PRODUCTS: FINPOWER AHU FAHU (UAE)
PROJECTS: PROP B+G+M+2 FLR @ AL MESHAWAR CONTRACTOR : M/S BIN SHAFAR
THERMALWHEEL
SUPPLYFAN RETURN EXTRACT SUPPLY
ESP FANESP AIRON AIROFF AIRON AIROFF
QTY QA RA
No CFM Pa CFM Pa DB1 WB1 DB2 WB2 DB1 WB1 DB2 WB2
(C) (C) (C) (C) (C) (C) (C) (C)
UNITREFERENCE
FAHU 1 3680 - 2543 - - - - - - - - -
FF-AHU-01 1 4874 - - - - - - - - - - -
FF-AHU-02 1 5880 - - - - - - - - - - -
MZ-AHU - 01 1 15848 - - - - - - - - - - -
G-AHU-01 1 14198 - - - - - - - - - - -
FF-AHU-03 1 18435 - - - - - - - - - - -
FF-AHU-04 1 15893 - - - - - - - - - - -
G-AHU-01 1 12714 - - - - - - - - - - -
THERMALWHEEL
SUPPLYFAN RETURN EXTRACT SUPPLY
ESP FANESP AIRON AIROFF AIRON AIROFF
QTY QA RA
No CFM Pa CFM Pa DB1 WB1 DB2 WB2 DB1 WB1 DB2 WB2
UNITREFERENCE UNITMODEL (C) (C) (C) (C) (C) (C) (C) (C)
FAHU FAHU-SK50T-PW-FM-64 1 3560 500 2543 500 25 18.7 42.1 28.2 46 30 33.8 24.4
Legend
QA - Quantity of Air (CFM) TW2 - Chilled Water Leaving Temp (deg C)
SPECIFIEDDATA
HEATPIPEPRE-COOLING COOLINGCOIL HEATPIPERE-HEATING
AIRONPRECOOL AIROFFPRECOOL AIRONCOIL AIROFFCOIL Total Sensible TW1 TW2 QW Refrigerant WPD VW AIRONRE-
HEATING
DB1 WB1 DB2 WB2 DB1 WB1 DB2 WB2 TR KW KW (C) (C) (L/S) (KPA) (M/S) DB1
(C) (C) (C) (C) (C) (C) (C) (C) (C)
- - - - - - - - 25 - - - - - - - -
- - - - - - - - 18 - - - - - - - -
- - - - - - - - 15 - - - - - - - -
- - - - - - - - 45 - - - - - - - -
- - - - - - - - 30 - - - - - - - -
- - - - - - - - 30 - - - - - - - -
- - - - - - - - 30 - - - - - - - -
- - - - - - - - 30 - - - - - - - -
PROPOSEDDATA
HEATPIPEPRE-COOLING COOLINGCOIL HEATPIPERE-HEATING
AIRONPRECOOL AIROFFPRECOOL AIRONCOIL AIROFFCOIL Total Sensible TW1 TW2 QW Refrigerant WPD VW AIRONRE-
HEATING
DB1 WB1 DB2 WB2 DB1 WB1 DB2 WB2 TR KW KW (C) (C) (L/S) (KPA) (M/S) DB1
(C) (C) (C) (C) (C) (C) (C) (C) (C)
33.8 24.4 27.9 22.88 27.9 22.88 14.1 13.79 16 56.45 27.88 5.5 12.2 2.01 ChilledWater 45 1.13 14.1
- - - - 24 18.4 9.86 9.76 18 63.17 39.41 5.5 12.2 2.25 ChilledWater 56 1.19 -
1/1
HEATPIPERE-HEATING
RETURN
SUPPLYFAN
FANMotor
AIRONRE- AIROFFRE- Motorcapacity
capacity
HEATING HEATING Pefilter BagFilter DIMENSIONSINMM WEIGHT
WB1 DB2 WB2 (KW) QTY (KW) QTY LENGTH HEIGHT WIDTH KG
(C) (C) (C)
- - - - - - - - - - - - -
- - - - - - - - - - - - -
- - - - - - - - - - - - -
- - - - - - - - - - - - -
- - - - - - - - - - - - -
- - - - - - - - - - - - -
- - - - - - - - - - - - -
- - - - - - - - - - - - -
HEATPIPERE-HEATING
RETURN
SUPPLYFAN
FANMotor
AIRONRE- AIROFFRE- Motorcapacity
capacity
HEATING HEATING Pefilter BagFilter DIMENSIONSINMM WEIGHT
WB1 DB2 WB2 (KW) QTY (KW) QTY LENGTH HEIGHT WIDTH KG
(C) (C) (C)
13.79 20 15.8 G4 F7/MERV13 4 1 2.2 1 3965 1830 1630 1251