Evacuation Plans and Procedures eTool

Emergency Standards Design and Construction Requirements for Exit Routes


This section contains requirements for the design and construction of exit routes. It includes a requirement
that exit routes be permanent, addresses fire resistance-ratings of construction materials used in exit stairways
(exits), describes openings into exits, defines the minimum number of exit routes in workplaces, addresses exit
discharges, and discusses locked exit route doors, and exit route doors. It also addresses the capacity, height
and width of exit routes, and finally, it sets forth requirements for exit routes that are outside a building.

Exit routes must meet the following design and construction requirements [29 CFR 1910.36(a)]:

What is an exit route?


Basic requirements
Number of exits
Exit discharge
Locking arrangements
Door swing OSHA's Exit Route
Exit route capacity
Height and width requirements
Examples
See OSHA's Demonstrative Exit Routes
Outdoor exit routes
#1 and #2 to learn how to apply the
OSHA standards for exit routes. For
further assistance, consult NFPA 101
,
Demonstration #1 Life Safety Code.

[In the image above, there is an exit hallway leading to a set of double doors marked with an "Exit" sign. Demonstration #1
The wall to the right has an opening. The wall to the left has two openings. Against the right side wall is a Demonstration #2
large planter marked with a number 1; The double doors are marked with a number 2; To the left, in the
first opening, is a set of stairs marked with a number 3; The first opening is marked with a number 4; The
ceiling in the middle of the hallway is marked with a number 5; Adjacent to the opening on the left side
wall is a second opening with a sign above, "Chemical Stock Room" with a hazard triangle, marked with a number 6.]

1. Furnishings and Decorations [Rollover image includes white lines which enclose the plantar in front of the double doors]. Each exit route must be
free of decorations that obscure the visibility of the exit route door. [29 CFR 1910.37(b)(3)]
2. Access to Exits [Rollover image includes a white rectangle which encloses the double doors]. Each exit must be clearly visible and marked by a sign
reading "Exit". [29 CFR 1910.37(b)(2)]
3. Discharge From Exits [Rollover image includes a white arrow with the text stairs which appears in the hallway pointing through the left side
opening to the stairs]. Exit stairs that continue beyond the level on which the exit discharge is located must be interrupted at that level by doors,
partitions, or other effective means that clearly indicate the direction of travel leading to the exit discharge. [29 CFR 1910.36(c)(3)]
4. Exit Marking [Rollover image includes a white rectangle which encloses the left side wall opening]. Each doorway or passageway along an exit
access that could be mistaken fro an exit must be marked "Not an Exit" or similar designation, or be identified by a sign indicating its actual use
(e.g., closet). [29 CFR 1910.37(b)(5)]
5. Exit Marking [Rollover image includes a white rectangle which encloses the "Exit" sign and the security camera above the double doors]. If the
direction of travel to the exit or exit discharge is not immediately apparent, signs must be posted along the exit access indicating the direction of
travel to the nearest exit and exit discharge. Additionally, the line-of-sight to an exit sign must clearly be visible at all times. [29 CFR 1910.37(b)
(4)]
6. Access to Exits [Rollover image includes white lines which enclose the second wall opening on the left side and the sign above, "Chemical Stock
Room" with a hazard triangle]. Exit routes must be arranged so that employees will not have to travel toward a high hazard area, unless the path
of travel is effectively shielded from the high hazard area by suitable partitions or other physical barriers. [29 CFR 1910.37(a)(2)]

Demonstration #2
[In the upper left hand corner, there is a hanging ceiling light with inadequate lighting that is marked with a number 1; to the right is an Exit sign in
letters that are too small that is marked with a number 2; further along the wall are pipes hanging from the ceiling marked with a number 3; on the far
right side is a door marked with a sign saying Production Area that is marked with a number 5. Access to the stairway on the opposite wall is blocked
by a large receptacle with laundry. The stairway is marked with a number 4, and a janitor's cart is also blocking access to the stairway.]

1. Exit Lighting. Each exit route must be adequately lighted so that an employee with normal vision can see along the exit route. [29 CFR 1910.37(b)
(1)]
2. Exit Marking. Each exit sign must have the word "Exit" in plainly legible letters not less than six inches (15.2 cm) high, with the principal strokes of
the letters in the word "Exit" not less than three-fourths of an inch (1.9 cm) wide. [29 CFR 1910.37(b)(7)]
3. Adequate Headroom. The ceiling of an exit route must be at least seven feet six inches (2.3 m) high. Any projection from the ceiling must not
reach a point less than six feet eight inches (2.0 m) from the floor. [29 CFR 1910.36(g)(1)]
4. Access to Exits. Exit routes must be free and unobstructed. No materials or equipment may be placed, either permanently or temporarily, within
the exit route. The exit access must not go through a room that can be locked, such as a bathroom, to reach an exit or exit discharge, nor may it
lead into a dead-end corridor. Stairs or a ramp must be provided where the exit route is not substantially level. [29 CFR 1910.37(a)(3)]
5. Access to Exits. The door that connects any room to an exit route must swing out in the direction of exit travel if the room is designed to be
occupied by more than 50 people or if the room is a high hazard area (i.e., contains contents that are likely to burn with extreme rapidity or
explode). [29 CFR 1910.36(e)(2)]
WHAT IS AN EXIT ROUTE?

An exit route is a continuous and unobstructed path of exit travel from any point within a workplace to a place of safety. An exit route consists of three
parts:

Exit access - portion of an exit route that leads to an exit. [29 CFR 1910.36(a)(3)]
Exit - portion of an exit route that is generally separated from other areas to provide a protected way of travel to the exit discharge.
Exit discharge - part of the exit route that leads directly outside or to a street, walkway, refuge area, public way, or open space with access to the
outside.

BASIC REQUIREMENTS

An exit route must be permanent. Each exit route must be a permanent part of the workplace. [29 CFR 1910.36(a)(1)]

An exit must be separated by fire resistant materials. Construction materials used to separate an exit from other parts of the workplace must have a
one-hour fire resistance-rating if the exit connects three or fewer stories and a two-hour fire resistance-rating if the exit connects four or more stories.
[29 CFR 1910.36(a)(2)]

Openings into an exit must be limited. An exit is permitted to have only those openings necessary to allow access to the exit from occupied areas of the
workplace, or to the exit discharge. An opening into an exit must be protected by a self-closing fire door that remains closed or automatically closes in
an emergency upon the sounding of a fire alarm or employee alarm system. Each fire door, including its frame and hardware, must be listed or
approved by a nationally recognized testing laboratory. Section 29 CFR 1910.155(c)(3)(iv)(A) of this part defines "listed" and Appendix A of section 29
CFR 1910.7 defines a "nationally recognized testing laboratory". [29 CFR 1910.36(a)(3)]

NUMBER OF EXITS

The number of exit routes must be adequate. [29 CFR 1910.36(b)]

At least two exit routes must be available in a workplace to permit prompt evacuation of employees and other building occupants during an emergency,
except as allowed in paragraph (b)(3) of this section. The exit routes must be located as far away as practical from each other so that if one exit route is
blocked by fire or smoke, employees can evacuate using the second exit route. [29 CFR 1910.36(b)(1)]

More than two exit routes must be available in a workplace if the number of employees, the size of the building, its occupancy, or the arrangement of
the workplace is such that all employees would not be able to evacuate safely during an emergency. [29 CFR 1910.36(b)(2)]

A single exit route is permitted where the number of employees, the size of the building, its occupancy, or the arrangement of the workplace is such that
all employees would be able to evacuate safely during an emergency. [29 CFR 1910.36(b)(3)]

Note to paragraph: For assistance in determining the number of exit routes necessary for your workplace, consult NFPA 101, Life Safety Code. [29 CFR
1910.36(b)]

EXIT DISCHARGE

Each exit discharge must lead directly outside or to a street, walkway, refuge area, public way, or open space with access to the outside. [29 CFR
1910.36(c)(1)]

The street, walkway, refuge area, public way, or open space to which an exit discharge leads must be large enough to accommodate the building
occupants likely to use the exit route. [29 CFR 1910.36(c)(2)]

Exit stairs that continue beyond the level on which the exit discharge is located must be interrupted at that level by doors, partitions, or other effective
means that clearly indicate the direction of travel leading to the exit discharge. [29 CFR 1910.36(c)(3)]

LOCKING ARRANGEMENTS

An exit door must be unlocked from the inside. [29 CFR 1910.36(d)]

Employees must be able to open an exit route door from the inside at all times without keys, tools, or special knowledge. A device such as a panic bar
that locks only from the outside is permitted on exit discharge doors. [29 CFR 1910.36(d)(1)]

Exit route doors must be free of any device or alarm that could restrict emergency use of the exit route if the device or alarm fails. [29 CFR 1910.36(d)
(2)]

An exit route door may be locked from the inside only in mental, penal, or correctional facilities and then only if supervisory personnel are continuously
on duty and the employer has a plan to remove occupants from the facility during an emergency. [29 CFR 1910.36(d)(3)]

DOOR SWING

A side-hinged exit door must be used. [29 CFR 1910.36(e)]

A side-hinged door must be used to connect any room to an exit route. [29 CFR 1910.36(e)(1)]

The door that connects any room to an exit route must swing out in the direction of exit travel if the room is designed to be occupied by more than 50
people or if the room is a high hazard area (i.e., contains contents that are likely to burn with extreme rapidity or explode). [29 CFR 1910.36(e)(2)]

EXIT ROUTE CAPACITY

The capacity of an exit route must be adequate. [29 CFR 1910.36(f)]

Exit routes must support the maximum permitted occupant load for each floor served. [29 CFR 1910.36(f)(1)]

The capacity of an exit route may not decrease in the direction of exit route travel to the exit discharge. [29 CFR 1910.36(f)(2)]

Note to paragraph: Information regarding "Occupant load" is located in NFPA 101, Life Safety Code. [29 CFR 1910.36(f)]

HEIGHT AND WIDTH REQUIREMENTS


An exit route must meet minimum height and width requirements. [29 CFR 1910.36(g)]

The ceiling of an exit route must be at least seven feet six inches (2.3 m) high. Any projection from the ceiling must not reach a point less than six feet
eight inches (2.0 m) from the floor. [29 CFR 1910.36(g)(1)]

An exit access must be at least 28 inches (71.1 cm) wide at all points. Where there is only one exit access leading to an exit or exit discharge, the width
of the exit and exit discharge must be at least equal to the width of the exit access. [29 CFR 1910.36(g)(2)]

The width of an exit route must be sufficient to accommodate the maximum permitted occupant load of each floor served by the exit route. [29 CFR
1910.36(g)(3)]

Objects that project into the exit route must not reduce the width of the exit route to less than the minimum width requirements for exit routes. [29 CFR
1910.36(g)(4)]

OUTDOOR EXIT ROUTES

An outdoor exit route is permitted. [29 CFR 1910.36(h)]

The outdoor exit route must have guardrails to protect unenclosed sides if a fall hazard exists. [29 CFR 1910.36(h)(1)]

The outdoor exit route must be covered if snow or ice is likely to accumulate along the route, unless the employer can demonstrate that any snow or ice
accumulation will be removed before it presents a slipping hazard. [29 CFR 1910.36(h)(2)]

The outdoor exit route must be reasonably straight and have smooth, solid, substantially level walkways. [29 CFR 1910.36(h)(3)]

The outdoor exit route must not have a dead-end that is longer than 20 feet (6.2 m). [29 CFR 1910.36(h)(4)]

UNITED STATES
DEPARTMENT OF LABOR

Occupational Safety and Health Administration


200 Constitution Ave., NW,
Washington, DC 20210
800-321-6742 (OSHA)
TTY
www.OSHA.gov

FEDERAL GOVERNMENT OCCUPATIONAL SAFETY AND HEALTH ABOUT THE SITE

White House Frequently Asked Questions Freedom of Information Act


Affordable Care Act A - Z Index Privacy & Security Statement
Disaster Recovery Assistance Freedom of Information Act Disclaimers
USA.gov Read the OSHA Newsletter Important Web Site Notices
Disability.gov Subscribe to the OSHA Newsletter Plug-ins Used by DOL
Plain Writing Act OSHA Publications RSS Feeds from DOL
Recovery Act Office of Inspector General Accessibility Statement
No Fear Act
U.S. Office of Special Counsel

Das könnte Ihnen auch gefallen