Series Concepts

Best suited functions for


HVAC application

Contribution to energy-saving

A broad range of model variations

Easy maintenance

Simple operation

Global products

The HVAC Inverter


Series
is an inverter exclusively designed for fans and pumps.
Developed by Fuji Electric, a leading inverter company, to meet global needs for economy.

Features such as the special functions for the HVAC (Heating, Ventilating, and Air-Conditioning) market,
space saving, simple operation, a wide variety of models and global compatibility contribute
to energy-savings and power-savings for variable torque load equipment.
Requirements for total cost reduction in the fan and pump can be easily met with the FRENIC-Eco.

2
Default functions for fans and pumps

Line/inverter switching Switching among remote/panel/independent


A line frequency starting program for the inverter is installed inverter operation modes
to support line/inverter switching through an external Through frequency setting 1 and frequency setting 2,
sequence. As well, two types of line/inverter operation operation/stop command 1 and operation/stop command 2,
switching sequences are built in: Fuji's standard sequence and local operation (keypad operation), the
and automatic line switching sequence at an inverter fault. remote/panel/independent inverter operation modes can be
selected for both operation commands and frequency
commands.

Full PID control functions Various frequency setting methods


A "small water flow stopping function" and "deviation The best method can be selected for the frequency setting
alarm/absolute value alarm output" are added to the PID according to the frequency signal to be used.
regulator that controls the temperature, pressure, flow rate Keypad operation ( and keys), analog input (4 to
and so on. Further, an anti-reset wind-up function for the 20mA, 0 to +5V, 0 to +10V, +1 to +5, normal or inverse
prevention of overshooting in the PID control, PID output operation), 8-step multi-step frequency (step 0 to 7)
limiter and integration hold/reset signals are provided as setting, UP/DOWN operation, communication, etc.
easy-to-adjust PID control functions.

Continued operation upon momentary power failure Motor pick-up during idling
The inverter automatically restarts upon recovery from If the motor runs due to natural convection or other similar
momentary power failure. You can choose starting at the situations, you can use the pick-up function to start smoothly.
frequency at momentary power failure occurrence or starting
at 0Hz. Another option can be chosen: Operation continues Sleep function with low limiter
at a lower frequency while using the kinetic energy obtained
A function for stopping the fan or pump at speeds lower than
from the inertia of the load at momentary power failure.
the lower limit is provided to assure the minimum speed. The
function can be used also to stop at a low water flow.

Energy
saving
Contribution to energy-saving
110
Automatic energy-saving 100
Energy savings effect
(Energy savings effect varies depending on the motor characteristics.)
operation function
In addition to the motor loss, the inverter loss is also kept to 90
a minimum with the FRENIC-Eco when applied to fans or When damper or valve is used
80
pumps.
Required power P[%]

70
Capable of electric power monitoring
60
Simplified monitoring of the electric power can be done
through the keypad and the communication ports (power 50 Energy saved
consumption, cumulative watt-hour display, watt-hour
application display, etc.) 40

30
Cooling fan ON/OFF control function Inverter control (V/f control)
20
The inverter's cooling fan can be stopped for noise reduction
and energy savings whenever the motor is stopped. Inverter control
10 (Automatic energy-saving mode)

0 10 20 30 40 50 60 70 80 90 100
Air or liquid flow rate Q [%]

1. Use the contents of this catalog only for selecting product types and models. When using a product, read the Instruction
Manual beforehand to use the product correctly.
2. Products introduced in this catalog have not been designed or manufactured for such applications in a system or equipment
Safety that will affect human bodies or lives. Customers, who want to use the products introduced in this catalog for special systems
Precautions or devices such as for atomic-energy control, aerospace use, medical use, and traffic control, are requested to consult the
Fuji's Sales Division. Customers are requested to prepare safety measures when they apply the products introduced in this
catalog to such systems or facilities that will affect human lives or cause severe damage to property if the products become
faulty.

3
Consideration for surrounding environment

Semi-standard series integrated with DC REACTOR Semi-standard series integrated with EMC filter
(available soon) (available soon)
In this series, the Guideline for Suppressing Harmonics can The product can be used to comply with the EMC Directives
be satisfied by integrating optional DC REACTOR (DCR) for in EU. (15kW or smaller [planned])
harmonic suppression. (55kW or smaller [planned])

All models are equipped with Standard installation of input terminals for
an inrush current suppression circuit. auxiliary control power of all models
An inrush current suppression circuit is provided as standard The terminal is convenient for automatic line/inverter
in all models, therefore the cost of peripheral devices such switching operation as the control power of the inverter is
as magnetic switches can be reduced. standardized.

Easy maintenance and many protective functions

The lifetime of the main circuit capacitor The alarm history for the
can be estimated. 4 latest alarms is recorded.
Because the capacitor's life compared with its initial value Detailed information from back as far as the latest 4 alarms
can be checked, the replacement timing of the main circuit can also be checked.
capacitor can be determined.

A long-life cooling fan is provided. Protective function against phase loss in


Use of a long-life cooling fan (design life: 7 years for models input/output
smaller than 5.5kW); 4.5 years for models higher than 7.5 Protection against phase loss in input/output circuits is
and up to 30kW [at ambient temperature: 40˚C]) reduces possible upon start-up and operation.
replacement work.

Cumulative running time is recorded Protective function for grounding fault


and displayed. Protection is provided for an overcurrent caused by a
The inverter records and displays the cumulative "motor grounding fault.
running time" and "inverter running time" (PC board capacitor
running time, cooling fan running time), so that they can be
used to defermine machine and inverter maintenance.

It is possible to output lifetime Protection of motor with PTC thermistor


forecast signal to the transistor output. In addition to the protection of the motor with an electronic
This signal is output when the main circuit capacitors in the thermal relay, a PTC thermistor can be used for motor
DC bus circuit, the electrolytic capacitors on the PC boards protection.
or the cooling fans are nearing the end of their service life.

Simple operation and wiring

Standard keypad capable of Quick setup function


remote operation Only the 19 minimum function codes are displayed to set up
The optional extension cable allows easy remote operation. drives for fan or pump applications.
Data can be easily copied to the second or more inverters
with the code copying function. Multi-function keypad
(option; available soon)
A backlit LCD is installed to allow simple set up through
interactive data entry. Function codes can be added or
deleted to or from the 19 function codes within the quick
setup function.

4
Global products

All standard models comply with the EC Directive (CE marking),


UL standards and Canadian standards (cUL certification).
All standard FRENIC-Eco inverters comply with European and North American/Canadian standards, enabling standardization of
the specifications for machines and equipment used at home and abroad.

If the model with built-in EMC filter (available soon) is used,


the model conforms to the European EMC Directive (15kW or smaller).

Europe / EC North America/Canada


Directive (CE marking) UL standard (cUL certification)

Sink/source switching Network support (available soon)


The input/output mode (sink/source) of the digital input With an optional card, the inverter becomes compatible with
terminals can be easily switched. various open buses such as DeviceNet, PROFIBUS-DP,
LonWorks network, Modbus Plus or CC-Link. A standard
RS485 communication port (Modbus RTU) is provided. With
an additional RS485 communication card (optional), up to
two more ports can be installed.

Space saving

Side-by-side mounting is possible.


When multiple inverter units are installed inside a panel, the installation space can be minimized. (5.5kW or less, ambient
temperature: 40˚C or less)

260

150 150 150


(Unit : mm)
(Ex.: 3-phase 200V 5.5kW)

5
Flexible through optionals
Inverter loader software (option; available soon)
The inverter loader program (Windows-based, option), which simplifies setting of function codes, and data management, is
provided.

RS485 communications

(RJ-45 connector)
PC

Converter

USB cable

Remote operation is possible.


Remote operation can be done easily using the optional
extension cable.

Keypad

Extension cable for


remote operation

Function code copy function External cooling attachment


Because the optional multi-function keypad (available soon) An external cooling attachment (Option for 30kW or smaller ;
is provided with a built-in copy function, similar to that available soon. Standard for 37kW or larger) cools the
installed in the main body as a standard feature, data can be inverter outside the panel. It can be easily mounted on the
easily copied to the second inverters without requiring panel.
individual setups.

6
Use the contents of this catalog only for selecting product types and
Caution
Variation
models. When using a product, read the Instruction Manual
beforehand to use the product correctly.

Standard specifications

Applicable motor rating [kW] Three-phase 200V series Three-phase 400V series
 0.75 FRN0.75F1S-2A FRN0.75F1S-4A
 1.5 FRN1.5F1S-2A FRN1.5F1S-4A
 2.2 FRN2.2F1S-2A FRN2.2F1S-4A
 3.7 FRN3.7F1S-2A FRN3.7F1S-4A
 5.5 FRN5.5F1S-2A FRN5.5F1S-4A
 7.5 FRN7.5F1S-2A FRN7.5F1S-4A
 11 FRN11F1S-2A FRN11F1S-4A
 15 FRN15F1S-2A FRN15F1S-4A
 18.5 FRN18.5F1S-2A FRN18.5F1S-4A
 22 FRN22F1S-2A FRN22F1S-4A
 30 FRN30F1S-2A FRN30F1S-4A
 37 FRN37F1S-2A FRN37F1S-4A
 45 FRN45F1S-2A FRN45F1S-4A
 55 FRN55F1S-2A FRN55F1S-4A
 75 FRN75F1S-2A FRN75F1S-4A
 90 FRN90F1S-2A FRN90F1S-4A
110 FRN110F1S-2A FRN110F1S-4A
132 FRN132F1S-4A
160 FRN160F1S-4A
200 FRN200F1S-4A
220 FRN220F1S-4A
280 FRN280F1S-4A
315 FRN315F1S-4A
355 FRN355F1S-4A
400 FRN400F1S-4A
450 FRN450F1S-4A
500 FRN500F1S-4A

Available soon

How to read the model number

FRN 5.5 F 1 S - 2 A 5 1 1
Code Series name Code Control terminal block
FRN FRENIC series 1 Screw terminal (standard)
2 Rod terminal
Code Applicable motor rating [kW]
 0.75  0.75kW Code Built-in option
 1.5  1.5kW 1 None
 2.2  2.2kW 2 RS485 communication card
 3.7  3.7kW
 5.5  5.5kW Code Keypad
 7.5  7.5kW 1 Keypad (standard)
 11  11.kW Multi-function keypad
5
(Available soon)
 15  15.kW
9 No keypad

450  450.kW
500  500.kW Code Version/Manual
A Asia/English

Code Application range


Code Input power supply
F For fans and pumps
Multi-function keypad 2 3-phase 200V
(For variable torque load) 4 3-phase 400V

Code Developed inverter series Code Structure


1 1 S Standard type
E Type integrated with EMC filter
H Type integrated with DC REACTOR

Note : When the last three digits of the model number is for a keypad (standard), non built-in option, screw terminal (standard), the model number with a standard specification
 in the above model number table will apply.

7
Standard specifications

Standard specifications
Three-phase 200V series
Item Specifications
Type (FRN F1S-2A) 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 110

Applicable motor rating *1) kW 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 110

Rated capacity *2) kVA 1.6 2.6 3.8 6.2 8.3 11 16 21 25 30 40 49 59 75 102 121 146
Output ratings

Rated voltage *3) V Three-phase, 200V/50Hz, 200, 220, 230, 240V/60Hz (With AVR function)

Rated current *4) A 4.2 7.0 10 16.5 22.5 29 42 55 68 80 107 130 156 198 270 320 384

Overload capability 120% of rated current for 1min

Rated frequency 50, 60Hz

Three-phase, 200 to 220V/50Hz


Main power supply Three-phase, 200 to 240V, 50/60Hz Three-phase, 200 to 230V/60Hz
Phases, voltage,
frequency
Auxiliary control Single-phase, 200 to 220V/50Hz
Input ratings

Single-phase, 200 to 240V, 50/60Hz


power input Single-phase, 200 to 230V/60Hz

Voltage/frequency variations Voltage: +10 to -15% (Voltage unbalance: 2% or less (*8)), Frequency: +5 to -5%

(with DCR) 3.2 6.1 8.9 15.0 21.1 28.8 42.2 57.6 71.0 84.4 114 138 167 203 282 334 410
Rated current *5) A
(without DCR) 5.3 9.5 13.2 22.2 31.5 42.7 60.7 80.1 97.0 112 151 185 225 270 - - -

Required power supply capacity *6) kVA 1.2 2.2 3.1 5.3 7.4 10 15 20 25 30 40 48 58 71 98 116 142
Braking

Torque *7) % 20 10 to 15

DC injection braking Starting frequency: 0.0 to 60.0Hz, Braking time: 0.0 to 30.0s, Braking level: 0 to 60%

DC REACTOR(DCR) Option Standard

Applicable safety standards UL508C, C22.2No.14, EN50178:1997(Applying)

Enclosure(IEC60529) IP20 UL close type IP00 UL open type

Cooling method Natural cooling Fan cooling

Weight / Mass kg 3.3 5.6 6.6 9.3 9.5 11.7 23 31 34 41

*1) Fuji's 4-pole standard motor


*2) Rated capacity is calculated by assuming the output rated voltage as 220V for three-phase 200V series.
*3) Output voltage cannot exceed the power supply voltage.
*4) When setting the carrier frequency (F26) to 1 kHz, reduce the load to 80% of its rated value.
*5) Calculated under Fuji-specified conditions.
*6) Obtained when a DC REACTOR is used.
*7) Average braking torque without optional braking resistor (Varies with the efficiency of the motor.)
Max. voltage [V] - Min. voltage [V]
*8) Voltage unbalance [%] = x 67 (IEC61800-3(5.2.3))
Three-phase average voltage [V]
 If this value is 2 to 3%, use an AC REACTOR.

8
Standard specifications
Three-phase 400V series (0.75 to 55kW)
Item Specifications
Type (FRN F1S-4A) 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55

Applicable motor rating *1) kW 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55

Rated capacity *2) kVA 1.9 2.8 4.1 6.8 9.5 12 17 22 28 33 44 54 64 77


Output ratings

Rated voltage *3) V Three-phase, 380, 400V/50Hz, 380, 400, 440, 460V/60Hz (with AVR function)

Rated current *4) A 2.5 3.7 5.5 9.0 12.5 16.5 23 30 37 44 58 71 84 102

Overload capability 120% of rated current for 1min

Rated frequency 50, 60Hz

Three-phase, 380 to 440V/50Hz


Main power supply Three-phase, 380 to 480V, 50/60Hz Three-phase, 380 to 480V/60Hz
Phases, voltage,
frequency
Auxiliary control Single-phase, 380 to 440V/50Hz
Input ratings

Single-phase, 380 to 480V, 50/60Hz


power input Single-phase, 380 to 480V/60Hz

Voltage/frequency variations Voltage: +10 to -15% (Voltage unbalance: 2% or less (*8)), Frequency: +5 to -5%

(with DCR) 1.6 3.0 4.5 7.5 10.6 14.4 21.1 28.8 35.5 42.2 57.0 68.5 83.2 102
Rated current *5) A
(without DCR) 3.1 5.9 8.2 13.0 17.3 23.2 33.0 43.8 52.3 60.6 77.9 94.3 114 140

Required power supply capacity *6) kVA 1.2 2.2 3.1 5.3 7.4 10 15 20 25 30 40 48 58 71
Braking

Torque *7) % 20 10 to 15

DC injection braking Starting frequency: 0.0 to 60.0Hz, Braking time: 0.0 to 30.0s, Braking level: 0 to 60%

DC REACTOR(DCR) Option

Applicable safety standards UL508C, C22.2No.14, EN50178:1997(Applying)

Enclosure (IEC60529) IP20 UL close type IP00 UL open type

Cooling method Natural cooling Fan cooling

Weight / Mass kg 3.3 5.6 5.7 6.6 9.2 10.3 11.7 23 23 30

Three-phase 400V series (75 to 500kW)


Item Specifications
Type (FRN F1S-4A) 75 90 110 132 160 200 220 280 315 355 400 450 500

Applicable motor rating *1) kW 75 90 110 132 160 200 220 280 315 355 400 450 500

Rated capacity *2) kVA 105 128 154 182 221 274 316 396 445 495 584 640 731
Output ratings

Rated voltage *3) V Three-phase, 380, 400V/50Hz, 380, 400, 440, 460V/60Hz (with AVR function)

Rated current *4) A 139 168 203 240 290 360 415 520 585 650 740 840 960

Overload capability 120% of rated current for 1min

Rated frequency 50, 60Hz

Three-phase, 380 to 440V, 50Hz


Main power supply
Phases, voltage, Three-phase, 380 to 480V, 60Hz
frequency
Auxiliary control Single -phase, 380 to 480V, 50/60Hz
Input ratings

power input

Voltage/frequency variations Voltage: +10 to -15% (Voltage unbalance: 2% or less (*8)), Frequency: +5 to -5%

(with DCR) 138 164 201 238 286 357 390 500 559 628 705 789 881
Rated current *5) A
(without DCR) - - - - - - - - - - - - -

Required power supply capacity *6) kVA 96 114 140 165 199 248 271 347 388 435 489 547 611
Braking

Torque *7) % 10 to 15

DC injection braking Starting frequency: 0.0 to 60.0Hz, Braking time: 0.0 to 30.0s, Braking level: 0 to 60%

DC REACTOR(DCR) Standard

Applicable safety standards UL508C, C22.2No.14, EN50178:1997(Applying)

Enclosure (IEC60529) IP00 UL open type

Cooling method Fan cooling

Weight / Mass kg 35

*1) Fuji's 4-pole standard motor


*2) Rated capacity is calculated by assuming the output rated voltage as 440V for three-phase 400V series.
*3) Output voltage cannot exceed the power supply voltage.
*4) When setting the carrier frequency (F26) to 1 kHz, reduce the load to 80% of its rated value.
*5) Calculated under Fuji-specified conditions.
*6) Obtained when a DC REACTOR is used.
*7) Average braking torque without optional braking resistor (Varies with the efficiency of the motor.)
Max. voltage [V] - Min. voltage [V]
*8) Voltage unbalance [%] = x 67 (IEC61800-3(5.2.3))
Three-phase average voltage [V]
 If this value is 2 to 3%, use an AC REACTOR.

9
Common specifications

Common specifications
Item Explanation Remarks Related
function code
Maximum frequency 25 to 120Hz F03
Setting range

Base frequency 25 to 120Hz F04


Starting frequency 0.1 to 60.0Hz F23
Carrier frequency • 0.75 to 15kHz (200V/400V:0.75 to 22kW) The carrier frequency may drop automatically according to the F26
Output frequency

• 0.75 to 10kHz (200V/400V:30 to 75kW) ambient temperature or output current to protect the inverter. F27
• 0.75 to 6kHz (200V/400V:90 to 500kW) This protective operation can be canceled by function code H98
H98.
Accuracy (Stability) • Analog setting: ±0.2% of maximum frequency (at 25±10˚C)
• Keypad setting: ±0.01% of maximum frequency (at -10 to +50˚C)
Setting resolution • Analog setting: 1/1000 of maximum frequency (ex. 0.06Hz at 60Hz, 0.12Hz at 120Hz)
Setting with , keys.
• Keypad setting: 0.01Hz (99.99Hz or less), 0.1Hz (100.0Hz or more)
• Link setting: Selectable from 2 types-
• 1/20000 of maximum frequency (ex. 0.003Hz at 60Hz, 0.006Hz at 120Hz)
• 0.01Hz (fixed)
Control method V/f control
Voltage/freq. characteristic Possible to set output voltage at base frequency and at maximum output frequency Three-phase 200V: 80 to 240V F03 to F05
(common spec.). AVR control can be turned ON or OFF. Three-phase 400V: 160 to 500V
(Non-linear V/f setting) 1 point (Arbitrary voltage and frequency can be set.) Three-phase 200V: 0 to 240V/0 to 120Hz H50, H51
Three-phase 400V: 0 to 500V/0 to 120Hz
Torque boost Torque boost can be set with the function code F09. Set when 0, 1, 3, or 4 is selected at F37. F09, F37
(Load selection) Select application load type with the function code F37. F09, F37
0: Variable torque load 1: Variable torque load (for high starting torque) 2: Auto-torque boost
3: Auto-energy-saving operation (variable torque load in acceleration/deceleration)
4: Auto-energy-saving operation (variable torque load (for high starting torque) for acceleration/deceleration)
5: Auto-energy-saving operation (auto-torque boost in acceleration/deceleration)
Starting torque 50% or over
Start/stop Keypad Keypad (standard) F02
Start (FWD/REV) and stop with , keys
operation
Multi-function keypad (optional) F02
Start and stop with / , keys

External signals (7 digital inputs): Forward (reverse) rotation, stop command (capable of 3-wire E01 to E05
operation), second operation command, coast-to-stop command, external alarm, alarm reset, etc. E98, E99
Link operation: Operation through RS485 communication and Field Bus communication (option) H30, y98
Operation command switch: Remote/local switch, link switch, second operation command switch
Frequency setting F01, C30
Keypad operation: Can be set with , keys.

External potentiometer: Can be set with the external resistor (1 to 5kΩ, 1/2W) Connected to analog input terminals 13, 12,
11. A separate variable resistor is necessary.
Analog input Can be set with external voltage/current input. 0 to +5V DC:change (200%) in analog F18, C50, C32 to
 0 to +10V DC (0 to +5V DC)/0 to 100% (terminal 12, V2) input gain setting. +1 to +5V DC:adjustable C34, C37 to C39,
 4 to 20mA DC/0 to 100% (terminal C1) with bias/analog input gain C42 to C44
Multistep frequency: Selectable from 8 steps (step 0 to 7) C05 to C11
UP/DOWN operation: The frequency rises or lowers while the digital input signal is turned on. F01, C30
Link operation: Can be set with RS485 communications and field bus communications (option). H30, y98
Control

Frequency setting change: Two types of frequency settings can be switched with an external signal (digital input). F01, C30
Changeover between remote and local (keypad operation) or frequency setup through communication is also possible.
Auxiliary frequency setting: Inputs at terminal 12, C1 or V2 can be added to the main setting E61 to E63
as auxiliary frequency settings.
Reverse action: The digital input signal and function code setting sets or switches between C53
the forward and reverse actions.
• +10 to 0V DC/0 to 100%(Terminal 12, V2) • 20 to 4mA DC/0 to 100%(Terminal C1)
Acceleration / deceleration 0 to 3600s F07, F08
time • Acceleration and deceleration pattern can be selected from 4 types: Linear, H07
S-curve (weak), S-curve (strong), Curve (constant output max. capacity). H11
• Shutoff of the operation command coasts the motor to decelerate and stop.
Frequency limiter High and low limiters can be set (setting range: 0 to 120Hz) Selection can be made between continuation of operation and F15, F16
stopping at frequencies equal to or smaller than the lower limit. H63
Bias frequency Bias of set frequency and PID command can be set in the range between 0 and ±100%. F18, C50 to C52
Gain for frequency setting The analog input gain can be set in the range from 0 to 200%. Voltage signals (terminal 12, V2) and current C32, C34, C37
signal (terminal C1) can be set independently. C39, C42, C44
Jump frequency setting 3 operation points and their common jump hysteresis width (0 to 30Hz) can be set. C01 to C04
Restart after momentary • The inverter restarts upon recovery from power failure without stopping the motor. F14
power failure • In the "operation continuation mode," recovery of the power supply is waited for while the output frequency slightly drops.
• Selection can be made among starting at 0Hz, starting at the frequency immediately before the momentary power failure,
and starting at a set frequency for the starting method after power recovery. H13 to H16, H92, H93
Current limit Keeps the current under the preset value during operation. F43, F44
Line/inverter switching • Line/inverter switching (starting at line frequency) can be made with a digital input signal (SW50, SW60). J22
• A built-in line/inverter switching sequence performs sequence control with a digital input signal (ISW50, ISW60) to
output a signal (SW88, SW52-1, SW52-2) for controlling an external magnetic contactor (MC). As a built-in
sequence, two types can be selected, including the one switching automatically to the line upon an inverter alarm.
PID control Capable of PID regulator control for process E61 to E63
Process commands J01 to J06
• Key operation (UP and DOWN keys):0 to 100% J10 to 0J19
• Analog input (terminal 12, V2):0 to +10V DC/0 to 100%
• Analog input (terminal C1):4 to 20mA DC/0 to 100%
• UP/DOWN (digital input):0 to 100%
• Communication (RS485, bus option):0 to 20,000/0 to 100

10
Common specifications
Related
Item Explanation Remarks function code
PID control Feedback value E61 to E6
• Analog input (terminal 12, V2):0 to +10V DC/0 to 100% J01 to J06
• Analog input (terminal C1):4 to 20mA DC/0 to 100% J10 to J19
Accessory functions
• Alarm output (absolute value alarm, deviation alarm) • Normal operation/inverse operation
• Small water flow stoppage function • Anti-reset wind-up function
• PID output limiter • Integration reset/hold
Pick-up Operation begins at a preset pick-up frequency to search for the motor speed to start an H09, H17
Control

idling motor without stopping it.


Automatic deceleration Upon a DC link voltage exceeding the overvoltage limit level during deceleration, the H69
deceleration time automatically extends to avoid an OV trip.
Deceleration characteristic The motor loss increases during deceleration to reduce the load energy regenerating at the inverter to avoid an OV trip upon mode selection. H71
Automatic energy-saving operation The output voltage is controlled to minimize the total sum of the motor loss and inverter loss at a constant speed. F37
Active drive The output frequency is automatically reduced to suppress the overload protection trip of the inverter H70
caused by an increase in the ambient temperature, operation frequency, motor load or the like.
Auto-tuning The motor parameters are automatically tuned. P04
Cooling fan ON/OFF control Detects inverter internal temperature and stops cooling fan when the temperature is low. An external output is issued in a transistor H06
output signal.
Running/stopping • Speed monitor, output current [A], output voltage [V], torque calculation value, input power E43
[kW], PID reference value, PID feedback value, PID output, load factor, motor output
• Select the speed monitor to be displayed from the following. E48
Output frequency [Hz], motor speed [r/min.], load shaft speed [r/min.], % indication
Life early warning The life early warning of the main circuit capacitors, capacitors on the PC boards and the An external output is issued in a transistor
cooling fan can be displayed. output signal.
Cumulative run hours The cumulative motor running hours, cumulative inverter running hours and cumulative watt-hours can be displayed.
Trip mode Displays the cause of trip by codes.
Indication

• (Overcurrent during acceleration) • (Overcurrent during deceleration) • (Overcurrent at constant speed)


• (Grounding fault) • (Input phase loss) • (Undervoltage)
• (Output phase loss) • (Overvoltage during acceleration) • (Overvoltage during deceleration)
• (Overvoltage at constant speed)• (Overheating of the heat sink) • (External alarm)
• (Inverter overheat) • (Motor protection (PTC thermistor)) • (Motor overload)
• (Inverter overload) • (Blown fuse) • (Charging circuit fault)
• (Memory error) • (Keypad communication error) • (CPU error)
• (Optional communication error) • (Option error)  • (Incorrect operation error)
• (Tuning error) • (RS485 communication error) • (Data save error due to undervoltage)
• (RS485 communication error (option))
Running or trip mode Trip history: Saves and displays the last 4 trip codes and their detailed description.
Overcurrent protection The inverter is stopped upon an overcurrent caused by an overload.
Short circuit protection The inverter is stopped upon an overcurrent caused by a short circuit in the output circuit.
Grounding fault protection The inverter is stopped upon an overcurrent caused by a grounding fault in the output circuit.
Overvoltage protection An excessive DC link circuit voltage is detected to stop the inverter. 3-phase 200V / 400VDC
3-phase400V / 800VDC
Surge protection The inverter is protected against surge voltages intruding across the main circuit power cable and ground.
Undervoltage Stops the inverter by detecting voltage drop in DC link circuit. 3-phase 200V / 200VDC F14
3-phase 400V / 400VDC
Input phase loss Stops or protects the inverter against input phase loss. The protective function can be canceled with function code 99. H98
Output phase loss Detects breaks in inverter output wiring at the start of running and during running, stopping the inverter output. The protective function can be canceled with function code 99. H98
Protection

Overheating The temperature of the heat sink of the inverter or that inside the inverter unit is detected to
stop the inverter, upon a failure or overload of the cooling fan.
Overload The inverter is stopped upon the temperature of the heat sink of the inverter or the temperature of the switching element calculated from the output current.
Motor protection

Electronic thermal The inverter is stopped upon an electronic thermal function setting to protect the motor. Thermal time constant can be adjusted (0.5 to 75.0min.). F10 to F12, P99
PTC thermistor A PTC thermistor input stops the inverter to protect the motor. H26, H27
Overload early warning Warning signal can be output based on the set level before the inverter trips. F10, F12, E34,
E35, P99
Stall prevention The output frequency decreases upon an output current exceeding the limit during acceleration or constant speed operation, to avoid overcurrent trip.
Momentary power failure • A protective function (inverter stoppage) is activated upon a momentary power failure for 15msec or longer.
protection • If restart upon momentary power failure is selected, the inverter restarts upon recovery of the voltage within the set time. F14
Retry function When the motor is tripped and stopped, this function automatically resets the tripping state Waiting time before resetting and the H04, H05
and restarts operation. number of retry times can be set.
Command loss detection A loss (broken wire, etc.) of the frequency command is detected to output an alarm and E65
continue operation at the preset frequency (set at a ratio to the frequency before detection).
Installation location Shall be free from corrosive gases, flammable gases, oil mist, dusts, and direct sunlight.
(Pollution degree 2 (IEC60664-1)). Indoor use only.
Ambient temperature -10 to +50˚C -10 to 40˚C when inverters are installed
side by side without clearance.
Ambient humidity 5 to 95% (no condensation)
Altitude Altitude [m] Output derating * If the altitude exceeds 2,000m, insulate
Environment

Lower than 1,000 None the interface circuit from the main power
supply to conform to the Low Voltage
1,001 to 2,000 Decreases
Directives.
2,001 to 3,000 Decreases*

Vibration [Smaller than 75kW] [90kW or more]


3mm (vibration width): 2 to less than 9Hz, 3mm (vibration width): 2 to less than 9Hz
9.8m/s2 : 9 to less than 20Hz 2m/s2 : 9 to less than 55Hz
2m/s2 :20 to less than 55Hz 1m/s2 :55 to less than 200Hz
1m/s2 :55 to less than 200Hz
Storage

Amb. temp. -25 to +65˚C


Amb. humidity 5 to 95%RH (no condensation)

11
External Dimensions

Main body of inverter (5.5kW)


Unit : mm
150 163
7 136 7 101.5 61.5
2 6 5
7
260
246

Power supply
Type
voltage
Three-phase 200V FRN5.5F1S-2A
7

Three-phase 400V FRN5.5F1S-4A


6
45 30 30
23.5

PULL

3 27
(Height of grounding terminal)
98.9

81.4

Main body of inverter (7.5 to 30kW)


Unit : mm
W D
12 W1 12 D1 D2
2 10 11.2
11
H1
H
11

10
A

W2 W3 W4
2 B Power supply Dimensions (mm)
Type
voltage W W1 W2 W3 W4 H H1 H2 H3 H4 D D1 D2 A B
H3

PULL
FRN7.5F1S-2A
220 196 63.5 46.5 46.5 260 238 141.7 16 172.9 27 34
(Height of separate power terminal block)

FRN11F1S-2A 118.5 96.5


Three-phase FRN15F1S-2A 136.7 21
215
200V FRN18.5F1S-2A 34 42
67 58 58 166.2 2 175.2
FRN22F1S-2A 250 226 400 378 85 130
FRN30F1S-2A - - - - 186.2 - -
FRN7.5F1S-4A
H4

27 34
220 196 63.5 46.5 46.5 260 238 141.7 16 172.9
H2

FRN11F1S-4A 118.5 96.5


Three-phase FRN15F1S-4A 136.7 21
215
400V FRN18.5F1S-4A 34 42
250 226 67 58 58 400 378 166.2 2 175.2 85 130
FRN22F1S-4A
FRN30F1S-4A - - - - - 186.2 - -

12
Main body of inverter (37 to 75kW)
2 10 W 4.5 D Unit : mm
W1 D1 D2
12
H1
H

10

Power supply Dimensions (mm)


Type
voltage W W1 W2 W3 H H1 H2 H3 D D1 D2
FRN37F1S-2A 320 240 304 310.2 550 530 192 220.5 255 140
Three-phase FRN45F1S-2A
H2

H3

615 595 115


200V FRN55F1S-2A 355 275 339 345.2 201.5 230.5 270 155
FRN75F1S-2A 740 720
FRN37F1S-4A
320 240 304 310.2 192 220.5 255 140
Three-phase FRN45F1S-4A 550 530
115
400V FRN55F1S-4A
355 275 339 345.2 209.5 238 270 155
W3 FRN75F1S-4A 615 595
(8) W2 8

* The above dimensions are planned ones; they are subject to change.

Keypad
Unit : mm

80 18.2 61 9.5
(14.615)

(13.775)
10.5

2 M3
15.08

8.17
45
65

Inside panel Back side view


Panel surface

(80)
(10.5)

58 4.5
1
23

Panel cutout
(65)

45
11.4

2 4
8.1

(16.98) 11.68
(53.8) 15.24
61 (9.5)

13
Wiring Diagram

Basic wiring diagram


The following diagram is for reference only. For detailed wiring diagrams, refer to the Instruction Manual.

Keypad operation

DC REACTOR Run/Stop operation and frequency setting on the keypad


DCR (Note1)
P1 [Wiring procedure]
(Note2)
MCCB or (Note3)
Main circuit (1) Wire the inverter main power circuit.
ELCB MC P1 P(+) N(-)
Power supply
Three-phase L1/R U Motor [Operation method]
200 to 240V
50/60Hz L2/S V M (1) Run/Stop : Press or key on the keypad.
or three-phase
380 to 480V L3/T W (2) Setting frequency: Set the frequency with or key.
50/60Hz
R0 Note1: When connecting a DC REACTOR (DCR option), remove the jumper bar
(Note4)
T0 from across the terminals [P1] and [P (+)]. The DCR is a standard
Grounding G G Grounding terminal accessory for 75kW or larger capacity inverters. It must be connected
terminal
when provided.
Control circuit
30C Note2: Install a recommended molded-case circuit-breaker (MCCB) or an earth-
[13]
30B
[12] 30 30A Alarm relay output leakage circuit-breaker (ELCB) (with an overcurrent protection function) in
[11] SINK (for any fault)
the primary circuit of the inverter to protect wiring. At this time, ensure that
Analog input

Y5C

[V2] SOURCE Y5A


Relay output the circuit breaker capacity is equivalent to or lower than the
recommended capacity.
[C1] Note3: Install a magnetic contactor (MC) for each inverter to separate the inverter
[11]
form the power supply, apart from the MCCB or ELCB, when necessary.
[FMA] Connect a surge suppressor in parallel when installing a coil such as the
MC or solenoid near the inverter.
[FMP] Note4: Connect the control circuit with the main circuit power supply to bring the
inverter in a waiting state. If this terminal is not connected, the inverter
(FWD) can still be operated with the application of main power.
(REV)
(CM)
Digital input

(X1)
Transistor output

(X2)
(X3) <Y1>
(X4) <Y2>
(X5) <Y3>
(CM) <CMY>
(PLC)

Operation by external signal inputs

Run/Stop operation and frequency setting through external signals


[Wiring procedure]
DC REACTOR
DCR (Note1) (1) Wire both the inverter main power circuit and control circuit.
P1 (2) Set (external signal) at function code . Next, set (voltage input (terminal
(Note2) 12) (0 to +10VDC)), (current input (terminal C1) (+4 to 20mADC)), or other
MCCB or (Note3)
Main circuit
ELCB MC P1 P(+) N(-) value at function code .
Power supply
Three-phase L1/R U Motor
200 to 240V
[Operation method]
50/60Hz L2/S V M (1)Run/Stop : Operate the inverter across terminals FDW and CM short-
or three-phase L3/T W
380 to 480V circuited, and stop with open terminals.
50/60Hz (2)Frequency setting: Voltage input (0 to +10VDC), current input (+4 to 20mADC)
R0
(Note4) Note1: When connecting a DC REACTOR (DCR option), remove the jumper bar
T0
from across the terminals [P1] and [P (+)]. The DCR is a standard
Grounding G G Grounding terminal
terminal
accessory for 75kW or larger capacity inverters. It must be connected
(Note5)
Power supply for Control circuit
when provided.
variable resistor 3
2 [13]
30C Note2: Install a recommended molded-case circuit-breaker (MCCB) or an earth-
30B
Voltage input for
1 [12]
SINK
30 30A Alarm relay output
(for any fault)
leakage circuit-breaker (ELCB) (with an overcurrent protection function) in
setting 0 to 10Vdc
Analog input

[11]
Y5C the primary circuit of the inverter to protect wiring. At this time, ensure that
Voltage input for (+) [V2] SOURCE Y5A
Relay output the circuit breaker capacity is equivalent to or lower than the
setting 0 to 10Vdc (-) recommended capacity.
Current input for (+)
Note3: Install a magnetic contactor (MC) for each inverter to separate the inverter
[C1]
setting 4 to 20mAdc (-) [11] form the power supply, apart from the MCCB or ELCB, when necessary.
Connect a surge suppressor in parallel when installing a coil such as the
[FMA]
Analog meter MC or solenoid near the inverter.
Note4: Connect the control circuit with the main circuit power supply to bring the
Digital frequency meter
[FMP] inverter in a waiting state. If this terminal is not connected, the inverter
can still be operated with the application of main power.
(FWD) Note5: Frequency can be set by connecting a frequency setting device (external
(REV) potentiometer) between the terminals 11, 12 and 13 instead of inputting a
(CM)
voltage signal (0 to +10V DC, 0 to +5V DC or +1 to +5V DC) between the
Digital input

(X1) terminals 12 and 11.


Transistor output

(X2) Note6: For the control signal wires, use shielded or twisted wires. Ground
(X3) <Y1>
(X4) <Y2> shielded wires. To prevent malfunction due to noise, keep the control
(X5) <Y3>
(CM) <CMY> circuit wiring away from the main circuit wiring as far as possible
(Note6) (PLC) (recommended: 10cm or more). Never install them in the same wire duct.
When crossing the control circuit wiring with the main circuit wiring, set
them at right angles.

14
Terminal Functions

Terminal Functions
Division

Related
Symbol Terminal name Functions Remarks
function code
L1/R,L2/S,L3/T Power input Connect a three-phase power supply.
Main circuit

R0,T0 Auxiliary control power input Connect a single-phase power supply.


U,V,W Inverter output Connect a three-phase motor.
P(+),P1 For DC REACTOR Connect the DC reactor (DCR).
P(+),N(-) For DC bus connection Used for DC bus connection.
G Grounding Terminal for inverter grounding Two terminals are provided.
13 Potentiometer power supply Used for frequency setting device power supply (variable resistance: 1 to 5kΩ) (10Vdc 10mAdc max.)
12 Voltage input Used as a frequency setting voltage input. Input impedance:22kΩ F18
0 to +10V DC/0 to 100% (0 to +5V DC/0 to 100%) Maximum input:+15V DC C32 to C34
(Inverse operation) +10 to 0V DC/0 to 100% E61
(PID control) Used for setting signal (PID process command value) or feedback signal.
(Frequency aux. setting) Used as additional auxiliary setting to various frequency settings.
(Analog input monitor) The peripheral analog signal can be displayed on the keypad. (Displaying coefficient: valid)
Frequency setting

C1 Current input Used as a frequency setting current input. Input impedance:250Ω F18
4 to 20mA DC/0 to 100% Maximum input:30mA DC C37 to C39
(Inverse operation) 20 to 4mA DC/0 to 100% E62
(PID control) Used for setting signal (PID process command value) or feedback signal.
(Frequency aux. setting) Used as additional auxiliary setting to various frequency settings.
(Analog input monitor) The peripheral analog signal can be displayed on the keypad. (Displaying coefficient: valid)
V2 Analog setting voltage input Used as a frequency setting voltage input. Input impedance:22kΩ F18
0 to +10V DC/0 to 100% (0 to +5V DC/0 to 100%) Maximum input:+15V DC C42 to C44
(Inverse operation) +10 to 0V DC/0 to 100% E63
(PID control) Used for setting signal (PID process command value) or feedback signal.
(For PTC thermistor) Connects PTC thermistor for motor protection.
(Frequency aux. setting) Used as additional auxiliary setting to various frequency settings.
(Analog input monitor) The peripheral analog signal can be displayed on the keypad. (Displaying coefficient: valid)
11 Analog common Common terminal for frequency setting signals (12, 13, C1, V2, FMA) Isolated from terminals CM and CMY.
Two terminals are provided.
X1 Digital input 1 The following functions can be set at terminals X1 to X5, FWD and REV for ON state E01
X2 Digital input 2 signal input. Source current:2.5 to 5mA E02
X3 Digital input 3 <Common function> Voltage level:2V E03
X4 Digital input 4 • Sink and source are changeable using the built-in sliding switch. OFF state E04
• ON timing can be changed between short-circuit of terminals X1 and CM and Allowable leakage current:
X5 Digital input 5 E05
open circuits of them. The same setting is possible between CM and any of the Smaller than 0.5mA
FWD Forward operation command terminals among X2, X3, X4, X5, FWD, and REV. Voltage:22 to 27V E98
REV Reverse operation command E99
(FWD) Forward operation command The motor runs in the forward direction upon ON across (FWD) and CM.The motor decelerates and stops upon OFF. This function can be set only for the
(REV) Reverse operation command The motor runs in the reverse direction upon ON across (REV) and CM.The motor decelerates and stops upon OFF. terminals FWD and REV.
(SS1) Multistep freq. 8-step operation can be conducted with ON/OFF signals at (SS1) to (SS4). Multistep frequency
C05 to C11
(SS2) selection 0 1 2 3 4 5 6 7
Digital input
(SS4)
(SS1) - ON - ON - ON - ON
(SS2) - - ON ON - - ON ON
(SS4) - - - - ON ON ON ON

(HLD) 3-wire operation stop Used for 3-wire operation.


command ON across (HLD) and CM: The inverter self-holds FWD or REV signal.
OFF across (HLD) and CM: The inverter releases self-holding.
(BX) Coast-to-stop command ON across (BX) and CM: The inverter output is shut off immediately and the motor coasts to a stop. No alarm signal will be output.
(RST) Alarm reset ON across (RST) and CM: Faults are reset. Alarm reset signal width: 0.1(s) or more
(THR) Trip command (External fault) OFF across (THR) and CM: The inverter output is shut off immediately and the motor coasts-to-stop. Alarm signal will be output.
(Hz2/Hz1) Freq. set 2/Freq. set 1 ON across (Hz2/Hz1)and CM: Freq. set 2 is effective. F01, F30
(DCBRK) DC braking command ON across (DCBRK) and CM: Starts DC braking action. F20 to F22
(SW50) Line/inverter switch(50Hz) OFF across (SW50) and CM: Starts at 50Hz.
(SW60) Line/inverter switch(60Hz) OFF across (SW60) and CM: Starts at 60Hz
Digital input

(UP) UP command The output frequency rises while the circuit across (UP) and CM is connected. F01, C30
(DOWN) DOWN command The output frequency drops while the circuit across (DOWN) and CM is connected. J02
(WE-KP) Write enable for KEYPAD The function code data can be changed from the keypad only when (WEE-KP) is ON. F00
(Hz/PID) PID cancel PID control can be canceled when the circuit across (Hz/PID) and CM is connected. (Operation proceeds J01 to J06
according to the selected frequency setting method such as the multi-step frequency, keypad and analog input.) J10 to J19
(IVS) Inverse mode The frequency setting or PID control output signal (frequency setting) action mode switches C50, J01
changeover between normal and inverse actions when the circuit across (IVS) and CM is connected.
(IL) Interlock Connect an auxiliary contact of a switch installed between the inverter and motor. This signal is input upon F14
momentary power failure to detect momentary power failure, and the inverter restarts upon power recovery.
(LE) Link enable Operation proceeds according to commands sent via RS485 communication or H30, y98
(RS485, Bus) field bus (option) when the circuit across (LE) and CM is connected.
(U-DI) Universal DI An arbitrary digital input signal is transmitted to the host controller.
(STM) Starting characteristic selection ON across (STM) and CM: Starting at the pick-up frequency becomes valid. H17, H09
(STOP) Forcible stop ON across (STOP) and CM: The inverter is forcibly stopped in the special deceleration time. H56
(PID-RST) PID differentiation / integration reset ON across (PID-RST) and CM: Resets differentiation and integration values of PID. J01 to J06
(PID-HLD) PID integral hold ON across (PID-HLD) and CM: Holds integration values of PID. J10 to J19
(LOC) Local (keypad) command selection ON across (LOC) and CM: The operation commands and frequency settings given at the keypad become valid.
(RE) Operation permission After an operation command is input, operation starts upon activation of (RE).
(DWP) Dew prevention ON across (DWP) and CM: A current flows through the motor to avoid motor J21
temperature drop during inverter stoppage so that condensation will not occur. F21, F22
(ISW50) Line/inverter switching OFF across (ISW50) and CM: Line operation starts according to the switching J22
sequence(50Hz) sequence built in the inverter. (For 50Hz commercial line)
(ISW60) Line/inverter switching OFF across (ISW60) and CM: Line operation starts according to the switching J22
sequence(60Hz) sequence built in the inverter. (For 60Hz commercial line)
(FR2/FR1) Operation command 2/1 ON across (FR2/FR1) and CM: The operation command switches to (FWD2) (REV2) side. F02
(FWD2) Forward rotation/stop command 2 Forward operation upon ON across (FWD) and CM. Deceleration and stop upon OFF. (Second operation command)
(REV2) Reverse operation/stop command 2 Reverse operation upon ON across (REV) and CM. Deceleration and stop upon OFF. (Second operation command)
PLC PLC terminal Connect to PLC output signal power supply. Common for 24V power. +24V 50mA max.
CM Common Common terminal for digital input signal Isolated from terminals 11 and
CMY.Two terminals are provided.
15
Terminal Functions

Terminal Functions
Pulse output Analog output Division

Related
Symbol Terminal name Functions Remarks
function code
FMA Analog monitor The output style can be selected between DC voltage (0 to 10V) and DC current (4 to 20mA). In the case of voltage output, up to two analog voltmeters F29 to F31
One of the following items can be output in the selected output style. (0 to 10Vdc, input impedance: 10kΩ) can be connected.
• Output frequency. • Output current. • Output voltage. • Output torque. • Load factor. In the case of current output, analog ammeters (up to
• Input power. • PID feedback value. • DC link circuit voltage. • Universal AO. 500Ω) can be connected.
• Motor output. • Analog output test. • PID command. • PID output Gain adjustment range: 0 to 200%
FMP Pulse monitor One of the following items can be output in a pulse frequency. Up to two analog voltmeters (0 to F33 to F35
• Output frequency. • Output current. • Output voltage. • Output torque. • Load factor. 10Vdc, input impedance: 10kΩ) can be
• Power consumption. • PID feedback value. • DC link circuit voltage. • Universal AO. connected. (Driven at average voltage)
• Motor output. • Analog output test. • PID command. • PID output Gain adjustment range: 0 to 200%
(PLC) Transistor output power • Power supply for a transistor output load.(24Vdc 50mAdc Max.)(Note: Same terminal as digital input PLC terminal) Short circuit across terminals CM and CMY to use.
Y1 Transistor output 1 The following functions can be set at terminals Y1 to Y3 for signal output. Max. voltage: 27Vdc, max. current: E20
Y2 Transistor output 2 • The setting of "short circuit upon active signal output" or "open upon active signal output" is possible. 50mA, leak current: 0.1mA max., ON E21
• Sink/source support (switching unnecessary) voltage: within 2V (at 50mA)
Y3 Transistor output 3 E22
(RUN) Inverter running (speed exists) An active signal is issued when the inverter runs at higher than the starting frequency.
(RUN2) Inverter output on A signal is issued when the inverter runs at smaller than the starting frequency or when DC braking is in action.
(FAR) Speed/freq. arrival An active signal is issued when the output frequency reaches the set frequency. Detection width (fixed): 2.5 (Hz)
(FDT) Speed/freq. detection An active signal is issued at output frequencies above a preset detection level. Hysteresis width (fixed): 1.0 (Hz) E31
The signal is deactivated if the output frequency falls below the detection level.
(LV) Undervoltage detection The signal is output when the inverter stops because of undervoltage.
(IOL) Inverter output limit (limit on current) The signal is output when the inverter is limiting the current. F43, F44
(IPF) Auto-restarting The signal is output during auto restart operation (after momentary power failure and until completion of restart). F14
(OL) Overload early warning (motor) The signal is output when the electronic thermal relay value is higher than the preset alarm level. F10 to F12
(RDY) Operation ready output A signal is issued if preparation for inverter operation is completed.
Transistor output

(SW88) Line-to-inverter switching The magnetic contactor on the line side of line-to-inverter switching is controlled.
(SW52-2) Line-to-inverter switching The magnetic contactor on the inverter output side (secondary side) of line-to-inverter switching is controlled.
(SW52-1) Line-to-inverter switching The magnetic contactor on the inverter input side (primary side) of line-to-inverter switching is controlled.
(AX) AX terminal function The electromagnetic contactor on the inverter input side (primary side) is controlled.
(FAN) Cooling fan ON/OFF control The ON/OFF signal of the cooling fan is issued. H06
(TRY) Retry in action The signal is output during an active retry. H04, H05
(U-DO) Universal DO The signal transmitted from the host controller is issued.
(OH) Heat sink overheat early warning An early warning signal is issued before the heat sink trips due to an overheat.
(LIFE) Lifetime alarm Outputs alarm signal according to the preset lifetime level. H42, H43, H98
(REF OFF) Command loss detection A loss of the frequency command is detected. E65
(OLP) Overload preventive control The signal is output when the overload control is activated. H70
(ID) Current detection The signal is output when a current larger than the set value has been detected for the timer-set time. E34, E35
(PID-ALM) PID alarm output An absolute value alarm or deviation alarm under PID control is issued as a signal. J11 to J13
(PID-CTL) Under PID control The valid state of PID control is issued as a signal.
(PID-STP) PID stop upon small water flow A signal is issued if operation is stopped due to a small water flow under PID control. (The inverter is stopped even if the operation command is issued.) J15 to J17
(U-TL) Low torque detection A signal is issued if the torque falls below the preset low torque detection level for a set time. E80, E81
(RMT) In remote mode A signal is issued in the remote mode.
(AX2) Operation command input A signal is issued if there is an operation command input and operation ready is completed.
(ALM) Alarm relay output (for any fault) An alarm relay output (for any fault) signal is issued as a transistor output signal.
CMY Transistor output common Common terminal for transistor output The terminal is isolated from terminals 11 and CM.
Communication Contact output

Y5A,Y5C General-purpose relay • Multi-purpose relay output; signals similar to above-mentioned signals Y1 to Y3 can be selected. Contact capacity:250 V AC, 0.3A, cos =0.3 E24
output • An alarm output is issued upon either excitation or no excitation according to selection.  +48 V DC, 0.5A
30A,30B,30C Alarm relay output (for • A no-voltage contact signal (1c) is issued when the inverter is stopped due to an alarm. E27
any fault) output • Multi-purpose relay output; signals similar to above-mentioned signals Y1 to Y3 can be selected.
• An alarm output is issued upon either excitation or no excitation according to selection.
RJ45 connector for One of the following protocols can be selected. Power (+5V) is supplied to the H30
connection of keypad • Modbus RTU keypad. y01 to y20
• Protocol exclusively for keypad (default selection) y98, y99
• Fuji's special inverter protocol
• SX protocol for PC loader

16
Terminal Functions

Terminal Arrangement
Main circuit terminals
Power supply  Applicable motor 
voltage rating (kW)  Inverter type  Reference Fig. A Fig. D

Three-phase  0.75 FRN0.75F1S-2A


200V 1.5 FRN1.5F1S-2A
Available soon Control circuit terminal block Control circuit 
2.2 FRN2.2F1S-2A terminal block
3.7 FRN3.7F1S-2A R0 T0 U V W

5.5 FRN5.5F1S-2A Fig. A


7.5 FRN7.5F1S-2A R0 T0
L1/R L2/S L3/T P1 P(+) N(-) U V W
11 FRN11F1S-2A Fig. B L1/R L2/S L3/T P1 P(+) N(-)
G G
15 FRN15F1S-2A
18.5 FRN18.5F1S-2A G G
Fig. C
22 FRN22F1S-2A
30 FRN30F1S-2A Fig. D Terminal sizes R0, T0:M3.5, other:M4 Terminal sizes R0, T0:M3.5, other:M8

37 FRN37F1S-2A Fig. E Fig. B Fig. E


45 FRN45F1S-2A
55 FRN55F1S-2A Fig. F Control circuit 
Control circuit  terminal block
75 FRN75F1S-2A R0 T0
terminal block
90 FRN90F1S-2A R0 T0
Available soon
110 FRN110F1S-2A
Three-phase  0.75 FRN0.75F1S-4A L1/R L2/S L3/T U V W
400V 1.5 FRN1.5F1S-4A L1/R L2/S L3/T P1 P(+) N(-) U V W
Available soon
2.2 FRN2.2F1S-4A P1 P(+) N(-)
3.7 FRN3.7F1S-4A
5.5 FRN5.5F1S-4A Fig. A G G G G

7.5 FRN7.5F1S-4A Terminal sizes R0, T0:M3.5, other:M5 Terminal sizes R0, T0:M3.5, other:M8


11 FRN11F1S-4A Fig. B
Fig. C Fig. F
15 FRN15F1S-4A
18.5 FRN18.5F1S-4A
Fig. C Control circuit 
22 FRN22F1S-4A Control circuit 
terminal block R0 T0 terminal block R0 T0
30 FRN30F1S-4A Fig. D
37 FRN37F1S-4A
U V W
45 FRN45F1S-4A
Fig. E L1/R L2/S L3/T
55 FRN55F1S-4A
L1/R L2/S L3/T P1 P(+) N(-) U V W P1 P(+) N(-)
75 FRN75F1S-4A
90 FRN90F1S-4A
G G
110 FRN110F1S-4A G G
132 FRN132F1S-4A
Terminal sizes R0, T0:M3.5, other:M6 Terminal sizes R0, T0:M3.5,     G:M8, other:M10
160 FRN160F1S-4A
200 FRN200F1S-4A
220 FRN220F1S-4A
Available soon
280 FRN280F1S-4A
315 FRN315F1S-4A
355 FRN355F1S-4A
400 FRN400F1S-4A
450 FRN450F1S-4A
500 FRN500F1S-4A

Control circuit terminals (common to all models)

Y5A Y5C Y3 V2 FMA FMP X5

30B Y1 Y2 C1 11 PLC X1 X2 X3 X4

30A 30C CMY 11 12 13 CM FWD REV CM

Terminal sizes:M3

17
Protective Functions

Protective Functions
LED Alarm output Related
Function Description
indication (30A, B, C) Note) function code
Overcurrent protection The inverter is stopped for protection against overcurrent. During acceleration
Short circuit protection The inverter is stopped for protection against overcurrent caused by a short circuit in the output circuit. During deceleration
Grounding The inverter is stopped upon start-up for protection against overcurrent caused by a During constant
fault protection grounding fault in the output circuit. If the power supply is turned on with the grounding fault, speed operation
the protection may be invalidated. (3-phase 200V 75kW or less, 3-phase 400V 220kW or less)
The inverter is stopped upon detection of a zero-phase current on the output current
and for protection against overcurrent caused by a grounding fault in the output circuit.
(3-phase 200V 90kW or more, 3-phase 400V 280kW or more)
Overvoltage An excessive voltage (3-phase 200V series: 400VDC, 3-phase 400V series: 800VDC) in During acceleration
protection the DC link circuit is detected and the inverter is stopped. If a large voltage is applied by During deceleration
mistake, the protection cannot be guaranteed. During constant speed
operation (when stopped)
Undervoltage The voltage drop (3-phase 200V series: 200VDC, 3-phase 400V series: 400VDC) in the DC link circuit is detected to stop
F14
protection the inverter.However, when "F14: 4 or 5" is selected, an alarm is not issued even upon a voltage drop in the DC link circuit.
Input phase loss The input phase loss is detected to shut off the inverter output. This function protects the inverter from being H98
protection damaged by adding extreme stress caused by a power phase loss or imbalance between phases.When the
load to be connected is small or DC REACTOR is connected a phase loss is not detected.
Output phase loss protection Detects breaks in inverter output wiring at the start of operation and during running, to shut off the inverter output. H98
Overheating The temperature of the heat sink in the event of cooling fan trouble and overload is detected to stop the inverter. H43
protection The temperature inside the inverter unit in the event of cooling fan trouble and overload is detected to stop the inverter.
Overload protection The temperature inside the IGBT is calculated from the detection of output current and internal temperature, to shut off the inverter output.
External alarm input With the digital input signal (THR) opened, the inverter is stopped with an alarm. E01 to E03
E98, E99
Fuse blown The wiring breakage of the main circuit fuse in the inverter is detected to stop the inverter. (3-phase 200V 90kW or more, 3-phase 400V 90kW or more)
Charging circuit fault The charging circuit fault in the inverter is detected to stop the inverter. (3-phase 200V 45kW or more, 3-phase 400V 55kW or more)
Electronic The inverter is stopped with an electronic thermal function set to protect the motor. F10
Motor protection

thermal • The standard motor is protected at all the frequencies.


• The inverter motor is protected at all the frequencies.
*The operation level and thermal time constant can be set. F11,F12
PTC thermistor A PTC thermistor input stops the inverter to protect the motor. H26,H27
• The PTC thermistor is connected between terminals V2 and 11 to set switches and function codes on the control PC board.
Overload early Warning signal is output at the predetermined level before stopping the inverter with the electronic thermal E34,E35
warning function to protect the motor.
Stall prevention This is protected when the instantaneous overcurrent limit works. H12
•Instantaneous overcurrent limit: operates when the inverter output current goes beyond the instantaneous
overcurrent limiting level, and avoids tripping (during acceleration and constant speed operation).
Alarm relay output The relay signal is output when the inverter stops upon an alarm. E20,E27
(for any fault) <Alarm reset> E01 to E03
The key or digital input signal (RST) is used to reset the alarm stop state. E98,E99
<Storage of alarm history and detailed data>
Up to the last 4 alarms can be stored and displayed.
Memory error Data is checked upon power-on and data writing to detect any fault in the memory and to stop the inverter if any.
Keypad The keypad (standard) or multi-function keypad (optional) is used to detect a communication fault between F02
communication error the keypad and inverter main body during operation and to stop the inverter.
CPU error Detects a CPU error or LS1 error caused by noise.
Option communication error When each option card is used, a fault of communication with the inverter main body is detected to stop the inverter.
Option error When each option card is used, the option card detects a fault to stop the inverter.
STOP key Pressing the key on the keypad forcibly decelerates and stops the motor even if the H96
priority operation command is given through a terminal block or communication. ( will be
displayed after stopping.)
Operation error Start check If the operation command is entered in the following cases, will be displayed on the
LED monitor to prohibit operation.
•Power-on
•Alarm reset ( key ON)
•The link operation selection "LE" is used to switch operation.
Tuning error When tuning failure, interruption, or any fault as a result of turning is detected while tuning for motor constant. P04
RS485 When the connection port of the keypad connected via RS485 communication port to detects a communication
communication error error, the inverter is stopped and displays an error.
Data save error upon undervoltage When the undervoltage protection works, an error is displayed if data cannot be stored.
RS485 communication When an optional RS485 communication card is used to configure the network, a fault of communication
error (optional) with the inverter main body is detected to stop the inverter.
Retry When the motor is tripped and stopped, this function automatically resets the tripping state and restarts H04,H05
operation.(The number of retries and the length of wait before resetting can be set.)
Surge protection The inverter is protected against surge voltage intruding between the main circuit power line and ground.
Command loss A loss (broken wire, etc.) of the frequency command is detected to output an alarm and continue operation at E65
detection the preset frequency (set at a ratio to the frequency before detection).
Momentary power •A protective function (inverter stoppage) is activated upon a momentary power failure for 15msec or longer. F14
failure protection •If restart upon momentary power failure is selected, the inverter restarts upon recovery of the voltage within the set time. H13 to H16
Active drive The inverter output frequency is reduced to avoid tripping before heat sink overheating or tripping due to an H70
overload (alarm indication: or ).
Note : The item indicated with in the alarm output (30A, B, C) column may not be issued according to some function code settings.

18
Keypad Operations

Keypad switches and functions

LED monitor Operation mode display


When the motor is running or stopped: During keypad operation:
The monitor displays parameters such as output frequency, When function code is , or
set frequency, motor speed, load shaft speed, output voltage, (keypad operation), the green KEYPAD CONTROL LED lights up.
output current, and input power.
During operation:
Alarm mode:
The monitor shows the alarm description with a fault code. The green RUN LED lights up.

Program/Reset key Unit display


Used to change the mode. The unit of the data displayed at the LED
Programming mode: monitor is indicated. Use the FUNC/DATA key
Used to shift the digit (cursor movement) to to switch the displayed data.
set data.
Alarm mode: Run key
Resets a trip.
Used to start the operation.
Function/Data select key While the motor is stopped:
Used to change the LED monitor and to This key is invalid if the function code is
store the function code and data. set to (operation by external signals).
Stop key
Up/Down keys
Used to stop the operation.
During operation:Used to increase or decrease the
frequency or motor speed. During operation:
In data setting :Used to indicate the function code This key is invalid if the function code is set to (operation by
number or to change data set value. external signals).
The inverter stops when the function code is set to or .

Monitor display and key operation The keypad modes are classified
in the following 3 modes.

Operation mode Programming mode Running mode


Alarm mode
Monitor, keys STOP RUN STOP RUN
Displays the function code or data. Displays the output frequency, set frequency, loaded motor Displays the alarm
Function
speed, required power, output current, and output voltage. description and alarm history.
Display ON Blinking ON Blinking/ON
The program mode is indicated. Displays the unit of frequency, output current, None
Function
required power, speed, and line speed.
PRG.MODE PRG.MODE
Frequency Speed
PRG.MODE Hz A kW ON Hz A kW ON
indication r/min m/min indication r/min m/min
Hz A kW
r/min m/min PRG.MODE
Monitor

Display Hz A kW ON OFF
r/min m/min Capacity
PRG.MODE PRG.MODE
Current or current Blink
Hz A kW ON Hz A kW
indication r/min m/min indication r/min m/min or lit

KEYPAD Function Operation selection (keypad operation/terminal operation) is displayed.


CONTROL Display Lit in keypad operation mode
Function Absence of operation Presence of operation Absence of operation Presence of operation Presence of operation command is displayed.
command is displayed. command is displayed. command is displayed. command is displayed. /Stoppage due to trip is displayed.
If an alarm occurs during
RUN operation, unlit during keypad
Display RUN unlit / RUN lit RUN unlit / RUN lit RUN unlit / RUN lit RUN unlit / RUN lit
operation or lit during terminal
block operation.
Switches to running mode Switches to programming mode Releases the trip and
Function switches to stop mode
Digit shift (cursor movement) in data setting or running mode.
Determines the function code, stores Switches the LED monitor display. Displays the operation
Function
Keys

and updates data. information.


Increases/decreases the function code Increases/decreases the frequency, Displays the
Function and data. motor speed and other settings. alarm history.
Starts running (switches to
Function Invalid Invalid Invalid
running mode (RUN)).
Decreases and stops (switches Decreases and stops (switches
Function Invalid Invalid Invalid
to programming mode (STOP)). to running mode (STOP)).
This keypad supports a full menu mode which allows you to set or display the following information.
Indication and setting change of changed function code, drive monitor, I/O check, maintenance information, and alarm information.
For concrete operation methods, refer to the FRENIC-Eco Instruction Manual or User's Manual.

19
Functions Settings

Function Settings
F codes: Fundamental Functions
Func. Data
Name Data setting range Min. Unit copy*2 Default setting
Code
Data Protection 0: Disable data protection (Function code data can be edited.) - - Y 0
1: Enable data protection (Function code data can not be edited.)
Frequency Command 1 0: Enable the and keys on the built-in keypad - - Y 0
1: Enable the voltage input to terminal [12](0 to +10 V DC)
2: Enable the current input to terminal [C1](+4 to +20 mA DC)
3: Enable the sum of voltage and current inputs to terminals [12] and [C1]
5: Enable the voltage input to the terminal [V2](0 to +10 V DC)
7: Enable the terminal signal command (UP) and (DOWN) control
Running/Stopping and 0: Enable the and keys on the built-in keypad to run and stop motor - - Y 2
Rotational Direction (The (FWD) or (REV) command should be ON for forward or reverse rotation.)
1: Enable the terminal signal command (FWD) or (REV) command to run motor
2: Enable the and keys on the keypad to run/stop motor forward
3: Enable the and keys on the keypad to run/stop motor reverse
Maximum Frequency 25.0 to 120.0 0.1 Hz Y 60.0
Base Frequency 25.0 to 120.0 0.1 Hz Y 60.0
Rated Voltage (at base frequency) 0 : Output voltage in line with variance in input voltage 1 V Y2
80 to 240 : Output voltage AVR-controlled 200
160 to 500: Output voltage AVR-controlled 400
Acceleration Time 1 0.00 to 3600 0.01 s Y 20.0
Note: Acceleration time is ignored at 0.00. (External gradual acceleration pattern)
Deceleration Time 1 0.00 to 3600 0.01 s Y 20.0
Note: Deceleration time is ignored at 0.00. (External gradual deceleration pattern)
Torque Boost 0.0 to 20.0 0.1 % Y Depending on the
(The set voltage at base frequency for F05 is 100%.) motor applied
Note: This setting is effective for auto torque boost/auto energy saving
operations specified by function code F37 (= 0, 1, 3, or 4).
Electronic Thermal (Select the motor property) 1: For general-purpose motors with built-in self-cooled fans - - Y 1
Overload for Motor Protection 2: For motors with forced-cooled fans
 (Overload detection level) 0.00 (Disabled) 0.01 A Y1 100% of the motor
1 to 135% of rated current (allowable continuous drive current) of the inverter Y2 rated current
 (Thermal time constant) 0.5 to 75.0 0.1 min Y _ 22 kW)
5 (<
 10 (>_30 kW)
Restart Mode after Instantaneous 0: Inactive (Trip immediately without restart) - - Y 1
Power Failure 1: Inactive (Trip without restart after recovery of power)
3: Active (Continuous running for the heavy inertia or general load)
4: Active (Restart at the frequency at which the power failure occurred, for general load)
5: Active (Restart at the starting frequency, for low-inertia load)
Frequency Limiter  (Peak) 0.0 to120.0 0.1 Hz Y 70.0
 (Bottom) 0.0 to120.0 0.1 Hz Y 0.0
Bias (for Frequency Command 1) -100.00 to 100.00 *1 0.01 % Y 0.00
DC Braking  (Starting frequency) 0.0 to 60.0 0.1 Hz Y 0.0
 (Braking level) 0 to 60 (Rated output current of the inverter interpreted as 100%.) 1 % Y 0
 (Braking time) 0.00: (Disabled), 0.01 to 30.00 0.01 s Y 0.00
Starting Frequency 0.1 to 60.0 0.1 Hz Y 0.5
Stop Frequency 0.1 to 60.0 0.1 Hz Y 0.2
Motor Sound (Carrier frequency) 0.75 to 15 (<_ 22 kW) *3 1 kHz Y 2
0.75 to 10 (30 to 75 kW)
0.75 to 6 (>_90 kW)
 (Sound tone) 0: Level 0 (Inactive) - - Y 0
1: Level 1
2: Level 2
3: Level 3
Analog Output Signal Selection 0: Output in voltage (0 to +10 V DC)
for [FMA] 1: Output in current (+4 to +20 mA DC)
 (Output gain) 0 to 200 1 % Y 100
Analog Output Signal  (Monitor object) Select the object to be monitored as follows. - - Y 0
Selection for [FMA]  0: Output frequency
 2: Output current
 3: Output voltage
 4: Output torque
 5: Load rate
 6: Input power
 7: PID feedback amount
 9: DC link circuit voltage
10: Universal AO
13: Motor output
14: Test analog output (+) voltage
15: PID process command (SV)
16: PID process output (MV)
Digital Output Signal (Pulse rate) 25 to 6000 (Pulse rate at 100% output) 1 p/s Y 1440
Selection for [FMP]
 (Output gain) 0 :Output pulse rate (Fixed at 50% duty) 1 % Y 0
1 to 200:Voltage output adjustment (Pulse rate is fixed at 2000 p/s. Adjust the pulse duty)

20
Functions Settings

Function Settings
F codes: Fundamental Functions
Func. Data
Name Data setting range Min. Unit copy*2 Default setting
Code
 (Monitor object) Select the object to be monitored as follows. - - Y 0
0: Output frequency 9: DC link circuit voltage
2: Output current 10: Universal AO
3: Output voltage 13: Motor output
4: Output torque 14: Test analog output (+) voltage
5: Load rate 15: PID process command (SV)
6: Input power 16: PID process output (MV)
7: PID feedback amount
Load Selection/ 0: Variable torque load - - Y 1
Auto Torque Boost/ 1: Variable torque load
Auto Energy Saving Operation (Higher startup torque required)
2: Auto-torque boost
3: Auto-energy saving operation
(Variable torque load increasing in proportion to square of speed)
4: Auto-energy saving operation
(Variable torque load increasing in proportion to square of speed
(Higher startup torque required))
Note: Apply this setting to a load with short acceleration time.
5: Auto-energy saving operation(Auto-torque boost)
Note: Apply this setting to a load with long acceleration time.
Current Limiter  (Operation condition) 0: Disabled - - Y 0
1: In constant speed (Disabled during acceleration and deceleration)
2: At acceleration and in constant speed (Disabled during deceleration)
 (Limiting level) 20 to 120 (The data is interpreted as the rated output current of the inverter for 100%.) 1 % Y 110

E codes: Extension Terminal Functions


Func. Data
Name Data setting range Min. Unit copy*2 Default setting
Code
Terminal Command Assignment to:  [X1] Select data to specify the function of terminals [X1] to [X5] as follows. - - Y 6
 [X1] To assign a negative logic input to a terminal, set the value of 1000s - - Y 7
 [X3] shown in ( ) in the table below to the function code. - - Y 8
 [X4] Any negative logic cannot be applied for functions without (1000s) data. - - Y 11
 [X5] 0: (1000)Multi-step frequency selection (0 to 1 steps) (SS1) - - Y 35
1: (1001)Multi-step frequency selection (0 to 3 steps)  (SS2)
2: (1002)Multi-step frequency selection (0 to 7 steps)  (SS4)
6: (1006)Self-hold the terminal command  (HLD)
7: (1007)Coast-to-stop command  (BX)
8: (1008)Alarm reset  (RST)
9: (1009)Alarm from external equipment  (THR)
11: (1011) Frequency command 2 or 1  (Hz2/Hz1)
 Note: PID process command follows this command.
13:  DC braking command  (DCBRK)
15:  Switch the motor drive source to thecommercial power lines (50 Hz) (SW50)
16:  Switch the motor drive source to thecommercial power lines (60 Hz) (SW60)
17: (1017)UP command  (UP)
18: (1018)DOWN command  (DOWN)
19: (1019)Enable editing of function codes from keypad  (WE-KP)
20: (1020)Disable PID control  (Hz/PID)
21: (1021)Switch normal/inverted driving  (IVS)
22: (1022)Interlock command  (IL)
24: (1024)Select link operation (RS485 communication, option)  (LE)
25: (1025)Universal DI  (U-DI)
26: (1026)Select starting characteristics  (STM)
30: (1030)Forced stop  (STOP)
33: (1033)Reset PID integral and differential components  (PID-RST)
34: (1034)Hold PID integral component  (PID-HLD)
35: (1035)Select the local (keypad)  (LOC)
38: (1038)Enable to run  (RE)
39:  Protect the inverter from a dew condensation  (DWP)
40:  Enable the integrated commercial line switching sequence (50 Hz)(ISW50)
41:  Enable the integrated commercial line switching sequence (60 Hz) (ISW60)
87: (1087)Select the run command 1 or 2  (FR2/FR1)
88: Run Forward/Stop command 2 (FWD2)
89: Run Reverse/Stop command 2 (REV2)
Note: For (THR) and (STOP), data (1009) and (1030) are assigned for
normal logic, and "9" and "30" are for negative logic respectively.
*1 When you make settings from the keypad, the incremental unit is *2 Symbols in the "Data copy" column
restricted by the number of digits that the LED monitor can display. Y: Will be copied unconditionally.
(Example) If the setting range is from -200.00 to 200.00, Y1: Will not be copied if the rated capacity differs from the source inverter.
the incremental unit is: Y2: Will not be copied if the rated input voltage differs from the source inverter.
"1" for -200 to -100, "0.1" for -99.9 to -10.0 and for N: Will not be copied.
100.0 to 200.0, and "0.01" for -9.99 to -0.01 and for 0.00 to 99.99. *3 If the carrier frequency is set at 1 kHz or below, estimate the motor output torque
at 80% or less of the rated motor torque.
<Changing, validating, and saving function code data when the motor is running>
: Impossible, : Possible (Change data with keys and then save/validate it with key),
: Possible (Change and validate data with keys and then save it with key)
21
Functions Settings

Function Settings
E codes: Extension Terminal Functions
Func. Data
Name Data setting range Min. Unit copy*2 Default setting
Code
Status Signal Assignment to:  [Y1] Select data to specify the terminal function as follows. To assign a - - Y 1
 [Y2] negative logic output to a terminal, set the value of 1000s shown in ( ) on - - Y 2
 [Y3] the table below to the function code. (OFF if short-circuited) Any negative - - Y 15
Relay Contact Output  [Y5A, Y5C] logic cannot be applied for functions without (1000s) data. - - Y 0
 [30A, B, C] - - Y 99
(Mechanical relay contacts)
0: (1000)Inverter running  (RUN)
1: (1001)Frequency equivalence signal  (FAR)
2: (1002)Frequency level detection  (FDT)
3: (1003)Undervoltage detection signal  (LU)
5: (1005)Torque limiting (Current limiting)  (IOL)
6: (1006)Auto-restarting after recovery of power  (IPF)
7: (1007)Motor overload early warning  (OL)
10: (1010)Inverter ready to run (RDY)
11: Switch the motor drive source from the
 commercial power lines to the inverter output (SW88)
12:  Switch the motor drive source from the
 commercial power lines to the inverter output 2 (SW52-2)
13:  Switch the motor drive source from the
 commercial power lines to the inverter output 1  (SW52-1)
15: (1015)Select the AX terminal function (AX)
25: (1025)Turn on/off the cooling fan (FAN)
26: (1026)Retry in operation  (TRY)
27: (1027)The universal DO enabled  (U-DO)
28: (1028) Overheat early warning (OH)
30: (1030)Lifetime alarm  (LIFE)
33: (1033)Command missing detected  (REF OFF)
35: (1035)Inverter running  (RUN2)
36: (1036)Overload prevention control  (OLP)
37: (1037)Current detection  (ID)
42: (1042)PID alarm warning  (PID-ALM)
43: (1043)PID control in operation  (PID-CTL)
44: (1044)PID control out of operation due to the
 slow flow-rate  (PID-STP)
45: (1045)Low output torque detected  (L-TL)
54: (1054)Inverter in remote operation  (RMT)
55: (1055)Run command activated  (AX2)
56: (1056)Motor overheat detected (PTC)  (THM)
99: (1099)Alarm relay output (for any alarm)  (ALM)
Frequency Detection (FDT)(Detection level) 0.0 to 120.0 0.1 Hz Y 60.0
Overload Early Warning/ (Level) 0 (Disabled) 0.01 A Y1 Nominal rated
Current Detection Current value of 1 to 200% of the rated inverter current Y2 current (100%) of
the motor

 (Timer) 0.01 to 600.00*1 0.01 s Y 10.00


PID Display Coefficient A -999 to 0.00 to 999 0.01 - Y 100
PID Display Coefficient B -999 to 0.00 to 999 0.01 - Y 0.00
LED Monitor Item Selection 0: Speed monitor (Select by E48.) - - Y 0
3: Output current
4: Output voltage
8: Calculated torque
9: Input power
10: PID final command value
12: PID feedback amount
14: PID output amount
15: Load rate
16: Motor output
17: Analog input (Monitor)
LED Monitor Item Selection 0: Display the operation guide - - Y 0
1: Display the speed, current or output torque in bar-graph
Display Language Selection 0: Japanese - - Y 0
1: English
2: German
3: French
4: Spanish
5: Italian
Display Contrast Control 0 (low) to 10 (high) - - Y 5
LED Monitor (Speed monitor item) 0: Output frequency - - Y 0
3: Motor speed in rpm
4: Load shaft speed in rpm
7: Display speed in %
Coefficient for Speed Indication 0.01 to 200.00*1 0.01 - Y 30.00
Display Coefficient for 0.0 (Cancel/reset)0.001 to 9999 0.001 - Y 0.010
Accumulated Power Consumption
Keypad(Menu display mode) 0: Function code data setting mode (Menu #0, #1 and #7) - - Y 0
1: Function code data check mode (Menu #2 and #7)
2: Full-menu mode

22
Functions Settings

Function Settings

Func. Data
Name Data setting range Min. Unit copy*2 Default setting
Code
Analog Input Signal Definition for: [12] Select the data to specify the terminal function as follows. - - Y 0
 [C1] - - Y 0
 [V2] - - Y 0
0: None
1: Auxiliary frequency command 1
2: Auxiliary frequency command 2
3: PID process command 1
5: PID feedback amount
20: Analog signal input monitor
Specify How to Save the Digital Set 0: Auto-saving - - Y 0
Frequency 1: Saving by pressing the key

Specify the Inverter Operation 0: Coast-to-stop the motor, 1 to 120, 999: Cancel 1 % Y 999
when Detecting Command Missing
Detect Low Torque(Detection level) 0 to 150 1 % Y 20
 (Timer) 0.01 to 600.00 0.01 s Y 20.00
Terminal Command Assignment to: [FWD] Select data to specify the terminal function as follows. To assign a - - N 98
 [REV] negative logic input to a terminal, set the value of 1000s shown in ( ) in - N Y 99
the table below to the function code.Any negative logic cannot be applied
for functions without (1000s) data.

00: (1000)Multi-step frequency selection (0 to 1 steps)  (SS1)


01: (1001)Multi-step frequency selection (0 to 3 steps)  (SS2)
02: (1002)Multi-step frequency selection (0 to 7 steps)  (SS4)
06: (1006)Self-hold the terminal command  (HLD)
07: (1007)Coast-to-stop command (BX)
8: (1008) Alarm reset  (RST)
09: (1009)Alarm from external equipment  (THR)
11: (1011) Frequency command 2 or 1  (Hz2/Hz1)
 Note: PID process command follows this setting.
13:  DC brake command  (DCBRK)
15:  Switch the motor drive source between the
 commercial line and inverter (50 Hz)  (SW50)
16:  Switch the motor drive source between the
 commercial line and inverter (60 Hz)  (SW60)
17: (1017)UP command  (UP)
18: (1018)DOWN command  (DOWN)
19: (1019)Enable editing of function codes from keypad (WE-KP)  (WE-KP)
20: (1020)Disable PID control  (Hz/PID)
21: (1021)Switch normal/inverted driving  (IVS)
22: (1022)Interlock command  (IL)
24: (1024)Select link operation (Standard and TB bus-optional RS485 communication) (LE)
25: (1025)Universal DI  (U-DI)
26: (1026)Select starting characteristics  (STM)
30: (1030)Forced stop  (STOP)
33: (1033)Reset PID integral and differential components (PID-RST)
34: (1034)Hold PID integral component  (PID-HLD)
35: (1035)Select the local (keypad)  (LOC)
38: (1038)Enable to run  (RE)
39:  Protect the inverter from a dew condensation  (DWP)
40:  Enable the integrated commercial line
 switching sequence (50 Hz) (ISW50)
41:  Enable the integrated commercial line
 switching sequence (60 Hz) (ISW60)
87: (1087)Select the run command 1 or 2  (FR2/FR1)
88:  Run Forward/Stop command 2  (FWD2)
89:  Run Reverse/Stop command 2  (REV2)
98: Run Forward/Stop command  (FWD)
99: Run Reverse/Stop command  (REV)
Note: For (THR) and (STOP), data (1009) and (1030) are assigned for
normal logic, and "9" and "30" are for negative logic respectively.
*1 When you make settings from the keypad, the incremental unit is restricted by the number of digits that the LED monitor can display.
(Example) If the setting range is from -200.00 to 200.00, the incremental unit is:
"1" for -200 to -100, "0.1" for -99.9 to -10.0 and for 100.0 to 200.0, and "0.01" for -9.99 to -0.01 and for 0.00 to 99.99.
*2 Symbols in the "Data copy" column
Y: Will be copied unconditionally.
Y1: Will not be copied if the rated capacity differs from the source inverter.
Y2: Will not be copied if the rated input voltage differs from the source inverter.
N: Will not be copied.

<Changing, validating, and saving function code data when the motor is running>
: Impossible, : Possible (Change data with keys and then save/validate it with key),
: Possible (Change and validate data with keys and then save it with key)

23
Functions Settings

Function Settings
C codes: Control Functions of Frequency
Func. Data
Name Data setting range Min. Unit copy*2 Default setting
Code
Jump Frequency 1 0.0 to 120.0 0.1 Hz Y 0.0
 2 Y 0.0
 3 Y 0.0
Jump Frequency Band 0.0 to 30.0 0.1 Hz Y 0.0
Multi-step Frequency Settings 1 0.00 to 120.00 0.01 Hz Y 0.00
 2 Y 0.00
 3 Y 0.00
 4 Y 0.00
 5 Y 0.00
 6 Y 0.00
 7 Y 0.00
Frequency Command 2 0: Enable the and keys on the keypad - - Y 2
1: Enable the voltage input to terminal [12] (0 to +10 V DC)
2: Enable the current input to terminal [C1] (+4 to +20 mA DC)
3: Enable the sum of voltage and current inputs to terminals [12] and [C1]
5: Enable the voltage input to terminal [V2] (0 to +10 V DC)
7: Enable the (UP)/(DOWN) terminal signal control
Analog Input Adjustment(Gain for terminal input [12]) 0.00 to 200.00*1 0.01 % Y 100.0
 (Filter time constant) 0.00 to 5.00 0.01 s Y 0.05
 (Gain reference point) 0.00 to 100.00*1 0.01 % Y 100.0
Analog Input Adjustment(Gain for terminal input [C1]) 0.00 to 200.00*1 0.01 % Y 100.0
 (Filter time constant) 0.00 to 5.00 0.01 s Y 0.05
 (Gain reference point) 0.00 to 100.00*1 0.01 % Y 100.0
Analog Input Adjustment(Gain for terminal input [V2]) 0.00 to 200.00*1 0.01 % Y 100.0
 (Filter time constant) 0.00 to 5.00 0.01 s Y 0.05
 (Gain reference point) 0.00 to 100.00*1 0.01 % Y 100.0
Bias(Frequency command 1)(Bias reference point) 0.00 to 100.00*1 0.01 % Y 0.00
Bias (PID command 1) (Bias value) -100.00 to 100.00*1 0.01 % Y 0.00
 (Bias reference point) 0.00 to 100.00*1 0.01 % Y 0.00
Select to Run the Motor Forward 0: Forward - - Y 0
or Reverse for the Set Frequency 1 1: Reverse

P codes: Motor Parameters


Func. Data
Name Data setting range Min. Unit copy*2 Default setting
Code
Motor (No. of the poles) 2 to 22 2 Pole Y1 4
Y2
 (Rated capacity) 0.01 to 1,000 kW (where, the data of function code P99 is 0, 3, or 4.) 0.01 kW Y1 Nominal rated capacity
 0.01 to 1,000 HP (where, the data of function code P99 is 1.) 0.01 HP Y2 of standard motors
 (Rated current) 0.00 to 2,000 0.01 A Y1 Nominal rated current of Fuji's standard motor
 (Auto-tuning) 0: Disabled - - N 0
1: Enabled (Tune %R1 and %X while the motor is stopped.)
2: Enabled (Tune %R1 and %X while the motor is stopped, and
no load current while running.)
 (No load current) 0.00 to 2,000 0.01 A Y1 Nominal rated current of Fuji's standard motor
 (%R1) 0.00 to 50.00 0.01 % Y1, Y2 Nominal rated current of Fuji's standard motor
 (%X) 0.00 to 50.00 0.01 % Y1, Y2 Nominal rated current of Fuji's standard motor
Motor Selection 0: Characteristics of motor 0 (Fuji's standard 8- and 9-series motors) - - Y1, Y2 0
1: Characteristics of motor 1 (HP motors)
3: Characteristics of motor 3 (Fuji's standard 6- and 9-series motors)
4: Other motors

H codes: High Performance Functions


Func. Data
Name Data setting range Min. Unit copy*2 Default setting
Code
Data Initializing (Data reset) 0: Disable initialization (All function code data manually set remains.) - - N 0
1: Initialize all function code data to the factory defaults
2: Initialize motor parameters
Retry  (No. of retries) 0: Inactive 1 Times Y 0
1 to 10
 (Latency time) 0.5 to 20.0 0.1 s Y 5.0
Cooling Fan ON/OFF 0: Inactive (Always ON) - - Y 0
1: Active (ON/OFF controllable)
Gradual Acceleration/ Deceleration 0: Inactive (Linear) - - Y 0
1: S-curve (Weak)
2: S-curve (Strong)
3: Curvilinear
Starting Characteristics of the Motor 0: Inactive - - Y 0
 (Synchronization mode) 3: Active (As following the RUN command, the inverter synchronizes the motor rotation either forward or reverse.)
4: Active (As following the RUN command, the inverter synchronizes the motor rotation both forward and reverse.)
5: Active (As following the RUN command, the inverter synchronizes the motor rotation reversely either forward or reverse.)
Deceleration Mode 0: Normal deceleration - - Y
0: Coast-to-stop
Instantaneous Overcurrent Limiting 0: Inactive - - Y 1
1: Active

24
Functions Settings

Function Settings
H codes: High Performance Functions
Func. Data
Name Data setting range Min. Unit copy*2 Default setting
Code
Specify the Inverter Operation at (Waiting time) 0.1 to 10.0 0.1 s Y Depending on the
Instantaneous Power Failure Restarting motor capacity
 (Frequency reduction rate) 0: Set deceleration time 0.01 Hz/s Y 999
 0.01 to 100.00
999: Follow the set current limit
 (DC link voltage allowable to run) 200V series: 200 to 300 1 V Y2 235
400V series: 400 to 600 470
 (Allowable instantaneous 0.0 to 30.0 0.1 s Y 999
 power failure time) 999: The longest time automatically determined by the inverter
Starting Characteristics 0.0 to 120.0 0.1 Hz Y 999
 (Synchronous frequency) 999: Synchronize at the highest output frequency
PTC Thermistor Input 0: Inactive - - Y 0
1: Active (Display on the LED and trip, and immediately stop the inverter after detecting (PTC).)
2: Active (Output PTC warning status on (THM), and continue to run.)
 (Level) 0.00 to 5.00 0.01 V Y 1.60
Communication  (Function selection) Frequency command Run command - - Y 0
Link Operation 0: F01/C30 F02
1: RS485 Link F02
2: F01/C30 RS485 Link
3: RS485 Link RS485 Link
4: RS485 Link (Option) F02
5: RS485 Link (Option) RS485 Link
6: F01/C30 RS485 Link (Option)
7: RS485 Link RS485 Link (Option)
8: RS485 Link (Option) RS485 Link (Option)
Capacity of DC Link Bus Capacitor For indication for replacing the DC link bus capacitor (0000 to FFFF: Hexadecimal) 1 - N -
Accumulated Run Time of Cooling Fan Show an accumulated run time of the cooling fan for replacing it - - N -
Initial Capacity of DC Link Bus Capacitor For indication for replacing the DC link bus capacitor (0000 to FFFF: Hexadecimal) 1 - N Set at factory shipping
Accumulated Run Time of For indication for replacing the capacitors on the PCB - - N -
Capacitors on the PCB (Printed Circuit Board) (0000 to FFFF: Hexadecimal). Resettable.
Non-linear V/f Pattern (Frequency) 0.0 (Cancel), 0.1 to 120.0 0.1 Hz Y 0.0
 (Voltage) 0 to 240: Output voltage AVR-controlled for 200 V class motors 1 V Y2 0
0 to 500: Output voltage AVR-controlled for 400 V class motors
Deceleration Time for Forced Stop 0.00 to 3,600 0.01 s Y 20.0
Bottom Limiter (Specify operation) Peak Freq./Operation Bottom Freq./Operation - - Y 0
0: Limit by F15 (Peak) and continue to run Limit by F16 (Bottom) and continue to run
1: Limit by F15 (Peak) and continue to run Limit by F16 (Bottom) and coast-to-stop
upon lowering the limit.
(Min. freq. when limiter is activated) 0.0 (Depends on F16: Freq. limiter (bottom)), 0.1 Hz Y 2.0
0.1 to 60.0
Automatic Deceleration 0: Inactive - - Y 0
1: Active
Overload Prevention Control 0.00 (Equivalent to deceleration time), 0.01 Hz/s Y 999
 (Frequency drop rate) 0.01 to 100.00, 999 (Cancel)
Deceleration Characteristics 0: Inactive, 1: Active - - Y 0
Gain for Suppression of Output 0.00 to 0.40 0.01 - Y _22 kW
0.20 for <
Current Fluctuation for Motor _30 kW
0.10 for >
Continue to Run(P Component: Gain) 0.000 to 10.000*1 0.001 Times Y 0.250 for <_22 kW
0.244 for >_30 kW
 (I Component: Time) 0.000 to 10.000 *1 0.001 s Y 0.038 for <_22 kW
0.066 for >_30 kW
Accumulated Run Time of Motor Initialize data (Resettable) - - N -

DC Braking 0: Slow - - Y 1
 (Braking response mode) 1: Quick
STOP Key Priority/Start 0 1 2 3 - - Y 0
Check Function
STOP Key Priority OFF ON OFF ON
Start Check Function OFF OFF ON ON
Clear Alarm Data Returns to zero after clearing alarm data (if H97 = 1). - - Y -
Protection/ (Specify operation) 0 to 31: (Display data on the LCD of keypad in decimal format. - - Y 19
Maintenance Values of bit are: "0" for disabled, "1" for enabled (Bits 4, 1, 0 = 1)
Function Bit 0: Auto-lowering the carrier frequency
Bit 1: Protecting the inverter operation from input phase loss
Bit 2: Protecting the inverter operation from output phase loss
Bit 3: Specify a service life criteria for replacing the DC link bus capacitor
Bit 4: Indication the service life for the DC link bus capacitor
*1 When you make settings from the keypad, the incremental unit is restricted by the number of digits that the LED monitor can display.
(Example) If the setting range is from -200.00 to 200.00, the incremental unit is:
"1" for -200 to -100, "0.1" for -99.9 to -10.0 and for 100.0 to 200.0, and "0.01" for -9.99 to -0.01 and for 0.00 to 99.99.
*2 Symbols in the "Data copy" column
Y: Will be copied unconditionally.
Y1: Will not be copied if the rated capacity differs from the source inverter.
Y2: Will not be copied if the rated input voltage differs from the source inverter.
N: Will not be copied.
<Changing, validating, and saving function code data when the motor is running>
: Impossible, : Possible (Change data with keys and then save/validate it with key),
: Possible (Change and validate data with keys and then save it with key)
25
Functions Settings

Function Settings
J codes: Application Functions
Func. Data
Name Data setting range Min. Unit copy*2 Default setting
Code
PID Control 0: Inactive - - Y 0
1: Process control use (Normal action)
2: Process control use (Inverse action)
 (Remote process command) 0: Keypad - - Y 0
1: PID process command 1 (Data settings of E60, E61 and E62 are also
required.)
3: UP/DOWN
4: Communication
 P (Gain) 0.000 to 30.000*1 0.001 Times Y 0.100
 I (Integration time) 0.0 to 3600.0*1 0.1 s Y 0.0
 D (Differentiation time) 0.00 to 600.00*1 0.01 s Y 0.00
 (Feedback filter) 0.0 to 900.0 0.1 s Y 0.5
 (Anti-rest/windup) 0 to 200 1 % Y 200
 (Select alarm output) 0: Alarm in absolute value - - Y 0
1: Alarm in absolute value with HOLD
2: Alarm in absolute value with LATCH
3: Alarm in absolute value with HOLD and LATCH
4: Alarm in deviation value
5: Alarm in deviation value with HOLD
6: Alarm in deviation value with LATCH
7: Alarm in deviation value with HOLD and LATCH
 (Peak limit alarm(AH)) 0 to 100 1 % Y 100
 (Bottom limit alarm(AL)) 0 to 100 1 % Y 0
 (Stop frequency for slow flowrate) 0: Disabled, 1 to 120 1 % Y 0
(Elapsed stop time for slow flowrate) 1 to 60 1 s Y 0
 (Starting frequency) 0: Disabled, 1 to 120 1 Hz Y 0
 (Upper limit of PID process output) 1 to120, 999: Depends on setting of F15 1 Hz Y 999
 (Lower limit of PID process output) 1 to120, 999: Depends on setting of F16 1 Hz Y 999
Dew Condensation Protection(Duty) 1 to 50 1 % Y 1
Commercial Line Switching Sequence 0: Integrated standard switching sequence - - Y 0
1: Auto-switching sequence for inverter alarm

y codes: Link Functions


Func. Data
Name Data setting range Min. Unit copy*2 Default setting
Code
RS485 Communication (Station address) 1 to 255 1 - Y 1
(Standard)
(Mode selection on no response error) 0: Immediate trip and alarm - - Y 0
1: Trip and alarm after running for the period of the timer set by y03
2: Retry during the period of the timer set by y03. If retry fails, trip and
alarm If it succeeds, continue to run.
3: Continue to run
 (Timer) 0.0 to 60.0 0.1 s Y 2.0
 (Transmission rate) 0: 2,400 - bps Y 3
1: 4,800
2: 9,600
3: 19,200
4: 38,400
 (Data length) 0: 8 - bit Y 0
1: 7
 (Parity check) 0: None - - Y 0
1: Even parity
2: Odd parity
 (Stop bits) 0: 2 - bit Y 0
1: 1
(No response error detection time) 0 (No detection), 1 to 60 1 s Y 0
 (Response interval) 0.00 to 1.00 0.01 s Y 0.01
 (Protocol selection) 0: Modbus RTU protocol - - Y 1
1: SX protocol (Loader protocol)
2: Fuji general-purpose inverter protocol

26
Functions Settings

Function Settings
y codes: Link Functions
Func. Data
Name Data setting range Min. Unit copy*2 Default setting
Code
RS485 Communication (Station address) 1 to 255 1 - Y 1
(TB bus option)
(Mode selection on no response error) 0: Immediate trip and alarm - - Y 0
1: Trip and alarm after running for the period of the timer set by y03
2: Retry during the period of the timer set by y03. If retry fails, trip and
alarm If it succeeds, continue to run.
3: Continue to run
 (Timer) 0.0 to 60.0 0.1 s Y 2.0
 (Transmission rate) 0: 2,400 - bps Y 3
1: 4,800
2: 9,600
3: 19,200
4: 38,400
 (Data length) 0: 8 - bit Y 0
1: 7
 (Parity check) 0: None - - Y 0
1: Even parity
2: Odd parity
 (Stop bits) 0: 2 - bit Y 0
1: 1
(No response error detection time) 0 (No detection), 1 to 60 1 s Y 0
 (Response interval) 0.00 to 1.00 0.01 s Y 0.01
 (Protocol selection) 0: Modbus RTU protocol - - Y 1
1: SX protocol (Loader protocol)
2: Fuji general-purpose inverter protocol
Bus Link Function for Frequency Command source Run command source - - Y 0
Supporting Data Input 0: Follow H30 Follow H30
1: Field bus option Follow H30
2: Follow H30 Field bus option
3: Field bus option Field bus option
Loader Link Function for Frequency Command source Run command source - - N 0
Supporting Data Input 0: Follow H30 and y98  Follow H30 and y98
1: Loader  Follow H30 and y98
2: Follow H30 and y98  Loader
3: Loader  Loader

*1 When you make settings from the keypad, the incremental unit is restricted by the number of digits that the LED monitor can display.
(Example) If the setting range is from -200.00 to 200.00, the incremental unit is:
"1" for -200 to -100, "0.1" for -99.9 to -10.0 and for 100.0 to 200.0, and "0.01" for -9.99 to -0.01 and for 0.00 to 99.99.
*2 Symbols in the "Data copy" column
Y: Will be copied unconditionally.
Y1: Will not be copied if the rated capacity differs from the source inverter.
Y2: Will not be copied if the rated input voltage differs from the source inverter.
N: Will not be copied.

<Changing, validating, and saving function code data when the motor is running>
: Impossible, : Possible (Change data with keys and then save/validate it with key),
: Possible (Change and validate data with keys and then save it with key)

27
Options

Options
Name (Type) Appearance Name (Type) Appearance
DC REACTOR Remote operation Type Length(m)
extension cable CB-5S 5
CB-3S 3
CB-1S 1

Cable
Connector : RJ45

8
1
L

Wiring equipment
Molded-case circuit breaker (MCCB), Magnetic contactor(MC) Recommended cable size [mm2]
Power Applicable
supply motor Earth-leakage circuit breaker (ELCB), Input circuit Output
Inverter type Input circuit Output DB circuit
voltage rating Rated current [A] (L1/R, L2/S, L3/T) circuit
circuit (P1, P(+))
[kW] With DCR Without reactor With DCR Without reactor With DCR Without reactor (U, V, W)
Three-  0.75 FRN0.75F1S-2A
phase  1.5 FRN1.5F1S-2A
200V  2.2 FRN2.2F1S-2A
 3.7 FRN3.7F1S-2A
 5.5 FRN5.5F1S-2A 30 50 SC-05 SC-N1 SC-4-0 2.0 5.5 2.0 2.0
 7.5 FRN7.5F1S-2A 40 75 SC-5-1 SC-N2 SC-5-1 3.5 8.0 3.5 3.5
 11 FRN11F1S-2A 50 100 SC-N1 SC-N2S SC-N1 5.5 14 5.5 8.0
 15 FRN15F1S-2A 75 125 SC-N2 SC-N3 SC-N2 14 22 8.0 14
 18.5 FRN18.5F1S-2A 100 150 SC-N2S SC-N4 SC-N2S 14 38 14 22
 22 FRN22F1S-2A 100 175 SC-N2S SC-N5 SC-N2S 14 38 14 22
 30 FRN30F1S-2A 150 200 SC-N4 SC-N7 SC-N4 38 60 38 38
 37 FRN37F1S-2A 175 250 SC-N5 SC-N8 SC-N5 38 60 38 60
 45 FRN45F1S-2A 200 300 SC-N7 SC-N8 SC-N7 60 100 60 100
 55 FRN55F1S-2A 250 350 SC-N8 SC-N11 SC-N8 100 100 100 100
 75 FRN75F1S-2A 350 - SC-N11 - SC-N11 100 - 100 150
 90 FRN90F1S-2A
 110 FRN110F1S-2A
Three-  0.75 FRN0.75F1S-4A
phase  1.5 FRN1.5F1S-4A
400V  2.2 FRN2.2F1S-4A
 3.7 FRN3.7F1S-4A
 5.5 FRN5.5F1S-4A 15 30 SC-05 SC-4-0 SC-05 2.0 2.0 2.0 2.0
 7.5 FRN7.5F1S-4A 20 40 SC-05 SC-5-1 SC-05 2.0 3.5 2.0 2.0
 11 FRN11F1S-4A 30 50 SC-05 SC-N1 SC-4-0 2.0 5.5 2.0 2.0
 15 FRN15F1S-4A 40 60 SC-5-1 SC-N1 SC-5-1 3.5 8.0 3.5 3.5
 18.5 FRN18.5F1S-4A 40 75 SC-N1 SC-N2 SC-N1 5.5 14 5.5 5.5
 22 FRN22F1S-4A 50 100 SC-N1 SC-N2S SC-N1 5.5 14 5.5 8.0
 30 FRN30F1S-4A 75 125 SC-N2 SC-N3 SC-N2 14 22 14 14
 37 FRN37F1S-4A 100 125 SC-N2S SC-N4 SC-N2S 14 22 14 22
 45 FRN45F1S-4A 100 150 SC-N3 SC-N4 SC-N3 22 38 22 22
 55 FRN55F1S-4A 125 200 SC-N3 SC-N5 SC-N4 22 60 38 38
 75 FRN75F1S-4A 175 - SC-N4 - SC-N5 38 - 60 60
 90 FRN90F1S-4A
 110 FRN110F1S-4A
 132 FRN132F1S-4A
 160 FRN160F1S-4A
 200 FRN200F1S-4A
 220 FRN220F1S-4A
 280 FRN280F1S-4A
 315 FRN315F1S-4A
 355 FRN355F1S-4A
 400 FRN400F1S-4A
 450 FRN450F1S-4A
 500 FRN500F1S-4A
• For MCCB and ELCB, the required frame type and series depend on the facility transformer capacity and other factors. When selecting optimal breakers, refer to the relevant
catalog or technical data.
• Also select the rated sensitive current of ELCB utilizing the technical data. The above rated currents of MCCB and ELCB are for Fuji's SA B/ , SA R/ breakers.
• The recommended wire sizes are based on the temperature inside the panel not exceeding 50˚C.
• The above wires are 600V HIV insulated solid wires (75˚C).
• Data in the above table may differ according to environmental conditions (ambient temperature, power supply voltage, and other factors).
(Note) Use low-pressure crimp terminal CB150-10 (JEM1399) for the crimp terminal of FRN75F1S-2A.
Inverter types indicated with are available soon.
28
Japanese Guidelines for Suppressing Harmonics

Guideline for Suppressing Harmonics in


Home Electric and General-purpose Appliances
Our three-phase, 200V series inverters of 3.7kW or less (FRENIC-Eco series) are the products specified in the "Guideline for Suppressing Harmonics in Home Electric and General-purpose Appliances"
(established in September 1994, and revised in October 1999) published by the Ministry of Economy, Trade and Industry. The Japan Electrical Manufacturers' Association has determined a standard of
regulation levels based on this guideline. To meet this standard, a reactor (for harmonic suppression) must be connected to an inverter. Use a "DC REACTOR" introduced in this catalog.
For a reactor you want to prepare, please contact us about detailed specifications.

Guideline for Suppressing Harmonics by Customers


Receiving High Voltage or Special High Voltage
Our three-phase, 200V series inverters of 5.5kW or more and three-phase, 400V series inverters (FRENIC-Eco series) are the products specified in the "Guideline for Suppressing Harmonics by Customers Receiving High
Voltage or Special High Voltage." When you enter into a new contract with an electric power company or update a contract, you are requested by the electric power company to submit an accounting statement form.

(1) Scope of regulation Table 4 "Input fundamental currents" of general-purpose inverters determined by the nominal applied motors
Nominal applied
In principle, the guideline applies to the customers that meet the following two conditions: motor[kW] 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22
• The customer receives high voltage or special high voltage. Input 200V *Inapplicable inverter models 19.1 25.6 36.9 49.8 61.4 73.1
• The "equivalent capacity" of the converter load exceeds the standard value fundamental
current [A]
400V 0.81 1.37 2.75 3.96 6.50 9.55 12.8 18.5 24.9 30.7 36.6
for the receiving voltage (50kVA at a receiving voltage of 6.6kV).
6.6kV converted
value [mA] 49 83 167 240 394 579 776 1121 1509 1860 2220
(2) Regulation method Nominal applied
The level (calculated value) of the harmonic current that flows from the customer's receiving motor[kW] 30 37 45 55 75 90 110 132 160 200 220
point out to the system is subjected to the regulation. The regulation value is proportional to Input 200V 98.0 121 147 180 245 293 357
the contract demand. The regulation values specified in the guideline are shown in Table 1. fundamental
current [A]
400V 49.0 60.4 73.5 89.9 123 147 179 216 258 323 355
6.6kV converted
Table 1 Upper limits of harmonic outflow current per kW of contract demand [mA/kW] value [mA] 2970 3660 4450 5450 7450 8910 10850 13090 15640 19580 21500
Nominal applied
Receiving voltage 5th 7th 11th 13th 17th 19th 23th Over 25th motor[kW] 250 280 315 355 400 450 500 530 560 630
6.6kV 3.5 2.5 1.6 1.3 1.0 0.90 0.76 0.70 Input 200V
fundamental
22kV 1.8 1.3 0.82 0.69 0.53 0.47 0.39 0.36 current [A]
400V 403 450 506 571 643 723 804 852 900 1013
6.6kV converted
value [mA] 24400 27300 30700 34600 39000 43800 48700 51600 54500 61400
1. Calculation of Equivalent Capacity (Pi)
(2) Calculation of harmonic current
Although the equivalent capacity (Pi) is calculated using the equation of (input rated
capacity) x (conversion factor), catalog of conventional inverters do not contain Table 5 Generated harmonic current [%], 3-phase bridge (capacitor smoothing)
input rated capacities. A description of the input rated capacity is shown below: Degree 5th 7th 11th 13th 17th 19th 23th 25th
(1) "Inverter rated capacity" corresponding to "Pi" Without a reactor 65 41 8.5 7.7 4.3 3.1 2.6 1.8
• Calculate the input fundamental current l1 from the kW rating and efficiency With a reactor (ACR) 38 14.5 7.4 3.4 3.2 1.9 1.7 1.3
of the load motor, as well as the efficiency of the inverter. Then, calculate the With a reactor (DCR) 30 13 8.4 5.0 4.7 3.2 3.0 2.2
input rated capacity as shown below:
Input rated capacity = 3 x (power supply voltage) x l1 x 1.0228/1,000 [kVA] With reactors (ACR and DCR) 28 9.1 7.2 4.1 3.2 2.4 1.6 1.4
Where 1.0228 is the 6-pulse converter's value of (effective current) / • ACR: 3%
(fundamental current). • DCR: Accumulated energy equal to 0.08 to 0.15ms (100% load conversion)
• When a general-purpose motor or inverter motor is used, the appropriate • Smoothing capacitor: Accumulated energy equal to 15 to 30ms (100% load conversion)
value shown in Table 2 can be used. Select a value based on the kW rating • Load: 100%
of the motor used, irrespective of the inverter type. Calculate the harmonic current of each degree using the following equation:
Generated nth harmonic current [%]
Table 2 "Input rated capacities" of general-purpose inverters determined by the nominal applied motors nth harmonic current [A] = Fundamental current [A] x
Nominal applied 100
motor[kW] 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22
(3) Maximum availability factor
Pi 200V *Inapplicable inverter models 6.77 9.07 13.1 17.6 21.8 25.9 • For a load for elevators, which provides intermittent operation, or a load with a sufficient
[kVA] 400V 0.57 0.97 1.95 2.81 4.61 6.77 9.07 13.1 17.6 21.8 25.9
designed motor rating, reduce the current by multiplying the equation by the "maximum
Nominal applied availability factor" of the load.
motor[kW] 30 37 45 55 75 90 110 132 160 200 220
• The "maximum availability factor of an appliance" means the ratio of the capacity of the
Pi 200V 34.7 42.8 52.1 63.7 87.2 104 127 harmonic generator in operation at which the availability reaches the maximum, to its total
[kVA] 400V 34.7 42.8 52.1 63.7 87.2 104 127 153 183 229 252 capacity, and the capacity of the generator in operation is an average for 30 minutes.
Nominal applied • In general, the maximum availability factor is calculated according to this definition, but the
motor[kW] 250 280 315 355 400 450 500 530 560 630 standard values shown in Table 6 are recommended for inverters for building equipment.
Pi 200V
[kVA] 400V 286 Table 6 Availability factors of inverters, etc. for building equipment (standard values)
319 359 405 456 512 570 604 638 718
Equipment type Inverter capacity category Single inverter availability factor
Air conditioning 200kW or less 0.55
(2) Values of "Ki (conversion factor)" system
• Depending on whether an optional ACR (AC REACTOR) or DCR (DC REACTOR)
Over 200kW 0.60
is used, apply the appropriate conversion factor specified in the appendix to the Sanitary pump 0.30
guideline. The values of the converter factor are shown in Table 3. Elevator 0.25
Table 3 "Conversion factors Ki" for general-purpose inverters determined by reactors Refrigerator, freezer 50kW or less 0.60
UPS (6-pulse) 200kVA 0.60
Circuit category Circuit type Conversion factor Ki Main applications
Without a reactor K31=3.4 • General-purpose inverters [Correction coefficient according to contract demand level]
Three-phase bridge With a reactor (ACR) K32=1.8 • Elevators • Since the total availability factor decreases if the scale of a building increases, calculating
3 • Refrigerators, reduced harmonics with the correction coefficient s defined in Table 7 below is permitted.
(capacitor smoothing) With a reactor (DCR) K33=1.8 air conditioning systems
Table 7 Correction coefficient
With reactors (ACR and DCR) K34=1.4 • Other general appliances Contract demand [kW] Correction coefficient
according to the building scale
300 1.00
2. Calculation of Harmonic Current 500 0.90
*If the contract demand is between two
(1) Value of "input fundamental current" 1000 0.85
specified values shown in Table 7,
• Apply the appropriate value shown in Table 4 based on the kW rating of the 2000 0.80 calculate the value by interpolation.
motor, irrespective of the inverter type or whether a reactor is used.
* If the input voltage is different, calculate the input fundamental current in (4) Degree of harmonics to be calculated
inverse proportion to the voltage. Calculate only the "5th and 7th" harmonic currents.

29
Lineup

Fuji inverter family consisting of wide model


variations for various purposes of use

Series name
Application Features
(Catalog No.)

High-performance, multifunction inverter


(Three-phase 200V: 0.2 to 90kW, Three-phase 400V: 0.4 to 400kW)
FRENIC5000G11S • Fuji's dynamic torque vector control has made it possible to achieve 200% starting torque at 0.5Hz.
(MEH403 for JE)
• Loaded with many convenient functions such as automatic tuning.
(MEH413 for EN)
• Compact and full-closed (22kW or smaller), and selectable from wide variations ranging from 0.2 to 400kW.

Inverter best suited for HVAC (Heating, Ventilating, and Air-Conditioning)


(Three-phase 200V: 0.75 to 110kW, Three-phase 400V: 0.75 to 500kW)
[New]
• Line/Inverter switching, full PID control functions for optimum fan and pump control
FRENIC-Eco • Various functions contributing to energy-saving
(MEH442) • Consideration for surrounding environment and global compatibility

Fan/pump drive inverter


(Three-phase 200V: 5.5 to 110kW, Three-phase 400V: 5.5 to 500kW)
• Developed specifically for variable torque load required to drive funs and pumps.
FRENIC5000P11S
(MEH403) • Energy-saving operation is easy, thanks to automatic energy saving function.
• Interactive keypad is standard-equipped for easy operation.

General use
for industrial
equipment High-performance compact inverter
(Three-phase 200V: 0.1 to 7.5kW, Single-phase 200V: 0.1 to 2.2kW, Three-phase 400V: 0.4 to 7.5kW)
FVR-E11S • Fuji's dynamic torque vector control has made it possible to achieve 200% starting torque at 0.5Hz.
(MEH404 for JE) • Loaded with many convenient functions such as automatic tuning, slip compensation, torque limit, and 16-
(MEH414 for EN) step speed change.
• Various maintenance functions are available; for example, indication of main circuit capacitor life and
indication of cumulative operation time.

Compact inverter
[New] (Three-phase 200V: 0.1 to 3.7kW, Single-phase 200V: 0.1 to 2.2kW, Three-phase 400V: 0.4 to 3.7kW)
• Frequency setting dial is standard-equipped for each operation.
FRENIC-Mini
• Loaded with automatic torque boost, current limit and slip compensation functions, which are best-suited
(MEH441 for Asia) for operating transverse conveyors.
(MEH451 for Europe)
• Equipped with automatic energy-saving function and PID control function, which are suitable for driving
fans and pumps.

High-performance vector control inverter


(Three-phase 200V: 0.75 to 90kW, Three-phase 400V: 3.7 to 400kW)
• High-precision inverter that quickly responds to the control signals and has stable torque characteristics.
FRENIC5000VG7S
(MEH405) • Abundant functions and various options permit wide application to general industrial systems.
• Automatic tuning function allows you to operate general-purpose motors under vector control.

30
31
NOTES
cause poor lubrication. Avoid such operation. to  improve  the  inverter  power  factor.)  Do  not  use 
In running general-purpose motors power  factor  correcting  capacitors  in  the  inverter 
• Synchronous motors
output  circuit.  An  overcurrent  trip  will  occur, 
• Driving a 400V general-purpose motor It  is  necessary  to  use  software  suitable  for  this 
disabling motor operation.
When  driving  a  400V  general-purpose  motor  with  motor type. Contact Fuji for details.
an inverter using extremely long cables, damage to  • Single-phase motors • Discontinuance of surge killer
the  insulation  of  the  motor  may  occur.  Use  an  Do not mount surge killers in the inverter secondary 
Single-phase  motors  are  not  suitable  for  inverter-
output circuit filter (OFL) if necessary after checking  circuit.
driven  variable  speed  operation.  Use  three-phase 
with  the  motor  manufacturer.  Fuji's  motors  do  not  motors. • Reducing noise
require  the  use  of  output  circuit  filters  because  of  * Even if a single-phase power supply is available,  Use  of  a  filter  and  shielded  wires  are  typical 
their reinforced insulation. use a three-phase motor as the inverter provides  measures  against  noise  to  ensure  that  EMC 
• Torque characteristics and temperature rise three-phase output. Directives  are  met.  Refer  to  Appendices,  App.  A 
When the inverter is used to run a general-purpose  "Advantageous Use of Inverters (Notes on electrical 
motor,  the  temperature  of  the  motor  becomes  Environmental conditions noise)" for details.
higher than when it is operated using a commercial  • Measures against surge currents
power  supply.  In  the  low-speed  range,  the  cooling  • Installation location
Use  the  inverter  in  a  location  with  an  ambient  If  an  overvoltage  trip  occurs  while  the  inverter  is 
effect  will  be  weakened,  so  decrease  the  output  stopped  or  operated  under  a  light  load,  it  is 
torque of the motor. If constant torque is required in  temperature range of -10 to 50˚C.
The  inverter  and  braking  resistor  surfaces  become  assumed  that  the  surge  current  is  generated  by 
the low-speed range, use a Fuji inverter motor or a  open/close of the phase-advancing capacitor in the 
motor  equipped  with  an  externally  powered  hot  under  certain  operating  conditions.  Install  the 
inverter on nonflammable material such as metal. power system.
ventilating fan. * Connect a DC REACTOR to the inverter.
Ensure  that  the  installation  location  meets  the 
• Vibration environmental conditions specified in "Environment"  • Megger test
Use of an inverter does not increase vibration of a  in Common specifications on page 11. When  checking  the  insulation  resistance  of  the 
general-purpose  motor,  but  when  the  motor  is  inverter,  use  a  500V  megger  and  follow  the 
mounted  to  a  machine,  resonance  may  be  caused  Combination with peripheral devices instructions  contained  in  the  FRENIC-Eco 
by  the  natural  frequencies,  including  that  of  the  Instruction Manual.
machine system. • Installing a molded case circuit breaker (MCCB) 
* The use of a rubber coupling or vibration  or earth leakage circuit breaker (ELCB) Wiring
dampening rubber is recommended. Install a recommended molded case circuit breaker 
* It is also recommended to use the inverter jump  (MCCB) or an earth leakage circuit breaker (ELCB)  • Control circuit wiring length
frequency control to avoid resonance points. (with  the  exception  of  those  exclusively  designed  When  using  remote  control,  limit  the  wiring  length 
Note  that  operation  of  a  2-pole  motor  at  60Hz  or  for  protection  from  ground  faults)  in  the  primary  between  the  inverter  and  operator  box  to  20m  or 
more may cause abnormal vibration. circuit  of  the  inverter  to  protect  the  wiring.  Ensure  less and use twisted shielded cable.
that  the  circuit  breaker  capacity  is  equivalent  to  or 
• Noise • Wiring length between inverter and motor
lower than the recommended capacity.
When  an  inverter  is  used  with  a  general-purpose  If  long  wiring  is  used  between  the  inverter  and  the 
motor, the motor noise level is higher than that with  • Installing a magnetic contactor (MC)  motor, the inverter will overheat or trip as a result of 
a commercial power supply. To reduce noise, raise  in the secondary circuit overcurrent (high-frequency current flowing into the 
carrier  frequency  of  the  inverter.  High-speed  If  a  magnetic  contactor  (MC)  is  mounted  in  the  stray  capacitance)  in  the  wires  connected  to  the 
operation  at  60Hz  or  more  can  also  result  in  more  inverter's  secondary  circuit  for  switching  the  motor  phases. Ensure that the wiring is shorter than 50m. 
noise. to  commercial  power  or  for  any  other  purpose,  If  this  length  must  be  exceeded,  lower  the  carrier 
ensure that both the inverter and the motor are fully  frequency or mount an output circuit filter (OFL).
In running special motors stopped before you turn the MC on or off.
Remove  the  surge  sappressor  integrated  with  the  • Wiring size
• Explosion-proof motors MC. Select cables with a sufficient capacity by referring 
When  driving  an  explosion-proof  motor  with  an  to the current value or recommended wire size.
inverter,  use  a  combination  of  a  motor  and  an  • Installing a magnetic contactor (MC) 
in the primary circuit • Wiring type
inverter that has been approved in advance. Do not use multicore cables.
Do  not  turn  the  magnetic  contactor  (MC)  in  the 
• Submersible motors and pumps primary circuit on or off more than once an hour as  • Grounding
These  motors  have  a  larger  rated  current  than  an  inverter  fault  may  result.  If  frequent  starts  or  Securely  ground  the  inverter  using  the  grounding 
general-purpose  motors.  Select  an  inverter  whose  stops  are  required  during  motor  operation,  use  terminal.
rated  output  current  is  greater  than  that  of  the  FWD/REV signals.
motor. Selecting inverter capacity
These motors differ from general-purpose motors in  • Protecting the motor
thermal  characteristics.  Set  a  low  value  in  the  The  electronic  thermal  facility  of  the  inverter  can  • Driving general-purpose motor
thermal time constant of the motor when setting the  protect the motor. The operation level and the motor  Select an inverter according to the applicable motor 
electronic thermal facility. type (general-purpose motor, inverter motor) should  ratings listed in the standard specifications table for 
be  set.  For  high-speed  motors  or  water-cooled  the  inverter.  When  high  starting  torque  is  required 
• Brake motors motors,  set  a  small  value  for  the  thermal  time 
For  motors  equipped  with  parallel-connected  or  quick  acceleration  or  deceleration  is  required, 
constant  to  protect  the  motor,  in  combination  with  select  an  inverter  with  a  capacity  one  size  greater 
brakes,  their  braking  power  must  be  supplied  from  the "cooling system OFF" signal.
the primary circuit (commercial power supply). If the  than the standard.
If you connect the motor thermal relay to the motor 
brake  power  is  connected  to  the  inverter  power  with  a  long  cable,  a  high-frequency  current  may  • Driving special motors
output  circuit  (secondary  circuit)  by  mistake,  flow  into  the  wiring  stray  capacitance.  This  may  Select an inverter that meets the following condition:
problems may occur. cause  the  relay  to  trip  at  a  current  lower  than  the  Inverter rated current > Motor rated current
Do  not  use  inverters  for  driving  motors  equipped  set  value  for  the  thermal  relay.  If  this  happens, 
with series-connected brakes. lower the carrier frequency or use the output circuit  Transportation and storage
• Geared motors filter (OFL).
When  transporting  or  storing  inverters,  follow  the 
If  the  power  transmission  mechanism  uses  an  oil- • Discontinuance of power-factor correcting capacitor procedures  and  select  locations  that  meet  the 
lubricated  gearbox  or  speed  changer/reducer,  then  Do not mount power factor correcting capacitors in  environmental  conditions  listed  in  the  FRENIC-Eco 
continuous  motor  operation  at  low  speed  may  the inverter primary circuit. (Use the DC REACTOR  Instruction Manual.