A USERS GUIDE

Valve and Damper


Actuation for
the Power Industry


Valve and Damper Actuation
for the
Power Industry

By: Pete Kundin


Rotork Controls, Inc.
675 Mile Crossing Blvd.
Rochester, NY 14624
Phone: 585-247-2304
Fax: 585-247-2308
Web site: www.rotork.com
E-mail: info@rotork.com

Copyright 2007 by Rotork Controls, Inc. All rights reserved.


Contents

Introduction ........................................................... 2
Evolution of Electric Actuator Controls .................. 3
Recent Developments ........................................... 4
Asset Management ............................................... 5
Valuable Data from Smart Actuators ..................... 5
Networked Valves ................................................. 7
Actuator Applications in a Typical Power Plant .... 8
Coal Preparation ................................................... 9
Steam Generator ................................................. 10
Typical Coal-fired Power Plant Illustration .......... 12
Cooling Tower ..................................................... 15
Plant Circulating Water ....................................... 16
Turbine Island ..................................................... 17
Flue Gas .............................................................. 18
Major Problems Associated with Actuators in Power
Plants:
High Temperatures ....................................... 19
High Speed ................................................... 20
Actuator Sizing, Modulating Service,
Voltage Drops ..................................................... 20
Summary ............................................................ 23
Family of Rotork Actuators ................................. 24
INTRODUCTION toward accomplishing many
Today, power plants face many of the important operational,
tough challenges. business, environmental, and
For example, there are safety challenges they face.
increasing demands for Todays power plants use
them to improve operating a wide range of devices to
efficiencies, increase actuate many different types
productivity, and become of valves, gates, and dampers.
better environmental stewards. There are a number of different
Other important goals include processes throughout the plant
enhancing worker safety, that have their own unique
maximizing bottom-line actuation needs.
profitability, and attaining The basic, underlying
higher levels of maintenance requirement, however, is that
proficiency. the type of actuator chosen
Whether a power plant can survive in the environment.
uses coal, natural gas, oil, Some typical environmental
hydropower, nuclear energy, or challenges include: outdoor
even waste by-products as the service, high vibration, extreme
energy source for its process, temperature, dust, and a
it has a need for effective severe duty cycle.
valve and damper actuation Because of the rugged
throughout the plant. demands found throughout the
By wisely choosing and plant, the power industry in the
upgrading to the new actuator past has tended to stay with
technology that is available traditional actuators that do
today, power plants can not have integral controls. But,
make substantial progress today, that is changing.

Proper selection of valve and damper actuators can help todays power
plants solve many of the performance, maintenance, environmental, and
safety challenges they face.
-2-
A schematic of a traditional remote motor starter system.
THE EVOLUTION OF Traditionally, the motor
ELECTRIC ACTUATOR starter equipment was located
CONTROLS in a central motor control
The use of electric actuators center of the plant known as an
in power plants has a rich, MCC. In such plants, a limited
evolving history. amount of extra space was
When motors were first allocated in the MCC for future
adapted to gearing, some growth.
of the early actuators were In the 1980s, many existing
designed for power industry plants found the necessity
applications. for such safety upgrades
In fact, power plants always as turbine water induction
had the need for automation protection. At that time,
as well as electric interlocks engineers started to evaluate
to provide adequate safety. actuators that had integral
Therefore, early motor and starters for the following
gear sets with external limit reasons:
switches once were considered 1) They were running out of
state-of-the-art technology. available space in the MCCs;
Through the 1970s, 2) They recognized that
coal-fired plants were built there was a substantial cost
with electric actuators which savings that could be realized
included motors, gears, hand related to wiring savings;
wheels, limit switches, and 3) They saw other benefits
torque protection. of integral controls such
-3-
as monitoring relay, phase designers to look for ways to
rotation protection, and 24-volt include efficiencies gained
DC control. by using modern distributed
During the 1980s and control systems with intelligent
1990s, there was a resurgence field devices.
in the construction of gas- For example, todays power
fired power plants. Certain plant designers are integrating
designers used the advantages asset management technology
of integral motor controls and into their plant designs as
incorporated them extensively a focal point for improved
throughout their plant operational performance. In
configurations. doing so, they are introducing
Another important sophisticated electronic
change in power plant design controls found in such devices
happened during this time. as the latest generation of
Distributed control systems valve actuators to provide vital
(DCS) became the standard diagnostic and performance
in most cases and interlocks information to the control room.
could be accomplished via While the benefits of
software. This eliminated the diagnostic monitoring and
need for numerous switches automated control are
inside the electric actuator. It impressive, many seasoned
also enabled a way to eliminate plant engineers may ask: Can
much of the wiring required these devices survive in a
inside the actuator itself, which power plant environment?
results in a more reliable and In short, the answer for
maintenance-friendly actuator. many applications is Yes.
The surge in building of However, there are exceptions,
power plants during the past and this booklet will help give
ten years has stimulated power insights to clarify specific
plant designers to re-evaluate situations.
their core designs. Another pressing
RECENT DEVELOPMENTS question arises with existing
Integral motor starters power plants that are under
have become the standard in mandate to increase efficiency
many of the latest generation both operationally and
of power stations that are environmentally.
currently in design or under Many retrofit projects
construction. In fact, the vast involve re-automating existing
majority of plant designers valves, gates, and dampers.
have eagerly embraced the The question is, Do you
world of digital control. replace like with like, or Do
The many challenges faced you look at new technology?
by the next generation power In fact, there are significant
plants have caused new-plant advantages to using new

-4-
technology in an older plant
environment to improve the
performance of a single
process. This booklet will
provide useful information on
some of the available options.
ASSET MANAGEMENT
Todays modern power
plant needs to run as
efficiently as possible with
minimal downtime. Asset
management is strategically
important and requires data
from all instrumentation and
field devices to function as a
system.
A supervisor at a combined-cycle
More megawatts are being
natural gas plant uses a hand
produced with less staff in setting tool to check configuration,
every type of plant, regardless troubleshooting, and predictive
of the fuel used. The theory maintenance data.
is that with more automation
less manpower will be needed First, it is important to
during normal operation, at understand what type of
plant start-up as well as during information is available at the
outages. actuator, how to access it, and
In fact, many utilities how to manage it.
today outsource their outages Generally, we can break
to specialists, who may not down the type of information
be familiar with the specific that can be captured in
equipment in their plant. This sophisticated actuators into
requires an even greater need three main categories:
to plan ahead and to have predictive maintenance,
relevant valve operating and configuration, and trouble-
historical data on hand. shooting data. This information
Distributed control systems can relate to the valves,
are very sophisticated and actuators, and control room
have the ability to gather large requirements.
streams of data and send them For example, we can obtain
to planners and engineers for torque profiling information
analysis. by capturing the torque
VALUABLE DATA FROM characteristics of an individual
SMART ACTUATORS valve and storing it in the
Below is a description of asset management system.
some of the information todays Then, it can be compared with
smart actuators can provide. additional profiles throughout

-5-
the valves life history. This can problems such as over
help predict valve performance pressure in a particular line or
and assist in the scheduling material clogging in a valve.
of normal maintenance tasks, One might find that a loss
such as packing replacement. of a maintained signal could
We can also monitor seat indicate an error in software
wear. programming under certain
Another example of conditions.
predictive maintenance is that Furthermore, control room
the actuator data logger can operators would be interested
give us alarm logs that are in interlock failures related to
date and time stamped. Details faulty wiring issues. Anything
such as the number of times a that could possibly stop a
contactor has been energized system from getting through
can be analyzed. Also, last its process can be monitored
operations and historical and adjusted with this type of
operations logs are of great diagnostic information.
use to planners. There are several different
From an operations point ways that the smart actuators
of view, information like phase information can be accessed.
loss monitoring can pinpoint The most basic way is
areas of the power system that that a lot of information can
need attention. Over-torque be accessed locally at the
trips can mean operational actuator via its help screens;

Data from todays electronic actuators, such as the Rotork IQ Pro, can be
accessed locally via the actuators display screen; downloaded locally via
a hand setting tool, PDA, or laptop computer; and accessed remotely via
the plants network and/or a secure Ethernet web browser.
-6-
Actuators, such as the Rotork IQ Pro, can be easily and economically
connected to the plants network via a two-wire Pakscan communication
system and master station (inset).

however, that does not data locally, most modern


automatically get the data into plants that use asset
the asset management system. management tools have their
Nonetheless, the diagnostic electric actuators connected on
information displayed on the their network, so that much of
help screens provide exact the actuators data is available
data on the conditions inside at the control room.
the actuator. NETWORKED VALVES
In the past, the traditional Configuration of smart
way to get such information valve actuators on a network
was with multi-core cables. is simple. The actuators on
But, the abundance of the network can be configured
available information has made remotely, including the setting
that method impractical. of the electric actuator network
Therefore, todays smart baud rates and addresses.
actuator have evolved so Network maps can be seen
that they can be accessed and adjusted from the human-
locally using a PDA or machine interface (HMI).
laptop computer. This way, Also, many items within the
large amounts of valuable motor operator can be adjusted
information can be quickly remotely, including dead bands
downloaded from the actuator and spans on modulating
for easy transfer into the asset operators. Torque values can
management system. be monitored and adjusted
In addition to accessing over todays networks.

-7-
Troubleshooting is another
area which has been enhanced
by the use of networks. From
the actuator, we can now
download profiles and transmit
them electronically to remote
service centers for assistance.
The profiles can be analyzed
with selected computer A major benefit of linking actuators
on a network is that valve
programs, which allow end- monitoring and troubleshooting
users to troubleshoot their can be done remotely without the
equipment without opening the need to open actuator covers.
covers.
The negative side of this is information thats available and
that the large amounts of data work with vendors you have
can load up the highway. So, confidence in.
some end-users are looking at ACTUATOR APPLICATIONS
ways to get the information off- IN A TYPICAL POWER
line. PLANT
One very practical Because coal-fired power
solution is to use an Ethernet plants generate about half
connection, which can provide of the worlds electricity,
secure Web access. Also, this booklet will discuss the
some manufacturers are process of a typical coal-fired
looking at wireless as a method facility. However, many of the
of extracting information for processes are applicable to
diagnostics purposes (but, other types of plants, so the
NOT for control). information is relevant to a
Managing the information wide range of different power
is another challenge in todays generating facilities.
plants. The DCS is one This booklet describes
place to do it, but many are how actuators are involved in
looking to third party suppliers the processes where coal is
to manage the data with transported and stored at the
prepackaged software. facility, how it is moved through
Web sites are another option the system, and how it is
as well as subcontracting plant processed with air and water in
maintenance all together. order to produce steam. Then,
A few things are worthy well discuss the role actuators
to note. Watch the network play in how steam is used to
traffic. Many believe that a produce power, and how the
faster network speed will waste needs to be treated as a
solve all problems. This is by product.
not necessarily true. Be sure Please note: An illustration
to take advantage of all the identifying valve and damper

-8-
actuator locations in a typical requirements are other
coal-fired power plant is found important considerations.
on pages 12 and 13. Electric actuators can have an
COAL PREPARATION advantage with their integral
The process begins by limit switches, emergency
getting coal from the rail car to manual hand wheels, and
the steam generator. easily achieved torque
Coal is removed from rail protection. The advantages
cars and moved via conveyor of pneumatic power include
systems. The coal is typically increased air pressure to
dropped through hoppers overcome occasional clogging
equipped with special hopper with increased forces from the
valves. cylinder. Also, the air cylinder
Steps include moving coal can provide quicker operating
to storage silos, bulk handling, times than the typical motor
and conveyor isolation. without increasing horsepower.
Most of the valves used in As coal is moved through
these areas are slide gates. the process, valves are used
They are shut-off gates, which at several locations, including
do not require tight sealing and grinding mills and coal mill
are typically operated by multi- feeders, which prepare the
turn actuators. The multi-turn coal for the boiler feed stage.
operation can be accomplished During the movement of
by an electric motor operator, the coal to these areas, there
manual gear box, or pneumatic are many diverter applications
cylinder. for hoppers, basket diverters,
Often, if operation is and flapper gates. These often
infrequent, manual gearboxes require quarter-turn operation,
are used. (For example, which can be achieved with a
manual operation is common if cylinder and exposed clevis
the valve needs to be operated arrangement, or quarter-turn
only during maintenance electric motor actuators.
outages.)
However, if the gate valve
is operated more frequently
and needs automation, the
decision of what type of power
should be used is important. In
northern climates, pneumatic
power typically does not fare
well outside, and electric power
is preferred. In very high thrust
conditions, hydraulic power
can be considered. A Jordan SM-5000 electric actuator
Gate size and control used in a coal diverter application.

-9-
All of these applications
move coal in different directions
per the requirements of the
process. And, for todays
efficient plant, that means the
need for information being fed
back to the control process.
In many of the more
critical applications, heavy-
duty lock gates are used.
These are double gates that
can isolate and measure
flow. They actually have two
actuation assemblies which
can be linked and operated
with one motor or cylinder. In
some of these applications, A Rotork Fluid System P-Range
temperatures can be quite high spring-return pneumatic actuator
at relatively low pressures. operates a block valve in gas
service.
As coal is broken down and
crushed, different devices are pipelines where gas is brought
needed to keep the particles to the plant in relatively high
moving. The end result is so pressures.
fine that the pulverized coal The gas is moved through
resembles talcum powder. Teflon-seated ball valves,
The equipment in the which are typically 300lb or
coal-handling and processing 600lb ANSI pressure class
applications is difficult to keep valves. Usually, they are either
clean, so sometimes self- flanged or weld-end valves
cleaning valves are used. and are motor operated for
The front-end of a coal- metering service.
fired facility is an area where Block valves are used, too,
health and safety margins are and are often fitted with spring-
high-priority considerations for return pneumatic actuators.
system designers. It is also an They require limit switches for
area that is difficult to interlock, indication.
because the particulate can STEAM GENERATOR
cause valves to have difficulty The steam generator, which
making the ends of travel is commonly called the boiler, is
limits. where the fuel is mixed with air.
The front-ends of other The fuel is ignited, and the
types of power plants have resulting heat is transferred to
very different considerations. water-filled pipes in the walls of
For example, natural gas the boiler. The heat generated
plants are connected to there is used to vaporize water,

-10-
are starting to be used in
modulating applications as
well, since their duty cycles
have improved over the
years. Modulating electric
drives provide an important
advantage, because they can
be easily added to the network
(such as a HART network) that
A Jordan LA2000 modulating controls vital aspects of boiler
electric linear actuator operates a functionality.
secondary damper. The firing of the boiler most
often is regulated under strict
and steam is produced. Super- codes and national safety
heated steam is introduced to regulations. Boiler firing is
the steam turbine. an integral part of the control
Because a wide variety of system of the various boiler
temperature ranges must be manufacturers.
accommodated in this stage One of the most critical
of the process, many different phases of boiler operation is
types of actuators are used. the start-up sequence. In super
At the start of the process, critical boilers that operate at
pulverized coal is initially very high pressures, the valves
moved via an air stream, are often very large y-pattern
which is powered by fans. The globe valves for block valve
fans often work with control service that require some
dampers, which modulate of the biggest electric valve
constantly in continuous-duty actuators in the plant.
mode. Traditionally, the motor
These dampers are called starter equipment for these
axial fan dampers. While they valves is located in the central
can be controlled with close- motor control center. These
coupled actuators, in most cases, valves are heavy wall, high-
they are controlled from floor-
mounted drives with lever arms.
The duct work leading
to the boiler usually has
traditional louver dampers and
close-coupled damper drives.
While electric drives are now
often used in many isolation
applications, traditionally,
the modulating applications
relied on pneumatic drives. Jordan SM1700 electric actuators
Now, however, electric drives control over-fired air dampers.

-11-
Typical Coal-fired
Power Plant

Cooling Tower Steam Generator

Generator Steam Turbine

River Water Extraction Steam


This is added to the feedwater to make Extraction steam that has had its pressure
up for losses from the steam/power reduced to supply heating as part of the
generation process. Rankin cycle.
Feedwater Superheated Steam
Boiler feedwater is recovered from the Steam from the boiler drum goes through
condenser and re-circulated through the primary and secondary superheaters to
system by the boiler feed pump. This is produce dry superheated steam at a very
then pumped into the economizer and high temperature to drive the turbine.
furnace walls to generate steam within the
boiler drum.

-12-
Coal Handling

Flue Gas Desulphurization

Reheated Steam Limestone Slurry


The high-pressure return steam passes The exhaust gases are passed through a
through the reheater elements within the limestone slurry to remove sulphur oxides,
boiler, and this reheated steam drives thus reducing emissions. This process is
the second-stage turbine (intermediate known as flue gas desulphurization (FGD).
pressure). Then, this exhausts into the Gypsum Slurry
three stages of the low-pressure turbine, The by-product of passing the exhaust
and subsequently to the condenser where gases through the limestone slurry. After
it is cooled and becomes feedwater. drying, gypsum slurry is used in various
Exhaust Gases building materials, including breeze blocks
Gases created and exhausted as a result and wallboard.
of the combustion process.

-13-
pressure valves that are either The applications that have
pneumatic or electric powered. high-duty cycle requirements
Modern plants are tending to include burner tilts, air shrouds,
use electric actuators for ease and over-fired dampers. Other
of maintenance. applications near the boiler
There are literally hundreds include auxiliary and pulverizer
of actuators around the boiler. inlet air dampers.
The boiler fronts have many The majority of these
drives that are part of the dampers are modulated using
fuel-firing system. The system an incoming 4-20 MA control
includes dampers that control signal. They tend to be both
the combustion air flow into single- and three-phase power
the boiler. Typical applications actuated drives.
include over-fired air and Today, many of these
corner-fired air dampers. applications are utilizing
Customer preference dictates network protocols for enhancing
whether they are pneumatic or their diagnostic capability.
electric actuators. The industry is also starting
Depending on the boiler to use Foundation Fieldbus
design, dampers can be operated and Profibus communication
by either quarter-turn actuators in some areas to interface
or linear devices utilizing a drive more directly with plant
arm with clevis pin. Most of these control systems. Most drive
applications require high-rate manufacturers are producing
modulating actuators. actuators that can support all
of the major protocols.
Over-fired air dampers
control the air at the top of the
boiler and remove particulate.
This is another common
application that has a high-duty
cycle within the 1200 start-per-
hour range. It operates in the
middle range of the traditional
modulating actuator and the
true high-duty cycle drive.
Another application detail that
must be taken into account in
this area is temperature.
Certain areas can be
extremely hot. The designer
A Jordan SM6000 electric actuator needs to look at both ambient
provides continuous modulating temperature and heat transfer
duty and 0.1% accuracy for through the valve or damper
precise damper control. shafts.

-14-
Careful analysis of shape. Mechanical draft towers
temperature by application is use fans to provide a flow of air
required, because a rubber through the tower.
stamp approach can result in Fans can push air from the
costly mistakes. Interestingly, bottom or draw air from the
many designers may think top. The use of FD (forced)
they are taking a conservative or ID (induced) fans require
approach by over-estimating modulating drives. The
possible temperatures. velocities of these fans can be
However, a higher temperature quite high, so the actuators
requirement than that which is tend to be rigidly mounted with
actually needed may not allow output shafts.
the use of standard electronics, The air flow can
which do not operate reliably approximate wind speeds
at temperatures above 160 equal to 5 mph within the
degrees F. tower. The interior of the tower
The unnecessary removal is both windy and saturated
of electronics from a hot area with moisture. It is a difficult
often defeats the substantial application for electrical
benefits of wiring savings and equipment, so totally sealed
simple control. actuation is a must. It is best to
For these reasons, accurate specify submersible equipment
assessments of each situation in this area.
should be determined, since Towers often include cross-
each application and boiler is flow and counter-flow designs.
different. The technologies include
COOLING TOWER moving the water and air in
The basic function of the different patterns to affect the
cooling tower is to provide differing results intended.
cooling for the steam cycle. Therefore, there are
The most natural principle numerous valve applications in
of cooling is by evaporation. a typical tower. For example,
However, since directing wind blow down applications are
to cool the steam is usually used to eliminate impurities in
not a realistic option, a flow of the water. Collection basins
air over a large body of water are located in vessels below
is the most common cooling and integral to the tower.
technique used by todays There, water is collected
power plant. and redirected to the sump
There are several different or pump suction line. As in
types of cooling towers. For all applications with pumps,
example, atmospheric towers there are suction, discharge,
do not require fans to create air and bypass lines with electric
flow. Hyperbolic natural draft actuated valves. These
towers are distinctive in their valves are either rubber-lined

-15-
butterfly valves or knife gates,
depending on the preference of
the designer. The automation
of the quarter-turn butterfly
valve offers a significant cost
advantage. It also allows for a
better sealed package.
If a knife gate is used,
there is a higher chance that
moisture can enter the center
column area of the multi-turn
electric actuator that is used to
operate it. Adequate moisture
protection can usually be
accomplished if one starts with
a properly sealed actuator and
also takes special care in how
the stem cover is sealed.
The distribution system of
the cooling tower has many Actuated valves are often located
automated applications. in hard-to-access places. Here,
There are also many areas Rotork IQ electric actuators linked
that require flow regulation or to the plants network provide
throttling valves. These are not remote montioring and control.
true modulating applications
such as those required for the available three-phase power as
fan drives, but they do require the power of choice.
that the valves move to mid- Towers are excellent
travel positions. examples of how todays
Headers, laterals, branch actuators can provide
arms, and other applications operational, maintenance, and
help to distribute the water safety benefits. Specifically,
where required. Also, there modern, network-compatible
is often a need for fail-safe actuation enables remote
operation in this area, where monitoring of tower valves that
actuators fail on loss of main are located in hard-to-access
power. and potentially dangerous
There are many different areas of the facility. Because
piping arrangements of their difficult locations, tower
throughout the tower where valves and their actuators are
water comes in and out. Some ideal candidates for network
of the valves will be outside the control and monitoring.
tower, and are best operated PLANT CIRCULATING WATER
by electric actuators mounted In addition to cooling
at ground level with readily towers, there are many other

-16-
applications that require actuator at this point would be
moving and directing water to easily accomplish fail-safe
within the plant. operation.
Water is typically drawn However, if there is a need
from a nearby source through for manual back-up operation,
a pipeline, and the flow is then pneumatic actuators may
controlled via rubber-seated not be the best choice for
butterfly valves. large-size valves. Specifically,
The valves can be large quarter-turn valves with
anywhere from two-to-five pneumatic actuators that need
feet in diameter. If the water manual back up most often
is heated, then the valves require clumsy declutchable
often require metal rather than gearboxes or hydraulic hand
rubber seats. The metal seats pumps.
necessitate higher actuation For that reason, electric
forces and require more torque actuators usually make more
for the same line size of non- sense on large quarter-turn
heated water. valves.
Either electric or pneumatic TURBINE ISLAND
quarter-turn actuators are used The turbine is the key to
for rubber- or metal-seated the generation of electricity.
butterfly valves. The main It is an area that has need for
advantage of a pneumatic valve automation.
For example, there are
multiple drain valves that are
required to remove moisture
from the system.
The drain valves tend to
require motor-operated valves
on small line sizes with high
pressures. In most cases, drain
valves are one or two inches
in line size. The control system
of the turbine itself will control
these, so they are considered
an integral part of the steam
turbine. Because of this, they
are usually not on a broader
valve network.
There are also applications
for turbine water induction to
protect the turbine. The induction
Rotork IQ electric actuators operate system provides critical safety
48-inch butterfly valves located features to protect the turbine
about 20 feet above floor level. and insure that water is not

-17-
allowed to be introduced to the However, a good design will
turbine blades. consolidate actuators with
The valves here are similar power requirements
typically in the range of 6-18 as much as possible to
inches, ranging from the 150lb achieve overall operating and
through to the 900lb class. The maintenance efficiencies.
turbine stop valve can be quite MAJOR PROBLEMS
large and might have an ASSOCIATED WITH
electro-hydraulic operator. ACTUATORS IN POWER
FLUE GAS PLANTS
Flue gas desulphurization Power plants have
(FGD) is the name given to the demanding environments
highly automated process used that require a high level of
to clean the effluent gas that expertise related to actuator
results from the burning of coal. selection, performance, and
There are many different, maintenance.
evolving technologies used in The following are a few
the FGD process. However, in examples of problems that
general, the initial flue gas is need to be addressed in order
typically sent to a precipitator, to make sure that the actuators
which statically charges the selected are appropriate for the
particulate and removes it. The application.
gas then undergoes a chemical
neutralization process and
is sent through a slurry and
drying process. The end
result is a usable, marketable
by-product (such as gypsum
used in the manufacture of
wallboard).
The process requires
very large dampers and fans
to move the gas as well as
many automated valves and
gates, which control the flow
of the slurry throughout the
process. Many different types
of actuators are used, and it
is very important to make the
right choice of actuator for
each specific requirement.
In fact, many FGD facilities Rotork IQ electric actuators can
utilize a variety of pneumatic, take a lot of punishment. Here,
hydraulic, and electric networked IQs operate in a power
actuators in the same plant. plants rugged FGD environment.

-18-
HIGH TEMPERATURES insulations. O-rings and oil
There are areas in the plant seals are usually specified to
where temperature is a major be manufactured with Viton
concern. Some of the areas and wire insulation with
are straight forward, while Teflon materials. Suitable
others require some technical trim materials are required for
explanation to understand the high temperature areas. Rotork
consequences. has done extensive testing to
The ambient temperature insure that the non-electronic
in some areas of the plant will actuators designed for high
depend on typical weather temperature applications can
variants. In colder areas of the withstand temperatures up to
world, plants are built inside 300 degrees F.
buildings in order to protect A more difficult problem
against inclement weather. comes with the stem expansion
During the summer months of gate and globe valves in
ambient temperatures can high temperature service. The
easily reach 120 degrees F. effects of operating the valve
In warmer climates, plants with high temperature service
are not enclosed, but still see conditions for a typical gate or
high ambient temperatures globe valve are as follows.
due to direct sunlight and hot With the valve in the fully
summer weather. Again, 120 opened position, a portion of
degrees F is not uncommon. the length of the valve stem is
The transfer of heat from outside the valve bonnet and
pipes with steam at 1000 is relatively cool. When the
degrees F can radiate to valve is seated by a motor in
nearby equipment to have a relatively quick amount of
temperatures higher than time (that is, before the stem
ambient. When one adds heats up and expands), the
the heat which is conducted stem is then heated by the
through a valve or damper hot service fluid trapped in the
stem inside an electric body of the valve and exerts
actuator, the temperatures can additional thrust pushing the
exceed the 160 degree F limit valve further into the seat. That
of the electronic actuator. thrust is then absorbed by the
The exact temperatures in valve seats, the actuator thrust
these different applications are bearing, and drive nut.
difficult to ascertain. Suffice it After the valve has been
to say, many designers specify closed, the valve cools and the
actuator trims to meet these seats contract. That leads to
high temperature conditions. difficulty in unseating the valve
Areas of concern include when it needs to be reopened.
suitable lubricants, soft Also, the valve can unseat
rubber seals, and electric wire itself causing it to leak by

-19-
driving the disc/shaft up. When the electric actuator
The solution to this problem is driving a secondary gearbox,
is to use a temperature there are times that the
compensator. It can be actuator can be operating at
achieved by either springs or quite a high output speed.
beveled washers in the drive These situations are rare, but
bushing area, or at the thrust need to be considered in the
base to allow for some stem combination of the actuator
movement. and gearbox so that damage
This is a commercial to the operating mechanism or
manufacturing issue that adds gearbox will not occur.
cost to the initial purchase This issue is especially
price of the equipment, but important to look at in
it is a situation that needs to applications where the actuator
be addressed by designers to is holding a piece of equipment
insure proper operation of any in place against flow or gravity,
valve and actuator that will be such as with a guillotine
exposed to high-temperature damper.
conditions. ACTUATOR SIZING,
HIGH SPEED MODULATING SERVICE,
Wherever self-locking VOLTAGE DROPS
gearing is required, attention Sizing of actuators is an
should be paid to how high- integral part of the process and
speed electric actuators are can have an enormous effect
configured. on the installed cost of the
Self-locking actuator automated valve.
and stem combinations can There are some specific
be accomplished either by issues related to sizing
the actuator gear ratio or actuators in power plants that
valve stem threading. It is an should be addressed.
important item to look at in A basic concern of sizing
certain applications. Basically, any actuator for a valve is to
if the stem is self-locking, the insure that there is enough
actuator does not need to be. force to move the valve.
The opposite is also true. In the case of a threaded
However, back driving a stem, a few important facts
valve is such a bad situation need to be considered.
that it must be double-checked. The first calculation is
Most designers feel if the made to determine the thrust
gear ratio is a minimum of 60:1, that is required. (In this
then the actuator is self-locking. booklet, we measure thrust in
There are also common pounds.)
charts to determine whether In a simple equation,
the stem with its particular the raw thrust required for a
characteristics is self-locking. particular valve is a function

-20-
of the bore area relative to the where similar valves are used
differential pressure across the at lower temperatures, full
valve. differential pressure might be
A valve factor, which is used to insure there is a sizing
dependant on the type of safety factor. Of course, this
valve, is also included. This is not sensible when the valve
equates to a raw thrust which classification is chosen due to
is the major component of the temperature considerations.
thrust requirement. On very high thrust
In most cases, the stem applications, the stem factors
piston thrust is added, which need to be looked at quite
is dependant on stem size. carefully, and the thrust
The actual force to turn a calculations can be affected by
valve stem is measured in the stem data itself. This is an
foot pounds of torque. This area where close coordination
is determined by multiplying between valve and actuator
the required thrust by a stem suppliers is required.
factor, which comes from the Most motor operated
stem data of the valve. valve applications are sized
It is best to run the raw under guidelines that assume
numbers and then add a operating times of about 12
suitable safety factor. inches per minute. Based on
In certain industries, the this assumption, the typical
same valves can be sized operating times for a MOV
quite differently. In areas will be three minutes or less.

Rotork can provide you with a sizing guide. Ask for publication number
AE2/0.2; or, download it at Rotorks Web site: www.rotork.com.

-21-
When this is the case, the damper. The gearing for a fan
rated torque of the machine is damper drive is oversized in
considered to be acceptable order to withstand the heavy-
for the entire stroke. Some duty cycle encountered.
manufacturers tend to de-rate Actuator manufacturers
the actuator in cases where rate their electric motor
the operating time starts to operators for 1200 or more
increase to limit temperature operational starts per hour
rise in the motor. This type as high-modulating rates.
of extended service needs to Many consider that rate
be considered in very large to be synonymous with
valves or applications such as continuously modulating.
guillotine dampers. However, in reality, continuous
Another common area duty means the drive could
where an electric actuator will be required to move in either
be de-rated is in modulating direction constantly for some
service. Manufacturers have considerable amount of time,
different opinions about this, until it finds its equilibrium
but most have some way point.
of calculating the de-rating Any drive that never finds
of the actuator if it is to run its set point will have a very
in a continuous mode. This short life expectancy. So, while
is strictly a consideration of it is rare that a valve would
torque over time. be constantly modulating, it is
The discussion of what reasonable that it might have
constitutes a modulating to operate continuously for
actuator must also take into days during start up modes
consideration other items and during times of ramping
within the actuator. These the units up and down.
include, but are not limited Therefore, it makes much
to, motor starters, motor more sense to discuss the
insulation, drive sleeve specific application rather
materials, and even drive than rely on rated starts and
sleeve configurations. stops. This is especially true
There are certain drive because different actuator
designs that specialize in manufacturers have different
continuous modulation, and opinions regarding duty cycles
the sizing is inherently in the and life expectancies of their
published figures. The more equipment.
specialized controls required Another type of sizing
for this service should not be consideration which often
considered add-ons or options, occurs in power plants is
but as standard equipment. sizing for reduced voltages.
An example of this type of It probably seems strange
drive is one that operates a fan for a power-producing facility

-22-
not to have sufficient voltage Contact us at:
for the equipment. There are Rotork Controls, Inc.
many reasons for this, and 675 Mile Crossing Blvd.
it is a problem that happens Rochester, NY 14624
frequently. Phone: 585-247-2304
Sizing on a reduced Fax: 585-247-2308
voltage of just 20% can E-mail: info@rotork.com
reduce the output power of the Web: www.rotork.com
machine by about one third. It
is not something that should Note: Rotork is a registered
be done lightly, as it means a trademark. Teflon is a registered
larger actuator, larger valve trademark of DuPont. Viton is a
stem, and more robust valve registered trademark of DuPont
bonnet assembly. Performance Elastomers, LLC.
SUMMARY
The information in this Rotork Controls, Inc., Rotork Fluid
booklet is a brief, general System, and Jordan Controls are
overview about the roles valve Rotork Group companies.
and damper actuators play in a
typical coal-fired power plant.
However, every plant and
every application is different
and has its own special
requirements.
Rotork has had more
than 50 years experience in
providing high-quality, reliable
solutions for the power industry
and can help you determine
the best actuator for your exact
needs.
We can provide information
about electric, pneumatic,
hydraulic, and electro-hydraulic
actuators. So, please feel
free to contact us if you have
questions or need information.

-23-
Family of Rotork Actuators
There are many
dozens of different
Rotork IQ Pro multi-
turn electric actuator valve and damper
and setting tool. The IQ actuators specifically
Pro includes on-board suited for Power
data logging for valve Industry applications
monitoring and predictive available from
maintenance. It is
easily integratable into the companies in
most facilities control the Rotork Group
systems. (including Rotork
Controls, Inc., Jordan
Controls, and Rotork
Fluid System).
The actuators
Rotork Skilmatic SI
at the left are only
electro-hydraulic, quarter- a small example of
turn, and linear actuators. the many products
Available for modulating Rotork offers to the
or two-positon fail-safe Power Industry.
applications.
In fact, we have a
wealth of engineering
knowledge and
Rotork Fluid System extensive experience
offers a full-range serving the Power
of pneumatic Industry, dating back
actuators. Available
in spring-return
more than 50 years.
or double-acting A professional
configurations. sales and service
force is available to
help you solve all
Jordan Controls of your valve and
provides modulating damper actuator
actuators ideal for
many power plant
requirements.
applications.

Rotork produces
IEEE-382
nuclear qualified
actuators and
high-temperature
A-range motor
operators.

-24-

Rotork Controls, Inc.


675 Mile Crossing Blvd. Rochester, NY 14624 USA
Phone: 585-247-2304 Fax: 585-247-2308
E-mail: info@rotork.com Web site: http://www.rotork.com