Beruflich Dokumente
Kultur Dokumente
a r t i c l e i n f o a b s t r a c t
Article history: The sizing of radiant ceilings for cooling applications requires the correct evaluation of the dynamic
Received 5 March 2014 removal thermal loads in indoor environments. The evaluation of thermal power removed by convection,
Received in revised form 30 October 2014 infrared radiation and direct absorption of solar radiation incident on ceiling surface, called direct water
Accepted 6 December 2014
load (DWL), for systems with low thermal inertia (chilled ceilings or ceilings made by capillary pipes)
Available online 12 December 2014
has to be carried out. The latter contribution must be evaluated in an accurate way because it is not a
thermal load for indoor environment and strongly modies the thermal balance in the air-conditioned
Keywords:
volume. In order to evaluate DWL, a parametric study developed as a function of the main optical and
Chilled ceilings
Solar heat gains
geometrical characteristics of the cavity has been carried out with TRNSYS code. The development of a
Cooling loads case study has highlighted the dynamic aspects of the several contributions involved in the thermal loads
Buildings dynamic simulation removal. The obtained results have allowed the denition of a new calculation methodology to evaluate
the effective solar radiation absorbed by the cavity and, subsequently, to determine the fraction of solar
radiation incident on ceiling surface and removed by DWL. Its evaluation has allowed estimation of the
DWL incidence on the sizing procedure of light radiant ceiling for cooling applications.
2014 Elsevier B.V. All rights reserved.
1. Introduction their light weight simplies the installation operations and there-
fore allows the system to be less expensive. Moreover, the use of
Radiant ceiling cooling systems are increasingly used since they capillary pipes directly drowned in the ceiling plaster coating leads
give better comfort conditions, owing to their particular ther- to a more uniform surface temperature with consequent benets to
mal exchange, and especially provide thermal energy savings [1]. the radiant thermal exchange and to thermal comfort conditions.
The energy savings can be extended also to the primary energy Finally, a low thermal inertia permits the use of simpler control
sources, because the inlet water temperature of radiant ceilings systems.
are higher than conventional air-conditioning systems. Additional A limitation in the use of radiant ceilings in cooling applications
advantages are the full utilization of spaces and the reduction of is the lack of appropriate sizing procedures and the uncertainty
vertical indoor air temperature stratication. Andrs-Chicote et al. in the determination of their performances when they are cou-
have recently investigated the cooling capacity of radiant ceiling in pled with other air-conditioning plants. Radiant panels, in fact, can
cooling applications by experimental results analysis [2]. Imanari remove only sensible loads, while the control of humidity level
et al. investigated the achievable energy savings and comfort condi- and air cleanliness is assigned to conventional air ventilation sys-
tions obtainable by radiant ceilings in an ofce building, comparing tems. In terms of achievable energy consumptions and thermal
their performances with traditional air-conditioning systems [3]. comfort level, Corgnati et al. have conrmed, with numerical and
The economic analysis developed has highlighted that the payback experimental analysis, the good performance of the radiant ceil-
period of radiant ceiling systems may be advantageous in relation to ing coupled to primary air ventilation systems in ofce buildings
the installation costs. In this context, the use of radiant ceiling with [46]. However the presence of sensible and latent loads delivered
negligible thermal inertia, such as chilled ceilings or capillary pipes by other plants can affect the sizing procedure of radiant ceilings.
radiant systems mounted in the ceiling, is very interesting because In this eld many calculation methodologies are available, but the
majority are steady state models validated for panels with non-
negligible thermal mass.
Corresponding author. Tel.: +39 0984 494158; fax: +39 0984 494673. Diaz and Cuevas, for instance, developed a procedure to evalu-
E-mail address: roberto.bruno@unical.it (R. Bruno). ate the main thermal performances by modelling the radiant ceiling
http://dx.doi.org/10.1016/j.enbuild.2014.12.009
0378-7788/ 2014 Elsevier B.V. All rights reserved.
230 N. Arcuri et al. / Energy and Buildings 88 (2015) 229237
the relation:
4 4
SL = R + C = (Tceil Tmr,cav )
where Tceil is the ceiling temperature, Top the indoor operative air
temperature measured at 1.10 m above the oor level and Tmr,cav
is the mean radiant temperature of the indoor environment evalu-
ated without the ceiling surface. The last two temperatures can be
evaluated by the following relations [12]:
Tia + Tmr
Top = Tia,adj (3)
2
4 4
Tmr,cav = TW,i fic (4)
i
2. Cooling capacity of radiant ceiling with low thermal The trends of the different parameters which participate to the
inertia removal of the thermal load can be determined by the dynamic
simulation code TRNSYS. With reference to the entering solar radi-
The radiant ceiling surface required to deliver cooling loads in ation, the simulation code does not consider the cavity as a black
an air conditioned environment is evaluable starting from its cool- body because, as a result of multiple reections, a part of the solar
ing capacity. In radiant ceilings with negligible thermal inertia, the radiation is reected outside through the same glazed system. To
cooling capacity is represented by CLW and it can be dened as the take into account this phenomenon, an absorption coefcient of
sum of the instantaneous DWL and the surface load SL. The cor- the cavity cav can be introduced. This coefcient is dened as the
respondent heat ux, evaluated with reference to a ceiling surface difference between the solar energy entering through the glazed
area Aceil , is dened as: surfaces with a transmission coefcient and the solar radiation
reected out of the same cavity Qsol,out . The optical component of
CLW = DWL + SL [W m2 ] (1) the transmitted solar radiation can be dened as the product of the
external incident solar radiation Qsol,inc by the coefcient.
In order to improve the radiant ceiling cooling performances,
Qsol,inc Qsol,out Qsol Qsol,out
it is preferable to increase the heat ux extracted by DWL rather cav = = (7)
Qsol,inc Qsol
than the heat ux extracted by SL, since the latter is limited by
the ceiling surface temperature, that it has to be greater than the With reference to the solar radiation incident on the external
indoor air dew point temperature to prevent condensation of water side of a glazed surface, the solar energy balance is shown in Fig. 2.
vapor. The heat ux related to surface load SL is calculated with In the absence of solar radiation intercepted by the window frame
232 N. Arcuri et al. / Energy and Buildings 88 (2015) 229237
= Qsol,inc ( cav + qi qe ) (8) In the simplied approach, the transmitted solar radiation inside
the cavity has been considered uniformly diffuse. In this way the
where Qsol,ass is the effective solar radiation absorbed by cavity, results can be generalized because other parameters such as the
Qsol,inc is the incident solar radiation on external glazed surface, time, the latitude, the exposition, the location of the window and
cav is the absorption coefcient of the indoor environment, is the effective room dimensions are not requested. The adopted
the transmitted solar radiation, the reected solar radiation from hypothesis is respected in the cases of air conditioned environ-
the external glazed surface, qi the fraction of absorbed solar radia- ments equipped with diffusing glass or for overcast sky conditions.
tion from glazed surface transferred to the indoor environment by Furthermore, transmitted solar radiation uniformly diffuse occurs
convection and infrared radiation and qe the fraction of solar radi- with external shading devices, solution widely used in summer to
ation absorbed from glazed surface and emitted towards outdoor. reduce the solar heat gain, without modifying the optical charac-
In the presence of external shading devices, Qsol,inc represents the teristics of the air-conditioning environment.
net diffuse solar radiation which strikes the window. The quantity
Qsol,inc (1 cav ) is the optical component of the solar radiation 4.2. Detailed approach
reected outside by the inner cavity surface; the product cav is
representative of the absorbed solar radiation by the opaque walls. To verify the difference between the results provided by the
To quantify the real solar radiation absorbed by the cavity, the simplied model and a more rigorous procedure, that takes into
following relation can be used [18]: account the real view factors and the real distribution of solar radi-
c ation in the cavity, further simulations in TRNSYS environment
m
cav = 1 a Exp b (9) varying the geometry of the cavity and the mean absorption coef-
cient dened by Eq. (10) have been carried out. The comparison
that, in the absence of inner shading devices, depends on: between the obtained results highlights a maximum deviation of
3% between the F values evaluated by Eq. (14) and the results of
- the average solar absorption coefcient of all opaque surfaces of the detailed model (see Table 1). The detailed model provides an
the cavity. Assuming to separate the contribution of the ceiling augment of the solar radiation absorbed by the ceiling that prevails
from that of the other walls, it can be expressed as: slightly on the simultaneous increase of solar radiation absorbed by
all the opaque walls of the cavity. Furthermore, the results provided
AW,i + ceil Aceil
m = i W,i (10) by the simplied model are always precautionary as they provide
A +
i W,i ceil lower F values than the detailed model. Table 1 lists the values of F,
- the ratio of total glazed surface to total opaque surface in the of the solar radiation absorbed from the ceiling (Qsol,ceil ) and from
indoor environment: the cavities (Qsol,in Qsol,out ) as a function of the mean absorption
coefcient of the cavity m , and in function of the dimensionless
A
j gl,j
= (11) ratio , for both simplied and detailed models. When the real view
A
i W,i
+ Aceil factors have been determined with the detailed model, a position
of the window perfectly centred in the opaque walls has been con-
- diffuse transmission coefcient of the glazed system d , by the
sidered. The type of glazing system has not been varied since it
three coefcients in Eq. (9) obtainable with the following corre-
affects the amount of solar radiation transmitted in the cavity. The
lations:
results of Table 1 refer to the three geometries of an air conditioned
a = 3.500 5.453 d + 4.516 d2 environment assuming an external incident net solar radiation of
b = 3.700 5.388 d + 3.462 d2 (12) 500 W m2 , and a glazed area varying between 4.5 m2 and 18 m2 .
Furthermore, three different optical congurations, obtained vary-
c= 0.124 + 0.545 d 0.355 d2 ing the values of the mean absorption coefcient of the cavity m ,
have been investigated: ceiling absorption coefcient ceil = 0.5 and
4. Evaluation of the direct water load (DWL) walls absorption coefcient w = 0.2, w = ceil = 0.3 and, nally,
w = ceil = 0.7. The rst value of the mean absorption coefcient
A part of the terms cav in Eq. (8) is instantly absorbed of the cavity, although lower than the other, allows to obtain an
from the ceiling and it represents the DWL. Therefore a correct higher value of the fraction F, because the more limited values of the
N. Arcuri et al. / Energy and Buildings 88 (2015) 229237 233
Table 1
Values of solar fraction F absorbed by the radiant ceiling, solar radiation absorbed by the chilled ceiling and solar radiation reected outside in detailed and simplied model,
varying the optical and geometrical cavity parameters.
Simplied Detailed F []
Fig. 3. Trend of the effective fraction F of solar radiation absorbed by the radiant ceil- To highlight the removal of the thermal load in an air condi-
ing varying the geometry of the cavity and the ratio . Average absorption coefcient tioned environment cooled by a radiant ceiling with low thermal
of the opaque walls m of 0.3. inertia, a reference room with particular geometrical and opti-
cal characteristics has been considered. The indoor environment
is equipped with an only dispersing wall with a double glass
absorption coefcient of the other walls allows to reect a greater window west-facing ( d = 0.59). Different values of solar absorp-
amount of solar radiation on the ceiling. In this optical congura- tion coefcients for oor, vertical walls and ceiling have been
tion, an absorbed solar radiation removed directly by DWL greater considered, ranging from 0.20 (white smooth plaster) to 0.80
than 50% has been determined (detailed model). It is interesting to (dark grey rough paint) [22]. To evaluate the inuence of the
observe, moreover, that for a xed geometry the gap between the total glazed surface to total opaque surface ratio, three different
fractions F calculated with the simplied and the detailed model geometries of the reference room have been considered vary-
decreases with the augment of the glazed surface. For indoor envi- ing the depth of the cavity with constant height and width. In
ronments with large glazed surface and with the same values of particular, depth values of 3 m, 6 m and 9 m have been inves-
the mean absorption coefcient, the gap between of the fraction F tigated. The suspended metallic chilled ceiling has a specic
is less than 0.5% for reective environments, and in any case less cooling capacity of 85 W m2 and it is supplied by a network of
than 1% for absorbent environments. Fig. 3 illustrates the trend of pipes located on the top side and connected in parallel, shown
F for the considered reference rooms, varying the ratio and for a in Fig. 4. To improve the radiant thermal exchange and ther-
xed mean absorption coefcient m = 0.3. mal comfort conditions, the whole ceiling surface was used [3].
Fig. 3 suggests that a smaller ceiling surface, results in a more The inlet temperature of the water ow rate has been dynam-
limited gap between fractions F calculated with the simplied and ically varied using an appropriate control strategy to regulate
234 N. Arcuri et al. / Energy and Buildings 88 (2015) 229237
Fig. 5. Trend of the parameters cav , F*, F and (1 F) as a function of the chilled
ceiling solar absorption coefcient. Reference room with depth of 6 m, glazed surface
of 9 m2 and w = 0.2.
Fig. 6. Hourly trend of the average thermal heat uxes involved in the indoor envi-
ronment on a clear day in July in Cosenza. Cavity with = 0.1 and chilled ceiling
Table 2 with ceil = 0.20.
Values of the main parameters for the analyzed cases.
Table 3
Indirect thermal exchange coefcient qi and direct transmission coefcient for beam
solar radiation b,n for different glazed systems.
importance of considering the optical and geometrical character- radiation is directly and entirely absorbed by the chilled ceiling
istics of the cavity in the evaluation of the chilled ceiling thermal assuming, for example, a unitary reection coefcient for the
performances. other walls of the cavity. In this manner, the chilled ceiling is
able to remove the endogenous loads and the secondary load
provided by the glazed surface using only SL. Eq. (19), assuming
5. The effect of geometrical and optical characteristics of
an indoor set point temperature of 26 C, allows evaluation of
the cavity in sizing procedure
the required ceiling surface temperature:
Qsol + Qin
Tceil = 26 (22)
h Aceil
that represents the required temperature to extract the thermal
loads assuming a zero DWL. Entering in Eq. (22) the value of
cav , to remove the hypothesis of black cavity to the transmitted
solar radiation, and the Qin value obtained by Eq. (21), Eq. (22)
can be rewritten in the following way:
Fig. 8. Hourly trend of the average thermal heat uxes involved in the indoor envi-
cav Qsol
ronment on a clear day in July in Cosenza. Cavity with = 0.047 and chilled ceiling Tceil = Tceil (23)
with ceil = 0.60. h Aceil
236 N. Arcuri et al. / Energy and Buildings 88 (2015) 229237
- sol = 550 W m2 ;
- int,Oc + int,A = 20 W m2 ; (EN ISO 13790)
- qi = 0.068; (EN ISO 410)
- b,n = 0.693
Fig. 9. Ceiling surface temperature trend in function of incident solar radiation on - m = 0.35
external side of the glazed surface.
- = 0.0667
- d = 0.590
where in set conditions, Qsol can be written as: - Tdp = 15.5 C (26 C and 60% respectively for indoor air tempera-
ture and relative humidity)
Qsol = sol Agl b,n (24)
with b,n values listed in Table 3 for three different types of some important considerations can be deduced. Initially apply-
glazed surface. Eq. (23) suggests that, for an internal cavity with ing Eq. (12) the three coefcients for the cav evaluation are
particular optical and geometric characteristics, the required determined:
ceiling surface temperature can be assumed as a linear function
of the incident solar radiation on the external glazed surface - a = 1.855
(Fig. 9), supposing that the liminar heat transfer coefcient, - b = 1.726
with little temperature difference between the ceiling surface - c = 0.322
temperature and the indoor air temperature, is slightly variable
near the value of 10 W m2 K1 [12]. and from Eq. (9) the cav value is evaluated:
Imposing in Eq. (23) the ceiling surface temperature equal to the - cav = 0.902
indoor dew point temperature Tdp , a critical solar heat ux * sol
value, beyond which it is requested to remove the load by DWL, Eq. (21) with a ceiling surface area of 36 m2 and Eq. (24) with a
can be determined: glazed surface of 9 m2 provide:
T )hA
(Tceil dp ceil
sol = (25) - Qin = 1060 W
cav b,n Agl - Qsol = 3430 W
Alternatively, xing the incident solar ux on external glazed
surface, a critical cavity absorption coefcient and a correspondent so, by using of Eqs. (20) and (23), it is possible to obtain:
mean absorption coefcient of the opaque walls, can be evaluate:
= 23 C
- Tceil
T )hA
(Tceil = 14.4 C
cav =
dp ceil
(26) - Tceil
sol b,n Agl
Supposing to verify the capacity of the chilled ceiling by Eq. (26),
from which:
the critical value of cav is:
1/c
ln(1 cav /a)
m = (27) - cav = 0.787
b
Eq. (23) analysis suggests the following cases: and the correspondent value of m is:
if T > Tdp the optical and geometrical characteristics of the cav- - m = 0.135
ceil
ity do not modify the mechanisms of extraction of the thermal
loads, because the chilled ceiling cooling power can be provided The latter value is the requested cavity mean absorption coef-
only by SL. In these circumstances, sol < sol and cav < cav ; cient to remove the thermal loads by using SL only, but it is not
if T < Tdp it is necessary to set a ceiling surface temperature equal to the set value and, moreover, it is not achievable; so, a frac-
ceil
greater than Tdp , for example 1 C to have an appropriate safety tion of solar load extracted by DWL is requested, also because the
is lower than the indoor air dew point tem-
obtained value of Tceil
margin, and use this value in Eq. (18) to determine a new F value.
= 16 C, from Eq. (18) the fraction F of solar
perature. Imposing Tceil
The latter F value is evaluated by using of Eqs. (13) and (14)
with proper value of ceil , imposing an initial m value requested thermal load extracted by DWL can be determined:
for cav evaluation. The ceiling absorption coefcient change
involves a variation also in the absorption coefcients of the other - F = 0.259
N. Arcuri et al. / Energy and Buildings 88 (2015) 229237 237
while, in the hypothesis of black cavity at the entering solar not affected by the entity of the solar load or by the presence of
radiation (Eq. (14)): other delivered thermal loads to the cavity.
The dynamic behaviour of a reference room and the following
- F* = 0.287 parametric study in order to determine the DWL contribution as a
function of the optical and geometrical characteristics of the indoor
Finally, from Eq. (13) the requested value of ceiling absorption environment, have allowed formulation of a calculation procedure
coefcient can be obtained: to determine the real performance of the building-plant system in
cooling applications. The DWL evaluation allows the correct eval-
- ceil = 0.38 uation of SL and the correct size of the cooling machine in the case
of buildings with different thermal zones.
and the other internal walls, to maintain the cavity mean absorp-
tion coefcient of 0.35, the new value of their solar absorption References
coefcient has to be imposed:
[1] Z. Tian, X. Yin, Y. Ding, C. Zhang, Research on the actual cooling performance of
ceiling radiant panel, Energy Build. 47 (2012) 636642.
- W = 0.34 [2] M. Andrs-Chicote, A. Tejero-Gonzales, E. Velasco-Gmez, F.J. Rey-Martnez,
Experimental study on the cooling capacity of a radiant cooled ceiling system,
Energy Build. 54 (2012) 207214.
Concluding, on the whole a thermal load of 4490 W in the cav-
[3] T. Imanari, T. Omori, K. Bogaki, Thermal comfort and energy consumption of the
ity, 1170 W (26%) is absorbed instantly by DWL and the remaining radiant ceiling panel system. Comparison with the conventional all-air system,
3320 W can be extracted later by SL with plausible ceiling surface Energy Build. 30 (1999) 167175.
temperature. [4] S.P. Corgnati, M. Perino, G.V. Fracastoro, P.V. Nielsen, Experimental and numeri-
cal analysis of air and radiant cooling systems in ofces, Energy Build. 44 (2009)
The latter consideration is much important in buildings with 801806.
different thermal zones that exploits chilled ceiling systems: the [5] S.J. Rees, P. Haves, An experimental study of air ow and temperature distri-
cooling machine, in fact, has to be sized as a function of the max- bution in a room with displacement ventilation and a chilled ceiling, Build.
Environ. 59 (2013) 358368.
imum contemporary thermal load, and the presence of DWL can [6] A.H. Taki, L. Jalil, D.L. Loveday, Experimental and computational investigation
affect strongly the machine size and, therefore, the primary energy into suppressing natural convection in chilled ceiling/displacement ventilation
requirements. environments, Energy Build. 43 (2011) 30823089.
[7] N.F. Diaz, C. Cuevas, Testing and thermal modeling of radiant panels systems
as commissioning tool, Energy Convers. Manage. 51 (2010) 26632677.
6. Conclusions [8] M. Tye-Gingras, L. Gosselin, Investigation on heat transfer modeling assump-
tions for radiant panels with serpentine layout, Energy Build. 43 (2011)
15981608.
A correct sizing of chilled ceiling systems must necessarily sep- [9] S. Okamoto, H. Kitora, H. Yamaguchi, T. Oka, A simplied calculation method
arate DWL, provided by solar radiation and by articial lighting for estimating heat ux from ceiling radiant panels, Energy Build. 42 (2010)
2933.
plants, from SL, representing the thermal load extracted by liminar
[10] J.W. Weong, S.A. Mumma, Practical cooling capacity estimation model for
exchange. The DWL evaluation allows evaluation of the real cool- a suspended metal ceiling radiant cooling panel, Energy Environ. 42 (2007)
ing capacity of the radiant panel because it is instantly removed 31763185.
by the cooled surface and it does not become a thermal load for [11] ASHRAE, ASHRAE Systems and Equipment Handbook: Chapter 6 Panel
Heating and Cooling, American Society of Heating, Refrigerating and Air-
the indoor environment. Simulations carried out by TRNSYS code Conditioning Engineers Inc., Atlanta, GA, 2004, pp. 6.16.22.
have highlighted that the DWL contribution is determined by the [12] F. Causone, S.P. Corgnati, M. Filippi, B.W. Olesen, Experimental evaluation of
cavity dimensions, the absorption coefcients of the opaque walls heat transfer coefcients between radiant ceiling and room, Energy Build. 41
(2009) 622628.
and by the percentage of glazed surface. The correct evaluation [13] M. De Carli, M. Tonon, Effect of modelling solar radiation on the cooling per-
of DWL requires the calculation of the effective solar radiation formance of radiant oors, Solar Energy 85 (2011) 689712.
absorbed by the cavity by using the absorption coefcient cav . [14] M. De Carli, M. Scarpa, R. Tomasi, A. Zarrella, DIGITHON: a numerical model for
the thermal balance of rooms equipped with radiant systems, Build. Environ.
The latter coefcient, supposing that the entering solar radiation 57 (2012) 126144.
is uniformly diffused, is function of the cavity mean absorption [15] G. Oliveti, N. Arcuri, R. Bruno, Resa termica di softti radianti che impiegano tubi
coefcient, of the ratio between the global glazed surface to the capillari per il riscaldamento e il raffrescamento degli ambienti, in: Proceedings
of the 62 Italian Congress ATI (Italian Thermotechnic Association), Cuzzolin
global opaque surface and of the diffuse coefcient transmission Editore Naples, Vol. I, 2007, pp. 119123.
of the glass. The analysis highlighted that the augment of the [16] AA.VV., TRNSYS vs. 17, A Transient Simulation Program, Solar Energy Labora-
ceiling solar absorption coefcient and the reduction of the ver- tory, University of Wisconsin, Madison, USA.
[17] M.S. Owen (Ed.), Handbook of Fundamentals, ASHRAE, Atlanta, USA, 2013.
tical wall absorption coefcient allow an increase in the fraction
[18] G. Oliveti, N. Arcuri, R. Bruno, M. De Simon, An accurate calculation model of
of DWL, with a consequent reduction of the thermal load in the solar heat gain through glazed surfaces, Energy Build. 43 (2011) 269274.
cavity. [19] F. Causone, S.P. Corgnati, M. Filippi, B.W. Olesen, Solar radiation and cooling
The cooling capacity of the chilled ceiling, per surface unit, is the load calculation for radiant systems: denition and evaluation of the direct
solar load, Energy Build. 42 (2010) 305314.
sum of DWL/Aceil and SL/Aceil but the latter contribution is limited [20] S.P. Corgnati, G.V. Fracastoro, M. Perino, Un metodo di calcolo per il dimension-
by the ceiling surface temperature to prevent water vapor conden- amento dei softti radianti per il raffrescamento estivo, AICARR J. CDA 7 (2000)
sation phenomena; therefore, a high value of DWL is preferable. 731742 (Italian Association for Heating and Air-conditioning Applications).
[21] F. Causone, S.P. Corgnati, M. Filippi, Metodo di calcolo basato sul direct water
High DWL values allow one to obtain a further margin of cooling load per la climatizzazione estiva con pannelli radianti, in: Proceedings of the
power to deliver for the extraction of other convective or radiative 62 Italian Congress ATI (Italian Thermotechnic Association), Cuzzolin Editore
thermal loads. Naples, Vol. I, 2007, pp. 175179.
[22] G. Oliveti, N. Arcuri, R. Bruno, M. De Simone, L. Marletta, G. Evola, Solar energy,
The development of a case study considering a clear day high- in: A. Magrini (Ed.), Building Refurbishment for Energy Performance, Springer
lighted that the maximum value of DWL is in phase with the solar International Publishing, Switzerland, 2014.
load, while the maximum value of SL is delayed and attenuated as a [23] ISO 13790:2008, Energy performance of buildings calculation of energy use
for space heating and cooling.
function of the thermal inertia of the cavity. This behaviour is more [24] ISO 9050:2003, Glass in building determination of light transmittance, solar
accentuated by using a chilled ceiling with high solar absorption direct transmittance, total solar energy transmittance, ultraviolet transmit-
coefcient. The procedure is generalizable because the results are tance and related glazing factors.