ANALYSIS FOR
ACMV
Hello!
I am Donny Gabriel
I am a Professional Mechanical Engineer
specializing in ACMV.
Relative
Humidity
Psychrometric
Chart
Wet Bulb
Temp
Psychrometric
Chart
Dry Bulb
Temp
Psychrometric
Chart
Entalphy
Psychrometric
Chart
Humidity
Ratio
3.
PSYCHROMETRIC
PROCESS
Psychrometric COOLING PROCESS
Process
HEATING PROCESS
HUMIDIFYING PROCESS
DEHUMIDIFYING PROCESS
COOLING + HUMIDIFYING
COOLING + DEHUMIDIFYING
HEATING + HUMIDIFYING
HEATING + DEHUMIDIFYING
4.
SAMPLE CALCULATION
SAMPLE CALCULATION
3 2
Design Condition
21C DB / 50%RH
Enthalpy 40.71kJ/kg
Humidity Ratio 7.76g/kg
Psychrometric
Process
Outside Air Condition
3 33.2C DB / 26.1C WB
Enthalpy 80.81kJ/kg
Humidity Ratio 18.55g/kg
Design Condition
21C DB / 50%RH
Enthalpy 40.71kJ/kg
Humidity Ratio 7.76g/kg
Psychrometric
Process
Outside Air Condition
3 33.2C DB / 26.1C WB
Enthalpy 80.81kJ/kg
Humidity Ratio 18.55g/kg
1 10
2 1
2 1
Using your room heat load data, determine the required air flow rate
Q = mh
Q = Room Heat Load = 100kW x 3,600kJ/hr/kW = 360,000kJ/hr
h = Change in enthalpy = 40.71 28.23 = 12.48kJ/kg
m = mass of air = 360,000/12.48 = 28,549kg/hr / 1.205kg/m = 23,938.72m/hr
Use mass of air = 24,000m/hr
2 1
Using your room heat load data, determine the required air flow rate
Q = mh
m = mass of air = 24,000x1.205 = 28,920kg/hr
h = Change in enthalpy = 80.11 28.23 = 51.88kJ/kg
Q = Coil Cooling Capacity = 28,920 x 51.88 = 1,500,369.60 / 3,600 = 416.77kW
Psychrometric
Process
3
1
2
SAMPLE CALCULATION
3 2
Using your room heat load data, determine the required air flow rate
mw = max
ma = mass of air = 24,000x1.205 = 28,920kg/hr
x = change in humidity ratio = 18.55 7.41 = 11.14g/kg
mw = mass of water = 28,920x11.14 = 322,168.8g/hr or approx 5.36l/min
5.
SAMPLE CALCULATION
SAMPLE CALCULATION
4 1
5
Psychrometric
Process
Outside Air Condition
2 33.2C DB / 26.1C WB
Enthalpy 80.81kJ/kg
Humidity Ratio 18.55g/kg
4
5
Off Coil Air Condition Supply Air Condition
8.95C DB / 100%RH 9.98C DB / 95%RH
Enthalpy 26.85kJ/kg Enthalpy 28.23kJ/kg
Humidity Ratio 7.14g/kg Humidity Ratio 7.27g/kg
Psychrometric
Process
Outside Air Condition
2 33.2C DB / 26.1C WB
Enthalpy 80.81kJ/kg
Humidity Ratio 18.55g/kg