Sie sind auf Seite 1von 4

Guillermo APONTE1, Hctor CADAVID2, Juan Carlos BURGOS3, Eduardo GOMEZ4

Universidad del Valle (1,2,4), Universidad Carlos III (3)

A methodology for obtaining by measurements the transformer


physical-circuital model parameters
Abstract. Modeling a transformer usually requires all its construction data, which is very difficult to obtain for the units in operation; for new
transformers manufacturers are not usually willing to provide this information. This paper presents a procedure to obtain the parameters of the
transformer physical-circuital model based on data obtained from external measurements, without need for design data. This was done by using
different tests, some routine tests like losses and other special tests such as frequency response or FRA. It is also presented the application of the
procedure to obtain the model of a 15-KVA 13200 / 244 V single-phase transformer, and its use to simulate the frequency response.

Streszczenie. W artykule zaprezentowano procedur okrelania parametrw modelu transformatora na podstawie pomiarowych danych
eksperymentalnych. Przedstawiono przykady testw rutynowych jak i specjalnych. Uzyskane wyniki sprawdzono na przykadzie transformatora 15-
KVA 13200/244 V. (Metodologia eksperymentalnego okrelania parametrw modelu transformatora)

Keywords: Transformer, diagnostic tests, equivalent circuit, parameters, frequency response analysis.
Sowa kluczowe: transformator, model transformatora, pomiary

Introduction
The model is "an approximation, representation, or
idealization of aspects related to the structure, behavior, or
operation of a real-world process, concept, or system" [1].
Transformer modeling is focused on from different
perspectives, finding a wide panorama in the numerous and
diverse research works carried out, which shows the
complexity of the theme [2],[3],[4],[5],[6],[7],[8].
Transformer model parameters are usually obtained Fig. 2. The no-load transformer circuit (50-60 Hz).
from the physical transformer characteristics, implying its
dismantling or working in partnership with the manufacturer If the secondary is short-circuited and a voltage is
that has the design and construction information; this is applied in the primary so that nominal currents I1 and I2
quite difficult because manufacturers usually do not provide circulate, which are much higher than the magnetization;
information on designs and materials used in the the effects of the windings (RH, LH, RL, LL) are now
construction of their transformers. dominant in the circuit and the magnetizing branch is
Alternatives have been proposed to build the neglected, Fig. 3.
transformer model by using data from field tests [6], [7], [8],
and [9], which makes it viable to obtain the model for
installed transformers. This work shows a procedure to
obtain the parameters for a physical extended circuital
classic transformer model, where it is assumed that:
- The parameters are concentrated.
- The parameters are not frequency dependent.

Transformer Circuit Physical model


The transformer at low frequency
The operation principle of the transformer at low Fig. 3.The short-circuited transformer circuit (50-60 Hz).
frequency (60-50 Hz) and without load is shown in Fig. 1,
where an alternating voltage on the primary side creates a For the transformer with normal load, the two previous
time-varying flow that magnetically concatenates the two conditions should be considered, leading to the equivalent
windings. circuit shown in Fig. 4.

d (t ) d(t)
e1 (t ) N1 e2 (t) N2
dt dt

Fig. 1. Transformer without load.


Fig. 4. The normal load transformer circuit (50-60 Hz).
When the transformer is without load, the time-varying
flow is created by the current flowing through the primary The transformer at mid frequencies
winding, given that this current is very small, winding losses If the transformer is analyzed at medium frequency, the
and leakage flux are neglected. Assuming that all the flux is capacitances between windings (CHL) and from these to
concentrated in the magnetic core (Rexc-Lexc), the equivalent earth (CH and CL) became important, as well as the series
transformer circuit is shown in Fig. 2. winding capacitances or internal capacitances Fig. 5.

12 PRZEGLD ELEKTROTECHNICZNY (Electrical Review), ISSN 0033-2097, R. 88 NR 9a/2012


Having Rexc, the Ife current can be obtained and the
magnetizing current Im can be calculated:
2
V
(1) I m Io
2 2

Rexc
Knowing the magnetization current Im, the excitation
inductance (Lexc) can be calculated:

Fig. 5. Internal winding capacitances. V


Lexc
2
The transformer circuit is modified at high frequency by (2) V
2f * I 0
2
the effect of the capacitances mentioned, along with the
capacitance associated with the magnetic core sheets or Rex
excitement capacitance (Cexc). The circuit transformer for
medium frequencies will be the shown in Fig. 6 which is Open circuit test in mid frequencies
known as the frequency extended classic physical-circuital The Cexc magnetizing capacitance begins to take effect
transformer model [9], [10], [11]. at frequencies above the nominal (Fig. 8), reaching the
condition of resonance with the excitation inductance Lexc,
at a frequency value denominated as Fn_Open.

Fig. 8. Branch magnetization at mid frequency.


Fig. 6. The frequency extended classic physical-circuital
transformer model. The resonance frequency (Fn_open) can be found from
the open circuit frequency response test (Fig. 12), and with
For high frequencies, the circuit components of Fig. 6 this value Cexc can be calculated:
should be considered distributed parameters and also
frequency dependent. 1
(3) Cexc
Procedure for obtaining the model parameters ( 2 * f n _open ) 2 * Lexc
The parameters for the model in Fig. 8 model can be Winding resistance test
obtained by external measurements [9], [12], using the In this test a DC voltage is applied to one transformer
results of the following tests: winding and the current is measured, with the other
windings open. With the current, the winding resistance
The no-load test values can be calculated (rDC).
In this test, a voltage of 60 Hz AC is applied over one
transformer side (usually the high voltage side), while the (4) VDC
other end is in open circuit. Neglecting the winding losses
rDC
I
and assuming no leakage flux, Fig. 7 shows the equivalent
no-load transformer circuit at low frequency, where I0 is the The transformer ratio test
total current, Im the current necessary to generate the core The transformation ratio test gives the turns ratio
magnetic flow, and Ife the current due to the losses in the between high-voltage and low-voltage windings. This a
magnetic material. relationship is used to refer to the parameter values from
one winding to another.

Leakage reactance test (short circuit)


In this test, a frequency sinusoidal voltage is applied to a
transformer winding (usually high voltage), while the other
winding is short-circuited, as shown in Fig. 9. The currents
must be equal to or close to the nominal values.

Fig. 7. The no-load current (50-60 Hz).

From the values of voltage V, current I0, and active


losses W, measured in the test, resistance (Rexc) and
excitation inductance (Lexc) values are determined. The Rexc
resistance is found from the active loses:
Fig. 9. The transformer under short-circuit condition.
V2
(1) Rexc
W

PRZEGLD ELEKTROTECHNICZNY (Electrical Review), ISSN 0033-2097, R. 88 NR 9a/2012 13


The core effect is negligible because the excitation Transformer test short-circuited in high frequency
voltage is nearly zero. When measuring the resistance of a When the transformer is in short-circuit condition and
winding, the other winding resistance will be present, but the frequency increases, the value associated with the
both values are referred to the measurement side, i.e. the windings series capacitive reactance decreases while their
high voltage side in Fig. 10. inductive reactance increase, until they reach resonance
condition. When the short circuit is at the low voltage side
the CSL effect is canceled, only impacting on the CSH
capacitance (Fig. 11). The reverse condition occurs if the
short circuit is at the high voltage side.

Fig. 10. Transformer short-circuit condition referred to the high


voltage side.

With the total current I and the measured active Wcc loss
values, the total AC resistance can be calculated (RH_AC in
the high voltage case):

(5) W
R cc
H_AC I2
But the RH_AC resistance seen from the high voltage side
Fig. 11. Equivalent circuit short-circuited in high frequency
involves the resistance of both windings:
The short-circuit resonance frequency, Fn_short, can be
(6) R R a 2 RL found in the transformer frequency response curves
H_AC H
(Figures 14 and 15). Given that LH and LL are known, the
It can be assumed that the relationship between the CSH and CSL values can be calculated by using Eqs. 14 and
values of DC resistance in (rL-DC and rH-DC) is approximately 15, respectively.
equal to the AC resistance ratio (RH and RL) [13], [14]:
(12) 1
Cs H
(7) RL r
L _ DC ( 2 * f H _ short ) 2 * LH
RH rH _ DC 1
CS L
From (7) and (8), the value of RH can be found:
(13) ( 2 * f L _ short ) 2 * LL
The Capacitance test
(9) RH _ AC With this test, the transformer total capacitances CH, CL,
With RH, it can RH be found RL
r and CHL are measured directly.
(Eq.7). 1 a 2 * L _ DC
r
H _ DC The SFRA test
The equivalent inductance LHeq can be calculated using The seep frequency response test, or SFRA, provides
Eq. (10). information about the impedance or admittance transformer
over a wide frequency range. It is a tool for evaluating the
transformers mechanical condition and it can be used to
(8) V Z * I ( RH _ AC ) 2 (2 * * f * LHeq ) 2 * I identify the high side and low side winding resonant
frequencies [15], [16], [17] y [18].
The equivalent inductance LHeq, involves the low side
and high side windings:
2
(9) L L a L
Heq H L

Assuming for the inductances the same relationship that


for DC resistances [13], [14]:
rL _ DC LL
(10)
From (11) and rH _ DC LH (12), the high voltage
winding inductance LH, can be calculated
(Eq 13):

Fig. 12. Open circuit resonant frequency (FL_open).


LHeq
(11) LH Although the SFRA test can be performed with different
r
1 a 2 * L _ DC connection configurations [15]19], for finding the resonant
r frequencies, it can be used the SFRA curves obtained from
H _ DC the high side under open circuit condition and from the low
side under short-circuit condition. The Fig. 12 shows the
frequency response obtained at the high side winding with
Once LH is obtained, it can be found LL Eq. (11). the low side under open circuit condition, where the first

14 PRZEGLD ELEKTROTECHNICZNY (Electrical Review), ISSN 0033-2097, R. 88 NR 9a/2012


resonant point corresponds to the open circuit resonance [2] J. A. Martinez, B. A. Mork. Transformer Modeling for Low- and
frequency FL_open [20], [21]. Mid-Frequency TransientsA Review. IEEE Transactions on
Fig. 13 shows the frequency response obtained at the Power Delivery, Vol. 20, No. 2, April 2002.
[3] Pleite J., Olas E., Barrado A., Lzaro A., Vzquez J.
high side winding with the low side under short-circuit
Transformer Modeling for FRA Techniques. IEEE-PES
condition, where the resonant point corresponds to the Transmission and Distribution Conf./Exhib. 2002 Asia Pacific.
short circuit resonance frequency FL_short [20], [21]. [4] C. C. Brozio. Wideband Modeling and Parameter Estimation of
Two-Winding Transformers. Doctoral Thesis. University of
Stellenbosch. South Africa. 1998.
[5] E. E. Mombello. Representation circuit model for transient
behavior during the resonance transformer with consideration
of the losses. Doctoral Thesis. Universidad Nacional de San
Juan, Argentina, 1998.
[6] E. Bjerkan. High Frequency Modeling of Power Transformers.
Doctoral Thesis. Norwegian University of Science and
Technology, Norway. 2005.
[7] K. Ragavan. An Efficient Solution to Generalized Model of a
Transformer Winding and Localization of Discrete Changes
Based on Measurements. Doctoral Thesis. Indian Institute of
Science. India. 2006.
[8] C. Gonzlez Garca. Modeling Discussion and Analysis of
Fig. 13. Short circuit resonant frequency (FL_short). Power Transformer from its frequency response. Master's
thesis, Universidad Carlos III de Madrid, 2009.
Model case [9] Long Pong, Modeling A Transformer With Double M Series
The procedure mentioned above was applied to find the Instruments 2004. Double Engineering Company.
[10] J. Pleite G. Modeling tool for predictive maintenance of
model for a single-phase transformer 13200/244 V, 15 KVA. transformers based on the Analysis of Frequency Response.
Once all the circuit model parameters were obtained (Fig. Thesis PhD. Universidad Carlos III de Madrid 2000.
6), the model was implemented in the Matlab simulation [11] E. Al-Ammar and G.G. Karady, Transfer function analysis
tool. Fig. 14, shows the measured and the modeled using STFT for improvement of the fault detection sensitivity in
frequency response curves, it can be observed that at low transformer impulse test, IEEE Power Engineering Society
and medium frequencies the measured and the modeled General Meeting, pp. 534-541; 2005.
curves have a good approximation. [12] Carlos A. Mesa. Obtaining the parameters of a physical model
of a transformer of circuit. Undergraduate Thesis 2010.
Universidad del Valle. Faculty of Electrical Engineering.
Research Group High Voltage.
[13] Bouchard, Ral-Paul lectrotechnique Quatrime ditions,
Cours 3.408, Dpartement de gnie lectrique, cole
Polytechnique de Montral, Canada, 1987, page 29.
[14] Vembu Gourishankar, Electromechanical energy
conversion", representation and engineering services, SA
Mexico 1975.
[15] J. Pleite, C. Gonzlez, "Seminar FRA, diagnosis of
transformers based on Frequency Response", Universidad
Carlos III de Madrid 2008.
[16] Frequency Response Analysis on Winding Deformation of
Power Transformers. The Electric Power Industry Standard of
People's Republic of China.
Fig. 14. FRA curve in open circuit, modeled and simulated
[17] Document 15182-2005.IEEE PC57.149/D8, Draft trial use.
Conclusions "Guide for the Application and Interpretation of Frequency
Response Analysis for Oil Immersed Transformers". 2009.
A simple procedure was developed to obtain the
[18] Working Group A2.26, CIGRE, Brochure 342. Mechanical
transformer physical circuit model parameters, based on condition assessment of transformer windings using Frequency
external measurements. Response Analysis (FRA). April 2008.
This model can be used to obtain the transformer [19] IEC 14/626CD (C0mmitte Draft) 60076-18 Ed.1: Power
frequency response, showing acceptable performance transformers - Part 18: Measurement of frequency response.
when comparing the modeled and the measured curves in November 2009.
the range of low and medium frequencies. [20] GRALTA, Research Group. Evaluation of the mechanical
The transformer physical-circuital model permits condition of the transformers by analyzing the frequency
response - use of physical and circuital model. Universidad del
establishing a direct relationship between its parameters
Valle, technical Report, 2010.
and the transformer physical elements, which can be used [21] G. Aponte, C. E. Castao, C. Gonzlez, A. Garcia, The use of
to associate the SFRA curve variations with real FRA technique for diagnosis of transformers. International
transformer changes. conference on high voltage isolation. ALTAE, Medelln,
Although the model most be adjusted, it can become a Colombia. 2009.
useful tool for supporting transformer diagnostic work,
particularly for use in SFRA application. Authors: Prof. Guillermo Aponte M.,
E-mail: guillermo.aponte@correounivalle.edu.co,
ACKNOWLEDGMENTS Prof. Hctor Cadavid Ramrez
The authors express their gratitude to COLCIENCIAS and E-mail: hector.cadavid@correounivalle.edu.co
EPSA for their support for this work. Student Ph.D, Eduardo Gmez Luna,
E-mail: eduardo.gomez@correounivalle.edu.co
REFERENCES Universidad del Valle, Cali-Colombia, Calle 13 #100-00.
[1] IEEE Std. 610.3 -1989. IEEE Standard Glossary of Modeling Prof. Juan Carlos Burgos.,. jcburgos@ing.uc3m.es
and Simulation Terminology. Standards coordinating University Carlos III, Madrid-Espaa. Avenida de la Universidad
committee, of the IEEE computer society. January 1, 1989. 30, 28911-Legans

PRZEGLD ELEKTROTECHNICZNY (Electrical Review), ISSN 0033-2097, R. 88 NR 9a/2012 15

Das könnte Ihnen auch gefallen