ANEXO DE CALCULO: GENERAL CABLE

Cdigo: A_CL_PMI-E-1.6 Pgina:1 / 2

A_CL_PMI-E-1.6

GENERAL CABLE

VALORES DEL FABRICANTE DE RESISTENCIA Y REACTANCIA A 60 Hz Y 75 C, PARA


CABLES CLASE 25

Titulo: GENERAL CABLE


Subtitulo: Valores del fabricante de
resistencia y reactancia a 60 Hz Y
75 C, para cables clase 25
No Hojas: 2
No Paginas: 2

CODIGO: A_CL_PMI-E-1.6 Pgina: 1 / 2


4.2.1 Table 11: Resistance and Reactance of Portable Power Cables
R[ac]1 XL [60HZ] 2
Ohms/1000 Ft. Ohms/1000 Ft.
Conductor Size
(AWG or kcmil) 2 kV3
2 kV3 5 kV 8 kV 15 kV 25 kV
75C 90C G-GC,
SHD-GC SHD-GC SHD-GC SHD-GC SHD-GC
G + GC
8 .838 .878 .034
7 .665 .696 .033
6 .528 .552 .032 .038 .043
5 .418 .438 .031 .036 .042
4 .332 .347 .031 .035 .040 .043
3 .263 .275 .031 .034 .039 .042
2 .209 .218 .029 .033 .038 .040 .044
1 .165 .173 .0303 .033 .036 .039 .042 .046
1/0 .128 .134 .029 .032 .035 .037 .040 .044
2/0 .102 .107 .029 .031 .034 .036 .039 .043
3/0 .081 .085 .028 .030 .033 .035 .038 .041
4/0 .065 .068 .027 .029 .032 .034 .036 .040
250 .055 .057 .0283 .0303 .031 .033 .036 .039
300 .046 .048 .027 .029 .031 .032 .035 .038
350 .039 .041 .027 .029 .030 .032 .034 .037
400 .035 .036 .027 .028 .030 .031 .033 .036
500 .028 .029 .026 .028 .029 .030 .032 .035
600 .023 .024 .026 .027 .028 .030 .032 .034
700 .020 .021 .026 .027 .028 .029 .031 .033
800 .018 .019 .025 .026 .028 .029 .030 .033
900 .016 .017 .025 .026 .027 .028 .030 .032
1000 .014 .015 .025 .026 .027 .028 .030 .032
1 a. Sizes 8 AWG - 1 AWG based on tinned copper 94.16% conductivity.
b. Sizes 1/0 AWG and larger based on tinned copper 96.16% conductivity.
c. Resistance increased per ASTM B-172, Note 7, to compensate for stranding factor.
d. Skin effect calculated according to Arnolds Table, National Bureau of Standards.
e. Nominal cross-sectional areas.
2 a. Based on conductor dimensions given for Class H Rope Lay conductors in ICEA S-75-381/NEMA WC 58.
b. Extruded strand thickness .015".
c. Insulation thickness according to nominals given in ICEA S-75-381/NEMA WC 58.
3 a. Deviations from normal progression due to changes in insulation thickness for same voltage rating.

4.2.2 Table 12: Resistance and Reactance of Mine Power Feeder Cables
R[ac]1 XL [60HZ] 2
Conductor Size Ohms/1000 Ft. Ohms/1000 Ft.
(AWG or kcmil) 5 kV 8 kV 15 kV 25 kV
90C
MP-GC MP-GC MP-GC MP-GC
6 .510 .041 .044
5 .404 .040 .042
4 .321 .038 .041
3 .254 .037 .039
2 .201 .036 .038 .042
1 .160 .035 .037 .041 .044
1/0 .127 .034 .035 .039 .043
2/0 .101 .033 .034 .038 .042
3/0 .080 .032 .033 .036 .040
4/0 .063 .031 .032 .035 .039
250 .054 .030 .031 .034 .038
300 .045 .029 .031 .034 .037
350 .039 .029 .030 .033 .036
400 .034 .029 .030 .032 .035
500 .027 .028 .029 .031 .034
600 .023 .028 .029 .031 .033
700 .020 .027 .028 .030 .032
800 .017 .027 .028 .030 .031
900 .016 .027 .027 .029 .031
1000 .014 .026 .027 .029
1 a. Based on bare copper 100% conductivity.
b. Nominal cross-sectional areas.
c. Resistance increased by increments per ASTM B-8 to compensate for stranding factor.
d. Skin effect calculated according to Arnolds Table, National Bureau of Standards.
2 a. Based on conductor dimensions given for Class B Concentric Stranded conductors in ICEA S-75-381/NEMA WC 58.
b. Extruded strand shield thickness .015".
c. Insulation thickness according to nominals given in ICEA S-75-381/NEMA WC 58.