Sie sind auf Seite 1von 16

shown the estimated net yearly savings

The Hydrogen-Cooled Turbine Generator with hydrogen cooling for different sizes
of generators, corresponding to these in
creases in efficiency. These savings as
D. S. SNELL sume a power cost of 0.3 cent per kilo
ASSOCIATE AIEE
watt-hour and an operating time of 80
per cent and take account of the cost of
the hydrogen and carbon dioxide re
H YDROGEN cooling for electrical
machinery was first proposed to the
industry through an AIEE paper pre
manufacturing company in connection
with the hydrogen-cooled generator have
been described.3,4 It is the purpose of
quired for operating and filling. They

sented in 1925. * The first hydrogen- the present paper to describe the work of ,Qi+Q*)X OF Ha

cooled machine to be placed in commer another large company in the commercial


cial service was a 12,500-kva synchronous development of this new-type machine,
condenser, installed in 1928.2 This was and to present some of the results of sev
followed by other machines of this type, eral months' operating experience with
and later, the hydrogen-cooled frequency- eight of these machines.
converter was introduced. There are
now in operation in the United States 20 Advantages of Hydrogen
of these two types of hydrogen-cooled as a Cooling Agent
machines, with a combined output of over
one-half million kva, and their records of These have been stated many times be QlA(l-Z) OF AIR
performance have been highly satisfac fore, and are here mentioned only in the
Figure 2 . Schematic diagram of shaft-sealing
tory. Prior to 1937, the application of interest of completeness.
system for hydrogen-cooled generators, using
hydrogen cooling to turbine generators
1. Windage and ventilation losses in hydro vacuum-treated oil
had been confined to developmental gen are only about one-tenth of their value
machines in the manufacturers' plants, in air, due to the lower density of hydrogen.
although several air-cooled generators 2. The rating of a machine can be in also assume the installed cost of the hy
had been built with provision for later creased approximately 20 per cent for a given drogen-cooled generator to be the same as
adaptation to hydrogen cooling. In amount of active material, by operation in that of the air-cooled generator, which is
October 1937 the first hydrogen-cooled hydrogen instead of in air, due to the supe usually the case. The savings thus cal
generator built for commercial service was rior cooling properties of hydrogen.
culated are shown to range from about
placed in operation at Dayton, Ohio. 3. The life of the winding insulation is in $4,000 a year for a 25,000-kw 3,600-rpm
This was a 3,600-rpm unit, of General creased, due to the absence of moisture,
oxygen, and dirt, and to the fact that corona unit to about $20,000 a year for a 160,-
Electric manufacture, rated at 31,250 damage is eliminated, in the hydrogen- 000-kw 1,800-rpm unit.
kva at 0.8 power factor. Since then, a cooled machine. The greater output per pound of mate
total of 10 hydrogen-cooled generators 4. Thefirehazard is eliminated. rial obtained with hydrogen cooling, ex
have been placed in service in various tends the limit of output of generators of
parts of the country, and 27 others are in The reduction of the windage and ven the 3,600-rpm type and allows the build
the course of installation or construction. tilation losses of a turbine generator with ing of generators with self-ventilation in
The total capacity of these 37 generators hydrogen cooling increases the full-load capacities which, if built for air cooling,
is over 2,000,000 kva, and their sizes efficiency about 0.7 per cent for 1,800- would require external fans. The larg
range from 17,000 kva to 81,250 kva at rpm machines and about 0.9 per cent for est capacity at 3,600 rpm now considered
3,600 rpm, and from 75,000 kva to 176,- 3,600-rpm machines. In figure 1 are practicable with air cooling is about 62,-
470 kva at 1,800 rpm. 500 kva, and such a machine would have
20i-
Two papers have already been pre l i t external fans; with hydrogen cooling,
sented before the Institute, in which the E S T I M A T E D NET
SW
AV
generators as large as 81,250 kva at 3,600
I TI N
H GHYDR
PEROGEN YEAR
development and design work of one large CO O L I NIG rpm are practicable, ventilated with in

Paper 39-105, recommended by the AIEE commit


6
^P ternal fans.
tee on electrical machinery, and presented at the
AIEE North Eastern District meeting, Springfield, < fi Type of Shaft Seal Used
Mass., May 3-5, 1939, and at the combined summer _
and Pacific Coast convention, San Francisco, oi2h
Calif., June 26-30, 1939. Manuscript submitted Q / / The most important part in the de
March 3, 1939; made available for preprinting
April 1, 1939.
/> velopment of the hydrogen-cooled genera
4
D. S. SNBLL is electrical engineer in the a-c turbine z tor was the design of a means for sealing
generator engineering department of the General 4 the rotating-shaft extensions against the
Electric Company, Schenectady, N. Y.
outward leakage of hydrogen. After in
The development of the hydrogen-cooled generator
described in the foregoing was carried out under the
direction of M. A. Savage, and in collaboration 7 vestigating many different sealing ar
rangements, of the mechanical, combina
with Chester W. Rice, E. H. Freiburghouse, and
Robert Hannah. The electrical system of the tion mechanical-and-liquid, and liquid-
hydrogen control cabinet was designed by E. J.
Flynn and A. J. Bialous. The tests on the Logan film types, the General Electric Company
and Cincinnati generators were obtained through % finally adopted the liquid-film type of
the co-operation of the Appalachian Electric Power 0 20 40 60 O IOO 120 I 4 0 160
Company and the Cincinnati Gas and Electric GENERATOR RATING -THOUSAND KW AT OS P-F seal for use with its hydrogen-cooled gen
Company, which co-operation is hereby gratefully erators. This type of seal is illustrated
acknowledged. Figure 1 . Estimated net yearly saving by
using hydrogen in place of air as the cooling schematically in figure 2 and includes a
1. For all numbered references, see list at end of
paper. agent, for generators in different sizes sealing ring surrounding the shaft, con-

JANUARY 1940, V O L . 59 SnellHydrogen-Cooled Generators TRANSACTIONS 35


160r
helium have been added, based on calcu
lation. The armature heating curves in
figure 5 have had deducted the calculated
temperature rise of the gas in the air gap
due to field PR loss. This rise is of the
order of from three to five degrees centi
grade. This was done in order to use the
curves for estimating the armature tem
perature rise at 0.8 power factor loads,
the tests having been made at zero power
factor.
The temperature difference between
armature copper and between-coil tem
Figure 3. A 6,250-kva 3,600-rpm generator
built for operation in hydrogen. Coolers are perature detector for different armature
located beneath the rotor. Vacuum tank loadings, in air and in hydrogen, is shown
for treating shaft-sealing oil shown in back in figure 6. At normal load, correspond
ground ing to a loss intensity of about 0.3 watt
per square inch, this temperature differ 0 0.5 1.0 1.5 20 2.5 3.0
W A T T S PER SQ N OP FIELD COIL
ence is about 15 degrees centigrade in air
as compared with 11.4 degrees centigrade Figure 4. Field heating characteristics of a
structed integral with the bearing, to
in hydrogen at 0.44 pound per square 6,250-kva generator with respect to tempera
which vacuum-treated lubricating oil is ture of gas leaving coolers, from tests with
inch pressure. The lower values of the
supplied under pressure.5'6 This creates generator operating in different cooling gases
temperature difference at higher hydro
a film of oil completely surrounding the
gen pressures indicate a slight increase
shaft which prevents the escape of hydro
in the thermal conductivity of the insula
gen from the casing at this point. This same short-circuit ratio at all ratings (by
tion at the higher pressures. The cross
type of shaft seal has the advantages of maintaining the same stator core dimen
ing of the curves at the higher armature
simplicity and ruggedness, and through sions but varying the rotor diameter) the
loadings may be due to changes in the
operating with vacuum-treated oil both increases in output with hydrogen cooling
insulation occurring at the higher tem
permits a high degree of hydrogen purity over the normal air rating, for the same
peratures.
to be maintained in the generator casing winding temperatures, would be approxi
and prevents the contamination of the oil From the foregoing tests, and tests
made on stationary models, it was deter mately 20, 30, and 35 per cent for hydro-
in the bearing lubrication system by the
hydrogen. mined that the thermal conductivity of
the armature insulation was increased
about ten per cent by operation in hydro
Tests on a 6,250-Kva
Hydrogen-Cooled Generator gen instead of air, while that of the field
insulation was practically doubled.
In 1926 a 6,250 kva, 3,600-rpm hydro These increases in thermal conductivity
gen-cooled generator was built by the are practically independent of the hydro
General Electric Company for develop gen pressure. The forced heat convec
mental purposes. This machine, figure tion from the internal machine surfaces
3, was provided with a heavy, cylindrical was estimated to be increased between
casing, cast-steel end shields, and with 30 and 50 per cent by operation in hydro
two gas coolers, contained in a rectangu gen at 0.44 pound per square inch pres
lar box beneath the rotor. A shaft seal sure instead of in air. For increased hy
of the oil-film type was provided in each drogen pressures the forced heat convec
generator bearing. This machine was tion varies approximately with the 0.8
tested as a synchronous condenser in hy power of the absolute hydrogen pressure.
drogen and in air over a period of about 12 The heating data obtained in these
months, during which time the operating tests indicate that the 6,250-kva genera
characteristics of the seals and auxiliary tor as originally designed could have its
equipment could be observed and infor rating at 0.8 power factor increased by
mation on the heating of the machine in very large percentages by operation in
hydrogen and in air obtained. The more hydrogen at various pressures instead of
important of the heating data obtained in air, for the same temperatures of
in the tests are summarized in figures 4 the windings. However, these increases
to 6. in rating would be at the expense of elec
Figures 4 and 5 give the field and ar trical stability, as the short-circuit ratio
mature heating characteristics of the of a generator is decreased in the same
6,250-kva generator for different loss in proportion as the output is increased.
W A T T S P E R SQ I N O F A R M A T U R E COIL
tensities on the coil surfaces, with air, To obtain the same stability from the hy
carbon dioxide, and hydrogen as the cool drogen-cooled generator as from the air- Figure 5. Armature heating characteristics of
ing media, the tests in hydrogen having cooled one, the former must be propor a 6,250-kva generator with respect to tem
been conducted at three different hydro tioned somewhat differently. For the perature of gas leaving coolers, from tests with
gen pressures. Curves for cooling with 6,250-kva generator redesigned for the generator operating in different cooling gases

SnellHydrogen-Cooled Generators ELECTRICAL ENGINEERING


36 TRANSACTIONS
35 per cent less, these disadvantages are helium in place of air as the cooling agent
compensated for, with respect to the would be considerably less than that ob
heating of the windings, by the fact that tained by the use of hydrogen in place of
the forced heat-convection coefficient is air.
about 20 per cent greater in carbon di
oxide than in air, and the product of spe Generator Construction
cific heat and density is 39 per cent greater
for carbon dioxide than for air, so that 39 The type of construction employed
per cent more heat can be absorbed by a with most of the hydrogen-cooled genera
given volume of the gas for the same tem tors built by the General Electric Com
perature rise. Although there is no ad pany is illustrated in figure 7 and in
vantage in the use of carbon dioxide as the cludes a cylindrical, gas-tight, outer cas
cooling agent for generators, as its higher ing, reinforced with a number of annular
density greatly increases the windage supporting-plates. Four gas coolers are
losses, there appears to be a distinct field usually provided, located within the cas
for its use in the case of induction motors ing with their long axes parallel to the
intended for operation in explosive at horizontal axis of the machine. The
mospheres. In the past year the General cooler tubes are made accessible for clean
Electric Company has placed in service ing without removing the hydrogen from
two induction motors of this type, using the casing by removing cover plates at
carbon dioxide as the cooling agent, the either end of the frame. In another de
0 0.1 0.2 03 0.4 0.5
WATTS PER Sq IN OF A R M A T U R E
.
COIL
0.7
motors being provided with shaft seals sign two coolers are used, placed length
similar to those used with hydrogen- wise of the generator and located in either
Figure 6. Temperature drop from armature the top half or the bottom half of the cas
copper to between-coil temperature detector, cooled generators.
The use of helium as the cooling gas for ing.
for different watts per square inch of armature
coil, from tests on a 6,250-kva generator rotating machinery has been frequently The outer end-shields of the generator
operating in air and in hydrogen proposed, and has the advantage of ef are of either cast-steel or fabricated con
fecting a reduction in windage and ven struction and are usually employed to
tilation losses comparable with that ob support the generator bearings, thus
gen pressures of 0.44, 15, and 25 pounds tained with hydrogen, without the attend minimizing the distance between bearing
per square inch, respectively. centers. The joint surfaces between the
ant disadvantage of inflammability in
mixture with air, possessed by hydrogen. end-shield halves and between the shields
Other Cooling Gases However, as shown by the curves in and the casing are carefully machined,
figures 4 and 5, the cooling effect with and are provided with grooves within the
Tests on the 6,250-kva generator using helium is distinctly inferior to that ob bolting line into which a plastic compound
carbon dioxide as the cooling agent indi tained with hydrogen, so that the in is forced, thereby minimizing the possi
cated, as shown in figures 4 and 5, that crease in output of a generator by using bility of hydrogen leakage from the
the heating of a machine in this gas is joints
practically the same as with air cooling. The frame construction is designed to
Although the density of carbon dioxide Figure 7. Longitudinal cross-section view of withstand safely the explosion pressure
is about 50 per cent greater than that of a 55,555-kva 3,600-rpm hydrogen-cooled of the most explosive mixture of hydrogen
air and its thermal conductivity is about generator and air, with the generator operating at a

MMHHPMH

JANUARY 1940, V O L . 59 SnellHydrogen-Cooled Generators TRANSACTIONS 37


Figure 8. A 53,- of the Chicago District Electric Generat
OOO-kw 3,600-rpm ing Corporation, State Line, Ind., ven
steam turbine-gen tilation is provided by four motor-driven
erator set; generator
fans, housed in domes in the top of the
hydrogen cooled
casing.
A device is connected to the bottom of
the generator casing which operates an
alarm if water or oil should start to collect,
as could result from a defective cooler-
tube or from improperly-functioning
shaft seals.
Figure 8 shows a 58,889-kva 3,600-rpm
General Electric hydrogen-cooled genera
tor, installed in the Waterside station of
the Consolidated Edison Company of
New York. This machine has four gas
coolers, located two above and two below
the floor line. Distilled water is circu
lated through the coolers, and a heat ex
changer external to the machine, sup
plied with raw water, is used to cool the
distilled water.
The 50,000-kva 3,600-rpm hydrogen-
cooled generator of the Appalachian
Power Company at Logan, W. Va., em
ploys a novel cooling system in which the
stator core is cooled by direct contact of
the laminations with a number of hollow
hydrogen pressure of 15 pounds per square permits a larger rotor diameter to be em metal pads, located between the lamina
inch. This explosion pressure is esti ployed than with the copper winding and tion packages, through which distilled
mated to be approximately 100 pounds thereby secures a greater rigidity for the water is circulated.8 The construction
per square inch. rotating shaft. The low rotational loss of this machine is illustrated in figure 9.
The rotors of 3,600-rpm hydrogen- in hydrogen permits such an increase in The rotor, and the armature end-wind
cooled generators consist of solid, one- rotor diameter, which would not be prac ings are cooled by the circulation of hy-
piece steel forgings, having slots milled tical with air cooling.
out of the body portion for carrying the The ventilation of these generators, in
field winding. For many of these genera all sizes but the very largest, is provided Figure 9. Longitudinal and end cross-section
tors the field winding is made from alumi by two centrifugal fans, mounted one on views of a 50,000-kva 3,600-rpm hydrogen-
num, instead of from copper, which, due either end of the rotor. For the 176,470- cooled generator having water-filled cooling
to the lower specific weight of aluminum, kva 1,800-rpm hydrogen-cooled generator pads in the stator core

urtuztte coouite

38 TRANSACTIONS SnellHydrogen-Cooled Generators ELECTRICAL ENGINEERING


drogen over them, the heated hydrogen uum treatment of the oil and the amount sufficiently to effect a saving in cost of
being cooled at the center of the machine of leakage from the casing. The purity windage loss comparable with the cost of
in passing to the back of the core through is shown to change exponentially with the hydrogen wasted. In practice, how
ducts formed between special finned pads time, following the initial starting-up of ever, it is preferable to maintain a high
and the laminations. A heat exchanger the generator, finally reaching a constant hydrogen purity by maintaining a high
external to the generator is used to cool value. The amount of hydrogen con degree of vacuum treatment, rather than
the distilled water circulated through the tinuously required by the generator is by leakage, and to have the casing leakage
pads. While no other generators of the shown to equal approximately the casing as small as possible.
pad-cooled type have since been built, leakage plus the amount of hydrogen ab A high hydrogen purity is, of course,
this cooling arrangement is believed to sorbed by the sealing oil. essential from the standpoint of safety,
have several advantages which may some Figure 10 shows the calculated varia as well as of economy, of operation, since
time encourage its more general use. The tion in hydrogen purity with time follow
use of cooling pads in place of the custom ing the starting-up of the generator, for
ary gas coolers permits a more compact different degrees of vacuum treatment of
construction and reduces the volume of the sealing oil, for the 50,000-kva 3,600-
gas that needs to be circulated. rpm Logan generator. A leakage from
the casing of 0.27 cubic foot per hour has
Operating Hydrogen Pressure been assumed, based upon tests. The
curves show that several weeks of opera
The hydrogen-cooled generators built tion are required for the hydrogen purity
by the General Electric Company are de in the casing to reach the final value corre
signed to operate normally at a hydrogen sponding to the vacuum and leakage
pressure of approximately one-half pound also that the final value is independent of
per square inch. Several machines have the initial hydrogen purity in the casing.
been built, however, with provision for Figure 11 shows the calculated final
operating at hydrogen pressures up to 15 hydrogen purity in the generator casing 30 26 26 24 22 20 16
DEGREE OF VACUU/ TREATMENT-IN.HG
pounds per square inch, if such operation for different degrees of vacuum treatment 600 600 1000 1200 1400 1600 1600
COST OF WINDAGE LOSS PER YEAR. - DOLLARS
should become desirable for securing addi of the sealing oil and different assumed
tional kilovolt-ampere output or lower values of the casing leakage, for the Logan Figure 11. Calculated per cent final hydrogen
generator temperatures under abnormal generator. A curve showing the estimated purity in casing of a hydrogen-cooled genera
water-temperature conditions. Operation yearly cost of the windage and ventilation tor for different degrees of vacuum-treatment
at hydrogen pressures greater than about losses of this machine for different values of oil supplied to shaft seals and different
1.5 pounds per square inch requires the of hydrogen purity in the casing is also rates of hydrogen leakage q. Also estimated
provision of additional control features in given, which illustrates the economic ad yearly cost of windage losses versus per cent
the seal-oil and gas control systems. hydrogen purity
vantage of operating at a high purity.
This curve was calculated for an assumed Hydrogen pressure ten inches water
Shaft Sealing System power cost of 0.3 cent per kilowatt-hour
Characteristics and an operating time of 80 per cent. a mixture of less than 72 per cent hydro
It can be shown from the curves of figure gen in air is explosive. In practice it is
SEALS SUPPLIED WITH 11 that for values of vacuum treatment
VACUUM-TREATED OIL usual never to allow the hydrogen purity
less than about 29 inches, a slight casing in the generator casing to decrease below
The equations for the shaft sealing sys leakage may increase the hydrogen purity 90 per cent.
tem employed with these generators are The degree of vacuum treatment of the
derived in the appendix. These show sealing oil is determined by the effective
that, with vacuum-treated oil supplied Figure 10. Calculated per cent hydrogen ness of the treating system. For the
to the shaft seals, the degree of hydrogen purity in casing of a hydrogen-cooled genera spray-recirculation system of vacuum
purity maintained in the generator casing tor versus time for different degrees of vacuum- treatment used with these generators, the
is a function chiefly of the degree of vac- treatment of oil supplied to shaft seals vacuum treatment obtained is generally
between 0.1 and 0.3 inch less than the
100 vacuum held in the vacuum tank.

SEALS SUPPLIED WITH UNTREATED OIL

If the shaft seals are supplied with un


treated oil, as may occur under certain
9
emergency conditions of operation, the
z Barometer 30 inches. air given up from the oil flowing to the
Final hydrogen pur
07 hydrogen side of the seals will cause the
ity by test 99 per hydrogen purity in the casing gradually

H
cent for 29.7 inches
to decrease. This will require that the
vacuum in vacuum
UJ tank. Hydrogen
casing be scavenged at intervals with
consumption by test fresh hydrogen to keep the purity always
1.48 cubic feet per above 90 per cent. Figure 12 shows the
hour. Hydrogen calculated and test values of hydrogen
94i pressure in casing 10 purity under this condition of operation,
15 20 25
TIME IN DAYS inches water for the Logan 50,000-kva generator.

JANUARY 1940, V O L . 59 SnellHydrogen-Cooled Generators TRANSACTIONS 39


The curves show that, for the normal GENERATOR END SHIELD
rate of oil flow to the seals, with untreated (UPPER HALF)

oil, it is necessary to scavenge the genera ELECTRICAL


tor casing with fresh hydrogen about once CONNECTIONS

every 15 hours, to maintain the purity be


tween 90 and 95 per cent. The amount
of hydrogen of 99.8 per cent purity re GENERATOR BEARING
quired to increase the hydrogen purity in
PRESSURE REGULATING
the casing from 90 to 95 per cent is, ap VALVE SEAL OIL FEED

proximately,7
|A S^
CHECK
S
VALVE
PRESSURE-CONTROL
SWITCH
99 890 OIL
0.7X2.3X 1,000 log -500 cubic feet , , -SOLENOID
VALVE COOLER I
99.8-95 |>-
^ BEARING OIL
where the coefficient 0.7 is an "experience FEED
PRESSURE k
factor" and 1,000 the casing volume. MACHINE PRESSURE CONNECTION-
REGULATING
SEAL PRESSURE CONNECTION- VALVE
As this amount of hydrogen is required
every 15 hours the average hourly hydro
VENT
SEAL OIL DRAIN
VACUUM
TANK>
HYDROGEN DETRAINING TANK
N ^
gen requirement for this condition of
operation would be 500/15 = 33.3 cubic
feet per hour. This compares with 1.48
cubic feet per hour continuously required
by this machine to maintain a hydrogen
TO ATMOSPHERE
purity of 99 per cent when the vacuum
system is in operation. (The amount of \7~= END :
(LOWER HALF)
V ACTOR
hydrogen continuously required to main 1L>E ^:
tain a constant pressure in the casing,
when the seals are supplied with un
treated oil, is usually negative, that is, gas
must be vented from the casing. This MAIN TURBINE
OIL TANK ! SCREEN!
follows from the fact that for small values
of casing leakage more air is brought into
the casing by the sealing oil than hydro
gen is discharged by absorption and leak the oil the gas solubilities should be taken Figure 13. Arrangement of shaft-sealing sys
age.) as about one-tenth their values for the tem for hydrogen-cooled generator, with detail
rotating condition. With untreated oil of shaft-sealing arrangement shown for one
STANDSTILL OPERATION OF SEALS generator bearing. Arrangement for other
supplied to the seals, the gas solubilities
bearing is similar
The characteristics of the shaft-sealing used in the seal equations should be taken
system with the generator at rest are as about one-tenth their values for the
somewhat different than with the genera rotating condition. The practical results
tor operative, owing to the different of these differences in seal characteristics about equal to the casing leakage, and
values for the gas solubilities in the oil to for the stationary and rotating conditions the hydrogen purity decreases only about
be used in the seal equations. With vac are, that with vacuum-treated oil supplied one-tenth as rapidly as with the shaft ro
uum-treated oil supplied to the seals, two to the seals the hydrogen requirement is tating.
different values for both the hydrogen and only slightly less with the shaft at rest
the air solubilities must be used; for the than with the shaft rotating, but the hy Shaft Sealing System
absorption of gas by the vacuum-treated drogen purity in the casing is slightly Arrangement Details
oil, about the same solubilities may be higher. With untreated oil supplied to
assumed whether the shaft is rotating or the seals, however, the amount of hydro VACUUM-TREATING SYSTEM
stationary, while for the release of gas by gen required with the shaft at rest is The arrangement of the shaft-sealing
system employed with General Electric
hydrogen-cooled generators is illustrated
CUriVE fa)CALCULATED AND TEST VALUES OF P U f t l T Y FOR
Figure 12. Calcu diagrammatically in figure 13. The seal
Q!= 4 0 CU FT/MR (1.6 X NORMAL) lated and test values ing ring, which is attached to the genera
CURVE(b)CALCULATED VALUES OF P U R I T Y FOR Q i 3 0 of per cent hydrogen
C U F T / H R ( N O R M A L OIL FLOW) tor side of each bearing, contains an an
purity in casing ver
sus time, for a hydro
nular feed groove to which vacuum-
gen-cooled genera treated lubricating oil is supplied under
tor operating with pressure. The oil passes axially along
untreated oil sup the shaft in both directions from the feed
plied to shaft seals. groove to release grooves in the sealing
Casing scavenged ring and bearing, into which it is de
when purity de flected. The oil from the hydrogen-side
creases to 90 per release grooves passes into the hydrogen-
cent detraining tank, where the larger bubbles
Hydrogen pressure of gas absorbed by the oil flowing from
20
TIME
24
IN HOURS 18 inches water the seals are given up and pass back into

40 TRANSACTIONS SnellHydrogen-Cooled Generators ELECTRICAL ENGINEERING


training of the hydrogen from the oil gen to be discharged to atmosphere if it
under this emergency condition of opera becomes necessary to increase the purity
tion. of the hydrogen in the casing.
The principal elements of the vacuum-
treating system are usually constructed as Hydrogen Control
a unit, as shown in figure 14, and the
whole arrangement is conveniently lo CONTROL SYSTEM
cated underneath the generator. The system of hydrogen control em
ployed with these generators is illustrated
EMERGENCY SEAL OIL SUPPLY
in figure 15. The hydrogen supply is
In the event of any failure in the vac contained in several commercial cylinders,
uum-treating system which would cause or "bottles/* connected with a manifold
failure of the discharge pressure of the through pressure-reducing regulators. A
seal oil pump, the shaft seals would be solenoid-operated valve controlled by a
supplied with untreated oil from the pressure switch admits hydrogen to the
bearing supply system through pressure- casing from the connected cylinders to
regulating valve A, figure 13. This valve maintain the casing pressure within pre
is normally open but is prevented from determined limits. These are normally
supplying oil to the seals by the normally- from 8 to 12 inches of water.
closed solenoid-valve B. Failure of the In filling the casing with hydrogen ini
discharge pressure of the seal oil pump tially, or in removing the hydrogen from
Figure 14. Combination vacuum and hydro
opens the pressure switch C, allowing the casing, carbon dioxide is first ad
gen-detraining tank with auxiliary equipment, valve B to open. This operation also mitted, through a pipe at the bottom of
for shaft-sealing system of a hydrogen-cooled closes the normally-open solenoid-valve the casing, and the air or hydrogen dis
generator E in the suction line of the vacuum pump, charged from the hydrogen feed pipe.
preventing the rising of foam in the vac To determine when sufficient carbon di
uum tank, which would occur with the oxide has been admitted to render the
the generator. The oil from the air-side spray nozzles unsupplied with oil. mixture nonexplosive with hydrogen or
release grooves unites with the bearing With the shaft seals supplied with oil
oil and passes to the main oil tank, whence from the bearing supply system, hydro
an equal amount flows by gravity to the gen-saturated oil from the seals passes to
air-detraining tank (or to an air-detrain the air-detraining tank, and thence to the
ing compartment in the main oil tank) main oil tank, through the overflow pipe
where the larger bubbles of air contained in the hydrogen-detraining tank. Opera
in the oil are given up. From the hydro tion of the vapor extractor is relied upon
gen-detraining and air-detraining tanks to maintain the atmosphere above the
the oil passes into the vacuum tank, where oil in the main oil tank well below the
practically all of the hydrogen and air re lower limit of hydrogen-air inflammability
maining in the oil is removed. (four per cent) under this condition of
Oil is pumped to the seals from the operation.
vacuum tank by a rotary pump of the
ATMOSPHERIC RELIEF AND
constant-displacement type, having a ca
SCAVENGING VALVES
pacity several times the normal seal oil
flow. Pressure regulating valve D holds The maximum operating hydrogen
a constant differential between the seal pressure for generators not designed for
and hydrogen pressures by diverting into
the vacuum tank the part of the pump
delivery not sent to the seals. The oil
operation up to 15 pounds per square inch
pressure, is represented in figure 13 by
the elevation of the oil level in the main
ifirWp
diverted through valve D enters the oil tank above the low point of the over Figure 15. Arrangement of hydrogen piping
vacuum tank through spray nozzles, flow pipe from the hydrogen-detraining For hydrogen-cooled generator
which serve to expose large areas of the tank (dimension L). An atmospheric
oil to vacuum treatment. relief valve of the mercury-column type is
A vacuum of between 0.1 and 0.5 inch provided at the hydrogen-detraining tank, air, an Orsat is used, or, in some cases, a
of mercury, absolute, is held in the vac figure 15, which discharges hydrogen to special scale on the hydrogen purity in
uum tank by the operation of a rotary atmosphere if the pressure in the casing dicator is provided.
vacuum pump. As the vacuum pump approaches this limiting pressure. If
discharges to atmosphere an explosive this valve should fail to operate, hydrogen PURITY INDICATORS
mixture of hydrogen and air, the pump would be discharged into the vent pipe in An indication of the percentage hydro
is made explosion proof. the air-detraining tank and would be gen purity in the generator casing is pro
The by-pass tank shown in figure 13 is carried to atmosphere by the vapor ex vided by an instrument operating on the
used to divert the oil from the seal drain tractor. thermal-conductivity principle. Hydro
to the air-detraining tank if it becomes A solenoid-operated scavenging valve is gen from the casing is passed continu
necessary to remove the hydrogen-de also provided at the hydrogen-detraining ously through the analysis cell of the
training tank from service. Its cross-sec tank, figure 15, operated from the hydro purity-indicating instrument by the ac
tion area is sufficient to permit partial de gen control cabinet, which allows hydro tion of the generator fans or by continu-

JANUARY 1940, VOL. 59 SnellHydrogen-Cooled Generators TRANSACTIONS 41


Table I. Heating Tests on 31,250-Kva 3,600-RPM Turbine Generator for Dayton Power and
Light Company Operating as a Synchronous Condenser at Zero Power Factor Overexcited

A l l Temperatures In Degrees Centigrade

Cooling Medium
Air Hydrogen

Kilovolt-amperes at zero power factor 19,200 30,000


Field input, kilowatts 62.5 98
Temperature of gas to coolers 63.4 46.1
Temperature of gas from coolers 40.3 33.1
Temperature rise of gas through coolers 23.1 13.0
Temperature of water to coolers 15.6 18.3
Temperature of water from coolers 26.5 26.6
Temperature rise of water in coolers 10.9 8.2
Water flow to coolers, relative 1.41 1.0
Temperature rise field winding above ingoing gas 67 67
Temperature rise field winding above ingoing water 91.7 81.8
Temperature rise maximum armature temperature coil above ingoing gas 38 32
Temperature rise maximum armature temperature coil above ingoing water 62.7 46.8

rounding it. Since the thermal conduc of this gauge can be calibrated to indicate
tivity of hydrogen is about seven times percentage hydrogen purity.
that of air, a small percentage of air in the
hydrogen will cause a relatively large CONTROL CABINET
change in the thermal conductivity of the The gas admission device, purity indi
hydrogen and will thus effect a propor cating equipment, and the other indicat
tionately large change in the coil resist ing instruments required for operating
ance. The purity indicator is a galva the generator in hydrogen are housed in a
nometer-type of instrument, and indicates control cabinet, usually located near the
Figure 16. Instrument panel of hydrogen- the purity of the gas in the analysis cell
control cabinet for a hydrogen-cooled
generator on the operating floor. Figure
by comparing the resistance of the above 16 shows the instrument panel of the con
generator
coil with that of a standard coil arranged trol cabinet for a 55,555-kva 3,600-rpm
in another arm of the Wheatstone bridge hydrogen-cooled generator. The large
ally wasting a small amount of hydrogen. circuit. A contact in the indicator case round instrument shown at the center of
In the analysis cell a platinum coil, ar operates an alarm to indicate low hydro the upper row of gauges is the fan-pres
ranged in one of the arms of a Wheat- gen purity. sure gauge. Directly below it is the hy
stone Bridge circuit, is passed over by A secondary indication of the hydrogen drogen purity indicator. Other instru-
the hydrogen at a slow rate. This coil purity in the generator casing is provided
carries a heating current, supplied by a by the reading of a gauge showing the
12-volt battery, which causes the coil to pressure developed by the generator fans. Figure 17. Schematic diagram of electrical
increase in temperature, and therefore in As the fan pressure, with the generator circuits of the control cabinet for a hydrogen-
resistance, by an amount depending upon operating at constant speed, is propor cooled generator. Items with (*) are located
the thermal conductivity of the gas sur- tional to the hydrogen density, the scale away from cabinet

110 VOLT 1 CONTACT MAKING


RELAY N0.1

SWITCH

TJOy '
SOLENOID 6AS
ADMISSION
VALVE
110 VOLT A - C '
SOLENOID'
VALVE 125 VOLT D-C PILOT
EMERGENCY
SEAL O I L * PILOT LIGHT U 6 H T 125V0LT0-C

S O L E N O I D VALVE VACUUM PUMP SUCTION

42 TRANSACTIONS SnellHydrogen-Cooled Generators ELECTRICAL ENGINEERING


ments shown are the gauge for indicating
the hydrogen presssure in the generator
casing, the gauge for reading the reduced
hydrogen-bottle pressure, a gauge for
reading the vacuum in the vacuum tank,
and a dial thermometer for indicating the
hydrogen temperature at discharge from
the coolers. The different instruments
are provided with contacts which operate
the alarm system of the cabinet to indi
cate any abnormal condition. The cabi
net is mounted on rubber supports to pro
tect the instruments against vibration.
The three hand-valves shown at the
bottom of the cabinet in figure 16 corre
spond with valves 1, 2, and 3 in figure 15.
The alarm system for the control cabi
net is represented in figure 17 and includes
two contact-making relays of the vacuum-
tube type which are used to operate two
in the casings of these machines have Figure 19. Temperature rise of cooling gas in
alarm horns. Operation of the alarm
been maintained at values between 97.5 ventilation circuit of a 31,250-kva 3,600-rpm
contact of any instrument lights a signal
generator built for operation in hydrogen, from
lamp and causes a current to flow through and 99 per cent.
tests in air and in hydrogen, with generator
a small step-up transformer; this im Although some little time is usually re operating as an overexcited synchronous-
presses a grid-bias on the vacuum tube quired to familiarize the operators with condenser at zero power factor
of one of the contact-making relays, the various details of the auxiliary equip
causing the relay to drop out and operate ment no real operating difficulties have Paths of ventilatins gas shown by arrows
the horns. This arrangement permits been encountered, and in most cases the
a minimum passage of current through operators have come to regard the opera
the instrument contacts for the operation tion of hydtogen-cooled generators as 56 per cent greater load than in air for the
of the horns. being only little more complicated than same temperature rise of the field wind
the operation of the air-cooled type of ing, with respect to the temperature of the
Operating Experience with Eight machine. gas leaving the coolers, while the arma
Hydrogen-Cooled Generators ture winding operated at a temperature
Heating Tests on a rise even lower. Operating with air as
Within the past 18 months eight Gen 31,250-Kva Generator the cooling medium, this generator could
eral Electric hydrogen-cooled generators carry nearly full load rating with the
in capacities ranging from 31,250 kva at The first hydrogen-cooled generator to same heating of the windings as for a
3,600 rpm to 176,470 kva at 1,800 rpm be placed in commercial service, the 31,- standard air-cooled machine. In hydro
and with a combined output of 522,164 250-kva 3,600-rpm Dayton machine, was gen the full-load temperature rises are
kva, have been placed in service. The given extensive tests in hydrogen and in considerably lower than the normal
individual ratings of these machines, and air previous to shipment. Some of the values for air-cooled machines. The
their service records, are given in figure test results are shown in table I and figure curves of figure 19 show the marked re
18. These units have operated almost 19. It will be observed from table I that duction with hydrogen cooling, in the
continuously since installation, with no this machine, operating at zero power temperature rise of the gas in the air gap
outages from faulty operation of the hy factor, carried in hydrogen approximately which has an important influence on
drogen features, and have amply dem the heating of the rotordue to the lower
onstrated the many advantages of hydro rotational loss in hydrogen.
gen cooling. The rates of hydrogen con NEW ORLEANS - 3600RPM:37,500KVA
sumption have averaged from 35 to 60 Future Trends in Generator Design
cubic feet per day for the six 3,600-rpm ROCHESTER - 3600RJ?M.- 3I.250KVA
units, and are about 65 and 120 cubic It will be apparent, from the large num
feet per day respectively for the two ber of hydrogen-cooled generators now in
CINCINNATI 1800RPM.-81,250KVA.
1,800-rpm units. The costs of these successful operation, that this new type
amounts of hydrogen range from $0.45 to of machine has now definitely emerged
CONS. EDISON 3600RPM.-58,889KVA.
$1.50 per day. The hydrogen purities from the experimental stage and has be
come an accepted piece of central-station
PUB. SER. OF N. J.-3600R.PM.-55^55KVA.
equipment. Much remains to be done,
however, now that some operating experi
STATE LINE GENr 1800R.PMrl76,470KVA.
ence with these machines has been gained,
Figure 18. Ratings toward simplification of the equipment
and lengths of time LOGAN 3600RPMr50,000KVA. and improvement of the general design.
in service of eight
In developing the design described in the
General Electric
hydrogen - cooled
DAYTON 3600R.PM.-3I.250KVA. foregoing, the General Electric Company
generators OCT NOV. DEC. JAN. FEa MAR.APR. MAY JUNE JULY AUG. SEPT. 0CT NOV. DEC. JAN. FEa MAR. APR. has endeavored to obtain a system that
1*37 93 1939

JANUARY 1940, VOL. 59 SnellHydrogen-Cooled Generators TRANSACTIONS 43


would b e as reliable a n d as nearly "fool gen purity in the casing of a hydrogen- sure in the generator casing the following
proof" a s possible, even a t t h e expense cooled generator provided with shaft seals equation must be true
of the oil-film type. These equations are
of some complexity. Present develop
based upon the theory of this t y p e of shaft Qi(x+y) +Qs -q+QiHz+QiAH -z) 0)
m e n t a l work is being directed t o w a r d t h e seal as given in the article of reference 5.
Substituting the values of x and y from
reduction in t h e n u m b e r a n d size of t h e
(a) SEALS SUPPLIED W I T H equations 1 and 2 in (3) and solving for qs
auxiliaries a n d in t h e simplification of t h e gives
VACUUM-TREATED O I L
control e q u i p m e n t . A new t y p e of shaft
seal employing smaller shaft clearances Referring to the schematic diagram of the qs = q+Qi [Hz+A(l -)]-
sealing system in figure 2, let
t h a n t h e present seal h a s been developed,
Qi = n u m b e r of cubic feet of oil flowing -j^iQtlHz+Ail-zil+QtA] (4)
which p e r m i t s t h e use of smaller t r e a t i n g yi-r/2
into the generator casing per hour
t a n k s a n d e q u i p m e n t t h a n a r e used a t cubic feet per hour
(from both shaft seals)
present, a n d requires less hydrogen. A Qt=number of cubic feet of oil flowing for the amount of hydrogen t h a t must be
new p u r i t y indicator, with hydrogen a n d out on the air side per hour (from continuously supplied to the generator cas
c a r b o n dioxide scales, h a s been developed, both shaft seals) ing to make up for t h a t lost through absorp
JC=number of cubic feet of hydrogen tion in the sealing oil and t h a t lost by leak
which is more rugged t h a n t h e indicator
contained in one cubic foot of oil age. For high degrees of vacuum and purity
used on t h e earlier machines. A new coming from the vacuum tank at both P and (1 2) are small so t h a t the terms
s t a t o r frame design permits greater ac the time t of equation 4 containing these quantities
cessibility t o t h e coolers for servicing, y = number of cubic feet of air contained may be neglected and the equation for the
t h a n t h e present design. in one cubic foot of oil coming from approximate hydrogen requirement of the
the vacuum tank a t the time t generator written as
A t present n o hydrogen-cooled genera q = number of cubic feet of gas leaving
t o r s smaller t h a n 28,125 k v a a t 3,600 r p m the casing per hour as leakage a t qs = q+QiHz cubic feet per hour (5)
or smaller t h a n 81,250 k v a a t 1,800 r p m the time / T o determine the degree of hydrogen
h a v e been built, or are u n d e r construc 2, = number of cubic feet of hydrogen of purity z t h a t would be maintained in t h e
purity 5 entering the casing per generator casing with the system shown in
tion, b y t h e General Electric C o m p a n y .
hour a t the time t figure 2, let the purity a t time t be 2, and at
F o r sizes appreciably smaller t h a n these, t = time in hours time t-\-dt be z+dz. The latter purity can
t h e gains with hydrogen cooling d o n o t a t i n s o l u b i l i t y of hydrogen in the oil be shown to be
present a p p e a r sufficient t o justify t h e leaving the seal (that is, the number
additional expense a n d complication in of cubic feet of hydrogen in one
cubic foot of oil) z+dz = (6)
volved in its use. However, further im
i 4 = solubility of air in the oil leaving
p r o v e m e n t s in design, a n d increasing the seal (that is, the number of cubic Substituting the value of x from equation 1
familiarity w i t h hydrogen cooling on t h e feet of air in one cubic foot of oil) an expression for dz/dt is obtained of t h e
p a r t of t h e i n d u s t r y m a y eventually m a k e 2 p e r unit hydrogen purity in casing form
desirable t h e extension of hydrogen cool a t the time t
1 2=proportion of air in casing a t time /
ing t o include even t h e smaller sizes of = C +T D (7)
Z 0 = per unit initial hydrogen purity in dt V
machines. F o r t h e larger sizes, t h a t is, drum (that is, z=Z0 a t / = 0 )
a b o v e a b o u t 37,500 k v a a t 3,600 r p m a n d V=total volume of gas in drum and the solution of which is
75,000 k v a a t 1,800 r p m , it is probable connected apparatus in cubic feet
et
5 = p r o p o r t i o n of hydrogen in gas supply "V (8)
t h a t practically all future generators will
per unit
b e hydrogen cooled. 15 = proportion of air in gas supply, per
unit where
P = a b s o l u t e pressure corresponding to
Appendix degree of vacuum treatment of oil, C=2+ [Cid-maix
atmospheres Qi+Qi
[H-S(H-A)} (9)
Equations of t h e Shaft Sealing S y s t e m For the determination of the hydrogen and
consumption, referring to figure 2, note t h a t
In the following are derived the equations the amount of gas in the oil flowing to the
for thehydrogen consumption and thehydro- seals equals the difference between the D=~[q+QiA(l-P)] (10)
amount of gas in the oil entering the vacuum
tank and the amount of gas discharged The second term in equation 8 becomes
( Q 1 + Q 2 A OF AIR from the vacuum pump. This can be shown zero for / = infinity, so t h a t the first term
to be represents the final hydrogen purity in the
casing. I n figure 10 the hydrogen purity in
SEALING RING QxPWz+Att-zK+QtAP the casing of the Logan generator, as a func
tion of time following the starting-up of the
which must equal generator, has been calculated from equa
tion 8 for different values of P , for the value
Qi(x+y)+Q2(x+y) of q obtained in tests on this machine. In
figure 11 the final values of purity from equa
Equating the hydrogen terms and the air tion 8 have been calculated for different
terms in these two expressions gives values of P and q. In these calculations S
has been taken as 0.998. The rates of oil
I / ' Q l Hz OF Ha LOST PHz flow from the gas and air sides of the seal
r
MAIN TURBINE * = <2i (i)
HYDROGEN f Q1+Q2 have been taken from tests as Qi = 30 and
DETRAINING OIL TANK
TANK Q2 = 61.6 cubic feet per hour, respectively.
Q1 Hz OF H 2 O- and An average temperature of the seal oil of
Q,A(1-Z) OF AIR 42 degrees centigrade was used, for which
QtPA(l-z) , Q2AP the hydrogen and air solubilities were taken
Figure 2 0 . Schematic diagram of shaft-sealing y= ~ . ~+- ~ (2) as 4 = 0 . 1 1 and H=0.041, respectively.
Ql+Qt Ql+Q2
system for hydrogen-cooled generators, using The casing volume V was taken as 1,000
untreated oil For the condition of constant gas pres- cubic feet.

44 TRANSACTIONS SnellHydrogen-Cooled Generators ELECTRICAL ENGINEERING


(b) SHAFT SEALS SUPPLIED W I T H estimated to be 0.041 and this value was
UNTREATED LUBRICATING O I L used in estimating the curves in figures 10
For this condition of operation figure 20 and 11.
applies. For the condition of constant gas Until more definite information is avail
pressure in the generator casing we have, able regarding the solubility of hydrogen in
using the symbols given under (a), turbine oil under the conditions which ob
tain at the shaft seals of a hydrogen-cooled
qs+QiA=QlHz+QiA(l-z) (") generator, it may be considered sufficiently
accurate to assume this solubility to be from
whence 60 to 70 per cent of the solubility for hydro
gen in transformer oil, as given byfigure21.
qs = q Qiz(A H) cubic feet per hour (12)
for the amount of hydrogen continuously re
quired by the generator with the seals sup
References
plied with untreated lubricating oil. For 1 HYDROGEN AS A COOLING MEDIUM FOR ELEC
small values of q, qs is negative, that is, TRICAL MACHINES, E. Knowlton, C. W. Rice, and
hydrogen must be discharged from the cas . H. Freiburghouse. AI BE TRANSACTIONS, vol
ing to hold a constant pressure. ume 44, 1925, pages 922-34.
To determine the hydrogen purity in the 2. OUTDOOR HYDROGENVENTILATED SYNCHRO
generator casing under this condition, re NOUS CONDENSERS, R. W. Wieseman. AIEE
*-H 2 SOLUBILITY IN TURBINE Oil.
FROM LOGAN TESTS TRANSACTIONS, volume 48, 1929, pages 1221-9.
ferring to figure 20 the purity at any time
3. T H E APPLICATION OP HYDROGEN COOLINO TO
t+dt can be represented by the equation TURBINE GENERATORS, M. D. ROSS. AIEB
"0 20 40 60 80 IOO TRANSACTIONS, volume 50, 1931, pages 381-6.
Vz-{QiHz+qz-qsS)dt TEMPERATURE OF OIL - DE C
z-\-dz (13) 4. HYDROGEN COOLING OF ROTATING MACHINES,
Figure 2 1 . Solubilities of air and hydrogen C. M. Laffoon. AIEE TRANSACTIONS, volume 55,
1936, pages 703-09.
whence in transformer oil at atmospheric pressure and
5. LIQUID FILM SEAL FOR HYDROGEN-COOLED
at the temperature of the determination, for MACHINES, C. W. Rice. General Electric Review,
dz_-ZE different oil temperatures, from tests b y Rod volume 30, 1927, pages 516-30.
+F (14)
dt~~ man and Maude 9 6. C. W. Rice, United States Patent No. 1,559,182.

The solution of equation 14 is 7. INTERCHANGING HYDROGEN AND AIR IN HYDRO


GEN-COOLED MACHINERY, C. J. Fechheimer.
test values exactly. This value for air Electric Journal, volume 28, 1931, pages 361-2.
F I -FV\ _*.' solubility also agrees closely with the curve
(W) for transformer oil given in figure 21. 8. M. A. Savage, United States Patent No. 2,099,-
575.
However, calculation of transient values of
where hydrogen purity for the Cincinnati genera 9. EFFECTS OF GASES IN TRANSFORMER OILS,
C. J. Rodman and A. H. Maude. American Elec
tor indicated that an assumption of an air trochemical Society Transactions, volume 47, 1925,
E= q+Ql[H+S{A-H)] (16) solubility of seven per cent, for oil at 36 pages 71-92.
degrees centigrade, was required in order to 10. LIMITS OF INFLAMMABILITY OF GASES AND
and
check the test values of hydrogen purity. VAPORS, United States Bureau of Mines Bulletin

-4 However, the turbine oil for the Cincinnati No. 279.


(17) machine had a viscosity of 200 seconds 11. HYDROGEN-COOLED GENERATORS, E. H. Frei
Saybolt Universal at 36 degrees centigrade, burghouse and D . S. Snell. Power, volume 82,
as compared with a viscosity of 130 seconds number 8, 1938, pages 38-41.
In figure 12 the hydrogen purity in the
casing of the Logan generator, with un Saybolt Universal at 42 degrees centigrade 12. SOME DESIGN FEATURES OF HYDROGEN-
COOLED TURBINE GENERATORS, D. S. Snell.
treated oil supplied to the shaft seals, has for the oil in the Logan turbine. Also the General Electric Review, volume 42, number 2, 1939,
been calculated from equation 15 for two shaft speed of the Logan generator was 45 pages 78-80.
different values of oil flow to the hydrogen per cent higher than that for the Cincinnati
side of the seals, namely, Q\=30 and Qi=48 generator, so that there was greater likeli
cubic feet per hour. For (?=48 cubic feet hood that all the air in the seal oil of the
per hour, using an air solubility A =0.11 in Logan machine would be given up to the Discussion
equation 15 gave values of purity z which hydrogen in the casing than would be the
checked the test values of purity exactly. case for the Cincinnati generator. Sterling Beckwith: See discussion, page 34.
This value of A was used, therefore, in It may be deduced from the above that,
calculating curve b in figure 12 and the for the solubility of air in the turbine oil to
curves of figure 10. be used in the equations for the shaft seal, E. H . Freiburghouse (General Electric
the curve for air solubility in transformer oil Company, Schenectady, N . Y . ) : The re
Solubilities of Air and in figure 21 may be assumed correct if the liability of hydrogen cooling of large tur
Hydrogen in the Sealing Oil oil is of low viscosity, and if the shaft speed bine generators has been thoroughly demon
is of the order of 12,000 feet per minute; strated. Referring to figure 18 of Mr.
In applying the equations of the fore however, for oils of high viscosity and at Snell's paper, it is seen that a continuous
going section, the solubilities of air and fairly low shaft speeds, the air solubility service record without interruption from
hydrogen in the oil supplied to the shaft should be taken as 60-70 per cent of the any cause associated with the hydrogen-
seals must be either known or assumed. values for transformer oil. cooling features has been obtained on all
The curves in figure 21 give the solubilities For determining the solubility of hydro of the generators of the design described in
of air and hydrogen in transformer oil, which gen in the turbine oil, tests made on the his paper. Nine of these machines are now
has a viscosity considerably lower than that Logan generator at standstill with the shaft in service. As a result of our operating
of turbine oil and should therefore absorb seals supplied with treated and with un experience with these machines, however,
gas more readily. Tests made by the writer treated oil were used. Substituting the a number of simplifications and improve
indicated the solubility of air in turbine oil test values of hydrogen consumption for ments have been found possible and these
to be 10.8 per cent at 40 degrees centi these two conditions in equations 4 and 11 are being incorporated in the designs of our
grade, which agrees closely with the curve of the preceding section gave a value for newer hydrogen-cooled generators. Some
for transformer oil infigure21. hydrogen solubility of 0.037 at 30 degrees of these design changes and novel construc
In the calculation of figure 12 in the pre centigrade. This is 62 per cent of the tion features will be mentioned in this dis
ceding section the assumption of an air solubility of hydrogen in transformer oil at cussion.
solubility of 11 per cent, for oil at 42 degrees this temperature. Assuming this same Figure 1 of this discussion shows the type
centigrade, was found to give transient percentage to apply for other temperatures, of construction used with our latest hydro
values of hydrogen purity in the casing of the hydrogen solubility at the running gen-cooled generators of the 3,600-rpm
the Logan generator which checked the temperature of 42 degrees centigrade was type, and the arrangement of the gas-

JANUARY 1940, VOL. 59 SnellHydrogen-Cooled Generators TRANSACTIONS 45


" 3^9
y*
Hs J
' ;
RSj 5^;7: tl

control and shaft-sealing systems. In this Figure 1 Our laboratory has developed a new type
design the four gas coolers are located above of hydrogen purity indicator for use with
the floor line, with the water connections hydrogen-cooled machines, which is more
at the extreme ends of the frame instead of experienced with the solenoid valves, and rugged and also more accurate than the
at the sides, as in the earlier design. This also to eliminate the mercury relief valve. indicator now used. This operates on the
construction permits easier cleaning of the The arrangement of the carbon-dioxide thermal-conductivity principle, as does the
cooler tubes than with the former arrange equipment shown in figure 1 is similar to present indicator, but uses alternating in
ment. that used with the machines now in service, stead of direct current, thus eliminating the
The arrangement of the gas control sys and includes heating equipment which per need for the storage battery and rectifier.
tem shown in the above figure is appreci mits the carbon dioxide to be admitted to The horizontal arrangement of shaft-
ably simpler than the arrangement formerly the generator casing as a gas. Carbon di sealing equipment shown in figure 1 is being
used. Wherever possible, valves with dia oxide in the liquid form may be used thereby used with a number of generators now under
phragm-packed stems are being used to reducing the time for purging and eliminat construction. This provides greater accessi
reduce the possibilities of leakage. The ing the heating equipment, however, some bility of the parts; however, a vertical ar
solenoid gas-admission and scavenging what more carbon dioxide would be re rangement of the treating tanks has been
valves, used with our present machines, quired. used wherever it was more suited to the
have been replaced in the arrangement station space. The different elements of
shown in figure 1 with diaphragm-type either arrangement may be mounted on a
valves. This was done to avoid the leakage Figure 2 common base and assembled as a unit.

46 TRANSACTIONS SnellHydrogen-Cooled Generators ELECTRICAL ENGINEERING


One of the more unusual designs for Also, if the cost would thereby be reduced bring the construction of hydrogen-cooled
hydrogen-cooled generators is that employed appreciably, and if the control equipment machines to the forefront, is that now we can
with the 137,500-kva vertical compound and shaft seals were simplified, as suggested calculate quite closely the fans, pressures
turbine generator set built for the Ford by Mr. Snell, would it not be economically and volumes, as well as the distribution of
Motor Company, which is illustrated in desirable to build hydrogen-cooled turbine the cooling medium throughout the machine,
figure 2 of this discussion. This generating generators for smaller ratings than recom which could not have been done a compara
unit, which is now being installed at Dear mended in the paper? tively few years ago.
born, Mich., consists of two separate hydro It is of interest to study table I on tem It seems that today, instead of hydrogen-
gen-cooled generators, each of 68,750 kva peratures. The losses with air for 64 per cooled machines being hazardous, they are
at 1,800 rpm, which are mounted one on top cent of the load with hydrogen are 78 per actually the safest machines, because there
of the other. Each generator is provided cent higher as given by the gas tempera is no internal gas to support combustion,
with a double armature winding, and the ture rise, and 87 per cent higher as given by there is negligible damage from corona, and
windings of the two machines are paralleled the water temperature rise. The fairly they are as clean after years of service as
through connections at one end as shown in close check between the two methods of when first placed in operation.
the above figure. The casing of one gene computation is interesting. Undoubtedly,
rator is connected with the casing of the the windage loss was a very large percentage
other through the conduits used for the of the total loss. Even with considerably P. L. Alger (General Electric Company,
electrical connections between the two higher I2R losses, the field temperature rise Schenectady, N. Y.): When hydrogen
armatures, so that the two casings are con above the ingoing gas temperature was the cooling for electrical machinery was first
sidered as one in filling or emptying the same, but was ten degrees less with hydro proposed, the chief objection to its use was
casings with hydrogen and carbon dioxide. gen, if referred to the ingoing water tempera the fear of an explosion. Tests made to
However, each machine is provided with its ture. As it is the ingoing water that is the determine the pressure developed in an
own hydrogen purity indicator and a sepa ambient, why not take the water tempera explosion of the most explosive hydrogen-
rate fan pressure gauge. Two gas coolers ture, and not the gas temperature, as refer air mixture, initially at atmospheric pres
are provided with each generator, those of ence? sure, indicated that the explosion pressure,
the upper generator being located in the The armature-coil temperature rises are for a machine assembled with core and
bottom of the frame, while those of the even more favorable for hydrogen, they windings, would not exceed 50 pounds per
lower generator are in the upper part of the being only 75 per cent as high (referred to square inch. The theoretical explosion
frame. The hydrogen control panel, item the ambient water), even though the PR pressure, for no heat loss to the surround
11, figure 2, is located in the side of the frame loss was approximately 2.4 times as great. ings, is 180 pounds. Since, however it is not
structure of the lower generator. A single This considerable gain was undoubtedly difficult to construct the frame of the
set of treating tanks is provided for the due chiefly to the relatively high heat con machine to withstand a force of 200 pounds
shaft-sealing oil for both generators, also a ductivity with hydrogen, which reduced the per square inch, it is apparent that there is
single seal oil pump and vacuum pump. thermal drop from the copper to the iron,
This paper clearly indicates that much the transverse drop in the iron packages,
has been accomplished and important prog and the heat transfer drop from the cooling
ress is being made in regard to the cooling surfaces to the cooling medium. Has Mr.
of turbine generators by means of hydrogen. Snell given consideration in the design to the
Operating experience is being rapidly ac feasibility of using thicker iron packages,
cumulated, also further improvements in and of increasing the current density in the
design and materials may be expected. It armature copper, than would be employed
is, therefore, certain that hydrogen cooling in an air-cooled machine?
will be an essential feature of large high It seems from the test results that the
speed machines which are to be built, and usual ratio of rating for hydrogen to air
generators of even larger power output per cooling of 1.2 to 1.3 is entirely too conserva
shaft will be possible in the near future. tive. If the data for this machine are
typical of other hydrogen-cooled turbine
generators, even 50 per cent increase in
Carl J. Fechheimer (consulting engineer, rating is conservative.
Milwaukee, Wis.): The desirability of In figure 9 the use of diffusers to improve
using hydrogen as a cooling medium in the efficiency and increase the pressure of
large high-speed electrical machinery has the centrifugal fan is interesting, and was
been recognized since the presentation of the considered many years ago. It was found
splendid paper by Knowlton, Rice, and that propeller fans were more efficient, were
Freiburghouse in 1925. Having done con not so much restricted at entrance as centrifu
siderable work some years ago in the de gal fans, and could be applied to larger
velopment of gland seals, devices for control sizes of machines. It is worthy of note that
and proportioning of parts when hydrogen with the very high peripheral velocities of
cooling was beginning to be discussed, the the centrifugal fans, more pressure can be H
0 20 40 SO lOO
paper by Mr. Snell is of especial interest to developed than is necessary; the result is P E R C E N T O F H E L I U M IN H Y D R O G E N
me. that the fans are not operated at the most
It seems to me that the fear of an ex favorable point on their pressure-volume Figure 3
plosion has caused our engineers to be overly curves. Is it not likely, as shown in table I,
cautious. If an inert gas is used properly that the high gas temperature rise when air is
as an intermediary when changing from air used, is largely due to the high fan pressure very little to fear from an explosion in a
to hydrogen or the reverse, it should not be and rather low fan efficiency? If so, per hydrogen-cooled machine.
necessary to burden the generator with the haps the ratio of ratings would not be so Nevertheless, it is interesting to consider
additional expense attended with making it high (as suggested in the preceding para other gases which could be used for cooling
explosion proof. Particularly with the graph) if the temperature rise of the air that are not subject to these explosion risks,
large diameters associated with the large when passing through the fans were reduced? slight as they are, thus promoting economy
slower speed 1,800-rpm machines, it is es As indicated in figure 9, a number of in methods of installation and handling.
sential to make the enclosing brackets with hollow metal pads between lamination pack An obvious possibility is the use of helium.
thick walls, probably with ribbing, and to ages, were used for the water coolers. The The light weight of helium gives very low
curve them, so that they will withstand an details of construction are not entirely windage losses, but its materially higher
explosion safely. I would inquire of the clear and I would inquire whether the pads cost and its inferior cooling properties make
author whether consideration has been given interfered with the flow of hydrogen, and it undesirable for use as a pure gas. It
to the design which will be sufficiently strong whether the thermal drops from laminations therefore occurred to me that the properties
for ordinary operation only, and if so, by to water were appreciably altered, as com of a mixture of helium and hydrogen should
what percentage the cost of a large 1,800- pared with the usual finned surface cooler. be investigated, in the hope of obtaining a
rpm generator would thereby be reduced? Perhaps one thing that has helped to gas free from explosion risk, that would pre-

JANUARY 1940, VOL. 59 SnellHydrogen-Cooled Generators TRANSACTIONS 47


serve practically all of the advantages of parent hydrogen consumption. Mr. Snell mately 25 per cent a t 55 degrees centigrade,
pure hydrogen. The results of a theoretical in his paper stresses the contaminating in a dew point of 30 degrees centigrade and
study of this subject by Doctor Saul Dush- fluence of air from the seal oil, b u t it is our volume concentration of water vapor of
man and D. S. Snell are presented in the two experience t h a t moisture can also be a seri 4.8 per cent. Under these conditions the
accompanying figures. ous diluent of the hydrogen. hydrogen consumption was very high and
Figure 3 of this discussion shows the limits This moisture problem has been elimi water was condensed from the gas a t the
of inflammability of a mixture of hydrogen nated by the combination of an oil vacuum coolers which were operating approximately
and helium, also the thermal properties of treating unit and a gas drying unit which are 10 degrees centigrade below the dew point.
described by Messrs. Ross and Sterrett. The necessity of removing moisture from the
The simple vacuum-treating unit reduces the oil going to the seals is thus indicated.
water content of the oil to less than 0.003 Returning again to the electrical insula
per cent by weight. With added complica tion, the combined oil-treating and gas-
tions, the vacuum system could be made to drying system so effectively removes mois
reduce the moisture content still lower. ture and air from the oil that the insulation
But even a t very low concentrations, some may be considered almost hermetically
moisture is always vaporized from the oil sealed in an inert medium. The problems
in passing over the seals which will gradually caused by the effects of ozone, oxides of
build up moisture concentration in the ma nitrogen, moisture, and accumulation of
chine and this will eventually increase the dirt are all eliminated. The performance of
hydrogen consumption. This, together with the insulation in hydrogen should therefore
the possibility of failure of the oil vacuum be far better than in air.
treating system, justifies the addition of the
exceedingly simple activated-alumina gas
dryer described by Messrs. Ross and Ster S. H. Mortensen (Allis-Chalmers Manufac
rett. turing Company, Milwaukee, Wis.): The
We have studied one of these machines authors of the papers on hydrogen-cooled
and the results may be of interest. Actual turbine generators have so admirably
determination of the moisture content of the covered the design and operating problems
gas in a 50,000-kw machine which had been incidental to hydrogen-cooling of turbine
i II 1 I I I I o in operation for some time has been made. generators, that I find nothing to add except
O 20 40 60 60 WO With the vacuum-treating unit and dryer in a description of the Allis-Chalmers com
PERCENT OF HELIUM IN HYDROGEN
operation the moisture content was approxi pany's hydrogen-shaft seal and a discussion
Figure 4 mately 0.01 gram per cubic foot of gas. of its effect upon certain faces of the genera
This corresponds to a relative humidity of tor operation.
0.4 per cent a t machine temperature of The Allis-Chalmers company's shaft seal
the mixture compared with air. Figure 4 55 degrees centigrade (machine was only is shown in figure 5 of this discussion and
shows the calculated effect on the explosion partially loaded at time of test), a dew point consists of a small runner, item 1, provided
pressure at the upper limit of inflammability, in the neighborhood of 25 degrees centi on the generator shaft at each end of the
of mixing helium with hydrogen. The grade, and volume concentration of water machine close to the main bearing, and
curves were calculated for an assumed heat
loss of 25 per cent. The amount of helium
shown to be required, and its cost, in order
Figure 5. Shaft seal
to produce a significant reduction in the
explosion pressure, are so large, however, as
to make this procedure unattractive.
OIL DRAIN TO
- DETRAINING
C. F. Hill and L. J. Berberich (Westing- TANK
house Electric and Manufacturing Com
pany, East Pittsburgh, P a . ) : The operat
ing experience described in these papers on
hydrogen-cooled generators indicates t h a t
hydrogen will in the near future be the - CUP LEATHERS
generally accepted cooling medium for
machines of the larger ratings. I t should be
mentioned again that electrical insulation
is subjected to fewer deteriorating influences
when operating in hydrogen as compared
with air.
We should like to re-emphasize one or two AIR
of these. The effects of oxygen, ozone, and
oxides of nitrogen, the last two being pro
duced only under corona conditions, are
completely absent. These phenomena
have been discussed in previous papers and
need be only mentioned here. But even
more important, is the problem of moisture
absorption by the insulation which can be
almost completely eliminated in the hydro
gen-cooled machine.
Here the only source of moisture is from vapor of approximately 0.06 per cent. The against each face of the runner a conven
the oil supplied to the hydrogen seals. T h e effectiveness of this system of moisture and tional babbitt thrust bearing, item 2, is held
moisture is, of course, introduced into the air removal is attested by the fact that the by springs, item 3, permanently set to give
lubricating oil system by the turbine. hydrogen consumption for this machine is a pressure equal to about a third of the
When moisture-laden oil is passed into the only 20 cubic feet per day. A similar test normal capacity of the bearing. Around the
seals, which run in the neighborhood of was made on the same machine with the inner periphery of each thrust bearing, but
100 degrees centigrade, a considerable moisture elimination system not in opera separated from it by a groove, is a continu
amount of water is vaporized into the ma tion and a water content of roughly 1.0 ous babbitt face about an eighth of an inch
chine. This water vapor acts as a contami gram per cubic foot gas was found. This wide. During operation this continuous
nant to the hydrogen and increases the ap corresponds to a relative humidity approxi face provides the required seal, since it is

SnellHydrogen-Cooled Generators ELECTRICAL ENGINEERING


48 TRANSACTIONS
separated from the runner by only the thick 2, 1937, and from t h a t time until February erence for basing temperature rises for
ness of the oil film in the thrust bearing. 28, 1939, the unit has run a combined total hydrogen-cooled machines, we have given
Oil under pressure is circulated around the of 232 days. The running time lost during considerable thought to this matter but
flange between the two thrust-bearing faces this period has not been occasioned by any still feel that the use of the ingoing gas tem
to provide cooling and lubrication and to trouble or maintenance in connection with perature offers the best basis for making
oppose the pressure of the hydrogen at the the generator proper or its gas sealing sys guarantees on this type of machine. The
small clearance between the continuous tem. N o difficulty of any great importance use of the ingoing gas temperature as a basis
babbitt face and the flange. The oil pres has been experienced with the shaft-sealing for temperature rise allows an accurate
sure counterbalances the spring pressure so system and its accessory equipment. No comparison between different machines as
that resulting bearing load is very low. failure to maintain the seals has occurred at the true rise of the machine alone is ob
Cup leathers, item 4, are provided at the any time. As of February 28, 1939, this tained, whereas if the ingoing water tempera
outer periphery of the oil chamber to retain seal system had operated 308 days. We are ture were used as a basis, a designer could
the oil and provide flexibility. now maintaining a purity varying from 99 skimp the design of the generator and use
The Allis-Chalmers type of seal is suitable to 100 per cent and the gas consumption is an extra large cooler, obtaining the same
for operation with hydrogen pressures from averaging approximately 40 cubic feet per over-all temperature rise with this machine
zero up to ten pounds per square inch with day. The delivered cost of this gas, includ as with a machine of more liberal design.
out oil or seal adjustments. ing handling of the cylinders, amounts to Obviously the machine with the lower tem
As this type of seal provides an air-tight approximately 2 cents per cubic foot, so perature rise within itself is the more liberal
joint, air or gas can be removed from the that the yearly cost on this basis is less than design.
generator by evacuation. This makes it $300. Also, since it is easy to test the coolers and
practicable to simplify the scavenging proc Mr. Snell describes in his paper the pad the generator separately, there is little or
ess described by authors to the extent of cooling arrangement for direct water cool no reason to combine the two in one over
eliminating the use of carbon dioxide and ing of the stator. Plant condensate was all guarantee, and especially is this true due
offering advantages such as; used as make-up for this pad liquid system. to the fact t h a t the generator is the major
In order to eliminate the possibility of air portion of the investment and the more
1. No carbon-dioxide or other inert gas is required pockets in the pads, it is necessary to ob critical.
for scavenging generator.
tain a high vacuum before filling with con The Institute a t the present time has
2. Since interchange of hydrogen and air takes densate. In this respect some difficulty adopted the ingoing gas or air as a basis for
place at one fifth of an atmosphere or less, only
about one fifth as much excess hydrogen above one was experienced initially but by circulating the ambient temperature on which rises
volume is required. the pad liquid for some time and by wasting should be predicated, and we can see no
3. Extra pipes to drain all "pockets" of carbon- a portion from the overhead expansion tank, reason for the Institute's making two differ
dioxide are not essential. it was possible to remove practically all of ent standards for large rotating equipment
4. Less time is required to empty or fill generator the air still remaining in the pads. The because one happens to be enclosed and the
with hydrogen. operation of the system has been entirely other an open machine, as basically the
5. The filling operation is simplified. satisfactory. temperature rises, which are satisfactory
Mention is made of operation at gas pres for one machine are applicable to the other
Operating experience, over a period of sures as high, as 15 pounds per square inch. type.
months, further shows that the sealing oil The Logan unit has been run for short pe Regarding the thickness of the stator iron
volume which gets into contact with the riods at these higher pressures with satis packages and the armature current density
generator hydrogen is so small that oil factory performance of the shaft-sealing in the hydrogen-cooled machine, both these
treatment becomes unnecessary except for system and without obtaining excessive quantities have been increased over then-
its passing through a hydrogen detraining consumption of gas. We have had consider values for the air-cooled machine.
tank before it is returned to the oiling sys able experience with the operation of hydro Mr. Fechheimer's suggestion that the in
tem. gen-cooled synchronous condensers at pres crease in rating of a generator by the use of
I t is expected t h a t additional operating sures up to and including 15 pounds per hydrogen should be considerably greater
experiences will result in further simplifica square inch. We hope to present detailed than the 20 per cent mentioned in the paper,
tions in the application of hydrogen as a operating data covering such performance based on the data given in table I, neglects
ventilating medium. in a coming paper before the Institute. the fact that the hydrogen-cooled generator
must be proportioned differently than the
air-cooled machine, to obtain the same elec
Philip Sporn (American Gas and Electric D. S. Snell: I wish to thank Mr. Fech- trical stability. If this change in design is
Service Corporation, New York, N . Y . ) : heimer for his interesting and valuable dis considered it will be found that the increased
Early in 1935 studies indicated the desir cussion. Mr. Fechheimer has contributed output per pound of material with hydrogen
ability of installing a t Logan, W. Va., a much to the development of hydrogen cool will be of the order of 20 to 25 per cent.
40,000-kw 3,(500-rpm high-pressure super ing and his comments on the subject are Regarding the use of diffusers in conjunc
position turbine, in order most economically welcomed. As to the saving effected with tion with the centrifugal fans employed with
to develop and increase the capacity of the hydrogen-cooled generators of the 1,800- these machines, while these are generally
existing power plant a t this location. At rpm type through making the machine provided with air-cooled generators they
that time the manufacturer stated that structure strong enough only for normal have been omitted from many of the hydro
cooling of the rotor for a generator of this operation, but not strong enough to with gen-cooled machines for the reason that fan
size and speed could be accomplished only stand an explosion, I believe that for the efficiency is relatively unimportant in a
by utilizing hydrogen ventilation. Follow type of construction employed with our hydrogen-cooled machine, while the reduc
ing our extensive and successful experience hydrogen-cooled generators no saving would tion in machine length obtained by omit
with seven large-capacity hydrogen-cooled be obtained. For with a construction in ting the diffusers is of value. This omission
synchronous condensers then in service on which the generator bearings are supported results in a rather high windage loss and
the American Gas and Electric Company in the end shields, a construction that is temperature rise of the air when the ma
system, we unhesitatingly accepted hydro rigid enough for ordinary operation is also chine is operated in air, as Mr. Fechheimer
gen cooling for this new generator unit. strong enough to withstand an explosion. has observed in connection with table I;
In the case of synchronous condensers, the At the present time the cost differential be however, since these machines are intended
bearings are entirely enclosed in the outer tween the hydrogen-cooled and the air- principally for operation in hydrogen, this
shell, and therefore the problem of sealing cooled machine is principally due to the cost feature is not considered important. As to
the shaft against gas leakage is not en of the auxiliary equipment, and as this cost the relative merits of centrifugal and pro
countered. However, extensive tests and does not vary greatly with different sizes of peller fans, we recognize that while the
factory operating experience with the oil machines, it is difficult at the present time propeller fan has a slight advantage in
seal at Schenectady over a period of years, to justify the use of hydrogen cooling for efficiency it also requires a greater amount of
provided a basis for anticipating satisfac generators in sizes much smaller than the axial space on the shaft for its support, thus
tory performance from this shaft-sealing minimum sizes mentioned in the paper. increasing the distance between bearing
arrangement in power-station service. Regarding Mr. Fechheimer's proposal centers.
The Logan generator went into operation that ingoing water temperature rather than Referring to Mr. Fechheimer's inquiry as
as a hydrogen-cooled machine on December ingoing gas temperature be used as the ref- to the construction of the machine illus-

JANUARY 1940, VOL. 59 SnellHydro gen-Cooled Generators TRANSACTIONS 49


trated in figure 9, figure 6 of this discussion ings of the turbine generator set, since vac Mr. Sporn describes operating experiences
illustrates the construction of the metal uum treatment of oil removes impurities with the Logan generator, which was one of
pads which are employed for removing the and thereby prolongs its life. Considering the first hydrogen-cooled generators to be
heat from the stator core and the cooling that the vacuum tank requires little space placed in service. It is gratifying to us that
gas. The pads of the plain type are used in and practically no servicing, it does not this machine, which embodied two radical
the end sections of the stator core and re seem that the elimination of this device departures from conventional design-hydro
move the generated heat by direct conduc offers as many advantages as its retention. gen cooling and pad coolingshould have
tion to the cooled pad. The finned pads The evacuation of the generator casing operated practically without trouble since
are used in the center part of the core and before filling with hydrogen, or when empty- installation. Mr. Sporn's company has
been a pioneer in the use of hydrogen-
cooled machinery, having installed in 1928
Figure 6. Monel- one of the first hydrogen-cooled synchronous
meial cooling pad condensers and in 1937 one of the first hy
for hydrogen-cooled drogen-cooled generators. His faith in this
generator, copper- new development has contributed largely
brazed to its success and it is gratifying to us to
see that his confidence in hydrogen cooling
Arrows indicate has been justified.
brazed joints Mr. Alger mentions a theoretical study
made to determine the desirability of using a
mixture of helium with hydrogen to reduce
the explosion pressure. At the time this
investigation was made the cost of commer
cial helium was approximately six times the
cost of hydrogen. Since then the cost of
helium has been greatly reduced and it can
now be obtained for approximately twice
the cost of hydrogen. Even with this reduc
tion in cost, however, the use of helium as a
cooling agent is not considered desirable
since its cooling properties, as explained in
absorb heat both by conduction through ing, as proposed by Mr. Mortensen, has the paper, are considerably inferior to those
contact with the laminations, and by con some advantages over the use of an inert of hydrogen. Since the type of generator
vection, through passage of the heated gas gas. However, to evacuate the casing re construction and the shaft-sealing and gas-
from the air gap to the back of the core be quires that the generator be at rest, whereas control equipment would be substantially
tween the fins. The finned pads take the the inert gas may be introduced with the the same whichever cooling medium were
place of the surface gas coolers used with the generator rotating, which is frequently done used, and the helium-cooled generator would
ordinary type of generator. The fan pres to save time. be appreciably larger than the hydrogen-
sure required to ventilate this type of ma Messrs. Hill and Berberick mention the cooled machine for a given output, it will be
chine is practically the same as is required problem of contamination of the hydrogen evident that the use of helium is not eco
with the ordinary type, for the same volume by moisture given up from the sealing oil as nomically advantageous.
of gas circulated. being of equal importance to the problem of Mr. Freiburghouse has mentioned some of
It is true, as Mr. Fechheimer suggests, contamination by air from the oil. While the recent improvements that have been
that the development of the hydrogen- this is probably true where the temperature made in the design of the hydrogen-cooled
cooled machine has been accelerated by the of the oil leaving the seals is in the neighbor generator, also some of the details of con
progress previously made in methods of hood of 100 degrees centigrade, it is not the struction of the 137,500-kva hydrogen-
calculating fan performance and ventilation case where the temperature of this oil is cooled generating set for the Ford Motor
characteristics, and also, I would add, in approximately 60 degrees centigrade, as is Company. This generator set has recently
methods of predetermining the thermal be the case with the type of seal described in been placed in service with hydrogen. The
havior of electrical machines. For much of my paper. Since the radial shaft clearance shaft seals used with these generators are of
this progress we are indebted to the re of this seal is the same as that of the bearing a different type from those used with our
searches of Mr. Fechheimer. the energy loss in the oil film is low compared earlier generators and consist of metal
The shaft seal described by Mr. Morten- with the oil flow so that only moderate oil rings bearing radially on the shaft, the rings
sen possesses many desirable features. temperatures are obtained. This precludes being supported in a housing attached to the
Several years ago we tested a seal of a some the possibility of moisture being vaporized end shield. This type of seal requires less
what similar type, in which a stationary out of the oil into the generator. oil than the type described in the paper, so
carbon ring pressed axially against a runner Mr. Beckwith suggests the elimination of that smaller treating tanks and equipment
carried on the shaft. Trouble was experi the hydrogen relief valve. In the system may be used.
enced, however, through air being pumped described in my paper a relief valve of the Besides the Ford generators, two other
into the generator casing between the ring mercury type is used to prevent the dis hydrogen-cooled generators have been
and runner by centrifugal force. In Mr. charge of hydrogen into the air detraining placed in service by our company since my
Mortensen's seal this pumping action is pre tank in the event of excessive pressure in paper was written. We have now 12 of these
vented by supplying lubricant to the rub the casing. In our later designs a dia machines in operation, their combined rat
bing surface under pressure. phragm type of relief valve is used, which ing being 770,000 kva. The largest 3,600-
While it is desirable to eliminate from the serves also for scavenging. In our case this rpm machine is rated 66,667 kva while the
sealing system as many auxiliaries as possi valve can hardly be dispensed with. largest 1,800-rpm generator is rated 176,470
ble, the elimination of the vacuum tank, as The hydrogen requirement for these ma kva. A total of 19 hydrogen-cooled genera
suggested by Mr. Mortensen has certain chines has been found to vary approximately tors are under construction at the factory,
disadvantages. Without the use of vac with the square root of the hydrogen pres with a combined output of 1,035,000 kva.
uum-treated oil in the shaft seals, the hydro sure, as stated by Mr. Beckwith, although One of these units is rated 50,000 kva at
gen purity in the generator casing will de theoretically the part of the hydrogen re 3,000 rpm and will be installed at Buenos
crease, even if at a slow rate, and the opera quirement due to absorption in the sealing Aires. This is the first hydrogen-cooled
tor must manually scavenge the casing at oil should vary about directly with the generator to be sold for foreign installation.
intervals in order to maintain the desired absolute pressure. The discrepancy is prob The growing popularity of this new type of
hydrogen purity. If the oil is vacuum ably due to a slight opening-up of the cas generator indicates that the former appre
treated, however, no scavenging is required. ing joints at the higher pressures. Tests on hensions regarding hydrogen cooling have
Also, the vacuum treatment of the sealing the Logan 50,000-kva generator showed a been largely dissipated by the successful
oil, aside from its value in the operation of hydrogen requirement of 40 cubic feet per operation of the units now in service and
the hydrogen system, is of definite value day at one-half pound pressure and 300 that the many advantages of hydrogen cool
with respect to the operation of the bear cubic feet per day at 15 pounds. ing are becoming widely recognized.

50 TRANSACTIONS SnellHydrogen-Cooled Generators ELECTRICAL ENGINEERING

Das könnte Ihnen auch gefallen