Beruflich Dokumente
Kultur Dokumente
GENERAL California
The System Sensor 5451 plug-in rate-of-rise with fixed heat MEA State Fire
Marshal
detector contains a unique dual thermistor sensing circuit 167-93-E
to provide both maximum performance and solid state re- 7270-1209:105
liability. Additional features include a recess mounting op- S2101
tion, various mounting bases, and a full line of accesso-
ries.
The 5451 thermal detector is specifically designed to meet
the stringent performance requirements of industrial and
commercial fire detection/alarm systems. The design of
these detectors emphasizes ease of installation and field
maintenance.
FEATURES
Dual solid-state thermistor sensors.
Fixed heat with rate-of-rise response (57.2C/135F alarm
point).
Rate-of-rise feature activates when the ambient temper-
ature increases at a rate greater than 15F (9.4C) per
minute.
Exceptional stability and reliability.
Thermistor technology.
Restorable. Construction: flame-retardant white plastic.
Two visible LEDs blink in standby and latch on in alarm. Temperature: 32F to 100F (0C to 37.8C).
Sealed against back pressure. Humidity range: 10% to 93% RH non-condensing.
Three year warranty. Agency listings: UL (listed for 50 ft. spacing).
Built-in test switch.
Low standby current.
ELECTRICAL RATINGS
Built-in tamper-resistant feature. Voltage range: 15 to 35 VDC.
Designed for electrical box mounting. Ripple voltage: 4 Vpp.
360 field viewing angle of the visual alarm LEDs. Maximum standby current: 100A.
Easy plug-in of the head to base. Input capacitance: 0.02F.
SEMS screws for easy wiring. Reset voltage: 2.50 V.
Optional recess mounting kit (flangeless bases only). Reset time: 0.03 to 0.30 seconds.
UL listed for 50 ft. spacing.
Power-up time: 1 second maximum.
APPLICATIONS ORDERING INFORMATION
The 5451 135 Fixed Temperature and Rate-of-Rise Ther-
5451 Fixed heat detector with rate-of-rise. Alarm
mal Detector is ideal for areas in which a smoke detector
point at 57C (135F). Must be mounted to
is not practical. Independent studies show that heat de-
one of the 400 Series bases listed on page 2
tectors should be used when property protection alone is
(order separately).
involved.
RA400Z Remote annunciator for 2- or 4-wire systems,
SPECIFICATIONS 3 32 V. Use with any 400 Series plug-in
Operating voltage: mounting base dependent (see chart detector. Fits standard U.S. single-gang elec-
on page 2). trical box.
Weight: 0.6 lb. (277 g). RMK400 Recessed mounting kit. Use with any 400
Size: 2" (52 mm) high, 4" (102 mm) diameter; 6.2" (158 Series plug-in detector. Recesses detector
mm) diameter with flanged bases. by 0.8".
This document is not intended to be used for installation purposes. We try to keep our
product information up-to-date and accurate. We cannot cover all specific applications or
anticipate all requirements. All specifications are subject to change without notice.
For more information, contact NOTIFIER. Phone: (203) 484-7161 FAX: (203) 484-7118
()
() () WIRING DIAGRAMS
OPTIONAL OPTIONAL
RA400Z () () RA400Z () ()
2 2
3 3 EOL
RESISTOR
(+) (+)
1 1
4 4
For B401B
(+) (+)
(+) (+)
PURPLE
RELAY, A77-716
SUPERVISION
EOL POWER
() ()
OPTIONAL OPTIONAL
RA400Z RA400Z
4 4 ()
3 3
RESISTOR
2 2 BLK
PURPLE
5 5
14 14
EOL
COM COM
(+) 1 13 (+) 1 13
N.C. N.C.
() 12 N.O. 12 N.O.
11 11
10 10
For B402B
AUXILIARY AUXILIARY
8 9 CONTACTS 8 9 CONTACTS
ALARM CIRCUIT
BL
BL
BL
AC
AC
AC
AC
K
K
K
() ()
OPTIONAL OPTIONAL
3 3
RA400Z RA400Z
2 4 2 4
1 1
5 14 COM 5 14 COM
13 N.C. 13 N.C.
(+) 12 N.O. (+) 12 N.O.
6 11 6 11
10 10
For B404B
7 AUXILIARY 7 AUXILIARY
8 9 FORM C 8 9 FORM C
CONTACTS CONTACTS
EOL
RESISTOR
ALARM
CONTROL
PANEL
(+)
EOL
RESISTOR
4 4
2 3 2 3
5 5
1 1
14 COM 14 COM
13 AUXILIARY 13 AUXILIARY
N.C. CONTACTS N.C. CONTACTS
12 12
For B406B
N.O. N.O.
()