DESIGN CALCULATION OF

FIRE WATER TANK


FOUNDATION-BINTULU
REGIONAL OFFICE

REV.
DOCUMENT NO. SSGP S-DC-2012-A4 1 1 of 14
NO.

PROJECT SABAH SARAWAK GAS PIPELINE PROJECT

CUSTOMER PETRONAS CARIGALI SDN BHD

CONTRACTOR PUNJ LLOYD DIALOG PETROSAB CONSORTIUM

Comments incorporated and issued as


1 21/01/10 DSG AJX RGX
approved for construction
0 25/11/09 Issued for Approval DSG AJX RGX

Rev. Prepared Approved


Date Description of revision Checked by
No. by by
This document is exclusive property of PL Engineering Ltd. It is to be used only for the purpose, which it is lent and must not be copied or used in any
way detrimental to the interest of this company and subject to return on demand
DESIGN CALCULATION OF FIRE
WATER TANK FOUNDATION -
BINTULU REGIONAL OFFICE

DOCUMENTNO. SSGPSDC2012A4 REV.NO. 1 2 of 14

TABLE OF CONTENTS

1.0 OBJECTIVE 3
2.0 REFERENCES 3
3.0 DESIGN METHOD 3
4.0 MATERIALS 3
5.0 GENERAL DATA 3
6.0 LOADING 3
7.0 DESIGN AND ANALYSIS OF RING WALL 4
8.0 APPENDIX-A - CALCULATION FOR
BEARING CAPACITY
9.0 APPENDIX-B - REFERENCES FOR SETTLEMENT CALCULATION
10.0 APPENDIX-C - LOADING FROM TANKAGES
11.0 APPENDIX-D - NFPA-22 REQUIREMENTS
DESIGN CALCULATION OF FIRE
WATER TANK FOUNDATION -
BINTULU REGIONAL OFFICE

DOCUMENTNO. SSGPSDC2012A4 REV.NO. 1 3 of 14

1.0 OBJECTIVE:
This document is prepared for analysis and design of fire water tank foundation at
Bintulu Regional office.

2.0 REFERENCES:
2.1 BS 8110-1 : 1997
2.2 BS 6399-1 : 1996
2.3 BS 6399-3 : 1988
2.4 PTS 34.00.01.30
2.5 PTS 34.11.00.11
2.6 UBC
2.7 Geotechnical investigation report- Bintulu Regional Office.
2.8 ACI360R92
2.9 SSGP-MDS-1006-A4
2.10 ACI 318M

3.0 DESIGN METHOD:


Limit state method for design
g as per
p ACI 318.

4.0 MATERIALS:
4.1 Reinforcement: Hot rolled high yield deformed bars with specified strength of
460 N/mm2 in accordance with BS 4449 & BS 4483.
4.2 Sub Structure Concrete: Concrete grade C40
4.3 Super Structure Concrete: Concrete grade C30
4.4 Blinding Concrete: Concrete grade C20

5.0 GENERAL DATA:


2
5.1 Net safe bearing capacity of soil @ 0.8m depth = 90 kN/m
5.2 Characteristic strength of Superstructure concrete = 30 N/mm2
5.3 Characteristic strength of Substructure concrete = 40 N/mm2
2
5.4 Yield stress of reinforcement steel = 460 N/mm
3
5.5 Unit weight of PCC = 24 kN/m
5.6 Unit weight of RCC = 25 kN/m3
5.7 Submerged unit weight of soil = 8.69 kN/m3
5.8 Note # For calculation of safe bearing capacity refer Appendix - A

6.0 LOADING:
ForloadingreferAppendixC
DESIGN CALCULATION OF FIRE
WATER TANK FOUNDATION -
BINTULU REGIONAL OFFICE

DOCUMENTNO. SSGPSDC2012A4 REV.NO. 1 4 of 14

7.0 DESIGN AND ANLYSIS OF RING WALL

A A

C/LofWall PLAN C/LofWall


D3 = 10.016

D1 = 10.416

D = 10

Tank D2 = 9.616
Ring Wall

0.4 0.7
FGL / HPP
EL +0.00m Compacted
0.8 Structural Fill 1.5

0.3 8.816
1.2 1.2
SECTION A-A
a Note : All Levels & Dimesions are in m.
DESIGN CALCULATION OF FIRE
WATER TANK FOUNDATION -
BINTULU REGIONAL OFFICE

DOCUMENTNO. SSGPSDC2012A4 REV.NO. 1 5 of 14

A) INPUT DATA
Tank
Internal Diameter of the tank shell, D = 10 m
Thickness of tank bottom plate,t = 10 mm
Thickness of tank shell, t2 = 8 mm
Ring wall thickness, t1 = 0.4 m
Inner diameter, D2 (as shown in the Sketch) = 9.616 m
Outer diameter, D1 (as shown in the Sketch) = 10.416 m
D3 (as shown in the Sketch) = 10.016 m
Height of the liquid in the tank,H = 6.866 m
Width of footing slab = 1.2 m
Thickness of footing slab = 0.3 m

Foundation
Main bar dia. = 16 mm
Clear cover to Bottom reinforcement = 75 mm
Bottom of ring wall from FGL = 08
0.8 m
FGL to top of ring wall = 0.7 m
Distance between ring wall inside edge to O/D tank = 0.2 m
3
Bulk density of Structural Fill = 8.69 kN/m
Friction coefficient between soil and concrete, = 0.35
of soil = 28 degrees
Ko = (1-SIN ) = 0.53
2
Safe bearing capacity of Soil = 90 kN/m
2
Safe bearing capacity of Soil in seismic/wind case = 112.5 kN/m
(Increasing 25%)
Gross Bearing Capacity of Soil at found. Depth
2
(90+8.69x0.8) = 99.56 kN/m
Gross Bearing Capacity of Soil at found. Depth
(112.5+8.69x0.8) = 122.059 kN/m2
(In case of Seismic/Wind)

3
Density of Concrete, c = 25 kN/m
DESIGN CALCULATION OF FIRE
WATER TANK FOUNDATION -
BINTULU REGIONAL OFFICE

DOCUMENTNO. SSGPSDC2012A4 REV.NO. 1 6 of 14

B) FOUNDATION LOADING DATA


EmptyWeight = 360 kN
Shelldeadload = 142.2 kN
OperatingWeight(includingselfweight) = 5750 kN
HydroTestWeight(includingselfweight) = 6010 kN
HorizontalLoadatTankbaseduetoWind = 60 kN
MomentatTankbaseduetoWind = 520 kN-m
HorizontalLoadatTankbaseduetoSeismic = 230 kN
MomentatTankbaseduetoSeismic = 750 kN-m

D) MATERIAL PROPERTIES
ConcreteGrade,fc'= = 40 N/mm2
2
Reinforcement,fy= = 460 N/mm
WeightofRingWall,W1 (Pix10.016x0.4x1.5x25) = 471.99 kN
Weightoffootingslab,W2 (Pi x 10.016 x 1.2 x 0.3 x 25) = 283.2 kN
Weightofsoilonfootingslabinside,W3
(Pi x ((9.616^2)
((9.616 2) - (8.816
(8.816^2))/4)
2))/4) x 1.5 x 8.69 = 150.96 kN
Weightofsoilonfootingslaboutside,W4
(Pix(((10.016+1.2)^2)(10.016+0.4)^2))/4)x0.8x8.69 = 94.49 kN
Totalload = 1000.64 kN

F) GROSS BEARING PRESSURE CALCULATION UNDER VERTICAL LOAD

C/L of wall
Shell + Portion of Roof
supported on shell Weight
Wind / Seismic moments Liquid Wt. (Lw)
F acting on Influence area
Wind / Seismic forces
m
0.7
FGL W3

1.8 1.5 W4 W1

W2 KoYh Koq
DESIGN CALCULATION OF FIRE
WATER TANK FOUNDATION -
BINTULU REGIONAL OFFICE

DOCUMENTNO. SSGPSDC2012A4 REV.NO. 1 7 of 14

Z =3.14*((10.016+1.2)^4(10.0161.2)^4)/((10.016+1.2)*32)
3
= 85.65 m
A =3.14*((10.016+1.2)^2(10.0161.2)^2)/4
2
= 37.76 m

PressureduetoOperatingweight
Wt.ofbottomplate = /4 x D22 x t x 78.5
= 57 kN
HydroTestweightlessemptywtoftank = 6010-360
= 5650 kN
Operatingweightlessemptywtoftank = 5750-360
= 5390 kN
Hence,operatingwttobeconsidered = 5650 kN
Tankarea = xD2/4 = 3.14x(10^2)/4
= 78.50 m2
Pressure,q=ContentWeight/Tankarea = 5650/78.5
= 71.97 kN/m2
Koq,atringwallbottom = 0.53x71.97
0 3 19
= 38.14 kN/m2
KoYh,atringwallbase = 0.53x8.69x1.8
= 8.3 kN/m2
Momentduetoearthpressure = (0.5x8.3x1.8) x (1.8/3)
= 4.48 kNm/m
Momentduetosurcharge = 38.1441x1.8x1.8/2
= 61.7934 kNm/m
AdditionalMomentduetoUnsymetricloadingonFootingslabPermeterlength
wtofliquidoninfluencearea(Lw) = (PIx((9.616^2)(8.816^2))/4x71.97)
= 833.87 kN
Totalmomentabout(a)= ((471.99+283.2+360)x(1.2/2))+(150.96(1.2((1.20.4)/4)))
(94.49x((1.20.4)/4))+(833.87x(((1.2/2)((8/1000)+((0.4/2)(8/1000))/2))
= 1252.57 kNm
Totalweight = 833.87+360+1000.64
= 2194.51 kN
X = 1252.57/2194.51 = 0.57 m
e1 = 1.2/20.57 = 0.03 m
M = 0.03x2194.51= 65.84 kNmor (0.03x2194.51)/(3.142x10.016)kNm/m
= 2.09 kNm/m
DESIGN CALCULATION OF FIRE
WATER TANK FOUNDATION -
BINTULU REGIONAL OFFICE

DOCUMENTNO. SSGPSDC2012A4 REV.NO. 1 8 of 14

Mduetoseismicforce(Fsxh)= 230x1.8 = 414 kNm


or 13.16 kNm/m
Mduetowindforce(Fwxh)= 60x1.8 = 108 kNm
or 3.43 kNm/m

Bearingpressurebelowfootingslab
Case1DL+Operatingload

Totalverticalload = Emptyweight+liquidweightoninfluenceaera= 1193.87 kN


Grossload,P = (Totalverticalload+W1+W2+W3+W4)/(pi()xD)= 69.73 kN/m
Moment,M = 2.09((4.48+61.793442)/(3.142x10.016))= 0.02 kNm/m
3
z = (1x1.2^2)/6 = 0.24 m
GrossinsideMaxpressure= (69.73/(1x1.2))(0.02/0.24) = 58.19 kN/m2
safe< 99.56 kN/m2
GrossinsideMinpressure= (69.73/(1x1.2))+(0.02/0.24) = 58.03 kN/m2
safe> 0 kN/m2

Bearing pressure below footing slab as a whole


Bearingpressurebelowfootingslabasawhole
Case2DL+Operatingload+Seismic
Totalverticalload,P = 1193.87 kN
M,Moment = 414+750 = 1164 kNm
Grossload,P = 1193.87+1000.64 = 2194.51 kN
GrossMaxpressure =(2194.51/37.76)+(1164/85.65)= 71.71 Safe<122.059kN/m2
GrossMinpressure =(2194.51/37.76)(1164/85.65)= 44.53 Safe<122.059kN/m2

Case3DL+Operatingload+Wind
Totalverticalload,P = 1193.87 kN
M,Moment = 108+520 = 628 kNm
Grossload,P = 1193.87+1000.64 = 2194.51 kN
GrossMaxpressure =(2194.51/37.76)+(628/85.65)= 65.45 Safe<122.059kN/m2
GrossMinpressure =(2194.51/37.76)(628/85.65)= 50.79 Safe<122.059kN/m2

Case4DL+Emptytank
Emptyweight = 360 kN
Grossload,P = 360+1000.64 = 1360.64 kN
GrossMaxpressure= 1360.64/37.76 = 36.03 Safe<99.56kN/m2
DESIGN CALCULATION OF FIRE
WATER TANK FOUNDATION -
BINTULU REGIONAL OFFICE

DOCUMENTNO. SSGPSDC2012A4 REV.NO. 1 9 of 14

Case5DL+EmptyTank+Wind
Emptyweight = 360 kN
M,Moment = 108+520 = 628 kNm
Grossload,P = 360+1000.64 = 1360.64 kN
GrossinsideMaxpressure =(1360.64/37.76)+(628/85.65)= 43.37 Safe<122.059kN/m2
GrossinsideMinpressure =(1360.64/37.76)(628/85.65)= 28.7 Safe<122.059kN/m2

GrossPressurebelowfillarea
q = Hydrotestweight/tankarea+soilpressureduetofill
= (6010360)/78.5+(8.69x1.8)= 87.62 Safe<99.56kN/m2

CHECK FOR OVERTURNING


Case : Empty tank with wind
Total Overturning moment =
Wind moment+Moment due to wind force = 628 kNm
Restoringmomentaboutbasepointa= DeadweightofTank
= 1000.64x0.9x10.416/2+(360x/2)= 6565.08 kNm
Factor of Safety against overturning = Restoring moment/Overturning moment
= 10.45 >2ok

CHECK FOR SLIDING


Case : Empty tank with wind
Total sliding force = 60
Total weight W = (Empty weight + total load) = 1360.64
Resisting force =0.9xxW = 428.6
FOS = 7.1433333 >1.5ok
Case : Operating tank with seismic
Total sliding force = 230 kN
Total weight W = (Operating weight +Total load) = 6750.64 kN
Resisting force =0.9xxW = 2126.45 kN
FOS =2126.4516/230= 9.25 >1.5ok

G) DESIGN OF RING WALL


Ringwallsectionmodulus () = (D14-D24)/32xD1
= (3.14x((10.416^4)-(9.616^4)))/(32x10.416)
= 30.34 m3
HoopReinforcement
Innerdiameter = 10.016-(0.4/2)x2
(betweentankdiaandinnerfaceoftheringwall)= 9.616 m

Outerdiameter = 10.016+(0.4/2)x2
(betweentankdiaandouterfaceoftheringwall)= 10.416 m
DESIGN CALCULATION OF FIRE
WATER TANK FOUNDATION -
BINTULU REGIONAL OFFICE

DOCUMENTNO. SSGPSDC2012A4 REV.NO. 1 10 of 14

Case:Operating+Seismiccondition
KoYh+Koq+M/ZduetoSeismic = 8.3+((5750/78.5)x0.53)+(1164/30.34)
2
= 84.1 kN/m
Case:Operating+windcondition
KoYh+Koq+M/ZduetoWind = 8.3+((5750/78.5)x0.53)+(628/30.34)
2
= 66.43 kN/m
TotalpressureatBase = Kaq+KaYh
2
= 46.44 kN/m
MaximumHooptension = 84.10 kN/m2
Hooptension=PD2/2= 84.1x(9.616/2) = 404.35 kN/m
FactoredHooptension = 566.09 kN/m height of Wall
StrengthReductionFactorforSteel= 0.8
2
Permissibletensilestressinsteel=0.8fy= 368 N/mm
Horizontalsteelreqd = 566.09x1000/368
2
= 1538.29 mm /m ht.
Steelrequiredoneachface = 1538.29/2
2
= 769.15 mm
Minimum horizontal reinforcement reqd
Minimumhorizontalreinforcementreqd. = 0 0020x 1000 x 400
0.0020x (Refer cl 14 3 3
(Refercl14.3.3,
2
= 800 mm ACI318M)
BarSize = 16 mm
2
NominalAreaofbar = 201.1 mm
Spacingrequired = 201.06x1000/800
= 251.33 mm
ProvideSpacingateachface = 200 mm C/C
Thereforesteelprovidedateachface = 201.06x1000/200
2
= 1005.3 mm
Henceprovidehorz.reinforcementof16mmbars@200mmc/c(Astprovided=2010.6mm2)
Verticalreinforcement
Totalwalllength = 3.14xD3
= 3.14x10.016
= 31.45 m
Totalnumberofboltsprovidedthroughoutwall= 0
(Since there is no tension, anchor bolts are not required)
Minimumverticalreinforcementreqd.= 0.0012x 1000 x 400 (Refercl14.3.2,
2
= 480 mm ACI318M)
BarSize = 16 mm
ProvideSpacingateachface = 200 mm C/C
Thereforesteelprovidedateachface = 201.06x1000/200
2
= 1005.3 mm
Henceprovidehorz.reinforcementof16mmbars@200mmc/c(Astprovided=2010.6mm2)
DESIGN CALCULATION OF FIRE
WATER TANK FOUNDATION -
BINTULU REGIONAL OFFICE

DOCUMENTNO. SSGPSDC2012A4 REV.NO. 1 11 of 14

Design of Footing Slab


2
Maximum pressure under Footing slab =(max pr due to DL+ operating load) = 87.6 kN/m
Minimum pressure under Footing slab = 28.7 kN/m2
Design pr under Footing slab = (For conservative side taken maximum value)= 87.6 kN/m2
Pr due to soil W3= =1.5*8.69 = 13.035 kN/m2
Pr due to concrete =0.3*25 = 7.5 kN/m2
2
Net Maximum Pressure= =87.6213.0357.5 = 67.1 kN/m
Strength reduction factor, = 0.9
W3(duetosoil)

0.3

0.4 0.4
Mu =1.5*67.085*0.4*0.4/2 = 8.05 kNm
Mn =Mu/ = 8.94 kNm
Effectivedepthofslab =0.3x10007512/2 = 219 mm
2
Rn =Mn / bd2 = 19 N/mm
0.19
0
= 27.55 psi
Pt = 100 * Ast / b d ACI 318-02, Fig-7.2 = 0.02
2
Ast Required = 60 mm
Minimumverticalreinforcementreqd.(ACI 318-02, cl-10.5) = 3x(fc'/fy)xbwxd
2
=3x {(40x145)^0.5) / (460x145)} x (1000x0.03937)x (219x0.03937) = 1.16 inch
2
= 748.43 mm
BarSize = 12 mm
2
NominalAreaofbar = 113.1 mm
Spacingrequired = 113.1x1000/748.432 = 151.12 mm
ProvideSpacingateachface = 150 mm c/c
2
Thereforesteelprovidedateachface = 113.1x1000/150 = 754 mm
2
Minimumareaofsteelrequired= (0.13/100)x1000x150 =
195 mm
Henceprovidehorz.reinforcementof12mmbars@150mmc/c(Astprovided=754mm2)
atBottom(Bothways)
Providehorz.reinforcementof12mmbars@200mmc/c(Astprovided=565mm2)atTop(Bothways)

Checkforshear
Shear force at the distance d from wall face =67.085*(0.3219/1000)= 5.43 kN
Factoredshearforce =1.4*5.43 = 7.6 kN
2
DesignShearstress, Vu = (7.6x1000)/(1000x219)= 0.03 N/mm
Shearstress,c =2x fcxbwxd (Refercl11.3.1.1,ACI318) = 12.6491 N/mm2
2
> 0.03 N/mm
Hencesafe
DESIGN CALCULATION OF FIRE
WATER TANK FOUNDATION -
BINTULU REGIONAL OFFICE

DOCUMENTNO. SSGPSDC2012A4 REV.NO. 1 12 of 14

CALCULATIONOFIMMEDIATESETTLEMENT
Areaofcircularfoundation
Correspondingsizeofsquare
ReferenceBorehole = /4 x D22 = 78.8 m2
Totaluniformloadatbottomoffoundationleve = 8.9 x 8.9 m
SincetheBoreholedataisnotavailablebelow7 = BHAR5(BCSSoilInvestigationReport)
grainedSANDSTONEisassumedtobecontinued= 87.62 Kpa

1.45 8.9 EL -65.3 Loosereddishbrown


3.9 Bottom of mottledwithpalegrey
2.9 foundation level siltySAND.N=5.
2.9mthick.
EL -62.4
VeryVerydense
mediumgreysiltSAND.
N=50,2.0mthick.
2
7.9
EL -60.4
Fairtogoodlightgrey
moderatelytoslightly
3
EL -57
-57.4
4 weathered fine grained
weatheredfinegrained
SANDSTONE.N=50,3.0m
Loaddisperiondiagram
9.3475
CalculationofImmediatesettlement
Depthconsideredfor 1.5xB = 13.795 m
immediatesettlement =
Thefollowingequationhasbeenusedforcalculatingtheimmediatesettlement
2
H qB'(1 )mIsIf (SeefoundationAnalysis&Design
= Es ofJosephE.Bowlrs."SH.B2OfB7)
N SPTvalue
m = 4 atcenter; 2 atthefootingcorner
Es = Elasticsoilparameterseetables56
= fromJoseph.E.Bowles (SeeSH.B3OfB7)
0.35 Seetable27(SeeSH.B4OfB7)
q IntensityofcontactpressureinunitsofEs
B' = Leastlateraldimensionofbasearea
IsIf = Influencefactors,whichdependonL'/B',thicknessof
= stratumH,Poisson'sratioandbaseembedmentdepthD
B Widthoffoundation
Is = I1+12I2 (SeeSH.B2OfB7)
=
I1&I2 Fromtable52ofJoseph.E.Bowles (SeeSH.B6&B7OfB7)
If = FromFigure57ofJoseph.E.Bowles (SeeSH.B5OfB7)
=
DESIGN CALCULATION OF FIRE
WATER TANK FOUNDATION -
BINTULU REGIONAL OFFICE

DOCUMENTNO. SSGPSDC2012A4 REV.NO. 1 13 of 14

IstLayer
N = 5
B = 11.8 5000 Kpa
= 0.35
Es = 250(N+15) =
q = 49.8447 Kpa
H = 2.9 m atcorner
L = 11.8 m atcorner
L' =(L/2forcenter) = 5.9 atcenter; 11.80
B' =(B/2forcenter) = 5.9 atcenter; 11.80
M =L/B = 1
D = 1.1
D/B = 0.09322 atcorner
If = 0.82 atcorner
N =H/B' = 0.49153 atcenter; 0.25 atcorner
I1 = 0.0495 atcenter; 0.013 atcorner
I2 = 0.072 atcenter; 0.052 mm
Is = 0.08273 atcenter; 0.037
H = 14 mm 6.3
atcenter atcorner
IIndLayer
N = 50
B = 16.7 16250 Kpa
= 0.35
Es = 250(N+15) =
q = 24.8857 Kpa
H = 2m atcorner
L = 16.7 m atcorner
L' =(L/2forcenter;) = 8.35 atcenter; 16.70
B' =(B/2forcenter;) = 8.35 atcenter; 16.70
M =L/B = 1
D = 1.1
D/B = 0.06587 atcorner
If = 0.85 atcorner
N =H/B' = 0.23952 atcenter; 0.12 atcorner
I1 = 0.009 atcenter; 0.009 atcorner
I2 = 0.041 atcenter; 0.041 mm
Is = 0.02792 atcenter; 0.02792
H = 1.1 mm 1.1
atcenter atcorner
DESIGN CALCULATION OF FIRE
WATER TANK FOUNDATION -
BINTULU REGIONAL OFFICE

DOCUMENTNO. SSGPSDC2012A4 REV.NO. 1 14 of 14

IIIrdLayer
N = 50
B = 27.595 16250 Kpa
= 0.35
Es = 250(N+6) =
q = 9.11428 Kpa
H = 8.895 m atcorner
L = 27.595 m atcorner
L' =(L/2forcenter;) = 13.7975 atcenter; 27.60
B' =(B/2forcenter;) = 13.7975 atcenter; 27.60
M =L/B = 1
D = 1.1
D/B = 0.03986 atcorner
If = 0.86 atcorner
N =H/B' = 0.64468 atcenter; 0.32 atcorner
I1 = 0.086 atcenter; 0.017 atcorner
I2 = 0.081 atcenter; 0.057 mm
Is = 0.12338 atcenter; 0.04331
H = 2.9 mm 1
atcenter atcorner
Totalimmediatesettlement = 14+1.1+2.9 6.3+1.1+1mm
underLayerI+II+III atcenter atcorner
= 18 mm 8.4
atcenter atcorner
<20mm,Hencesafe
DESIGN CALCULATION OF
FIRE WATER TANK
FUNDATION BINTULU
REGIONAL OFFICE

REV.
DOCUMENT NO. SSGP S-DC-2012-A4 1 APPENDIX- A
NO.

APPENDIX-A BEARING CAPACITY CALCULATION


1 of 3

DESIGN CALCULATION OF FIRE


WATER TANK FOUNDATION -
BINTULU REGIONAL OFFICE

REV.
DOCUMENTNO. SSGPSDC2012A4 1 APPENDIXA
NO.

BEARINGCAPACITYCALCULATIONASPERSOILINVESTIGATIONREPORT
FOOTINGTYPECF1

Netqult= CNCSCDCIC+q(Nq1)SqDqIq+0.5YBNYSYDYIY

BearingcapacityiscalculatedasperVesic'sEquationforNetUltimateBearingCapacity
asper"FoundationAnalysisandDesignByJosephE.Bowles"&referencesgivenbelowareforsamebook.

SoilParameters
Reference = BHAR5
Report = BintuluCompressorStationSoil
InvestigationReport
BoreHoleRL = 66.41 m
SoilType = BoreHoleisinCutArea
GradeLevel = 66.41 m
SPTvalue = 5 N/cm Atadepthof1.1mfromRL
2
Cohesion C = 0 kN/m
AngleofShearingResistance = 28 indeg. (Ref:Table34)

FoundationParameters

FootingWidth B = 1.2 m
FootingLength L = 31.0 m
FootingThickness T = 0.3 m
DepthofFooting D = 1.1 m
Clearcoverofreinforcement cc = 75.0 mm
Bardia.ForEffectiveDepth R = 12.0 mm
EffectiveDepthforInnerreinf. D1 = 0.207 m
EffectiveDepthforouterreinf. D2 = 0.219 m

Soilunitweight,(w) Y = 8.69 kN/m3

BearingCapacityUsingVesic'sMethod

0
InclinationofLoad = 0 (Sincethereisnoinclination)
Effectivestressatbaselevel,(xD) q = 9.56 kN/m2
2 of 3

DESIGN CALCULATION OF FIRE


WATER TANK FOUNDATION -
BINTULU REGIONAL OFFICE

REV.
DOCUMENTNO. SSGPSDC2012A4 1 APPENDIXA
NO.

Vesic'sbearingcapacityparameters(Ref:Table.44)

2 0 tan
Nq=tan (45 +/2)(e ) Nq = 14.70
NC=(Nq1)cot NC = 25.79
N=2(Nq+1)tan N = 16.70

ShapeFactors (Ref:Table.45a)

Sq=1+tan Sq = 1.53
SC=1+(Nq/Nc)x(B/L) SC =
1.02
SY=10.4(B/L) SY = 0.98452

DepthFactors (Referpage224ofbookFoundationAnalysisandDesignbyJosephE.Bowles)

2
Dq=1+2tan(1Sin) (Df/B) Dq = 1.27
DC=1+0.4(Df/B) DC = 1.37
DY(=1,forallvaluesof) DY = 1

InclinationFactors

IC=Iq=(10/90)2 IC=Iq = 1
0 2
IY=(1 /) IY = 1

HENCE,
UltimateNetBearingCapacity qult = 341.298 kN/m2
FactorofSafety FOS = 3
AllowableNetBearingCapacity qa = 113.766 kN/m2
HENCE,
RecommendedNetBearingCapacity = 90 kN/m2
3 of 3

DESIGN CALCULATION OF FIRE


WATER TANK FOUNDATION -
BINTULU REGIONAL OFFICE

REV.
DOCUMENTNO. SSGPSDC2012A4 1 APPENDIXA
NO.
ElasticSettlementAssesment

ElasticSettlement (ReferCanadianManualofFoundationEngineering1987)

= (2.3PoH/E)xlog10(Po+p/Po)

IncreaseinPressuredueto
superstructureload p = 90 kN/m2
ThicknessofLayerconsidered(1.5xB) H = 1.8
Effectiveoverburdenpressure,(xD) Po = 9.559 kN/m2
ModulusofElasticityofSoil,(800xNc) E = 7092.9 kN/m2
whereas,
NC=CNNF NC = 8.9
CN=0.77log10(1920/Po) CN = 1.77

Hence,
ElasticSettlement = 0.00713 m
= 7.13
7 13 mm

NOTE: BoreHoleconsideredforbearingcapacitycalculationisNearesrboreholetothebuilding.
ThoughwearegettingBearingCapcityof113.7kN/m 2 weareusingbearingcapacity
of90kN/m 2 forfoundationdesign.
DESIGN CALCULATION OF
FIRE WATER TANK
FUNDATION BINTULU
REGIONAL OFFICE

REV.
DOCUMENT NO. SSGP S-DC-2012-A4 1 APPENDIX- B
NO.

APPENDIX-B REFERENCES FOR SETTLEMENT CALCULATION


B1 OF B7
B2 of B7
B3 of B7
B4 of B7
B5 of B7
B6 of B7
B7 of B7
DESIGN CALCULATION OF
FIRE WATER TANK
FUNDATION BINTULU
REGIONAL OFFICE

REV.
DOCUMENT NO. SSGP S-DC-2012-A4 1 APPENDIX- C
NO.

APPENDIX-C LOADING FROM TANKAGES


C1 of C2
C2 of C2
DESIGN CALCULATION OF
FIRE WATER TANK
FUNDATION BINTULU
REGIONAL OFFICE

REV.
DOCUMENT NO. SSGP S-DC-2012-A4 1 APPENDIX- D
NO.

APPENDIX-D NFPA-22 REQUIREMENTS