Cooling Technologies
Balcke | Hamon Dry Cooling | Marley
/ Visible plume an avoidable problem /
Every wet cooling tower generates Such plume can, however, lead to
a visible plume which can be very negative reactions such as:
extensive particularly in cold
and/or humid weather. It is the complaints and objections from
physical functioning principle of a local residents
wet cooling tower, in which the
water to be cooled is essentially problems relating to acceptance
cooled by evaporating a small pro- and approval at plant locations
portion thereof, which causes the
plume. When it leaves the cooling corrosion and ice formation on
tower, the visible plume therefore components in the vicinity
consists only of small water
droplets and is normally neither endangering of nearby traffic
dangerous nor environmentally routes (roads and railways) in
hazardous. the case of larger cooling towers
3
/ The most frequent design cell-type hybrid cooling towers /
Fig. 1
Fig. 2
4
Cooling tower made of concrete
for a Spanish paper mill.
Adjustable roller shutter doors can
be seen in front of the heat
exchangers. These control the
required hot air flow rate to ensure
plume-free operation. (Fig. 1)
Fig. 5
5
/ The top class Hybrid cooling tower of a round design /
SPX Cooling Technologies hybrid towers only one hot water pipe
cooling towers are the ideal solu- leads to the cooling tower whilst
tion for power stations and chemi- in cell-type cooling towers one
cal plants in which large water individual pipe has to be allocated
flows need to be cooled. to each cell.
Recirculation and interference
occur in large cell-type cooling Round hybrid cooling towers have
towers, i.e. the hot cooling tower separate forced draught fans in
plume is sucked back into the air front of the wet and dry sections.
inlets. This significantly reduces Whilst the speed of the wet
the thermal performance of the section fans is adjusted to ensure
cooling tower and additional cells the required cooling water temper-
would have to be built in order to ature, the appropriate speed
Hybrid cooling tower with forced
compensate for the reduction in adjustment of the dry section fans
draught fans
performance. Recirculation and controls the required hot air flow
interference problems are hardly rate for plume-free operation.
ever experienced in round cooling Optimal, energy-saving process
towers due to their greater overall control can therefore be achieved
height. in such cooling towers.
Fig. 1
Fig. 3
Fig. 4
/ Key components of a hybrid cooling tower /
Fig. 2
Fig. 3 Fig. 4
/ Mixing systems patented tube walls are kept clean during / Bypass systems flexible
efficiency / continuous operation in a large mode of operation /
cooling tower. In cell-type cooling
The mixing systems patented by towers it is preferable to use a In principle it should be possible
SPX Cooling Technologies ensure cleaning fluid. Manual or semi- to operate a hybrid cooling tower
compliance with the guaranteed automatic water jet cleaning purely as a wet cooling tower or
invisibility of plume. Appropriately equipment ensures thorough purely as a dry cooling tower in
designed mixing discs and mixing cleaning of the tube outer sur- order to guarantee 100% avail-
ducts generate the vortices faces/fins. The cleaning equipment ability. To do this, the plant section
required to mix the immense air is used once or twice per year. not in operation must be suitably
flows. Effectiveness and low pres- and reliably bypassed. Controlled
sure drop are the main features of / Evacuation only applied valves in conjunction with over-
these mixing systems. when required / flow weirs ensure absolutely reli-
able operation.
/ Cleaning equipment The syphon-principle mode of
custom-built for easy main- operation has to be applied in
tenance / order to operate the dry section
economically. Accumulation of
A custom-designed heat exchang- inert gases may disturb or inter-
er for the dry section requires an rupt the syphon effect. It may be
appropriate cleaning system in necessary to use evacuation
order to keep the fouling factor as equipment depending on the
low as possible. design and configuration of the
Rubber balls ensure that the inner heat exchanger.
9
/ Automatic process control and instrumentation
Guarantee for optimal operation /
When operating hybrid cooling The automatic hybrid cooling The automatic process control for
towers it is extremely important to tower process control developed hybrid cooling towers is designed
ensure optimal adjustment to the by SPX Cooling Technologies and engineered by an experienced
mode of operation so that: which comprises the latest instru- team of experts at SPX Cooling
mentation and control technology Technologies who are well-versed
operation is plume-free irrespec- including Programmable Logic in cooling tower operation and
tive of the changing ambient Control (PLC) systems guarantees: have specific technical expertise
meteorological conditions in instrumentation and control
the cooling water temperatures fully automatic operation to technology.
being a function of the cooling ensure invisibility of plume or
water flow rate, the heat rejec- minimum plume Upon request, we can also supply
tion rate and the changing maximum profitability with optimal automated process control
ambient air conditions are as minimal power consumption for the entire cooling circuit.
required maximum reliability and
power consumption of the cool- availability of the plant
ing tower fans is minimised minimal personnel expenses