Sie sind auf Seite 1von 2
JECRNICAL SPEUIFIVALIIN THREE — PHASE OIL-IMMERSED DISTRIBUTION TRANSFORMER Type CTMP 18 HC 2000 Standard IEC 60076 Rated Power, kVA 2000 Voltage ratio, V at no-load 1380022X2.5%/400 Frequency, Hz 60 Cooling method ONAN Gonnection Dynt1 Insulation level, kV LI95 AC 38/LI_AC 3 Design ambient temperature, deg. C 50°C Temperature rise oillwindings, deg. C 50/55°C Impedance voltage, % 6.0% Winding material, HV/LV Copper/Copper *) Guaranteed with tolerance according fo IEC 60076 standards Hermetically sealed type with corrugated tank and off-circuit tap changer, lifting lugs, pulling eyes, oil drain device with sampling facility, earthing terminals, rating and diagram plates Surface treatment: painted RAL7033, cement grey HV & LV cable boxes with undrilled gland plates excluding cable glands HV porcelain bushings - LV porcelain bushings - Pressure relief device ~ Oil temperature indicator with contacts; alarm & trip = Oillevel indicator without contact - Plain rollers, 90 deg. turnable ~ “HV & LV Bushings on the top cover Notes: = Transformers will be suitable for indoor (or) outdoor installation with degree of protection {P55 for tank and IPS4 for cable boxes. ~ Transformer will be hermetically sealed type with corrugated cooling fins fully filled with mineral oil (no gas/nitrogen cushion) as per manufacturer standard - The temperature class of the insulation shall be Class ‘A’ (105°C), in acoordance with IEC 60085 for oil filled transformers. - Transformer will be suitable for an altitude level of up to 1000m ASL = Accessories will be as mentioned above only and as per manufacturer standard - HV & LV cable boxes as per manufacturer standard on the top cover will be provided, which would be suitable for bottom cable entry. _ Transformer shall be as per IEC 60076 standards only. Any ANSI/IEEE standards and other specification will not be followed - Uninhibited mineral oil as per IEC 60296 will be provided. ~ Surface treatment and painting will be as per manufacturer standard ~ Only routine test will be conducted as per IEC 60076 at our factory. TECHNICAL SPECIFICATION THREE — PHASE OIL-IMMERSED DISTRIBUTION TRANSFORMER Type KTMP 18 HC 3000 Standard IEC 60076 Rated Power, KVA 3000 Voltage ratio, V at no-load 1450082X2.5%/380 Frequency, Hz 60 Cooling method ONAN Connection YNd 14 Insulation level, kV LI95 AC 38/LI__ AC 3 Design ambient temperature, deg. C 50°C Temperature rise oiltwindings, deg. C 50/55 Impedance voltage, % 70 Winding material, HV/LV CopperiCopper *) Guaranteed with tolerance according to IEC 60076 standards Hermetically sealed type with corrugated tank and off-circuit tap changer, lifting lugs, pulling eyes, oil drain device with sampling facility, earthing terminals, rating and diagram plates Surface treatment: Painted RAL7033, cement grey - HV &LV cable boxes with undrilled gland plate excluding cable glands - HV porcelain bushings = LV porcelain bushings - Pressure relief device ~ Oil temperature indicator with contacts, alarm & trip il level indicator without contact Plain rollers, 90 deg. turnable HV & LV bushings on the top cover Notes: - Transformers will be suitable for indoor (or) outdoor installation with degree of protection IP56 for tank and IP54 for cable boxes. Transformer will be hermetically sealed type with corrugated cooling fins fully filled with mineral oil (no gasinitrogen cushion) as per manufacturer standard The temperature class of the insulation shall be Class ‘A’ (105°C), in accordance with IEC 60085 for oil filled transformers. - Transformer will be suitable for an altitude level of up to 1000m ASL - Accessories will be as mentioned above and as per manufacturer standard - No-load voltage ratio 14500 V/380 V - Vector group will be YNd 11. HV side- Star, LV side- Delta Transformer shall be as per IEC 60076 standards only. Any ANSINEEE standards and other specification will not be followed - Uninhibited mineral oil as per IEC 60296 will be provided. - Surface treatment and painting will be as per manufacturer standard - Only routine test will be conducted as per IEC 60076 at our factory.

Das könnte Ihnen auch gefallen