNTING HEIGHT OF WIRING DEVICES SHALL BE AS FOLLOWS :
F - FIRE ALARM STATION OUTLET
a. LIGHT SWITCH - 1.20 M ABOVE FINISH FLOOR
- VIBRATING BELL OUTLET
B

b. CONVENIENCE OUTLET - 0.30 M ABOVE FINISH FLOOR. OVERHEAD SERVICE ENTRANCE


B - FIRE ALARM BELL
CONNECTED TO 220V AC, 1O,
2 WIRE, 60 Hz FITTED WITH
c. PANELBOARD - 1.50 M ABOVE FINISH FLOOR M - SERVICE METER 25mm O TYPE "F" CONDULET

- SERVICE ENTRANCE
d. FIRE ALARM STATION OUTLET - 1.50 M. ABOVE FINISH FLOOR
BUILDING WALL

TO SIMILAR OUTLET

@ SECOND FLOOR
2ND FLOOR LINE
e. PUSH BUTTON OUTLET - 1.20 M ABOVE FINISH FLOOR

PANEL LP
f. FIRE ALARM & VIBRATING BELL - 0.30 M BELOW CEILING LINE

2
2-14mm THW B B
IN 25mmORSC

60AT, 100AF, 2P, 230V AC


TO LINE SIDE OF LP

20 20 F
METERING CONDUIT
2
20 20 3-3.5mm THW
KWHR METER IN 15MMORSC

20
FA 2
20
2-3.5mm THW
IN 15MMORSC

TO NEAREST C.O.
ENCLOSED ACB
RATING: 20AT, 50AF,
230V, 2P

1500 mm
2

GROUND TERMINAL 2-3.5mm THW

1800 mm
IN 15MMORSC

2
#8mm BARE COPPER WIRE

ELECTRICAL FIRE ALARM VIBRATING BELL


16mm O x 2.40m GROUND FLOOR LINE
I
COPPERWELD
GROUND ROD

FIN. GRADE LINE

2
1-8.0mm BARE COPPER WIRE
IN 15mmO C

16MMO x 240MM LENGTH

SINGLE LINE DIAGRAM


GROUNDING ROD COPPERWELD

NOT TO SCALE

RISER DIAGRAM
NOT TO SCALE

CONSULTANT / DESIGNER REVIEWED BY: RECOMMENDING APPROVAL : APPROVED FOR ACCREDITATION : CONCURRED : PROJECT TITLE : PROJECT NO: 99-017 OWNER : SHEET NO:

REPUBLIC OF THE PHILIPPINES DESIGNED BY: RDS


IC
o
f t h e PH
IL
I
F
E A

TWO STOREY DEPARTMENT OF EDUCATION


DEPARTMENT OF EDUCATION (DepED) E-1
T
M
L

P
B

TA
PU

I TO R I NG
IN

SK
RE

ES

SOFIA T. SANTIAGO GILBERTO S. REYES RAMON C. BACANI


DepED
F O RC E

BERNADETTE N. AQUINO WILFREDO S. LOPEZ


FOUR CLASSROOM
ON

ENCODED BY: RDS


D

TASK FORCE ENGINEERING, ASSESSMENT AND MONITORING


M
PE

NO

EN

MCMXCIX
&

IN
G
I
A

E N
E
R

ER
T

IN SM
A

A S SE S
T C
M U G ,

SCHOOL BUILDING
E DE
TN

OIC, DIRECTOR III OIC, DIRECTOR IV


F O

ENGINEER III OIC, STRUCTURAL DIVISION UNDERSECRETARY


MERALCO AVENUE, PASIG CITY SHEET CONTENTS :
BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH DEPATMENT OF EDUCATION (DepED) CHECKED BY: LOAD SCHEDULE

2
PRC NO. :
0074495
TIN :
199-674-196 BUREAU OF DESIGN, DPWH
GENERAL NOTES LEGEND
PTR NO. : DATE : LOCATION : DATE : 5-5-00 SINGLE LINE DIAGRAM RISER DIAGRAM

THEREVIEW
THE REVIEW& &APPROVAL
APPROVALOFOFTHIS
THISPLANS
PLANSBYBYTHE
THEDPWH
DPWHDOES
DOESNOT
NOTRELIEVE
RELIEVETHE
THEDESIGNER/CONSULTANT
DESIGNER/CONSULTANT NOTE:
FROMRESPONSIBILTY
FROM RESPONSIBILTYFOR
FORTHE
THESAFETY
SAFETYOFOFTHE
THECOMPLETED
COMPLETEDFACILITIES
FACILITIESASASWELL
WELLASASFOR
FORTHE
THEFAILURE
FAILURE THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF TASK FORCE ENGINEERING, ASSESSMENT AND
OFOFTHE
THESAME
SAMEDUE
DUETOTOFAULTY
FAULTYDESIGN.
DESIGN. MONITORING AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


1 2 3 4 5 6 1 2 3 4 5 6

A A

a b c d 2

2 2 2 2

CLASSROOM CLASSROOM

S
F F

a b c d

2 2 2 2

Sab Sf Scd Sf
B B
Sefg
LP e f g
2 2 2 2

B B
LP
F

C
5

SECOND FLOOR POWER LAYOUT SECOND FLOOR LIGHTING LAYOUT


SCALE : 1:100 M SCALE : 1:100 M

1 2 3 4 5 6 1 2 3 4 5 6

A A S EF
EF

a b c d

2 2 2 2 S

CLASSROOM CLASSROOM h
Shi
F F
i

a b c d

2 2 2 2

LP

Sab Sf Scd Sf 4

B B
TO C.O. Sefg
LP
e f g
2 2 2
1

B B LP
TO FA
F
LP

C
FA

C
3
M

ENCLOSED AIR CIRCUIT BREAKER


RATING: 220 V, 2P, 20AT, 50AF
TO LINE SIDE OF LP

OVERHEAD SERVICE ENTRANCE


REFER TO RISER DIAGRAM

GROUND FLOOR POWER LAYOUT GROUND FLOOR LIGHTING LAYOUT


SCALE : 1:100 M
SCALE : 1:100 M

CONSULTANT / DESIGNER REVIEWED BY: RECOMMENDING APPROVAL : APPROVED FOR ACCREDITATION : CONCURRED : PROJECT TITLE : PROJECT NO: 99-017 OWNER : SHEET NO:

REPUBLIC OF THE PHILIPPINES DESIGNED BY: RDS


IC
o
f t h e PH
IL
I
F
E A

TWO STOREY DEPARTMENT OF EDUCATION


DEPARTMENT OF EDUCATION (DepED) E-2
T
M
L

P
B

TA
PU

I TO R I NG
IN

SK
RE

ES

SOFIA T. SANTIAGO GILBERTO S. REYES RAMON C. BACANI


DepED
F O RC E

BERNADETTE N. AQUINO WILFREDO S. LOPEZ


FOUR CLASSROOM
ON

ENCODED BY: RDS


D

TASK FORCE ENGINEERING, ASSESSMENT AND MONITORING


M
PE

NO

EN

MCMXCIX
&

IN
G
I
A

E N
E
R

ER
T

IN SM
A

A S SE S
T C
M U G ,

SCHOOL BUILDING
E DE
TN

OIC, DIRECTOR III OIC, DIRECTOR IV


F O

ENGINEER III OIC, STRUCTURAL DIVISION UNDERSECRETARY


MERALCO AVENUE, PASIG CITY SHEET CONTENTS : GROUND FLOOR POWER LAYOUT
BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH DEPATMENT OF EDUCATION (DepED) CHECKED BY:

2
PRC NO. :
0074495
TIN :
199-674-196 BUREAU OF DESIGN, DPWH SECOND FLOOR POWER LAYOUT
GROUND FLOOR LIGHTING LAYOUT
PTR NO. : DATE : LOCATION : DATE : 5-5-00
SECOND FLOOR LIGHTING LAYOUT

THEREVIEW
THE REVIEW& &APPROVAL
APPROVALOFOFTHIS
THISPLANS
PLANSBYBYTHE
THEDPWH
DPWHDOES
DOESNOT
NOTRELIEVE
RELIEVETHE
THEDESIGNER/CONSULTANT
DESIGNER/CONSULTANT NOTE:
FROMRESPONSIBILTY
FROM RESPONSIBILTYFOR
FORTHE
THESAFETY
SAFETYOFOFTHE
THECOMPLETED
COMPLETEDFACILITIES
FACILITIESASASWELL
WELLASASFOR
FORTHE
THEFAILURE
FAILURE THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF TASK FORCE ENGINEERING, ASSESSMENT AND
OFOFTHE
THESAME
SAMEDUE
DUETOTOFAULTY
FAULTYDESIGN.
DESIGN. MONITORING AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


1 2 3 4 5 6
9000 9000

600 4500 4500 4500 4500 4500 600

RD RD RD RD RD RD

1000
A

7000

B
2500

C
1000

LN. OF STRUCTURE

RD RD RD RD RD RD

2 ROOF DRAIN LAYOUT


P-1 SCALE : 1 : 100 METERS

3 2 1 4 5 2500 1000
6 R
VT
PV
C

3950
m
0m5

R
E
W

0
0

E T O

E
0

T S T

S
1
2300

2000

Y R P
A S
E C

S E
SEPTIC TANK V

M
0

P
0

0
5

50mm

WTVCVP mm05
5
2
PVCSP TO

S
3
L
W

75mmPVCDS
S

P
NEAREST SEWER I

K
N
5

R
C
V
TA
V

T
G
V

C
P
m

PVCVTR
m m
SYSTEM

P
TI 0m 12

C
m W
m
10 50 ISE
V

T
P

R
S

P
V

C
V

C
S
150mmCPD 150mmCPD

P
R

P
L

P
m W
CB m
S
CB 0m
m

C
m I

C
TW
V 0m

C
CB W 5 0

P
W

G
CV
10 O 10 m V

T
PV

0
m

C
H V

C
E
0
12

P
m

S
m

0
0 m

3
75mm
5 S m
F 50 ISE

R
S

C
B

D
PVCWP

C
100mm

C
4

R
5

C
W

PVCSP

P
P

m
O

m
V
75

C
m
C
V

R
W
LA

C
H F

D
P
75mm PVCDS H

E
100mm PVCSP
75mm PVCDS
75mm PVCDS

R
A
75mPVCDS

L
50mm PVCVTR W

T
75mPVCDS
I
L
75mPVCDS

C
V E

R
CV
T
W
IS

G
5
m
0
V
C
V
P
T
W
m
I
V

C
RISER

G
m

R
P
WC m

D
V
50mPVCTR
20
m
m

P
O

C
2m
m F

D
m

C
0 50

P
W
1
12mm GICWL

m
SHE 15

75mmPVCDS
P
V

GICWL

C
HE
1

P
m
0m

m
m
75mmPVCDS
50mm PVCVTR 10
100mm PVCWP

P
RISER U

0
5
12mm
LY
FD

P
P
W
L SU

R
I N
AI
CO
E

G
CS

T
A M
W O m
ROOF LINE

50mm PVCVTW m

T
38
V
CO

G
B

D
C
100mm PVCSP

C
M

V
2

P
OO
WC

M
m
V
75

G
S
D
HCR

R
12mm GICWL

C
S

V
LA

P
S
50mPVCTW

m
FD 75

m
C
CLASSROOM CLASSROOM
150mm CDP

LAV 50mm PVCVTW


RISER
CO

D
P

P P
AM

C
20mm GICWL F

D
m
0

m
15

B
U

C
3

75mmPVCDS

75mmPVCDS
EM

T
S
SY
E

G
D
A

C
IN

m
m
A

R
0
5

D
1

P
D
N

C
AI

D
S

P
D
M

C
m
V

m
O 0m
0

T
m
15

P
15
m
OO

M
m

S
5

D
R

C
7

V
LA

P
S
B

m
C
75

m
C
UP

B
C
E
N
LI

75mmPVCDS
F

A
O
O

R
P
D
C

C
FD FD

D
m

P
C
m

m
0
75mPVCDS

75mPVCDS

75mm PVCDS 75mm PVCDS 0

m
5
15
75mPVCDS

1
75mm PVCDS

S
D
RAMP V

C
WATER SUPPLY

150mm CDP

P
GICWL

UP m
m

5
7
MAIN

150mmCPD 150mmCPD
38mm

B
CB CB CB
TO

3C ISOMETRIC VIEW

B
C
GV
SYSTEM

SYSTEM

EM

T
M

S
SY

P-1 SCALE : N T S
E

G
A

PLUMBING RO-IN LAYOUT


N
AI
GV

2
DRAINAGE

DRAINAGE

R
D
P
D
N

C
AI
M m
O 0m

T
15
CDP

CDP

P-1 SCALE : 1 : 100 METERS


TO MAIN

TO MAIN
150mm

150mm

CONSULTANT / DESIGNER REVIEWED BY: RECOMMENDING APPROVAL : APPROVED FOR ACCREDITATION : CONCURRED : PROJECT TITLE : PROJECT NO: OWNER : SHEET NO:

REPUBLIC OF THE PHILIPPINES DESIGNED BY:


IC
o
f t h e PH
IL
I
F
E A

TWO STOREY DEPARTMENT OF EDUCATION


DEPARTMENT OF EDUCATION (DepED) P-1
T
M
L

P
B

TA
PU

I TO R I NG
IN

SK
RE

ES

EMMANUEL P. CUNTAPAY SOFIA T. SANTIAGO GILBERTO S. REYES RAMON C. BACANI


DepED
F O RC E

ELIAS MELQUIADES EMEL B. CUBA II


FOUR CLASSROOM
ON

ENCODED BY: Max C


D

TASK FORCE ENGINEERING, ASSESSMENT AND MONITORING


M
PE

NO

EN

MCMXCIX
&

IN
G
I
A

E N
E
R

ER
T

IN SM
A

A S SE S
T C
M U G ,

SCHOOL BUILDING
E DE
TN

OIC, DIRECTOR III OIC, DIRECTOR IV


F O

SANITARY ENGINEER CHIEF, ARCHITECTURAL DIVISION UNDERSECRETARY


MERALCO AVENUE, PASIG CITY SHEET CONTENTS :
BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH DEPATMENT OF EDUCATION (DepED) CHECKED BY: PLUMBING RO.-IN LAYOUT
2
BUREAU OF DESIGN, DPWH
PRC NO. : TIN :
ISOMETRIC VIEW
PTR NO. : DATE : LOCATION : DATE : ROOF DRAIN LAYOUT

THEREVIEW
THE REVIEW& &APPROVAL
APPROVALOFOFTHIS
THISPLANS
PLANSBYBYTHE
THEDPWH
DPWHDOES
DOESNOT
NOTRELIEVE
RELIEVETHE
THEDESIGNER/CONSULTANT
DESIGNER/CONSULTANT NOTE:
FROMRESPONSIBILTY
FROM RESPONSIBILTYFOR
FORTHE
THESAFETY
SAFETYOFOFTHE
THECOMPLETED
COMPLETEDFACILITIES
FACILITIESASASWELL
WELLASASFOR
FORTHE
THEFAILURE
FAILURE THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF TASK FORCE ENGINEERING, ASSESSMENT AND
OFOFTHE
THESAME
SAMEDUE
DUETOTOFAULTY
FAULTYDESIGN.
DESIGN. MONITORING AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


LEGEND:

CB CATCH BASIN

CDP CONCRETE DRAIN PIPE

CO CLEAN OUT

CV CHECK VALVE

HB HOSE BIBB

FD FLOOR DRAIN

GICWL GALVANIZED IRON COLD WATER LINE (SCH. 40)

4650 100mm THK. + FIN. SLAB W/ GICWR GALVANIZED IRON COLD WATER RISER (SCH. 40)
10mm BENT UP 2 OUT OF 3 AT
100mm THK. + FIN. SLAB W/ L/4 FROM FACE SUPPORT BW
10mm REBARS AT 200mm O.C. GV GATE VALVE
BENT UP 2 OUT OF 3 AT L/4
FROM FACE SUPPORT. BOTH WAYS 150X300mm RC BEAM W/2-16mm
TOP AND BOT. REBARS & 10mm STIRRUPS MH MANHOLE

100
1@50,3@100, REST @300mm O.C. NGL
600 MH
AIR SPACE
PVCDS POLYVINYL CHLORIDE DOWNSPOUT
NGL AIR SPACE INLET

100
100

PVCDP POLYVINYL CHLORIDE DRAIN PIPE


VAR

MANHOLE MANHOLE

AIR SPACE INLET WATER LEVEL 700


PVCDS POLYVINYL CHLORIDE DOWNSPOUT
100

PLASTERED W/WATERPROOFING
COMPOUND OR APPLY ONE FACE
DIGESTIVE (W. LEVEL)

BITUMEN TAR 150 400 150


PVCSP POLYVINYL CHLORIDE SOIL PIPE
1600350

300
25
WATER
LEVEL
PVCVAC POLYVINYL CHLORIDE VENT. ACROSS CEILING
150 700 150
WALLS REINFORCEMENT
LEACHING 10mm VERT. & HOR. BAR PLASTERED W/ WATERPROOFING 10mm REINF. VERT & HOR.
PVCVP POLYVINYL CHLORIDE VENT. PIPE

150
2125

@200mm OC BW COMPOUND OR APPLY ONE @200mm O.C BWAYS


CHAMBER
FACE BITUMEN TAR
DRAINAGE PIPE
DIGESTIVE CHAMBER
PVCVS POLYVINYL CHLORIDE VENT STACK
GRAVEL BED

700

400
100mm THK. SLAB W/ OUTLET
10mm REBARS @ 150 2500 150
INLET PVCVTR/W POLYVINYL CHLORIDE VENT TROUGH ROOF/WALL
300mm BOTH WAYS 2SLOPE
125

2800
PVCWP POLYVINYL CHLORIDE WASTE PIPE

150
100mm THK. + FIM. SLAB W/
10mm REBARS @300mm O.C. BW
PVCWS POLYVINYL CHLORIDE WASTE STACK
150 1000 150 3200 150

RD ROOF DRAIN

5a DETAIL PLAN
2 SECTION DETAIL 3 SECTION DETAIL
UD URINAL DRAIN

P-2 SCALE : 1:20 M


P-2 SCALE : 1:50 M WC WATER CLOSET
P-2 SCALE : 1:50 M

LAV LAVATORY

CS COUNTER SINK

2-10mm EXTRA
S-1a 100mm THK. + FIN. SLAB W/
BARS TOP/BOT. ON 10mm REBARS @ 300mm O.C. PLUMBING NOTES:
TWO PARALLEL SIDE
BENT UP 2 OUT OF 3 AT L/4
FROM FACE OF SUPPORT B.W. 1. GRADES OF HORIZONTAL PIPINGS
4650 RUN ALL HORIZONTAL PIPINGS IN PERPECT ALIGNMENT AND AT A FORM GRADE NOT LESS THAN TWO PERCENT (2
1000 3200
150 150 150
2. CHANGE IN DIRECTION
700
200 600 200 1100 150 700 150 1100
ALL CHANGE IN DIRECTION SHALL BE MADE BY APPROPRIATE USE OF FORTY-FIVE DEGREES (45) WYES, LONG SWEEP
75mm PVCDS
QUARTER BEND, SIXTH-EIIGHT OR SIXTEENTH BEND. WHEN THE CHANGE OF FLOW IS FROM HORIZONTAL TO VERTICAL A
150 400 150
SINGLE 1/8 BEND COMBINATION MAYBE USED ON VERTICAL STACKS AND SHORT QUARTER BENDS MAYBE USED ON WASTE
150MM THK. CHB W/ 10mm LINE, TEE AND CROSSES MAYBE USED IN BENT PIPES.
REBARS HOR. EVERY 2-LAYERS
75 VERT. @600mm O.C.
150

3. PROHIBITED FITTINGS
NO DOUBLE HUB OR TEE BRANCH SHALL BE USED ON HORIZONTAL SOIL AND WASTE LINES, THE DRILLINGS AND TAPPING

100
10mm BAR
OF HOUSE DRAIN, WASTE OR VENT PIPES AND USED OF SADDLE HUB AND BEND ARE PROHIBITED.
3-10mm (E.W.)
900

OUTLET HANDLE
CDP

1.
4. PIPE CLEAN-OUTS
600

(VARIABLE)
min.
50 CLEAN-OUTS ARE REQUIRED UNDER THE F0LLOWING CONDITIONS:
50 600 50

250 100 250 2SLOPE


INLET
CDP a) EVERY CHANGE OF HORIZONTAL DIRECTION EXCEEDING TWENTY TWOAND ONE-HALF DEGREES (22 1/2).
2800
2500

b) ONE AND ONE-HALF METERS (1.50m.) INSIDE THE PROPERTY LINES BEFORE THE HOUSE DRAINAGE CONNECTION.

600
2SLOPE
MH MH
50
c) EVERY FIFTEEN METERS (15.00m) IN HORIZONTAL RUN OF PIPES.
50 (TYP.) 2
OUTLET
d) AT THE END OF ANY HORIZONTAL PIPE LINES.

100
100

P-2

100
900

5. THE DIGESTION CHAMBER OF SEPTIC VAULT MUST BE WATERPROOFED.


50 50
6. NOT LESS THAN 0.30 METER OF AIR SPACE MUST BE LEFT BETWEEN THE TOP OF THE SEWAGE AND THE UNDER PART OF
50 50
150

VAULT ROOF SLAB.

S2 100mm THK. + FIN. SLAB W/


10mm REBARS @ 300mm O.C.
5b DETAIL SECTION 7. NO SEPTIC VAULT SHALL BE CONSTRUCTED UNDER THE BUILDING.

BENT UP 2/3 OUT AT L/4 FACE


INLET SUPPORT AND SHORT SPAN AND
10mm TEMP BARS @300mm E.W.
INLET 4 MANHOLE DET. SECTION P-2 SCALE : 1:20 M 8. ALL PLUMBING
CONTRACTOR.
WORKS SHALL BE UNDER THE SUPRVISION OF A LICENSED MASTER PLUMBER AND A LICENCED PLUMBING

3
P-2 SCALE : 1:10 M

DESIGN CRITERIA
P-2

5 CATCH BASIN DETAIL SECTION i. LIVE LOAD_________________ 1000Pa


ii ALLOWABLE STRESSES
P-2 SCALE : 1:20 M
1. CONCRETE
1 SEPTIC TANK DETAIL a. FOR FOOTING, BEAMS AND SLABS
P-2 SCALE : 1:50 M fc'' = 20 MPa
2. CONCRETE MASONRY UNITS (LOAD BEARING CHB)
fm' =6.90 MPa, fm = 2.41 MPa
3. REINFORCING STEEL BARS
FOR BARS SMALLER THAN 16mm

fy = 230 MPa
4. ASSUMED ALLOWABLE BEARING CAPACITY Y = 100KPa

NOTE:

CONSULTANT / DESIGNER REVIEWED BY: RECOMMENDING APPROVAL : APPROVED FOR ACCREDITATION : CONCURRED : PROJECT TITLE : PROJECT NO: OWNER : SHEET NO:

REPUBLIC OF THE PHILIPPINES DESIGNED BY:


IC
o
f t h e PH
IL
I
F
E A

TWO STOREY DEPARTMENT OF EDUCATION


DEPARTMENT OF EDUCATION (DepED) P-2
T
M
L

P
B

TA
PU

I TO R I NG
IN

SK
RE

ES

EMMANUEL P. CUNTAPAY SOFIA T. SANTIAGO GILBERTO S. REYES RAMON C. BACANI


DepED
F O RC E

ELIAS MELQUIADES EMEL B. CUBA II


FOUR CLASSROOM
ON

ENCODED BY: Max C


D

TASK FORCE ENGINEERING, ASSESSMENT AND MONITORING


M
PE

NO

EN

MCMXCIX
&

IN
G
I
A

E N
E
R

ER
T

IN SM
A

A S SE S
T C
M U G ,

SCHOOL BUILDING
E DE
TN

OIC, DIRECTOR III OIC, DIRECTOR IV


F O

SANITARY ENGINEER CHIEF, ARCHITECTURAL DIVISION UNDERSECRETARY


MERALCO AVENUE, PASIG CITY SHEET CONTENTS :
BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH DEPATMENT OF EDUCATION (DepED) CHECKED BY: SEPTIC TANK DETAIL
2
BUREAU OF DESIGN, DPWH
PRC NO. : TIN :
DESIGN CRITERIA, LEGEND
PTR NO. : DATE : LOCATION : DATE : MISC. DETAILS

THEREVIEW
THE REVIEW& &APPROVAL
APPROVALOFOFTHIS
THISPLANS
PLANSBYBYTHE
THEDPWH
DPWHDOES
DOESNOT
NOTRELIEVE
RELIEVETHE
THEDESIGNER/CONSULTANT
DESIGNER/CONSULTANT NOTE:
FROMRESPONSIBILTY
FROM RESPONSIBILTYFOR
FORTHE
THESAFETY
SAFETYOFOFTHE
THECOMPLETED
COMPLETEDFACILITIES
FACILITIESASASWELL
WELLASASFOR
FORTHE
THEFAILURE
FAILURE THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF TASK FORCE ENGINEERING, ASSESSMENT AND
OFOFTHE
THESAME
SAMEDUE
DUETOTOFAULTY
FAULTYDESIGN.
DESIGN. MONITORING AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


REPUBLIC OF THE PHILIPPINES

TABLE OFFICE OF THE CITY/MUNICIPAL


ENGINEER/BUILDING OFFICIAL
OF
CONTENTS
DISTRICT/CITY/MUNICIPALITY

ARCHITECTURAL LAND USE & ZONING

A-1 PERSPECTIVE VIEW & TABLE OF


CONTENTS

A-2 GROUND, SECOND FLOOR, ROOF,


REFLECTED CEILING PLANS

A-3 LONGITUDINAL, CROSS SECTION,


FRONT, REAR, RIGHT, LEFT SIDE
ELEV.

A-4 LEFT SIDE ELEV., SCHED. OF


DOORS & WINDOWS, BALCONY
LINE & GRADE
RAILING, EAVES,
VENT., & RAMP DETAILS

A-6 STAIR, HANDRAIL DETAILS

A-5 TOILET, CONC. COUNTER,


SUN BREAKER DETAILS

ARCHITECTURAL

STRUCTURAL

S-1 FOUNDATION, SCHEDULE OF SLAB


2ND FLOOR & ROOF FRAMING PLAN
STRUCTURAL
1 PERSPECTIVE VIEW S-2 DET. STAIR ON GRADE, RAMP &
BEAM, FOOTING/TIE BEAM/COLUMN
A-1 SCALE : N T S
DETAIL
S-3 TRUSS DIAGRAM, STAIR DET.
DETAILS OF STEEL CONNECTION

SANITARY

ELECTRICAL

E-1 GEN. NOTES, LEGEND, LOAD


SCHEDULE, RISER DIAGRAM, SINGLE
LINE DIAGRAM

E-2 GROUND FLOOR POWER LAYOUT


SECOND FLOOR POWER LAYOUT

ELECTRICAL
E-3 GROUND FLOOR LIGHTING LAYOUT
SECOND FLOOR LIGHTING LAYOUT

SANITARY

P-1 PLUMBING RO-IN LAYOUT, ROOF


DRAIN LAYOUT & ISOMETRIC VIEW

P-2 SEPTIC TANK, CATCH BASIN DETAILS


MECHANICAL
LEGEND, NOTES & DESIGN CRITERIA

CONSULTANT / DESIGNER REVIEWED BY: RECOMMENDING APPROVAL : APPROVED FOR ACCREDITATION : CONCURRED : PROJECT TITLE : PROJECT NO: OWNER : SHEET NO:

REPUBLIC OF THE PHILIPPINES DESIGNED BY:


IC
o
f t he PH
IL
I
F
E A

TWO STOREY DEPARTMENT OF EDUCATION


DEPARTMENT OF EDUCATION (DepED)
T
M
L

P
B

TA
PU

I TO R I NG

A-1
IN

SK
RE

ES

EMMANUEL P. CUNTAPAY SOFIA T. SANTIAGO GILBERTO S. REYES RAMON C. BACANI SIX CLASSROOM DepED
F O RC E

ALBERT Z. DE BELEN
ON

ENCODED BY: Max C.


D

TASK FORCE ENGINEERING, ASSESSMENT AND MONITORING


M
PE

NO

EN

MCMXCIX
&

IN
G
I

T
A

E N

G.I. ROOF SCHOOL BUILDING


E
R

ER
T

IN SM
A

A S SE S
T C
M
E U G ,
DE

ARCHITECT / ENGINEER
TN

CHIEF, ARCHITECTURAL DIVISION OIC, DIRECTOR III OIC, DIRECTOR IV


F O

UNDERSECRETARY
MERALCO AVENUE, PASIG CITY
6
SHEET CONTENTS :
BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH DEPATMENT OF EDUCATION (DepED) CHECKED BY:
PRC NO. : 0010990 TIN : 149 460 161 PERSPECTIVE VIEW
PTR NO. : DATE : 27 OCT. 2002 TABLE OF CONTENTS
LOCATION : DATE : 08/06/2004

NOTE:
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF TASK FORCE ENGINEERING, ASSESSMENT AND
MONITORING AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


A B C
CONCRETE SUNBREAKER
1 2 3 4 5 6 7 8 9500
1000 7000 2500 1000
(SEE DETAIL)
9000 9000 9000 4500 600 APEX LINE OF TRUSS
150mm THK. CHB WALL 4500 4500 4500 4500 4500 4500
PLASTER AND PAINT FIN. CONCRETE
GA. 26 CORR. G.I.
SUNBREAKER (SEE

2500
SHEET ROOFING

LINE OF ROOF
DETAIL) (PAINT FINISH)
1

A-3
675

TOP OF ROOF BEAM


A
GA. 26 PLAIN G.I. SHEET
GUTTER ON 12x300mm
W-1 FIBER CEMENT FASCIA BOARD

WF1 (PAINT FINISH)

3200
LANDING

150mm THK. CHB


DN. PLAIN PLASTER
SECOND FLR. LVL.

6725
PAINT FIN.
7000

CLASSROOM-4 CLASSROOM-5 CLASSROOM-5


WF1
FL1 FL1 FL1

3200
32mm G.I. PIPE
HANDRAIL WITH 32mm
VERT. SUPPORT

GROUND FLR. LVL. @300mm O.C. (PAINT

325
NAT. GRD. LN. FINISH)

B
4 LEFT SIDE ELEVATION
2500

FL1 C O R R I D O R
A-3 SCALE : 1 : 100 METERS

FD WF3 FD FD FD FD FD

RAILING (SEE DETAIL) ROOF LINE C B A


9500

1000 2500 7000 1000

APEX LINE OF TRUSS


2 SECOND FLOOR PLAN GA. 26 CORR. G.I.

SHEET ROOFING (PAINT


A-2 SCALE : 1 : 100 METERS

2500
FINISH)

TOP OF ROOF BEAM GA. 26 PLAIN G.I.


SHEET GUTTER ON
12x300mm FIBER
CEMENT FASCIA BOARD

1 2 3 4 5 6 7 6 (PAINT FINISH)

3200
9000 9000 9000 4500 150mm THK. CHB PLAIN
PLASTER PAINT FIN.
4500 4500 4500 4500 4500 4500 2550 1700

150mm THK. CHB WALL SECOND FLR. LVL.

6725
3
PLASTER AND PAINT FIN.
A-3

3200
LN. OF SUNBREAKER
SCHEDULE OF FINISH
WF2 W-3
675

32mm G.I. PIPE

A
HANDRAIL WITH 32mm
VERT. SUPPORT

800
850
FLOORS :
SHE 3 GROUND FLR. LVL. @300mm O.C. (PAINT
HE

325
D-4
D-3
D-4 A-3 NAT. GRD. LN. FINISH)

1100
FL1 - PLAIN CEMENT FLOOR FINISH

860
D-3

3 RIGHT SIDE ELEVATION


WF4 D-2

1500
A-2 SCALE : 1 : 100 METERS FL2 - PLAIN CEMENT FLOOR ROUGH

7000
7000

HCR WITH GROOVES

1 2 3

4776
FL3 - 200X200 VITRIFIED FLR TILES
9500

( UNGLAZED )
WF1

WALLS :

B CONCRETE HOLLOW
BLOCKS
WF1 - 150 MM THK. CHB W/ PLAIN
UP CEMENT PLASTER FIN (PAINT)
CONCRETE SLAB
2500

POLYETHYLENE SHEET DAMP PROOFING


FL1 C O R R I D O R
GRAVEL BEDDING WF2 - 150mm THK. CHB w/200X200mm
FD WF3 FD FD FD FD VITRIFIED WALL TILES ( GLAZED )
C WF3

RAILING (SEE DETAIL)


UP RAMP WF3 - 100mm THK. CHB PLAIN CEMENT
UP
PLASTER w/50mm G.I. PIPE
5 HANDRAIL PAINT FIN.
1 GROUND FLOOR PLAN ENTRY A-3
5 DAMP PROOFING DET.
NOT TO SCALE
A-2 SCALE : 1 : 100 METERS
A-2 WF4 - 100mm THK. CHB w/200X200mm
VITRIFIED WALL TILES ( GLAZED )

CONSULTANT / DESIGNER REVIEWED BY: RECOMMENDING APPROVAL : APPROVED FOR ACCREDITATION : CONCURRED : PROJECT TITLE : PROJECT NO: OWNER : SHEET NO:

REPUBLIC OF THE PHILIPPINES DESIGNED BY:


IC
o
f t he PH
IL
I
F
E A

TWO STOREY DEPARTMENT OF EDUCATION


DEPARTMENT OF EDUCATION (DepED)
T
M
L

P
B

TA
PU

I TO R I NG
IN

SK
RE

ES

DepED A-2
EMMANUEL P. CUNTAPAY SOFIA T. SANTIAGO GILBERTO S. REYES RAMON C. BACANI SIX CLASSROOM
F O RC E

ALBERT Z. DE BELEN
ON

ENCODED BY: Max C.


D

TASK FORCE ENGINEERING, ASSESSMENT AND MONITORING


M
PE

NO

EN

MCMXCIX
&

IN
G
I

T
A

E N

G.I. ROOF SCHOOL BUILDING


E
R

ER
T

IN SM
A

A S SE S
T C
M
E U G ,
DE

ARCHITECT / ENGINEER
TN

CHIEF, ARCHITECTURAL DIVISION OIC, DIRECTOR III OIC, DIRECTOR IV


F O

UNDERSECRETARY
MERALCO AVENUE, PASIG CITY
6
SHEET CONTENTS :
BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH DEPATMENT OF EDUCATION (DepED) CHECKED BY:
PRC NO. : 0010990 TIN : 149 460 161 FLOOR PLANS
PTR NO. : DATE : 27 OCT. 2002 LEFT & RIGHT ELEVATION
LOCATION : DATE : 08/06/2004
SCHEDULE OF FINISHES, DAMP PROOFING
NOTE:
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF TASK FORCE ENGINEERING, ASSESSMENT AND
MONITORING AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


1 2 3 4 5 6 7 8
9000 9000 9000 A B C
600 4500 4500 4500 4500 4500 4500 4500 600 9500

APEX OF TRUSS 1000 7000 2500 1000

TOP OF TRUSS

2500 SEE TRUSS DETAILS

2500
TOP OF ROOF BEAM SEE TRUSS DETAIL

TOP OF ROOF BEAM

538
3200
10200

3200
10
W-1 W-2
4 5 6 W-1 A-5
SECOND FLOOR LEVEL
LANDING
CLASSROOM 3
SECOND FLOOR LEVEL CORRIDOR

6725
EXPOSED CEILING UNDER
SLAB PAINT FIN.
W-3
3200

50mm GA# 40
200x200mm G.I. PIPE

3200
GLAZED WALL HANDRAIL
TILES 9
W-1 W-2
1 2 3 HE SHE A-4
GROUND FLOOR LEVEL
150mm THK. CHB WALL
325

NAT. GRD. LN.


CLASSROOM 1 PLASTER PAINT FIN.
GROUND FLOOR LEVEL

325
FIN. GRD. LN.

3 LONGITUDINAL SECTION EXPOSE CEILING


UNDERSLAB PAINT FINISH
A-3 SCALE : 100
4 CROSS SECTION

8 7 6 5 4 3 2 1 A-3 SCALE : 1 : 100 METERS


2-32mm G.I. PIPE

200
HANDRAIL w/32mm
VERT. SUPPORT @300mm
9000 9000 9000
OC (PAINT FIN.)
600
600 4500 4500 4500 4500 4500 4500 4500

APEX LINE OF TRUSS 2-32mm G.I. PIPE HANDRAIL

900
GA.26 CORR. G.I.
SHEET ROOFING w/32mm VERT. SUPPORT
@300mm O.C.(PAINT FIN.)
(PAINT FINISH) 12mM STEEL DOWEL
2500

700
EMBEDD IN CONC.
NON-SKID PLAIN A-3
GA.26 PLAIN G.I. CEMENT FLOOR FINISH NON-SKID PLAIN CEMENT
SHEET GUTTER ON w/GROOVE LINES FLOOR FIN. w/ GROOVE

200
TOP OF ROOF BEAM
12x300mm FIBER LINES

100
200
CEMENT FASCIA BD.

900
700

1200
(PAINT FINISH)

900

700
3200

300
PLAIN CEMENT
PLASTER PAINT WALL
FINISH

W-1
SECOND FLOOR LEVEL
6 DET. ELEVATION OF RAMP 7 DETAIL SECTION
6725

GA. 26 CORR. G.I.


SHEET SUN BREAKER A-3 SCALE 1:50 M A-3 SCALE 1:10 M

ON STEEL FRAMING 100


3200

(SEE DETAIL)
W-3
100X100 CONCRETE
SKIRTING
5 6
GROUND FLOOR LEVEL
4500
325

FIN. GRD. LN. 32 mm G.I PIPE VERTICAL


SUPPORT @ 300mm ON

REAR ELEVATION
CENTER PROVIDE 12mm
2

100
STEEL DOWELS (PAINT FIN.)

150
A-3 SCALE : 1 : 100 METERS

1 2 3 4 5 6 7 8 B

9000 9000 9000

600 4500 4500 4500 4500 4500 4500 4500 600


APEX LINE OF TRUSS

2500
GA.26 CORR G.I. SHEET C O R R I D O R
ROOFING (PAINT FIN.)
8 SPOT DETAIL
2500

1200
A-3 SCALE 1:5 M

GA.26 PLAIN G.I.SHT.


TOP OF ROOF BEAM
GUTTER ON 12x300mm
THK FIBER CEMENT
C

175
FASCIA BOARD (PAINT
FIN.)
3200

D-1 D-1 D-1 D-1 D-1 D-1

1400
1400
100mm THK. CHB RAILING RAMP UP

W-2 W-2 W-2 W-2 W-2 W-2


w/50mm G.I. PIPE HANDRAIL 6
W-1
SECOND FLOOR LEVEL (PAINT FINISH) A-3
6725

3600
NON-SKID PLAIN
3200

5150
D-1 D-1 D-1 D-1 D-1 D-1 32mm G.I. PIPE CEMENT FLOOR

HANDRAIL w/32mm FINISH w/GROOVE TOTAL RUN OF RAMP 32mm G.I. PIPE
LINES
VERT. SUPPORT @150mm 7 HANDRAIL w/32mm
D-1
W-2 W-2 W-2 W-2 W-2 W-2 O.C. (PAINT FIN.) A-3 VERT. SUPPORT @300mm
GROUND FLOOR LEVEL
O.C. (PAINT FIN.)
325

NAT. GRD. LN.


5 DET. PLAN OF RAMP
1 FRONT ELEVATION A-3 SCALE 1:50 M

A-3 SCALE : 1 : 100 METERS

CONSULTANT / DESIGNER REVIEWED BY: RECOMMENDING APPROVAL : APPROVED FOR ACCREDITATION : CONCURRED : PROJECT TITLE : PROJECT NO: OWNER : SHEET NO:

REPUBLIC OF THE PHILIPPINES DESIGNED BY:


IC
o
f t he PH
IL
I
F
E A

TWO STOREY DEPARTMENT OF EDUCATION


DEPARTMENT OF EDUCATION (DepED)
T
M
L

P
B

TA
PU

I TO R I NG
IN

SK
RE

ES

DepED A-3
EMMANUEL P. CUNTAPAY SOFIA T. SANTIAGO GILBERTO S. REYES RAMON C. BACANI SIX CLASSROOM
F O RC E

ALBERT Z. DE BELEN
ON

ENCODED BY: Max C.


D

TASK FORCE ENGINEERING, ASSESSMENT AND MONITORING


M
PE

NO

EN

MCMXCIX
&

IN
G
I

T
A

E N

G.I. ROOF SCHOOL BUILDING


E
R

ER
T

IN SM
A

A S SE S
T C
M
E U G ,
DE

ARCHITECT / ENGINEER
TN

CHIEF, ARCHITECTURAL DIVISION OIC, DIRECTOR III OIC, DIRECTOR IV


F O

UNDERSECRETARY
MERALCO AVENUE, PASIG CITY
6
SHEET CONTENTS :
BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH DEPATMENT OF EDUCATION (DepED) CHECKED BY:
PRC NO. : 0010990 TIN : 149 460 161 FRONT& REAR ELEVATION, SECTIONS, DET OF
PTR NO. : DATE : 27 OCT. 2002 RAMP & RAILING
LOCATION : DATE : 08/06/2004

NOTE:
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF TASK FORCE ENGINEERING, ASSESSMENT AND
MONITORING AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


1000 700 4 EQUAL PARTS = 2500 2 EQUAL PARTS = 1225 4 EQUAL PARTS = 2500
900

7-BLADES
260
260
300

635
600 GA#26 CORR. G.I.
ROOFING SHT. PAINT FIN.

14-BLADES

14-BLADES
1240
6mm THK. MARINE PLYWOOD

1240
CEILING ON 50x50mm CEILING
JOIST @600mm BW

2400
2400

2400

2400
2100

2100
2054
STAINLESS STEEL
38mm TEKSCREW

1200

1765
KICKING PLATE
800
GA#26 GI STRAP

1500
COPPER RIVET

900
900
12x300mm FIBER CEMENT

300
FASCIA BOARD FIX W/METAL

300
FFL FFL SCREW ON STL. FRAME PAINT
FINISH
CLASSROOM TOILET (DISABLED) TOILET TOILET (CUBICLE)
TANGUILE PANEL DOOR ON 50X150 MM HOLLOW CORE FLUSH TYPE SWING HOLLOW CORE FLUSH TYPE SWING DOOR SWING DOOR ON 50X100 JALOUSIE WINDOWS WITH CLEAR GLASS JALOUSIE WINDOWS WITH CLEAR GLASS BLADES JALOUSIE WINDOWS WITH CLEAR GLASS
GA#26 GI GUTTER PAINT FIN.
D-1 THK. YACAL/GUIJO JAMB W/ FIXED D-2 DOOR W/ MARINE PLYWOOD FACING D-3 W/ MARINE PLYWOOD FACING INSIDE AND D-4 YACAL/GUIJO DOOR JAMB BLADES ON STANDARD ALUMINUM CASING ON STANDARD ALUMINUM CASING AND FIXED BLADES ON STANDARD ALUMINUM CASING
20x20X2mm ANGULAR BAR
AND FIXED CLEAR GLASS TRANSOM ON CLEAR GLASS TRANSOM ON 50X150
CLEAR GLASS TRANSOM COMPLETE INSIDE AND ORDINARY OUTSIDE
ORDINARY OUTSIDE COMPLETE W/ COMPLETE WITH HARDWARES
W-1 W-2 W-3 ON 50X150 YACAL/GUIJO JAMB COMPLETE FOR FASCIA BOARD FRAME
WITH HARDWARES AND ACCESSORIES
COMPLETE W/ HARDWARES AND HARDWARES AND ACCESSORIES ACCESSORIES 50X150 YACAL/GUIJO JAMB COMPLETE WITH YACAL/GUIJO JAMB COMPLETE WITH WITH HARDWARES AND ACCESSORIES
COATED WITH PRIMER
ACCESSORIES PROVIDE KICK PLATE HARDWARES AND ACCESSORIES HARDWARES AND ACCESSORIES

BASKET STRAINER

1 2 3 4 5 6 7 8 3 DOORS AND WINDOWS SCHEDULE


9000 9000 9000 A-4 SCALE : 1:50m

600 4500 4500 4500 4500 4500 4500 4500 600 75mm PVC
DOWNSPOUT PAINT
FINISH
RD RD

8
SPOT DETAIL (EAVES)
1000

A A-4 SCALE : 1:10 m.


1000

TOP CHORD SEE STRUCTURAL DETAIL

38mm TEKSCREW

C-PURLIN (SEE STRUC'L DETAIL)


GA.26 CORR. G.I. SAG ROD SEE STRUCTURAL DETAIL
SHEET ROOFING
7000

PAINT FINISH
6mm THK. MARINE PLYWOOD CEILING
ON 50x50mm CEILING JOIST
@600mm BW
GA. 26 PLAIN G.I. SHT.
RIDGE ROLL PAINT FIN. 6mm THK. ORD. GA#26 GI STRAP
PLYWOOD CEILING W/ ROOF
6mm GROOVE ON
5
BEAM GA#26 G.I. GUTTER ON 12x300mm
A-4 FIBER CEMENT FASCIA BOARD PAINT
50x50mm CEILING
FIN.
JOIST @600mm BW

(PAINT FIN.)
B GA.26 PLAIN.
SHEET FLASHING
G.I.
ON
BASKET STRAINER

12x300mm FIBER
75mm PVC DOWNSPOUT PAINT
2500

CEMENT FASCIA BOARD 8


FINISH
PAINT FINISH A-4

CEILING VENT (SEE DETAIL)

C
LINE OF STRUCTURE

6
SECTION DETAIL (EAVES)
1000

GA.26 PLAIN. G.I.

A-4 SCALE : 1 : 40 m.
RD RD SHEET GUTTER
PAINT FINISH
LN. OF STRUCTURE SEE TRUSS DET.

2 ROOF PLAN 4
A-4
FR. 25x75mm WOOD
6 A-4 SCALE : 1 : 100 METERS
FRAMEPAINT FIN.

A-4
1 2 3 4 5 6 7 8
9000 9000 9000 4500 600 6mm THK. ORD.

300
PLYWD. CEILING
600 4500 4500 4500 4500 4500 4500
(PAINT) ON 50x50mm CONC. BEAM
CLG. JST. @600mm
OC BW
1000

A 1175
25x25mm WOOD VENT
6mm THK. MARINE PROVIDE INSECT SCREEN
FR. QUARTER-C
PLYWD. CEILING
MOULDING CEILING
LIGHTING FIXTURE
CONTACT TO CONC. (PAINT) ON 50x50mm
7
DETAIL PLAN (VENT.)
CLG. JST. @600mm
WALL
6mm THK. ORD PLYWOOD CEILING OC BW
w/6mm GROOVE ON 50x50mm
5
SPOT DETAIL (CORNER CLG) A-4 SCALE : 1 : 10 m.
CLEILING JOISTS (PAINT FIN.)
7000

A-4 SCALE : 1 : 10 m.

25x25mm WOOD VENT.


PROVIDE INSECT SCREEN
10mm @250mm
50 12 325 12 50 ON CENTER

100
100
b
6mm THK. MARINE PLYWOOD CEILING

w/GROOVE ON 50x50mm CEILING 12x12mm GROOVE


2500

JOISTS (PAINT FIN.)


CEILING VENT. (SEE BEAM REBARS SEE
6 25 300
DETAIL) 6mm THK PLYWOOD STRUCTURAL DETAIL
FR.25x75mm CEILING ON 50x50mm 675
c VENT FRAME CEILING JOIST @600mm
1000

GA.26 PLAIN G.I. GUTTER


(PAINT FIN.) OC. BW (PAINT FIN.)
ON 12x300mm THK.
FIBER
BOARD
CEMENT FASCIA 4
SECTION DETAIL (VENT.) 9 CONCRETE SUNBREAKER DET.
1 SECOND FLOOR REFLECTED CEILING PLAN A-4 SCALE : 1 : 5 m A-4 SCALE: 1:10 mts.

A-4
A-4 SCALE : 1 : 100 METERS

CONSULTANT / DESIGNER REVIEWED BY: RECOMMENDING APPROVAL : APPROVED FOR ACCREDITATION : CONCURRED : PROJECT TITLE : PROJECT NO: OWNER : SHEET NO:

REPUBLIC OF THE PHILIPPINES DESIGNED BY:


IC
o
f t he PH
IL
I
F
E A

TWO STOREY DEPARTMENT OF EDUCATION


DEPARTMENT OF EDUCATION (DepED)
T
M
L

P
B

TA
PU

I TO R I NG
IN

SK
RE

ES

DepED A-4
EMMANUEL P. CUNTAPAY SOFIA T. SANTIAGO GILBERTO S. REYES RAMON C. BACANI SIX CLASSROOM
F O RC E

ALBERT Z. DE BELEN
ON

ENCODED BY: Max C.


D

TASK FORCE ENGINEERING, ASSESSMENT AND MONITORING


M
PE

NO

EN

MCMXCIX
&

IN
G
I

T
A

E N

G.I. ROOF SCHOOL BUILDING


E
R

ER
T

IN SM
A

A S SE S
T C
M
E U G ,
DE

ARCHITECT / ENGINEER
TN

CHIEF, ARCHITECTURAL DIVISION OIC, DIRECTOR III OIC, DIRECTOR IV


F O

UNDERSECRETARY
MERALCO AVENUE, PASIG CITY
6
SHEET CONTENTS :
BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH DEPATMENT OF EDUCATION (DepED) CHECKED BY:
PRC NO. : 0010990 TIN : 149 460 161 SCHEDULE OF DOORS AND WINDOW, ROOF
PTR NO. : DATE : 27 OCT. 2002 AND REFLECTED CEILING PLAN, EAVES, VENT.
LOCATION : DATE : 08/06/2004
AND SUN BREAKER DETAIL
NOTE:
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF TASK FORCE ENGINEERING, ASSESSMENT AND
MONITORING AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


3
5 A-5
6
5 50mm G.I. PIPE SCH.
50mm G.I. PIPE SCH. 250
40 PAINT FIN.
4500 A-5 40 PAINT FIN.
2200 2200 50mmG.I. PIPE SCH.
100 146 40 PAINT FIN.
100
50mm G.I. PIPE

50
SCHEDULE 40
19mm SQUARE BAR (PAINT FINISH)
19mm SQUARE BAR
WELD TO G.I. PIPE
W-1 WELDED TO G.I. PIPE
HANDRAIL @146mm O.C.
HANDRAIL @146mm O.C.

PLAIN CEMENT STEEL


19mm SQUARE BAR
TROWELL FIN.

900
WELDED TO G.I. PIPE
19mm SQUARE BAR
2500

LANDING HANDRAIL @146mm O.C.


WELD TO G.I. PIPE

TYPICAL

L
HANDRAIL @146mm O.C.
9

900

A L
50
8
A-5

900

850
A-5 6 SECOND F.F.L.
5

W
HANDRAIL DETAIL

TYPICAL
A-5

168
18 17

146
ANCHOR @R.C. STAIR

19 16
A-5 SCALE : 1:20 mts

50
LANDING ANCHOR @R.C. STAIR
TREAD
15 50mm G.I. PIPE SCH.
DN
40 w/19mm SQ. BAR
@ 292mm EACH = 4672mm

14
@146mm ON CENTER 146
25x25x2mm ANGULAR
7000

13 PAINT FIN.
BAR NOSING
7 9 SPOT DETAIL
12 292
25
CRASH RAILING
TYPICAL
11
A-5 SCALE : 1:20 mts A-5 SCALE : 1:20 MTS

10
4 SECTION DETAIL

25
2x25x25mm
4672

A-5 SCALE : 1:20 mts


ANGULAR BAR

337
NOSING @STEP

12x12x2mm FLAT
16 TREADS

BAR STRAP
@600mm O.C.

175
50mm SCH. 40 G.I.
175 50mm G.I. PIPE
PIPE PAINT FIN. 50
SCHEDULE 40
50 50
6 NOSING DETAIL (PAINT FINISH)
19mm SQ. BAR

B A-5 SCALE : 1:10 mts ANCHORED TO THE WALL

(PAINT FIN.)

TREAD
(SECOND FLOOR TO GROUND FLOOR)

100

50
900mm FROM
2 DETAIL PLAN OF STAIR 19 mm SQUARE
BAR ANCHOR TO

1:50 mts THE WALL (PAINT


A-5 SCALE :
FIN.)

5 6
7000 2500

8 SPOT DETAIL
ROOF LINE 2460 4540
4500

2200 A-5 SCALE : 1:5 MTS

2067

A 10 SPOT DETAIL
W-1
11 A-5 SCALE : 1:5 MTS
3200
1100

W-1 A-5
TOILET 4 146
2328
100

A-6

200
100 650 100
@168
850

900
700
SECOND FLOOR LINE CORRIDOR
2 RISERS

19 50mm G.I.PIPE SCH. 40


17
C HANDRAIL w/25mm SQ.
337

18
18 16
LANDING 17
50mm SCH. 40 G.I. BRACKECT @600mm O.C. C
16 PAINT FIN.
19 15 15
PIPE HANDRAIL w/19mm
SQ. BAR @146mm O.C
14
14 38mm STAINLESS
13
2856
= 4672mm

STEEL GRAB BAR 1


12 5

200
13
7000

W-3 0
5mm THK.

0
11

20
PLASTER PAINT FIN. FACIAL MIRROR 700 400 10
RISERS @168 =

12
3200

100mm THK CHB RAILING

700
9
2863

PLASTER AND PAINT FIN.


2763

11 8

600
7 SECOND FLOOR LEVEL

50
200x200mm VITRIFIED
16TREADS @ 292mm EACH

10 50mm G.I. PIPE SCH.


GLAZED WALL TILES 6
40 w/19mm SQ. BAR
295

300
5

1726
1625
4672

200
9 @146mm ON CENTER 292 4
PAINT FIN. CS LAV 3
8 342

168
WC

900

900
WC 2 ELEV.
787

700
17

7
GROUND FLOOR LINE
1
CORRIDOR SCALE: 1:50m DETAIL
SHE HCR SCALE: 1:20m
6
325

10 NATURAL GRADE LINE


5
A-5 11 BALCONY RAILING DET.
4
2460 4672
A-5 SCALE: AS SHOWN
292

3
16 TREADS @ 292 = 4672
50

B 1

UP 3 DETAIL SECTION OF STAIR


7
(GRD FLOOR TO SECOND FLOOR)
1
A-5 A-6 SCALE : 1:50 mts.

DETAIL PLAN OF STAIR


A-5 SCALE : 1:100 mts

CONSULTANT / DESIGNER REVIEWED BY: RECOMMENDING APPROVAL : APPROVED FOR ACCREDITATION : CONCURRED : PROJECT TITLE : PROJECT NO: OWNER : SHEET NO:

REPUBLIC OF THE PHILIPPINES DESIGNED BY:


IC
o
f t he PH
IL
I
F
E A

TWO STOREY DEPARTMENT OF EDUCATION


DEPARTMENT OF EDUCATION (DepED)
T
M
L

P
B

TA
PU

I TO R I NG
IN

SK
RE

ES

DepED A-5
EMMANUEL P. CUNTAPAY SOFIA T. SANTIAGO GILBERTO S. REYES RAMON C. BACANI SIX CLASSROOM
F O RC E

ALBERT Z. DE BELEN
ON

ENCODED BY: Max C.


D

TASK FORCE ENGINEERING, ASSESSMENT AND MONITORING


M
PE

NO

EN

MCMXCIX
&

IN
G
I

T
A

E N

G.I. ROOF SCHOOL BUILDING


E
R

ER
T

IN SM
A

A S SE S
T C
M
E U G ,
DE

ARCHITECT / ENGINEER
TN

CHIEF, ARCHITECTURAL DIVISION OIC, DIRECTOR III OIC, DIRECTOR IV


F O

UNDERSECRETARY
MERALCO AVENUE, PASIG CITY
6
SHEET CONTENTS :
BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH DEPATMENT OF EDUCATION (DepED) CHECKED BY:
PRC NO. : 0010990 TIN : 149 460 161 STAIR AND RAILING DETAIL
PTR NO. : DATE : 27 OCT. 2002
LOCATION : DATE : 08/06/2004

NOTE:
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF TASK FORCE ENGINEERING, ASSESSMENT AND
MONITORING AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


PLAIN CEM. PLASTER 3mm THK. FACIAL
PAINT FIN. MIRROR ON AL. FRAMING

1100

650

200x200mm VITRIFIED
7 8 200x200mm GLAZED
1100
WALL TILES (GLAZED)
WALL TILES 350 400 350

600
4500
PLAIN CEM. PLASTER
PAINT FIN.
PLAIN CEMENT PLASTER
PAINT WALL FINISH

200

1710
100 1700 200X200 VITRIFIED
CERAMIC WALL
2ND FLR. LVL.
TILES ( GLAZED )

600
W-3 COUNTER SINK
4

300
512

LANDING LVL. A-7 LANDING

100

800
6
A-7
3200

W-3
2688

2738
2613
CONC. COUNTER 5 DET.PLAN OF C. SINK 6 DETAIL ELEVATION

1600
SINK

300
A-7 SCALE : 1:20 M
A-7 SCALE : 1:20 m.
800

WC

800
MALE
CLASSROOM LVL. TOILET
50

300
TOILET LVL.

600 URINAL

2 DETAIL SECTION OF TOILET


A-7 SCALE : 1:40 m.

DET. SECTION

2680 1820 4 SPOT DETAIL


3
A-7 A-7 SCALE : 1:20 m.

8
A-5 LINE OF DOOR JAMB

850
SHE
1100

SECOND FLOOR LINE


HE
2
A-7 LANDING FLOOR LINE 17
D-4
2074

D-4
16
D-3 50mm SCH. 40 G.I.
15 PIPE HANDRAIL w/19mm
SQ. BAR @300mm OC.
14
1100

10
13
850

D-3 38mm STAINLESS A-5


12
STEEL GRAB BAR
W-3
5mm THK. FACIAL 11

0
20
PLASTER PAINT FIN. 150mm THK CHB WALL
MIRROR
UNDER SLAB 700 400 10 PLASTER PAINT FIN.

3200
9

2856
8

2763

600
7
200x200mm VITRIFIED
D-2
GLAZED WALL TILES 6

2100

2100
5

200
1609 1074
1500

300
1625
292 4
3
342
HCR

920
2

168
1
SHE HCR
GROUND FLOOR LINE

NATURAL GRADE LINE

1 DET. PLAN OF TOILET 922 1259 1615 3336

A-7 SCALE : 1:30 m.

3 DET. SECTION OF TOILET/STAIR


A-7 SCALE : 1 : 30 m.

CONSULTANT / DESIGNER REVIEWED BY: RECOMMENDING APPROVAL : APPROVED FOR ACCREDITATION : CONCURRED : PROJECT TITLE : PROJECT NO: OWNER : SHEET NO:

REPUBLIC OF THE PHILIPPINES DESIGNED BY:


IC
o
f t he PH
IL
I
F
E A

TWO STOREY DEPARTMENT OF EDUCATION


DEPARTMENT OF EDUCATION (DepED)
T
M
L

P
B

TA
PU

I TO R I NG
IN

SK
RE

ES

DepED A-6
EMMANUEL P. CUNTAPAY SOFIA T. SANTIAGO GILBERTO S. REYES RAMON C. BACANI SIX CLASSROOM
F O RC E

ALBERT Z. DE BELEN
ON

ENCODED BY: Max C.


D

TASK FORCE ENGINEERING, ASSESSMENT AND MONITORING


M
PE

NO

EN

MCMXCIX
&

IN
G
I

T
A

E N

G.I. ROOF SCHOOL BUILDING


E
R

ER
T

IN SM
A

A S SE S
T C
M
E U G ,
DE

ARCHITECT / ENGINEER
TN

CHIEF, ARCHITECTURAL DIVISION OIC, DIRECTOR III OIC, DIRECTOR IV


F O

UNDERSECRETARY
MERALCO AVENUE, PASIG CITY SHEET CONTENTS :

6
BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH DEPATMENT OF EDUCATION (DepED) CHECKED BY:
PRC NO. : 0010990 TIN : 149 460 161 TOILET DETAIL
PTR NO. : DATE : 27 OCT. 2002
LOCATION : DATE : 08/06/2004

NOTE:
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF TASK FORCE ENGINEERING, ASSESSMENT AND
MONITORING AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


1 2 3 4 5 6 7 8

4500 4500 4500 4500 4500 4500 4500

F-3 F-3 F-3 F-3 F-3 F-3 F-3 F-3


C-3 C-3 C-3 C-3 C-3 C-3 C-3 C-3

A TG-3 TG-3 TG-3 TG-3 TG-3 TG-3 TG-3

TG-2

TG-2

TG-2

TG-2

TG-2
7000
100mm THICK
SLAB ON FILL
WITH 10mm
SPACED AT 400
BOTHWAYS

F-2 F-2 F-2 F-2 F-2 F-2 F-2 F-2


C-2 C-2 C-2 C-2 C-2 C-2 C-2 C-2

B TG-3 TG-3 TG-3 TG-3 TG-3 TG-3 TG-3

2500

TG-1

TG-1

TG-1

TG-1
B

S-3

F-1 F-1 F-1 F-1 F-1 F-1 F-1 F-1


C C-1
TG-3
C-1
TG-3
C-1
TG-3
C-1
TG-3
C-1
TG-3
C-1
TG-3
C-1
TG-3
C-1

A FOUNDATION PLAN
S-1 SCALE : 1:100 M.

1 2 3 4 5 6 7 8

4500 4500 4500 4500 4500 4500 4500

G-3 G-3 G-3 G-3 G-3 G-3 G-3a


A

STAIR WELL
S-1 S-1 S-1 S-1 S-1 S-1
G - 7

G - 7

G - 7

G - 7

G - 7

G - 7
B-1 B-1 B-1 B-1 B-1 B-1 CB-1
7000

G-5

G-5
B-2
S-2
S-1 S-1 S-1 S-1 S-1 S-1

G-2 G-2 G-2 G-2 G-2 G-2 G-2


B
S-2 S-2 S-2 S-2 S-2 S-2 S-2
2500

G-4

G-6

G-6

G-6

G-6

G-6

G-6

G-4
G-1 G-1 G-1 G-1 G-1 G-1 G-1
C

B 2ND FLOOR FRAMING PLAN


S-1 SCALE : 1:100 M.

CONSULTANT / DESIGNER REVIEWED BY: RECOMMENDING APPROVAL : APPROVED FOR ACCREDITATION : CONCURRED : PROJECT TITLE : PROJECT NO: OWNER : SHEET NO:

REPUBLIC OF THE PHILIPPINES DESIGNED BY:


IC
o
f t he PH
IL
I
F
E A

TWO STOREY DEPARTMENT OF EDUCATION


DEPARTMENT OF EDUCATION (DepED)
T
M
L

P
B

TA
PU

I TO R I NG
IN

SK
RE

ES

ANTONIA M. MANIO WILFREDO S. LOPEZ SOFIA T. SANTIAGO GILBERTO S. REYES RAMON C. BACANI SIX CLASSROOM DepED
F O RC E

S-1
ON

ENCODED BY: Max C.


D

TASK FORCE ENGINEERING, ASSESSMENT AND MONITORING


M
PE

NO

EN

MCMXCIX
&

IN
G
I

T
A

E N

G.I. ROOF SCHOOL BUILDING


E
R

ER
T

IN SM
A

A S SE S
T C
M
E U G ,
DE
TN

OIC, STRUCTURAL DIVISION OIC, DIRECTOR III OIC, DIRECTOR IV


F O

CIVIL ENGINEER UNDERSECRETARY


MERALCO AVENUE, PASIG CITY SHEET CONTENTS :

PRC NO. : 70071 TIN : 188-342-853


BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH DEPATMENT OF EDUCATION (DepED) CHECKED BY:
4
FOUNDATION
PTR NO. : DATE : LOCATION : DATE : 08/06/2004 2ND FLOOR PLAN

NOTE:
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF TASK FORCE ENGINEERING, ASSESSMENT AND
MONITORING AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


1 2 3 4 5 6 7 8
4500 4500 4500 4500 4500 4500 4500

RG-1 RG-1 RG-1 RG-1 RG-1 RG-1 RG-1


A

RG-2

RG-2

RG-2

RG-2

RG-2

RG-2

RG-2

RG-2
T-1

T-1

T-1

T-1

T-1

T-1

T-1

T-1
7000
B
RG-1 RG-1 RG-1 RG-1 RG-1 RG-1 RG-1

2500

RG-1

RG-1
RG-1

RG-1

RG-1

RG-1

RG-1

RG-1
RG-1 RG-1 RG-1 RG-1 RG-1 RG-1 RG-1
C

LC-120x40x20x2.0 PURLINS
12mm CROSS
SPACED @ 750 mm O.C
BRACINGS
WITH %10 SAGRODS @ MIDSPAN

A ROOF DECK FRAMING PLAN


S-2 SCALE : 1:100 M.

L1 L2

L1/3 TOP BAR


L1/3 L2/3 TOP BAR

L1/6 BOTTOM BAR L1/5 L2/5 BOTTOM BAR

B TYPICAL SLAB ELEVATION


S-2

S C H E D U L E OF S L A B S
REBAR SPACING ALONG SHORT DIRECTION REBAR SPACING ALONG LONG DIRECTION
in mm in mm
THICK-
FLOOR SLAB
NESS LEFT SUPPORT MIDSPAN RIGHT SUPPORT LEFT SUPPORT MIDSPAN RIGHT SUPPORT REMARKS
LEVEL MARK REBAR REBAR
in mm SIZE SIZE
TOP BOTT. TOP BOTT. TOP BOTT. TOP BOTT. TOP BOTT. TOP BOTT.
LEVEL
SECOND

S-1 100 10 200 300 - 300 200 300 10 250 300 - 300 250 300 TWO-WAY

S-2 100 10 300 300 - 300 300 300 10 300 300 - 300 300 300 TWO-WAY

CONSULTANT / DESIGNER REVIEWED BY: RECOMMENDING APPROVAL : APPROVED FOR ACCREDITATION : CONCURRED : PROJECT TITLE : PROJECT NO: OWNER : SHEET NO:

REPUBLIC OF THE PHILIPPINES DESIGNED BY:


IC
o
f t he PH
IL
I
F
E A

TWO STOREY DEPARTMENT OF EDUCATION


DEPARTMENT OF EDUCATION (DepED)
T
M
L

P
B

TA
PU

I TO R I NG
IN

SK
RE

ES

ANTONIA M. MANIO WILFREDO S. LOPEZ SOFIA T. SANTIAGO GILBERTO S. REYES RAMON C. BACANI SIX CLASSROOM DepED
F O RC E

S-2
ON

ENCODED BY: Max C.


D

TASK FORCE ENGINEERING, ASSESSMENT AND MONITORING


M
PE

NO

EN

MCMXCIX
&

IN
G
I

T
A

E N

G.I. ROOF SCHOOL BUILDING


E
R

ER
T

IN SM
A

A S SE S
T C
M
E U G ,
DE
TN

OIC, STRUCTURAL DIVISION OIC, DIRECTOR III OIC, DIRECTOR IV


F O

CIVIL ENGINEER UNDERSECRETARY


MERALCO AVENUE, PASIG CITY SHEET CONTENTS :

PRC NO. : 70071 TIN : 188-342-853


BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH DEPATMENT OF EDUCATION (DepED) CHECKED BY:
3
ROOF DECK FRAMING PLAN
PTR NO. : DATE : LOCATION : DATE : 08/06/2004 SCHEDULE OF SLAB

NOTE:
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF TASK FORCE ENGINEERING, ASSESSMENT AND
MONITORING AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


C O L U M N S C H E D U L E AS SHOWN
%10 SPACED

8
MAIN BARS
%10 @250 10 @250
CUT BARS
7
LEVEL C-1 C-2 C-3 1-10
NOSING BAR
NGL

100
350 350 350

125
5
TIE BEAM

12
10 300mm TEMP
(SEE SCHEDULE)
BARS BOTHWAYS

100
400
350

350

350
4-10 CONT. BARS

125
10 @250
10mm
CUT BARS
FLOOR LEVEL TO

DECKLEVEL

DETAIL OF TIE BEAM DETAIL OF STAIR ON GRADE DETAIL OF RAMP


MAIN BAR: MAIN BAR: MAIN BAR:

6-%16mm 8-%20mm 8-%20mm


A B C
SCALE NTS SCALE 1 : 25M SCALE 1 : 50M
TIES : 10 mm TIES : 10 mm TIES : 10 mm S-3 S-3 S-3
1@50, 8@75, REST @ 1@50, 8@75, REST @ 1@50, 8@75, REST @
ROOF

150mm TO CENTER 150mm TO CENTER 150mm TO CENTER


2ND

L1 L2 L3

350 350 350


L2/3 L2/3 L3/3 L3/3

2D 2D LAP SPLICES ARE ALLOWED 2D 2D LAP SPLICES ARE ALLOWED 2D


ONLY IN THIS PORTION ONLY IN THIS PORTION

D
350

350

350
L2/5 L2/5 L2/5 L3/6
LEVEL TO

2-12mm SIDE BARS


2ND FLOOR LEVEL

MAIN BAR:

8-%16mm
MAIN BAR:

14-%20mm
MAIN BAR:

12-%20mm
D TYPICAL BEAM ELEVATION
FOUNDATION

TIES : 10 mm TIES : 10 mm TIES : 10 mm


S-3
1@50, 8@75, REST @ 1@50, 8@75, REST @ 1@50, 8@75, REST @
150mm TO CENTER 150mm TO CENTER 150mm TO CENTER

B E A M S C H E D U L E

BEAM S T E E L R E I N F O R C E M E N T S
DIMENSIONS S T I R R U P S
FLOOR BEAM
LEVEL MARK ( in / mm ) REBAR
LEFT MID SPAN RIGHT
10mm
L
(mm ) (UNLESS NOTED OTHERWISE)
b h TOP BOTTOM TOP BOTTOM TOP BOTTOM

NGL
G-1 200 400 20mm 2 2 2 2 2 2 1@50, 6@100, REST@200

G-2 200 400 20mm 4 3 2 2 4 3 1@50, 6@100, REST@200

G-3 200 400 20mm 3 2 2 2 3 2 1@50, 6@100, REST@200


D

Y-BARS
X-BARS G-3a 200 800 20mm 3 2 2 2 3 2 1@50, 8@175, REST@300
W

G-4 200 400 20mm 3 2 2 2 3 3 1@50, 6@100, REST@200

2ND FLOOR LEVEL


t

Y-BARS G-5 250 500 20mm 5 3 2 4 5 3 1@50, 8@100, REST@200


100

X-BARS
G-6 200 400 20mm 3 2 2 2 3 3 1@50, 6@100, REST@200
100 mm THICK
L G-7 250 500 20mm 5 3 2 6 5 3 1@50, 8@100, REST@200
GRAVEL BEDDING

PLAN SECTION B-1 200 400 16mm 4 2 2 2 4 2 1@50, 6@100, REST@200

B-2 200 400 16mm 2 2 2 4 2 2 1@50, 6@100, REST@200

E TYP. FOOTING DETAIL CB-1 200 400 16mm 4 2 4 2 4 2 1@50, 6@100, REST@200

SCALE NTS
S-3
RG-1 200 400 16mm 2 2 2 2 2 2 1@50, 6@100, REST@200

ROOF
LEVEL
RG-2 200 500 16mm 3 3 2
3 3 3 3 1@50, 8@100, REST@200

S C H E D U L E O F F O O T I N G
TG-1 300 500 20mm 3 2 2 2 4 3 1@50, 8@100, REST@200

BEAM
FOOTING DIMENSIONS (mm)

TIE
REINFORCEMENT REMARKS
FOOTING TG-2 300 500 20mm 4 3 2 2 4 3 1@50, 8@100, REST@200

MARK LENGTH WIDTH DEPTH Thickness


BAR X BAR Y TG-3 300 500 20mm 3 3 2 2 3 3 1@50, 6@100, REST@200
(L) (W) (D) (t)

F-1 1100 1100 1500 250 5 - 16mm% 5 - 16mm% SQUARE FOOTING


STB-1 200 400 16mm 3 2 2 4 3 2 1@50, 6@100, REST@200
BEAM
STAIR

SQUARE FOOTING STB-2 200 500 16mm 4 2 2 4 4 2 1@50, 8@100, REST@200


F-2 2200 2200 1500 300 12 - 16mm% 12- 16mm%

F-3 1900 1900 1500 300 11 - 16mm% 11 - 16mm% SQUARE FOOTING

CONSULTANT / DESIGNER REVIEWED BY: RECOMMENDING APPROVAL : APPROVED FOR ACCREDITATION : CONCURRED : PROJECT TITLE : PROJECT NO: OWNER : SHEET NO:

REPUBLIC OF THE PHILIPPINES DESIGNED BY:


IC
o
f t he PH
IL
I
F
E A

TWO STOREY DEPARTMENT OF EDUCATION


DEPARTMENT OF EDUCATION (DepED)
T
M
L

P
B

TA
PU

I TO R I NG
IN

SK
RE

ES

ANTONIA M. MANIO WILFREDO S. LOPEZ SOFIA T. SANTIAGO GILBERTO S. REYES RAMON C. BACANI SIX CLASSROOM DepED
F O RC E

S-3
ON

ENCODED BY: Max C.


D

TASK FORCE ENGINEERING, ASSESSMENT AND MONITORING


M
PE

NO

EN

MCMXCIX
&

IN
G
I

T
A

E N

G.I. ROOF SCHOOL BUILDING


E
R

ER
T

IN SM
A

A S SE S
T C
M
E U G ,
DE
TN

OIC, STRUCTURAL DIVISION OIC, DIRECTOR III OIC, DIRECTOR IV


F O

CIVIL ENGINEER UNDERSECRETARY


MERALCO AVENUE, PASIG CITY SHEET CONTENTS :

PRC NO. : 70071 TIN : 188-342-853


BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH DEPATMENT OF EDUCATION (DepED) CHECKED BY:
4
DET. STAIR ON GRADE, RAMP & BEAM
PTR NO. : DATE : LOCATION : DATE : 08/06/2004 DET. OF FOOTING, TIE BEAM & COLUMN
NOTE:
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF TASK FORCE ENGINEERING, ASSESSMENT AND
MONITORING AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


S-4
L

5 S-3
6
C
250 4500
S-4

29 30 25 38 38 25 30 29 2200 2200

6mm GUSSET PLATE

BOTTOM CHORD A
2500

W-2
1
W
- 4-12x300mm LONG A

W
1

2
-

W-2

W-2
W

-
-
BENT ANCHOR BOLTS

W
2
2

2
F

W-2
-
S-2

W-2
-

2150
W

W
S-4

50
2

W-2
- 250x200x10mm BASE

W-2
W

2834
PLATE

1187
W-1
W-2

W-2

200

100
STB-2
E
W-2 S-4
2L-2x2x1/4 STRUT W-2 DC-1
DC-1

1000 2-SPAN @1250 2-SPAN @1125 4-SPAN @1187.5 1000 P


2500 2250 4750

50
9500 S-3
SEE SCHEDULE OF

= 4500mm
2ND FLOOR LEVEL
DN S-2 (2ND/3RD LVL)
CB-1 FOR DETAIL OF REIN.
CB-1

PLAN

7000
A DETAIL OF T-1 G-3a
STB-2 M
G-2

15 TREADS @ 300mm EACH


SCALE 1 : 25 M S-3
S-3 2150
N

4500

3200
S-3

2856
6mm GUSSET PLATE
292
250

SCHEDULE OF TRUSS MEMBERS

0
BOTTOM CHORD (FULLY

20
29 30 25 38 38 25 30 29
WELDED TO BASE PLATED)

B-2
TO 6mm GUSSET PLATE (TYP.)

168
P
RD CH
O O
CH RD
MARK DESCRIPTION
P QTY SIZE 4-12x300mm LONG
TO
BENT ANCHOR BOLTS

W-1 TOP & BOT. CHORDS 2L 2"x2"x1/4" GROUND FLOOR LEVEL


250x200x10mm BASE
PLATE
W-2 WEB MEMBERS 2L 2"x2"x3/16"

FULL WELD
COLUMN OR BEAM
B S-3
TG-3

O
KING POST

D CONNECTION DETAIL K STAIR FRAMING PLAN (TYP.) L STAIR SECTION DETAIL


1 : 5 M
S-3
SCALE
O
RD S-3 SCALE 1:50 M
S-3 SCALE 1:50 M

CH
TO
P 6mm GUSSET PLATE (TYP.)

16 @200 10 @300
FULL WELD
TEMP BARS

12@ 125 TOP 12@ 125


MAIN BARS STEP BARS 2-10

SECTION STEP BAR

200mm 200

200
12 @120

TYPICAL TRUSS

200
H ANCHORAGE DETAIL 16 @ 200
MAIN BAR MAIN BAR:
FULL WELD SCALE 1:5 M 4-16mm
S-3

0
0
F CONNECTION DETAIL M SECTION OF STAIR SLAB

2
6mm GUSSET PLATE (TYP.) %12 @300
TIES : 10 mm

SCALE 1 : 5 M 1@50, 8@75, REST @


S-3 S-3 SCALE 1:25 M
150mm TO CENTER

N SPOT DETAIL DC-1


BOTTOM CHORD SCALE 1 : 25 M
SEE TRUSS ANCHORAGE DETAIL
S-3 (FROM LANDING TO
2ND/3RD FLOOR LEVEL)
CONNECTION DETAIL
W 10 @300
-
E 1

SCALE 1 : 5 M 120x40x20x2.0mm
S-3 STEEL C-PURLINS
2-10
750mm O.C.
STEP BAR
10mm% SAG ROD WITH 200mm
STANDARD NUTS & 10 @300
75

W-2
WASHERS @ EACH END
7
50
LC-120x40x20x2.0 6-%10x200mm LONG
2-10
PURLINS
STEP BAR
75

1-%10mm A-307
ANCHOR BOLT
L-2.5x2.5x1/4

100
100
100 100
100
CB-1
W-2
10mm @
TG-3
300mm o.c.

3-10mm STB-2

HALF TRUSS O SPOT DETAIL P SPOT DETAIL


G PURLIN CONNECTION DETAIL I SAG ROD CONNECTION DETAIL J CONNECTION DETAIL S-3
SCALE 1 : 25 M
S-3
SCALE 1 : 25 M

SCALE 1 : 5 M SCALE 1 : 10 M SCALE 1 : 10 M


S-3 S-3 S-3

CONSULTANT / DESIGNER REVIEWED BY: RECOMMENDING APPROVAL : APPROVED FOR ACCREDITATION : CONCURRED : PROJECT TITLE : PROJECT NO: OWNER : SHEET NO:

REPUBLIC OF THE PHILIPPINES DESIGNED BY:


IC
o
f t he PH
IL
I
F
E A

TWO STOREY DEPARTMENT OF EDUCATION


DEPARTMENT OF EDUCATION (DepED)
T
M
L

P
B

TA
PU

I TO R I NG
IN

SK
RE

ES

ANTONIA M. MANIO WILFREDO S. LOPEZ SOFIA T. SANTIAGO GILBERTO S. REYES RAMON C. BACANI SIX CLASSROOM DepED S-4
F O RC E

ON

ENCODED BY: Max C.


D

TASK FORCE ENGINEERING, ASSESSMENT AND MONITORING


M
PE

NO

EN

MCMXCIX
&

IN
G
I

T
A

E N

G.I. ROOF SCHOOL BUILDING


E
R

ER
T

IN SM
A

A S SE S
T C
M
E U G ,
DE
TN

OIC, STRUCTURAL DIVISION OIC, DIRECTOR III OIC, DIRECTOR IV


F O

CIVIL ENGINEER UNDERSECRETARY


MERALCO AVENUE, PASIG CITY
4
SHEET CONTENTS :
BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH DEPATMENT OF EDUCATION (DepED) CHECKED BY:
PRC NO. : 70071 TIN : 188-342-853
TRUSS DIAGRAM, DETAIL OF STAIR
PTR NO. : DATE : LOCATION : DATE : 08/06/2004 DETAILS OF STEEL CONNECTION

NOTE:
THE REVIEW & APPROVAL OF THIS PLANS BY THE DPWH DOES NOT RELIEVE THE DESIGNER/CONSULTANT THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF TASK FORCE ENGINEERING, ASSESSMENT AND
FROM RESPONSIBILTY FOR THE SAFETY OF THE COMPLETED FACILITIES AS WELL AS FOR THE FAILURE
MONITORING AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
OF THE SAME DUE TO FAULTY DESIGN. ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


LEGEND LOAD SCHEDULE
GENERAL NOTES
SYMBOL DESCRIPTION
1. ALL ELECTRICAL WORKS SHALL COMPLY IN ACCORDANCE WITH

THESE PLANS AND SPECIFICATIONS. THE APPLICABLE PROVISIONS - CEILING LIGHT OUTLET
PANELBOARD: LP MAIN : 100AT, 100AF, 2P, 230V
OF THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL CODE (PEC). 2
- 2 x 40 WATTS FLUORESCENT LAMP

THE RULES AND REGULATION OF THE LOCAL ENFORCING AUTHORITY CIRCUIT BREAKER
F - CEILING FAN OUTLET CKT. VA
DESCRIPTION WIRE & CONDUIT SIZE
AND THE REQUIREMENTS OF THE LOCAL POWER COMPANY. NO. LOAD
S/Sa - ONE GANG DEVICE SWITCH VOLT POLE AT AF

THE ELECTRICAL WORKS SHALL BE UNDER IMMEDIATE SUPERVISION


2
CONV. OUTLET - 9 x 180W 1620 230 2 50
S ab - TWO GANG DEVICE SWITCH 1 20 3-3.5mm THW IN 15mm C
OF A DULY REGISTERED ELECTRICAL ENGINEER.
2
S cde - THREE GANG DEVICE SWITCH 2 CONV. OUTLET - 9 x 180W 1620 230 2 20 50 3-3.5mm THW IN 15mm C
2. THE ELECTRICAL SERVICE POWER IS 1-PHASE, 2-WIRE,
LIGHT OUTLET - 7 x 100W 2
230 V AC, 60 Hz. S 3W - THREE WAY DEVICE SWITCH 3
EXHAUST FAN OUTLET - 1 x 180W
880 230 2 20 50 3-3.5mm THW IN 15mm C

2
3. WIRING METHOD SHALL BE AS FOLLOWS : Sf - FAN CONTROL SWITCH 4 LIGHT OUTLET - 15 x 100W 1500 230 2 20 50 3-3.5mm THW IN 15mm C

2
a. FEEDERS AND RISERS - INTERMEDIATE METALLIC CONDUIT - EXHAUST FAN SWITCH 5 LIGHT OUTLET - 10 x 100W 1000 230 2 20 50 3-3.5mm THW IN 15mm C
S EF
2
b. LIGHTING, POWER RECEPTACLE - POLYVINYL CHLORIDE CONDUIT - RACEWAY CONDUIT CONCEALED IN CEILING 6 LIGHT OUTLET - 10 x 100W 1000 230 2 20 3-3.5mm THW IN 15mm C
50
BRANCH CKT., & AUXILIARY SCH. 40
- RACEWAY CONDUIT CONCEALED UNDER FLOOR 7 S P A R E 1500 230 2 20 50

4. ALL WIRES SHALL BE COPPER AND THERMOPLASTIC INSULATED TYPE


8 S P A R E 1500 230 2 20 50
"THW" UNLESS OTHERWISE INDICATED IN THE PLAN. THE MINIMUM
- PANELBOARD
TOTAL 10620
SIZE OF WIRE FOR POWER AND LIGHTING CIRCUIT HOMERUN SHALL BE
2
- CKT. BREAKER, RATING AS INDICATED
3.5mm AND INSULATED FOR 600 VOLTS. SMALLEST RACEWAY SHALL
- DUPLEX CONVENIENCE OUTLET, GROUNDING TYPE
BE 15mmO
I TRADE/NOMINAL SIZE.
10 AMPS, 250 VOLT WITH MODERN PLATE COVER IL @ 80D.F. = 10620 x 80 x 1.25 = 46.2 A
5. ALL OUTLET BOXES SHALL BE GALVANIZED GAUGE NO. 16 DEEP
- EXHAUST FAN OUTLET, SINGLE, GROUNDING TYPE 230 V
TYPE WITH FACTORY KNOCKOUTS. EF
10 AMPS, 250 VOLT WITH MODERN PLATE COVER
6. ALL MATERIALS TO BE USED SHALL BE BRAND NEW AND APPROVED LP 2

- HOMERUN DIRECT TO PANELBOARD FEEDER: 2-30mm THW IN 32mm C


TYPE FOR THE PARTICULAR LOCATION AND PURPOSE OF USAGE.
PROTECTION: 100 AT, 100 AF, 2P, 230 V
- PUSH BUTTON
7. GROUNDING SYSTEM SHALL BE PROVIDED TO ALL LIGHTING AND
POWER CIRCUIT AS PER PHILIPPINE ELECTRICAL CODE REQUIREMENT. - ENCLOSED AIR CIRCUIT BREAKER

FA - FIRE ALARM CONTROL PANEL


8. MOUNTING HEIGHT OF WIRING DEVICES SHALL BE AS FOLLOWS :
F - FIRE ALARM STATION OUTLET
a. LIGHT SWITCH - 1.20 M ABOVE FINISH FLOOR
- VIBRATING BELL OUTLET
B

b. CONVENIENCE OUTLET - 0.30 M ABOVE FINISH FLOOR.


B - FIRE ALARM BELL

c. PANELBOARD - 1.50 M ABOVE FINISH FLOOR M - SERVICE METER


OVERHEAD SERVICE ENTRANCE
CONNECTED TO 220V AC, 1O,
- SERVICE ENTRANCE 2 WIRE, 60 Hz FITTED WITH
32mm O TYPE "F" CONDULET
d. FIRE ALARM STATION OUTLET - 1.50 M. ABOVE FINISH FLOOR

BUILDING WALL
e. PUSH BUTTON OUTLET - 1.20 M ABOVE FINISH FLOOR
TO SIMILAR OUTLET

@ SECOND FLOOR
2ND FLOOR LINE

f. FIRE ALARM & VIBRATING BELL - 0.30 M BELOW CEILING LINE

PANEL LP
2
2-30mm THW B B
IN 32MMORSC

TO LINE SIDE OF LP

100AT, 100AF, 2P, 230V AC F


METERING CONDUIT
2
3-3.5mm THW
20 20
KWHR METER IN 15MMORSC

FA
20 20 2
2-3.5mm THW
IN 15MMORSC

20
20 TO NEAREST C.O.
ENCLOSED ACB
RATING: 20AT, 50AF,
230V, 2P

1500 mm
2
2-3.5mm THW

1800 mm
20 20
IN 15MMORSC

GROUND TERMINAL
ELECTRICAL FIRE ALARM VIBRATING BELL
GROUND FLOOR LINE

2
#8mm BARE COPPER WIRE
FIN. GRADE LINE

2
1-8.0mm BARE COPPER WIRE
16mm O x 2.40m
IN 15mmO C
I

COPPERWELD
GROUND ROD 16MMO x 240MM LENGTH
GROUNDING ROD COPPERWELD

SINGLE LINE DIAGRAM RISER DIAGRAM


NOT TO SCALE
NOT TO SCALE

CONSULTANT / DESIGNER REVIEWED BY: RECOMMENDING APPROVAL : APPROVED FOR ACCREDITATION : CONCURRED : PROJECT TITLE : PROJECT NO: 99-013 OWNER : SHEET NO:

REPUBLIC OF THE PHILIPPINES DESIGNED BY: RDS


IC
o
f t he PH
IL
I
F
E A

TWO STOREY DEPARTMENT OF EDUCATION


DEPARTMENT OF EDUCATION (DepED)
T
M
L

P
B

TA

E-1
PU

I TO R I NG
IN

SK
RE

ES

VENERANDO D. SAHAGUN FE M. BARRIENTOS SOFIA T. SANTIAGO GILBERTO S. REYES RAMON C. BACANI SIX CLASSROOM DepED
F O RC E

ON

ENCODED BY: Max


RDS C.
D

TASK FORCE ENGINEERING, ASSESSMENT AND MONITORING


M
PE

NO

EN

MCMXCIX
&

IN
G
I

T
A

E N

G.I. ROOF SCHOOL BUILDING


E
R

ER
T

IN SM
A

A S SE S
T C
M
E U G ,
DE
TN

OIC, DIRECTOR III OIC, DIRECTOR IV


F O

ENGINEER III CHIEF, ELECTRICAL DIVISION UNDERSECRETARY


MERALCO AVENUE, PASIG CITY SHEET CONTENTS :
BUREAU OF DESIGN, DPWH CHECKED BY: LOAD SCHEDULE
3
BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH DEPATMENT OF EDUCATION (DepED)
PRC NO. : TIN :
GENERAL NOTES LEGEND
PTR NO. : DATE : LOCATION : : 08/06/2004
DATE :5-5-00 SINGLE LINE DIAGRAM RISER DIAGRAM

NOTE:
THE REVIEW & APPROVAL OF THIS PLANS BY THE DPWH DOES NOT RELIEVE THE DESIGNER/CONSULTANT THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF TASK FORCE ENGINEERING, ASSESSMENT AND
FROM RESPONSIBILTY FOR THE SAFETY OF THE COMPLETED FACILITIES AS WELL AS FOR THE FAILURE
MONITORING AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
OF THE SAME DUE TO FAULTY DESIGN. ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


1 2 3 4 5 6 7 8

CLASSROOM CLASSROOM CLASSROOM

B
LP

B B
F

SECOND FLOOR POWER LAYOUT


SCALE 1 : 100 M

1 2 3 4 5 6 7 8

CLASSROOM CLASSROOM CLASSROOM

B
UP

TO C.O.
LP

B B LP
TO FA
F

C
FA

ENCLOSED AIR CIRCUIT BREAKER


RATING: 220 V, 2P, 20AT, 50AF
TO LINE SIDE OF LP

OVERHEAD SERVICE ENTRANCE


REFER TO RISER DIAGRAM

GROUND FLOOR POWER LAYOUT


SCALE 1 : 100 M

CONSULTANT / DESIGNER REVIEWED BY: RECOMMENDING APPROVAL : APPROVED FOR ACCREDITATION : CONCURRED : PROJECT TITLE : PROJECT
PROJECTNO:
NO:99-017 OWNER : SHEET NO:

REPUBLIC OF THE PHILIPPINES DESIGNED


DESIGNEDBY:
BY:RDS
IC
o
f t he PH
IL
I
F
E A

TWO STOREY DEPARTMENT OF EDUCATION


DEPARTMENT OF EDUCATION (DepED)
T
M
L

P
B

TA
PU

I TO R I NG

E-2
IN

SK
RE

ES

VENERANDO D. SAHAGUN FE M. BARRIENTOS SOFIA T. SANTIAGO GILBERTO S. REYES RAMON C. BACANI SIX CLASSROOM DepED
F O RC E

ON

ENCODED
ENCODEDBY: Max C.
BY:RDS
D

TASK FORCE ENGINEERING, ASSESSMENT AND MONITORING


M
PE

NO

EN

MCMXCIX
&

IN
G
I

T
A

E N

G.I. ROOF SCHOOL BUILDING


E
R

ER
T

IN SM
A

A S SE S
T C
M
E U G ,
DE
TN

OIC, DIRECTOR III OIC, DIRECTOR IV


F O

ENGINEER III CHIEF, ELECTRICAL DIVISION UNDERSECRETARY


MERALCO AVENUE, PASIG CITY SHEET CONTENTS :
BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH DEPATMENT OF EDUCATION (DepED) CHECKED
CHECKEDBY:
BY:

3
BUREAU OF DESIGN, DPWH
PRC NO. : TIN :
GROUND FLOOR POWER LAYOUT
PTR NO. : DATE : LOCATION : DATE : 08/06/2004
DATE:5-5-00
SECOND FLOOR POWER LAYOUT

NOTE:
THE REVIEW & APPROVAL OF THIS PLANS BY THE DPWH DOES NOT RELIEVE THE DESIGNER/CONSULTANT THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF TASK FORCE ENGINEERING, ASSESSMENT AND
FROM RESPONSIBILTY FOR THE SAFETY OF THE COMPLETED FACILITIES AS WELL AS FOR THE FAILURE
MONITORING AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
OF THE SAME DUE TO FAULTY DESIGN. ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


1 2 3 4 5 6 7 8

A
a b c d e f 2

2 2 2 2 2 2

S
F F F

a b c d e f

2 2 2 2 2 2

LP

Sab Sf Scd Sf 6
Sef Sf
B
Sgh Sij
g h i j
2 2 2 2

LP

SECOND FLOOR LIGHTING LAYOUT


SCALE 1 : 100 M

1 2 3 4 5 6 7 8

A S EF
EF

a b c d e f S

2 2 2 2 2 2

k
Skl
F F F

a b c d e f

2 2 2 2 2 2

LP

Sab Sf Scd Sf Sef Sf 4

B
UP
Sgh Sij
g h i j
2 2 2
2

LP

C
3

RAMP
UP

GROUND FLOOR LIGHTING LAYOUT


SCALE 1 : 100 M

PROJECT NO: 99-017


CONSULTANT / DESIGNER REVIEWED BY: RECOMMENDING APPROVAL : APPROVED FOR ACCREDITATION : CONCURRED : PROJECT TITLE : PROJECT NO: OWNER : SHEET NO:

REPUBLIC OF THE PHILIPPINES DESIGNED BY: RDS


DESIGNED BY:
o
f t he PH
IL
F
E A

TWO STOREY DEPARTMENT OF EDUCATION


E-3
IC I

DEPARTMENT OF EDUCATION (DepED)


T
M
L

P
B

TA
PU

I TO R I NG
IN

SK
RE

ES

VENERANDO D. SAHAGUN FE M. BARRIENTOS SOFIA T. SANTIAGO GILBERTO S. REYES RAMON C. BACANI SIX CLASSROOM DepED
F O RC E

ENCODED BY: RDS


ON

ENCODED BY: Max C.


D

TASK FORCE ENGINEERING, ASSESSMENT AND MONITORING


M
PE

NO

EN

MCMXCIX
&

IN
G
I

T
A

E N

G.I. ROOF SCHOOL BUILDING


E
R

ER
T

IN SM
A

A S SE S
T C
M
E U G ,
DE
TN

OIC, DIRECTOR III OIC, DIRECTOR IV


F O

ENGINEER III CHIEF, ELECTRICAL DIVISION UNDERSECRETARY


MERALCO AVENUE, PASIG CITY
3
CHECKED BY: SHEET CONTENTS :
BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH DEPATMENT OF EDUCATION (DepED) CHECKED BY:
PRC NO. : TIN : GROUND FLOOR LIGHTING LAYOUT
DATE :5-5-00
PTR NO. : DATE : LOCATION : DATE : 08/06/2004 SECOND FLOOR LIGHTING LAYOUT

NOTE:
THE REVIEW & APPROVAL OF THIS PLANS BY THE DPWH DOES NOT RELIEVE THE DESIGNER/CONSULTANT THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF TASK FORCE ENGINEERING, ASSESSMENT AND
FROM RESPONSIBILTY FOR THE SAFETY OF THE COMPLETED FACILITIES AS WELL AS FOR THE FAILURE
MONITORING AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
OF THE SAME DUE TO FAULTY DESIGN. ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


1 2 3 4 5 6 7 8
9000 9000 9000

600 4500 4500 4500 4500 4500 4500 4500 600

RD RD RD RD RD RD RD RD

1000
A

7000

B
2500

C
1000

LN. OF STRUCTURE
TR
CV
PV
m

RD RD RD RD RD RD RD RD
m
50

R
E
00

W
10

E T O

E
T S T

S
R P
ROOF DRAIN LAYOUT

A S
2

S E

M
00

V
P
25 50

E
50mm PVCVTR

WTVCVP
39

Y
S
L
W

75mmPVCDS
S

P
K
AN VT

R
IC
V

G
V

C
P
m

T
5
P-1
m m

P
I m 12

mm05
C
m
SCALE : 1 : 100 METERS
W
00 m VT

T
1 50 SE
SE

R
S

P
V

C
V

C
I

P
R

P
L

P
S m m W
m
m

C
50 0m

IC
TW
V 0m

C
W

P
W

G
CV
10 10 m VT

3 2 1 4 5 4 5 6

O
00 PV E m

C
2500 1000
V
SH

C
20 12

P
00 m
m 4 m
23 50
75mm S m
50 SE

-
F

R
C
B

D
PVCWP
m

C
m S

I
4

R
C
W
75 V 3 3

O
C

C
D

D
3950
V

R
E LA

C
4 H F

D
H

-
D
2

-
L

D
W
VT
L

IC
SE

R
W

IC
D

G
V

C
P

G
m

I
R
C

P
m
m m
m
20
0m

O
m
m F

D
C
12
50

P
W
15

75mmPVCDS
V

C
2300

2000

P
m
0m

75mmPVCDS
5
SEPTIC TANK 10

P
U
LY

P
PVCSP TO

P
U
L S
W

IC

R
IN
E

G
A
AT
NEAREST SEWER
M
W m

O
T m
38
V

G
B
m

C
SYSTEM m
75 V
S
OM
M

D
RO
V

G
SS

P
m
150mmCPD 150mmCPD 150mmCPD CL
A m
75 V
S

D
CB CB CB

C
CB

P
D
P
C
m

P P
0m F

M
A
15

B
U

75mmPVCDS

C
7

100mm
5

75mmPVCDS
PVCSP

1
P

m
V

m
C
75mm 75mm

P
W

D
C
P
75mm PVCDS 75mm 100mm PVCSP 0m
m
EM
15
PVCDS PVCDS ST

D
P
SY
PVCDS

R
A
75mPVCDS

75mPVCDS

C
m E
50mm PVCVTR 0m

G
T
75mPVCDS
A
75mPVCDS

IN
B
m
15

V
C
A
m S M

R
5
m
0
V
C
V
P
T
W
m
RISER 75 V

D
C
OO

P
D

IN
WC

C
SR

V
A

50mPVCTR

2
M

P
m
S

O
m 0m
A
T
12mm GICWL m S 15
SHE CL

P
75 V

12mm GICWL

D
HE

C
P
m
m
D-4 50mm PVCVTR

D
D-4

P
C
100mm PVCWP D-3 m
RISER 0m F

D
0
5
15

B
C
FD

75mmPVCDS
D-3

75mmPVCDS
3
CS CO
ROOF LINE

50mm PVCVTW
CO

D
P
100mm PVCSP S

C
m
WC

D
V 0m

C
15

P
D-2 m M
HCR 12mm GICWL m
RO
O
75
SS

50mPVCTW
m
FD A m S

B
CL

C
75 V

D
150mm CDP

CLASSROOM CLASSROOM CLASSROOM

C
LAV 50mm PVCVTW

P
RISER
CO

B
20mm GICWL

C
E
N
LI

75mmPVCDS
F
O
O

R
15
0m

D
P
m

C
m
0m
15

C
D
P
S

D
V

C
P
m
m
75

B
B

B
UP

C
EM
ST
SY
E

G
A

IN
A

R
D
P
D

IN
C
A
M m

O
0m T
15

C FD FD FD
75mPVCDS

75mPVCDS

75mPVCDS
75mm 75mm 75mm
75mPVCDS

75mm PVCDS
PVCDS PVCDS PVCDS
RAMP

WATER SUPPLY
150mm CDP

GICWL
UP

TO MAIN
150mmCPD 150mmCPD 150mmCPD

38mm
CB CB CB CB

GV
1 PUMBING RO-IN LAYOUT 3 I S O M E T R I C V I E W

M
GV
P-1 P-1
TO MAIN DRAINAGE SYSTEM

TO MAIN DRAINAGE SYSTEM

SCALE : 1:100m SCALE : N T S


150mm CDP

150mm CDP

CONSULTANT / DESIGNER REVIEWED BY: RECOMMENDING APPROVAL : APPROVED FOR ACCREDITATION : CONCURRED : PROJECT TITLE : PROJECT NO: OWNER : SHEET NO:

REPUBLIC OF THE PHILIPPINES DESIGNED BY:


IC
o
f t he PH
IL
I
F
E A

TWO STOREY DEPARTMENT OF EDUCATION


DEPARTMENT OF EDUCATION (DepED)
T
M
L

P
B

TA
PU

I TO R I NG
IN

SK
RE

ES

DepED P-1
EMMANUEL P. CUNTAPAY SOFIA T. SANTIAGO GILBERTO S. REYES RAMON C. BACANI SIX CLASSROOM
F O RC E

ELIAS MELQUIADES EMEL B. CUBA II


ON

ENCODED BY: Max C.


D

TASK FORCE ENGINEERING, ASSESSMENT AND MONITORING


M
PE

NO

EN

MCMXCIX
&

IN
G
I

T
A

E N

G.I. ROOF SCHOOL BUILDING


E
R

ER
T

IN SM
A

A S SE S
T C
M
E U G ,
DE
TN

OIC, DIRECTOR III OIC, DIRECTOR IV


F O

SANITARY ENGINEER CHIEF, ARCHITECTURAL DIVISION UNDERSECRETARY


MERALCO AVENUE, PASIG CITY
2
SHEET CONTENTS :
BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH DEPATMENT OF EDUCATION (DepED) CHECKED BY:
PRC NO. : TIN : PLUMBING RO-IN LAYOUT, ROOF DRAIN LAOUT,
ISOMETRIC VIEW
PTR NO. : DATE : LOCATION : DATE : 08/06/2004

NOTE:
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF TASK FORCE ENGINEERING, ASSESSMENT AND
MONITORING AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


LEGEND:

CB CATCH BASIN

CDP CONCRETE DRAIN PIPE

CO CLEAN OUT

CV CHECK VALVE

HB HOSE BIBB

FD FLOOR DRAIN

GICWL GALVANIZED IRON COLD WATER LINE (SCH. 40)

4650 GICWR GALVANIZED IRON COLD WATER RISER (SCH. 40)


100mm THK. + FIN. SLAB W/ 150X300mm RC BEAM W/2-16mm
10mm REBARS AT 200mm O.C. GV GATE VALVE
TOP AND BOT. REBARS & 10mm STIRRUPS
BENT UP 2 OUT OF 3 AT L/4 1@50,3@100, REST @300mm O.C.
FROM FACE SUPPORT. BOTH WAYS 100mm THK. + FIN. SLAB W/
10mm BENT UP 2 OUT OF 3 AT MH MANHOLE
L/4 FROM FACE SUPPORT BW
600
PVCDS POLYVINYL CHLORIDE DOWNSPOUT
AIR SPACE
NGL

100
100

NGL
MH PVCDP POLYVINYL CHLORIDE DRAIN PIPE
VAR

MANHOLE AIR SPACE


MANHOLE
AIR SPACE
INLET
PVCDS POLYVINYL CHLORIDE DOWNSPOUT
100

INLET

100
PVCSP POLYVINYL CHLORIDE SOIL PIPE
350

300
WATER LEVEL 700

25
WATER
LEVEL PLASTERED W/WATERPROOFING
COMPOUND OR APPLY ONE FACE PVCVAC POLYVINYL CHLORIDE VENT. ACROSS CEILING
150 700 150
PLASTERED W/ WATERPROOFING BITUMEN TAR 150 400 150
WALLS REINFORCEMENT COMPOUND OR APPLY ONE
LEACHING 10mm VERT. & HOR. BAR FACE BITUMEN TAR
PVCVP POLYVINYL CHLORIDE VENT. PIPE
2125

CHAMBER @200mm OC BW

DIGESTIVE CHAMBER
DIGESTIVE (W. LEVEL)

PVCVS POLYVINYL CHLORIDE VENT STACK


GRAVEL BED
10mm REINF. VERT & HOR.

150
DRAINAGE PIPE
@200mm O.C BWAYS
100mm THK. SLAB W/
1600

10mm REBARS @ PVCVTR/W POLYVINYL CHLORIDE VENT TROUGH ROOF/WALL


300mm BOTH WAYS 2SLOPE
125

PVCWP POLYVINYL CHLORIDE WASTE PIPE

700

400
INLET OUTLET
150 2500 150
PVCWS POLYVINYL CHLORIDE WASTE STACK
150 1000 150 3200 150
2800

RD ROOF DRAIN

150
100mm THK. + FIM. SLAB W/
10mm REBARS @300mm O.C. BW
2 SECTION DETAIL UD URINAL DRAIN

P-3 SCALE : 1:50 Mts.


3 5a
SECTION DETAIL DETAIL PLAN WC WATER CLOSET

P-3 SCALE : 1:50 Mts.


P-3 SCALE : 1:20 M LAV LAVATORY

2-10mm EXTRA
S-1a 100mm THK. + FIN. SLAB W/ CS COUNTER SINK
BARS TOP/BOT. ON 10mm REBARS @ 300mm O.C.

TWO PARALLEL SIDE BENT UP 2 OUT OF 3 AT L/4 150MM THK. CHB W/ 10mm
FROM FACE OF SUPPORT B.W. REBARS HOR. EVERY 2-LAYERS
700
VERT. @600mm O.C.
4650
1000 3200
150 150 150 150 400 150 PLUMBING NOTES:

200 600 200 1100 150 700 150 1100 75 75mm 1. GRADES OF HORIZONTAL PIPINGS
PVCDS
RUN ALL HORIZONTAL PIPINGS IN PERPECT ALIGNMENT AND AT A FORM GRADE NOT LESS THAN TWO PERCENT (2
150

100
2. CHANGE IN DIRECTION
CDP
ALL CHANGE IN DIRECTION SHALL BE MADE BY APPROPRIATE USE OF FORTY-FIVE DEGREES (45) WYES, LONG SWEEP
900

OUTLET QUARTER BEND, SIXTH-EIIGHT OR SIXTEENTH BEND. WHEN THE CHANGE OF FLOW IS FROM HORIZONTAL TO VERTICAL A
50
2SLOPE SINGLE 1/8 BEND COMBINATION MAYBE USED ON VERTICAL STACKS AND SHORT QUARTER BENDS MAYBE USED ON WASTE
INLET
CDP LINE, TEE AND CROSSES MAYBE USED IN BENT PIPES.

(VARIABLE)
50 600 50

600 min.
2SLOPE
50
2800
2500

3. PROHIBITED FITTINGS
MH MH OUTLET
NO DOUBLE HUB OR TEE BRANCH SHALL BE USED ON HORIZONTAL SOIL AND WASTE LINES, THE DRILLINGS AND TAPPING

100
10mm BAR
OF HOUSE DRAIN, WASTE OR VENT PIPES AND USED OF SADDLE HUB AND BEND ARE PROHIBITED.
HANDLE 3-10mm (E.W.)
50 (TYP.)

100
P-3
1.
4. PIPE CLEAN-OUTS
2 600
900

CLEAN-OUTS ARE REQUIRED UNDER THE F0LLOWING CONDITIONS:


250 100 250
a) EVERY CHANGE OF HORIZONTAL DIRECTION EXCEEDING TWENTY TWOAND ONE-HALF DEGREES (22 1/2).
5b DETAIL SECTION b) ONE AND ONE-HALF METERS (1.50m.) INSIDE THE PROPERTY LINES BEFORE THE HOUSE DRAINAGE CONNECTION.
150

c) EVERY FIFTEEN METERS (15.00m) IN HORIZONTAL RUN OF PIPES.


d) AT THE END OF ANY HORIZONTAL PIPE LINES.
S2 100mm THK. + FIN. SLAB W/
P-3 SCALE : 1:20 M
100

10mm REBARS @ 300mm O.C.

BENT UP 2/3 OUT AT L/4 FACE


SUPPORT AND SHORT SPAN AND 5. THE DIGESTION CHAMBER OF SEPTIC VAULT MUST BE WATERPROOFED.
INLET INLET
10mm TEMP BARS @300mm E.W. 50 50
6. NOT LESS THAN 0.30 METER OF AIR SPACE MUST BE LEFT BETWEEN THE TOP OF THE SEWAGE AND THE UNDER PART OF
50 50
3 5 CATCH BASIN DETAIL SECTION
VAULT ROOF SLAB.

P-3 7. NO SEPTIC VAULT SHALL BE CONSTRUCTED UNDER THE BUILDING.


P-3 SCALE : 1:20 MTS.

8. ALL PLUMBING WORKS SHALL BE UNDER THE SUPRVISION OF A LICENSED MASTER PLUMBER AND A LICENCED PLUMBING
1 SEPTIC TANK DETAIL 4 MANHOLE DET. SECTION CONTRACTOR.

P-3 SCALE : 1:50 Mts.


P-3 SCALE : 1:10 Mts.

DESIGN CRITERIA

i. LIVE LOAD_________________ 1000Pa


ii ALLOWABLE STRESSES
1. CONCRETE

a. FOR FOOTING, BEAMS AND SLABS


fc'' = 20 MPa
2. CONCRETE MASONRY UNITS (LOAD BEARING CHB)
fm' =6.90 MPa, fm = 2.41 MPa
3. REINFORCING STEEL BARS
FOR BARS SMALLER THAN 16mm

fy = 230 MPa
4. ASSUMED ALLOWABLE BEARING CAPACITY Y = 100KPa

NOTE:
WATER TABLE IS 1500 BELOW GROUND LEVEL.

CONSULTANT / DESIGNER REVIEWED BY: RECOMMENDING APPROVAL : APPROVED FOR ACCREDITATION : CONCURRED : PROJECT TITLE : PROJECT NO: OWNER : SHEET NO:

REPUBLIC OF THE PHILIPPINES DESIGNED BY:


IC
o
f t he PH
IL
I
F
E A

TWO STOREY DEPARTMENT OF EDUCATION


DEPARTMENT OF EDUCATION (DepED)
T
M
L

P
B

TA
PU

I TO R I NG
IN

SK
RE

ES

DepED P-2
EMMANUEL P. CUNTAPAY SOFIA T. SANTIAGO GILBERTO S. REYES RAMON C. BACANI SIX CLASSROOM
F O RC E

ELIAS MELQUIADES EMEL B. CUBA II


ON

ENCODED BY: Max C.


D

TASK FORCE ENGINEERING, ASSESSMENT AND MONITORING


M
PE

NO

EN

MCMXCIX
&

IN
G
I

T
A

E N

G.I. ROOF SCHOOL BUILDING


E
R

ER
T

IN SM
A

A S SE S
T C
M
E U G ,
DE
TN

OIC, DIRECTOR III OIC, DIRECTOR IV


F O

SANITARY ENGINEER CHIEF, ARCHITECTURAL DIVISION UNDERSECRETARY


MERALCO AVENUE, PASIG CITY
2
SHEET CONTENTS :
BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH BUREAU OF DESIGN, DPWH DEPATMENT OF EDUCATION (DepED) CHECKED BY:
PRC NO. : TIN : SEPTIC TANK, CATCH BASIN DETAIL, LEGEND, NOTES
& DESIGN CRITERIA
PTR NO. : DATE : LOCATION : DATE : 08/06/2004

NOTE:
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF TASK FORCE ENGINEERING, ASSESSMENT AND
MONITORING AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.

REP. ACT 545


REPUBLIC OF THE PHILIPPINES

TABLE OFFICE OF THE CITY/MUNICIPAL


ENGINEER/BUILDING OFFICIAL

OF
CONTENTS
DISTRICT/CITY/MUNICIPALITY

ARCHITECTURAL LAND USE & ZONING

A-1 PERSPECTIVE VIEW & TABLE OF CONTENTS

A-2 GROUND FLOOR PLAN SECOND FLOOR PLAN

A-3 REFLECTED CEILING PLAN CROSS SECTION


RIGHT SIDE ELEVATION