WI/OPR - E001

METHOD FOR INSULATION RESISTANCE TEST Rev. 0

Date / /

Flow Descriptive Procedures Supplementary Information


Process Constraint Corrective Measures Point 1 : At Start, all participants for Insulation Instrument :Insulation
Resistance Test are present.
Resistance Tester
(1)
Start
Point 2 : Test instrument, reference drawings and Maker :Hioki
Test Forms should be available.
Type :Digital M
(2) Point 3 : Verify that the other end of cables is safe Model :Hioki 3453
Tester ,Dwg. for persons not to touch.
and Forms
Serial No. :20505858
Isolate all connected electronic
equipment,capacitors,power controllers,
(3) ( DRemove
) dimmer switches , pilot lamps and
Verification and the damaged electronic ballast.
Isolation then replace with new

Yes Damaged
Point 4 : Check battery and select 500 V range. Insulation Resistance Test Form
( 4 ) Check Tester then No damaged Cable & ( FM / OPR-E001)
(C) wire
set the range
condition
Point 5 : Connect the test probe ( red & black ) to
test object .
( 5 ) Measure Ins. Res. of Measure Insulation Resistance within
( B ) Check condition 60 seconds minimum to achieve ideal
Wires or Cables within of wires and cables
60sec. result

Point 6 : Check the reading : If < 0.5 M not


Test If Result < 0.5 M ( A ) Trace the caused passed ;If > 0.5M passed.
(6)
Result Result Not Passed of failure
Point 7 : Record the test result to Test Form ( FM /
Result > 0.5 M Result Passed OPR-E001 ) and keep as final after signed
by respective attending parties.

( 7 ) Read and Record


the Test Result to Test Point 8 : Discharge the residual voltage that is
Form accumulated during the test to avoid
electric shock.

(7)
Discharge residual
voltage Point A : Trace the caused of cable or wire failure.
accumulated during test
Point B After the caused of failur has been
determined, check the conditions of
& C: cables or wires if damaged or not
damaged.
(8)
Finished
After the caused of failur has been
determined, check the conditions of
cables or wires if damaged or not
damaged.
(8)
Finished

Point D : If the cables or wires are damaged,


remove immediately then replace with
new one.