Illumination of Type A control building

ILLUMINATION DESIGN CALCULATION FOR


TYPE A CONTROL BUILDING

Project : Expansion of Distribution Networks in the Eastern Region of Nepal


Contract no : ICB - PMD - DSAEP - 071/72-04 (Lot 1)
1. Input Data: (For 33kV Control Room )

Required level of Luminiosity, lux Rlus 300


Work Plane Height, m Hw 0.8
Heigh of the fitting above work plane, m Hc 2.3
Reflection factor for white color ceiling, % Rf 70
Reflection factor for white color wall, % Rw 70
Length of the room, m RL 10.3
Width of the room, m RW 5.4
Height of the room, m RH 3.75
Area of the room, Sq m RA RL RW = 55.62

Room index RL RW
RI = 1.54
RL + RW Hc
From the table,
Utilization factor corresponding to the rood index: Uf 0.51
Maintenace Factor Mf 0.7
2. Light Fixture Sample:

Selecting Flourescent / LED light 4 ft long


Wattage of each lamp, watt W 44
Lumen per watt of each lamp, lm/watt eff 102.27
Number of lamps per fixtures NF 2
Lumen of each fixtures, lm L eff W NF = 9 10 3

3. Calculations:
Rlus RA
N = 5.193
Number of Fixture L Uf Mf
N6
Selecting number of Fixture
N L Uf Mf
Actual value of Illumination, lux Eav = 346.593
RA

Design Calculation by:

----------------------
Er. Santosh Gairhe
Senior Electrical Engineer
Tripureswar Conductor - Jaya Durge Engineering J/V