Beruflich Dokumente
Kultur Dokumente
The Hydrogen-Cooled Turbine Generator with hydrogen cooling for different sizes
of generators, corresponding to these in
creases in efficiency. These savings as
D. S. SNELL sume a power cost of 0.3 cent per kilo
ASSOCIATE AIEE
watt-hour and an operating time of 80
per cent and take account of the cost of
the hydrogen and carbon dioxide re
H YDROGEN cooling for electrical
machinery was first proposed to the
industry through an AIEE paper pre
manufacturing company in connection
with the hydrogen-cooled generator have
been described.3,4 It is the purpose of
quired for operating and filling. They
sented in 1925. * The first hydrogen- the present paper to describe the work of ,Qi+Q*)X OF Ha
MMHHPMH
urtuztte coouite
H
cent for 29.7 inches
to decrease. This will require that the
vacuum in vacuum
UJ tank. Hydrogen
casing be scavenged at intervals with
consumption by test fresh hydrogen to keep the purity always
1.48 cubic feet per above 90 per cent. Figure 12 shows the
hour. Hydrogen calculated and test values of hydrogen
94i pressure in casing 10 purity under this condition of operation,
15 20 25
TIME IN DAYS inches water for the Logan 50,000-kva generator.
proximately,7
|A S^
CHECK
S
VALVE
PRESSURE-CONTROL
SWITCH
99 890 OIL
0.7X2.3X 1,000 log -500 cubic feet , , -SOLENOID
VALVE COOLER I
99.8-95 |>-
^ BEARING OIL
where the coefficient 0.7 is an "experience FEED
PRESSURE k
factor" and 1,000 the casing volume. MACHINE PRESSURE CONNECTION-
REGULATING
SEAL PRESSURE CONNECTION- VALVE
As this amount of hydrogen is required
every 15 hours the average hourly hydro
VENT
SEAL OIL DRAIN
VACUUM
TANK>
HYDROGEN DETRAINING TANK
N ^
gen requirement for this condition of
operation would be 500/15 = 33.3 cubic
feet per hour. This compares with 1.48
cubic feet per hour continuously required
by this machine to maintain a hydrogen
TO ATMOSPHERE
purity of 99 per cent when the vacuum
system is in operation. (The amount of \7~= END :
(LOWER HALF)
V ACTOR
hydrogen continuously required to main 1L>E ^:
tain a constant pressure in the casing,
when the seals are supplied with un
treated oil, is usually negative, that is, gas
must be vented from the casing. This MAIN TURBINE
OIL TANK ! SCREEN!
follows from the fact that for small values
of casing leakage more air is brought into
the casing by the sealing oil than hydro
gen is discharged by absorption and leak the oil the gas solubilities should be taken Figure 13. Arrangement of shaft-sealing sys
age.) as about one-tenth their values for the tem for hydrogen-cooled generator, with detail
rotating condition. With untreated oil of shaft-sealing arrangement shown for one
STANDSTILL OPERATION OF SEALS generator bearing. Arrangement for other
supplied to the seals, the gas solubilities
bearing is similar
The characteristics of the shaft-sealing used in the seal equations should be taken
system with the generator at rest are as about one-tenth their values for the
somewhat different than with the genera rotating condition. The practical results
tor operative, owing to the different of these differences in seal characteristics about equal to the casing leakage, and
values for the gas solubilities in the oil to for the stationary and rotating conditions the hydrogen purity decreases only about
be used in the seal equations. With vac are, that with vacuum-treated oil supplied one-tenth as rapidly as with the shaft ro
uum-treated oil supplied to the seals, two to the seals the hydrogen requirement is tating.
different values for both the hydrogen and only slightly less with the shaft at rest
the air solubilities must be used; for the than with the shaft rotating, but the hy Shaft Sealing System
absorption of gas by the vacuum-treated drogen purity in the casing is slightly Arrangement Details
oil, about the same solubilities may be higher. With untreated oil supplied to
assumed whether the shaft is rotating or the seals, however, the amount of hydro VACUUM-TREATING SYSTEM
stationary, while for the release of gas by gen required with the shaft at rest is The arrangement of the shaft-sealing
system employed with General Electric
hydrogen-cooled generators is illustrated
CUriVE fa)CALCULATED AND TEST VALUES OF P U f t l T Y FOR
Figure 12. Calcu diagrammatically in figure 13. The seal
Q!= 4 0 CU FT/MR (1.6 X NORMAL) lated and test values ing ring, which is attached to the genera
CURVE(b)CALCULATED VALUES OF P U R I T Y FOR Q i 3 0 of per cent hydrogen
C U F T / H R ( N O R M A L OIL FLOW) tor side of each bearing, contains an an
purity in casing ver
sus time, for a hydro
nular feed groove to which vacuum-
gen-cooled genera treated lubricating oil is supplied under
tor operating with pressure. The oil passes axially along
untreated oil sup the shaft in both directions from the feed
plied to shaft seals. groove to release grooves in the sealing
Casing scavenged ring and bearing, into which it is de
when purity de flected. The oil from the hydrogen-side
creases to 90 per release grooves passes into the hydrogen-
cent detraining tank, where the larger bubbles
Hydrogen pressure of gas absorbed by the oil flowing from
20
TIME
24
IN HOURS 18 inches water the seals are given up and pass back into
Cooling Medium
Air Hydrogen
rounding it. Since the thermal conduc of this gauge can be calibrated to indicate
tivity of hydrogen is about seven times percentage hydrogen purity.
that of air, a small percentage of air in the
hydrogen will cause a relatively large CONTROL CABINET
change in the thermal conductivity of the The gas admission device, purity indi
hydrogen and will thus effect a propor cating equipment, and the other indicat
tionately large change in the coil resist ing instruments required for operating
ance. The purity indicator is a galva the generator in hydrogen are housed in a
nometer-type of instrument, and indicates control cabinet, usually located near the
Figure 16. Instrument panel of hydrogen- the purity of the gas in the analysis cell
control cabinet for a hydrogen-cooled
generator on the operating floor. Figure
by comparing the resistance of the above 16 shows the instrument panel of the con
generator
coil with that of a standard coil arranged trol cabinet for a 55,555-kva 3,600-rpm
in another arm of the Wheatstone bridge hydrogen-cooled generator. The large
ally wasting a small amount of hydrogen. circuit. A contact in the indicator case round instrument shown at the center of
In the analysis cell a platinum coil, ar operates an alarm to indicate low hydro the upper row of gauges is the fan-pres
ranged in one of the arms of a Wheat- gen purity. sure gauge. Directly below it is the hy
stone Bridge circuit, is passed over by A secondary indication of the hydrogen drogen purity indicator. Other instru-
the hydrogen at a slow rate. This coil purity in the generator casing is provided
carries a heating current, supplied by a by the reading of a gauge showing the
12-volt battery, which causes the coil to pressure developed by the generator fans. Figure 17. Schematic diagram of electrical
increase in temperature, and therefore in As the fan pressure, with the generator circuits of the control cabinet for a hydrogen-
resistance, by an amount depending upon operating at constant speed, is propor cooled generator. Items with (*) are located
the thermal conductivity of the gas sur- tional to the hydrogen density, the scale away from cabinet
SWITCH
TJOy '
SOLENOID 6AS
ADMISSION
VALVE
110 VOLT A - C '
SOLENOID'
VALVE 125 VOLT D-C PILOT
EMERGENCY
SEAL O I L * PILOT LIGHT U 6 H T 125V0LT0-C
control and shaft-sealing systems. In this Figure 1 Our laboratory has developed a new type
design the four gas coolers are located above of hydrogen purity indicator for use with
the floor line, with the water connections hydrogen-cooled machines, which is more
at the extreme ends of the frame instead of experienced with the solenoid valves, and rugged and also more accurate than the
at the sides, as in the earlier design. This also to eliminate the mercury relief valve. indicator now used. This operates on the
construction permits easier cleaning of the The arrangement of the carbon-dioxide thermal-conductivity principle, as does the
cooler tubes than with the former arrange equipment shown in figure 1 is similar to present indicator, but uses alternating in
ment. that used with the machines now in service, stead of direct current, thus eliminating the
The arrangement of the gas control sys and includes heating equipment which per need for the storage battery and rectifier.
tem shown in the above figure is appreci mits the carbon dioxide to be admitted to The horizontal arrangement of shaft-
ably simpler than the arrangement formerly the generator casing as a gas. Carbon di sealing equipment shown in figure 1 is being
used. Wherever possible, valves with dia oxide in the liquid form may be used thereby used with a number of generators now under
phragm-packed stems are being used to reducing the time for purging and eliminat construction. This provides greater accessi
reduce the possibilities of leakage. The ing the heating equipment, however, some bility of the parts; however, a vertical ar
solenoid gas-admission and scavenging what more carbon dioxide would be re rangement of the treating tanks has been
valves, used with our present machines, quired. used wherever it was more suited to the
have been replaced in the arrangement station space. The different elements of
shown in figure 1 with diaphragm-type either arrangement may be mounted on a
valves. This was done to avoid the leakage Figure 2 common base and assembled as a unit.