7.1 Scope.
This chapter shall apply to areas where Class I liquids are stored or handled and to areas where Class II or Class III liquids are stored or
handled at or above their flash points. 7.2 Definitions Specific to Chapter 7. (Reserved)
7.3.4 A classified area shall not extend beyond a floor, wall, roof, or other solid partition that has no
openings within the classified area.
7.3.5 The designation of classes, divisions, and zones shall be as defined in Chapter 5 of NFPA 70,
National Electrical Code.
7.3.6 The area classifications listed in Table 7.3.3 are based on the premise that all applicable
requirements of this code have been met. If this is not the case, the authority having jurisdiction shall
have the authority to classify the extent of the area.
7.3.7* Where the provisions of 7.3.1 through 7.3.6 require the installation of electrical equipment
suitable for Class I, Division 1 or 2, or Zone 1 or 2 locations, ordinary electrical equipment, including
switchgear, shall be permitted to be used if installed in a room or enclosure that is maintained under
positive pressure with respect to the classified area.
7.3.7.1 Ventilation make-up air shall be taken from an uncontaminated source.
7.4 Application of Area Classification. (Reserved)
Chapter 8 Reserved