TABLE OF CONTENTS
MECHANICAL PLUMBING
This is and shall remain in the property of
Monian Ltd., for which it was commissioned.
M-01 LEGENDS, GENERAL NOTES & SCHEDULES E-13 ELECTRICAL-AUXILIARY-DATA LAYOUT P-00 PLUMBING - LEGENDS Unauthorised use of the document in any way is
prohibited. Dimensions shall rule over scale in
M-02 MECHANICAL - AIR-CONDITIONING LAYOUT HOTEL & GAMING BUILDING - GROUND FLOOR P-01 PLUMBING - WATERLINE LAYOUT - case of conflict.

HOTEL AND GAMING BUILDING - GROUND FLOOR E-14 ELECTRICAL-AUXILIARY-DATA LAYOUT HOTEL & GAMING BUILDING - Dimensions must be verified at the site before
commencing any work or making any shop
M-03 MECHANICAL - AIR-CONDITIONING LAYOUT HOTEL & GAMING BUILDING - LEVEL 1 GROUND FLOOR drawings. IF IN DOUBT, CONFIRM WITH
ARCHITECT.
HOTEL AND GAMING BUILDING - LEVEL 1 E-15 ELECTRICAL-AUXILIARY-DATA LAYOUT P-02 PLUMBING - WATERLINE LAYOUT -
M-04 MECHANICAL - AIR-CONDITIONING LAYOUT HOTEL & GAMING BUILDING - LEVEL 2 HOTEL & GAMING BUILDING - LEVEL 1
REV. DESCRIPTION DATE
HOTEL AND GAMING BUILDING - LEVEL 2 E-16 ELECTRICAL-AUXILIARY-DATA LAYOUT P-03 PLUMBING - WATERLINE LAYOUT -
M-05 MECHANICAL - AIR-CONDITIONING LAYOUT HOTEL & GAMING BUILDING - LEVEL 3 HOTEL & GAMING BUILDING - LEVEL 2
HOTEL AND GAMING BUILDING - LEVEL 3 E-17 ELECTRICAL-AUXILIARY-DATA LAYOUT P-04 PLUMBING - WATERLINE LAYOUT -
M-06 MECHANICAL - AIR-CONDITIONING LAYOUT HOTEL & GAMING BUILDING - LEVEL 4 HOTEL & GAMING BUILDING - LEVEL 3
HOTEL AND GAMING BUILDING - LEVEL 4 E-18 ELECTRICAL-AUXILIARY-CABLE TRAY LAYOUT P-05 PLUMBING - WATERLINE LAYOUT -
M-07 MECHANICAL - AIR-CONDITIONING LAYOUT HOTEL & GAMING BUILDING - GROUND FLOOR HOTEL & GAMING BUILDING - LEVEL 4
HOTEL AND GAMING BUILDING - ROOF E-19 ELECTRICAL-AUXILIARY-CABLE TRAY LAYOUT P-06 PLUMBING - WATERLINE LAYOUT -
M-08 MECHANICAL - HOTEL AND GAMING BUILDING - HOTEL & GAMING BUILDING - LEVEL 1 HOTEL & GAMING BUILDING - ROOF
INDOOR FAN COIL UNIT SCHEDULE E-20 ELECTRICAL-AUXILIARY-CABLE TRAY LAYOUT P-07 PLUMBING - SANITARY LAYOUT
M-09 MECHANICAL - HOTEL AND GAMING BUILDING - HOTEL & GAMING BUILDING - LEVEL 2 HOTEL & GAMING BUILDING -
INDOOR FAN COIL UNIT SCHEDULE E-21 ELECTRICAL-AUXILIARY-CABLE TRAY LAYOUT GROUND FLOOR
M-10 MECHANICAL - HOTEL AND GAMING BUILDING - HOTEL & GAMING BUILDING - LEVEL 3 P-08 PLUMBING - SANITARY LAYOUT
INDOOR FAN COIL UNIT SCHEDULE & ERV SCHEDULE E-22 ELECTRICAL-AUXILIARY-CABLE TRAY LAYOUT HOTEL & GAMING BUILDING - LEVEL 1
M-11 MECHANICAL - HOTEL AND GAMING BUILDING - HOTEL & GAMING BUILDING - LEVEL 4 P-09 PLUMBING - SANITARY LAYOUT
CONDENSER SCHEDULE E-23 ELECTRICAL-AUXILIARY-EMERGENCY LIGHT LAYOUT HOTEL & GAMING BUILDING - LEVEL 2
M-12 MECHANICAL - HOTEL AND GAMING BUILDING - HOTEL & GAMING BUILDING - GROUND FLOOR P-10 PLUMBING - SANITARY LAYOUT
FAN SCHEDULE E-24 ELECTRICAL-AUXILIARY-EMERGENCY LIGHT LAYOUT HOTEL & GAMING BUILDING - LEVEL 3
M-13 MECHANICAL - HOTEL AND GAMING BUILDING - HOTEL & GAMING BUILDING - LEVEL 1 P-11 PLUMBING - SANITARY LAYOUT
TYPICAL DETAILS E-25 ELECTRICAL-AUXILIARY-EMERGENCY LIGHT LAYOUT HOTEL & GAMING BUILDING - LEVEL 4
HOTEL & GAMING BUILDING - LEVEL 2 P-12 PLUMBING - SANITARY LAYOUT
ELECTRICAL E-26 ELECTRICAL-AUXILIARY-EMERGENCY LIGHT LAYOUT HOTEL & GAMING BUILDING - ROOF
E-00 ELECTRICAL - LEGENDS AND GENERAL NOTES HOTEL & GAMING BUILDING - LEVEL 3
E-01 ELECTRICAL - LIGHTING LAYOUT - E-27 ELECTRICAL-AUXILIARY-EMERGENCY LIGHT LAYOUT FIRE SERVICES
HOTEL & GAMING BUILDING - GROUND FLOOR HOTEL & GAMING BUILDING - LEVEL 4
E-02 ELECTRICAL - LIGHTING LAYOUT - E-28 ELECTRICAL-AUXILIARY-AUDIO SYSTEM LAYOUT F-00 FIRE SERVICES DESIGN - LEGENDS
HOTEL & GAMING BUILDING - LEVEL 1 HOTEL & GAMING BUILDING - GROUND FLOOR F-01 FIRE SERVICES DESIGN - CLIENT

E-03 ELECTRICAL - LIGHTING LAYOUT - E-29 ELECTRICAL-AUXILIARY-AUDIO SYSTEM LAYOUT HOTEL & GAMING BUILDING
HOTEL & GAMING BUILDING - LEVEL 2 HOTEL & GAMING BUILDING - LEVEL 1 MONIAN LIMITED
GROUND FLOOR
E-04 ELECTRICAL - LIGHTING LAYOUT - E-30 ELECTRICAL-AUXILIARY-AUDIO SYSTEM LAYOUT F-02 FIRE SERVICES DESIGN -
HOTEL & GAMING BUILDING - LEVEL 3 HOTEL & GAMING BUILDING - LEVEL 2 HOTEL & GAMING BUILDING PROJECT NAME:
E-05 ELECTRICAL - LIGHTING LAYOUT - E-31 ELECTRICAL-AUXILIARY-AUDIO SYSTEM LAYOUT LEVEL 1 ELEMENTS WAIGANI SOUTH
HOTEL & GAMING BUILDING - LEVEL 4 HOTEL & GAMING BUILDING - LEVEL 3 F-03 FIRE SERVICES DESIGN SECTION: S496 LOT: L16
E-06 ELECTRICAL - LIGHTING LAYOUT - E-32 ELECTRICAL-AUXILIARY-AUDIO SYSTEM LAYOUT HOTEL & GAMING BUILDING SUBURB/TOWN:

HOTEL & GAMING BUILDING - LEVEL 4 Hohola, Port Moresby


HOTEL & GAMING BUILDING - ROOF LEVEL 2
E-07 ELECTRICAL - POWER LAYOUT - E-33 ELECTRICAL-AUXILIARY-SECURITY DESIGN LAYOUT F-04 FIRE SERVICES DESIGN SUPERVISOR:

HOTEL & GAMING BUILDING - GROUND FLOOR HOTEL & GAMING BUILDING - GROUND FLOOR HOTEL & GAMING BUILDING RTD
E-08 ELECTRICAL - POWER LAYOUT - E-34 ELECTRICAL-AUXILIARY-SECURITY DESIGN LAYOUT LEVEL 3 ARCHITECT / DRAFTSMAN

HOTEL & GAMING BUILDING - LEVEL 1 HOTEL & GAMING BUILDING - LEVEL 1 FN / AP / BH / SL
F-05 FIRE SERVICES DESIGN
E-09 ELECTRICAL - POWER LAYOUT - E-35 ELECTRICAL-AUXILIARY-SECURITY DESIGN LAYOUT HOTEL & GAMING BUILDING
DRAWING TITLE:
HOTEL & GAMING BUILDING - LEVEL 2 HOTEL & GAMING BUILDING - LEVEL 2 LEVEL 4
E-10 ELECTRICAL - POWER LAYOUT - E-36 ELECTRICAL-AUXILIARY-SECURITY DESIGN LAYOUT HOTEL AND GAMING BUILDING
HOTEL & GAMING BUILDING - LEVEL 3 HOTEL & GAMING BUILDING - LEVEL 3 TABLE OF CONTENTS
E-11 ELECTRICAL - POWER LAYOUT - E-37 ELECTRICAL-AUXILIARY-SECURITY DESIGN LAYOUT
HOTEL & GAMING BUILDING - LEVEL 4 HOTEL & GAMING BUILDING - LEVEL 4
E-12A ELECTRICAL - POWER LAYOUT - E-38 ELECTRICAL-AUXILIARY-SECURITY DESIGN LAYOUT
HOTEL & GAMING BUILDING - ROOF HOTEL & GAMING BUILDING - SCHEMATICS
E-12B ELECTRICAL - SINGLE LINE DIAGRAM DESIGNED BY: DRAWING SCALE:
HOTEL AND GAMING BUILDING FN
E-12C SCHEMATICS CHECKED BY: FILE NAME:

HOTEL AND GAMING BUILDING RTD


APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani - S496L16 - AP - TOC - 180516.dwg 090715 A-0

H:\WEEKLY DRAWINGS\ELEMENTS WAIGANI SOUTH (S496L16 Hohola NCD)\DRAWINGS\ARCHITECTURAL V.03.1


This is and shall remain in the property of
Monian Ltd., for which it was commissioned.
Unauthorised use of the document in any way is
prohibited. Dimensions shall rule over scale in
case of conflict.

Dimensions must be verified at the site before


commencing any work or making any shop
drawings. IF IN DOUBT, CONFIRM WITH
ARCHITECT.

REV. DESCRIPTION DATE

A AS PER DMA ENGINEERS

RECOMMENDATION 050516

D AS PER DMA 7382-E-SK-MASTER [P2] 150416

CLIENT

MONIAN LIMITED

PROJECT NAME:

ELEMENTS WAIGANI
SECTION: S496 LOT: L16
SUBURB/TOWN:
Hohola, Port Moresby
SUPERVISOR:

RTD
NOTES : (Lift Requirements) ARCHITECT / DRAFTSMAN
FN/AP/BH/SL
-LIFT FDP, CONFIRM LOCATION WITH LIFT
CONTRACTOR.
PROVIDE 4 PAIRS COMMS CABLE (FIRE RATED DRAWING TITLE:
WS51W) FROM MDF.
HOTEL & GAMING BLDG.
-PROVIDE UNINTERRUPTED TEMPORARY POWER
PRIOR TO THE COMMENCEMENT AND DURING THE
GENERAL NOTES
ENTIRE INSTALLATION OF THE ELEVATOR.
LEGENDS
-CONFIRM POWER REQUIREMENTS AND
LOCATIONS WITH LIFT CONTRACTORS. GRILLE SCHEDULE
-PERMANENT POWER WITH AN ADDITIONAL TAIL SCHEDULE OF FLEXIBLE DUCTS
OF 5M FROM THE POINT OF CONNECTION
REQUIRED FOR LIFT. CONFIRM REQUIREMENTS
AND LOCATION WITH LIFT CONTRACTOR. CABLE DESIGNED BY: DRAWING SCALE:
TO BE 2 HR FIRE RATED MIN. 2S53W.
DMA 1:150
CHECKED BY: FILE NAME:
RTD
APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - AP - Mechanical .Acu Lay-out - Rev 30 - 250516.dwg 090715 M-01

V.03.2
18
DIA. 20 uPVC INSULATED
CONDENSATE PIPEWORK RISE 17 16 15 14 13 11
OFF UNIT AND RUN TO BOXING
TO DROP INTO TUNDISH.
BY HYDRAULIC; TYPICAL N O R T H This is and shall remain in the property of
Monian Ltd., for which it was commissioned.
Unauthorised use of the document in any way is
prohibited. Dimensions shall rule over scale in
TD TD TD
A case of conflict.

Dimensions must be verified at the site before


commencing any work or making any shop

800 x 450 WP LOUVRE AC-03 drawings. IF IN DOUBT, CONFIRM WITH


ARCHITECT.
02
REV. DESCRIPTION DATE

B A AS PER DMA ENGINEERS

RECOMMENDATION 050516
LGH-200 700x450 RISER TO ROOF AS PER DMA 7382-E-SK-02 [P2]
MOUNTED FAN. PROVIDE B AC-21-01 - ADDED 050216

HRV-2 DRAIN POINT AND ACCESS


AC-01 AC-01 AC-02 PANELS PER AS 4254.1

03 04 04

D AC-03
01
AC-02
LGH-150

1200 x 600 WP LOUVRE


03
AC-04
02

600 x 450 WP LOUVRE AC-02


02
AC-01
AC-02 AC-04
02
01 01 TD
G
AC-05
LGH-80
05
HEAT RECLAIM AC-01 HRV-4
VENTILATOR C/W AIR 01 AC-05 AC-05 CLIENT

FILTERS
04 03
TD
MONIAN LIMITED
500 x 400 WP LOUVRE

FILTER ELEVATION
PROJECT NAME:
LGH-80
ELEMENTS WAIGANI
500 x 400 WP LOUVRE
AC-05
SECTION: S496 LOT: L16
AC-05 SUBURB/TOWN:
01 Hohola, Port Moresby
02 TD TD
K AC-21 SUPERVISOR:

01 RTD
ARCHITECT / DRAFTSMAN
ROOF MOUNTED VERTICAL
FN/AP/BH/SL
DISCHARGE FAN LOCATE
6M FROM WINDOW AND
VENTILATION OPENINGS NOTES: DRAWING TITLE:
-ALL mechanical power locations and ratings are to be confirmed with the mechanical contractor prior
to install. HOTEL & GAMING BLDG.
M -Connect sign power to DB on matching Level.
-PE cell location to be confirmed by the electrical contractor and installed in a suitable location to ensure
GROUND FLOOR
proper operation. MECHANICAL
-Confirm location of all electrical connections for Hydraulic and mechanical equipment of site. Indicative
positions only shown. Power rating for hot water units, pumps, solar hot water and other hydraulic AIRCONDITIONING LAYOUT
equipment to be confirmed with hydraulics prior to install.

HOTEL AND GAMING BUILDING


DESIGNED BY: DRAWING SCALE:
1 GROUND FLR - AIR CONDITIONING LAYOUT DMA
CHECKED BY: FILE NAME:
1:150
SCALE 1: 150 METERS
M-02 RTD
APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - AP - Mechanical .Acu Lay-out - Rev 30 - 250516.dwg 090715 M-02

V.03.2
18 17 16 15 13 12
FIRE DAMPER TO RISER
PENETRATION WITH RISER ALSO INCLUDES HYDRAULIC
SERVICES PROVIDE COORDINATED DETAIL
ACCESS PANEL FOR
SHOWING EXHAUST DUCT. REFRIGERANT
N O R T H
INSPECTION TYPICAL ALL This is and shall remain in the property of
TOILET EXHUAUST RISERS PIPEWORK DRAINAGE DOWNPIPES, VENT Monian Ltd., for which it was commissioned.
PIPES, HOT & COLD WATER PIPEWORK, Unauthorised use of the document in any way is
prohibited. Dimensions shall rule over scale in
PRESSURE REDUCTION VALVES, TMV ETC.
case of conflict.
TYPICAL ALL RISERS

A Dimensions must be verified at the site before


commencing any work or making any shop
drawings. IF IN DOUBT, CONFIRM WITH
CU
ARCHITECT.
23

REV. DESCRIPTION DATE


CU A AS PER DMA ENGINEERS
B 22
RECOMMENDATION 050516

AC-12 CU
01 AC-12 AC-13 AC-13 AC-14 AC-14 AC-15 AC-15 24

02 01 02 01 02 01 02

AC-09
04
D

AC-11 AC-09 TOILET EXHAUST TO RUN TO AC-09


02 RISER ABOVE DAMPER REQ.
02 03

E'
AC-08
AC-11 02
01
AC-08
01

G
AC-06 REFRIGERANT PIPEWORK
04 RISE FROM
AC-09
TYPICAL
TD 01 CLIENT
AC-10 NOTES : (Lift Requirements)
02 MONIAN LIMITED
-LIFT FDP, CONFIRM LOCATION WITH LIFT
AC-06 CONTRACTOR.
AC-09 02
PROVIDE 4 PAIRS COMMS CABLE (FIRE RATED
WS51W) FROM MDF.
05 AC-08 AC-08 PROJECT NAME:
AC-10 03 04 -PROVIDE UNINTERRUPTED TEMPORARY POWER
PRIOR TO THE COMMENCEMENT AND DURING THE ELEMENTS WAIGANI
01 ENTIRE INSTALLATION OF THE ELEVATOR.
AC-07 AC-07 SECTION: S496 LOT: L16
AC-06 AC-06 -CONFIRM POWER REQUIREMENTS AND
SUBURB/TOWN:
01 02 Hohola, Port Moresby
01 03 LOCATIONS WITH LIFT CONTRACTORS.
SUPERVISOR:

K
TD
-PERMANENT POWER WITH AN ADDITIONAL TAIL
TD OF 5M FROM THE POINT OF CONNECTION RTD
WALL MOUNTED REQUIRED FOR LIFT. CONFIRM REQUIREMENTS
AND LOCATION WITH LIFT CONTRACTOR. CABLE ARCHITECT / DRAFTSMAN
AC UNITS TYPICAL
TO BE 2 HR FIRE RATED MIN. 2S53W. FN/AP/BH/SL

M DRAWING TITLE:

HOTEL & GAMING BLDG.


LEVEL 1
HOTEL AND GAMING BUILDING
NOTES : MECHANICAL
1 LEVEL 1 AIR CONDITIONING LAYOUT -All DB's within cupboards are to be smoke sealed. Cupboards to have smoke detector inside.
-600mm clearance is to be maintained from full extend of DB cupboard door swing or DB door swing.
AIRCONDITIONING LAYOUT
SCALE 1:150 METERS -All penetrations are to be sealed accordingly.
M-03 -All TV outlets and provisions are to be confirmed and locations coordinated on site.
- Any UPS installation that has a capacity exceeding 10 ampere hours or voltage higher than 24
volts is required to be 2 HR fire separated from the rest of the building. DESIGNED BY: DRAWING SCALE:
-Confirm outlets that are to UPS supplied. Typically all outlets servicing essential security and
data services are to be on UPS power. DMA 1:150
-All electrical penetrations on are to be confirmed and coordinated on site. CHECKED BY: FILE NAME:
-Confirm ACU locations with mechanical for all levels.
RTD
APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - AP - Mechanical .Acu Lay-out - Rev 30 - 250516.dwg 090715 M-03

V.03.2
18 17 16 15 14 13 This is and shall remain in the property of
Monian Ltd., for which it was commissioned.
Unauthorised use of the document in any way is
prohibited. Dimensions shall rule over scale in
N O R T H case of conflict.

Dimensions must be verified at the site before

A commencing any work or making any shop


drawings. IF IN DOUBT, CONFIRM WITH
ARCHITECT.

REV. DESCRIPTION DATE

A AS PER DMA ENGINEERS

B RECOMMENDATION 050516

AC-12 AC-12 AC-13 AC-13 AC-14 AC-14 AC-15 AC-15


03 04 03 04 03 04 03 04

AC-11
04 AC-09 AC-09 AC-09 REFRIGERANT PIPEWORK
09 07 08 RISE FROM
TYPICAL

AC-11
03

AC-17 AC-17 AC-16 AC-16


G AC-09 02 01 02 01
10
AC-09
AC-10 06 CLIENT

04
MONIAN LIMITED

AC-18 AC-18
PROJECT NAME:
02 01
AC-10 ELEMENTS WAIGANI
03 SECTION: S496 LOT: L16
SUBURB/TOWN:
Hohola, Port Moresby
SUPERVISOR:

K
TD
RTD
ARCHITECT / DRAFTSMAN
WALL MOUNTED FN/AP/BH/SL
AC UNITS TYPICAL

DRAWING TITLE:

HOTEL & GAMING BLDG.


LEVEL 2
HOTEL AND GAMING BUILDING NOTES :
-All DB's within cupboards are to be smoke sealed. Cupboards to have smoke detector inside. MECHANICAL
1 LEVEL 2 AIR CONDITIONING LAYOUT -600mm clearance is to be maintained from full extend of DB cupboard door swing or DB door swing.
-All penetrations are to be sealed accordingly.
-All TV outlets and provisions are to be confirmed and locations coordinated on site.
AIRCONDITIONING LAYOUT
SCALE 1:150 METERS
M-04 - Any UPS installation that has a capacity exceeding 10 ampere hours or voltage higher than 24
volts is required to be 2 HR fire separated from the rest of the building.
-Confirm outlets that are to UPS supplied. Typically all outlets servicing essential security and
data services are to be on UPS power. DESIGNED BY: DRAWING SCALE:
-All electrical penetrations on are to be confirmed and coordinated on site. DMA 1:150
-Confirm ACU locations with mechanical for all levels.
CHECKED BY: FILE NAME:
RTD
APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - AP - Mechanical .Acu Lay-out - Rev 30 - 250516.dwg 090715 M-04

V.03.2
18 17 16 15 14 13 This is and shall remain in the property of
Monian Ltd., for which it was commissioned.
Unauthorised use of the document in any way is
prohibited. Dimensions shall rule over scale in
case of conflict.
N O R T H
Dimensions must be verified at the site before
commencing any work or making any shop
drawings. IF IN DOUBT, CONFIRM WITH
A ARCHITECT.

REV. DESCRIPTION DATE

A AS PER DMA ENGINEERS

RECOMMENDATION 050516

B
AC-12 AC-13 AC-13 AC-14 AC-14 AC-15 AC-15
AC-12 06 05 06 05 06 05 06
05

AC-21
04
D
TD

AC-11
06 AC-21 AC-21
02 03

AC-11
05

G AC-21 AC-17 AC-17 AC-16 AC-16


05 AC-21 04 03 04 03 CLIENT
01
AC-10
06
MONIAN LIMITED

AC-18 AC-18 PROJECT NAME:

04 03 ELEMENTS WAIGANI
AC-10 SECTION: S496 LOT: L16
SUBURB/TOWN:
05 Hohola, Port Moresby
SUPERVISOR:

TD
RTD
K ARCHITECT / DRAFTSMAN

FN/AP/BH/SL
WALL MOUNTED
AC UNITS TYPICAL
RISER OFF UNITS AND RUN TO BOXING TO DRAWING TITLE:
DROP INTO TUNDISH,
BY HYDRAULICS, TYPICAL HOTEL & GAMING BLDG.
NOTES : LEVEL 3
HOTEL AND GAMING BUILDING -All DB's within cupboards are to be smoke sealed. Cupboards to have smoke detector inside.
-600mm clearance is to be maintained from full extend of DB cupboard door swing or DB door swing. MECHANICAL
1 LEVEL 3 AIR CONDITIONING LAYOUT -All penetrations are to be sealed accordingly.
-All TV outlets and provisions are to be confirmed and locations coordinated on site.
- Any UPS installation that has a capacity exceeding 10 ampere hours or voltage higher than 24
AIRCONDITIONING LAYOUT
SCALE 1:150 METERS
M-05 volts is required to be 2 HR fire separated from the rest of the building.
-Confirm outlets that are to UPS supplied. Typically all outlets servicing essential security and
data services are to be on UPS power.
DESIGNED BY: DRAWING SCALE:
-All electrical penetrations on are to be confirmed and coordinated on site.
-Confirm ACU locations with mechanical for all levels. DMA 1:150
CHECKED BY: FILE NAME:
RTD
APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - AP - Mechanical .Acu Lay-out - Rev 30 - 250516.dwg 090715 M-05

V.03.2
18 17 16 15 14 13
N O R T H
This is and shall remain in the property of
Monian Ltd., for which it was commissioned.
Unauthorised use of the document in any way is
prohibited. Dimensions shall rule over scale in
case of conflict.

Dimensions must be verified at the site before


commencing any work or making any shop

A drawings. IF IN DOUBT, CONFIRM WITH


ARCHITECT.

REV. DESCRIPTION DATE

A AS PER DMA ENGINEERS


TD
RECOMMENDATION 050516
B
AC-19 AC-19
AC-20 05 04
05

AC-20
01 AC-19
D TD
01
50

AC-20
E' 02

TD

G AC-19 AC-19 AC-19


02 06 03
50
CLIENT

MONIAN LIMITED

AC-20 AC-20 PROJECT NAME:

03 ELEMENTS WAIGANI
04
SECTION: S496 LOT: L16
SUBURB/TOWN:
Hohola, Port Moresby
SUPERVISOR:

RTD
K ARCHITECT / DRAFTSMAN

FN/AP/BH/SL

DRAWING TITLE:

NOTES : HOTEL & GAMING BLDG.


-All DB's within cupboards are to be smoke sealed. Cupboards to have smoke detector inside.
-600mm clearance is to be maintained from full extend of DB cupboard door swing or DB door swing.
LEVEL 4
HOTEL AND GAMING BUILDING -All penetrations are to be sealed accordingly.
MECHANICAL
1 LEVEL 4 AIR CONDITIONING LAYOUT -All TV outlets and provisions are to be confirmed and locations coordinated on site.
- Any UPS installation that has a capacity exceeding 10 ampere hours or voltage higher than 24
volts is required to be 2 HR fire separated from the rest of the building.
AIRCONDITIONING LAYOUT
SCALE 1:150 METERS -Confirm outlets that are to UPS supplied. Typically all outlets servicing essential security and
M-06 data services are to be on UPS power.
-All electrical penetrations on are to be confirmed and coordinated on site.
-Confirm ACU locations with mechanical for all levels. DESIGNED BY: DRAWING SCALE:

DMA 1:150
CHECKED BY: FILE NAME:
RTD
APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - AP - Mechanical .Acu Lay-out - Rev 30 - 250516.dwg 090715 M-06

V.03.2
18 17 16 15 14 13
N O R T H
This is and shall remain in the property of
Monian Ltd., for which it was commissioned.
Unauthorised use of the document in any way is
prohibited. Dimensions shall rule over scale in
case of conflict.

Dimensions must be verified at the site before


commencing any work or making any shop
drawings. IF IN DOUBT, CONFIRM WITH
A ARCHITECT.

REV. DESCRIPTION DATE

A AS PER DMA ENGINEERS

RECOMMENDATION 050516
B

CU CU CU CU CU CU CU CU CU CU
06 07 08 09 10 16 17 18 19 20

E'

G CU
01
CU
02
CU
03
CU
04
CU
05
CU
21
CU
11
CU
12
CU
13
CU
14
CU
15

CLIENT

MONIAN LIMITED

PROJECT NAME:

NOTES : ELEMENTS WAIGANI


-All DB's within cupboards are to be smoke sealed. Cupboards to have smoke detector inside. SECTION: S496 LOT: L16
-600mm clearance is to be maintained from full extend of DB cupboard door swing or DB door swing. SUBURB/TOWN:
-All penetrations are to be sealed accordingly. Hohola, Port Moresby
-All TV outlets and provisions are to be confirmed and locations coordinated on site.
- Any UPS installation that has a capacity exceeding 10 ampere hours or voltage higher than 24 SUPERVISOR:
volts is required to be 2 HR fire separated from the rest of the building.
-Confirm outlets that are to UPS supplied. Typically all outlets servicing essential security and RTD
K data services are to be on UPS power.
-All electrical penetrations on are to be confirmed and coordinated on site.
ARCHITECT / DRAFTSMAN

-Confirm ACU locations with mechanical for all levels. FN/AP/BH/SL

DRAWING TITLE:
NOTES : (Lift Requirements)
HOTEL & GAMING BLDG.
-LIFT FDP, CONFIRM LOCATION WITH LIFT
CONTRACTOR. ROOF
HOTEL AND GAMING BUILDING PROVIDE 4 PAIRS COMMS CABLE (FIRE RATED
WS51W) FROM MDF. MECHANICAL
1 ROOF AIR CONDITIONING LAYOUT -PROVIDE UNINTERRUPTED TEMPORARY POWER
PRIOR TO THE COMMENCEMENT AND DURING THE
AIRCONDITIONING LAYOUT
SCALE 1:150 METERS ENTIRE INSTALLATION OF THE ELEVATOR.
M-07
-CONFIRM POWER REQUIREMENTS AND
LOCATIONS WITH LIFT CONTRACTORS. DESIGNED BY: DRAWING SCALE:

-PERMANENT POWER WITH AN ADDITIONAL TAIL DMA 1:150


OF 5M FROM THE POINT OF CONNECTION CHECKED BY: FILE NAME:
REQUIRED FOR LIFT. CONFIRM REQUIREMENTS RTD
AND LOCATION WITH LIFT CONTRACTOR. CABLE
TO BE 2 HR FIRE RATED MIN. 2S53W. APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - AP - Mechanical .Acu Lay-out - Rev 30 - 250516.dwg 090715 M-07

V.03.2
This is and shall remain in the property of
Monian Ltd., for which it was commissioned.
Unauthorised use of the document in any way is
prohibited. Dimensions shall rule over scale in
case of conflict.

Dimensions must be verified at the site before


commencing any work or making any shop
drawings. IF IN DOUBT, CONFIRM WITH
ARCHITECT.

REV. DESCRIPTION DATE

A AS PER DMA ENGINEERS

RECOMMENDATION 050516

CLIENT

MONIAN LIMITED

PROJECT NAME:

ELEMENTS WAIGANI
SECTION: S496 LOT: L16
SUBURB/TOWN:
Hohola, Port Moresby
SUPERVISOR:

RTD
ARCHITECT / DRAFTSMAN

FN/AP/BH/SL

DRAWING TITLE:

HOTEL & GAMING BLDG.


MECHANICAL
INDOOR FAN COIL UNIT SCHEDULE

DESIGNED BY: DRAWING SCALE:

DMA AS SHOWN
CHECKED BY: FILE NAME:
RTD
APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - AP - Mechanical .Acu Lay-out - Rev 30 - 250516.dwg 090715 M-08

V.03.2
This is and shall remain in the property of
Monian Ltd., for which it was commissioned.
Unauthorised use of the document in any way is
prohibited. Dimensions shall rule over scale in
case of conflict.

Dimensions must be verified at the site before


commencing any work or making any shop
drawings. IF IN DOUBT, CONFIRM WITH
ARCHITECT.

REV. DESCRIPTION DATE

A AS PER DMA ENGINEERS

RECOMMENDATION 050516

CLIENT

MONIAN LIMITED

PROJECT NAME:

ELEMENTS WAIGANI
SECTION: S496 LOT: L16
SUBURB/TOWN:
Hohola, Port Moresby
SUPERVISOR:

RTD
ARCHITECT / DRAFTSMAN

FN/AP/BH/SL

DRAWING TITLE:

HOTEL & GAMING BLDG.


MECHANICAL
INDOOR FAN COIL UNIT SCHEDULE

DESIGNED BY: DRAWING SCALE:

DMA AS SHOWN
CHECKED BY: FILE NAME:
RTD
APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - AP - Mechanical .Acu Lay-out - Rev 30 - 250516.dwg 090715 M-09

V.03.2
This is and shall remain in the property of
Monian Ltd., for which it was commissioned.
Unauthorised use of the document in any way is
prohibited. Dimensions shall rule over scale in
case of conflict.

Dimensions must be verified at the site before


commencing any work or making any shop
drawings. IF IN DOUBT, CONFIRM WITH
ARCHITECT.

REV. DESCRIPTION DATE

A AS PER DMA ENGINEERS

RECOMMENDATION 050516

CLIENT

MONIAN LIMITED

PROJECT NAME:

ELEMENTS WAIGANI
SECTION: S496 LOT: L16
SUBURB/TOWN:
Hohola, Port Moresby
SUPERVISOR:

RTD
ARCHITECT / DRAFTSMAN

FN/AP/BH/SL

DRAWING TITLE:

HOTEL & GAMING BLDG.


MECHANICAL
INDOOR FAN COIL UNIT SCHEDULE

ERV SCHEDULE

DESIGNED BY: DRAWING SCALE:

DMA AS SHOWN
CHECKED BY: FILE NAME:
RTD
APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - AP - Mechanical .Acu Lay-out - Rev 30 - 250516.dwg 090715 M-10

V.03.2
This is and shall remain in the property of
Monian Ltd., for which it was commissioned.
Unauthorised use of the document in any way is
prohibited. Dimensions shall rule over scale in
case of conflict.

Dimensions must be verified at the site before


commencing any work or making any shop
drawings. IF IN DOUBT, CONFIRM WITH
ARCHITECT.

REV. DESCRIPTION DATE

A AS PER DMA ENGINEERS

RECOMMENDATION 050516

CLIENT

MONIAN LIMITED

PROJECT NAME:

ELEMENTS WAIGANI
SECTION: S496 LOT: L16
SUBURB/TOWN:
Hohola, Port Moresby
SUPERVISOR:

RTD
ARCHITECT / DRAFTSMAN

FN/AP/BH/SL

DRAWING TITLE:

HOTEL & GAMING BLDG.


MECHANICAL
CONDENSER SCHEDULE

DESIGNED BY: DRAWING SCALE:

DMA AS SHOWN
CHECKED BY: FILE NAME:
RTD
APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - AP - Mechanical .Acu Lay-out - Rev 30 - 250516.dwg 090715 M-11

V.03.2
This is and shall remain in the property of
Monian Ltd., for which it was commissioned.
Unauthorised use of the document in any way is
prohibited. Dimensions shall rule over scale in
case of conflict.

Dimensions must be verified at the site before


commencing any work or making any shop
drawings. IF IN DOUBT, CONFIRM WITH
ARCHITECT.

REV. DESCRIPTION DATE

A AS PER DMA ENGINEERS

RECOMMENDATION 050516

CLIENT

MONIAN LIMITED

PROJECT NAME:

ELEMENTS WAIGANI
SECTION: S496 LOT: L16
SUBURB/TOWN:
Hohola, Port Moresby
SUPERVISOR:

RTD
ARCHITECT / DRAFTSMAN

FN/AP/BH/SL

DRAWING TITLE:

HOTEL & GAMING BLDG.


MECHANICAL
FAN SCHEDULE

DESIGNED BY: DRAWING SCALE:

DMA AS SHOWN
CHECKED BY: FILE NAME:
RTD
APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - AP - Mechanical .Acu Lay-out - Rev 30 - 250516.dwg 090715 M-12

V.03.2
This is and shall remain in the property of
Monian Ltd., for which it was commissioned.
Unauthorised use of the document in any way is
prohibited. Dimensions shall rule over scale in
case of conflict.

Dimensions must be verified at the site before


commencing any work or making any shop
drawings. IF IN DOUBT, CONFIRM WITH
ARCHITECT.

REV. DESCRIPTION DATE

A AS PER DMA ENGINEERS

RECOMMENDATION 050516

CLIENT

MONIAN LIMITED

PROJECT NAME:

ELEMENTS WAIGANI
SECTION: S496 LOT: L16
SUBURB/TOWN:
Hohola, Port Moresby
SUPERVISOR:

RTD
ARCHITECT / DRAFTSMAN

FN/AP/BH/SL

DRAWING TITLE:

HOTEL & GAMING BLDG.


MECHANICAL
TYPICAL DETAILS

DESIGNED BY: DRAWING SCALE:

DMA AS SHOWN
CHECKED BY: FILE NAME:
RTD
APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - AP - Mechanical .Acu Lay-out - Rev 30 - 250516.dwg 090715 M-13

V.03.2
ELECTRICAL SYMBOLS

This is and shall remain in the property of


SINGLE GPO FULL BODY CAMERA Monian Ltd., for which it was commissioned.
Unauthorised use of the document in any way is
prohibited. Dimensions shall rule over scale in
DOUBLE GPO INTERNAL DOME CAMERA case of conflict.

Dimensions must be verified at the site before


ACU GPO - AIRCON UNIT VANDAL DOME EXT CAMERA commencing any work or making any shop
drawings. IF IN DOUBT, CONFIRM WITH
ARCHITECT.
WP SINGLE GPO WEATHERPROOF PTZ PTZ DOME CAMERA

REV. DESCRIPTION DATE


MON MONITOR
A AS PER DMA ENGINEERS DRAWINGS
3 PHASE SWITCHED SOCKET OUTLET WITH
CCTV CCTV HEAD END
NEUTRAL IP66. RATING AS SHOWN 7382-E-SK-01 [P1]

7382-E-SK-02 [P1]

7382-E-SK-02 [P2]

THREE PHASE & NEUTRAL PERMANENTLY 7382-E-SK-02 [PROPOSED DB LOCATIONS]


CONNECTED SPECIAL PURPOSE OUTLET
7382-E-SK-03 [P1]
WITH ISOLATOR (IP_) RATING AS REQUIRED MON MONITOR
(20AMP MINIMUM) 7382-E-SK-05 [P1]
SMS SECURITY MANAGMENT SYSTEM CLIENT
7382-E-SK-07 [P1]

SINGLE PHASE PERMANENTLY SAP SECURITY ALARM PANEL 7382-E-SK-08 [P1]

CONNECTED SPECIAL PURPOSE OUTLET 7382-E-SK-09 [P1]


WITH ISOLATOR (IP_) RATING AS REQUIRED DGP DATA GATHERING PANEL
7382-E-SK-MASTER [P1]
(20AMP MINIMUM)
1DC SINGLE DOOR CONTROLLER 7382-E-SK-ROOM [P1]

7382-E-SK-ROOM [P1]-A
4DC 4 DOOR CONTROLLER
SINGLE PHASE PERMANENTLY
CONNECTED SPECIAL PURPOSE OUTLET
WITH ISOLATOR IP66 (20AMP MINIMUM) RAS REMOTE ARMING STATION

PROX CARD READER

EM ELECTROMAGNETIC DOOR LOCK

ES ELECTRIC DOOR STRIKE

SINGLE RJ45 TELEPHONE OUTLET DIRECT REED SWITCH


CONNECTED TO MBF/IDF/FDP
PIR

CLIENT
RG11 360 DEGREE PIR

SINGLE RJ45 TELEPHONE/DATA OUTLET BG


BREAK GLASS MONIAN LIMITED

DOUBLE RJ45 TELEPHONE/DATA OUTLET SS SIREN / STROBE


EM WAP PROJECT NAME:
WIRELESS ACCESS POINT PS PIEZO SCREAMER
ELEMENTS WAIGANI
PTE
SECTION: S496 LOT: L16
PUSH TO EXIT DOOR BUTTON
SUBURB/TOWN:
Hohola, Port Moresby
DURESS BUTTON
D
SUPERVISOR:

S SMOKE DETECTOR RTD


ARCHITECT / DRAFTSMAN
RELAY RELAY
FN/AP/BH/SL

DMA NOTE: LED EMERGENCY I INTERCOM STATION


DRAWING TITLE:

LIGHT. CLASSIFICATION C0/C90 IM INTERCOM MASTER STATION


HOTEL & GAMING BLDG.
D32 (MINIMUM)
Job name: MONIAN ELEMENTS ELECTRICAL LEGENDS
Drawing/sketch title: E-SK-MASTER
Description: MASTER

DMADate:
NOTE:
24/05/16 ALL
41 EMERGENCY
Pages:
P2 & EXITRevision:
File name:
LIGHTING TO BE INSTALLED TO AS2293 Job name: ELEMENTS WAIGANI DESIGNED BY:

DMA
DRAWING SCALE:
1:150
Drawing/sketch title: 7382-E-SK-C1
REQUIREMENTS Description: EMERGENCY LIGHTING
CHECKED BY:
RTD
FILE NAME:

APPROVED BY:
ILS
Date: 02/06/16 Pages: 6 Revision: P1
FILENAME: File name:
DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - SL - Electrical .Lighting Layout - Rev 04 - 110516.dwg 090715 E-00

V.03.2
18 17 DB - GL - L3 16 15 14 Lights are to be coordinated with 13 12 11
generators so they are not
impeded upon or damaged by generators
SWITCH C3 DB - GL - L23 N O R T H
DB - GL - L22 SWITCH C2

A LT7 LT7
LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1
This is and shall remain in the property of
Monian Ltd., for which it was commissioned.
LT5 LT5
SWITCH C7 DB - GL - L24 Unauthorised use of the document in any way is
2 1 3 2 LT1 1 3 2 1 3 2 1
LT4 LT4 prohibited. Dimensions shall rule over scale in
SWITCH C8 DB - GL - L25 LT3 LT3
case of conflict.

SWITCH C8 DB - GL - L26 Dimensions must be verified at the site before


LT13 LT1 LT1 LT1 LT1 LT1 LT1 LT1 commencing any work or making any shop
3 LT1 LT1
3 1 3 1 3 2 drawings. IF IN DOUBT, CONFIRM WITH
B
LT5 LT5 2 2 2 LT3 LT3
1 LT7 ARCHITECT.
LT7

LT7 LT7
LT3 LT3
REV. DESCRIPTION DATE
LT5 LT5 LT5 LT5
LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1
1 3 2 1
LT5
3
LT5 2 2 1 3 2 1 3 2 1 3 A AS PER DMA 7382 - SKE - 006 211015

B AS PER DMA 7382-E-SK-01 [P1] 231215

LT5 LT5 LT5 LT5 LT1 LT1 LT1 LT1 LT1 LT1 C AS PER DMA 7382-E-SK-02 [P2] 050216
LT1 LT3 DB - GEN - L1
LT5 LT5 1 2 LT1 1 LT1 3 2 1 3 2
3 2 1 3 2 1 1
LT7 D AS PER DMA 7382-E-SK-03 [P1] 231215
LT7
LT1 LT1 LT1 LT1 LT1 LT1 LT1
DB - K - L1
LT3 E AS PER DMA 7382-E-SK-MASTER [P1] 240516

D
2 1 3 2 1 3 2

LT5 LT5 LT5 LT5


LT7
2 2 1 LT5 LT5 3 LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 F AS PER DMA 7382-E-SK-MASTER [P2] 150416
1 3 LT1
1 3 LT1 3

LT1
LT1 LT6 LT6 LT6 LT6 LT6 LT6 LT6 LT6 DB - GL - L1
LT5 LT5 LT5 LT5 LT1 LT5
3 LT5 LT5 LT5 LT5
LT5 LT5 2 LT13
1 3 2 1 3 2 2
LT1
LT1 LT4
1
LT8
LT7 C1 LT5 LT5
LT5 LT5 LT5 LT5 LT5 LT6 LT5 LT5 LT5
DB - GL - L21 SWITCH C1 LT1 P P
LT5 C2 LT1
3 2 1 3 2 1 1
LT2 2 LT8 LT8
C3 P
C4 DB - GL - L5 LT8
LT6 P
C5 3 LT5 LT5
LT1 3 LT5
1 LT1 LT5 LT5
C6 LT2 LT1
LT5 2 LT5 LT5 LT5 2 LT5 LT5 LT6
1 3 1 3 LT8
LT1 P
DB - GL - L4 C12 LT5 LT5 LT5
LT7 2 LT5 LT5
LT2 LT4
LT6 3 2 P
LT1
C11 LT1
LT8

G
LT5 LT5 LT5 LT5
LT5 LT5 P LT5
1 3 2 1 3 2 1 1 1 1 LT6 LT5 LT5
LT7 LT7 LT7 LT7 LT7 LT5 LT5
C10 LT8 P
LT8
LT5 LT5 LT1
LT5
3 LT5 LT5
3 1 1 2 1 LT1 1 LT6 LT5
LT1
LT5 P LT5 LT5
LT5 LT5 LT5 LT5 LT5
LT5 LT8
1 P
3 2 1 3 2 LT5
LT8
LT6 P
LT5 LT5 LT1 LT8
LT1
1
C 1
LT1 1 1 LT5 P LT5 LT5 LT5 LT5
LT1 LT1 LT1
LT6
LT5 LT5 LT5 LT5 LT5 LT8
LT5 DB - GL - L7
2 1 3 2 1 3
LT7 LT1 LT7 LT1 LT1 C7 CLIENT
LT1 LT1 C8
1 LT6 LT2
1 1 C9 LT2
LT1 LT7 1 1 C10
DB - GL - L20 SWITCH C1
LT1
LT1 LT1 C11
C12
MONIAN LIMITED
1 LT1 LT2 LT2
LT5 LT5 LT5 LT5 LT7
LT5 1 LT5 LT1 LT1
DB - GL - L19 SWITCH C2 3 2 3 2

LT1 LT1 LT1


DB - GL - L18 SWITCH C3 LT5 LT5
LT7 LT5 LT5 1 1 2 2 2 2 2 PROJECT NAME:
3 2 1 3
LT1
LT7 LT7 LT1
ELEMENTS WAIGANI
K DB - GL - L6
LT5

1 1 1 1 1
SECTION: S496 LOT: L16
SIGNAGE
3
2 3 1 SUBURB/TOWN:
DB - GL - L17 SWITCH C1 1 2 3 1 2 3 1 2 3 2 3 1 2 3 1 Hohola, Port Moresby
1
SUPERVISOR:
DB - GL - L16 SWITCH C2
3
2
SWITCH C10 DB - GL - L8 RTD
1 SWITCH C4 DB - GL - L14 DB - GL - L2 SWITCH 12 DB - GL - L10 ARCHITECT / DRAFTSMAN
2
2 3 FN/AP/BH/SL
SWITCH C5 DB - GL - L13 SWITCH C10 DB - GL - L11 SWITCH C11 DB - GL - L9
DB - GL - L15 SWITCH C3

DRAWING TITLE:
SWITCH C6 DB - GL - L12 SWITCH C12 DB - GL - L10

1 2 3 1 HOTEL & GAMING BUILDING HOTEL & GAMING BLDG.


GROUND FLOOR GROUND FLOOR
NOTES: ELECTRICAL
1 ELECTRICAL - LIGHTING LAYOUT -15% of the lights are to be on a 24 HR circuit for security and safety. LIGHTING LAYOUT
SCALE 1:150 M - Each lighting circuit to have a maximum of 20 lights conected to it.
E-01.0 - Coordinate all light fittings with all other services on ceiling. Contractor to
NOTES :
-All DB's within cupboards are to be smoke sealed. Cupboards to have smoke detector inside. allow for each light to move up to 1000mm to avoid any clashes.
-600mm clearance is to be maintained from full extend of DB cupboard door swing or DB door swing. DESIGNED BY: DRAWING SCALE:
- Provide time clocks within each DB as required for the control of lights.
-All penetrations are to be sealed accordingly. DMA 1:150
- Any UPS installation that has a capacity exceeding 10 ampere hours or voltage higher than 24 Provide separate time clocks for internal lights, external lights and signs
CHECKED BY: FILE NAME:
volts is required to be 2 HR fire separated from the rest of the building.
-Confirm outlets that are to UPS supplied. Typically all outlets servicing essential security and
as required. Oly provide time licks for external lights and signs if not RTD
data services are to be on UPS power. connected to PE cell.
-All electrical penetrations on are to be confirmed and coordinated on site. APPROVED BY:
-Confirm ACU locations with mechanical for all levels. ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - Ap - Electrical .Lighting Layout - Rev 05 - 240516.dwg 090715 E-01.0

V.03.2
This is and shall remain in the property of
Monian Ltd., for which it was commissioned.
Unauthorised use of the document in any way is
prohibited. Dimensions shall rule over scale in
case of conflict.

Dimensions must be verified at the site before


commencing any work or making any shop
drawings. IF IN DOUBT, CONFIRM WITH
ARCHITECT.

REV. DESCRIPTION DATE

A AS PER DMA 7382 - SKE - 006 211015

B AS PER DMA 7382-E-SK-01 [P1] 231215

C AS PER DMA 7382-E-SK-02 [P2] 050216


CIRCUITS TO
DB-LAUNDRY D AS PER DMA 7382-E-SK-03 [P1] 231215

AS REQUIRED E AS PER DMA 7382-E-SK-MASTER [P1] 240516

F AS PER DMA 7382-E-SK-MASTER [P2] 150416

LT3 LT3 LT3

LT3 LT3 LT3 LT3

24hr

CLIENT

WALL MOUNT
LIGHT MONIAN LIMITED

PROJECT NAME:

ELEMENTS WAIGANI
SECTION: S496 LOT: L16
SUBURB/TOWN:
Hohola, Port Moresby
SUPERVISOR:

RTD
ARCHITECT / DRAFTSMAN
FN/AP/BH/SL

DRAWING TITLE:

LAUNDRY AREA
GROUND FLOOR
ELECTRICAL
LAUNDRY AREA LIGHTING LAYOUT

1 ELECTRICAL - LIGHTING LAYOUT


SCALE 1:50 M
E-01.1 DESIGNED BY: DRAWING SCALE:
1:150
DMA
CHECKED BY: FILE NAME:
RTD
APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - Ap - Electrical .Lighting Layout - Rev 05 - 240516.dwg 090715 E-01.1

V.03.2
18 17 16 15 14 13 12
N O R T H
This is and shall remain in the property of
Monian Ltd., for which it was commissioned.
Unauthorised use of the document in any way is
prohibited. Dimensions shall rule over scale in
case of conflict.
DB - GL- L3

A A Dimensions must be verified at the site before


commencing any work or making any shop
drawings. IF IN DOUBT, CONFIRM WITH
LT1
ARCHITECT.

LT4 LT4 PD
DB - L1 - L5 DB - L1 - L6 DB - L1 - L7
REV. DESCRIPTION DATE
LT1
A AS PER 7382 - SKE - 006 211015

B B B AS PER 7382-E-SK-01 [P1] 231215

LT1
LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 C AS PER DMA 7382-E-SK-02 [P2] 050216
LT1 LT1
LT1 LT1 LT1
LT1
LT1 LT1 LT1 LT1 LT1 LT1 LT1 D AS PER DMA 7382-E-SK-03 [P1] 231215

LT1

LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1
LT1
LT1
LT1 LT1
PD

LT1

D LT1
LT1
LT1 LT1
LT1 LT1
LT1
LT1
LT1 LT1 LT1
LT1
LT1 LT1
LT1
DB - L1 - L4
LT1
DB - L1- L1 LT1
LT1
LT1 LT1

DB - GL- L1
LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1
LT1 LT1 LT1 LT1 LT4
LT1 PD PD PD PD PD

PD

D LT4 DB - L1- L13


E'
LT1 LT1
LT1 LT1 LT1
LT1 LT1 LT1 LT1 LT1
LT1 LT2
LT1 LT1 LT2 LT2 LT2
PD
LT1
LT1 LT1
LT1
LT1 LT1
LT1
LT1 LT1 LT1 LT1
LT1 LT1 LT1 LT2
LT1
DB - L1- L2 LT1
LT4
LT1

G LT1
LT1
LT1 LT1

D
LT1

LT7 LT7
PD
LT7 LT7
LT2 LT2 LT2

DB - L1- L3 LT1
LT1 LT1
LT1 LT1 LT1
LT1 LT1 LT1 LT1
LT1 LT1 LT1 LT1 PD
LT1 LT1 LT1
LT1 LT1
PD LT1 CLIENT
D D

LT1
LT1

LT1
LT1

LT1
LT1

LT1 LT1 LT1 LT1


LT2 LT2 LT2
i MONIAN LIMITED
LT1 LT1

DB - L1- L12
LT2 LT2 LT2 LT2
LT1 LT1 LT1 LT1

LT1 LT1 PROJECT NAME:


LT1 LT1 LT1 LT1 LT1 LT1
LT1
ELEMENTS WAIGANI
PD LT2 LT2
LT1 LT1 LT1 LT1
LT2 LT2 LT2 SECTION: S496 LOT: L16
LT1 LT1
LT1 LT2 LT2 SUBURB/TOWN:
LT1
LT1 Hohola, Port Moresby
LT1 LT1 LT1 LT1
LT1
LT1
LT1 LT1 SUPERVISOR:
K K RTD
DB - L1- L9
ARCHITECT / DRAFTSMAN
DB - L1- L8 DB - L1- L11
DB - L1- L10 FN/AP/BH/SL

DRAWING TITLE:
HOTEL & GAMING BUILDING
LEVEL 1 HOTEL & GAMING BLDG.

NOTES: LEVEL 1
1 ELECTRICAL - LIGHTING LAYOUT -15% of the lights are to be on a 24 HR circuit for security and safety. ELECTRICAL
SCALE 1:150 M
E-02 -Finish circuiting and switching as required. Recommend maximum LIGHTING LAYOUT
NOTES : 25 lights per circuit.
-All DB's within cupboards are to be smoke sealed. Cupboards to have smoke detector inside. -Ensure switchboard has 600mm clearance from full extent of door swing.
-600mm clearance is to be maintained from full extend of DB cupboard door swing or DB door swing.
-It is recommended that the occupancy fob/cards turn off power, air conditioning
-All penetrations are to be sealed accordingly. DESIGNED BY: DRAWING SCALE:
- Any UPS installation that has a capacity exceeding 10 ampere hours or voltage higher than 24 and lighting in rooms.
volts is required to be 2 HR fire separated from the rest of the building. -Suggest the use of presence detectors in stairwell to aid safety. DMA 1:150
-Confirm outlets that are to UPS supplied. Typically all outlets servicing essential security and
-Recommend 24hr/security lights to be designated throughout halls. CHECKED BY: FILE NAME:
data services are to be on UPS power.
-All electrical penetrations on are to be confirmed and coordinated on site.
RTD
-Confirm ACU locations with mechanical for all levels. APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - Ap - Electrical .Lighting Layout - Rev 05 - 240516.dwg 090715 E-02

V.03.2
18 17 16 15 14 13 12
N O R T H
This is and shall remain in the property of
Monian Ltd., for which it was commissioned.
Unauthorised use of the document in any way is
prohibited. Dimensions shall rule over scale in
DB - GL- L3
case of conflict.

A Dimensions must be verified at the site before


commencing any work or making any shop
drawings. IF IN DOUBT, CONFIRM WITH
ARCHITECT.
LT4 LT4
DB - L2 - L5 DB - L2 - L6 DB - L2 - L7
PD
REV. DESCRIPTION DATE

A AS PER 7382 - SKE - 006 211015

B B B AS PER 7382-E-SK-01 [P1] 231215

LT1 LT1 LT1 LT1 LT1 LT1 LT1


LT1
LT1 LT1
LT1 LT1 LT1 LT1 C AS PER DMA 7382-E-SK-02 [P2] 050216
LT1
LT1
LT1
LT1
D AS PER DMA 7382-E-SK-03 [P1] 231215
LT1 LT1 LT1
LT1 LT1 LT1

LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1
LT1 LT1

LT1

D LT1
LT1 LT1
LT1 LT1
LT1 LT1
LT1 LT1
LT1
LT1
LT1 LT1
LT1

DB - L2 - L4
LT1
DB - L2- L1 LT1
LT1 LT1
PD
DB - GL- L1
LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1
PD PD LT4
PD PD PD

PD LT1 LT12 LT12


E
LT12 LT12
LT1
LT1 LT1 LT1 LT1 LT1 LT1 LT1
PD LT1 LT1 LT1

LT12 LT12

LT1 LT1 LT1


LT1
LT1

DB - L2- L2 LT12 LT4


LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1

G LT1
LT7 LT7 LT7 LT7
LT1
DB - L2- L3 LT1 LT1
LT1 LT1 LT1 PD LT1 LT1 LT1
LT1 LT1
LT1
LT1 LT1 LT1
LT1 LT1
LT1 LT1 LT1 LT1 LT1 LT1
PD CLIENT
LT1
LT1 LT1
LT1

LT1
I MONIAN LIMITED
DB - L2- L10 DB - L2 - L8
LT1
LT1 LT1
DB - L2 - L9
LT1
LT1
LT1
LT1
PROJECT NAME:
LT1
LT1 LT1
ELEMENTS WAIGANI
LT1
PD
LT1
SECTION: S496 LOT: L16
LT1 LT1
LT1 LT1 SUBURB/TOWN:
LT1 LT1
Hohola, Port Moresby
LT1 LT1
SUPERVISOR:
K K RTD
DB - GL- L2 ARCHITECT / DRAFTSMAN

FN/AP/BH/SL

HOTEL & GAMING BUILDING DRAWING TITLE:


LEVEL 2
NOTES: HOTEL & GAMING BLDG.
1 ELECTRICAL - LIGHTING LAYOUT -15% of the lights are to be on a 24 HR circuit for security and safety. LEVEL 2
SCALE 1:150 M -Finish circuiting and switching as required. Recommend maximum ELECTRICAL
E-03 25 lights per circuit.
NOTES : -Ensure switchboard has 600mm clearance from full extent of door swing. LIGHTING LAYOUT
-All DB's within cupboards are to be smoke sealed. Cupboards to have smoke detector inside. -It is recommended that the occupancy fob/cards turn off power, air conditioning
-600mm clearance is to be maintained from full extend of DB cupboard door swing or DB door swing.
-All penetrations are to be sealed accordingly. and lighting in rooms.
- Any UPS installation that has a capacity exceeding 10 ampere hours or voltage higher than 24 -Suggest the use of presence detectors in stairwell to aid safety.
volts is required to be 2 HR fire separated from the rest of the building. DESIGNED BY: DRAWING SCALE:
-Recommend 24hr/security lights to be designated throughout halls.
-Confirm outlets that are to UPS supplied. Typically all outlets servicing essential security and DMA 1:150
data services are to be on UPS power.
CHECKED BY: FILE NAME:
-All electrical penetrations on are to be confirmed and coordinated on site.
-Confirm ACU locations with mechanical for all levels. RTD
APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - Ap - Electrical .Lighting Layout - Rev 05 - 240516.dwg 090715 E-03

V.03.2
18 17 16 15 14 13 12
N O R T H
This is and shall remain in the property of
Monian Ltd., for which it was commissioned.
Unauthorised use of the document in any way is
prohibited. Dimensions shall rule over scale in
case of conflict.
DB - GL- L3
Dimensions must be verified at the site before
commencing any work or making any shop
A drawings. IF IN DOUBT, CONFIRM WITH
ARCHITECT.

LT1
LT4 LT4
DB - L3 - L5 DB - L3 - L6 DB - L3 - L7 REV. DESCRIPTION DATE
PD

LT1
A AS PER 7382 - SKE - 006 211015

B B AS PER 7382-E-SK-01 [P1] 231215

LT1 C AS PER DMA 7382-E-SK-02 [P2] 050216


LT1 LT1 LT1 LT1 LT1 LT1 LT1
LT1 LT1 LT1 LT1 LT1 LT1
LT1 LT1 LT1 D AS PER DMA 7382-E-SK-03 [P1] 231215
LT1
LT1 LT1
LT1 LT1 LT1 LT1 LT1

LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1
LT1 LT1

LT1

LT1 LT1
LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1

LT1 DB - L3 - L4
LT1
DB - L3- L1 LT1
LT1 LT1
PD
DB - GL- L1
LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1
LT1
LT1 PD LT4
PD PD PD
PD

LT1

PD LT12 LT12
E
LT12 LT12
LT1 LT1
LT1 LT1 LT1
PD LT1 LT1 LT1 LT1 LT1 LT1 LT1
LT1
LT12 LT12

LT1 LT1 LT1


LT1
LT1
LT1
DB - L3- L2 LT12 LT4
LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1

LT1
LT7 LT7 LT7 LT7
LT1
DB - L3- L3 LT1
LT1 LT1 PD LT1 LT1
LT1 LT1
LT1
LT1 LT1 LT1 LT1 LT1 LT1 LT1
LT1 LT1 CLIENT
LT1 LT1 LT1 LT1
PD
LT1 LT1
LT1 LT1

LT1
LT1
i MONIAN LIMITED
DB - L3- L10 DB - L3 - L8
LT1 LT1 LT1
DB - L3 - L9
LT1 LT1
LT1 PROJECT NAME:
LT1
LT1
LT1
LT1
ELEMENTS WAIGANI
LT1
SECTION: S496 LOT: L16
PD SUBURB/TOWN:
LT1 LT1
LT1
LT1
LT1
LT1 LT1
Hohola, Port Moresby
LT1 LT1

SUPERVISOR:
LT1 LT1

RTD
K ARCHITECT / DRAFTSMAN
FN/AP/BH/SL
DB - GL- L2

HOTEL & GAMING BUILDING DRAWING TITLE:

LEVEL 3 HOTEL & GAMING BLDG.


NOTES:
1 ELECTRICAL - LIGHTING LAYOUT -15% of the lights are to be on a 24 HR circuit for security and safety.
LEVEL 3
ELECTRICAL
SCALE 1:150 M -Finish circuiting and switching as required. Recommend maximum
NOTES : E-04 25 lights per circuit. LIGHTING LAYOUT
-All DB's within cupboards are to be smoke sealed. Cupboards to have smoke detector inside.
-600mm clearance is to be maintained from full extend of DB cupboard door swing or DB door swing.
-Ensure switchboard has 600mm clearance from full extent of door swing.
-All penetrations are to be sealed accordingly. -It is recommended that the occupancy fob/cards turn off power, air conditioning
- Any UPS installation that has a capacity exceeding 10 ampere hours or voltage higher than 24 and lighting in rooms. DESIGNED BY:
volts is required to be 2 HR fire separated from the rest of the building. DRAWING SCALE:
-Suggest the use of presence detectors in stairwell to aid safety.
-Confirm outlets that are to UPS supplied. Typically all outlets servicing essential security and DMA 1:150
data services are to be on UPS power. -Recommend 24hr/security lights to be designated throughout halls.
CHECKED BY: FILE NAME:
-All electrical penetrations on are to be confirmed and coordinated on site.
-Confirm ACU locations with mechanical for all levels. RTD
APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - Ap - Electrical .Lighting Layout - Rev 05 - 240516.dwg 090715 E-04

V.03.2
18 17 16 15 14 13 12
N O R T H
This is and shall remain in the property of
Monian Ltd., for which it was commissioned.
Unauthorised use of the document in any way is
prohibited. Dimensions shall rule over scale in
case of conflict.

A DB - L4- L1 Dimensions must be verified at the site before


commencing any work or making any shop
PD drawings. IF IN DOUBT, CONFIRM WITH
LT4 LT4 DB - L4- L2 ARCHITECT.

DB - L4- L3 REV. DESCRIPTION DATE

B A AS PER 7382 - SKE - 006 211015

LT1 LT1 LT1 LT1


LT1
LT1 LT1 B AS PER 7382-E-SK-01 [P1] 231215
LT1
LT1 WL
LT1
WL
C AS PER DMA 7382-E-SK-02 [P2] 050216

LT12 LT1

LT1 LT12 LT1 D AS PER DMA 7382-E-SK-03 [P1] 231215

LT1 E AS PER DMA 7382-E-SK-MASTER [P1] 240516


LT1 LT1
LT1 LT1 LT1 LT1 LT1
LT1
LT1 F AS PER DMA 7382-E-SK-MASTER [P2] 150416

WL
WL DB - L4- L4
LT1

D
LT12
LT1 LT1 LT1 LT1 LT1
LT1
LT1
LT1
LT1

WL

WL
LT1 LT1
DB- L4 LT1 LT1 LT1
LT1 DB/A- L4 LT1
LT1 LT1 LT1 LT1 LT4
DB/B- L4 LT1
WP

LT1 LT1 LT1


LT1
E
LT1
LT1 LT1 LT1
LT1 LT1 LT1
LT1 LT1 LT1

C
C
LT1 LT1
LT1
LT1 LT1 LT1 LT1 LT1 LT1 LT4
LT1 LT1
LT1

G LT1
LT7 LT7 LT7 LT7
LT1

LT1
LT1
LT1 LT1
LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1 LT1
LT1
LT1

i
LT1 CLIENT

LT1 LT1
LT1 LT1
LT1
LT1
LT1 LT1 LT1 LT1 LT1 MONIAN LIMITED
LT1
LT1

LT1
PROJECT NAME:
LT1 LT1 DB - L4- L6 DB - L4- L5
LT1 LT1 ELEMENTS WAIGANI
SECTION: S496 LOT: L16
SUBURB/TOWN:
LT1
LT1 Hohola, Port Moresby

K SUPERVISOR:

RTD
DB - L4- L7
ARCHITECT / DRAFTSMAN
FN/AP/BH/SL

HOTEL & GAMING BUILDING


LEVEL 4 DRAWING TITLE:

NOTES: HOTEL & GAMING BLDG.


1 ELECTRICAL - LIGHTING LAYOUT -15% of the lights are to be on a 24 HR circuit for security and safety.
LEVEL 4 - PENTHOUSE
SCALE 1:150 M -Finish circuiting and switching as required. Recommend maximum
E-05 25 lights per circuit. ELECTRICAL
-Ensure switchboard has 600mm clearance from full extent of door swing. LIGHTING LAYOUT
-It is recommended that the occupancy fob/cards turn off power, air conditioning
NOTES : and lighting in rooms.
-All DB's within cupboards are to be smoke sealed. Cupboards to have smoke detector inside.
-600mm clearance is to be maintained from full extend of DB cupboard door swing or DB door swing.
-Suggest the use of presence detectors in stairwell to aid safety.
-All penetrations are to be sealed accordingly. -Recommend 24hr/security lights to be designated throughout halls. DESIGNED BY: DRAWING SCALE:
- Any UPS installation that has a capacity exceeding 10 ampere hours or voltage higher than 24 1:150
DMA
volts is required to be 2 HR fire separated from the rest of the building.
-Confirm outlets that are to UPS supplied. Typically all outlets servicing essential security and CHECKED BY: FILE NAME:
data services are to be on UPS power. RTD
-All electrical penetrations on are to be confirmed and coordinated on site.
-Confirm ACU locations with mechanical for all levels. APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - Ap - Electrical .Lighting Layout - Rev 05 - 240516.dwg 090715 E-05

V.03.2
18 17 16 15 14 13 12
N O R T H
This is and shall remain in the property of
Monian Ltd., for which it was commissioned.
Unauthorised use of the document in any way is
prohibited. Dimensions shall rule over scale in
case of conflict.

A Dimensions must be verified at the site before


commencing any work or making any shop
drawings. IF IN DOUBT, CONFIRM WITH
ARCHITECT.

REV. DESCRIPTION DATE

SIGNAGE
B A AS PER 7382 - SKE - 006 211015

B AS PER 7382-E-SK-01 [P1] 231215

C AS PER DMA 7382-E-SK-02 [P2] 050216

D AS PER DMA 7382-E-SK-03 [P1] 231215

EM

D
LT3

E
EM EM

EM

G
DB - L4- L8 WP EM

i CLIENT

MONIAN LIMITED

PROJECT NAME:
SIGNAGE

ELEMENTS WAIGANI
SECTION: S496 LOT: L16
SUBURB/TOWN:
Hohola, Port Moresby

K SUPERVISOR:

RTD
ARCHITECT / DRAFTSMAN
FN/AP/BH/SL
NOTES:
HOTEL & GAMING BUILDING -ALL mechanical power locations and ratings are to be confirmed DRAWING TITLE:

ROOF with the mechanical contractor prior to install. HOTEL & GAMING BLDG.
-Connect sign power to DB on matching Level.
1 ELECTRICAL - LIGHTING LAYOUT -PE cell location to be confirmed by the electrical contractor and
ROOF
SCALE 1:150 M ELECTRICAL
E-06 installed in a suitable location to ensure proper operation. LIGHTING LAYOUT
NOTES : -Confirm location of all electrical connections for Hydraulic and
-All DB's within cupboards are to be smoke sealed. Cupboards to have smoke detector inside.
-600mm clearance is to be maintained from full extend of DB cupboard door swing or DB door swing. mechanical equipment of site. Indicative positions only shown.
-All penetrations are to be sealed accordingly.
- Any UPS installation that has a capacity exceeding 10 ampere hours or voltage higher than 24 Power rating for hot water units, pumps, solar hot water and other DESIGNED BY: DRAWING SCALE:
volts is required to be 2 HR fire separated from the rest of the building. DMA 1:150
-Confirm outlets that are to UPS supplied. Typically all outlets servicing essential security and hydraulic equipment to be confirmed with hydraulics prior to CHECKED BY: FILE NAME:
data services are to be on UPS power.
-All electrical penetrations on are to be confirmed and coordinated on site. install. RTD
-Confirm ACU locations with mechanical for all levels.
APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - Ap - Electrical .Lighting Layout - Rev 05 - 240516.dwg 090715 E-06

V.03.2
1 June 2016
DB - GL - P24
NOTES : Ensure generator room is adequately sized to ensure
-All DB's within cupboards are to be smoke sealed. Cupboards to have smoke detector inside. DB - GL - P23 DB - GL - P37 DB - GL - P36 appropriate clearances are maintained to all sides of each
-600mm clearance is to be maintained from full extend of DB cupboard door swing or DB door swing. generator. Ensure acoustic rating of room to adequately
DB - GL - P22
-All penetrations are to be sealed accordingly. DB - GL - P21 attenuate generator running noise.
-All TV outlets and provisions are to be confirmed and locations coordinated on site.
- Any UPS installation that has a capacity exceeding 10 ampere hours or voltage higher than 24 DB - GL - P20 DB - GL - P19 N O R T H
volts is required to be 2 HR fire separated from the rest of the building.
-Confirm outlets that are to UPS supplied. Typically all outlets servicing essential security and
data services are to be on UPS power.
16 15 14 12 11 This is and shall remain in the property of
Monian Ltd., for which it was commissioned.
DB - GL - P50 Unauthorised use of the document in any way is
-All electrical penetrations on are to be confirmed and coordinated on site. prohibited. Dimensions shall rule over scale in
-Confirm ACU locations with mechanical for all levels. case of conflict.

Dimensions must be verified at the site before


commencing any work or making any shop

A CL CL
drawings. IF IN DOUBT, CONFIRM WITH
ARCHITECT.

REV. DESCRIPTION DATE


CL

STANDBY GEN 1

STANDBY GEN 2
A AS PER 7382 - SKE - 006 211015
CL ACU WP

B CL
ACU
ACU
B AS PER 7382-E-SK-01 [P1] 231215

C AS PER DMA 7382-E-SK-MASTER [P1] 240516


WP

CL D AS PER DMA 7382-E-SK-MASTER [P2] 150416

DB - KITCHEN
WP WP
DB - GL - P2 DB - GL - P40 Change 3ph outlets to
CL ACU
ACU
DB - GL - P42 switched connections
DB - GL - P35
ALTERNATIVE MSB
DB - GL - P1 LOCATION TO
X2 PROVIDE AWNING
DB - GL - P25 OVER TO SUIT AND
BOLLARD PROTECTION
AS REQUIRED.

D CL CL CL
cm
CL
X2 X2 X2
X2 X2
DB - GL - P26
ACU CL

CL DB - GL - P28 DB - GL - P44 CL
CL CL

CL DB - GL - P27 CL CL

DB - GL - P38
CL DB - GL - P32
X2
ACU LIFT FDP DB - GL - P18 ACU
ACU
DB - GL - P39 INDICATIVE ONLY DB - GL - P16
DB - GL - P3 DB - GL - P30
CL
X2
CL DB - GL - P45
DB - GL - P29 DB - GL - P33
CL

G CL
DB - GL - P1
CL CL ACU

Proposed DB-GL Location. DB - GL - P31


will require a lockable X2 CL
DB - GL - P4 cupboard to conceal and
CL
appropriately signed.
ACU ATM GPO ACU
CLIENT

DB - GL - P41 CL
CL
DB - GL ACU X2 DB - GL - P15 MONIAN LIMITED
CL

X2 CL
CL
DB - GL - P48 PROJECT NAME:
DB - GL - P43 CL
CL
CL ACU ELEMENTS WAIGANI
cm cm DB - GL - P47 SECTION: S496 LOT: L16
ACU
SUBURB/TOWN:
DB - GL - P6
CL
CL
WP
Hohola, Port Moresby
X2 DB - GL - P14
SUPERVISOR:
CL
CL
RTD
K CL WP ARCHITECT / DRAFTSMAN
SEC

WP
DB - GL - P8
FN / AP / BH
ACU
UPS PABX
MDF

DB - GL - P49 DRAWING TITLE:


DB - GL - P34
DB - GL - P13 DB - GL - P46 NOTES : (Lift Requirements) HOTEL & GAMING BLDG.
DB - GL - P9 DB - GL - P5
DB - GL - P11
-LIFT FDP, CONFIRM LOCATION WITH LIFT GROUND FLOOR
DB - GL - P10 DB - GL - P12 CONTRACTOR.
PROVIDE 4 PAIRS COMMS CABLE (FIRE RATED ELECTRICAL
WP WS51W) FROM MDF.
POWER LAYOUT
-PROVIDE UNINTERRUPTED TEMPORARY POWER
HOTEL & GAMING BUILDING PRIOR TO THE COMMENCEMENT AND DURING THE
GROUND FLOOR ENTIRE INSTALLATION OF THE ELEVATOR.

-CONFIRM POWER REQUIREMENTS AND


ELECTRICAL - POWER LAYOUT
DESIGNED BY: DRAWING SCALE:

power for submersible pump 1 LOCATIONS WITH LIFT CONTRACTORS.


DMA 1:150
-PERMANENT POWER WITH AN ADDITIONAL TAIL FILE NAME:
SCALE 1:150 M CHECKED BY:
E.07.0 OF 5M FROM THE POINT OF CONNECTION
REQUIRED FOR LIFT. CONFIRM REQUIREMENTS
RTD
AND LOCATION WITH LIFT CONTRACTOR. CABLE APPROVED BY:
TO BE 2 HR FIRE RATED MIN. 2S53W. ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - Ap - Electrical .Power Layout - Rev 05 - 260516.dwg 090715 E.07.0

H:\WEEKLY DRAWINGS\ELEMENTS WAIGANI SOUTH (S496L16 Hohola NCD)\DRAWINGS\ELECTRICAL V.03.1


1 June 2016

This is and shall remain in the property of


Monian Ltd., for which it was commissioned.
Unauthorised use of the document in any way is
prohibited. Dimensions shall rule over scale in
case of conflict.

Dimensions must be verified at the site before

CONFIRM HOT WATER UNIT


9 8 DOMUS CM-3250 7 commencing any work or making any shop
drawings. IF IN DOUBT, CONFIRM WITH
TO BE SUPPLIED BY MSB ARCHITECT.
CONNECTION TYPE AND LOCATION
PRIOR TO INSTALL. REV. DESCRIPTION DATE
IP66 WEATHERPROOF POINT REQUIRED.
A AS PER 7382 - SKE - 006 211015

B AS PER 7382-E-SK-01 [P1] 231215

C AS PER DMA 7382-E-SK-02 [P2] 050216

A D AS PER DMA 7382-E-SK-MASTER [P1] 240516

E AS PER DMA 7382-E-SK-MASTER [P2] 150416

AS PER DMA 7382-E-SK-08[P1]

5 5 5 6 F LAUNDRY LAYOUT 150416

4
PRESS & BOARD
FOLDING

LAUNDRY AREA
DB-LAUNDRY

1 2 2 2 3 3 3
SOILED
WASHER AREA DRYER AREA CLIENT

LINEN AREA
1 MONIAN LIMITED

PROJECT NAME:

C ELEMENTS WAIGANI
SECTION: S496 LOT: L16
SUBURB/TOWN:
Hohola, Port Moresby
SUPERVISOR:

RTD
DRYER OUTLETS AND RATINGS ARCHITECT / DRAFTSMAN
TO BE CONFIRMED WITH HYDRAULICS
FN / AP / BH

DRAWING TITLE:

LAUNDRY AREA
- Confirm mode of operation MONIAN WAIGAINI ELEMENTS SOUTH GROUND FLOOR
(Electric / Gas/ Steam/ Oil) and ITEM NO. DESCRIPTION MODEL DIMENSIONS (MM) ELECTRICAL
LAUNDRY AREA electrical requirements of 1 LAUNDRY TROLLEY PLASTIC 900 LITRE 1040W x 630D x 1600H POWER LAYOUT
1 ELECTRICAL - POWER LAYOUT DTA-DTP-36.
Prior to Electrical provisions purchase
2 DOMUS 36KG WASHER DLS-36L 979W x 1166D x 1428H

3 DOMUS 36KG DRYER DTA-DTP-36 985W x 1200D x 1946H


SCALE 1:50 M
E.07.1 and install.
4 LG Commercial Washer Dryer Stacker Giant C 686W x 756D x 983H
DESIGNED BY: DRAWING SCALE:
DMA AS SHOWN

5 Simply Stainless Work Bench 900W x 600D x 900H


CHECKED BY: FILE NAME:
6 DOMUS CM-3250 CM-3250 4274W x 1070D x 1170H RTD
APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - Ap - Electrical .Power Layout - Rev 05 - 260516.dwg 090715 E.07.1

H:\WEEKLY DRAWINGS\ELEMENTS WAIGANI SOUTH (S496L16 Hohola NCD)\DRAWINGS\ELECTRICAL V.03.1


1 June 2016

Underground conduits to Coordinate in ground cable Cables to transition


Hot Water Units paths will all other in from underground to This is and shall remain in the property of
Monian Ltd., for which it was commissioned.

and Domus CM-3250. ground services in the in ceiling for Domus CM-3250 Unauthorised use of the document in any way is
prohibited. Dimensions shall rule over scale in
case of conflict.

immediate area. Dimensions must be verified at the site before


commencing any work or making any shop
drawings. IF IN DOUBT, CONFIRM WITH
ARCHITECT.

REV. DESCRIPTION DATE

A AS PER 7382 - SKE - 006 211015

B AS PER 7382-E-SK-01 [P1] 231215

C AS PER DMA 7382-E-SK-02 [P2] 050216

D AS PER DMA 7382-E-SK-MASTER [P1] 240516

E AS PER DMA 7382-E-SK-MASTER [P2] 150416

AS PER DMA 7382-E-SK-08[P1]


F LAUNDRY LAYOUT 150416

GENSET
ROOM
DB-LAUNDRY

MSB

LAUNDRY AREA

Conduit to ran underground CLIENT

then rise up wall and continue MONIAN LIMITED


in ceiling space to DB.
PROJECT NAME:

ELEMENTS WAIGANI
SECTION: S496 LOT: L16
NOTES : SUBURB/TOWN:
Hohola, Port Moresby

- All sizes are indicative only. SUPERVISOR:

- All equipment power connections are indicative only. RTD


ARCHITECT / DRAFTSMAN
Confirm all locations of equipment and connection FN / AP / BH/SL
points on site prior to install.
DRAWING TITLE:

LAUNDRY AREA
GROUND FLOOR
ELECTRICAL
LAUNDRY AREA
POWER LAYOUT
1 ELECTRICAL - POWER LAYOUT
SCALE 1:50 M
E.07.2 DESIGNED BY: DRAWING SCALE:
DMA AS SHOWN

CHECKED BY: FILE NAME:


RTD
APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - Ap - Electrical .Power Layout - Rev 05 - 260516.dwg 090715 E.07.2

H:\WEEKLY DRAWINGS\ELEMENTS WAIGANI SOUTH (S496L16 Hohola NCD)\DRAWINGS\ELECTRICAL V.03.1


1 June 2016
GAMING & HOTEL BUILDING
KITCHEN LAY-OUT

1 SS WORK BENCH 1500 X 700MM


2 SS SLOW MOVING RACK 1100MM
3 DECK MOUNTED PRE RINSE AND FAUCET
4 STARLINE M2 DISHWASHER
This is and shall remain in the property of
5 RUBBISH BIN 150L 597X597X730MMH Monian Ltd., for which it was commissioned.
6 INLET BENCH WITH 450MM X 450MM SINK Unauthorised use of the document in any way is
prohibited. Dimensions shall rule over scale in
7 DISHWASH RACK STAND (X2) case of conflict.
8 INFRARED STRIP HEATER 1830MML
Dimensions must be verified at the site before
9 OUTLET BENCH WITH 150MM UPSTAND ON SQ LEG commencing any work or making any shop
10 TONON 4 TIER SHELVING UNIT 1825 X 450 drawings. IF IN DOUBT, CONFIRM WITH
ARCHITECT.
11 WASH HAND BASIN MIXER
12 SS PREPARATION BENCH 1800 X 700MM
13 SS DOUBLE WALL SHELVES 1800 X 300MM REV. DESCRIPTION DATE
14 DRYSTORE by Others
A AS PER 7382 - SKE - 006 211015
15 TONON 4 TIER DRYSTORE SHELVING UNIT
16 KEG ROOM B AS PER 7382-E-SK-01 [P1] 231215

WP 17 FREEZER ROOM by Others


C AS PER DMA 7382-E-SK-02 [P2] 050216
18 TONON 4 TIER FREEZER SHELVING UNIT
19 COOLROOM D AS PER DMA 7382-E-SK-MASTER [P1] 240516

20 TONON 4 TIER COLDROOM SHELVING UNIT


E AS PER DMA 7382-E-SK-MASTER [P2] 150416
21 WASH HAND BASIN MIXER
22 SS DOUBLE WALL SHELVES 1800 X 300MM
23 TONON 4 TIER POT SHELVING 1530 X 600
24 SS MOBILE WORK BENCH 1500 X 700MM
25 SS MOBILE WORK BENCH 1500 X 700MM
26 SS PREP BENCH WITH 350X 415MM SINK
WP 27 STAINLESS 2 TIER WALL SHELVES

28 WHB AND FAUCET


29 SS WORK BENCH 1800 X 700MM
30 SS DOUBLE WALL SHELF 1800 X 300MM
DB - KITCHEN 31 EUROCHILL SINGLE DOOR UPRIGHT FREEZER
32 WASH HAND BASIN
33 SS SERVERY COUNTER
34 SS WET PREP AND LARDER BENCH WITH SINK
35 EUROCHILL 2 DOOR CHILLER
36 SS WORK BENCH 1800 X 700MM
37 DECK FAUCET
38 EUROCHILL 2 DOOR CHILLER
39 PLATE FOOD WARMER
40 EUROCHILL SUMMIT 2 DOOR FREEZER
41 WHB AND FAUCET
42 WALDORF 6 BURNER RANGE - STATIC OVEN
43 WALDORF CHAR GRILL 600MM
44 SS SALAMANDER TABLE
45 GAS SALAMANDER
46 WALDORF DEEP FRYER 450MM SINGLE PAN CLIENT
47 WALDORF INFILL BENCH 300MM
48 CONVOTHERM 10 TRAY COMBI STEAMER MONIAN LIMITED
49 STAINLESS WALL PANELS
50 BRITANNIA EXTRACTION CANOPY
51 STAINLESS 2 TIER SERVERY SHELVES W/ HEAT LAMP
52 COOKTEK DROP IN INDUCTION WARMERS PROJECT NAME:
53 DEVON CHILLED CABINET ELEMENTS WAIGANI
54 JOINERY CABINETRIES
55 WALL SHELF 1800 X 300MM
SECTION: S496 LOT: L16
SUBURB/TOWN:
54 IMPERVIOUS WALL LINING Hohola, Port Moresby
SUPERVISOR:

RTD
ARCHITECT / DRAFTSMAN

FN / AP / BH

DRAWING TITLE:

HOTEL KITCHEN AREA


GROUND FLOOR
ELECTRICAL
HOTEL KITCHEN AREA
POWER LAYOUT
1 ELECTRICAL - POWER LAYOUT
SCALE 1:50 M
E.07.3 DESIGNED BY: DRAWING SCALE:
DMA 1:150
CHECKED BY: FILE NAME:
RTD
APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - Ap - Electrical .Power Layout - Rev 05 - 260516.dwg 090715 E.07.3

H:\WEEKLY DRAWINGS\ELEMENTS WAIGANI SOUTH (S496L16 Hohola NCD)\DRAWINGS\ELECTRICAL V.03.1


1 June 2016
18 17 16 15 DB - L1 - P18
14 13 12
DB - L1 - P37
DB - L1 - P44 DB - L1 - P16 N O R T H
DB - L1 - P20 This is and shall remain in the property of
Monian Ltd., for which it was commissioned.
DB - L1 - P45 DB - L1 - P50 Unauthorised use of the document in any way is
DB - L1 - P33 DB - L1 - P34 DB - L1 - P38 prohibited. Dimensions shall rule over scale in
DB - L1 - P47 DB - L1 - P51 case of conflict.
DB - L1 - P35 DB - L1 - P41
A DB - L1 - P19 DB - L1 - P17
DB - L1 - P53
Dimensions must be verified at the site before
commencing any work or making any shop
drawings. IF IN DOUBT, CONFIRM WITH
CL DB - L1 - P54 ARCHITECT.
DB - L1 - P21 DB - L1 - P48
DB - L1 - P42
DB - L1 - P32 REV. DESCRIPTION DATE

A AS PER 7382 - SKE - 006 211015

B B AS PER 7382-E-SK-01 [P1] 231215

ACU S
C AS PER DMA 7382-E-SK-02 [P2] 050216

DB - L1 - P22
D AS PER DMA 7382-E-SK-MASTER [P1] 240516

DB - L1 - P2 CL
E AS PER DMA 7382-E-SK-MASTER [P2] 150416

DB - L1 - P15
ACU ACU ACU
ACU ACU ACU ACU
CL DB - L1 - P3
DB - L1 - P31
CL CL CL CL CL CL CL DB - L1 - P52
ACU

DB - L1 - P30
S
S S S S S S
DB - L1 - P5 CL DB - L1 - P4
CL
DB - L1 - P36 DB - L1 - P40 CL
DB - L1 - P49 CL
DB - L1- P23 DB - L1 - P9
ACU
DB - L1 - P28 DB - L1 - P39 DB - L1 - P43 DB - L1 - P74
S ACU
DB - L2 - P29 ACU
DB - L1 - P8 DB - L1 - P46 CL DB - L1 - P75 DB - L1 - P76
DB - L1 - P27 CL CL

cm
E'
CL DB-L1
DB - L1 - P26 S
ACU UPS DB - L1 - P72
DB - L1 - P24 X2
ACU DB - L1 - P77
ACU CL
CL
SERVER
X2
CL DB - L1 - P62
DB - L1 - P25 ROOM
CL
CL UPS CL
ACU

CL CL
X2 DB - L1 - P73
DB - L1 - P23 ACU
ACU
DB - L1 - P6 CM
CL CL
CL CLIENT

DB - L1 - P14
ACU S
X2 CL
CL CL
DB - L1 - P78 i MONIAN LIMITED
DB - L1 - P22 ACU
CL
Provide power and data
CL
ACU
X2 X2
to room as required.
ACU S CL ACU ACU CL CL
ACU
Allow for 5 DGPO's and PROJECT NAME:
DB - L1 - P13 ACU

CL
5 double data points. ELEMENTS WAIGANI
DB - L1 - P7 CL X2 Confirm required UPS powered
cm cm X2 SECTION: S496 LOT: L16
CL
ACU outlets on site. SUBURB/TOWN:
Hohola, Port Moresby
CL
X2 SUPERVISOR:
K K RTD
ARCHITECT / DRAFTSMAN

FN / AP
DB - L1 - P10
DB - L1 - P11 DB - L1 - P12 DB - L1 - P63
DB - L1 - P66 DB - L1 - P70
DRAWING TITLE:
DB - L1 - P58 DB - L1 - P58 DB - L1 - P59 DB - L1 - P60 DB - L1 - P61
DB - L1 - P24
HOTEL & GAMING BLDG.
DB - L1 - P56 DB - L1 - P67 DB - L1 - P68 DB - L1 - P69 DB - L1 - P71
LEVEL 1
DB - L1 - P1 DB - L1 - P64
ELECTRICAL
DB - L1 - P57
POWER LAYOUT
DB - L1 - P55 HOTEL & GAMING BUILDING
NOTES: DB - L1 - P65 LEVEL 1
-Ensure GPO's are 150mm away horizontal from the internal
ELECTRICAL - POWER LAYOUT
DESIGNED BY: DRAWING SCALE:
rim or 400mm above basins or sinks not exceeding 45L 1 DMA 1:150
capacity as per AS 3000. FILE NAME:
SCALE 1:150 M CHECKED BY:
E-08 RTD
APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - Ap - Electrical .Power Layout - Rev 05 - 260516.dwg 090715 E-08

H:\WEEKLY DRAWINGS\ELEMENTS WAIGANI SOUTH (S496L16 Hohola NCD)\DRAWINGS\ELECTRICAL V.03.1


1 June 2016

18 17 16 15 DB - L2 - P18
14 13 12
N O R T H
DB - L2 - P44
This is and shall remain in the property of
DB - L2 - P50 DB - L2 - P16 Monian Ltd., for which it was commissioned.
DB - L2 - P20 Unauthorised use of the document in any way is
prohibited. Dimensions shall rule over scale in
DB - L2 - P51 DB - L2 - P56
case of conflict.
DB - L2 - P37 DB - L2 - P42 DB - L2 - P45
DB - L2 - P53 DB - L2 - P57 Dimensions must be verified at the site before
DB - L2 - P41 DB - L2 - P47 commencing any work or making any shop

A DB - L2 - P19
DB - L2 - P17 DB - L2 - P59
drawings. IF IN DOUBT, CONFIRM WITH
ARCHITECT.

CL DB - L2 - P54 DB - L2 - P60
DB - L2 - P21
DB - L2 - P48 REV. DESCRIPTION DATE
DB - L2 - P39
A AS PER 7382 - SKE - 006 211015

B AS PER 7382-E-SK-01 [P1] 231215

B C AS PER DMA 7382-E-SK-01 [P2] 050216

ACU S
D AS PER DMA 7382-E-SK-MASTER [P1] 240516
DB - L2 - P22
E AS PER DMA 7382-E-SK-MASTER [P2] 150416

DB - L2 - P2 CL

DB - L2 - P15
ACU ACU ACU
ACU ACU ACU ACU
CL DB - L2 - P3
DB - L2 - P38
CL CL CL CL CL CL CL DB - L2 - P58
ACU

DB - L2 - P36
S S S S S S S
DB - L2 - P8 CL DB - L2 - P4
CL
DB - L2 - P40 DB - L2 - P46 CL
DB - L2 - P55 CL
DB - L2 - P23
ACU
DB - L2 - P34 DB - L2 - P43 DB - L2 - P49
ACU DB - L2 - P64
DB - L2 - P35 ACU S

DB - L2 - P31 DB - L2 - P11 DB - L2 - P70 DB - L2 - P52 DB - L2 - P67 DB - L2 - P12


CL CL

DB - L2 - P13
CL S S S S
E
CL DB-L2
DB - L2 - P33 S
ACU UPS

DB - L2 - P24
CL CL CL CL
CL
DB - L2 - P61
DB - L2 - P32 DB - L2 - P76 ACU ACU ACU ACU
DB - L2 - P5
S
DB - L2 - P29
CL
CL
DB - L2 - P29 ACU
S S
ACU CLIENT
DB - L2 - P9 DB - L2 - P62
CL

CL CL
MONIAN LIMITED
DB - L2 - P14
ACU S CL ACU
I
DB - L2 - P28 ACU
DB - L2 - P27 DB - L2 - P63

DB - L2 - P68 PROJECT NAME:

DB - L2 - P27
ACU S DB - L2 - P69 ELEMENTS WAIGANI
DB - L2 - P72 SECTION: S496 LOT: L16
DB - L2 - P7 DB - L2 - P66 SUBURB/TOWN:
CL DB - L2 - P71 Hohola, Port Moresby
DB - L2 - P65
CL SUPERVISOR:
CL
DB - L2 - P26 DB - L2 - P28
RTD
K ARCHITECT / DRAFTSMAN

FN / AP / SL

DB - L2 - P10
DRAWING TITLE:
DB - L2 - P26 DB - L2 - P25
DB - L2 - P6
HOTEL & GAMING BLDG.
DB - L2 - P30
DB - L2 - P78 DB - L2 - P74 LEVEL 2

DB - L2 - P77 DB - L2 - P73 ELECTRICAL


DB - L2 - P1
DB - L2 - P25
POWER LAYOUT
HOTEL & GAMING BUILDING
DB - L2 - P30
NOTES: DB - L2 - P75
LEVEL 2
ELECTRICAL - POWER LAYOUT
DESIGNED BY: DRAWING SCALE:
-Ensure GPO's are 150mm away horizontal from the internal 1
rim or 400mm above basins or sinks not exceeding 45L DMA 1:150
FILE NAME:
capacity as per AS 3000. SCALE 1:150 M CHECKED BY:
E-09 RTD
APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - Ap - Electrical .Power Layout - Rev 05 - 260516.dwg 090715 E-09

H:\WEEKLY DRAWINGS\ELEMENTS WAIGANI SOUTH (S496L16 Hohola NCD)\DRAWINGS\ELECTRICAL V.03.1


1 June 2016

18 17 16 15 DB - L3 - P18
14 13 12
DB - L3 - P44 N O R T H
DB - L3 - P50 DB - L3 - P16 This is and shall remain in the property of
DB - L3 - P20 Monian Ltd., for which it was commissioned.
Unauthorised use of the document in any way is
DB - L3 - P51 DB - L3 - P56 prohibited. Dimensions shall rule over scale in
DB - L3 - P37 DB - L3 - P42 DB - L3 - P45 case of conflict.
DB - L3 - P53 DB - L3 - P57
DB - L3 - P41 Dimensions must be verified at the site before
DB - L3 - P47 commencing any work or making any shop
A DB - L3 - P19
DB - L3 - P17 DB - L3 - P59 drawings. IF IN DOUBT, CONFIRM WITH
ARCHITECT.
CL DB - L3 - P54 DB - L3 - P60
DB - L3 - P21
DB - L3 - P48
REV. DESCRIPTION DATE
DB - L3 - P39
A AS PER 7382 - SKE - 006 211015

B B AS PER 7382-E-SK-01 [P1] 231215

C AS PER DMA 7382-E-SK-01 [P2] 050216


ACU S

DB - L3 - P22 D AS PER DMA 7382-E-SK-MASTER [P1] 240516

E AS PER DMA 7382-E-SK-MASTER [P2] 150416


DB - L3 - P2 CL

DB - L3 - P15
ACU ACU ACU ACU
ACU ACU ACU
CL DB - L3 - P3
DB - L3 - P38
CL CL CL CL CL CL CL DB - L3 - P58
ACU

DB - L3 - P36
S S S S S S S
DB - L3 - P8 CL DB - L3 - P4
CL
DB - L3 - P40 DB - L3 - P46 CL
DB - L3 - P55 CL
DB - L3 - P23
ACU
DB - L3 - P34 DB - L3 - P43 DB - L3 - P49
ACU DB - L3 - P64
DB - L3 - P35 ACU S

DB - L3 - P31 DB - L3 - P11 DB - L3 - P70 DB - L3 - P52 DB - L3 - P67 DB - L3 - P12


CL CL

DB - L3 - P13
CL S S S S
E
ACU CL DB-L3
DB - L3 - P33 S
UPS

DB - L3 - P24
CL CL CL CL
CL
DB - L3 - P61
DB - L3 - P32 DB - L3 - P76 ACU ACU ACU ACU
DB - L3 - P5
S

CL
DB - L3 - P29

CL
DB - L3 - P29 ACU
S S
ACU
DB - L3 - P9 DB - L3 - P62 CLIENT
CL
CL

DB - L3 - P14
ACU S CL ACU
CL
i MONIAN LIMITED
DB - L3 - P28 ACU
DB - L3 - P27 DB - L3 - P63

DB - L3 - P68
PROJECT NAME:

DB - L3 - P27
ACU S DB - L3 - P69 ELEMENTS WAIGANI
DB - L3 - P72
DB - L3 - P66
SECTION: S496 LOT: L16
DB - L3 - P7
SUBURB/TOWN:
CL DB - L3 - P71
DB - L3 - P65 Hohola, Port Moresby
CL
CL SUPERVISOR:
DB - L3 - P26 DB - L3 - P28
RTD
K ARCHITECT / DRAFTSMAN

FN / AP
DB - L3 - P10
DB - L3 - P26 DB - L3 - P25 DRAWING TITLE:
DB - L3 - P6

DB - L3 - P30
HOTEL & GAMING BLDG.
DB - L3 - P78 DB - L3 - P74
LEVEL 3
DB - L3 - P77 DB - L3 - P73 ELECTRICAL
DB - L3 - P1
DB - L3 - P25 POWER LAYOUT
DB - L3 - P30
HOTEL & GAMING BUILDING
DB - L3 - P75
NOTES: LEVEL 3
-Ensure GPO's are 150mm away horizontal from the internal
ELECTRICAL - POWER LAYOUT
DESIGNED BY: DRAWING SCALE:
rim or 400mm above basins or sinks not exceeding 45L 1 DMA 1:150
capacity as per AS 3000. SCALE 1:150 M CHECKED BY: FILE NAME:
E-10 RTD
APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - Ap - Electrical .Power Layout - Rev 05 - 260516.dwg 090715 E-10

H:\WEEKLY DRAWINGS\ELEMENTS WAIGANI SOUTH (S496L16 Hohola NCD)\DRAWINGS\ELECTRICAL V.03.1


1 June 2016
DB's to be IP56 and
18 17 16 15 have an awning over. 14 13 12
DB/B - L4 - P13
DB/A - L4 - P11 N O R T H
This is and shall remain in the property of
DB/B - L4 - P9 Monian Ltd., for which it was commissioned.
Unauthorised use of the document in any way is
DB/B - L4 - P14 prohibited. Dimensions shall rule over scale in
DB/A - L4 - P2 DB - L4 - P1 case of conflict.

A CL DB/A - L4 - P12
DB/B - L4 - P8

DB/B - L4 - P15
Dimensions must be verified at the site before
commencing any work or making any shop
drawings. IF IN DOUBT, CONFIRM WITH
DB/A - L4 - P3 DB/B - L4 - P11 DB/B - L4 - P7 ARCHITECT.
DB/B - L4 - P16
DB/A - L4 - P1
DB/B - L4 - P10
REV. DESCRIPTION DATE

WP
B A AS PER 7382 - SKE - 006 211015

DB/B - L4 - P17 B AS PER 7382-E-SK-01 [P1] 231215

S WP
C AS PER DMA 7382-E-SK-01 [P2] 050216

WP D AS PER DMA 7382-E-SK-MASTER [P1] 240516

DB - L4 - P4 CL HYD E AS PER DMA 7382-E-SK-MASTER [P2] 150416

ACU ACU
ACU
DB/B - L4 - P6
MSSB S
ACU CL
WP
CL

D DB/A - L4 - P9
DB/A - L4 S
WP

S S
DB/B - L4 - P18

CL DB/B - L4 - P19
CL CL
DB - L4
DB/A - L4 CL
DB/B - L4
DB - L4 - P6
ACU

S S
E
CL

DB/A - L4 - P7
CL
CL ACU
CL CL
CL
ACU

To be dedicated ACU
Switchboard Room.
G Key Lockable and
DB/B - L4 - P24

Appropriately Signed. S

CL
CL

CL
S ACU ACU CL
DB/A - L4 - P13
i CLIENT

MONIAN LIMITED
DB-L4, DB/A-L4 & DB/B-L4
to be in a 'chassis' within DB/B - L4 - P5
PROJECT NAME:
the main DB for Level 4
DB/B - L4 - P1 DB/B - L4 - P2 DB/B - L4 - P23 ELEMENTS WAIGANI
SECTION: S496 LOT: L16
DB/B - L4 - P4 SUBURB/TOWN:
DB/A - L4 - P8 Hohola, Port Moresby
CL DB/B - L4 - P22

K DB/B - L4 - P12 SUPERVISOR:

RTD
DB/B - L4 - P21
DB - L4 - P2
ARCHITECT / DRAFTSMAN
DB/B - L4 - P3
DB/A - L4 - P9 FN / AP / SL
DB/A - L4 - P17 DB/B - L4 - P20

NOTES: DB/A - L4 - P16 NOTES : (Lift Requirements)


DRAWING TITLE:

-Ensure GPO's are 150mm away horizontal from the internal HOTEL & GAMING BLDG.
rim or 400mm above basins or sinks not exceeding 45L -LIFT FDP, CONFIRM LOCATION WITH LIFT
DB/A - L4 - P10 CONTRACTOR.
capacity as per AS 3000. LEVEL 4 PENTHOUSE
DB/A - L4 - P15
PROVIDE 4 PAIRS COMMS CABLE (FIRE RATED
WS51W) FROM MDF.
NOTES: ELECTRICAL
DB/A - L4 - P14 -PROVIDE 3 x 10 AMP WEATHER PROOF GPO'S PER GAS BOOSTER.
-PROVIDE UNINTERRUPTED TEMPORARY POWER
EACH GAS BOOSTER TO BE ON SEPARATE CIRCUIT. FINAL LOCATION POWER LAYOUT
HOTEL & GAMING BUILDING PRIOR TO THE COMMENCEMENT AND DURING THE
ENTIRE INSTALLATION OF THE ELEVATOR. OF GPO's TO BE CONFIRMED WITH HYDRAULICS.
LEVEL 4 - PENTHOUSE -CONFIRM POWER REQUIREMENTS AND
-PROVIDE 10 x 15 AMP 1PH WEATHER PROOF HARD WIRED
LOCATIONS WITH LIFT CONTRACTORS. CONNECTIONS WITH ISOLATORS PER SOLAR HOT WATER SYSTEM.
ELECTRICAL - POWER LAYOUT
DESIGNED BY: DRAWING SCALE:
1 EACH SOLAR SYSTEM TO BE ON SEPARATE CIRCUIT. FINAL QUANTITIES
FN 1:150
-PERMANENT POWER WITH AN ADDITIONAL TAIL AND LOCATIONS TO BE CONFIRMED WITH HYDRAULICS.
SCALE 1:150 M OF 5M FROM THE POINT OF CONNECTION CHECKED BY: FILE NAME:
E-11 REQUIRED FOR LIFT. CONFIRM REQUIREMENTS -ALL POWER REQUIREMENTS FOR HYDRAULIC SYSTEMS ARE TO BE
RTD
AND LOCATION WITH LIFT CONTRACTOR. CABLE CONFIRMED WITH HYDRAULICS. PROVIDE PROVISIONS AS REQUIRED.
TO BE 2 HR FIRE RATED MIN. 2S53W. APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - Ap - Electrical .Power Layout - Rev 05 - 260516.dwg 090715 E-11

H:\WEEKLY DRAWINGS\ELEMENTS WAIGANI SOUTH (S496L16 Hohola NCD)\DRAWINGS\ELECTRICAL V.03.1


1 June 2016

18 17 16 15 14 13 12
N O R T H
This is and shall remain in the property of
Monian Ltd., for which it was commissioned.
Unauthorised use of the document in any way is
prohibited. Dimensions shall rule over scale in
case of conflict.

A Dimensions must be verified at the site before


commencing any work or making any shop
14800 drawings. IF IN DOUBT, CONFIRM WITH
Sign 15000 ARCHITECT.
Strip lights
REV. DESCRIPTION DATE
16500
16500 A AS PER 7382 - SKE - 006 211015
Strip lights 16500
Strip lights Strip lights B AS PER 7382-E-SK-01 [P1] 231215

C AS PER DMA 7382-E-SK-01 [P2] 050216

AS PER DMA
D ROOF SKETCH PLAN 080515

E AS PER DMA 7382-E-SK-MASTER [P1] 240516

F AS PER DMA 7382-E-SK-MASTER [P2] 150416

25A 25A 25A 25A 25A 20A 20A 20A 20A 25A 25A
E
CU-06 CU-07 CU-08 CU-09 CU-10 CU-21 CU-16 CU-17 CU-18 CU-19 CU-20

VRF VRF

19000
CU-01 CU-02 CU-03 CU-04 CU-05 CU-11 CU-12 CU-13 CU-14 CU-15
50A 35A 20A 35A 25A Sign 25A 25A 25A 25A 25A

G
16500
Strip lights
WP

4000 4000
i CLIENT

Column Column MONIAN LIMITED


19000
Sign
PROJECT NAME:

16500 ELEMENTS WAIGANI


Strip lights -PROVIDE 3 x 10 AMP WEATHER PROOF GPO'S PER GAS BOOSTER. EACH GAS BOOSTER TO BE ON SEPARATE CIRCUIT. FINAL LOCATION
SECTION: S496 LOT: L16
OF GPO's TO BE CONFIRMED WITH HYDRAULICS.
SUBURB/TOWN:
-PROVIDE 10 x 15 AMP 1PH WEATHER PROOF HARD WIRED CONNECTIONS WITH ISOLATORS PER SOLAR HOT WATER SYSTEM.
EACH SOLAR SYSTEM TO BE ON SEPARATE CIRCUIT. FINAL QUANTITIES AND LOCATIONS TO BE CONFIRMED WITH HYDRAULICS. Hohola, Port Moresby
14000 -ALL POWER REQUIREMENTS FOR HYDRAULIC SYSTEMS ARE TO BE CONFIRMED WITH HYDRAULICS. PROVIDE PROVISIONS AS REQUIRED.

K 7000mm 13000
Strip Lights SUPERVISOR:

RTD
4000 3000mm
10000 Column Sign ARCHITECT / DRAFTSMAN
LED Signs FN / AP / SL
NOTES:
DRAWING TITLE:

NOTES : -ALL mechanical power locations and ratings are to be confirmed


HOTEL & GAMING BLDG.
1. Connect approximately 20m of strip lighting per circuit with the mechanical contractor prior to install.
ROOF
2. External lights intended to be switch at Ground floor - -Connect sign power to DB on matching Level.
Manager's area & Level 1 - Manager's offices. ELECTRICAL
-PE cell location to be confirmed by the electrical contractor and
POWER LAYOUT
HOTEL & GAMING BUILDING installed in a suitable location to ensure proper operation.
ROOF LEVEL -Confirm location of all electrical connections for Hydraulic and
mechanical equipment of site. Indicative positions only shown.
ELECTRICAL - POWER LAYOUT
DESIGNED BY: DRAWING SCALE:
1 Power rating for hot water units, pumps, solar hot water and other FN 1:150
FILE NAME:
SCALE 1:150 M CHECKED BY:
E-12A hydraulic equipment to be confirmed with hydraulics prior to RTD
install. APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - Ap - Electrical .Power Layout - Rev 05 - 260516.dwg 090715 E-12A

H:\WEEKLY DRAWINGS\ELEMENTS WAIGANI SOUTH (S496L16 Hohola NCD)\DRAWINGS\ELECTRICAL V.03.1


1 June 2016

NOTES:
This is and shall remain in the property of
-Meters shall be compliant to all relevant standards. Monian Ltd., for which it was commissioned.
Unauthorised use of the document in any way is
prohibited. Dimensions shall rule over scale in
-Minimum cable sizes nominated for guidance only. case of conflict.

Cable sizes shall comply with maximum demand and voltage drop Dimensions must be verified at the site before
commencing any work or making any shop

requirements as per AS 3000:207. drawings. IF IN DOUBT, CONFIRM WITH


ARCHITECT.

-For circuits with very long cable runs exceeding 60m,


REV. DESCRIPTION DATE
the earth fault loop impedance would be high. Refer to AS/NZS
A AS PER 7382 - SKE - 006 211015
3000 appendix B table B1 for the selection of final sub circuit
B AS PER 7382-E-SK-01 [P1] 231215
cable size/circuit breaker combination.
C AS PER DMA 7382-E-SK-01 [P2] 050216

-Main switch board shall comply with all local supply authority D AS PER DMA 7382-E-SK-09 [P1] 180416

regulations. E AS PER DMA 7382-E-SK-MASTER [P2] 150416

CLIENT

MONIAN LIMITED

PROJECT NAME:

ELEMENTS WAIGANI
SECTION: S496 LOT: L16
SUBURB/TOWN:
Hohola, Port Moresby
SUPERVISOR:

RTD
Cable to be R-HF-110 ARCHITECT / DRAFTSMAN

WS52W rated FN / AP / SL

Line showing DRAWING TITLE:

extend of MSB HOTEL & GAMING BLDG.


SINGLE LINE DIAGRAM

1 SINGLE LINE DIAGRAM


SCALE N.T.S.
E-12B
DESIGNED BY: DRAWING SCALE:

FN 1:150
CHECKED BY: FILE NAME:
RTD
APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - Ap - Electrical .Power Layout - Rev 05 - 260516.dwg 090715 E-12B

H:\WEEKLY DRAWINGS\ELEMENTS WAIGANI SOUTH (S496L16 Hohola NCD)\DRAWINGS\ELECTRICAL V.03.1


1 June 2016

This is and shall remain in the property of


Monian Ltd., for which it was commissioned.
Unauthorised use of the document in any way is
prohibited. Dimensions shall rule over scale in
case of conflict.

Dimensions must be verified at the site before


commencing any work or making any shop
drawings. IF IN DOUBT, CONFIRM WITH
ARCHITECT.

REV. DESCRIPTION DATE

A AS PER 7382-E-SK-07[P1] 080515

B AS PER DMA 7382-E-SK-MASTER [P2] 150416

NOTES:
-Ensure GPO's are 150mm away horizontal from the internal rim or 400mm
above basins or sinks not exceeding 45L capacity as per AS 3000.

CLIENT

MONIAN LIMITED

PROJECT NAME:

ELEMENTS WAIGANI
SECTION: S496 LOT: L16
SUBURB/TOWN:
Hohola, Port Moresby
SUPERVISOR:

RTD
ARCHITECT / DRAFTSMAN

AP/BH

DRAWING TITLE:

HOTEL & GAMING BLDG.


SCHEMATICS

DESIGNED BY: DRAWING SCALE:

FN NTS
CHECKED BY: FILE NAME:
RTD
APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - Ap - Electrical .Power Layout - Rev 05 - 260516.dwg 090715 E-12C

H:\WEEKLY DRAWINGS\ELEMENTS WAIGANI SOUTH (S496L16 Hohola NCD)\DRAWINGS\ELECTRICAL V.03.1


1 June 2016

18 17 16 15 14 13 12 11
N O R T H
This is and shall remain in the property of
Monian Ltd., for which it was commissioned.
Unauthorised use of the document in any way is
A prohibited. Dimensions shall rule over scale in
case of conflict.

Dimensions must be verified at the site before


commencing any work or making any shop
drawings. IF IN DOUBT, CONFIRM WITH
ARCHITECT.

B REV. DESCRIPTION DATE

A AS PER DMA 7382 - SKE - 006 211015

B AS PER DMA 7382-E-SK-01 [P1] 231215

C AS PER DMA 7382-E-SK-02 [P2] 050216

D AS PER DMA 7382-E-SK-03 [P1] 231215

E AS PER DMA 7382-E-SK-MASTER [P2] 150416

CLIENT

MONIAN LIMITED

PROJECT NAME:

ELEMENTS WAIGANI
SECTION: S496 LOT: L16
K SUBURB/TOWN:
Hohola, Port Moresby
MDF SEC

SUPERVISOR:

RTD
ARCHITECT / DRAFTSMAN
PABX UPS

FN / AP / BH
FIP data and phone
connections are to be DRAWING TITLE:

connected directly to MDF.


HOTEL & GAMING BLDG.
GROUND FLOOR
ELECTRICAL - AUXILIARY
DATA LAYOUT
HOTEL & GAMING BUILDING
GROUND FLOOR
DESIGNED BY:

ELECTRICAL - AUXILIARY - DATA LAYOUT


DRAWING SCALE:
1 DMA 1:150
CHECKED BY: FILE NAME:
SCALE 1:150 M
E-13 RTD
APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - AP - Electrical . Auxiliary .Data Layout - Rev 05 - 230216.dwg 090715 E-13

H:\WEEKLY DRAWINGS\ELEMENTS WAIGANI SOUTH (S496L16 Hohola NCD)\DRAWINGS\ELECTRICAL V.03.1


1 June 2016
18 17 16 15 14 13 12
N O R T H
This is and shall remain in the property of
Monian Ltd., for which it was commissioned.
Unauthorised use of the document in any way is
prohibited. Dimensions shall rule over scale in
case of conflict.

A A Dimensions must be verified at the site before


commencing any work or making any shop
drawings. IF IN DOUBT, CONFIRM WITH
ARCHITECT.

REV. DESCRIPTION DATE

A AS PER 7382 - SKE - 006 211015

B B AS PER 7382-E-SK-01 [P1] 231215

C AS PER DMA 7382-E-SK-02 [P2] 050216

D AS PER DMA 7382-E-SK-03 [P1] 231215

E AS PER DMA 7382-E-SK-MASTER [P2] 150416

E'

CLIENT

i MONIAN LIMITED

PROJECT NAME:

ELEMENTS WAIGANI
SECTION: S496 LOT: L16
SUBURB/TOWN:
Hohola, Port Moresby
SUPERVISOR:
K K RTD
ARCHITECT / DRAFTSMAN

FN / AP

DRAWING TITLE:

HOTEL & GAMING BLDG.


LEVEL 1
ELECTRICAL - AUXILIARY
DATA LAYOUT
HOTEL & GAMING BUILDING
LEVEL 1
1 ELECTRICAL - AUXILIARY - DATA LAYOUT DESIGNED BY:

DMA
DRAWING SCALE:
1:150
SCALE 1:150 M
E-14 CHECKED BY: FILE NAME:
RTD
APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - AP - Electrical . Auxiliary .Data Layout - Rev 05 - 230216.dwg 090715 E-14

H:\WEEKLY DRAWINGS\ELEMENTS WAIGANI SOUTH (S496L16 Hohola NCD)\DRAWINGS\ELECTRICAL V.03.1


1 June 2016
18 17 16 15 14 13 12
N O R T H
This is and shall remain in the property of
Monian Ltd., for which it was commissioned.
Unauthorised use of the document in any way is
prohibited. Dimensions shall rule over scale in
case of conflict.

A Dimensions must be verified at the site before


commencing any work or making any shop
drawings. IF IN DOUBT, CONFIRM WITH
ARCHITECT.

REV. DESCRIPTION DATE

A AS PER 7382 - SKE - 006 211015

B B AS PER 7382-E-SK-01 [P1] 231215

C AS PER DMA 7382-E-SK-02 [P2] 050216

D AS PER DMA 7382-E-SK-03 [P1] 231215

E AS PER DMA 7382-E-SK-MASTER [P2] 150416

CLIENT

I MONIAN LIMITED

PROJECT NAME:

ELEMENTS WAIGANI
SECTION: S496 LOT: L16
SUBURB/TOWN:
Hohola, Port Moresby
SUPERVISOR:
K RTD
ARCHITECT / DRAFTSMAN

FN / AP

DRAWING TITLE:

HOTEL & GAMING BLDG.


LEVEL 2
HOTEL & GAMING BUILDING ELECTRICAL - AUXILIARY
LEVEL 2 DATA LAYOUT
1 ELECTRICAL - AUXILIARY - DATA LAYOUT
SCALE 1:150 M
E-15 DESIGNED BY: DRAWING SCALE:
DMA 1:150
CHECKED BY: FILE NAME:
RTD
APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - AP - Electrical . Auxiliary .Data Layout - Rev 05 - 230216.dwg 090715 E-15

H:\WEEKLY DRAWINGS\ELEMENTS WAIGANI SOUTH (S496L16 Hohola NCD)\DRAWINGS\ELECTRICAL V.03.1


1 June 2016

18 17 16 15 14 13 12
N O R T H
This is and shall remain in the property of
Monian Ltd., for which it was commissioned.
Unauthorised use of the document in any way is
prohibited. Dimensions shall rule over scale in
case of conflict.

Dimensions must be verified at the site before


commencing any work or making any shop
A drawings. IF IN DOUBT, CONFIRM WITH
ARCHITECT.

REV. DESCRIPTION DATE

A AS PER 7382 - SKE - 006 211015

B B AS PER 7382-E-SK-01 [P1] 231215

C AS PER DMA 7382-E-SK-02 [P2] 050216

D AS PER DMA 7382-E-SK-03 [P1] 231215

E AS PER DMA 7382-E-SK-MASTER [P2] 150416

CLIENT

i MONIAN LIMITED

PROJECT NAME:

ELEMENTS WAIGANI
SECTION: S496 LOT: L16
SUBURB/TOWN:
Hohola, Port Moresby
SUPERVISOR:

RTD
K ARCHITECT / DRAFTSMAN

FN / AP

DRAWING TITLE:

HOTEL & GAMING BLDG.


LEVEL 3
HOTEL & GAMING BUILDING ELECTRICAL - AUXILIARY
LEVEL 3 DATA LAYOUT
1 ELECTRICAL - AUXILIARY - DATA LAYOUT
SCALE 1:150 M
E-16 DESIGNED BY: DRAWING SCALE:

DMA 1:150
CHECKED BY: FILE NAME:
RTD
APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - AP - Electrical . Auxiliary .Data Layout - Rev 05 - 230216.dwg 090715 E-16

H:\WEEKLY DRAWINGS\ELEMENTS WAIGANI SOUTH (S496L16 Hohola NCD)\DRAWINGS\ELECTRICAL V.03.1


1 June 2016

18 17 16 15 14 13 12
N O R T H
This is and shall remain in the property of
Monian Ltd., for which it was commissioned.
Unauthorised use of the document in any way is
prohibited. Dimensions shall rule over scale in
case of conflict.

A Dimensions must be verified at the site before


commencing any work or making any shop
drawings. IF IN DOUBT, CONFIRM WITH
ARCHITECT.

REV. DESCRIPTION DATE

B A AS PER 7382 - SKE - 006 211015

B AS PER 7382-E-SK-01 [P1] 231215

C AS PER DMA 7382-E-SK-02 [P2] 050216

D AS PER DMA 7382-E-SK-03 [P1] 231215

E AS PER DMA 7382-E-SK-MASTER [P2] 150416

DB - L4
DB/A - L4
DB/B - L4

i CLIENT

MONIAN LIMITED

PROJECT NAME:

ELEMENTS WAIGANI
SECTION: S496 LOT: L16
SUBURB/TOWN:
Hohola, Port Moresby

K SUPERVISOR:

RTD
ARCHITECT / DRAFTSMAN

FN / AP

DRAWING TITLE:

HOTEL & GAMING BLDG.


LEVEL 4 PENTHOUSE
HOTEL & GAMING BUILDING ELECTRICAL - AUXILIARY
LEVEL 4 DATA LAYOUT
1 ELECTRICAL - AUXILIARY - DATA LAYOUT
SCALE 1:150 M
E-17 DESIGNED BY: DRAWING SCALE:

DMA 1:150
CHECKED BY: FILE NAME:
RTD
APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - AP - Electrical . Auxiliary .Data Layout - Rev 05 - 230216.dwg 090715 E-17

H:\WEEKLY DRAWINGS\ELEMENTS WAIGANI SOUTH (S496L16 Hohola NCD)\DRAWINGS\ELECTRICAL V.03.1


18 17 16 15 14 13 12 11
N O R T H
This is and shall remain in the property of
Monian Ltd., for which it was commissioned.
Unauthorised use of the document in any way is
A prohibited. Dimensions shall rule over scale in
case of conflict.

Dimensions must be verified at the site before


commencing any work or making any shop
drawings. IF IN DOUBT, CONFIRM WITH

STANDBY GEN 1

STANDBY GEN 2
ARCHITECT.

B REV. DESCRIPTION DATE

MSB
A AS PER DMA 7382 - SKE - 006 211015

B AS PER DMA 7382-E-SK-01 [P1] 231215


DB-KITCHEN

C AS PER DMA 7382-E-SK-02 [P2] 050216

AS PER DMA ENGINEERS


D EMAIL RECOMMENDATION 110516

E AS PER DMA 7382-E-SK-MASTER [P2] 150416

CLIENT

DB-GL
MONIAN LIMITED

PROJECT NAME:

ELEMENTS WAIGANI
SECTION: S496 LOT: L16

K SUBURB/TOWN:
Hohola, Port Moresby
MDF SEC

SUPERVISOR:

RTD
PABX USB

ARCHITECT / DRAFTSMAN
FN/AP/BH/SL

NOTES : DRAWING TITLE:

-Coordinate all cable tray on site with all other services. HOTEL & GAMING BLDG.
GROUND FLOOR
ELECTRICAL - AUXILIARY
CABLE TRAY LAYOUT

HOTEL & GAMING BUILDING


GROUND FLOOR DESIGNED BY: DRAWING SCALE:

1 ELECTRICAL - AUXILIARY - CABLE TRAY LAYOUT DMA


CHECKED BY: FILE NAME:
1:150

SCALE 1:150 M RTD


E-18
APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - AP - Electrical . Auxiliary .Cable Tray Layout - Rev 04 - 130216.dwg 090715 E-18

V.03.2
18 17 16 15 14 13 12
N O R T H
This is and shall remain in the property of
Monian Ltd., for which it was commissioned.
Unauthorised use of the document in any way is
prohibited. Dimensions shall rule over scale in
case of conflict.

A A Dimensions must be verified at the site before


commencing any work or making any shop
drawings. IF IN DOUBT, CONFIRM WITH
ARCHITECT.

REV. DESCRIPTION DATE

A AS PER 7382 - SKE - 006 211015

B B AS PER 7382-E-SK-01 [P1] 231215

C AS PER DMA 7382-E-SK-02 [P2] 050216

AS PER DMA ENGINEERS


D EMAIL RECOMMENDATION 110516

E AS PER DMA 7382-E-SK-MASTER [P2] 150416

E'

CLIENT

i MONIAN LIMITED

PROJECT NAME:

ELEMENTS WAIGANI
SECTION: S496 LOT: L16
SUBURB/TOWN:
Hohola, Port Moresby
SUPERVISOR:
K K RTD
ARCHITECT / DRAFTSMAN

FN/AP/BH/SL

DRAWING TITLE:
NOTES :
HOTEL & GAMING BLDG.
-Coordinate all cable tray on site with all other services.
LEVEL 1
ELECTRICAL - AUXILIARY
CABLE TRAY LAYOUT

HOTEL & GAMING BUILDING


LEVEL 1 DESIGNED BY: DRAWING SCALE:

1 ELECTRICAL - AUXILIARY - CABLE TRAY LAYOUT DMA


CHECKED BY: FILE NAME:
1:150

SCALE 1:150 M RTD


E-19
APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - AP - Electrical . Auxiliary .Cable Tray Layout - Rev 04 - 130216.dwg 090715 E-19

V.03.2
18 17 16 15 14 13 12
N O R T H
This is and shall remain in the property of
Monian Ltd., for which it was commissioned.
Unauthorised use of the document in any way is
prohibited. Dimensions shall rule over scale in
case of conflict.

A Dimensions must be verified at the site before


commencing any work or making any shop
drawings. IF IN DOUBT, CONFIRM WITH
ARCHITECT.

REV. DESCRIPTION DATE

A AS PER 7382 - SKE - 006 211015

B B AS PER 7382-E-SK-01 [P1] 231215

C AS PER DMA 7382-E-SK-02 [P2] 050216

AS PER DMA ENGINEERS


D EMAIL RECOMMENDATION 110516

E AS PER DMA 7382-E-SK-MASTER [P2] 150416

CLIENT

I MONIAN LIMITED

PROJECT NAME:

ELEMENTS WAIGANI
SECTION: S496 LOT: L16
SUBURB/TOWN:
Hohola, Port Moresby
SUPERVISOR:
K K RTD
ARCHITECT / DRAFTSMAN

FN/AP/BH/SL
NOTES :
DRAWING TITLE:
-Coordinate all cable tray on site with all other services.
HOTEL & GAMING BLDG.
LEVEL 2
ELECTRICAL - AUXILIARY
CABLE TRAY LAYOUT

HOTEL & GAMING BUILDING


LEVEL 2 DESIGNED BY: DRAWING SCALE:

1 ELECTRICAL - AUXILIARY - CABLE TRAY LAYOUT DMA


CHECKED BY: FILE NAME:
1:150

SCALE 1:150 M RTD


E-20
APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - AP - Electrical . Auxiliary .Cable Tray Layout - Rev 04 - 130216.dwg 090715 E-20

V.03.2
18 17 16 15 14 13 12
N O R T H
This is and shall remain in the property of
Monian Ltd., for which it was commissioned.
Unauthorised use of the document in any way is
prohibited. Dimensions shall rule over scale in
case of conflict.

Dimensions must be verified at the site before


commencing any work or making any shop
A drawings. IF IN DOUBT, CONFIRM WITH
ARCHITECT.

REV. DESCRIPTION DATE

A AS PER 7382 - SKE - 006 211015

B B AS PER 7382-E-SK-01 [P1] 231215

C AS PER DMA 7382-E-SK-02 [P2] 050216

AS PER DMA ENGINEERS


D EMAIL RECOMMENDATION 110516

E AS PER DMA 7382-E-SK-MASTER [P2] 150416

CLIENT

i MONIAN LIMITED

PROJECT NAME:

ELEMENTS WAIGANI
SECTION: S496 LOT: L16
SUBURB/TOWN:
Hohola, Port Moresby
SUPERVISOR:

RTD
K ARCHITECT / DRAFTSMAN

FN/AP/BH/SL

DRAWING TITLE:
NOTES :
HOTEL & GAMING BLDG.
-Coordinate all cable tray on site with all other services.
LEVEL 3
ELECTRICAL - AUXILIARY
CABLE TRAY LAYOUT

HOTEL & GAMING BUILDING


LEVEL 3 DESIGNED BY: DRAWING SCALE:

1 ELECTRICAL - AUXILIARY - CABLE TRAY LAYOUT DMA


CHECKED BY: FILE NAME:
1:150

SCALE 1:150 M RTD


E-21
APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - AP - Electrical . Auxiliary .Cable Tray Layout - Rev 04 - 130216.dwg 090715 E-21

V.03.2
18 17 16 15 14 13 12
N O R T H
This is and shall remain in the property of
Monian Ltd., for which it was commissioned.
Unauthorised use of the document in any way is
prohibited. Dimensions shall rule over scale in
case of conflict.

A Dimensions must be verified at the site before


commencing any work or making any shop
drawings. IF IN DOUBT, CONFIRM WITH
ARCHITECT.

REV. DESCRIPTION DATE

B A AS PER 7382 - SKE - 006 211015

B AS PER 7382-E-SK-01 [P1] 231215

C AS PER DMA 7382-E-SK-02 [P2] 050216

AS PER DMA ENGINEERS


D EMAIL RECOMMENDATION 110516

E AS PER DMA 7382-E-SK-MASTER [P2] 150416

i CLIENT

MONIAN LIMITED

PROJECT NAME:

ELEMENTS WAIGANI
SECTION: S496 LOT: L16
SUBURB/TOWN:
Hohola, Port Moresby

K SUPERVISOR:

RTD
ARCHITECT / DRAFTSMAN
FN/AP/BH/SL

NOTES : DRAWING TITLE:

-Coordinate all cable tray on site with all other services. HOTEL & GAMING BLDG.
LEVEL 4 - PENTHOUSE
ELECTRICAL - AUXILIARY
CABLE TRAY LAYOUT

HOTEL & GAMING BUILDING


LEVEL 4 DESIGNED BY: DRAWING SCALE:

1 ELECTRICAL - AUXILIARY - CABLE TRAY LAYOUT DMA


CHECKED BY: FILE NAME:
1:150

SCALE 1:150 M RTD


E-22
APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - AP - Electrical . Auxiliary .Cable Tray Layout - Rev 04 - 130216.dwg 090715 E-22

V.03.2
18 17 16 15 14 13 12 11
N O R T H
This is and shall remain in the property of
Monian Ltd., for which it was commissioned.
Unauthorised use of the document in any way is
A prohibited. Dimensions shall rule over scale in
case of conflict.

Dimensions must be verified at the site before


commencing any work or making any shop
drawings. IF IN DOUBT, CONFIRM WITH
ARCHITECT.

B REV. DESCRIPTION DATE

A AS PER DMA 7382 - SKE - 006 211015

B AS PER DMA 7382-E-SK-01 [P1] 231215

C AS PER DMA 7382-E-SK-02 [P2] 050216

D AS PER DMA 7382-E-SK-03 [P1] 231215

CLIENT

MONIAN LIMITED

PROJECT NAME:

ELEMENTS WAIGANI
SECTION: S496 LOT: L16

K SUBURB/TOWN:
Hohola, Port Moresby
SUPERVISOR:

RTD
ARCHITECT / DRAFTSMAN
FN/AP/BH/SL

DRAWING TITLE:

HOTEL & GAMING BLDG.


GROUND FLOOR
ELECTRICAL - AUXILIARY
EMERGENCY LIGHT LAYOUT
HOTEL & GAMING BUILDING
GROUND FLOOR Job name: ELEMENTS WAIGANI
Drawing/sketch title: 7382-E-SK-C1 DESIGNED BY:

ELECTRICAL - AUXILIARY - EMERGENCY LIGHT LAYOUT


DRAWING SCALE:
1 Description: EMERGENCY LIGHTING DMA 1:150
CHECKED BY: FILE NAME:
SCALE 1:150 M
E-23 RTD
Date: 02/06/16 Pages: 6 Revision: P1 APPROVED BY:
File name: ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - AP - Electrical . Auxiliary .Emergency Light Layout - Rev 01 - 130216.dwg 090715 E-23

V.03.2
18 17 16 15 14 13 12
DMA NOTE: SHOULD
N O R T H
HAVE ALTERNATIVE This is and shall remain in the property of
Monian Ltd., for which it was commissioned.
PATHS OF EGRESS Unauthorised use of the document in any way is
prohibited. Dimensions shall rule over scale in
case of conflict.

A A Dimensions must be verified at the site before


commencing any work or making any shop
drawings. IF IN DOUBT, CONFIRM WITH
ARCHITECT.

REV. DESCRIPTION DATE

A AS PER 7382 - SKE - 006 211015

B B AS PER 7382-E-SK-01 [P1] 231215

C AS PER DMA 7382-E-SK-02 [P2] 050216

D AS PER DMA 7382-E-SK-03 [P1] 231215

E'

CLIENT

i MONIAN LIMITED

PROJECT NAME:

ELEMENTS WAIGANI
SECTION: S496 LOT: L16
SUBURB/TOWN:
Hohola, Port Moresby
SUPERVISOR:
K K RTD
ARCHITECT / DRAFTSMAN

FN/AP/BH/SL

DRAWING TITLE:

DMA NOTE: RELOCATE FOR


BETTER VIEW FROM DOUBLE DMA NOTE: EXITS TO HOTEL & GAMING BLDG.

DOORS TO HALLWAY LEAD TOWARD EGRESS LEVEL 1


STAIRS ELECTRICAL - AUXILIARY
EMERGENCY LIGHT LAYOUT
HOTEL & GAMING BUILDING
LEVEL 1
DESIGNED BY:

ELECTRICAL - AUXILIARY - EMERGENCY LIGHT LAYOUT


DRAWING SCALE:
1 Job name: ELEMENTS WAIGANI DMA 1:150
SCALE 1:150 M Drawing/sketch title: 7382-E-SK-C1 CHECKED BY: FILE NAME:
E-24 Description: EMERGENCY LIGHTING RTD
APPROVED BY:
ILS
FILENAME: Date: 02/06/16 Pages: 6 Revision: P1 DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - AP - Electrical . Auxiliary .Emergency Light Layout - Rev 01 - 130216.dwg File name: 090715 E-24

V.03.2
18 17 16 15 14 13 12
DMA NOTE: SHOULD N O R T H
HAVE ALTERNATIVE This is and shall remain in the property of
Monian Ltd., for which it was commissioned.
PATHS OF EGRESS Unauthorised use of the document in any way is
prohibited. Dimensions shall rule over scale in
case of conflict.

A Dimensions must be verified at the site before


commencing any work or making any shop
drawings. IF IN DOUBT, CONFIRM WITH
ARCHITECT.

REV. DESCRIPTION DATE

A AS PER 7382 - SKE - 006 211015

B B AS PER 7382-E-SK-01 [P1] 231215

C AS PER DMA 7382-E-SK-02 [P2] 050216

D AS PER DMA 7382-E-SK-03 [P1] 231215

CLIENT

I MONIAN LIMITED

PROJECT NAME:

ELEMENTS WAIGANI
SECTION: S496 LOT: L16
SUBURB/TOWN:
Hohola, Port Moresby
SUPERVISOR:
K K RTD
ARCHITECT / DRAFTSMAN

FN/AP/BH/SL

DRAWING TITLE:
DMA NOTE: RELOCATE FOR
HOTEL & GAMING BLDG.
BETTER VIEW FROM DOUBLE
LEVEL 2
DOORS TO HALLWAY
ELECTRICAL - AUXILIARY
EMERGENCY LIGHT LAYOUT
HOTEL & GAMING BUILDING
LEVEL 2
DESIGNED BY:

ELECTRICAL - AUXILIARY - EMERGENCY LIGHT LAYOUT


DRAWING SCALE:
1 Job name: ELEMENTS WAIGANI DMA 1:150
SCALE 1:150 M Drawing/sketch title: 7382-E-SK-C1 CHECKED BY: FILE NAME:
E-25 Description: EMERGENCY LIGHTING RTD
APPROVED BY:
ILS
FILENAME: Date: 02/06/16 Pages: 6 Revision: P1 DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - AP - Electrical . Auxiliary .Emergency Light Layout - Rev 01 - 130216.dwg File name: 090715 E-25

V.03.2
18 17 16 15 14 13 12
DMA NOTE: SHOULD N O R T H
This is and shall remain in the property of
HAVE ALTERNATIVE Monian Ltd., for which it was commissioned.
Unauthorised use of the document in any way is
PATHS OF EGRESS prohibited. Dimensions shall rule over scale in
case of conflict.

Dimensions must be verified at the site before


commencing any work or making any shop
A drawings. IF IN DOUBT, CONFIRM WITH
ARCHITECT.

REV. DESCRIPTION DATE

A AS PER 7382 - SKE - 006 211015

B B AS PER 7382-E-SK-01 [P1] 231215

C AS PER DMA 7382-E-SK-02 [P2] 050216

D AS PER DMA 7382-E-SK-03 [P1] 231215

CLIENT

i MONIAN LIMITED

PROJECT NAME:

ELEMENTS WAIGANI
SECTION: S496 LOT: L16
SUBURB/TOWN:
Hohola, Port Moresby
SUPERVISOR:

RTD
K ARCHITECT / DRAFTSMAN
FN/AP/BH/SL

DRAWING TITLE:

DMA NOTE: RELOCATE FOR HOTEL & GAMING BLDG.

BETTER VIEW FROM DOUBLE LEVEL 3


DOORS TO HALLWAY ELECTRICAL - AUXILIARY
EMERGENCY LIGHT LAYOUT
HOTEL & GAMING BUILDING
LEVEL 3
DESIGNED BY:

ELECTRICAL - AUXILIARY - EMERGENCY LIGHT LAYOUT


DRAWING SCALE:
1 Job name: ELEMENTS WAIGANI DMA 1:150
Drawing/sketch title: 7382-E-SK-C1 CHECKED BY: FILE NAME:
SCALE 1:150 M
E-26 Description: EMERGENCY LIGHTING RTD
APPROVED BY:
ILS
FILENAME:
Date: 02/06/16 Pages: 6 Revision: P1 DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - AP - Electrical . Auxiliary .Emergency Light Layout - Rev 01 - 130216.dwg File name: 090715 E-26

V.03.2
18 17 16 15 14 13 12
N O R T H
This is and shall remain in the property of
Monian Ltd., for which it was commissioned.
Unauthorised use of the document in any way is
prohibited. Dimensions shall rule over scale in
case of conflict.

A Dimensions must be verified at the site before


commencing any work or making any shop
drawings. IF IN DOUBT, CONFIRM WITH
ARCHITECT.

REV. DESCRIPTION DATE

B A AS PER 7382 - SKE - 006 211015

B AS PER 7382-E-SK-01 [P1] 231215

C AS PER DMA 7382-E-SK-02 [P2] 050216

D AS PER DMA 7382-E-SK-03 [P1] 231215

DB - L4

DB/A - L4 DB/B - L4

i CLIENT

MONIAN LIMITED

PROJECT NAME:

ELEMENTS WAIGANI
SECTION: S496 LOT: L16
SUBURB/TOWN:
Hohola, Port Moresby

K SUPERVISOR:

RTD
ARCHITECT / DRAFTSMAN
FN/AP/BH/SL

DMA NOTE: EXTRA EXIT SIGN DRAWING TITLE:

FOR VIEWING FROM BESIDE


HOTEL & GAMING BLDG.
LIFT WELL
LEVEL 4 - PENTHOUSE
ELECTRICAL - AUXILIARY
EMERGENCY LIGHT LAYOUT
HOTEL & GAMING BUILDING
LEVEL 4
DESIGNED BY:

ELECTRICAL - AUXILIARY - EMERGENCY LIGHT LAYOUT


DRAWING SCALE:
1 Job name: ELEMENTS WAIGANI DMA 1:150
Drawing/sketch title: 7382-E-SK-C1 CHECKED BY: FILE NAME:
SCALE 1:150 M
E-27 Description: EMERGENCY LIGHTING RTD
APPROVED BY:
ILS
FILENAME:
Date: 02/06/16 Pages: 6 Revision: P1 DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - AP - Electrical . Auxiliary .Emergency Light Layout - Rev 01 - 130216.dwg File name: 090715 E-27

V.03.2
18 17 16 15 14 13 12 11
N O R T H
This is and shall remain in the property of
Monian Ltd., for which it was commissioned.
Unauthorised use of the document in any way is
A prohibited. Dimensions shall rule over scale in
case of conflict.

Dimensions must be verified at the site before


commencing any work or making any shop
drawings. IF IN DOUBT, CONFIRM WITH
ARCHITECT.

B REV. DESCRIPTION DATE

A AS PER DMA 7382 - SKE - 006 211015

B AS PER DMA 7382-E-SK-01 [P1] 231215

C AS PER DMA 7382-E-SK-02 [P2] 050216

D AS PER DMA 7382-E-SK-03 [P1] 231215

AS PER DMA ENGINEERS


E EMAIL RECOMMENDATION 110516

F AS PER DMA 7382-E-SK-MASTER [P2] 150416

CLIENT

MONIAN LIMITED

PROJECT NAME:

ELEMENTS WAIGANI
SECTION: S496 LOT: L16

K SUBURB/TOWN:
Hohola, Port Moresby
SUPERVISOR:

RTD
ARCHITECT / DRAFTSMAN
FN/AP/BH/SL

DRAWING TITLE:

HOTEL & GAMING BLDG.


NOTES :
GROUND FLOOR
-Client and security contractor to confirm all locations of
ELECTRICAL - AUXILIARY
security equipment.
AUDIO SYSTEM LAYOUT
HOTEL & GAMING BUILDING
GROUND FLOOR
DESIGNED BY:

ELECTRICAL - AUXILIARY - AUDIO SYSTEM LAYOUT


DRAWING SCALE:
1 DMA 1:150
CHECKED BY: FILE NAME:
SCALE 1:150 M
E-28 RTD
APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - AP - Electrical . Auxiliary .Audio System Layout - Rev 02 - 230216.dwg 090715 E-28

V.03.2
18 17 16 15 14 13 12
N O R T H
This is and shall remain in the property of
Monian Ltd., for which it was commissioned.
Unauthorised use of the document in any way is
prohibited. Dimensions shall rule over scale in
case of conflict.

A A Dimensions must be verified at the site before


commencing any work or making any shop
drawings. IF IN DOUBT, CONFIRM WITH
ARCHITECT.

REV. DESCRIPTION DATE

A AS PER 7382 - SKE - 006 211015

B B AS PER 7382-E-SK-01 [P1] 231215

C AS PER DMA 7382-E-SK-02 [P2] 050216

D AS PER DMA 7382-E-SK-03 [P1] 231215

AS PER DMA ENGINEERS


E EMAIL RECOMMENDATION 110516

F AS PER DMA 7382-E-SK-MASTER [P2] 150416

E'

CLIENT

i MONIAN LIMITED

PROJECT NAME:

ELEMENTS WAIGANI
SECTION: S496 LOT: L16
SUBURB/TOWN:
Hohola, Port Moresby
SUPERVISOR:
K K RTD
ARCHITECT / DRAFTSMAN

FN/AP/BH/SL

DRAWING TITLE:

HOTEL & GAMING BLDG.


NOTES : LEVEL 1
-Client and security contractor to confirm all locations of ELECTRICAL - AUXILIARY
security equipment. AUDIO SYSTEM LAYOUT
HOTEL & GAMING BUILDING
LEVEL1
DESIGNED BY:

ELECTRICAL - AUXILIARY - AUDIO SYSTEM LAYOUT


DRAWING SCALE:
1 DMA 1:150
CHECKED BY: FILE NAME:
SCALE 1:150 M
E-29 RTD
APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - AP - Electrical . Auxiliary .Audio System Layout - Rev 02 - 230216.dwg 090715 E-29

V.03.2
18 17 16 15 14 13 12
N O R T H
This is and shall remain in the property of
Monian Ltd., for which it was commissioned.
Unauthorised use of the document in any way is
prohibited. Dimensions shall rule over scale in
case of conflict.

A Dimensions must be verified at the site before


commencing any work or making any shop
drawings. IF IN DOUBT, CONFIRM WITH
ARCHITECT.

REV. DESCRIPTION DATE

A AS PER 7382 - SKE - 006 211015

B B AS PER 7382-E-SK-01 [P1] 231215

C AS PER DMA 7382-E-SK-02 [P2] 050216

D AS PER DMA 7382-E-SK-03 [P1] 231215

AS PER DMA ENGINEERS


E EMAIL RECOMMENDATION 110516

F AS PER DMA 7382-E-SK-MASTER [P2] 150416

CLIENT

I MONIAN LIMITED

PROJECT NAME:

ELEMENTS WAIGANI
SECTION: S496 LOT: L16
SUBURB/TOWN:
Hohola, Port Moresby
SUPERVISOR:
K K RTD
ARCHITECT / DRAFTSMAN

FN/AP/BH/SL

DRAWING TITLE:
NOTES :
HOTEL & GAMING BLDG.
-Client and security contractor to confirm all locations of
LEVEL 2
security equipment.
ELECTRICAL - AUXILIARY
AUDIO SYSTEM LAYOUT
HOTEL & GAMING BUILDING
LEVEL 2
DESIGNED BY:

ELECTRICAL - AUXILIARY - AUDIO SYSTEM LAYOUT


DRAWING SCALE:
1 DMA 1:150
CHECKED BY: FILE NAME:
SCALE 1:150 M
E-30 RTD
APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - AP - Electrical . Auxiliary .Audio System Layout - Rev 02 - 230216.dwg 090715 E-30

V.03.2
18 17 16 15 14 13 12
N O R T H
This is and shall remain in the property of
Monian Ltd., for which it was commissioned.
Unauthorised use of the document in any way is
prohibited. Dimensions shall rule over scale in
case of conflict.

Dimensions must be verified at the site before


commencing any work or making any shop
A drawings. IF IN DOUBT, CONFIRM WITH
ARCHITECT.

REV. DESCRIPTION DATE

A AS PER 7382 - SKE - 006 211015

B B AS PER 7382-E-SK-01 [P1] 231215

C AS PER DMA 7382-E-SK-02 [P2] 050216

D AS PER DMA 7382-E-SK-03 [P1] 231215

AS PER DMA ENGINEERS


E EMAIL RECOMMENDATION 110516

F AS PER DMA 7382-E-SK-MASTER [P2] 150416

CLIENT

i MONIAN LIMITED

PROJECT NAME:

ELEMENTS WAIGANI
SECTION: S496 LOT: L16
SUBURB/TOWN:
Hohola, Port Moresby
SUPERVISOR:

RTD
K ARCHITECT / DRAFTSMAN
FN/AP/BH/SL

NOTES : DRAWING TITLE:

-Client and security contractor to confirm all locations of HOTEL & GAMING BLDG.
security equipment. LEVEL 3
ELECTRICAL - AUXILIARY
AUDIO SYSTEM LAYOUT
HOTEL & GAMING BUILDING
LEVEL 3
DESIGNED BY:

ELECTRICAL - AUXILIARY - AUDIO SYSTEM LAYOUT


DRAWING SCALE:
1 DMA 1:150
CHECKED BY: FILE NAME:
SCALE 1:150 M
E-31 RTD
APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - AP - Electrical . Auxiliary .Audio System Layout - Rev 02 - 230216.dwg 090715 E-31

V.03.2
18 17 16 15 14 13 12
N O R T H
This is and shall remain in the property of
Monian Ltd., for which it was commissioned.
Unauthorised use of the document in any way is
prohibited. Dimensions shall rule over scale in
case of conflict.

A Dimensions must be verified at the site before


commencing any work or making any shop
drawings. IF IN DOUBT, CONFIRM WITH
ARCHITECT.

REV. DESCRIPTION DATE

B A AS PER 7382 - SKE - 006 211015

B AS PER 7382-E-SK-01 [P1] 231215

C AS PER DMA 7382-E-SK-02 [P2] 050216

D AS PER DMA 7382-E-SK-03 [P1] 231215

AS PER DMA ENGINEERS


E EMAIL RECOMMENDATION 110516

F AS PER DMA 7382-E-SK-MASTER [P2] 150416

i CLIENT

MONIAN LIMITED

PROJECT NAME:

ELEMENTS WAIGANI
SECTION: S496 LOT: L16
SUBURB/TOWN:
Hohola, Port Moresby

K SUPERVISOR:

RTD
ARCHITECT / DRAFTSMAN
NOTES : FN/AP/BH/SL
-Client and security contractor to confirm all locations of
security equipment. DRAWING TITLE:

HOTEL & GAMING BLDG.


LEVEL 4 - PENTHOUSE
ELECTRICAL - AUXILIARY
AUDIO SPEAKERS LAYOUT
HOTEL & GAMING BUILDING
LEVEL 4
DESIGNED BY:

ELECTRICAL - AUXILIARY - AUDIO SYSTEM LAYOUT


DRAWING SCALE:
1 DMA 1:150
CHECKED BY: FILE NAME:
SCALE 1:150 M
E-32 RTD
APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - AP - Electrical . Auxiliary .Audio System Layout - Rev 02 - 230216.dwg 090715 E-32

V.03.2
1 June 2016

This is and shall remain in the property of


Monian Ltd., for which it was commissioned.
Unauthorised use of the document in any way is
11 10 09 08 07 06 05 04 03 02 01 TV06 TV09 TV10 TV11 TV12 TV13 TV14
prohibited. Dimensions shall rule over scale in
20 18 18
54 59 case of conflict.
20
6 7 8 9 10 B13 18
Dimensions must be verified at the site before
20 18
5 11 19 COOLROOM
commencing any work or making any shop
12 13 14 15 16 17 18
B17 17 FREEZER drawings. IF IN DOUBT, CONFIRM WITH
B12
ARCHITECT.
4 12
B8 15

B7 23
14 DRYSTORE REV. DESCRIPTION DATE
TV04 TV05
60 3 B18

TV15
24 25
53 AS PER HILLS
B14 15 A 170216
C01 C02 65 2 B10 DWG00077184 - Elements Waigani
B11
Security Design
B6 B9 10
26 32
1 27 13
12
B19 7
5
30 55 BIN

B1 B2 B3 B4 B5 31 29 7
2
TV03

9 4 7
C03 B15 B16
49 34
36 45
42 43 46 47 48
B20 44
6 GAS BURNERS CHARCOAL GRILL DEEP FRYER

2 3 4 5 6 7 8 9 10 11 12

35

RAS
TV16
TV07

EXTRACTION CANOPY

22

1
01
08 08 10 08 08 10 08 08
13
B21 41
04/03 11 04/03
12 12
D D 38 39 40
13 36
02
C04 05
14

CONDIMENTS
TV17 / TV 18
15

MENU BOARD
01 18 18 17

A B
16

TV27
06
14 18 2 01
D A D A
13 02
M1 I 09 03
SAFE
C D B
6 E B

IM
04
12 15 05
F
C1 C
14 06
13 07
11 D 12 08
A 11 09

TV26
SAFE
1 2 3 10 10
I

10
TV02

A B B

C2
19 23 S1 7
A
1 B

09 24 27
A 3 B C D A
TV08

11
B
08
R1

TV25
A B
07
A 4 B

8
A
06 48 12
R2
D C D B

05 CLIENT
A 5 B

I
28
19 01
R3
TV01

33 18
17
02
03
SAFE
SAFE
MONIAN LIMITED
04 16 04 S1 S2 S3
RAS
15 05

EM

EM
14 PTE
06 PTE
03 37 39 13 07
12 08 PROJECT NAME:

MON
11 09 M2
02 10
S4 ELEMENTS WAIGANI SOUTH
S5 S6
01
34 36 SAFE
I
MON SECTION: S496 LOT: L16
SUBURB/TOWN:
Hohola, Port Moresby
SUPERVISOR:

RTD
CCTV

SAP ARCHITECT / DRAFTSMAN

BH

DRAWING TITLE:

GAMING & HOTEL BUILDING


NOTES :
GROUND FLOOR
-Client and security contractor to confirm all locations of
ELECTRICAL - AUXILIARY
security equipment.
SECURITY DESIGN LAYOUT

HOTEL & GAMING BUILDING


GROUND FLOOR DESIGNED BY: DRAWING SCALE:

1 ELECTRICAL - AUXILIARY - SECURITY DESIGN LAYOUT FN


CHECKED BY: FILE NAME:
1:150

SCALE 1:150 M RTD


E-33
APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Waigani Elements South - S496L16 - Ap - Electrical .Security Design Layout - Rev 01 - 130516.dwg 090715 E-33

H:\WEEKLY DRAWINGS\ELEMENTS WAIGANI SOUTH (S496L16 Hohola NCD)\DRAWINGS\ELECTRICAL V.03.1


1 June 2016

This is and shall remain in the property of


Monian Ltd., for which it was commissioned.
Unauthorised use of the document in any way is
11 10 09 08 07 06 05 04 03 02 01
prohibited. Dimensions shall rule over scale in
case of conflict.

Dimensions must be verified at the site before


12 13 14 15 16 17 18 commencing any work or making any shop
drawings. IF IN DOUBT, CONFIRM WITH
ARCHITECT.

REV. DESCRIPTION DATE


AS PER HILLS
A DWG00077184 - Elements Waigani
170216

Security Design

CABINET

FRIDGE

FRIDGE

FRIDGE

FRIDGE

FRIDGE

FRIDGE

FRIDGE
FRIDGE

CABINET

CABINET

CABINET

CABINET

CABINET

CABINET

CABINET

CABINET
FRIDGE

20

19

18

17 01

16 02
15 03

14 04
13 05

12 06
11 07

08

CABINET
FRIDGE

CABINET RAS
FRIDGE

CLIENT
20
19 01
18 02
17 03 MONIAN LIMITED
16 04
15 05
14 06
13 07
12 08
PROJECT NAME:

MON
11 09
10
ELEMENTS WAIGANI SOUTH
FRIDGE
CABINET MON SECTION: S496 LOT: L16
SUBURB/TOWN:
Hohola, Port Moresby
SUPERVISOR:

RTD
ARCHITECT / DRAFTSMAN

BH

DRAWING TITLE:
NOTES :
GAMING & HOTEL BUILDING
-Client and security contractor to confirm all locations of
security equipment. LEVEL 1
ELECTRICAL - AUXILIARY
SECURITY DESIGN LAYOUT

HOTEL & GAMING BUILDING


LEVEL 1 DESIGNED BY: DRAWING SCALE:

1 ELECTRICAL - AUXILIARY - SECURITY DESIGN LAYOUT FN


CHECKED BY: FILE NAME:
1:150

SCALE 1:150 M RTD


E-34
APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Waigani Elements South - S496L16 - Ap - Electrical .Security Design Layout - Rev 01 - 130516.dwg 090715 E-34

H:\WEEKLY DRAWINGS\ELEMENTS WAIGANI SOUTH (S496L16 Hohola NCD)\DRAWINGS\ELECTRICAL V.03.1


1 June 2016

This is and shall remain in the property of


Monian Ltd., for which it was commissioned.
Unauthorised use of the document in any way is
prohibited. Dimensions shall rule over scale in
case of conflict.

Dimensions must be verified at the site before


commencing any work or making any shop
drawings. IF IN DOUBT, CONFIRM WITH
11 10 09 08 07 06 05 04 03 02 01
ARCHITECT.

REV. DESCRIPTION DATE


12 13 14 15 16 17 18
AS PER HILLS
A DWG00077184 - Elements Waigani
170216

Security Design

CABINET

FRIDGE

FRIDGE

FRIDGE

FRIDGE

FRIDGE

FRIDGE

FRIDGE
FRIDGE

CABINET

CABINET

CABINET

CABINET

CABINET

CABINET

CABINET

CABINET
FRIDGE

16
15 01

14 02

CABINET

CABINET

CABINET

CABINET
13 03

12 04
11 05

FRIDGE

FRIDGE

FRIDGE

FRIDGE
10 06

09 07

08

CABINET
FRIDGE

CABINET
FRIDGE

CLIENT

MONIAN LIMITED
CABINET
FRIDGE
CABINET

PROJECT NAME:
FRIDGE

01
16
15
02
03 ELEMENTS WAIGANI SOUTH
14 04
13 05
SECTION: S496 LOT: L16
12 06 SUBURB/TOWN:
11
10
07
08
Hohola, Port Moresby
09
SUPERVISOR:

FRIDGE
CABINET
RTD
ARCHITECT / DRAFTSMAN

BH

DRAWING TITLE:

GAMING & HOTEL BUILDING


LEVEL 2
NOTES :
ELECTRICAL - AUXILIARY
-Client and security contractor to confirm all locations of
SECURITY DESIGN LAYOUT
security equipment.
HOTEL & GAMING BUILDING
LEVEL 2 DESIGNED BY: DRAWING SCALE:

1 ELECTRICAL - AUXILIARY - SECURITY DESIGN LAYOUT FN


CHECKED BY: FILE NAME:
1:150

SCALE 1:150 M RTD


E-35
APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Waigani Elements South - S496L16 - Ap - Electrical .Security Design Layout - Rev 01 - 130516.dwg 090715 E-35

H:\WEEKLY DRAWINGS\ELEMENTS WAIGANI SOUTH (S496L16 Hohola NCD)\DRAWINGS\ELECTRICAL V.03.1


1 June 2016

This is and shall remain in the property of


Monian Ltd., for which it was commissioned.
Unauthorised use of the document in any way is
prohibited. Dimensions shall rule over scale in
case of conflict.

Dimensions must be verified at the site before


commencing any work or making any shop
drawings. IF IN DOUBT, CONFIRM WITH
11 10 09 08 07 06 05 04 03 02 01 ARCHITECT.

REV. DESCRIPTION DATE


12 13 14 15 16 17 18
AS PER HILLS
A DWG00077184 - Elements Waigani
170216

Security Design

CABINET
FRIDGE

FRIDGE

FRIDGE

FRIDGE

FRIDGE

FRIDGE

FRIDGE

FRIDGE
CABINET

CABINET

CABINET

CABINET

CABINET

CABINET

CABINET

CABINET
FRIDGE

16
15 01

14 02

CABINET

CABINET

CABINET

CABINET
13 03

12 04
11 05

FRIDGE

FRIDGE

FRIDGE

FRIDGE
10 06

09 07

08

CABINET
FRIDGE

CABINET
FRIDGE

CLIENT

MONIAN LIMITED
CABINET
FRIDGE
CABINET
FRIDGE

01 PROJECT NAME:
16 02
15 03 ELEMENTS WAIGANI SOUTH
14 04
13 05 SECTION: S496 LOT: L16
12 06
11 07
SUBURB/TOWN:
10 08
Hohola, Port Moresby
09
SUPERVISOR:

FRIDGE
CABINET
RTD
ARCHITECT / DRAFTSMAN

BH

NOTES : DRAWING TITLE:

-Client and security contractor to confirm all locations of GAMING & HOTEL BUILDING
security equipment. LEVEL 3
ELECTRICAL - AUXILIARY
SECURITY DESIGN LAYOUT

HOTEL & GAMING BUILDING


LEVEL 3 DESIGNED BY: DRAWING SCALE:

1 ELECTRICAL - AUXILIARY - SECURITY DESIGN LAYOUT FN


CHECKED BY: FILE NAME:
1:150

SCALE 1:150 M RTD


E-36
APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Waigani Elements South - S496L16 - Ap - Electrical .Security Design Layout - Rev 01 - 130516.dwg 090715 E-36

H:\WEEKLY DRAWINGS\ELEMENTS WAIGANI SOUTH (S496L16 Hohola NCD)\DRAWINGS\ELECTRICAL V.03.1


1 June 2016

This is and shall remain in the property of


Monian Ltd., for which it was commissioned.
Unauthorised use of the document in any way is
prohibited. Dimensions shall rule over scale in
case of conflict.

Dimensions must be verified at the site before


commencing any work or making any shop
drawings. IF IN DOUBT, CONFIRM WITH
ARCHITECT.

REV. DESCRIPTION DATE


AS PER HILLS
A DWG00077184 - Elements Waigani
170216

Security Design

REF

CABINET

CABINET
CABINET
CLIENT

MONIAN LIMITED
CABINET

CABINET

16 02
PROJECT NAME:
15 03
14 04 ELEMENTS WAIGANI SOUTH
13 05
12 06 SECTION: S496 LOT: L16
11 07
SUBURB/TOWN:
10 08
09
Hohola, Port Moresby
SUPERVISOR:

RTD
ARCHITECT / DRAFTSMAN

BH

NOTES : DRAWING TITLE:

-Client and security contractor to confirm all locations of GAMING & HOTEL BUILDING
security equipment. LEVEL 4
ELECTRICAL - AUXILIARY
SECURITY DESIGN LAYOUT

HOTEL & GAMING BUILDING


LEVEL 4 DESIGNED BY: DRAWING SCALE:

1 ELECTRICAL - AUXILIARY - SECURITY DESIGN LAYOUT FN


CHECKED BY: FILE NAME:
1:150

SCALE 1:150 M RTD


E-37
APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Waigani Elements South - S496L16 - Ap - Electrical .Security Design Layout - Rev 01 - 130516.dwg 090715 E-37

H:\WEEKLY DRAWINGS\ELEMENTS WAIGANI SOUTH (S496L16 Hohola NCD)\DRAWINGS\ELECTRICAL V.03.1


1 June 2016
LEVEL 4
C NOTES :
This is and shall remain in the property of
-Client and security contractor to confirm all locations of Monian Ltd., for which it was commissioned.
Unauthorised use of the document in any way is
7x INTERNAL DOMES security equipment. prohibited. Dimensions shall rule over scale in
case of conflict.

Dimensions must be verified at the site before


commencing any work or making any shop
C drawings. IF IN DOUBT, CONFIRM WITH
ARCHITECT.

1x EXTERNAL DOME REV. DESCRIPTION DATE


AS PER HILLS
A DWG00077184 - Elements Waigani
170216
C C
Security Design

LEVEL 3 C

C JUNIPER 24 PORT SWITCH


240 V CABLE LEGEND :

7x INTERNAL DOMES A
240 V COAXIAL CABLE
UPS B
0.20 STRANDED CABLE
C C
D CAT - 5/6 4PR DATA CABLE
D
FIBER OPTIC CABLE
1x EXTERNAL DOME E
4 - CORE SECURITY CABLE
F
RS485 LAN CABLE
G
LEVEL 2 WIEGAND CABLE
H
6 - CORE SECURITY CABLE
C

7x INTERNAL DOMES

C C

1x EXTERNAL DOME C
CLIENT
C C
MON MON
LEVEL 1 C
MONIAN LIMITED
C
C

C JUNIPER 24 PORT SWITCH C PROJECT NAME:


240 V
PC PC
D ELEMENTS WAIGANI SOUTH
7x INTERNAL DOMES D
SECTION: S496 LOT: L16
240 V SUBURB/TOWN:
DIRECTOR'S GENERAL MANAGER'S Hohola, Port Moresby
UPS
OFFICE OFFICE
SUPERVISOR:
C
C C RTD
ARCHITECT / DRAFTSMAN
1x EXTERNAL DOME C C
BH
C
C C
C C DRAWING TITLE:

GROUND FLOOR C
D MON MON MON
GAMING & HOTEL BUILDING
JUNIPER 24 PORT SWITCH

C C 240 V C C ELECTRICAL - AUXILIARY


C
PC PC PC
SECURITY DESIGN LAYOUT
22x INTERNAL DOMES EXACQVISION Z-SERIES
240 V

240 V ADMIN. DUTY MANAGER'S GAMING MANAGER'S


C 240 V OFFICE OFFICE OFFICE DESIGNED BY: DRAWING SCALE:
UPS FN NTS
CHECKED BY: FILE NAME:
4x EXTERNAL DOME RTD
UPS ADDITIONAL BATTERY CAB APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Waigani Elements South - S496L16 - Ap - Electrical .Security Design Layout - Rev 01 - 130516.dwg 090715 E-38

H:\WEEKLY DRAWINGS\ELEMENTS WAIGANI SOUTH (S496L16 Hohola NCD)\DRAWINGS\ELECTRICAL V.03.1


1 June 2016

POTABLE COLD WATER SUPPLY

HOT WATER SUPPLY This is and shall remain in the property of


Monian Ltd., for which it was commissioned.
Unauthorised use of the document in any way is
TEMPERED WATER SUPPLY prohibited. Dimensions shall rule over scale in
case of conflict.

STOP COCK Dimensions must be verified at the site before


commencing any work or making any shop
drawings. IF IN DOUBT, CONFIRM WITH
NON RETURN VALVE ARCHITECT.

PRESSURE LIMITING VALVE (IF REQUIRED)


REV. DESCRIPTION DATE

EXPANSION CONTROL VALVE 1 AS PER DMA ENGINEERS 161115

2 AS PER DMA ENGINEERS 200416


GATE VALVE OR BALL VALVE

CIRCULATOR

UNION

TUNDISH

DIRECTION OF FLOW

M WATER METER

SEWER OR WATER LINE UNDER ROAD


WITH CONCRETE ENCASEMENT.

NON RETURN VALVE

THRUST BLOCK

END CAP

JUP JUMP UP CONNECTION

CLIENT

MONIAN LIMITED

PROJECT NAME:

ELEMENTS WAIGANI
SECTION: S496 LOT: L16
SUBURB/TOWN:
Holola, Port Moresby
SUPERVISOR:

RTD
ARCHITECT / DRAFTSMAN
JAn/Ap/FN

DRAWING TITLE:

PLUMBING
LEGENDS
GROUND FLOOR
HOTEL & GAMING BUILDING

DESIGNED BY: DRAWING SCALE:

FN 1:150
CHECKED BY: FILE NAME:
RTD
APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - Ap - Plumbing .Waterline Layout - Rev 03 - 270516.dwg 27-May-16 P-00

H:\WEEKLY DRAWINGS\ELEMENTS WAIGANI SOUTH (S496L16 Hohola NCD)\DRAWINGS\PLUMBING V.03


1 June 2016
18 17 16 15 14 13 11
N O R T H
This is and shall remain in the property of
Monian Ltd., for which it was commissioned.
Unauthorised use of the document in any way is
prohibited. Dimensions shall rule over scale in
case of conflict.

A Dimensions must be verified at the site before


commencing any work or making any shop
drawings. IF IN DOUBT, CONFIRM WITH
ARCHITECT.

B REV. DESCRIPTION DATE

1 AS PER DMA ENGINEERS 161115

2 AS PER DMA ENGINEERS 200416

POSSIBLE LOCATION FOR


HOT WATER PLANT AND 3 AS PER DMA 7382-E-SK-MASTER [P2] 150416
WATER SOFTENERS CWR
01
inwall

INCOMING WATER
SUPPLY FROM THE MAIN
BUILDING WATER TANK

K CLIENT

SUBMERSIBLE PUMP
WITH IN BREAK TANK. MONIAN LIMITED
REQUIRE 4.0L/S AT POTABLE WATER
46m HEAD BREAK TANK
UNDERGROUND 3.3m
W x 4.2m L x 3m H
M PROJECT NAME:

ELEMENTS WAIGANI
SECTION: S496 LOT: L16
SUBURB/TOWN:
Holola, Port Moresby
SUPERVISOR:

RTD
ARCHITECT / DRAFTSMAN
JAn/Ap/FN/SL

DRAWING TITLE:

PLUMBING
WATERLINE LAYOUT
GROUND FLOOR
HOTEL & GAMING BUILDING
HOTEL & GAMING BUILDING
GROUND FLOOR
DESIGNED BY: DRAWING SCALE:

1 PLUMBING- WATERLINE LAYOUT FN


CHECKED BY: FILE NAME:
1:150

SCALE 1:150 M
M P-01 RTD
APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - Ap - Plumbing .Waterline Layout - Rev 03 - 270516.dwg 27-May-16 P-01

H:\WEEKLY DRAWINGS\ELEMENTS WAIGANI SOUTH (S496L16 Hohola NCD)\DRAWINGS\PLUMBING V.03


1 June 2016

18 17 16 15 14 13 12
N O R T H
This is and shall remain in the property of
Monian Ltd., for which it was commissioned.
Unauthorised use of the document in any way is
A DS DS DS DS
DS
prohibited. Dimensions shall rule over scale in
case of conflict.

Dimensions must be verified at the site before


commencing any work or making any shop
drawings. IF IN DOUBT, CONFIRM WITH
ARCHITECT.

B REV. DESCRIPTION

AS PER DMA ENGINEERS


DATE

161115
1

2 AS PER DMA ENGINEERS 200416

3 AS PER DMA 7382-E-SK-MASTER [P2] 150416

7382-H-SK-01 (Preliminary)
4 010116
DS Roof - Gutter Sizes

E'

CLIENT

MONIAN LIMITED

PROJECT NAME:

ELEMENTS WAIGANI
SECTION: S496 LOT: L16
SUBURB/TOWN:

K Holola, Port Moresby


SUPERVISOR:

RTD
ARCHITECT / DRAFTSMAN

M JAn/AP/FN

DRAWING TITLE:
DS DS

PLUMBING
WATERLINE LAYOUT

HOTEL & GAMING BUILDING LEVEL 1

LEVEL 1 HOTEL & GAMING BUILDING

1 PLUMBING- WATERLINE LAYOUT


SCALE 1:150 M DESIGNED BY: DRAWING SCALE:
P-02 FN 1:150
CHECKED BY: FILE NAME:
RTD
APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - Ap - Plumbing .Waterline Layout - Rev 03 - 270516.dwg 27-May-16 P-02

H:\WEEKLY DRAWINGS\ELEMENTS WAIGANI SOUTH (S496L16 Hohola NCD)\DRAWINGS\PLUMBING V.03


1 June 2016
18 17 16 15 14 13
N O R T H
A This is and shall remain in the property of
Monian Ltd., for which it was commissioned.
Unauthorised use of the document in any way is
prohibited. Dimensions shall rule over scale in
case of conflict.

Dimensions must be verified at the site before


commencing any work or making any shop
drawings. IF IN DOUBT, CONFIRM WITH

B ARCHITECT.

REV. DESCRIPTION DATE

1 AS PER DMA ENGINEERS 171115

2 AS PER DMA ENGINEERS 200416

3 AS PER DMA 7382-E-SK-MASTER [P2] 150416

CLIENT

MONIAN LIMITED

PROJECT NAME:
DS DS DS
ELEMENTS WAIGANI
K SECTION: S496 LOT: L16
SUBURB/TOWN:
Holola, Port Moresby
SUPERVISOR:

RTD
ARCHITECT / DRAFTSMAN
JAn/AP/FN

DRAWING TITLE:

PLUMBING
WATERLINE LAYOUT

HOTEL & GAMING BUILDING LEVEL 2

LEVEL 2 HOTEL & GAMING BUILDING

1 PLUMBING- WATERLINE LAYOUT


SCALE 1:150 M DESIGNED BY: DRAWING SCALE:
P-03 FN 1:150
CHECKED BY: FILE NAME:
RTD
APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - Ap - Plumbing .Waterline Layout - Rev 03 - 270516.dwg 27-May-16 P-03

H:\WEEKLY DRAWINGS\ELEMENTS WAIGANI SOUTH (S496L16 Hohola NCD)\DRAWINGS\PLUMBING V.03


1 June 2016
18 17 16 15 14 13
N O R T H
A This is and shall remain in the property of
Monian Ltd., for which it was commissioned.
Unauthorised use of the document in any way is
prohibited. Dimensions shall rule over scale in
case of conflict.

Dimensions must be verified at the site before


commencing any work or making any shop
drawings. IF IN DOUBT, CONFIRM WITH

B ARCHITECT.

REV. DESCRIPTION DATE

1 AS PER DMA ENGINEERS 171115

2 AS PER DMA ENGINEERS 200416

3 AS PER DMA 7382-E-SK-MASTER [P2] 150416

CLIENT

MONIAN LIMITED

PROJECT NAME:

ELEMENTS WAIGANI
K SECTION: S496 LOT: L16
SUBURB/TOWN:
Holola, Port Moresby
SUPERVISOR:

RTD
ARCHITECT / DRAFTSMAN
JAn/AP/FN

DRAWING TITLE:

PLUMBING
WATERLINE LAYOUT

HOTEL & GAMING BUILDING LEVEL 3

ROOF LEVEL
1 PLUMBING- WATERLINE LAYOUT
SCALE 1:150 M DESIGNED BY: DRAWING SCALE:
P-04 FN 1:150
CHECKED BY: FILE NAME:
RTD
APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - Ap - Plumbing .Waterline Layout - Rev 03 - 270516.dwg 27-May-16 P-04

H:\WEEKLY DRAWINGS\ELEMENTS WAIGANI SOUTH (S496L16 Hohola NCD)\DRAWINGS\PLUMBING V.03


1 June 2016
18 17 16 15 14 13
N O R T H
This is and shall remain in the property of
Monian Ltd., for which it was commissioned.
Unauthorised use of the document in any way is
prohibited. Dimensions shall rule over scale in
case of conflict.

A Dimensions must be verified at the site before


commencing any work or making any shop
drawings. IF IN DOUBT, CONFIRM WITH
ARCHITECT.

REV. DESCRIPTION DATE

B DS
1 AS PER DMA ENGINEERS

AS PER DMA ENGINEERS


171115

200416
2

3 AS PER DMA 7382-E-SK-MASTER [P2] 150416

D DS

E'

G DS

CLIENT

MONIAN LIMITED

PROJECT NAME:

ELEMENTS WAIGANI
SECTION: S496 LOT: L16
SUBURB/TOWN:
Holola, Port Moresby
DS

K SUPERVISOR:

RTD
ARCHITECT / DRAFTSMAN
JAn/AP/FN

DRAWING TITLE:

PLUMBING
WATERLINE LAYOUT

HOTEL & GAMING BUILDING LEVEL 4

LEVEL 4 HOTEL AND GAMING LAYOUT

1 PLUMBING- WATERLINE LAYOUT


SCALE 1:150 M DESIGNED BY: DRAWING SCALE:
P-05 FN 1:150
CHECKED BY: FILE NAME:
RTD
APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - Ap - Plumbing .Waterline Layout - Rev 03 - 270516.dwg 27-May-16 P-05

H:\WEEKLY DRAWINGS\ELEMENTS WAIGANI SOUTH (S496L16 Hohola NCD)\DRAWINGS\PLUMBING V.03


1 June 2016

18 17 16 15 14 13

N O R T H This is and shall remain in the property of


Monian Ltd., for which it was commissioned.
Unauthorised use of the document in any way is
prohibited. Dimensions shall rule over scale in
case of conflict.

A DS Dimensions must be verified at the site before


commencing any work or making any shop
drawings. IF IN DOUBT, CONFIRM WITH
ARCHITECT.

DS DS DS
REV. DESCRIPTION DATE
DS DS DS DS
B DS
DS
1 AS PER DMA ENGINEERS

AS PER DMA ENGINEERS


171115

200416
2

3 AS PER DMA 7382-E-SK-MASTER [P2] 150416

7382-H-SK-01 (Preliminary)
4 010116
Roof - Gutter Sizes

D DS

DS

DS

E'

G DS
WT 1

CLIENT
DS
WT 2
MONIAN LIMITED

PROJECT NAME:

WT 3 ELEMENTS WAIGANI
SECTION: S496 LOT: L16
SUBURB/TOWN:
Holola, Port Moresby
DS

K SUPERVISOR:

RTD
ARCHITECT / DRAFTSMAN
JAn/Ap/FN/SL

DRAWING TITLE:

HOTEL & GAMING BUILDING


PLUMBING
WATERLINE LAYOUT
NOTES: ROOF LEVEL
HOTEL & GAMING BUILDING
ROOF LEVEL
1 PLUMBING- WATERLINE LAYOUT DESIGNED BY:

FN
DRAWING SCALE:
1:150
SCALE 1:150 M FILE NAME:
P-06 CHECKED BY:
RTD
APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - Ap - Plumbing .Waterline Layout - Rev 03 - 270516.dwg 27-May-16 P-06

H:\WEEKLY DRAWINGS\ELEMENTS WAIGANI SOUTH (S496L16 Hohola NCD)\DRAWINGS\PLUMBING V.03


1 June 2016
18 17 16 15 14 13 11
N O R T H
This is and shall remain in the property of
Monian Ltd., for which it was commissioned.

A Unauthorised use of the document in any way is


prohibited. Dimensions shall rule over scale in
case of conflict.

Dimensions must be verified at the site before


commencing any work or making any shop
drawings. IF IN DOUBT, CONFIRM WITH
BT ARCHITECT.
BT BT

B REV. DESCRIPTION DATE

1 Hyd Drainage Drawings Rev 1 111115

BT

DW
BT

COS COS COS


EPR3 100

D COS

GIT
BT EPR11 100
BT BT
COS TWVP 100
COS
COS
EPR8 100
COS
EPR5 100 EPR7 100

TWVP 100 BT

EPR2 100

EPR4 100

B
CLIENT
COS
COS
UR
B
MONIAN LIMITED
B B
UR
B

PROJECT NAME:
UR
COS COS ELEMENTS WAIGANI
WC WC WC
EPR1 100 SECTION: S496 LOT: L16
WC COS COS COS
K COS COS
SUBURB/TOWN:
Holola, Port Moresby
SUPERVISOR:

COS
RTD
ARCHITECT / DRAFTSMAN

COS COS
JAn/SL/AP

DRAWING TITLE:

M PLUMBING
COS SANITARY LAYOUT
COS
GROUND FLOOR
HOTEL & GAMING BUILDING HOTEL & GAMING BUILDING
GROUND FLOOR
1 PLUMBING- SANITARY LAYOUT DESIGNED BY: DRAWING SCALE:
SCALE 1:150 M AS SHOWN
P-07 FILE NAME:
CHECKED BY:
RTD
APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - SL - Plumbing.Sanitary Layout - Rev 01 - 210416.dwg 21-Apr-16 P-07

H:\WEEKLY DRAWINGS\ELEMENTS WAIGANI SOUTH (S496L16 Hohola NCD)\DRAWINGS\PLUMBING V.03


1 June 2016
18 17 16 15 14 13 12
N O R T H
This is and shall remain in the property of
Monian Ltd., for which it was commissioned.
DS Unauthorised use of the document in any way is
A DS DS DS DS
prohibited. Dimensions shall rule over scale in
case of conflict.

Dimensions must be verified at the site before


commencing any work or making any shop
drawings. IF IN DOUBT, CONFIRM WITH
ARCHITECT.
ST3 100

B COS
WC REV. DESCRIPTION

Hyd Drainage Drawings Rev 1


DATE

111115
1
B
SHR FWG

DS
EPR 100
SHR SHR SHR SHR SHR SHR SHR

COS COS COS COS COS COS


D WC FWG
FWG
WC WC
FWG FWG
WC WC
FWG FWG
WC WC
FWG
COS
B B B B B B B

ST6 100 EPR 9 100 EPR 9 100 EPR 12 100


B
SHR FWG
ST 10 100 ST 10 100 ST 13 100
ST2 100 EPR7 100 EPR8 100 EPR11 100
WC EPR5 100
COS

E' COS
TWVP 100 WC
WC WC COS
WC
COS
SHR FWG FWG COS
B UR
B
FWG
FWG
UP 7 50
B
B

G EPR2 100

ST4 100

B
SHR FWG
ST1 100 CLIENT
WC
COS

COS
MONIAN LIMITED
WC

SHR FWG
B PROJECT NAME:

ELEMENTS WAIGANI
SECTION: S496 LOT: L16
SUBURB/TOWN:

K EPR1 100
Holola, Port Moresby
SUPERVISOR:

RTD
ARCHITECT / DRAFTSMAN

JAn
M
DRAWING TITLE:
DS DS

PLUMBING
SANITARY LAYOUT
LEVEL 1
HOTEL & GAMING BUILDING
HOTEL & GAMING BUILDING
LEVEL 1
1 PLUMBING- SANITARY LAYOUT DESIGNED BY: DRAWING SCALE:
SCALE 1:150 M
P-08 AS SHOWN
CHECKED BY: FILE NAME:
RTD
APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - SL - Plumbing.Sanitary Layout - Rev 01 - 210416.dwg 21-Apr-16 P-08

H:\WEEKLY DRAWINGS\ELEMENTS WAIGANI SOUTH (S496L16 Hohola NCD)\DRAWINGS\PLUMBING V.03


1 June 2016
18 17 16 15 14 13
N O R T H
A This is and shall remain in the property of
Monian Ltd., for which it was commissioned.
Unauthorised use of the document in any way is
prohibited. Dimensions shall rule over scale in
case of conflict.

Dimensions must be verified at the site before


ST3 100
commencing any work or making any shop
drawings. IF IN DOUBT, CONFIRM WITH

B COS
WC ARCHITECT.

B REV. DESCRIPTION DATE


SHR FWG
1 Hyd Drainage Drawings Rev 1 141115

SHR SHR SHR SHR SHR SHR SHR

COS COS COS COS COS COS COS


D WC FWG FWG
WC
FWG FWG
WC
FWG FWG
WC
FWG
WC WC WC TWVP 100
B B B B B B B

ST6 100 ST10 100 ST13 100


ST5 100
B
SHR FWG EPR12 100
TWP 100 EPR9 100
WC ST12 100
COS ST2 100 ST9 100
VP7 50

COS B B B B
WC
RISES IN WALL. WC WC
FWG FWG FWG FWG FWG
SHR PROVIDE AAV IN WC WC
B COS COS COS COS
CEILING SPACE

SHR SHR SHR SHR


FWG
VP7 50
B COS

G COS

SHR
WC
COS
WC WC
FWG
FWG
B
B SHR
B
SHR FWG

WC
COS ST1 100
ST4 100
CLIENT
COS
WC

SHR FWG MONIAN LIMITED


B

PROJECT NAME:
DS DS DS
ELEMENTS WAIGANI
K SECTION: S496 LOT: L16
SUBURB/TOWN:
Holola, Port Moresby
SUPERVISOR:

RTD
ARCHITECT / DRAFTSMAN

JAn

DRAWING TITLE:

PLUMBING
SANITARY LAYOUT
HOTEL & GAMING BUILDING
LEVEL 2
LEVEL 2
HOTEL & GAMING BUILDING
1 PLUMBING- SANITARY LAYOUT
SCALE 1:150 M
P-09 DESIGNED BY: DRAWING SCALE:
AS SHOWN
CHECKED BY: FILE NAME:
RTD
APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - SL - Plumbing.Sanitary Layout - Rev 01 - 210416.dwg 21-Apr-16 P-09

H:\WEEKLY DRAWINGS\ELEMENTS WAIGANI SOUTH (S496L16 Hohola NCD)\DRAWINGS\PLUMBING V.03


1 June 2016
18 17 16 15 14 13
N O R T H
A This is and shall remain in the property of
Monian Ltd., for which it was commissioned.
DP Unauthorised use of the document in any way is
prohibited. Dimensions shall rule over scale in
case of conflict.

Dimensions must be verified at the site before


ST3 100
commencing any work or making any shop
drawings. IF IN DOUBT, CONFIRM WITH

B COS
WC ARCHITECT.

B REV. DESCRIPTION DATE


SHR FWG
1 Hyd Drainage Drawings Rev 1 141115

SHR SHR SHR SHR SHR SHR SHR

COS COS COS COS COS COS COS


D WC FWG
FWG
WC WC
FWG FWG
WC WC
FWG FWG
WC WC
FWG
DP
B B B B B B B

ST6 100 TWVP 100 TWVP 100


B
SHR FWG
ST 5 100 ST 10 100 ST13 100
WC
COS ST2 100 ST9 100 ST12 100
VP7 50

COS B B B B
WC
RISES IN WALL. FWG FWG FWG FWG
SHR FWG PROVIDE AAV IN WC WC
WC WC
B COS COS COS COS
CEILING SPACE
SHR SHR SHR SHR
FWG

B COS

G COS

SHR
WC
COS
DP WC WC
FWG
FWG
B
B SHR
B
SHR FWG

WC
COS ST1 100
ST4 100
CLIENT
COS
WC

SHR FWG MONIAN LIMITED


B

PROJECT NAME:

ELEMENTS WAIGANI
K SECTION: S496 LOT: L16
DP SUBURB/TOWN:
Holola, Port Moresby
SUPERVISOR:

RTD
ARCHITECT / DRAFTSMAN

JAn

DRAWING TITLE:

PLUMBING
SANITARY LAYOUT
HOTEL & GAMING BUILDING LEVEL 3
LEVEL 3 HOTEL & GAMING BUILDING
1 PLUMBING- SANITARY LAYOUT
SCALE 1:150 M
P-10 DESIGNED BY: DRAWING SCALE:
AS SHOWN
CHECKED BY: FILE NAME:
RTD
APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - SL - Plumbing.Sanitary Layout - Rev 01 - 210416.dwg 21-Apr-16 P-10

H:\WEEKLY DRAWINGS\ELEMENTS WAIGANI SOUTH (S496L16 Hohola NCD)\DRAWINGS\PLUMBING V.03


1 June 2016
18 17 16 15 14 13
N O R T H
This is and shall remain in the property of
Monian Ltd., for which it was commissioned.
Unauthorised use of the document in any way is
prohibited. Dimensions shall rule over scale in
case of conflict.

A Dimensions must be verified at the site before


commencing any work or making any shop
drawings. IF IN DOUBT, CONFIRM WITH
ARCHITECT.

VP3
REV. DESCRIPTION DATE
VP6 100
ST3 100
B DS
1 Hyd Drainage Drawings Rev 1

7382-H-SK-01 (Preliminary)
141115

SHR FWG SK 2 Roof - Gutter Sizes


010116

WC B
COS

SK

LT LT
SHR SHR

D DS
B ST10 100
WC
FWG
COS COS
WC
FWG
FWG
WC
B B
COS VP9 100
WC ST5 100
VP10 50 TWVP 100
ST6 100
ST13 100
TWVP 100
VP7 50
VP9 100

E' B B
ST12 100
FWG FWG
VP2 100 VP7 50 SHR SHR
ST2 100
COS WC WC COS

G DS
SHR
COS
B
SHR WC
COS FWG

B WC
FWG CLIENT
VP 50

ST4 100
MONIAN LIMITED

VP1 100 PROJECT NAME:


ST1 100
ELEMENTS WAIGANI
SECTION: S496 LOT: L16
SUBURB/TOWN:
Holola, Port Moresby
DS

K SUPERVISOR:

RTD
ARCHITECT / DRAFTSMAN

JAn

DRAWING TITLE:

PLUMBING
HOTEL & GAMING BUILDING
SANITARY LAYOUT
LEVEL 4
LEVEL 4
1 PLUMBING- SANITARY LAYOUT HOTEL AND GAMING BUILDING
SCALE 1:150 M
P-11
DESIGNED BY: DRAWING SCALE:
AS SHOWN
CHECKED BY: FILE NAME:
RTD
APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - SL - Plumbing.Sanitary Layout - Rev 01 - 210416.dwg 21-Apr-16 P-11

H:\WEEKLY DRAWINGS\ELEMENTS WAIGANI SOUTH (S496L16 Hohola NCD)\DRAWINGS\PLUMBING V.03


1 June 2016
18 17 16 15 14 13
N O R T H
This is and shall remain in the property of
Monian Ltd., for which it was commissioned.
Unauthorised use of the document in any way is
prohibited. Dimensions shall rule over scale in
case of conflict.

A DS Dimensions must be verified at the site before


commencing any work or making any shop
drawings. IF IN DOUBT, CONFIRM WITH
ARCHITECT.

REV. DESCRIPTION DATE


DS DS DS DS DS DS DS
B DS
DS
1

2
Hyd Drainage Drawings Rev 1

7382-H-SK-01 (Preliminary)
141115

010116
Roof - Gutter Sizes

D DS

DS

DS

E'

G DS

DS
CLIENT

MONIAN LIMITED

PROJECT NAME:

ELEMENTS WAIGANI
SECTION: S496 LOT: L16
SUBURB/TOWN:
Holola, Port Moresby
DS
K SUPERVISOR:

RTD
ARCHITECT / DRAFTSMAN

JAn/AP/SL

DRAWING TITLE:

PLUMBING
HOTEL & GAMING BUILDING
SANITARY LAYOUT
LEVEL 4
ROOF
1 PLUMBING- SANITARY LAYOUT HOTEL AND GAMING BUILDING
SCALE 1:150 M
P-12
DESIGNED BY: DRAWING SCALE:
AS SHOWN
CHECKED BY: FILE NAME:
RTD
APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - SL - Plumbing.Sanitary Layout - Rev 01 - 210416.dwg 21-Apr-16 P-12

H:\WEEKLY DRAWINGS\ELEMENTS WAIGANI SOUTH (S496L16 Hohola NCD)\DRAWINGS\PLUMBING V.03


1 June 2016

This is and shall remain in the property of


Monian Ltd., for which it was commissioned.
Unauthorised use of the document in any way is
prohibited. Dimensions shall rule over scale in
case of conflict.

Dimensions must be verified at the site before


commencing any work or making any shop
drawings. IF IN DOUBT, CONFIRM WITH
ARCHITECT.

REV. DESCRIPTION DATE

Fire Alarm Notes

Evacuation speaker layouts are indicative only.


Final location and numbers shall be in accordance with AS1670.1

Concealed smoke detectors shall be install in accordance with AS1670.1


Currently no detectors of this type are shown as there is insufficient information to position
these (Ceiling construction/heights etc.)

Test operation and sound level of all fire alarm


speakers following completion of works.
CLIENT

Provide access to all equipment requiring maintenance.


MONIAN LIMITED
All fire alarm cabling shall be run suspended from roof structure on dedicated cable trays or
catenary wires. Run concealed from view in roof or ceiling spaces and wall cavities where PROJECT NAME:

possible. ELEMENTS WAIGANI


SECTION: S496 LOT: L16
SUBURB/TOWN:
Hohola, Port Moresby
In addition to nominated works, allow for the supply and installation of the following to cater for
SUPERVISOR:
minor changes during construction :
RTD
-10 additional new detectors ARCHITECT / DRAFTSMAN
-6 additional ews speakers FN / AP / BH
-6 relocations of detectors
DRAWING TITLE:
-4 relocations of ews speakers
HOTEL & GAMING BLDG.
GROUND FLOOR
FIRE SERVICES DESIGN
LEGEND

DESIGNED BY: DRAWING SCALE:


DMA N/A
CHECKED BY: FILE NAME:
RTD
APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - AP - Hotel & Gaming Building .Fire Services Design - Rev 00 - 310516.dwg 090715 F-00

H:\WEEKLY DRAWINGS\ELEMENTS WAIGANI SOUTH (S496L16 Hohola NCD)\DRAWINGS\FIRE V.03.1


1 June 2016

N O R T H
18 17 16 15 14 13 12 11 This is and shall remain in the property of
Monian Ltd., for which it was commissioned.
Unauthorised use of the document in any way is
prohibited. Dimensions shall rule over scale in
case of conflict.

Dimensions must be verified at the site before


commencing any work or making any shop
drawings. IF IN DOUBT, CONFIRM WITH
ARCHITECT.

REV. DESCRIPTION DATE

CLIENT

MONIAN LIMITED

PROJECT NAME:

ELEMENTS WAIGANI
SECTION: S496 LOT: L16
SUBURB/TOWN:
Hohola, Port Moresby
SUPERVISOR:

RTD
ARCHITECT / DRAFTSMAN

FN / AP / BH

DRAWING TITLE:

HOTEL & GAMING BLDG.


Fire Indicator panel
GROUND FLOOR
with acknowledgement
FIRE SERVICES DESIGN
facility to be located at
HOTEL & GAMING BUILDING entrance
GROUND FLOOR
FIRE SERVICES DESIGN
DESIGNED BY: DRAWING SCALE:
1 DMA 1:150
FILE NAME:
SCALE 1:150 M CHECKED BY:
F-01 RTD
APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - AP - Hotel & Gaming Building .Fire Services Design - Rev 00 - 310516.dwg 090715 F-01

H:\WEEKLY DRAWINGS\ELEMENTS WAIGANI SOUTH (S496L16 Hohola NCD)\DRAWINGS\FIRE V.03.1


1 June 2016
18 17 16 15 14 13 12
N O R T H
This is and shall remain in the property of
Monian Ltd., for which it was commissioned.
Unauthorised use of the document in any way is
prohibited. Dimensions shall rule over scale in
case of conflict.

A Dimensions must be verified at the site before


commencing any work or making any shop
drawings. IF IN DOUBT, CONFIRM WITH
ARCHITECT.

REV. DESCRIPTION DATE

E'

CLIENT

i MONIAN LIMITED

PROJECT NAME:

ELEMENTS WAIGANI
SECTION: S496 LOT: L16
SUBURB/TOWN:
Hohola, Port Moresby
SUPERVISOR:
K K RTD
ARCHITECT / DRAFTSMAN

FN / AP

DRAWING TITLE:

HOTEL & GAMING BLDG.


LEVEL 1
FIRE SERVICES DESIGN
HOTEL & GAMING BUILDING
LEVEL 1
1 FIRE SERVICES DESIGN DESIGNED BY:

DMA
DRAWING SCALE:
1:150
SCALE 1:150 M
F-02 CHECKED BY: FILE NAME:
RTD
APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - AP - Hotel & Gaming Building .Fire Services Design - Rev 00 - 310516.dwg 090715 F-02

H:\WEEKLY DRAWINGS\ELEMENTS WAIGANI SOUTH (S496L16 Hohola NCD)\DRAWINGS\FIRE V.03.1


1 June 2016

18 17 16 15 14 13 12
N O R T H
This is and shall remain in the property of
Monian Ltd., for which it was commissioned.
Unauthorised use of the document in any way is
prohibited. Dimensions shall rule over scale in
case of conflict.

Dimensions must be verified at the site before


commencing any work or making any shop

A drawings. IF IN DOUBT, CONFIRM WITH


ARCHITECT.

REV. DESCRIPTION DATE

Alarm acknowledgement facility,


typical throughout all sole
occupancy hotel rooms

CLIENT

MONIAN LIMITED
I
PROJECT NAME:

ELEMENTS WAIGANI
SECTION: S496 LOT: L16
SUBURB/TOWN:
Hohola, Port Moresby
SUPERVISOR:

RTD
K ARCHITECT / DRAFTSMAN

FN / AP / SL

DRAWING TITLE:

HOTEL & GAMING BLDG.


LEVEL 2
FIRE SERVICES DESIGN
HOTEL & GAMING BUILDING
LEVEL 2
1 FIRE SERVICES DESIGN DESIGNED BY: DRAWING SCALE:
SCALE 1:150 M DMA 1:150
F-03 FILE NAME:
CHECKED BY:
RTD
APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - AP - Hotel & Gaming Building .Fire Services Design - Rev 00 - 310516.dwg 090715 F-03

H:\WEEKLY DRAWINGS\ELEMENTS WAIGANI SOUTH (S496L16 Hohola NCD)\DRAWINGS\FIRE V.03.1


1 June 2016

18 17 16 15 14 13 12
N O R T H
This is and shall remain in the property of
Monian Ltd., for which it was commissioned.
Unauthorised use of the document in any way is
prohibited. Dimensions shall rule over scale in
case of conflict.

Dimensions must be verified at the site before


commencing any work or making any shop
A drawings. IF IN DOUBT, CONFIRM WITH
ARCHITECT.

REV. DESCRIPTION DATE

CLIENT

i MONIAN LIMITED

PROJECT NAME:

ELEMENTS WAIGANI
SECTION: S496 LOT: L16
SUBURB/TOWN:
Hohola, Port Moresby
SUPERVISOR:

RTD
K ARCHITECT / DRAFTSMAN

FN / AP

DRAWING TITLE:

HOTEL & GAMING BLDG.


LEVEL 3

HOTEL & GAMING BUILDING FIRE SERVICES DESIGN


LEVEL 3
1 FIRE SERVICES DESIGN
SCALE 1:150 M DESIGNED BY: DRAWING SCALE:
F-04 DMA 1:150
CHECKED BY: FILE NAME:
RTD
APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - AP - Hotel & Gaming Building .Fire Services Design - Rev 00 - 310516.dwg 090715 F-04

H:\WEEKLY DRAWINGS\ELEMENTS WAIGANI SOUTH (S496L16 Hohola NCD)\DRAWINGS\FIRE V.03.1


1 June 2016

18 17 16 15 14 13 12
N O R T H
This is and shall remain in the property of
Monian Ltd., for which it was commissioned.
Unauthorised use of the document in any way is
prohibited. Dimensions shall rule over scale in
case of conflict.

A Dimensions must be verified at the site before


commencing any work or making any shop
drawings. IF IN DOUBT, CONFIRM WITH
ARCHITECT.

REV. DESCRIPTION DATE

i CLIENT

MONIAN LIMITED

PROJECT NAME:

ELEMENTS WAIGANI
SECTION: S496 LOT: L16
SUBURB/TOWN:
Hohola, Port Moresby

K SUPERVISOR:

RTD
ARCHITECT / DRAFTSMAN

FN / AP / SL

DRAWING TITLE:

HOTEL & GAMING BUILDING HOTEL & GAMING BLDG.


LEVEL 4 LEVEL 4 PENTHOUSE
FIRE SERVICES DESIGN
1 FIRE SERVICES DESIGN
SCALE 1:150 M
F-05
DESIGNED BY: DRAWING SCALE:

FN 1:150
CHECKED BY: FILE NAME:
RTD
APPROVED BY:
ILS
FILENAME: DATE APPD: DATE STARTED: SHEET NO.
Monian - Elements Waigani South - S496L16 - AP - Hotel & Gaming Building .Fire Services Design - Rev 00 - 310516.dwg 090715 F-05