.5 1 5 10 50 100 500 1K 5K 10K
1K 1K
TR2 CB-LDS-SE1 R0-LDS - P LUZ DEL SUR
310.58 MVAsc
Ampacity
R0-LDS
I>
CB-LDS-SE1
FLA
CB0 1-3/C 70
Merlin Gerin
R1- THYT NA10 (LL-SE1)
500 500
I>
Definite Time
I>
Thytronic
IEC/BS B
Time Delay = 0.1 s
100 Pickup = 0.8 (0.1 - 5 xCT Sec) 100 CB-SE1-SE2_3
1-3/C 50
R3 - S20 (RL-SAL-SE2)
R
CB-3
CT Ratio 200:5
OC2 OC1 TR2
1000 kVA
Seconds
Seconds
Sensor = 4000
LT Pickup = 0.4 (1600 Amps) CB-LDS-SE1 - P
LT Band = 0.5 CB-SE1-SE2_2 - P
ST Pickup = 4 (6400 Amps) CB-SE1-SE2_3 - P
ST Band = 0 (I^x)t = OUT TR2 CB-SE1-SE2_1 - P
R0-LDS - 3P
1 CB-SE2-TR2 - P 11.258kA @ 22.9kV
1
(Asym)
.5 R3 - S20 (RL-SAL-SE2) - P .5
R1- THYT NA10 (LL-SE1) - 3P
Square D
10.977kA @ 22.9kV
Sepam Series 20 (Asym)
CT Ratio 50:5
OC1
IEC - Very Inverse (TMS)
Pickup = 0.7 (0.1 - 2.4 xCT Sec)
Time Dial = 0.38
.1 3x = 2.57 s, 5x = 1.28 s, 8x = 0.733 s .1
TR2
Inst = 5 (0.1 - 24 xCT Sec)
Time Delay = 0.13 s Inrush
.05 OC2 .05
Inst = 7.6 (0.1 - 24 xCT Sec)
Time Delay = 0.05 s R2- THYT NA10 (SAL-SE1) - 3P
10.977kA @ 22.9kV
(Asym)
Amps X 10 SE 1 (LL-SAL) (Nom. kV=22.9, Plot Ref. kV=22.9) ETAP Star 12.6.0H