Beruflich Dokumente
Kultur Dokumente
Even though some of the duct systems addressed in 14.2.1.2 Terminal Units
this section are considered obsolete by the HVAC in
dustry, TAB firms may encounter them when rebal
ancing or retrofitting systems in older buildings. VAV terminal units (VAV boxes) can also be classified
as pressure independent and pressure dependent. A
Procedures will follow for: pressure independent device has a volume regulator
which will maintain the proper airflow regardless of
Variable air volume (VAV) systems
the terminal inlet static pressure. A pressure dependent
Multizone systems device will allow the airflow to vary in accordance
with the inlet static pressure.
Dual duct systems
14.2 VARIABLE AIR VOLUME (VAV) Usually, VAV systems are designed with a diversity
SYSTEMS factor which means that the supply fan airflow (cfm or
L/s) capacity is less than the sum of the airflows of all
14.2.1 Characteristics Of VAV Systems
the terminal devices. If the diversity factor is not giv
14.2.1.1 Categories en, it can be approximated by dividing the supply air
fan maximum airflow by the sum of the airflows of all
There are many types of VAV systems but they can fall VAV terminal units and converting the decimal num
into two basic categories: (1) bypass systems and (2) ber to a percentage.
POSSIBLE PRIMARY
OUTDOOR
PRE-HEA T COIL HEATING COIL COOLING AIR
AIR IN- FILTERS
COIL DUCT
TAKE S.P. CONTROLLER
OPTIONAL
EXHAUST EXHAUST AIR DAMPER RETURN
AIR AIR FAN
LOUVER
RETURN
AIR SYSTEM T T
O.A.
OUTDOOR
DM
AIR DAMPERS SUPPLY AIR
RETURN
FAN WITH
RELIEF AIR AIR DAMPER
INLET VANES
LOUVER
RETURN AIR DM
RELIEF
FAN WITH
AIR DAMPER VAV SUPPLY
INLET VANES
RETURN SYSTEM
AIR SYSTEM
The supply air fan installation for a VAV system is sim Open loop control uses an adjustable span and start
ilar to that for constant volume systems except that the point on the supply air and return air fan controls to se
fan air volume must be varied. Inlet or discharge quence the return air fan operation with the supply air
dampers and variable speed drives or motors may be fan (Figure 142). This system requires close attention
used to control the system airflow. A static pressure by the TAB technician. If the system load varies signif
sensor, usually located about twothirds of the way icantly among major zones the supply air fan serves,
from the fan to the end of the duct system, senses the resistance in the return air system may not vary in di
supply air duct static pressure and sends a signal back rect proportion to resistance in the supply air system.
to the apparatus controlling the fan airflow volume. Open loop control does not sense the effect of resist
Verify that the controls are set to maintain a constant ance variance between the supply air and return air
static pressure at the sensor location, as the system air systems, and building pressures may vary when major
flow varies. load variation occurs.
VELOCITY
PRESSURE
RECEIVER TRANSMITTER
RETURN AIR CONTROLLER
DAMPER FILTERS COOLING COIL
H L
O.A.
STATIC
HIGH STATIC
OUTSIDE OUTSIDE LIMIT PRESSURE
AIR INTAKE AIR TRANSMITTER
SUPPLY
DAMPERS AIR FAN WITH
SIGNAL
INLET VANES
SELECTOR CONTROLLER
OVERCOME DESIGN P
BY DISCHARGE FOR VAV d. With box set at maximum balance individual
DAMPER OR TERMINAL
TERMINAL UNIT UNIT outlets to design CFM.
P FOR
TERMINAL e. Turn box to minimum and adjust minimum
UNIT AT
REDUCED
stops if providedCif no stops are provided
AIRFLOW box will go to ?o" flow. Note: If box has flow
SYSTEM
sensor or voltage coils for measuring flow,
CURVE CONSTANT
SPEED
reading should be taken and recorded.
FAN CURVE
Pressure dependent systems with diversity may be bal a. Determine if the system designer has taken
anced as previously outlined in section 14.2.5.1 of this into account a diversity factor when selecting
manual if you attribute CFM proportionally to the out the equipment by comparing the fan design
lets in the same proportion as the diversity factor. airflow with the total airflow of the terminal
units shown on the drawings.
This method of balancing will guarantee proportional
If a diversity factor was used in equipment
air flow to all outlets under varying system operating
selection, set the number of units meeting this
parameters.
factor in the full cooling mode and the re
maining terminals in the fully closed posi
The diversity factor is the percent of the fan total as tion. Distribute the closed boxes throughout
compared to the outlet total. A fan that is scheduled for the system. If this procedure tends to over
8000 CFM and has a connected outlet total of 10,000 cool the building, the system supply air tem
has a diversity factor of 20% (8000/10,000 CFM). perature should be raised.
Once the diversity factor has been established, all out b. Set outside air dampers to the minimum posi
let CFMs are reduced by the diversity factor. The fac tion and exhaust and/or return air dampers to
tored outlet total will equal the fan or system total. a position that simulates full load.
l. If the system has a static pressure controller, Adjust the controller to achieve design
provide the control contractor with the re maximum airflow. Index the VAV box
quired setting and readings. to minimum (heating) and adjust the
controller to achieve design minimum
14.2.7 Pressure Dependent VAV System airflow.
Balancing Procedures
b. Pressure Dependent:
Pressure dependent VAV boxes or terminal units have Adjust maximum airflow by using one of the fol
no automatic volume controller to regulate the airflow lowing:
as the inlet static pressure to the box changes. The air
flow delivered by the box for any given condition will Adjust the stops or limiting devices on
change at any time the inlet static pressure changes. the actuator operated damper in the
Since the airflow delivered is dependent on the inlet VAV box.
static pressure furnished, the VAV boxes are consid
ered pressure dependent. Adjust the manual volume damper in
the primary air inlet or VAV box dis
These VAV boxes may have an inlet balancing damper charge.
in addition to an automatic temperature control (ATC)
Index the VAV box to the minimum
damper. The ATC damper may have limiters to pro
position. Adjust minimum airflow us
vide for adjustments of the minimum and maximum
ing stops or position limiting devices
position. The TAB technician must realize that every
on the actuator operated damper in the
change in damper setting, either manual or automatic,
VAV box.
is going to affect the airflow in the system.
14.2.8.3 Downstream Ductwork
14.2.8 Turndown (Shutoff) VAV Boxes
After the total airflow is adjusted, index the VAV box
The basic components of a turndown VAV box consist to maximum (cooling) position and balance down
of a plenum box with a primary air inlet, damper, or air stream duct system terminal outlets.