DESIGN OF PILE CAPS----PC1(12,14)
I) Design Parametres:-
As per Table 1 of IS:2911(Part III)-1980,safe load carrying capacity 375mm dia DUR piles in medium compact
sandy soils or clayey soils of medium consistency for 3.75m depth = 360.00KN
As per clause 5.2.7.2 of IS:2911(Part III)-1980,the minimum spacing between the centre to centre of bored DUR
piles should not be less than 1.5Du.
Assuming water table in the pile bulb,the safe load carrying capacity is to be reduced by 25% as per the
clause B-1.6 of IS 2911(Part III)-1980.
Providing THREE piles,the load carrying capacity of the pile cap will be 810.00KN
Further as per clause 5.2.8.1,the load carrying capacity of each individual pile should be reduced by 10% due to
group action.
729.00KN
Hence,ultimate load carrying capacity of the pile cap = 1093.50KN > Total load
Hence O.K
0.70
375mm DUR
X X
2.09
2.09
177.21mm
However assume 650mm overall depth,then the effective depth comes to 592.00mm
Hence No.of 16mm dia bars to be provided within pile diametre = 9Nos
177.21mm
However assume 650mm overall depth,then the effective depth comes to 592.00mm
Hence No.of 16mm dia bars to be provided within pile diametre = 9Nos
Then the area of reinforcement provided = 1808.64sqmm
The critical section of one way shear is at a distance of 'd' from the face of the column
The design shear strength of concrete for the above steel percentage from
As per clause 40.5.1 of IS 456:2000,the shear strength can be increased by 2d/a v times for the sections located
at a distance closer than 2d from concentrated load or face of support,where a v is the shear span
2d/av = 1.67
0.481 >0.454
Though,the truss action is not pre-dominant,the tensile reinforcement should be checked for horizontal tensile force ' H '
resulting from truss action,because av/d ratio is not more than 2.
H = Pu/24Ld[3L2-b2] = 173.25KN
Area of steel required to resist the above above tensile force Ast = 398.28sqmm
The tensile reinforcement provided is more than the above value.Hence O.K
d) Bursting steel:-
I) Design Parametres:-
As per Table 1 of IS:2911(Part III)-1980,safe load carrying capacity 375mm dia DUR piles in medium compact
sandy soils or clayey soils of medium consistency for 3.75m depth is = 360.00KN
As per clause 5.2.7.2 of IS:2911(Part III)-1980,the minimum spacing between the centre to centre of bored DUR
piles should not be less than 1.5Du.
Assuming water table in the pile bulb,the safe load carrying capacity is to be reduced by 25% as per the
clause B-1.6 of IS 2911(Part III)-1980.
Providing two piles,the load carrying capacity of the pile cap will be 540.00KN
Reducing 10% per each pile due to group action,the net safe load carrying 486.00KN
capacity
Hence,ultimate load carrying capacity of the pile cap = 729.00KN > Total load
Hence O.K
2.09
0.70
1.41
267.80mm
However assume 700mm overall depth,then the effective depth comes to 640.00mm
Hence No.of 16mm dia bars to be provided within pile diametre = 5Nos
The critical section of one way shear is at a distance of 'd' from the face of the column
The design shear strength of concrete for the above steel percentage from
As per clause 40.5.1 of IS 456:2000,the shear strength can be increased by 2d/a v times for the sections located
at a distance closer than 2d from concentrated load or face of support,where a v is the shear span
2d/av = 1.8
0.637 >0.591
Though,the truss action is not pre-dominant,the tensile reinforcement should be checked for horizontal tensile force ' H '
resulting from truss action,because av/d ratio is not more than 2.
Hd=(Pu/2)[L/2-a/4]
H = Pu/8d[2L-a] = 286.90KN
Area of steel required to resist the above above tensile force A st = 659.54sqmm
The tensile reinforcement provided is more than the above value.Hence O.K
d) Bursting steel:-
I) Design Parametres:-
As per Table 1 of IS:2911(Part III)-1980,safe load carrying capacity 300mm dia DUR piles in medium compact
sandy soils or clayey soils of medium consistency for 3.5m depth is = 240.00KN
As per clause 5.2.7.2 of IS:2911(Part III)-1980,the minimum spacing between the centre to centre of bored DUR
piles should not be less than 1.5Du.
Assuming water table in the pile bulb,the safe load carrying capacity is to be reduced by 25% as per the
clause B-1.6 of IS 2911(Part III)-1980.
Providing two piles,the load carrying capacity of the pile cap will be 375.75KN
Reducing 10% per each pile due to group action,the net safe load carrying 338.18KN
capacity
Hence,ultimate load carrying capacity of the pile cap = 507.26KN > Total load
Hence O.K
1.73
0.60
1.13
218.45mm
However assume 600mm overall depth,then the effective depth comes to 540.00mm
Hence No.of 16mm dia bars to be provided within pile diametre = 4Nos
The critical section of one way shear is at a distance of 'd' from the face of the column
The design shear strength of concrete for the above steel percentage from
As per clause 40.5.1 of IS 456:2000,the shear strength can be increased by 2d/a v times for the sections located
at a distance closer than 2d from concentrated load or face of support,where a v is the shear span
2d/av = 1.93
0.691 >0.649
Though,the truss action is not pre-dominant,the tensile reinforcement should be checked for horizontal tensile force ' H '
resulting from truss action,because av/d ratio is not more than 2.
Hd=(Pu/2)[L/2-a/4]
H = Pu/8d[2L-a] = 193.92KN
Area of steel required to resist the above above tensile force Ast = 445.79sqmm
The tensile reinforcement provided is more than the above value.Hence O.K
d) Bursting steel:-
879.75
#DIV/0!
DESIGN OF PILES
Design Parametres:-
Item P4(1,4,7)
Note:-1)The above design is as per clauses 6.3, 6.3.1, 6.6 and 8.3.2.2 of IS 2911(PartIII)-1973 duly
reducing bearing resistance by 25% for submerged condition)