A_CL_PMI-E-1.6
GENERAL CABLE
4.2.2 Table 12: Resistance and Reactance of Mine Power Feeder Cables
R[ac]1 XL [60HZ] 2
Conductor Size Ohms/1000 Ft. Ohms/1000 Ft.
(AWG or kcmil) 5 kV 8 kV 15 kV 25 kV
90C
MP-GC MP-GC MP-GC MP-GC
6 .510 .041 .044
5 .404 .040 .042
4 .321 .038 .041
3 .254 .037 .039
2 .201 .036 .038 .042
1 .160 .035 .037 .041 .044
1/0 .127 .034 .035 .039 .043
2/0 .101 .033 .034 .038 .042
3/0 .080 .032 .033 .036 .040
4/0 .063 .031 .032 .035 .039
250 .054 .030 .031 .034 .038
300 .045 .029 .031 .034 .037
350 .039 .029 .030 .033 .036
400 .034 .029 .030 .032 .035
500 .027 .028 .029 .031 .034
600 .023 .028 .029 .031 .033
700 .020 .027 .028 .030 .032
800 .017 .027 .028 .030 .031
900 .016 .027 .027 .029 .031
1000 .014 .026 .027 .029
1 a. Based on bare copper 100% conductivity.
b. Nominal cross-sectional areas.
c. Resistance increased by increments per ASTM B-8 to compensate for stranding factor.
d. Skin effect calculated according to Arnolds Table, National Bureau of Standards.
2 a. Based on conductor dimensions given for Class B Concentric Stranded conductors in ICEA S-75-381/NEMA WC 58.
b. Extruded strand shield thickness .015".
c. Insulation thickness according to nominals given in ICEA S-75-381/NEMA WC 58.
11