Business-Critical Continuity

Selecting Business-Critical

The d e c i s i o n s y o u Its time to rediscover performance benchmarks and design


mak e o n p o w e r innovations that separate power transfer switches
transfer switches for
protecting your Life safety, financial Although the backup not created equally.
business-critical loss, productivity, valuable power source may be There are important
information and conve- functional only when the differences that need to be
operations will
nience all are at stake when primary source fails, the weighed and new sophisti-
affe ct t h o s e power fails. Time is money, transfer switch is the only cated power transfer switch
operations for 20 or so time without power is link between the two power technology that requires
more years unacceptable because it can sources. So the automatic consideration.
cripple an organizations transfer switch is the brain Even if you feel you
operations. of the power distribution are up to speed on transfer
No matter what type of system and is always carry- switches, its time to look
power source is selected for ing power to crucial loads, again because the stakes are
backup power protection, regardless of which power so high.
a reliable electrical device source is feeding the load. Be certain you are
is needed to automatically Because so much hangs making the right decision
sense the unacceptability of in the balance, there is no on such a critical matter as
the primary power source room for error. Making the emergency and standby
ASCO Power Technologies and transfer the load to the right decision is the only power. Then have peace of
doesnt generate power, secondary. option. mind knowing you selected
it controls, distributes, But what decision is the the best products in the
transfers, monitors, right one? That depends on industry to protect a facility.
measures, manages, displays, a number of factors.
maintains, services and
All transfer switches are
communicates with it.

1
Power Transfer Switches
Theyre WHAT Data,
Consider 13 points for performance, reliability.
financial and
telecommunications New, important information to help you
centers, healthcare make the right decision...
facilities and other because your reputation is on the line.
operations Need
Would you put your power transfer technology, Controlling operation
reputation on the line with as justified by their field Transferring motor loads
just any automatic power proven technology perfor- without abnormal inrush
transfer switch? mance. currents
Shouldnt you depend Thirteen points of Providing the connection
on one with components differentiation separate strategy for the needs of
designed specifically for superior power transfer the load
transfer switch duty? Or one switches from all others. Open Transition Transfer
with components designed The points are: In phase
for other applications? Providing fast, consistent Delayed transition
The design of each and and dependable power Close Transition Transfer
every part in the product transfer High speed transfer
determines how reliably a Preserving contact integ- Softload transition
power transfer switch trans- rity and performance transfer
fers power. It also deter- Extinguishing arcs safely Employing remote com-
mines reliability of specific and quickly munications capability
functions, such as making Withstanding and closing Providing 24/7 service
and breaking electrical con- on fault currents and maintenance
nections, extinguishing arcs Overlapping switched Meeting or exceed-
and others. neutral poles ing minimum code
Every component of Designing quality and requirements
ASCO 7000 Series Power dependable components Capitalizing on innovative
Transfer Switches has been intelligently technology.
designed for one purpose.
They have ASCOs reputa-
tion for legendary reliability
built into every transfer
switch. They have stood
the test of time and are the
benchmarks for todays

Every component and


assembly, such as the transfer
switch assembly on the right,
has been designed exclusively
for automatic power transfer
switch duty.
2
Transferring Power
Requires a dependable mechanism.

The heart of all ASCO Its design ensures that connected to both power
transfer switches is the loads will never be unin- sources at the same time.
single solenoid operator, tentionally transferred Importantly, the
unique in the transfer to a dead or inadequate solenoid is never fused
switch industry. Time and source as the solenoid is as some operators are.
again, it provides repeat- powered from the source Fusing can render the
able, fast, true double- to which the load is being transfer switch inoper-
throw operation. transferred. The positive able, an obviously undesir-
The operator has a interlocking design helps able feature for business
proven track record for keep the main contacts critical uses.
simplicity, dependability closed during short circuit
and easy maintainability conditions. Its true,
because it has no motors, double throw design en- ASCO designed and com-
mercialized the first solenoid
gears or complicated sures crucial loads are not
operated transfer switch.
mechanisms.

3
ASCO-designed segmented contacts

Preser ving
Theres nothing quite
like a transfer switch.
Its performance
requirements are unique
in emergency and standby
Contact Integrity
power systems
And Performance
Between dissimilar power sources.
Transfer switches are contact integrity, high Segmented main
responsible for transferring conductivity to the main contacts are part of larger
loads between dissimilar contacts, and endurance to transfer switches for
power sources that could be carry the full load continu- business-critical applica-
as much as 180o apart. ously and still be capable tions. Segmented contacts
ASCO transfer switches of enduring damaging provide multiple points to
manage this task with overloads and short circuit ensure ample contact sur-
contacts designed specifi- currents. The alloy also face area and to minimize
cally for transfer switch duty prevents excessive tempera- heat rise.
by ASCO engineers. The ture rise that can deterio- Contacts designed for
contacts are not adapted rate insulation and cause a dedicated transfer switch
from other devices, such as breakdown. duty provide long-term,
circuit breakers, contactors Separate arcing con- reliable operation. This has
or motor starters. tacts on transfer switches been field proven by the
This dedicated design rated 800 amps and larger hundreds of thousands
approach has produced a protect the main contacts of ASCO transfer switch
contact that solves the spe- from arcings damaging products provided for in-
cial demands of transferring effects by making first and stallation in emergency and
critical loads reliably time breaking last. standby power systems.
after time. Smaller transfer
Main contact alloy switches are designed with
composition is specifically arc runners and arcing tips
selected from a silver alloy. to preserve main contact
The alloy provides optimum surface integrity.

4
ASCO arc splitters

Extinguishing Arcs
Ar cs c r eated wh en
tr ans fe r ring l o ads
fro m one so u rce t o
an o th er can be Prevents direct, source-to-source shorting.
catastr o p hic f o r
Heat damage to away from the main con- Transfer switches
transfe r switches and contacts is one problem. tacts quickly and safely using contacts designed
thei r B u siness-c ritical Another is direct, source- by pulling it up into the for other devices, such as
lo ads to-source shorting if the arc chute assembly plates with circuit breakers, have nar-
is not extinguished before magnetic force created by rower gaps, since they are
the switch closes in on the the current flow through the designed for interrupting
alternate source. This can transfer switch pole struc- currents in excess of their
result in a source-to-source ture. This also stretches and full load, continuous current
short circuit, which can to- cools the arc, minimizing rating (not below their rat-
tally destroy transfer switch heat damage. ing).
integrity . Consideration also must
ASCO power transfer be provided for extinguish-
switches extinguish arcs ing arcs at reduced load
Finite element analysis
and 3-D computer models using an arc chute assem- currents. ASCO has the
(above) create components bly specially designed for industrys widest arc gap
that are specifically designed double-throw operation. between fully opened
for transfer switch duty. The design moves the arc contacts. A wide gap main- ASCO has the industrys
Durability and reliability are tains the transfer switchs widest arc gap between fully
built in. See page 27 for more opened contacts.
low-connect interrupting
information on how ASCO effectiveness when it is
designs intelligently. lightly loaded and magnetic
forces are not as strong.

5
ASCO design technology keep contacts closed

Withstanding
And Closing
On Fault Currents
Demands robust withstand and close-on ratings.
Withstanding and clos-
ing on short circuit currents Withstand and Close-On Ratings* for ASCO 7000 Series Automatic Transfer Switches
require transfer switches 150-3000 amps
that can manage extremely
high magnetic forces and Amps Amps Amps
thermal dynamics. Continuous Current Rating 150-600 800-1200 1600-3000
While circuit break- Any breaker (three cycle) 35,000 50,000 100,000
ers and fuses are designed Specific breakers 50,000 65,000 100,000
to open on short circuit Short time (withstand) 36,000 65,000
currents, power transfer Short time (duration) 18 cycles 30 cycles
switches must withstand *(RMS symmetrical amps at 480 VAC)
the short circuit current
until the overcurrent device
clears the fault. Contact material com- a variety of overcurrent
ASCO power transfer position, pole and contact devices, such as circuit ASCO commercialized the
switches integrate technol- geometry, arcing contact breakers and fuses, and their first three cycle any break-
design and the bulk of the varying fault-clearing times. er withstand and close-on
ogy that employs those
current rating capability.
magnetic forces on larger current-carrying parts all af- In fact, ASCO trans-
switches. The forces close fect the ability of the power fer switches provide the
contacts more tightly, transfer switch to withstand industrys most extensive
rather than letting them and close-on the damaging solution to all withstand and
blow off, or open, as a effects of high fault cur- close-on conditions. Ratings
circuit breaker would do. rents. address all applicationsany
The power transfer ASCO employs a variety breaker ratings, specific
switches use extremely of computer software mod- breaker, current-limiting
powerful solenoids and eling programs to deter- fuses and short time ratings.
mechanical advantages to mine the optimal combina-
firmly close on a fault and tion of all these factors and
lock the contacts closed. create a superior transfer
switch design.
ASCO power transfer
switches include a full range
of withstand and close-on
ratings to accommodate 6
ASCOs overlapping switched neutral

Overlapping
Switched Neutral Contact Poles
Provide s olutions Overlapping is the Increasing neutral con- Neutral switching con-
operative word. ductor impedance and tacts are not created equal.
associated with ASCOs overlapping related voltage and Those that do not overlap
switched neutral design is heating issues caused by the main pole contact op-
grounding of all about timing. It makes switching neutral currents eration cannot prevent neu-
separately before it breaks in advance with conventional power tral conductor interruption,
of the breaking of the main switching poles. even if they are adjusted to
derived systems. and even arcing contacts. Arcing and consequent make before they break.
Its a superior solution for a deterioration of the con- ASCO overlapping
number of problems: tact surface on the neutral neutral poles are designed
Incomplete sensing of pole. to overlap. They are not a
total fault current due to modification of a conven-
As with conventional tional pole design.
multiple paths. four pole power switch-
Load voltage imbalances ing, the ASCO overlapping
during transfer that can switched neutral has the ASCO introduced the
damage sensitive elec- same full-load current, with- first true overlapping
tronic equipment. stand ratings as the phase switched neutral.
contacts. But the similarities
end there.

7
Bypass-Isolation
Operational Sequence
1 2

Managing Single
Bypass to the Utilit y Feeds
And Emergency Power
Normal Source

Automatic
When the bypass switch handle is moved to the
bypass-to-normal position (BP-NORM), the transfer
switch contacts are shunted by the right-hand BP
Designing Qualit y, Dependable
With a Service Entrance Rated Transfer Switch.
Transfer Operation
With the bypass switch handle in the AUTO (au-
tomatic) position and the isolation switch handle in
contacts.
The flow of current then divides between the
bypass and transfer contacts. This enables the trans- The ASCO 7000 Series Service Entrance Rated
Components Intelligently
the CLOSED position, the unit will provide its intended fer switch to be removed without even a momentary Transfer Switch combines automatic power
automatic transfer operation. Both bypass contacts interruption of power to the load. Note the isolation Simplifies installation, maintenance and testing.
are open. The isolation switch contacts are closed. contacts are still in the closed position. switching with a disconnect and an overcurrent
protective device on the utility source. Designing transfer Most special lug ar- Increasing use of

3 4
switches from the ground rangements that typically molded parts continues
The power transfer breaker serves as the service up has enabled ASCO to may require a larger en- to help produce a more
switch meets all Na- disconnect and links are engineer them for ease of closure for other transfer robust transfer switch. Their
tional Electrical Code provided to disconnect installation, maintenance switches usually can be closer tolerances, increased
requirements for installation both neutral and ground and testing. housed in the standard strength and improved
at a facilitys main utility connections. All key components, for ASCO enclosure. dimensional control com-
service entrance. This product is UL 891 example, can be inspected Front-replaceable main bine to enhance quality
ASCO 7000 Series Service entrance rated listed. The transfer switch or replaced from the front of contact assemblies repre- and reliability, and simplify
Service Entrance Rated transfer switches generally is UL 1008 listed and is the enclosure. sent another industry-set- maintenance.
Transfer Switch
are installed at facilities that available up to 600V and Crimp lugs, which are ting benchmark. Transfer Cutouts in a molded
have a single utility feed 4000A in standard, delayed, frequently specified for data switches rated 800 amps pole cover, for example,
and a single emergency closed transition, soft centers where heat build and above facilitate main- allow access to lug screws,
power source. A circuit load, and bypass-isolation up may be an issue, have a tenance of the main and eliminating the need to re-
ASCO debuted the first true configurations. long barrel and two holes to arcing contacts, without move the pole covers during
Test Position Complete Isolation service entrance transfer prevent lugs from turning. disassembling or removing cable installation.
When the isolation switch handle is moved to the Moving the isolation switch handle to the OPEN switch that integrates the They can be arranged in a the transfer switch from the
TEST position, the isolation switch drawout contacts position opens all isolation contacts, isolating the ATS switch and service variety of configurations, enclosure.
associated with the load terminal are opened. from the rest of the system. disconnect. depending on point of In addition, a block of
The total load current now is carried by the bypass No voltage is present at normal or emergency access and cabling require- eight sets of auxiliary con-
contacts. The normal and emergency input termi- inputs, load output, the control system, or any other ments. tacts, to indicate transfer
nals of the ATS are still connected to the normal and point on the transfer switch. The bypass switch now switch position, now are
emergency sources through the remaining still-closed carries the entire load. The ATS can be safely inspect- standard on most ASCO
isolation stabs. ed, serviced and even removed from the cabinet. 1 7000 transfer switches.
This permits the ATS to be electrically tested and The bypass switch provides bypass and can be oper- One line diagram of a
operated without interrupting power to the load. Note ated as a manual backup transfer switch. Once the typical service entrance
that since the isolation contacts never break load cur- engine starts, move the bypass switch handle from the rated transfer switch. 2

rent, they are not subject to arc erosion or burning. bypass to normal position to the bypass to emergency Its available with solid,
position. switched or overlapping
When maintenance is completed, the switch can be neutral poles.
returned first to the test position and then racked back
into its normal connected position.
Importantly, these steps do not interrupt power to 1
GFCT - Ground Fault Current
the loads, which are typically critical and sensitive to Transformer
2
ATS - Automatic Transfer Switch
disruptions. A CTTS with this bypass-isolation capabil-
ity provides ultimate protection.
18 21 8
Isolate Easily
Transferring Motor Loads Key Components
Simple bypass procedure is the new standard.
With minimal disruption Of Bypass-Isolation
A critical design innova- The isolation procedure
to chiller drives and other loads. Transfer Switch tion is a new bypass drawout can be completed without
mechanism. It sets the stan- opening enclosure doors.
Effective transfer Two transfer solu- transfers the motor when Closed transition dard for ease of operation Easy-to-understand instruc-
solutions are needed to tionsin-phase transfer the two are approaching transfer is the only way for no load break bypass and tions printed on the enclo-
avert large inrush current and closed transition zero phase angle. No more to mitigate transformer transfer switch isolation. sure door explain each step.
and associated torque transfer both require than normal inrush cur- magnetizing inrush cur- The drawout mecha- A protective safety
Upper and lower doors open
damage created when a fast and consistent trans- rent ever occurs. rent on transfer. It is a nism produces high hori- barrier between the power
and close independently
motor, which becomes a fer times. ASCOs uniquely For the most demand- passive transfer method zontal pull force with low transfer and bypass switches
generator at the moment designed solenoid opera- ing business-critical appli- that allows transfer only Monitor Transfer/Bypass Status Panel
(see page 20) handle torque. Its based on is standard.
of transfer, connects with tor delivers the required cations, closed transition when the two sources are ASCOs reliable and field- Mechanical indicators
a live source that is out and repeatable transfer transfer is the ultimate synchronized and within Front-mounted lugs proven four-bar linkage linked to the movement of
of phase with the discon- speed time after time. solution. It momentarily specific voltage and fre- External, permanently attached claw design that connects the transfer switch show the
nected source. They transfer potentially parallels the two live syn- quency differentials. bypass handle, per UL 1008 and isolates quickly. Perma- switchs true position, even
Two to three cycle hot problematic motor loads chronized sources during Soft load, closed tran- nently attached bypass and if both power sources are
to hot transfer times in reliably, and are the least hot-to-hot source trans- sition transfer also is avail- isolation handles prevent dead and LEDs that indicate
conjunction with in phase disruptive power transfer fers, using an overloading able when block loading of misplacement and help power position are dark.
Microprocessor controller Bypass and isolation controls
transfer are needed to solutions. transfer technique on all the generator is a factor to and operating instructions simplify the procedure for This is especially useful dur-
avert large inrush current In-phase transfer mon- switching poles which actively control the engine drawing out and reconnect- ing maintenance because
and associated torque itors the phases of both eliminates momentary generator and gradually ing the transfer switch. Lift- it eliminates the need for
damage created when the normal and emer- load interruptions. ramp the load from one ing handles facilitate easy operators to remove the
the motor is reconnected gency power sources. It source to another. The Quick-disconnect wiring switch removal. main contact pole covers to
at the completion of load result: no load interrup- see the contacts position.
transfer. tion, no inrush current, External, permanently attached
ASCOs single solenoid thus, no risk to sensitive isolation handle, per 45.4 of UL 1008
mechanism provides the equipment.
speed and consistency to
assure in phase transition.
Mechanical isolation status indicator Monitor Transfer/Bypass Status
Protective isolation barrier
ASCO introduced the first
in-phase monitor on transfer Status panel provides at-a-glance information,
Self-aligning power jaws
switches and the first closed-
transition transfer switch. control circuits disconnect automatically during isolation.
Another operator- Transfer switch in isolated
friendly innovation is the position
Easy-on, easy-off molded cover
Transfer/Bypass Status Transfer switch not in
Panel. Its a one-line diagram automatic
of the transfer switch that Normal source available
Mechanical transfer switch indicators uses LED indicators to show Emergency source
operational conditions. available
Tabs for sliding out bypass rack The panel communi- Load connected
cates at-a-glance informa- The panel also includes
tion more quickly than an engine control switch and
multiple pilot lights and is lamp test button. Opera-
an industry first. Indicated tors can manually start the
conditions are: generator if normal source
Bypass to normal power fails while the transfer
Bypass to emergency switch is in the isolate posi-
Load connected to normal tion.
Load connected to The bypass switch
emergency then can be used to manu-
Transfer switch in con- ally transfer the load to the
nected position generator, even though the
ASCO Transfer/Bypass
Transfer switch in test transfer switch is discon- Status Panel
o position nected.
Synchroscope representation
9 19 20
Easing Loads Transferring Power
Onto the Without Interruption
Power System Selecting
With the ASCO Closed Transition
Transfer Switch. It offers a reliable
Is simple with the ASCO 7000 Series solution to the problem of power
Soft Load Power Transfer Switch. Automatic Transfer Switches interruption on hot-to -hot transfer.

It enables large, mono- The difference is a soft Based on your need to: A closed transition constant from no load to full
lithic loads that are too big load transfer switch takes transfer switch (CTTS) load.
for the engine-generator to active control of the engine Transfer crucial loads safely, operates in a make-before- Closed transition trans-
handle as a single block to governor and voltage break mode, providing both fer not only makes testing
come on line gradually. The regulator on the generator reliably and seamlessly sources are acceptable and under load less objection-
standard closed transition and doesnt just wait for in synchronism. able, it provides many other
transfer switch applies its synchronization to occur.
Ease loads from one power source If the connected source benefits. Because there is no
load in a block when trans- Because the sources are to another is unacceptable, power load interruption, there is no
ferring to the generator set. paralleled for an extended transfer will occur in con- inrush current when trans-
So does the traditional period of time the ASCO Have complete power transfer ventional non-overlap ferring large motors.
open transition transfer Soft Load Power Transfer mode, or open transition The inrush problem
switch. The effect of the Switch contains all the monitoring and control transfer. associated with transfer-
block loading is even greater necessary protective func- For CTTS, most utilities ring transformers also is
with the open transition tions for extended parallel
ASCO 7000 Series Get ultimate power protection accept 100 milliseconds eliminated with CTTS. In ad-
Bypass-Isolation Transfer Switch
switch, since motors and operation. Manage single utility feeds (msec) as the maximum dition, if a critical computer
transformers have to be ASCO offers two ver- overlap time during transfer. load is served by a static
reenergized. sions of the soft load switch. and emergency power Typically, it doesnt exceed uninterruptible power sup-

Getting Ultimate
But, when the size of 50 to 80 msec. ply (UPS) system, the UPS ASCO 7000 Series
One uses a UL 1008 listed
the load is approximately closed transition transfer
ASCO 7000 Series Ensure continuous power by using Prior to transfer in ei- batteries never cycle when
Closed Transition Transfer Switch
Soft Load Power
80 percent or more of the switch, the other uses ther direction, both sources a synchronized transfer
alternate power sources
Power Protec tion
Transfer Switch
generator capacity, and the circuit breakers for systems are monitored by the CTTS, occurs. Because a CTTS mo-
individual loads cannot be where a service entrance and, if the voltage differ- By eliminating even mentarily parallels the
divided and connected to rating or overcurrent pro- ence is less than five percent a momentarydischarge onsite generator with the
smaller, sequenced transfer
What do you need in business critical power
tection is necessary. Ensures 7/24 availability of your business-critical transfer and load management? Emergency
and the frequency variation of the battery bank, the life utility during retransfer to
switches, a soft load power ASCO also offers a Soft less than 0.2 Hz, the relative of the battery is extended. normal power, or during
transfer switch can be used. Load Interconnect System onsite power system and the safety of maintenance Power? Peak Shaving? Prime Power? Load Priori- phase angle is monitored. Batteries are known to be a transfer and retransfer dur-
The soft load switch is (SLIS), which gradually tization? ASCO 7000 Series Automatic Transfer When the phase angle major maintenance expense ing generator testing and
similar to a closed transition ramps a specific amount of personnel and equipment. Switches can satisfy your business-critical require- difference approaches with- in a UPS system. load shedding operations,
switch in that it parallels the power from the connected ments...whatever they are. 14 in five electrical degrees, Another growing ap- utility approval is required
sources during transfer, but bus. This can be used during What do you do when added feature on automatic handle to isolate the trans- ASCO has installed more than 500,000 automatic transfer the switch operates, a mo- plication of a CTTS is in for each intended installa-
the soft load switch uses an peak demand periods. you need to service an auto- transfer bypass-isolation fer switch. The following key Select standard design, business-critical or highly switches worldwide. No other manufacturer comes close. mentary overlap occurs, Demand Side Management tion. ASCO personnel are
matic transfer switch that is products. A benchmark feature elements of the transfer
extended parallel time to custom engineered power transfer solutions. and the load transfers with (DSM) programs. Many elec- available to assist the cus-
allow a generating loading always hot and is connected Also called a main- of this transfer switch is au- switch and its operation virtually zero interruption. tric utilities offer incentives tomer during this approval
control to ramp the load to both power sources? tenance bypass switch, a tomatic secondary discon- are described on pages The presence of critical if a user reduces coincident process.
18-20:
Review the capabilities of the transfer switches on
from the utility source to the When it is necessary to bypass-isolation switch en- nects for control circuits. loads generally dictates the peak demand when request-
test, maintain and inspect ables the transfer switch to The male and female ends Bypass sequence the following pages, then discuss with us which
generator. of them best meets your onsite power system use of an isochronous gov- ed by the utility. Advance
an automatic transfer switch be completely isolated from separate as the transfer Isolation procedure ernor, because the engine notification is given to the
without interrupting power, the power system and safely switch drawout mechanism Status panel requirements.
generator output frequency DSM customer when peak
ASCO developed the first ASCO offers an integrally serviced. operates. should remain virtually shaving or peak demand
closed transition soft load A synchroscope representation on this Control Cen- mounted, two-way by- In addition, the transfer This feature further The power is in your hands.
ter screen shows the relative phase angle between reduction is needed.
power transfer switch quali- pass-isolation switch as an switch can be electrically simplifies transfer switch re-
normal and onsite power. Among other informa- ASCO commercialized the
fied and listed to UL 1008. tested without interrupting moval and installation, and
tion shown is phase-to-phase voltage, frequency, first automatic bypass-
kW, kVA and kVAR for each power source. connected loads by using enhances operator safety. isolation transfer switch ASCO pioneered the first
the bypass and isolation with a drawout design for closed transition transfer
serviceability. switch.
12 17 10 11
Easing Loads Transferring Power
Onto the Without Interruption
Power System Selecting
With the ASCO Closed Transition
Transfer Switch. It offers a reliable
Is simple with the ASCO 7000 Series solution to the problem of power
Soft Load Power Transfer Switch. Automatic Transfer Switches interruption on hot-to -hot transfer.

It enables large, mono- The difference is a soft Based on your need to: A closed transition constant from no load to full
lithic loads that are too big load transfer switch takes transfer switch (CTTS) load.
for the engine-generator to active control of the engine Transfer crucial loads safely, operates in a make-before- Closed transition trans-
handle as a single block to governor and voltage break mode, providing both fer not only makes testing
come on line gradually. The regulator on the generator reliably and seamlessly sources are acceptable and under load less objection-
standard closed transition and doesnt just wait for in synchronism. able, it provides many other
transfer switch applies its synchronization to occur.
Ease loads from one power source If the connected source benefits. Because there is no
load in a block when trans- Because the sources are to another is unacceptable, power load interruption, there is no
ferring to the generator set. paralleled for an extended transfer will occur in con- inrush current when trans-
So does the traditional period of time the ASCO Have complete power transfer ventional non-overlap ferring large motors.
open transition transfer Soft Load Power Transfer mode, or open transition The inrush problem
switch. The effect of the Switch contains all the monitoring and control transfer. associated with transfer-
block loading is even greater necessary protective func- For CTTS, most utilities ring transformers also is
with the open transition tions for extended parallel
ASCO 7000 Series Get ultimate power protection accept 100 milliseconds eliminated with CTTS. In ad-
Bypass-Isolation Transfer Switch
switch, since motors and operation. Manage single utility feeds (msec) as the maximum dition, if a critical computer
transformers have to be ASCO offers two ver- overlap time during transfer. load is served by a static
reenergized. sions of the soft load switch. and emergency power Typically, it doesnt exceed uninterruptible power sup-

Getting Ultimate
But, when the size of 50 to 80 msec. ply (UPS) system, the UPS ASCO 7000 Series
One uses a UL 1008 listed
the load is approximately closed transition transfer
ASCO 7000 Series Ensure continuous power by using Prior to transfer in ei- batteries never cycle when
Closed Transition Transfer Switch
Soft Load Power
80 percent or more of the switch, the other uses ther direction, both sources a synchronized transfer
alternate power sources
Power Protec tion
Transfer Switch
generator capacity, and the circuit breakers for systems are monitored by the CTTS, occurs. Because a CTTS mo-
individual loads cannot be where a service entrance and, if the voltage differ- By eliminating even mentarily parallels the
divided and connected to rating or overcurrent pro- ence is less than five percent a momentarydischarge onsite generator with the
smaller, sequenced transfer
What do you need in business critical power
tection is necessary. Ensures 7/24 availability of your business-critical transfer and load management? Emergency
and the frequency variation of the battery bank, the life utility during retransfer to
switches, a soft load power ASCO also offers a Soft less than 0.2 Hz, the relative of the battery is extended. normal power, or during
transfer switch can be used. Load Interconnect System onsite power system and the safety of maintenance Power? Peak Shaving? Prime Power? Load Priori- phase angle is monitored. Batteries are known to be a transfer and retransfer dur-
The soft load switch is (SLIS), which gradually tization? ASCO 7000 Series Automatic Transfer When the phase angle major maintenance expense ing generator testing and
similar to a closed transition ramps a specific amount of personnel and equipment. Switches can satisfy your business-critical require- difference approaches with- in a UPS system. load shedding operations,
switch in that it parallels the power from the connected ments...whatever they are. 14 in five electrical degrees, Another growing ap- utility approval is required
sources during transfer, but bus. This can be used during What do you do when added feature on automatic handle to isolate the trans- ASCO has installed more than 500,000 automatic transfer the switch operates, a mo- plication of a CTTS is in for each intended installa-
the soft load switch uses an peak demand periods. you need to service an auto- transfer bypass-isolation fer switch. The following key Select standard design, business-critical or highly switches worldwide. No other manufacturer comes close. mentary overlap occurs, Demand Side Management tion. ASCO personnel are
matic transfer switch that is products. A benchmark feature elements of the transfer
extended parallel time to custom engineered power transfer solutions. and the load transfers with (DSM) programs. Many elec- available to assist the cus-
allow a generating loading always hot and is connected Also called a main- of this transfer switch is au- switch and its operation virtually zero interruption. tric utilities offer incentives tomer during this approval
control to ramp the load to both power sources? tenance bypass switch, a tomatic secondary discon- are described on pages The presence of critical if a user reduces coincident process.
18-20:
Review the capabilities of the transfer switches on
from the utility source to the When it is necessary to bypass-isolation switch en- nects for control circuits. loads generally dictates the peak demand when request-
test, maintain and inspect ables the transfer switch to The male and female ends Bypass sequence the following pages, then discuss with us which
generator. of them best meets your onsite power system use of an isochronous gov- ed by the utility. Advance
an automatic transfer switch be completely isolated from separate as the transfer Isolation procedure ernor, because the engine notification is given to the
without interrupting power, the power system and safely switch drawout mechanism Status panel requirements.
generator output frequency DSM customer when peak
ASCO developed the first ASCO offers an integrally serviced. operates. should remain virtually shaving or peak demand
closed transition soft load A synchroscope representation on this Control Cen- mounted, two-way by- In addition, the transfer This feature further The power is in your hands.
ter screen shows the relative phase angle between reduction is needed.
power transfer switch quali- pass-isolation switch as an switch can be electrically simplifies transfer switch re-
normal and onsite power. Among other informa- ASCO commercialized the
fied and listed to UL 1008. tested without interrupting moval and installation, and
tion shown is phase-to-phase voltage, frequency, first automatic bypass-
kW, kVA and kVAR for each power source. connected loads by using enhances operator safety. isolation transfer switch ASCO pioneered the first
the bypass and isolation with a drawout design for closed transition transfer
serviceability. switch.
12 17 10 11
Easing Loads Transferring Power
Onto the Without Interruption
Power System Selecting
With the ASCO Closed Transition
Transfer Switch. It offers a reliable
Is simple with the ASCO 7000 Series solution to the problem of power
Soft Load Power Transfer Switch. Automatic Transfer Switches interruption on hot-to -hot transfer.

It enables large, mono- The difference is a soft Based on your need to: A closed transition constant from no load to full
lithic loads that are too big load transfer switch takes transfer switch (CTTS) load.
for the engine-generator to active control of the engine Transfer crucial loads safely, operates in a make-before- Closed transition trans-
handle as a single block to governor and voltage break mode, providing both fer not only makes testing
come on line gradually. The regulator on the generator reliably and seamlessly sources are acceptable and under load less objection-
standard closed transition and doesnt just wait for in synchronism. able, it provides many other
transfer switch applies its synchronization to occur.
Ease loads from one power source If the connected source benefits. Because there is no
load in a block when trans- Because the sources are to another is unacceptable, power load interruption, there is no
ferring to the generator set. paralleled for an extended transfer will occur in con- inrush current when trans-
So does the traditional period of time the ASCO Have complete power transfer ventional non-overlap ferring large motors.
open transition transfer Soft Load Power Transfer mode, or open transition The inrush problem
switch. The effect of the Switch contains all the monitoring and control transfer. associated with transfer-
block loading is even greater necessary protective func- For CTTS, most utilities ring transformers also is
with the open transition tions for extended parallel
ASCO 7000 Series Get ultimate power protection accept 100 milliseconds eliminated with CTTS. In ad-
Bypass-Isolation Transfer Switch
switch, since motors and operation. Manage single utility feeds (msec) as the maximum dition, if a critical computer
transformers have to be ASCO offers two ver- overlap time during transfer. load is served by a static
reenergized. sions of the soft load switch. and emergency power Typically, it doesnt exceed uninterruptible power sup-

Getting Ultimate
But, when the size of 50 to 80 msec. ply (UPS) system, the UPS ASCO 7000 Series
One uses a UL 1008 listed
the load is approximately closed transition transfer
ASCO 7000 Series Ensure continuous power by using Prior to transfer in ei- batteries never cycle when
Closed Transition Transfer Switch
Soft Load Power
80 percent or more of the switch, the other uses ther direction, both sources a synchronized transfer
alternate power sources
Power Protec tion
Transfer Switch
generator capacity, and the circuit breakers for systems are monitored by the CTTS, occurs. Because a CTTS mo-
individual loads cannot be where a service entrance and, if the voltage differ- By eliminating even mentarily parallels the
divided and connected to rating or overcurrent pro- ence is less than five percent a momentarydischarge onsite generator with the
smaller, sequenced transfer
What do you need in business critical power
tection is necessary. Ensures 7/24 availability of your business-critical transfer and load management? Emergency
and the frequency variation of the battery bank, the life utility during retransfer to
switches, a soft load power ASCO also offers a Soft less than 0.2 Hz, the relative of the battery is extended. normal power, or during
transfer switch can be used. Load Interconnect System onsite power system and the safety of maintenance Power? Peak Shaving? Prime Power? Load Priori- phase angle is monitored. Batteries are known to be a transfer and retransfer dur-
The soft load switch is (SLIS), which gradually tization? ASCO 7000 Series Automatic Transfer When the phase angle major maintenance expense ing generator testing and
similar to a closed transition ramps a specific amount of personnel and equipment. Switches can satisfy your business-critical require- difference approaches with- in a UPS system. load shedding operations,
switch in that it parallels the power from the connected ments...whatever they are. 14 in five electrical degrees, Another growing ap- utility approval is required
sources during transfer, but bus. This can be used during What do you do when added feature on automatic handle to isolate the trans- ASCO has installed more than 500,000 automatic transfer the switch operates, a mo- plication of a CTTS is in for each intended installa-
the soft load switch uses an peak demand periods. you need to service an auto- transfer bypass-isolation fer switch. The following key Select standard design, business-critical or highly switches worldwide. No other manufacturer comes close. mentary overlap occurs, Demand Side Management tion. ASCO personnel are
matic transfer switch that is products. A benchmark feature elements of the transfer
extended parallel time to custom engineered power transfer solutions. and the load transfers with (DSM) programs. Many elec- available to assist the cus-
allow a generating loading always hot and is connected Also called a main- of this transfer switch is au- switch and its operation virtually zero interruption. tric utilities offer incentives tomer during this approval
control to ramp the load to both power sources? tenance bypass switch, a tomatic secondary discon- are described on pages The presence of critical if a user reduces coincident process.
18-20:
Review the capabilities of the transfer switches on
from the utility source to the When it is necessary to bypass-isolation switch en- nects for control circuits. loads generally dictates the peak demand when request-
test, maintain and inspect ables the transfer switch to The male and female ends Bypass sequence the following pages, then discuss with us which
generator. of them best meets your onsite power system use of an isochronous gov- ed by the utility. Advance
an automatic transfer switch be completely isolated from separate as the transfer Isolation procedure ernor, because the engine notification is given to the
without interrupting power, the power system and safely switch drawout mechanism Status panel requirements.
generator output frequency DSM customer when peak
ASCO developed the first ASCO offers an integrally serviced. operates. should remain virtually shaving or peak demand
closed transition soft load A synchroscope representation on this Control Cen- mounted, two-way by- In addition, the transfer This feature further The power is in your hands.
ter screen shows the relative phase angle between reduction is needed.
power transfer switch quali- pass-isolation switch as an switch can be electrically simplifies transfer switch re-
normal and onsite power. Among other informa- ASCO commercialized the
fied and listed to UL 1008. tested without interrupting moval and installation, and
tion shown is phase-to-phase voltage, frequency, first automatic bypass-
kW, kVA and kVAR for each power source. connected loads by using enhances operator safety. isolation transfer switch ASCO pioneered the first
the bypass and isolation with a drawout design for closed transition transfer
serviceability. switch.
12 17 10 11
Controlling Transfer Operations
Four elements position ASCO as the leader
in control technology: Normal Voltage
1. Microprocessor Controller Dropout...... 85% .408V
2. Control and Indicator Panel Pickup........ 90% .432V
3. Operational parameters O.V. Trip.....110% .528V
4. Power Manager C o n t r o l and Indicator Panels Power Manager

Operational Parameters
M i c r o p r o c e s s o r Controller
Multiple source sensing capabilities, a variety of operational
The ASCO 7000 Series Operational settings parameters and flexible time delay settings ensure personnel get the
Microprocessor Controller and features can be tailored
allows easy access to data by the customer to a specific
information they need and that the onsite power system operates properly.
and control of a range of application using six-button
functions. programming and multi-
Voltage and
Intuitive, simple naviga- language screen messages. Frequency Sensing
tion presents real time in- The microprocessor Three phase under and Under and over frequency Frequency Sensing Sensing on normal and
formation on power source, logic board is separated and over voltage settings on settings on normal and Accuracy is +/- 0.2%. emergency; 50 or 60Hz.
voltage, frequency, status, isolated from the power normal and emergency emergency. Selectable settings: single Phase sequence sensing
timing and diagnostics. board to improve immunity sources. True RMS Voltage Sensing or three phase voltage. for phase sensitive loads.
The controller automat- to electrical noise and to Standard User Control and Indicator Panel CTTS User Control and Indicator Panel with +/- 1% accuracy; Voltage unbalance
ically starts the engine and help assure compliance with detection between
controls load transfer in the rigorous transient suppres- phases.
event the utility source fails sion standards noted below.
The ASCO 7000 Series Standard and CTTS User Control The microprocessor-based ASCO Power Manager provides real time
or becomes unacceptable. and Indicator Panels complement the microprocessor controller. Status and measurements of single and three phase power systems.
They provide at-a-glance operational status and push button control. Control Parameters
7000 Series Output contact (N/O or N/ The Power Manager The Power Manager
ly measures the frequency Output signals for remote Number of ATS trans-
Microprocessor Controller The Standard Con- quency, voltage unbalance The CTTS Control and A red push button C) for engine-start signals. uses digital signal process- includes one discrete input ASCO debuted the first power
difference between the indication of normal and fers caused by power
trol and Indicator Panel and phase sequence. Indicator Panel includes Transfer Switch Locked Selection between com- ing technology to measure for transfer switch posi- manager with embedded
two sources and initiates emergency source source failure.
comprises four industrial The three positions of the indicators and selec- Outprevents transfer in mit/no-commit on trans- voltage and current per tion, eight general-purpose I/O and kW command and
transfer at appropriate acceptability. Total number of days control.
grade LED indicators and the selector switch are: tor switch of the standard either direction, if extended fer to emergency after phase, real, reactive and ap- discrete inputs, and four
phase angle to minimize Statistical ATS/System ATS has operated.
a three-position selector Automatic, which main- panel, plus two additional parallel time is exceeded. engine start and normal parent power, and bidirec- relay outputs for control-
disturbances when trans- monitoring data screens Total number of hours
switch for conventional two- tains the normal position. red LEDs and three push- An Alarm Reset push restores before transfer. tional energy. ling or monitoring external
ferring motor loads. which provide: normal and emergency
position transfer switches. Test, a momentary posi- buttons that give the panel button resets extended par- Advanced inphase algo- All measurements can devices.
ASCO introduced the first Event log displays 99 Total number of ATS sources have been
Two green LEDs show tion simulating normal expanded functionality. allel and failure to synchro- rithm, which automatical- be viewed locally with a
microprocessor automatic logged events with the transfers. available.
when the transfer switch is source failure for testing One LED indicates when nize alarms. backlit liquid crystal display
7000 Series power transfer switch con- time and date of the
troller. connected to normal source the system functionality. the pre-set Parallel Time has A Closed Transition and/or displayed remotely Power Metering Reactive Power: KVARA,
Microprocessor Power event, event type and rea-
power and whether normal Reset Delay Bypass, also a been exceeded. In this case, Bypass push button allows with ASCO PowerQuest or Voltage: KVARB, KVARC, KVARNET
And Logic PC Boards son.
source is acceptable. momentary position that controls automatically open transfer between sources in SiteWeb products. Line-Line: VAB, VBC, VCA, Apparent Power: KVAA,
Two red LEDs indicate bypasses transfer and re- emergency or normal main an open transiton mode. The Power Manager VAVERAGE KVAB, KVAC, KVANET
when the transfer switch transfer time delays. contacts. Time Delays measures three phase cur- Line-Neutral: VAN, VBN, Real Energy: KWHIMPORT,
7000 Series Microprocessor Controller is connected to the emer- The other LED is a visual Engine start time delay Re-transfer to normal time with a programmable rents and a fourth current VCN, VAVERAGE KWHEXPORT, KWHNET
Contains all alarm signals,
Emission Standard - Group 1, Class A EN 55011:1991 gency source and whether alarm that indicates Failure Delays engine starting. delay with two settings: bypass on source failures. logic and time delays for input is available for measur- Frequency: 45.0 to 66.0 Reactive Energy:
Generic Immunity Standard, from which: EN 50082-2:1995 emergency source is to Synchronize if time delay Emergency source Power failure mode. Fully programmable use with closed transition ing current in the neutral Hertz KVARHIMPORT,
acceptable. settings are exceeded dur- stabilization time delay Test mode. engine exerciser with seven switches. conductor. Current: IA, IB, IC, IAVERAGE KVARHEXPORT, KVARHNET
Electrostatic Discharge (ESD) Immunity EN 61000-4-2:1995
Acceptability is deter- ing closed transition trans- to ignore momentary Unloaded running time independent routines Insynch time. Unbalance %: Voltage, Power Factor: PFA, PFB,
Radiated Electromagnetic Field Immunity ENV 50140:1993
mined by the control panels fer. transients during initial delay for engine cooldown. to exercise the engine- Failure to synchronize. Amps PFC, PFNET
Electrical Fast Transient (EFT) Immunity EN 61000-4-4:1995
settings for voltage, fre- generator set loading. Pre- and post-transfer generator, with or without Extended parallel. Real Power: KWA, KWB,
Surge Transient Immunity EN 61000-4-5:1995
Conducted Radio-Frequency Field Immunity EN 61000-4-6:1996 signal time delay for loads, every day, week, two Delayed transition load KWC, KWNET
Voltage Dips, Interruptions and Variations Immunity EN 61000-4-11:1994 selective load disconnect weeks or month. disconnect time delay.
13 14 15 16
Controlling Transfer Operations
Four elements position ASCO as the leader
in control technology: Normal Voltage
1. Microprocessor Controller Dropout...... 85% .408V
2. Control and Indicator Panel Pickup........ 90% .432V
3. Operational parameters O.V. Trip.....110% .528V
4. Power Manager C o n t r o l and Indicator Panels Power Manager

Operational Parameters
M i c r o p r o c e s s o r Controller
Multiple source sensing capabilities, a variety of operational
The ASCO 7000 Series Operational settings parameters and flexible time delay settings ensure personnel get the
Microprocessor Controller and features can be tailored
allows easy access to data by the customer to a specific
information they need and that the onsite power system operates properly.
and control of a range of application using six-button
functions. programming and multi-
Voltage and
Intuitive, simple naviga- language screen messages. Frequency Sensing
tion presents real time in- The microprocessor Three phase under and Under and over frequency Frequency Sensing Sensing on normal and
formation on power source, logic board is separated and over voltage settings on settings on normal and Accuracy is +/- 0.2%. emergency; 50 or 60Hz.
voltage, frequency, status, isolated from the power normal and emergency emergency. Selectable settings: single Phase sequence sensing
timing and diagnostics. board to improve immunity sources. True RMS Voltage Sensing or three phase voltage. for phase sensitive loads.
The controller automat- to electrical noise and to Standard User Control and Indicator Panel CTTS User Control and Indicator Panel with +/- 1% accuracy; Voltage unbalance
ically starts the engine and help assure compliance with detection between
controls load transfer in the rigorous transient suppres- phases.
event the utility source fails sion standards noted below.
The ASCO 7000 Series Standard and CTTS User Control The microprocessor-based ASCO Power Manager provides real time
or becomes unacceptable. and Indicator Panels complement the microprocessor controller. Status and measurements of single and three phase power systems.
They provide at-a-glance operational status and push button control. Control Parameters
7000 Series Output contact (N/O or N/ The Power Manager The Power Manager
ly measures the frequency Output signals for remote Number of ATS trans-
Microprocessor Controller The Standard Con- quency, voltage unbalance The CTTS Control and A red push button C) for engine-start signals. uses digital signal process- includes one discrete input ASCO debuted the first power
difference between the indication of normal and fers caused by power
trol and Indicator Panel and phase sequence. Indicator Panel includes Transfer Switch Locked Selection between com- ing technology to measure for transfer switch posi- manager with embedded
two sources and initiates emergency source source failure.
comprises four industrial The three positions of the indicators and selec- Outprevents transfer in mit/no-commit on trans- voltage and current per tion, eight general-purpose I/O and kW command and
transfer at appropriate acceptability. Total number of days control.
grade LED indicators and the selector switch are: tor switch of the standard either direction, if extended fer to emergency after phase, real, reactive and ap- discrete inputs, and four
phase angle to minimize Statistical ATS/System ATS has operated.
a three-position selector Automatic, which main- panel, plus two additional parallel time is exceeded. engine start and normal parent power, and bidirec- relay outputs for control-
disturbances when trans- monitoring data screens Total number of hours
switch for conventional two- tains the normal position. red LEDs and three push- An Alarm Reset push restores before transfer. tional energy. ling or monitoring external
ferring motor loads. which provide: normal and emergency
position transfer switches. Test, a momentary posi- buttons that give the panel button resets extended par- Advanced inphase algo- All measurements can devices.
ASCO introduced the first Event log displays 99 Total number of ATS sources have been
Two green LEDs show tion simulating normal expanded functionality. allel and failure to synchro- rithm, which automatical- be viewed locally with a
microprocessor automatic logged events with the transfers. available.
when the transfer switch is source failure for testing One LED indicates when nize alarms. backlit liquid crystal display
7000 Series power transfer switch con- time and date of the
troller. connected to normal source the system functionality. the pre-set Parallel Time has A Closed Transition and/or displayed remotely Power Metering Reactive Power: KVARA,
Microprocessor Power event, event type and rea-
power and whether normal Reset Delay Bypass, also a been exceeded. In this case, Bypass push button allows with ASCO PowerQuest or Voltage: KVARB, KVARC, KVARNET
And Logic PC Boards son.
source is acceptable. momentary position that controls automatically open transfer between sources in SiteWeb products. Line-Line: VAB, VBC, VCA, Apparent Power: KVAA,
Two red LEDs indicate bypasses transfer and re- emergency or normal main an open transiton mode. The Power Manager VAVERAGE KVAB, KVAC, KVANET
when the transfer switch transfer time delays. contacts. Time Delays measures three phase cur- Line-Neutral: VAN, VBN, Real Energy: KWHIMPORT,
7000 Series Microprocessor Controller is connected to the emer- The other LED is a visual Engine start time delay Re-transfer to normal time with a programmable rents and a fourth current VCN, VAVERAGE KWHEXPORT, KWHNET
Contains all alarm signals,
Emission Standard - Group 1, Class A EN 55011:1991 gency source and whether alarm that indicates Failure Delays engine starting. delay with two settings: bypass on source failures. logic and time delays for input is available for measur- Frequency: 45.0 to 66.0 Reactive Energy:
Generic Immunity Standard, from which: EN 50082-2:1995 emergency source is to Synchronize if time delay Emergency source Power failure mode. Fully programmable use with closed transition ing current in the neutral Hertz KVARHIMPORT,
acceptable. settings are exceeded dur- stabilization time delay Test mode. engine exerciser with seven switches. conductor. Current: IA, IB, IC, IAVERAGE KVARHEXPORT, KVARHNET
Electrostatic Discharge (ESD) Immunity EN 61000-4-2:1995
Acceptability is deter- ing closed transition trans- to ignore momentary Unloaded running time independent routines Insynch time. Unbalance %: Voltage, Power Factor: PFA, PFB,
Radiated Electromagnetic Field Immunity ENV 50140:1993
mined by the control panels fer. transients during initial delay for engine cooldown. to exercise the engine- Failure to synchronize. Amps PFC, PFNET
Electrical Fast Transient (EFT) Immunity EN 61000-4-4:1995
settings for voltage, fre- generator set loading. Pre- and post-transfer generator, with or without Extended parallel. Real Power: KWA, KWB,
Surge Transient Immunity EN 61000-4-5:1995
Conducted Radio-Frequency Field Immunity EN 61000-4-6:1996 signal time delay for loads, every day, week, two Delayed transition load KWC, KWNET
Voltage Dips, Interruptions and Variations Immunity EN 61000-4-11:1994 selective load disconnect weeks or month. disconnect time delay.
13 14 15 16
Controlling Transfer Operations
Four elements position ASCO as the leader
in control technology: Normal Voltage
1. Microprocessor Controller Dropout...... 85% .408V
2. Control and Indicator Panel Pickup........ 90% .432V
3. Operational parameters O.V. Trip.....110% .528V
4. Power Manager C o n t r o l and Indicator Panels Power Manager

Operational Parameters
M i c r o p r o c e s s o r Controller
Multiple source sensing capabilities, a variety of operational
The ASCO 7000 Series Operational settings parameters and flexible time delay settings ensure personnel get the
Microprocessor Controller and features can be tailored
allows easy access to data by the customer to a specific
information they need and that the onsite power system operates properly.
and control of a range of application using six-button
functions. programming and multi-
Voltage and
Intuitive, simple naviga- language screen messages. Frequency Sensing
tion presents real time in- The microprocessor Three phase under and Under and over frequency Frequency Sensing Sensing on normal and
formation on power source, logic board is separated and over voltage settings on settings on normal and Accuracy is +/- 0.2%. emergency; 50 or 60Hz.
voltage, frequency, status, isolated from the power normal and emergency emergency. Selectable settings: single Phase sequence sensing
timing and diagnostics. board to improve immunity sources. True RMS Voltage Sensing or three phase voltage. for phase sensitive loads.
The controller automat- to electrical noise and to Standard User Control and Indicator Panel CTTS User Control and Indicator Panel with +/- 1% accuracy; Voltage unbalance
ically starts the engine and help assure compliance with detection between
controls load transfer in the rigorous transient suppres- phases.
event the utility source fails sion standards noted below.
The ASCO 7000 Series Standard and CTTS User Control The microprocessor-based ASCO Power Manager provides real time
or becomes unacceptable. and Indicator Panels complement the microprocessor controller. Status and measurements of single and three phase power systems.
They provide at-a-glance operational status and push button control. Control Parameters
7000 Series Output contact (N/O or N/ The Power Manager The Power Manager
ly measures the frequency Output signals for remote Number of ATS trans-
Microprocessor Controller The Standard Con- quency, voltage unbalance The CTTS Control and A red push button C) for engine-start signals. uses digital signal process- includes one discrete input ASCO debuted the first power
difference between the indication of normal and fers caused by power
trol and Indicator Panel and phase sequence. Indicator Panel includes Transfer Switch Locked Selection between com- ing technology to measure for transfer switch posi- manager with embedded
two sources and initiates emergency source source failure.
comprises four industrial The three positions of the indicators and selec- Outprevents transfer in mit/no-commit on trans- voltage and current per tion, eight general-purpose I/O and kW command and
transfer at appropriate acceptability. Total number of days control.
grade LED indicators and the selector switch are: tor switch of the standard either direction, if extended fer to emergency after phase, real, reactive and ap- discrete inputs, and four
phase angle to minimize Statistical ATS/System ATS has operated.
a three-position selector Automatic, which main- panel, plus two additional parallel time is exceeded. engine start and normal parent power, and bidirec- relay outputs for control-
disturbances when trans- monitoring data screens Total number of hours
switch for conventional two- tains the normal position. red LEDs and three push- An Alarm Reset push restores before transfer. tional energy. ling or monitoring external
ferring motor loads. which provide: normal and emergency
position transfer switches. Test, a momentary posi- buttons that give the panel button resets extended par- Advanced inphase algo- All measurements can devices.
ASCO introduced the first Event log displays 99 Total number of ATS sources have been
Two green LEDs show tion simulating normal expanded functionality. allel and failure to synchro- rithm, which automatical- be viewed locally with a
microprocessor automatic logged events with the transfers. available.
when the transfer switch is source failure for testing One LED indicates when nize alarms. backlit liquid crystal display
7000 Series power transfer switch con- time and date of the
troller. connected to normal source the system functionality. the pre-set Parallel Time has A Closed Transition and/or displayed remotely Power Metering Reactive Power: KVARA,
Microprocessor Power event, event type and rea-
power and whether normal Reset Delay Bypass, also a been exceeded. In this case, Bypass push button allows with ASCO PowerQuest or Voltage: KVARB, KVARC, KVARNET
And Logic PC Boards son.
source is acceptable. momentary position that controls automatically open transfer between sources in SiteWeb products. Line-Line: VAB, VBC, VCA, Apparent Power: KVAA,
Two red LEDs indicate bypasses transfer and re- emergency or normal main an open transiton mode. The Power Manager VAVERAGE KVAB, KVAC, KVANET
when the transfer switch transfer time delays. contacts. Time Delays measures three phase cur- Line-Neutral: VAN, VBN, Real Energy: KWHIMPORT,
7000 Series Microprocessor Controller is connected to the emer- The other LED is a visual Engine start time delay Re-transfer to normal time with a programmable rents and a fourth current VCN, VAVERAGE KWHEXPORT, KWHNET
Contains all alarm signals,
Emission Standard - Group 1, Class A EN 55011:1991 gency source and whether alarm that indicates Failure Delays engine starting. delay with two settings: bypass on source failures. logic and time delays for input is available for measur- Frequency: 45.0 to 66.0 Reactive Energy:
Generic Immunity Standard, from which: EN 50082-2:1995 emergency source is to Synchronize if time delay Emergency source Power failure mode. Fully programmable use with closed transition ing current in the neutral Hertz KVARHIMPORT,
acceptable. settings are exceeded dur- stabilization time delay Test mode. engine exerciser with seven switches. conductor. Current: IA, IB, IC, IAVERAGE KVARHEXPORT, KVARHNET
Electrostatic Discharge (ESD) Immunity EN 61000-4-2:1995
Acceptability is deter- ing closed transition trans- to ignore momentary Unloaded running time independent routines Insynch time. Unbalance %: Voltage, Power Factor: PFA, PFB,
Radiated Electromagnetic Field Immunity ENV 50140:1993
mined by the control panels fer. transients during initial delay for engine cooldown. to exercise the engine- Failure to synchronize. Amps PFC, PFNET
Electrical Fast Transient (EFT) Immunity EN 61000-4-4:1995
settings for voltage, fre- generator set loading. Pre- and post-transfer generator, with or without Extended parallel. Real Power: KWA, KWB,
Surge Transient Immunity EN 61000-4-5:1995
Conducted Radio-Frequency Field Immunity EN 61000-4-6:1996 signal time delay for loads, every day, week, two Delayed transition load KWC, KWNET
Voltage Dips, Interruptions and Variations Immunity EN 61000-4-11:1994 selective load disconnect weeks or month. disconnect time delay.
13 14 15 16
Controlling Transfer Operations
Four elements position ASCO as the leader
in control technology: Normal Voltage
1. Microprocessor Controller Dropout...... 85% .408V
2. Control and Indicator Panel Pickup........ 90% .432V
3. Operational parameters O.V. Trip.....110% .528V
4. Power Manager C o n t r o l and Indicator Panels Power Manager

Operational Parameters
M i c r o p r o c e s s o r Controller
Multiple source sensing capabilities, a variety of operational
The ASCO 7000 Series Operational settings parameters and flexible time delay settings ensure personnel get the
Microprocessor Controller and features can be tailored
allows easy access to data by the customer to a specific
information they need and that the onsite power system operates properly.
and control of a range of application using six-button
functions. programming and multi-
Voltage and
Intuitive, simple naviga- language screen messages. Frequency Sensing
tion presents real time in- The microprocessor Three phase under and Under and over frequency Frequency Sensing Sensing on normal and
formation on power source, logic board is separated and over voltage settings on settings on normal and Accuracy is +/- 0.2%. emergency; 50 or 60Hz.
voltage, frequency, status, isolated from the power normal and emergency emergency. Selectable settings: single Phase sequence sensing
timing and diagnostics. board to improve immunity sources. True RMS Voltage Sensing or three phase voltage. for phase sensitive loads.
The controller automat- to electrical noise and to Standard User Control and Indicator Panel CTTS User Control and Indicator Panel with +/- 1% accuracy; Voltage unbalance
ically starts the engine and help assure compliance with detection between
controls load transfer in the rigorous transient suppres- phases.
event the utility source fails sion standards noted below.
The ASCO 7000 Series Standard and CTTS User Control The microprocessor-based ASCO Power Manager provides real time
or becomes unacceptable. and Indicator Panels complement the microprocessor controller. Status and measurements of single and three phase power systems.
They provide at-a-glance operational status and push button control. Control Parameters
7000 Series Output contact (N/O or N/ The Power Manager The Power Manager
ly measures the frequency Output signals for remote Number of ATS trans-
Microprocessor Controller The Standard Con- quency, voltage unbalance The CTTS Control and A red push button C) for engine-start signals. uses digital signal process- includes one discrete input ASCO debuted the first power
difference between the indication of normal and fers caused by power
trol and Indicator Panel and phase sequence. Indicator Panel includes Transfer Switch Locked Selection between com- ing technology to measure for transfer switch posi- manager with embedded
two sources and initiates emergency source source failure.
comprises four industrial The three positions of the indicators and selec- Outprevents transfer in mit/no-commit on trans- voltage and current per tion, eight general-purpose I/O and kW command and
transfer at appropriate acceptability. Total number of days control.
grade LED indicators and the selector switch are: tor switch of the standard either direction, if extended fer to emergency after phase, real, reactive and ap- discrete inputs, and four
phase angle to minimize Statistical ATS/System ATS has operated.
a three-position selector Automatic, which main- panel, plus two additional parallel time is exceeded. engine start and normal parent power, and bidirec- relay outputs for control-
disturbances when trans- monitoring data screens Total number of hours
switch for conventional two- tains the normal position. red LEDs and three push- An Alarm Reset push restores before transfer. tional energy. ling or monitoring external
ferring motor loads. which provide: normal and emergency
position transfer switches. Test, a momentary posi- buttons that give the panel button resets extended par- Advanced inphase algo- All measurements can devices.
ASCO introduced the first Event log displays 99 Total number of ATS sources have been
Two green LEDs show tion simulating normal expanded functionality. allel and failure to synchro- rithm, which automatical- be viewed locally with a
microprocessor automatic logged events with the transfers. available.
when the transfer switch is source failure for testing One LED indicates when nize alarms. backlit liquid crystal display
7000 Series power transfer switch con- time and date of the
troller. connected to normal source the system functionality. the pre-set Parallel Time has A Closed Transition and/or displayed remotely Power Metering Reactive Power: KVARA,
Microprocessor Power event, event type and rea-
power and whether normal Reset Delay Bypass, also a been exceeded. In this case, Bypass push button allows with ASCO PowerQuest or Voltage: KVARB, KVARC, KVARNET
And Logic PC Boards son.
source is acceptable. momentary position that controls automatically open transfer between sources in SiteWeb products. Line-Line: VAB, VBC, VCA, Apparent Power: KVAA,
Two red LEDs indicate bypasses transfer and re- emergency or normal main an open transiton mode. The Power Manager VAVERAGE KVAB, KVAC, KVANET
when the transfer switch transfer time delays. contacts. Time Delays measures three phase cur- Line-Neutral: VAN, VBN, Real Energy: KWHIMPORT,
7000 Series Microprocessor Controller is connected to the emer- The other LED is a visual Engine start time delay Re-transfer to normal time with a programmable rents and a fourth current VCN, VAVERAGE KWHEXPORT, KWHNET
Contains all alarm signals,
Emission Standard - Group 1, Class A EN 55011:1991 gency source and whether alarm that indicates Failure Delays engine starting. delay with two settings: bypass on source failures. logic and time delays for input is available for measur- Frequency: 45.0 to 66.0 Reactive Energy:
Generic Immunity Standard, from which: EN 50082-2:1995 emergency source is to Synchronize if time delay Emergency source Power failure mode. Fully programmable use with closed transition ing current in the neutral Hertz KVARHIMPORT,
acceptable. settings are exceeded dur- stabilization time delay Test mode. engine exerciser with seven switches. conductor. Current: IA, IB, IC, IAVERAGE KVARHEXPORT, KVARHNET
Electrostatic Discharge (ESD) Immunity EN 61000-4-2:1995
Acceptability is deter- ing closed transition trans- to ignore momentary Unloaded running time independent routines Insynch time. Unbalance %: Voltage, Power Factor: PFA, PFB,
Radiated Electromagnetic Field Immunity ENV 50140:1993
mined by the control panels fer. transients during initial delay for engine cooldown. to exercise the engine- Failure to synchronize. Amps PFC, PFNET
Electrical Fast Transient (EFT) Immunity EN 61000-4-4:1995
settings for voltage, fre- generator set loading. Pre- and post-transfer generator, with or without Extended parallel. Real Power: KWA, KWB,
Surge Transient Immunity EN 61000-4-5:1995
Conducted Radio-Frequency Field Immunity EN 61000-4-6:1996 signal time delay for loads, every day, week, two Delayed transition load KWC, KWNET
Voltage Dips, Interruptions and Variations Immunity EN 61000-4-11:1994 selective load disconnect weeks or month. disconnect time delay.
13 14 15 16
Easing Loads Transferring Power
Onto the Without Interruption
Power System Selecting
With the ASCO Closed Transition
Transfer Switch. It offers a reliable
Is simple with the ASCO 7000 Series solution to the problem of power
Soft Load Power Transfer Switch. Automatic Transfer Switches interruption on hot-to -hot transfer.

It enables large, mono- The difference is a soft Based on your need to: A closed transition constant from no load to full
lithic loads that are too big load transfer switch takes transfer switch (CTTS) load.
for the engine-generator to active control of the engine Transfer crucial loads safely, operates in a make-before- Closed transition trans-
handle as a single block to governor and voltage break mode, providing both fer not only makes testing
come on line gradually. The regulator on the generator reliably and seamlessly sources are acceptable and under load less objection-
standard closed transition and doesnt just wait for in synchronism. able, it provides many other
transfer switch applies its synchronization to occur.
Ease loads from one power source If the connected source benefits. Because there is no
load in a block when trans- Because the sources are to another is unacceptable, power load interruption, there is no
ferring to the generator set. paralleled for an extended transfer will occur in con- inrush current when trans-
So does the traditional period of time the ASCO Have complete power transfer ventional non-overlap ferring large motors.
open transition transfer Soft Load Power Transfer mode, or open transition The inrush problem
switch. The effect of the Switch contains all the monitoring and control transfer. associated with transfer-
block loading is even greater necessary protective func- For CTTS, most utilities ring transformers also is
with the open transition tions for extended parallel
ASCO 7000 Series Get ultimate power protection accept 100 milliseconds eliminated with CTTS. In ad-
Bypass-Isolation Transfer Switch
switch, since motors and operation. Manage single utility feeds (msec) as the maximum dition, if a critical computer
transformers have to be ASCO offers two ver- overlap time during transfer. load is served by a static
reenergized. sions of the soft load switch. and emergency power Typically, it doesnt exceed uninterruptible power sup-

Getting Ultimate
But, when the size of 50 to 80 msec. ply (UPS) system, the UPS ASCO 7000 Series
One uses a UL 1008 listed
the load is approximately closed transition transfer
ASCO 7000 Series Ensure continuous power by using Prior to transfer in ei- batteries never cycle when
Closed Transition Transfer Switch
Soft Load Power
80 percent or more of the switch, the other uses ther direction, both sources a synchronized transfer
alternate power sources
Power Protec tion
Transfer Switch
generator capacity, and the circuit breakers for systems are monitored by the CTTS, occurs. Because a CTTS mo-
individual loads cannot be where a service entrance and, if the voltage differ- By eliminating even mentarily parallels the
divided and connected to rating or overcurrent pro- ence is less than five percent a momentarydischarge onsite generator with the
smaller, sequenced transfer
What do you need in business critical power
tection is necessary. Ensures 7/24 availability of your business-critical transfer and load management? Emergency
and the frequency variation of the battery bank, the life utility during retransfer to
switches, a soft load power ASCO also offers a Soft less than 0.2 Hz, the relative of the battery is extended. normal power, or during
transfer switch can be used. Load Interconnect System onsite power system and the safety of maintenance Power? Peak Shaving? Prime Power? Load Priori- phase angle is monitored. Batteries are known to be a transfer and retransfer dur-
The soft load switch is (SLIS), which gradually tization? ASCO 7000 Series Automatic Transfer When the phase angle major maintenance expense ing generator testing and
similar to a closed transition ramps a specific amount of personnel and equipment. Switches can satisfy your business-critical require- difference approaches with- in a UPS system. load shedding operations,
switch in that it parallels the power from the connected ments...whatever they are. 14 in five electrical degrees, Another growing ap- utility approval is required
sources during transfer, but bus. This can be used during What do you do when added feature on automatic handle to isolate the trans- ASCO has installed more than 500,000 automatic transfer the switch operates, a mo- plication of a CTTS is in for each intended installa-
the soft load switch uses an peak demand periods. you need to service an auto- transfer bypass-isolation fer switch. The following key Select standard design, business-critical or highly switches worldwide. No other manufacturer comes close. mentary overlap occurs, Demand Side Management tion. ASCO personnel are
matic transfer switch that is products. A benchmark feature elements of the transfer
extended parallel time to custom engineered power transfer solutions. and the load transfers with (DSM) programs. Many elec- available to assist the cus-
allow a generating loading always hot and is connected Also called a main- of this transfer switch is au- switch and its operation virtually zero interruption. tric utilities offer incentives tomer during this approval
control to ramp the load to both power sources? tenance bypass switch, a tomatic secondary discon- are described on pages The presence of critical if a user reduces coincident process.
18-20:
Review the capabilities of the transfer switches on
from the utility source to the When it is necessary to bypass-isolation switch en- nects for control circuits. loads generally dictates the peak demand when request-
test, maintain and inspect ables the transfer switch to The male and female ends Bypass sequence the following pages, then discuss with us which
generator. of them best meets your onsite power system use of an isochronous gov- ed by the utility. Advance
an automatic transfer switch be completely isolated from separate as the transfer Isolation procedure ernor, because the engine notification is given to the
without interrupting power, the power system and safely switch drawout mechanism Status panel requirements.
generator output frequency DSM customer when peak
ASCO developed the first ASCO offers an integrally serviced. operates. should remain virtually shaving or peak demand
closed transition soft load A synchroscope representation on this Control Cen- mounted, two-way by- In addition, the transfer This feature further The power is in your hands.
ter screen shows the relative phase angle between reduction is needed.
power transfer switch quali- pass-isolation switch as an switch can be electrically simplifies transfer switch re-
normal and onsite power. Among other informa- ASCO commercialized the
fied and listed to UL 1008. tested without interrupting moval and installation, and
tion shown is phase-to-phase voltage, frequency, first automatic bypass-
kW, kVA and kVAR for each power source. connected loads by using enhances operator safety. isolation transfer switch ASCO pioneered the first
the bypass and isolation with a drawout design for closed transition transfer
serviceability. switch.
12 17 10 11
Bypass-Isolation
Operational Sequence
1 2

Managing Single
Bypass to the Utilit y Feeds
And Emergency Power
Normal Source

Automatic
When the bypass switch handle is moved to the
bypass-to-normal position (BP-NORM), the transfer
switch contacts are shunted by the right-hand BP
Designing Qualit y, Dependable
With a Service Entrance Rated Transfer Switch.
Transfer Operation
With the bypass switch handle in the AUTO (au-
tomatic) position and the isolation switch handle in
contacts.
The flow of current then divides between the
bypass and transfer contacts. This enables the trans- The ASCO 7000 Series Service Entrance Rated
Components Intelligently
the CLOSED position, the unit will provide its intended fer switch to be removed without even a momentary Transfer Switch combines automatic power
automatic transfer operation. Both bypass contacts interruption of power to the load. Note the isolation Simplifies installation, maintenance and testing.
are open. The isolation switch contacts are closed. contacts are still in the closed position. switching with a disconnect and an overcurrent
protective device on the utility source. Designing transfer Most special lug ar- Increasing use of

3 4
switches from the ground rangements that typically molded parts continues
The power transfer breaker serves as the service up has enabled ASCO to may require a larger en- to help produce a more
switch meets all Na- disconnect and links are engineer them for ease of closure for other transfer robust transfer switch. Their
tional Electrical Code provided to disconnect installation, maintenance switches usually can be closer tolerances, increased
requirements for installation both neutral and ground and testing. housed in the standard strength and improved
at a facilitys main utility connections. All key components, for ASCO enclosure. dimensional control com-
service entrance. This product is UL 891 example, can be inspected Front-replaceable main bine to enhance quality
ASCO 7000 Series Service entrance rated listed. The transfer switch or replaced from the front of contact assemblies repre- and reliability, and simplify
Service Entrance Rated transfer switches generally is UL 1008 listed and is the enclosure. sent another industry-set- maintenance.
Transfer Switch
are installed at facilities that available up to 600V and Crimp lugs, which are ting benchmark. Transfer Cutouts in a molded
have a single utility feed 4000A in standard, delayed, frequently specified for data switches rated 800 amps pole cover, for example,
and a single emergency closed transition, soft centers where heat build and above facilitate main- allow access to lug screws,
power source. A circuit load, and bypass-isolation up may be an issue, have a tenance of the main and eliminating the need to re-
ASCO debuted the first true configurations. long barrel and two holes to arcing contacts, without move the pole covers during
Test Position Complete Isolation service entrance transfer prevent lugs from turning. disassembling or removing cable installation.
When the isolation switch handle is moved to the Moving the isolation switch handle to the OPEN switch that integrates the They can be arranged in a the transfer switch from the
TEST position, the isolation switch drawout contacts position opens all isolation contacts, isolating the ATS switch and service variety of configurations, enclosure.
associated with the load terminal are opened. from the rest of the system. disconnect. depending on point of In addition, a block of
The total load current now is carried by the bypass No voltage is present at normal or emergency access and cabling require- eight sets of auxiliary con-
contacts. The normal and emergency input termi- inputs, load output, the control system, or any other ments. tacts, to indicate transfer
nals of the ATS are still connected to the normal and point on the transfer switch. The bypass switch now switch position, now are
emergency sources through the remaining still-closed carries the entire load. The ATS can be safely inspect- standard on most ASCO
isolation stabs. ed, serviced and even removed from the cabinet. 1 7000 transfer switches.
This permits the ATS to be electrically tested and The bypass switch provides bypass and can be oper- One line diagram of a
operated without interrupting power to the load. Note ated as a manual backup transfer switch. Once the typical service entrance
that since the isolation contacts never break load cur- engine starts, move the bypass switch handle from the rated transfer switch. 2

rent, they are not subject to arc erosion or burning. bypass to normal position to the bypass to emergency Its available with solid,
position. switched or overlapping
When maintenance is completed, the switch can be neutral poles.
returned first to the test position and then racked back
into its normal connected position.
Importantly, these steps do not interrupt power to 1
GFCT - Ground Fault Current
the loads, which are typically critical and sensitive to Transformer
2
ATS - Automatic Transfer Switch
disruptions. A CTTS with this bypass-isolation capabil-
ity provides ultimate protection.
18 21 8
Isolate Easily
Transferring Motor Loads Key Components
Simple bypass procedure is the new standard.
With minimal disruption Of Bypass-Isolation
A critical design innova- The isolation procedure
to chiller drives and other loads. Transfer Switch tion is a new bypass drawout can be completed without
mechanism. It sets the stan- opening enclosure doors.
Effective transfer Two transfer solu- transfers the motor when Closed transition dard for ease of operation Easy-to-understand instruc-
solutions are needed to tionsin-phase transfer the two are approaching transfer is the only way for no load break bypass and tions printed on the enclo-
avert large inrush current and closed transition zero phase angle. No more to mitigate transformer transfer switch isolation. sure door explain each step.
and associated torque transfer both require than normal inrush cur- magnetizing inrush cur- The drawout mecha- A protective safety
Upper and lower doors open
damage created when a fast and consistent trans- rent ever occurs. rent on transfer. It is a nism produces high hori- barrier between the power
and close independently
motor, which becomes a fer times. ASCOs uniquely For the most demand- passive transfer method zontal pull force with low transfer and bypass switches
generator at the moment designed solenoid opera- ing business-critical appli- that allows transfer only Monitor Transfer/Bypass Status Panel
(see page 20) handle torque. Its based on is standard.
of transfer, connects with tor delivers the required cations, closed transition when the two sources are ASCOs reliable and field- Mechanical indicators
a live source that is out and repeatable transfer transfer is the ultimate synchronized and within Front-mounted lugs proven four-bar linkage linked to the movement of
of phase with the discon- speed time after time. solution. It momentarily specific voltage and fre- External, permanently attached claw design that connects the transfer switch show the
nected source. They transfer potentially parallels the two live syn- quency differentials. bypass handle, per UL 1008 and isolates quickly. Perma- switchs true position, even
Two to three cycle hot problematic motor loads chronized sources during Soft load, closed tran- nently attached bypass and if both power sources are
to hot transfer times in reliably, and are the least hot-to-hot source trans- sition transfer also is avail- isolation handles prevent dead and LEDs that indicate
conjunction with in phase disruptive power transfer fers, using an overloading able when block loading of misplacement and help power position are dark.
Microprocessor controller Bypass and isolation controls
transfer are needed to solutions. transfer technique on all the generator is a factor to and operating instructions simplify the procedure for This is especially useful dur-
avert large inrush current In-phase transfer mon- switching poles which actively control the engine drawing out and reconnect- ing maintenance because
and associated torque itors the phases of both eliminates momentary generator and gradually ing the transfer switch. Lift- it eliminates the need for
damage created when the normal and emer- load interruptions. ramp the load from one ing handles facilitate easy operators to remove the
the motor is reconnected gency power sources. It source to another. The Quick-disconnect wiring switch removal. main contact pole covers to
at the completion of load result: no load interrup- see the contacts position.
transfer. tion, no inrush current, External, permanently attached
ASCOs single solenoid thus, no risk to sensitive isolation handle, per 45.4 of UL 1008
mechanism provides the equipment.
speed and consistency to
assure in phase transition.
Mechanical isolation status indicator Monitor Transfer/Bypass Status
Protective isolation barrier
ASCO introduced the first
in-phase monitor on transfer Status panel provides at-a-glance information,
Self-aligning power jaws
switches and the first closed-
transition transfer switch. control circuits disconnect automatically during isolation.
Another operator- Transfer switch in isolated
friendly innovation is the position
Easy-on, easy-off molded cover
Transfer/Bypass Status Transfer switch not in
Panel. Its a one-line diagram automatic
of the transfer switch that Normal source available
Mechanical transfer switch indicators uses LED indicators to show Emergency source
operational conditions. available
Tabs for sliding out bypass rack The panel communi- Load connected
cates at-a-glance informa- The panel also includes
tion more quickly than an engine control switch and
multiple pilot lights and is lamp test button. Opera-
an industry first. Indicated tors can manually start the
conditions are: generator if normal source
Bypass to normal power fails while the transfer
Bypass to emergency switch is in the isolate posi-
Load connected to normal tion.
Load connected to The bypass switch
emergency then can be used to manu-
Transfer switch in con- ally transfer the load to the
nected position generator, even though the
ASCO Transfer/Bypass
Transfer switch in test transfer switch is discon- Status Panel
o position nected.
Synchroscope representation
9 19 20
Isolate Easily
Transferring Motor Loads Key Components
Simple bypass procedure is the new standard.
With minimal disruption Of Bypass-Isolation
A critical design innova- The isolation procedure
to chiller drives and other loads. Transfer Switch tion is a new bypass drawout can be completed without
mechanism. It sets the stan- opening enclosure doors.
Effective transfer Two transfer solu- transfers the motor when Closed transition dard for ease of operation Easy-to-understand instruc-
solutions are needed to tionsin-phase transfer the two are approaching transfer is the only way for no load break bypass and tions printed on the enclo-
avert large inrush current and closed transition zero phase angle. No more to mitigate transformer transfer switch isolation. sure door explain each step.
and associated torque transfer both require than normal inrush cur- magnetizing inrush cur- The drawout mecha- A protective safety
Upper and lower doors open
damage created when a fast and consistent trans- rent ever occurs. rent on transfer. It is a nism produces high hori- barrier between the power
and close independently
motor, which becomes a fer times. ASCOs uniquely For the most demand- passive transfer method zontal pull force with low transfer and bypass switches
generator at the moment designed solenoid opera- ing business-critical appli- that allows transfer only Monitor Transfer/Bypass Status Panel
(see page 20) handle torque. Its based on is standard.
of transfer, connects with tor delivers the required cations, closed transition when the two sources are ASCOs reliable and field- Mechanical indicators
a live source that is out and repeatable transfer transfer is the ultimate synchronized and within Front-mounted lugs proven four-bar linkage linked to the movement of
of phase with the discon- speed time after time. solution. It momentarily specific voltage and fre- External, permanently attached claw design that connects the transfer switch show the
nected source. They transfer potentially parallels the two live syn- quency differentials. bypass handle, per UL 1008 and isolates quickly. Perma- switchs true position, even
Two to three cycle hot problematic motor loads chronized sources during Soft load, closed tran- nently attached bypass and if both power sources are
to hot transfer times in reliably, and are the least hot-to-hot source trans- sition transfer also is avail- isolation handles prevent dead and LEDs that indicate
conjunction with in phase disruptive power transfer fers, using an overloading able when block loading of misplacement and help power position are dark.
Microprocessor controller Bypass and isolation controls
transfer are needed to solutions. transfer technique on all the generator is a factor to and operating instructions simplify the procedure for This is especially useful dur-
avert large inrush current In-phase transfer mon- switching poles which actively control the engine drawing out and reconnect- ing maintenance because
and associated torque itors the phases of both eliminates momentary generator and gradually ing the transfer switch. Lift- it eliminates the need for
damage created when the normal and emer- load interruptions. ramp the load from one ing handles facilitate easy operators to remove the
the motor is reconnected gency power sources. It source to another. The Quick-disconnect wiring switch removal. main contact pole covers to
at the completion of load result: no load interrup- see the contacts position.
transfer. tion, no inrush current, External, permanently attached
ASCOs single solenoid thus, no risk to sensitive isolation handle, per 45.4 of UL 1008
mechanism provides the equipment.
speed and consistency to
assure in phase transition.
Mechanical isolation status indicator Monitor Transfer/Bypass Status
Protective isolation barrier
ASCO introduced the first
in-phase monitor on transfer Status panel provides at-a-glance information,
Self-aligning power jaws
switches and the first closed-
transition transfer switch. control circuits disconnect automatically during isolation.
Another operator- Transfer switch in isolated
friendly innovation is the position
Easy-on, easy-off molded cover
Transfer/Bypass Status Transfer switch not in
Panel. Its a one-line diagram automatic
of the transfer switch that Normal source available
Mechanical transfer switch indicators uses LED indicators to show Emergency source
operational conditions. available
Tabs for sliding out bypass rack The panel communi- Load connected
cates at-a-glance informa- The panel also includes
tion more quickly than an engine control switch and
multiple pilot lights and is lamp test button. Opera-
an industry first. Indicated tors can manually start the
conditions are: generator if normal source
Bypass to normal power fails while the transfer
Bypass to emergency switch is in the isolate posi-
Load connected to normal tion.
Load connected to The bypass switch
emergency then can be used to manu-
Transfer switch in con- ally transfer the load to the
nected position generator, even though the
ASCO Transfer/Bypass
Transfer switch in test transfer switch is discon- Status Panel
o position nected.
Synchroscope representation
9 19 20
Bypass-Isolation
Operational Sequence
1 2

Managing Single
Bypass to the Utilit y Feeds
And Emergency Power
Normal Source

Automatic
When the bypass switch handle is moved to the
bypass-to-normal position (BP-NORM), the transfer
switch contacts are shunted by the right-hand BP
Designing Qualit y, Dependable
With a Service Entrance Rated Transfer Switch.
Transfer Operation
With the bypass switch handle in the AUTO (au-
tomatic) position and the isolation switch handle in
contacts.
The flow of current then divides between the
bypass and transfer contacts. This enables the trans- The ASCO 7000 Series Service Entrance Rated
Components Intelligently
the CLOSED position, the unit will provide its intended fer switch to be removed without even a momentary Transfer Switch combines automatic power
automatic transfer operation. Both bypass contacts interruption of power to the load. Note the isolation Simplifies installation, maintenance and testing.
are open. The isolation switch contacts are closed. contacts are still in the closed position. switching with a disconnect and an overcurrent
protective device on the utility source. Designing transfer Most special lug ar- Increasing use of

3 4
switches from the ground rangements that typically molded parts continues
The power transfer breaker serves as the service up has enabled ASCO to may require a larger en- to help produce a more
switch meets all Na- disconnect and links are engineer them for ease of closure for other transfer robust transfer switch. Their
tional Electrical Code provided to disconnect installation, maintenance switches usually can be closer tolerances, increased
requirements for installation both neutral and ground and testing. housed in the standard strength and improved
at a facilitys main utility connections. All key components, for ASCO enclosure. dimensional control com-
service entrance. This product is UL 891 example, can be inspected Front-replaceable main bine to enhance quality
ASCO 7000 Series Service entrance rated listed. The transfer switch or replaced from the front of contact assemblies repre- and reliability, and simplify
Service Entrance Rated transfer switches generally is UL 1008 listed and is the enclosure. sent another industry-set- maintenance.
Transfer Switch
are installed at facilities that available up to 600V and Crimp lugs, which are ting benchmark. Transfer Cutouts in a molded
have a single utility feed 4000A in standard, delayed, frequently specified for data switches rated 800 amps pole cover, for example,
and a single emergency closed transition, soft centers where heat build and above facilitate main- allow access to lug screws,
power source. A circuit load, and bypass-isolation up may be an issue, have a tenance of the main and eliminating the need to re-
ASCO debuted the first true configurations. long barrel and two holes to arcing contacts, without move the pole covers during
Test Position Complete Isolation service entrance transfer prevent lugs from turning. disassembling or removing cable installation.
When the isolation switch handle is moved to the Moving the isolation switch handle to the OPEN switch that integrates the They can be arranged in a the transfer switch from the
TEST position, the isolation switch drawout contacts position opens all isolation contacts, isolating the ATS switch and service variety of configurations, enclosure.
associated with the load terminal are opened. from the rest of the system. disconnect. depending on point of In addition, a block of
The total load current now is carried by the bypass No voltage is present at normal or emergency access and cabling require- eight sets of auxiliary con-
contacts. The normal and emergency input termi- inputs, load output, the control system, or any other ments. tacts, to indicate transfer
nals of the ATS are still connected to the normal and point on the transfer switch. The bypass switch now switch position, now are
emergency sources through the remaining still-closed carries the entire load. The ATS can be safely inspect- standard on most ASCO
isolation stabs. ed, serviced and even removed from the cabinet. 1 7000 transfer switches.
This permits the ATS to be electrically tested and The bypass switch provides bypass and can be oper- One line diagram of a
operated without interrupting power to the load. Note ated as a manual backup transfer switch. Once the typical service entrance
that since the isolation contacts never break load cur- engine starts, move the bypass switch handle from the rated transfer switch. 2

rent, they are not subject to arc erosion or burning. bypass to normal position to the bypass to emergency Its available with solid,
position. switched or overlapping
When maintenance is completed, the switch can be neutral poles.
returned first to the test position and then racked back
into its normal connected position.
Importantly, these steps do not interrupt power to 1
GFCT - Ground Fault Current
the loads, which are typically critical and sensitive to Transformer
2
ATS - Automatic Transfer Switch
disruptions. A CTTS with this bypass-isolation capabil-
ity provides ultimate protection.
18 21 8
Ensuring Power with
Multiple Standby Power Sources
By using special controls for managing prime, emergency and standby power.
The ASCO 7000 Series Critical loads are auto- second will be automatically in its own enclosure, or as
matically transferred to the restarted and the load will a package with a standard
Three Source Transfer first alternate power source be transferred from the first transfer switch.
System provides all that achieves acceptable alternate power source to The package can in-
necessary controls voltage and frequency. The the second alternate power clude a separate enclosure
second alternate power source. When normal power for each transfer switch, or
to start both primary source then is shutdown is restored, the controls a single enclosure housing
and secondary power automatically after a time automatically retransfer the both transfer switches.
delay and cooldown period. load to the utility source
sources upon the loss If the first alternate The Three Source Trans-
of the utility source. power source fails, the fer System can be furnished

Utility
One line diagram of a typical
three source power design. ATS #1
The three source transfer
switch (ATS #2) automatically Facility
Loads
connects to the power source
that achieves acceptable volt- ATS #2
age and frequency first.

Gen #1 Gen #2

22
Employing Remote
Communications Capability
Can be efficient, economic and reliable.

PowerQuest Monitoring and Control

What s t he m ost Thats a frequently used to practically eliminate PowerQuest monitoring


eff icient, ec on o mic asked question. communications wiring. and control system and
The answer has many Interfacing with legacy ASCO Thin Web server offer
and reliable desi g n challenging facets. They systems is easier because it every capability described
for emer gency p o wer include remote monitor- minimizes costs for writing here, and more. They deliver
ing and control. Seamless software code. efficiency, economy and
co mmu nications ?
integration with building No investment in hard- reliability.
automation systems. Reli- ware, software, or addition- And they lead to one
able, easily understood and al staffing is needed. The inescapable conclusion. As
real time information. Auto- entire emergency power communications improve,
matic alerts that eliminate system can be monitored so does the performance of
monitor watching. and controlled remotely, emergency power systems.
The solution is Web- 24/7.
enabled communications The solution delivers
based on open protocols. these capabilities to a desk-
The benefits are many fold. top computer, pager, fax, or
Existing Ethernet or cell phone. The information
other infrastructures can be is straightforward, shrink-
ing the time required to
diagnose a situation.
When will these
capabilities be available?
They already are. The ASCO

ASCO developed the first


communications and data-
logging capability for trans-
fer switches.

23
Local Computer Remote Access Computer

Ethernet
RS 485

Ethernet Internet
Hub Pager
Firewall

ASCO 5500 Email Server


Thin Web Server
ATS Annunciator

Monitoring Ethernet
and Control
RS 422 Modbus

(72E)
Building
RS-485 Management
Computer
ASCO
4000 Series Ethernet Hub
Power Control
System
Monitoring and Control Monitoring
ASCO ASCO
5110 (72A) 5150 (72E)
Serial Connectivity
Modules Modules

To Additional To Additional
ASCO ATS Automatic Automatic ASCO ATS
Switches Transfer Transfer Switches
Switches Switches

SiteWeb Is THE Connectivity Solution


SiteWeb TM is a When combined with Internet communication enables monitoring of up to
the ASCO Communication system for monitoring and 64 power transfer switches
client-server Interface Modules (Acc 72A, controlling power transfer and eight engine-genera-
Acc 72E), the ASCO 5500 switches and engine-gen- tors. In addition, automatic
application that Series Thin Web Server and erators. paging is provided for all
the ASCO 5200 Series Power The SiteWeb communi- alarm signals.
requires no Manager, as shown above, cation system allows mul-
installation of SiteWeb provides the most tiple client access from local
comprehensive Intranet and or remote locations and ASCO introduced the first
software on the Ethernet/Web-enabled
connectivity for transfer
client computer. switches.

24
Relying on 24/7 Service
Helps avert the most common cause of transfer switch
failure: lack of regular maintenance.
Because power failures laptop computer. The com- contact erosion and a num-
can be life-threatening and puter tests multiple compo- ber of other causes. Maintenance Programs
costly, there is no room for nents quickly and accurately Besides maintaining
Two levels of mainte-
error when it comes to test- and can send maintenance equipment, ASCO Services
nance programs can be cus-
ing and maintaining power results to a printer for hard- can install and upgrade
tomized to meet the needs
transfer switches and paral- copy documentation. power transfer switches and
of one facility or many net-
leling control switchgear. Technicians are avail- power control systems.
worked facilities.
Skilled ASCO Ser- able 24/7 in most areas.
Level One includes
vices technicians properly Fully stocked vans sup-
annual scheduled mainte-
maintain and test transfer port the technicians during
nance during or after busi-
switches and power control onsite visits, often eliminat-
ness hours, a discount on
systems coast to coast. ing the need to order parts.
parts and a reduced hourly
Technicians check op- ASCO Services main- ASCO Services is the largest
rate for additional labor that
eration of engine-generator tains and upgrades a range organization of its kind in the
United States.
might be required.
paralleling systems and of transfer switches from a
Level Two includes Level
transfer switches with a variety of manufacturers.
One service, plus all parts,
Technicians resolve prob-
labor, expenses and emer-
lems created by corrosion,
gency service calls. Emer-
evidence of overheating,
gency service is dispatched
24/7/365.
25
Meeting Code Requirements
Demands con- Weekly inspection systemPowerQuestin- ings.
sheets for an emergency tegrates the operation of Personnel can select
siderable record- power system can include monitoring and controlling, from seven automatic test
55 or more data points and multiple engine-genera- schedules. Code references
keeping that too require writing comments tor paralleling systems and for NFPA 99 emergency
often can mean in long hand. Monthly test- automatic power transfer power systems testing are
ing logs can have nearly 40 switches. included in PowerQuest.
personnel spend or more data points. A third The 7000 Series Con- The transfer switch con-
form, a generator load re- troller automatically ex- troller stores up to 99 events
many hours op- port, builds the pile of nec- ercises engine-generator with time and date stamp-
essary paperwork. systems and logs data on ing. An optional printer in-
erating onsite Its no wonder that er- the exercise. terface produces hard-copy
power systems rors can and do occur. PowerQuest can con- documentation.
A solution to testing duct transfer tests remotely An ASCO Power Manag-
and recording emergency power systems that simulate a power fail- er module measures single
more efficiently is to auto- ure, start the gen-set, trans- and three phase power
data manually. mate the testing procedure fer the load to the alternate systems in real time. The
and data recording. Auto- power source and run the bottom line is an integrated
mating the process facili- generator under load for the emergency power system
tates compliance, substanti- period specified in the codes that better equips main-
ates insurance claims and and standards. tenance and engineering
defends against litigation PowerQuest then staffs to meet the require-
arising from potentially life- initiates retransfers back ments of NFPA 110, NFPA
threatening events. It also to normal power and runs 99 and, for healthcare orga-
helps manage the facilitys the generator through cool nizations, the JCAHO*.
energy consumption more down. The system moni-
effectively. tors the engine-generators * Joint Commission on Accreditation of
Healthcare Organizations
An automated Web- throughout the test and
based communications automatically records read- 26
Creating Innovation
Reliability is what Satisfies the needs of engineering decision makers
engineering departments
and facilities directors
responsible for on-site power systems. Its one reason
want most in automatic why ASCO Power Technologies is the number one
transfer switches.
manufacturer of power transfer switches on the planet.
Reliability means the
difference between a night Reliability is a product First 1600 and 2000 First 18- and 30-cycle
spent resolving problems, of innovative and proven de- ampere transfer switches withstand current rating
or sleeping soundly
sign, configuration flexibili- First overlapping switched for transfer switches
ty, quality, ease of operation neutral First power manager with
and serviceability. ASCO embedded I/O and kW
First inphase monitor em-
Power Transfer Switches de- command and control
ployed on transfer switch-
liver it all.
es and first advanced, First communications and
For almost a century,
self-regulating inphase data-logging capability
every major advance in
power technology for transfer switches
power transfer switching
and control design and de- First 3000 and 4000 First Ethernet/Web en-
velopment has come from ampere transfer switches abled connectivity for
ASCO. ASCO pioneered the First integrated power transfer switches
worlds: transfer bypass-isolation First U.L. approved, CE
First automatic transfer switch marked, IEC 60947-6-1
switch in 1920 First two-way bypass-isola- compliant and third-party
First solenoid operated tion transfer switch Kema Keur marked auto-
transfer switch matic transfer switch
First automatic bypass-
First 1200 ampere transfer isolation transfer switch First load shed optimiza-
switch with drawout design for tion for power control
serviceability systems
First solid state automatic
power transfer switch First closed transition First 6KA &10KA UL main
control panel transfer switch bus rating for engine par-
alleling systems.
First microprocessor au- First high-speed power
tomatic power transfer transfer switch ASCO also pioneered
switch controller the worlds most advanced
First three cycle any
automatic transfer switch
breaker withstand and
the 7000 Series. The com-
close-on current rating
pany developed the 7000
capability
Series using a powerful array
First closed transition soft of human and technological
load power transfer switch resources. These innova-
qualified and listed to UL tive firsts evolved from the
1008 expressed needs of our cus-
tomers.

27
Through High Technology

Experienced engineers with decades of accomplishments


and advanced degrees in design theory and analysis employ
cutting-edge value engineering to design, test and qualify
innovative transfer switch technology.
Technological tools over time frames of a few
such as 3-D computer-aided milliseconds. A Case in Point
modeling facilitate the de- The result is a continu-
sign process. Finite element ing stream of innovations in The worlds most so- transition, delayed transi-
analysis helps engineering power transfer technology phisticated power transfer tion, closed transition and
teams design components that meets the evolving technology comes to life as soft load).
that manage magnetic and needs of hospitals, data and the 7000 Series Automatic Quality is assured with
mechanical stresses financial centers, and other Transfer Switch family. the ISO 9001:2000 certifica-
dependably. business-critical facilities. In terms of configura- tion earned by ASCO for its
Teams evaluate proto- Besides innovative tion flexibility, the family is production facilities.
types with fused deposition technology, ASCO offers the based on a four-pole archi- ASCO Power Transfer
modeling and a state-of- security of a dependable tecture and a single or dual Switches are easy to operate
the-art power lab. The lab company large enough to solenoid operator. Also, because information-rich,
verifies performance under satisfy customers evolving one controller is utilized for menu-driven and multi-lan-
real conditions and qualifies need for application sup- all amperages, voltages, guage displays are intuitive
designs to listing agency port, project management frequencies and transfer for virtually any operator.
standards. High-speed and 24/7 field service. switch configurations (open
video photography enables Whatever the challenge,
engineers to analyze how ASCO can help facility engi-
designs react to stress neers keep their power on.
28
A SCO Power Te chnologies
50 Hanover Road Florham Park
N E W J E R SE Y 07932
USA

8 0 0 8 0 0 A SCO
W W W. A SCO P OWER.CO M
A SIA

AUS TRALIA

BRAZIL

C AN A DA

GERMANY

J A PAN

ME X I CO

SOUTH AFRIC A

SOUTH AMERIC A

UNITED ARAB E M I R ATE S

UNITED KINGD O M

U N I T E D S TAT E S

Emerson Network Power.


The world leader in business-critical continuity. EmersonNetworkPower.com
AC Power Systems Embedded Power Power Switching & Controls Site Monitoring
Connectivity Integrated Cabinet Solutions Precision Cooling Surge & Signal Protection
DC Power Systems Outside Plant Services

Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. 2006 Emerson Electric Co.
Publication 3158 R2 November, 2006 Printed in the U.S.A.