Products.................................................................................................................................................................... 5
Slim 1 way cassette................................................................................................................................................ 8
1-1. Specifications......................................................................................................................................................................8
1-2. Dimensional drawing.........................................................................................................................................................9
1-3. Electrical wiring diagram.................................................................................................................................................10
1-4. Sound pressure level.......................................................................................................................................................11
1-5. Temperature and air flow distribution...........................................................................................................................12
Mini 4 way cassette.............................................................................................................................................. 13
2-1. Specifications....................................................................................................................................................................13
2-2. Dimensional drawing.......................................................................................................................................................14
2-3. Electrical wiring diagram.................................................................................................................................................15
2-4. Sound pressure level.......................................................................................................................................................16
2-5. Temperature and air flow distribution.............................................................................................................................17
4 way cassette....................................................................................................................................................... 19
3-1. Specifications....................................................................................................................................................................19
3-2. Dimensional drawing.......................................................................................................................................................21
3-3. Electrical wiring diagram..................................................................................................................................................22
3-4. Sound pressure level.......................................................................................................................................................23
3-5. Temperature and air flow distribution...........................................................................................................................24
Slim duct................................................................................................................................................................ 33
4-1. Specifications....................................................................................................................................................................33
4-2. Dimensional drawing.......................................................................................................................................................35
4-3. Electrical wiring diagram.................................................................................................................................................38
4-4. Sound pressure level.......................................................................................................................................................40
4-5. Recommended operation range....................................................................................................................................42
2 VRF-PRC006-EN
MSP (Middle static pressure) duct..................................................................................................................... 44
5-1. Specifications....................................................................................................................................................................44
5-2. Dimensional drawing.......................................................................................................................................................46
5-3. Dimensional drawing.......................................................................................................................................................48
5-4. Electrical wiring diagram.................................................................................................................................................49
5-5. Sound pressure level.......................................................................................................................................................50
5-6. Recommended operation range....................................................................................................................................52
HSP (High static pressure) duct.......................................................................................................................... 53
6-1. Specifications....................................................................................................................................................................53
Indoor units
6-2. Dimensional drawing.......................................................................................................................................................54
6-3. Electrical wiring diagram.................................................................................................................................................56
6-4. Sound pressure level.......................................................................................................................................................57
6-5. Recommended operation range....................................................................................................................................58
Ceiling Suspended (Floor)................................................................................................................................... 59
7-1. Specifications....................................................................................................................................................................59
7-2. Dimensional drawing.......................................................................................................................................................60
7-3. Electrical wiring diagram.................................................................................................................................................61
7-4. Sound pressure level.......................................................................................................................................................62
7-5. Temperature and air flow distribution...........................................................................................................................63
High Wall................................................................................................................................................................ 65
8-1. Specifications....................................................................................................................................................................65
8-2. Dimensional drawing.......................................................................................................................................................67
8-3. Electrical wiring diagram.................................................................................................................................................69
8-4. Sound pressure level.......................................................................................................................................................70
8-5. Temperature and air flow distribution...........................................................................................................................72
EEV Kit Application Table.................................................................................................................................... 74
VRF-PRC006-EN 3
Nomenclature
Indoor Units
Nomenclature
4 T V D 0 0 1 8 B 1 0 0 N B
1 2 3 4 5 6 7 8 9 10 11 12 13 14
Digit 1 Refrigerant Digit 5 Reserved for Future Digit 11 Reserved for Future
4 = R-410a Use Use
Digit 2 Brand Name 0 = Not currently used 0 = Not currently used
T = Trane Digit 6, 7, 8 Nominal Capacity Digit 12 Reserved for Future
Digit 3 System Type (Btu/h x 1,000) Use
V = Variable Refrigerant Flow 007= 7,000 Btu/h 0 = Not currently used
009= 9,000 Btu/h
Digit 4 Configuration Type 012= 12,000 Btu/h
Digit 13 Region of Sale
A = High Pressure Static Duct Type 015= 15,000 Btu/h N = North America (UL or ETL)
B = Mini 4-Way Cassette 018= 18,000 Btu/h Digit 14 Minor Design
C = 4-Way Cassette 024= 24,000 Btu/h
030= 30,000 Btu/h
Sequence
D = Mid Pressure Static Duct Type
E = 1-Way Cassette 036= 36,000 Btu/h B = Second Design Sequence
L = Slim Duct Type (Low Pressure) 048= 48,000 Btu/h
X = Convertible Floor/Ceiling 076= 76,000 Btu/h
W = High Wall Type 096= 96,000 Btu/h
Digit 9 Major Development
Sequence
B = Second Development Sequence
Digit 10 Electric Power
Supply Characteristics
1 = 208~230/60/1
VRF-PRC008-EN 5
4 VRF-PRC006-EN
VRF-PRC008-EN.book Page 6 Thursday, August 15, 2013 4:08 PM
1 Products
Products
Application Matrix
Capacity
7.5MBH 9.0MBH 9.5MBH 12MBH 18MBH 20MBH 24MBH 30MBH 36MBH 48MBH 76.8MBH 96MBH
Type
Slim
1 way
cassette
Indoor units
4 way
cassette
Mini 4
way
cassette
Slim
duct
MSP
duct
HSP
duct
Ceiling
High Wall
6 VRF-PRC008-EN
VRF-PRC006-EN 5
Products
Products
Controls
VRF-PRC008-EN 7
6 VRF-PRC006-EN
Products
Accessories
Indoor units
VRF Y-joint 240-336MBh 4YDK3419B0336A
VRF Y-joint 336-468MBh 4YDK4119B0468A
VRF Y-joint >468MBh 4YDK4422B0999A
VRF Y-joint HR 80MBh 4YDK1500B0080A
Y-joint VRF Y-joint HR 80-240MBh 4YDK2500B0240A
(High Pressure Gas for
HR) VRF Y-joint HR 240-468MBh 4YDK3100B0468A
VRF Y-joint HR >468MBh 4YDK3800B0999A
8 VRF-PRC008-EN
VRF-PRC006-EN 7
1 Slim 1 way cassette
1-1. Specifications
Technical specifications
Drain Pipe inch VP 20 (OD 1", ID 3/4") VP 20 (OD 1", ID 3/4") VP 20 (OD 1", ID 3/4")
Shipping Dimensions (Wxhxd) inches 43 7/8 x 8 3/8 x 15 13/16 43 7/8 x 8 3/8 x 15 13/16 43 7/8 x 8 3/8 x 15 13/16
Net Dimensions (Wxhxd) inches 46 1/2 x 1.0 x 18 1/8 46 1/2 x 1.0 x 18 1/8 46 1/2 x 1.0 x 18 1/8
Shipping Dimensions (Wxhxd) inches 49 5/8 x 5 11/16 x 21.25 49 5/8 x 5 11/16 x 21.25 49 5/8 x 5 11/16 x 21.25
Max. Lifting
Drain Pump inches 29.5 29.5 29.5
Additional Features Height
1. Nominal capacity based on 25 ft. of equivalent refrigerant piping with 0 ft. level difference.
- Cooling: Indoor temperature 80F DB, 67F WB/Outdoor temperature 95F DB, 75F WB
- Heating: Indoor temperature 70F DB, 60F WB/Outdoor temperature 47F DB, 43F WB
2. Sound pressure was acquired in a dead room. Actual noise level may be different depending on installation conditions.
3. Cassette panel must be ordered separately
4. Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.
8 VRF-PRC006-EN
1-2. Dimensional drawing
Unit: mm(inch)
410(16-1/8)
280(11)
Indoor units
970(38-1/4)
1036(40-3/4)
135(5-3/8)
150(5-7/8)
85(3-3/8)
119(4-5/8)
52(2-1/16)
25(1)
3 2 1
6
1180(46-1/2)
863(34) 5
94(3-3/4)
460(18-1/8)
197(7-3/4)
861(33-7/8)
Description
No. Name
7.5 MBH 9.5 MBH 12.0 MBH
1 Liquid pipe connection 6.35(1/4") Flare
2 Gas pipe connection 12.70(1/2") Flare
3 Drain pipe connection VP20 (OD 26, ID 20) / VP20 (OD 1", ID 3/4")
4 Conduit for power supply & communication wiring -
5 Air inlet grille -
6 Air outlet louver -
VRF-PRC006-EN 9
1 Slim 1 way cassette
1-3. Electrical wiring diagram
10 VRF-PRC006-EN
1-4. Sound pressure level
Operation sound level Unit : dB(A)
1m 4TVE0009B100NB 29 24
4TVE0012B100NB 35 27
Microphone
Note
Indoor units
These operation values were obtained in an anechoic room. Sound pressure level will vary depending on a range of
factors such as the construction of the particular room where the equipment is installed.
Operation sound level may differ depending on operation and ambient conditions.
2) NC curves
(1) 4TVE0007B100NB (2) 4TVE0009B100NB
45 45
NC 45 NC 45
40 40
NC 40 NC 40
Sound pressure level (dB)
35 35
HIGH
NC 35 NC 35
HIGH
30 30
NC 30 NC 30
25 25
LOW
LOW
20 NC 25 20 NC 25
15 NC 20 15 NC 20
10 NC 15 10 NC 15
5 5
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
(3) 4TVE0012B100NB
45
NC 45
40
HIGH
NC 40
Sound pressure level (dB)
35
NC 35
30 LOW
NC 30
25
20 NC 25
15 NC 20
10 NC 15
0
63 125 250 500 1000 2000 4000 8000
VRF-PRC006-EN 11
1 Slim 1 way cassette
1-5. Temperature and air flow distribution
4TVE0007-0012B100NB
(1) Cooling air velocity distribution Discharge angle : 60
3m
(9.8 ft)
1.0m/s
Ceiling height
(3.28ft/s)
2m
(6.6 ft)
1m
0.8m/s 0.2m/s (3.3 ft)
(2.62ft/s) (0.66ft/s)
0.2m/s
(0.66ft/s)
0.6m/s 0.6m/s
(1.97ft/s) (1.97ft/s)
0m 1m 2m 3m 4m 5m 6m 7m 8m
(0 ft) (3.3 ft) (6.6 ft) (9.8 ft) (13.1 ft) (16.4 ft) (19.7 ft) (23.0 ft) (26.2 ft)
Floor distance
22 25
(71.6F) (77.0F) 2m
(6.6 ft)
25
(77.0F)
1m
23
(3.3 ft)
(73.4F)
24
24 23 (75.2F)
(75.2F) (73.4F)
0m 1m 2m 3m 4m 5m 6m 7m 8m
(0 ft) (3.3 ft) (6.6 ft) (9.8 ft) (13.1 ft) (16.4 ft) (19.7 ft) (23.0 ft) (26.2 ft)
Floor distance
2m
(6.6 ft)
0.6m/s
(1.97ft/s)
0.4m/s
1m
(1.31ft/s) (3.3 ft)
0.2m/s
(0.66ft/s)
0m 1m 2m 3m 4m 5m 6m 7m 8m
(0 ft) (3.3 ft) (6.6 ft) (9.8 ft) (13.1 ft) (16.4 ft) (19.7 ft) (23.0 ft) (26.2 ft)
Floor distance
33
(91.4F)
2m
(6.6 ft)
23 31
(73.4F) (87.8F) 27 25
(80.6F) (77.0F)
1m
(3.3 ft)
21
(69.8F)
0m 1m 2m 3m 4m 5m 6m 7m 8m
(0 ft) (3.3 ft) (6.6 ft) (9.8 ft) (13.1 ft) (16.4 ft) (19.7 ft) (23.0 ft) (26.2 ft)
Floor distance
12 VRF-PRC006-EN
12 Mini 4 way cassette
2-1. Specifications
Technical specifications
Model Name 4TVB0009B100NB 4TVB0012B100NB 4TVB0018B100NB 4TVB0020B100NB
Indoor units
Heating 0.17 0.19 0.27 0.30
Type (Qty.) - Turbo Fan Turbo Fan Turbo Fan Turbo Fan
Motor
Output (Each) W 65 x 1 65 x 1 65 x 1 65 x 1
Fan Airflow Rate H/M/L Cfm 350/300/265 370/335/280 460/390/335 475/425/360
External Static
Min/Std/Max In. WG - - - -
Pressure
Shipping Dimensions (WxHxD) inches 24 1/2 x 11 3/4 x 22 3/4 24 1/2 x 11 3/4 x 22 3/4 24 1/2 x 11 3/4 x 22 3/4 24 1/2 x 11 3/4 x 22 3/4
Net Dimensions (WxHxD) inches 26 3/8 X 1 3/4 X 26 3/8 26 3/8 X 1 3/4 X 26 3/8 26 3/8 X 1 3/4 X 26 3/8 26 3/8 X 1 3/4 X 26 3/8
Shipping Dimensions (WxHxD) inches 28 1/8 X 4 3/16 X 28 1/2 28 1/8 X 4 3/16 X 28 1/2 28 1/8 X 4 3/16 X 28 1/2 28 1/8 X 4 3/16 X 28 1/2
Drain Pump Max. Lifting Height inches 29.5 29.5 29.5 29.5
Additional
Displacement Gal/Hr. 6.25 6.25 6.25 6.25
Features
Air Filter - Washable Filter Washable Filter Washable Filter Washable Filter
1. Nominal capacity based on 25 ft. of equivalent refrigerant piping with 0 ft. level difference.
- Cooling: Indoor temperature 80F DB, 67F WB/Outdoor temperature 95F DB, 75F WB
- Heating: Indoor temperature 70F DB, 60F WB/Outdoor temperature 47F DB, 43F WB
2. Sound pressure was acquired in a dead room. Actual noise level may be different depending on installation conditions.
3. Cassette panel must be ordered separately
4. Motion sensor must be ordered separately
5. Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.
VRF-PRC006-EN 13
2 Mini 4 way cassette
2-2. Dimensional drawing
Unit: mm(inch)
43(1.7)
250(9.8)
295(11.6)
225(8.9)
195(7.7)
176(6.9)
131(5.2)
40(1.6)
7 165(6.5)
249(9.8)
269(10.6)
670(26.4)
381(15) 5
57(2.2)
6
670(26.4)
381(15)
300(11.8)
150(5.9)
120(4.7)
Description
No. Name
9.5 MBH 12.0 MBH 18.0 MBH 20.0 MBH
1 Liquid pipe connection 6.35(1/4") Flare
2 Gas pipe connection 12.70(1/2") Flare
3 Drain pipe connection VP25 (OD 32, ID 25)/VP25 (OD 1 1/4", ID 1")
4 Conduit for power supply & communication wiring -
5 Air inlet grille -
6 Air outlet louver -
7 Fresh air intake 100(3.9")
14 VRF-PRC006-EN
2-3. Electrical wiring diagram
Indoor units
VRF-PRC006-EN 15
2 Mini 4 way cassette
2-4. Sound pressure level
Operation sound level
Unit : dB(A)
Model High Low
4TVB0009B100NB 34 26
4TVB0012B100NB 36 31
1.5m 4TVB0018B100NB 40 34
Microphone 4TVB0020B100NB 41 35
Note
These operation values were obtained in an anechoic room. Sound pressure level will vary depending on a range of
factors such as the construction of the particular room where the equipment is installed.
Operation sound level may differ depending on operation and ambient conditions.
2) NC curves
(1) 4TVB0009B100NB (2) 4TVB0012B100NB
60 60
50 50
Sound pressure level (dB)
NC 45 NC 45
40 40 HIGH
NC 40 Mid NC 40
HIGH LOW
NC 35 NC 35
30 Mid 30
LOW NC 30 NC 30
20 NC 25 20 NC 25
NC 20 NC 20
10 NC 15 10 NC 15
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
60 60
50 50
Sound pressure level (dB)
HIGH HIGH
Mid Mid
NC 45 NC 45
40 LOW
40 LOW
NC 40 NC 40
NC 35 NC 35
30 30
NC 30 NC 30
20 NC 25 20 NC 25
NC 20 NC 20
10 NC 15 10 NC 15
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
16 VRF-PRC006-EN
2-5. Temperature and air flow distribution
4TVB0009-0012B100NB
(1) Cooling air velocity distribution Discharge angle : 37
3m
(9.8 ft)
0.6m/s 0.6m/s
(1.97ft/s) (1.97ft/s)
Ceiling height
2m
(6.6 ft)
0.4m/s
(1.31ft/s)
0.4m/s
(1.31ft/s)
1m
(3.3 ft)
Indoor units
0.2m/s 0.2m/s
(0.66ft/s) (0.66ft/s)
21 21
Ceiling height
(69.8F) (69.8F)
24 2m
24 (75.2F)
(75.2F) 22 22 (6.6 ft)
(71.6F) (71.6F)
23 23
(73.4F) (73.4F) 1m
24 (3.3 ft)
(75.2F)
0.8m/s 2m
0.8m/s
(2.62ft/s) (2.62ft/s) (6.6 ft)
0.6m/s
0.6m/s (1.97ft/s)
(1.97ft/s) 0.4m/s
(1.31ft/s) 0.4m/s
(1.31ft/s)
0.2m/s
(0.66ft/s) 1m
0.2m/s
(0.66ft/s) (3.3 ft)
31
(87.8F)
Ceiling height
31
(87.8F) 2m
25
(77.0F) 29
(6.6 ft)
29
(84.2F) (84.2F)
27 27
(80.6F) (80.6F)
23
1m
(73.4F) (3.3 ft)
21
(69.8F)
VRF-PRC006-EN 17
2 Mini 4 way cassette
4TVB0018-0020B100NB
(1) Cooling air velocity distribution Discharge angle : 37
3m
(9.8 ft)
0.8m/s 0.8m/s
(2.62ft/s) (2.62ft/s)
Ceiling height
0.6m/s 0.6m/s 2m
(1.97ft/s) (1.97ft/s) (6.6 ft)
0.4m/s
1m
0.4m/s
(1.31ft/s) (1.31ft/s) (3.3 ft)
0.2m/s 0.2m/s
(0.66ft/s) (0.66ft/s)
2m
23
(73.4F)
23
(73.4F)
(6.6 ft)
24
(75.2F) 24
(75.2F)
24
1m
(75.2F) (3.3 ft)
0.8m/s 0.8m/s
Ceiling height
(2.62ft/s) 0.4m/s
(1.31ft/s)
(2.62ft/s) 2m
(6.6 ft)
0.6m/s 0.6m/s
(1.97ft/s) (1.97ft/s)
0.2m/s 1m
(0.66ft/s)
(3.3 ft)
31
(87.8F) 31 2m
29
(87.8F)
29 (6.6 ft)
(84.2F) (84.2F) 27
(80.6F)
25
27 (77.0F)
(80.6F) 1m
(3.3 ft)
23
(73.4F)
21
(69.8F)
18 VRF-PRC006-EN
13 4 way cassette
3-1. Specifications
Technical specifications
Model Name 4TVC0009B100NB 4TVC0018B100NB 4TVC0024B100NB
Indoor units
Heating 0.25 0.25 0.30
External Static
Min/Std/Max In. WG - - -
Pressure
Drain Pipe inch VP 25 (OD 1 1/4", ID 1") VP 25 (OD 1 1/4", ID 1") VP 25 (OD 1 1/4", ID 1")
Shipping Dimensions (WxHxD) inches 35 3/8 x 10 7/8 x 35 3/8 35 3/8 x 10 7/8 x 35 3/8 35 3/8 x 10 7/8 x 35 3/8
Net Dimensions (WxHxD) inches 37 7/16 x 1 3/4 x 37 7/16 37 7/16 x 1 3/4 x 37 7/16 37 7/16 x 1 3/4 x 37 7/16
Shipping Dimensions (WxHxD) inches 39 9/16 x 4 x 39 9/16 39 9/16 x 4 x 39 9/16 39 9/16 x 4 x 39 9/16
1. Nominal capacity based on 25 ft. of equivalent refrigerant piping with 0 ft. level difference.
- Cooling: Indoor temperature 80F DB, 67F WB/Outdoor temperature 95F DB, 75F WB
- Heating: Indoor temperature 70F DB, 60F WB/Outdoor temperature 47F DB, 43F WB
2. Sound pressure was acquired in a dead room. Actual noise level may be different depending on installation conditions.
3. Cassette panel must be ordered separately
4. Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.
VRF-PRC006-EN 19
3 4 way cassette
Technical specifications
Model Name 4TVC0030B100NB 4TVC0036B100NB 4TVC0048B100NB
External Static
Min/Std/Max In. WG - - -
Pressure
Drain Pipe inch VP 25 (OD 1 1/4", ID 1") VP 25 (OD 1 1/4", ID 1") VP 25 (OD 1 1/4", ID 1")
Shipping Dimensions (WxHxD) inches 35 3/8 x 14 x 35 3/8 35 3/8 x 14 x 35 3/8 35 3/8 x 14 x 35 3/8
Net Dimensions (WxHxD) inches 37 7/16 x 1 3/4 x 37 7/16 37 7/16 x 1 3/4 x 37 7/16 37 7/16 x 1 3/4 x 37 7/16
Shipping Dimensions (WxHxD) inches 39 9/16 x 4 x 39 9/16 39 9/16 x 4 x 39 9/16 39 9/16 x 4 x 39 9/16
1. Nominal capacity based on 25 ft. of equivalent refrigerant piping with 0 ft. level difference.
- Cooling: Indoor temperature 80F DB, 67F WB/Outdoor temperature 95F DB, 75F WB
- Heating: Indoor temperature 70F DB, 60F WB/Outdoor temperature 47F DB, 43F WB
2. Sound pressure was acquired in a dead room. Actual noise level may be different depending on installation conditions.
3. Cassette panel must be ordered separately
4. Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.
20 VRF-PRC006-EN
3-2. Dimensional drawing
Unit: mm(inch)
6
890~910(35~35.8) Celling opening
950(37.4) 735(28.9) Suspension position
Indoor units
950(37.4)
6 5 3 2 1
B A
216(8.5)
164(6.5)
86(3.4)
45(1.8)
330(13) 240(9.4)
Sub duct connection 270(10.6) 4
7 300(11.8)
4(0.2)-3.3(0.1) 80(3.1)
195(7.7)
Description
No. Name
9MBH 18MBH 24MBH 30MBH 36MBH 48MBH
1 Liquid pipe connection 6.35(1/4") Flare 9.52(3/8") Flare
2 Gas pipe connection 12.70(1/2") Flare 15.88(5/8") Flare
3 Drain pipe connection VP25 (OD 32, ID 25)/VP25 (OD 1 1/4", ID 1")
4 Conduit for power supply & communication wiring -
5 Air inlet grille -
6 Air outlet louver -
7 Sub-Duct -
Description
9/18/24 MBH 30/36/48 MBH
A mm(inch) 204(8.0) 288(11.3)
B mm(inch) 253(10.0) 337(13.3)
VRF-PRC006-EN 21
3 4 way cassette
3-3. Electrical wiring diagram
22 VRF-PRC006-EN
3-4. Sound pressure level
Operation sound level
Unit: dB(A)
Model High Low
4TVC0009B100NB 34 31
4TVC0018B100NB 34 31
4TVC0024B100NB 36 34
1.5m 4TVC0030B100NB 39 30
Microphone 4TVC0036B100NB 40 33
4TVC0048B100NB 44 39
Note
Indoor units
These operation values were obtained in an anechoic room. Sound pressure level will vary depending on a
range of factors such as the construction of the particular room where the equipment is installed.
Operation sound level may differ depending on operation and ambient conditions.
NC curves
(1) 4TVC0009B100NB (2) 4TVC0018B100NB (3) 4TVC0024B100NB
60 60 60
Sound pressure level (dB)
NC 45 NC 45 NC 45
40 40 40 HIGH
HIGH HIGH
NC 40 NC 40 NC 40
LOW
LOW NC 35 LOW NC 35 NC 35
30 30 30
NC 30 NC 30 NC 30
20 NC 25 20 NC 25 20 NC 25
NC 20 NC 20 NC 20
10 NC 15 10 NC 15 10 NC 15
0 0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave band center frequency(Hz) Octave band center frequency(Hz) Octave band center frequency(Hz)
50 50 50 HIGH
HIGH
NC 45 NC 45 LOW NC 45
40 40 HIGH 40
LOW
NC 40 NC 40 NC 40
NC 35 LOW NC 35 NC 35
30 30 30
NC 30 NC 30 NC 30
20 NC 25 20 NC 25 20 NC 25
NC 20 NC 20 NC 20
10 NC 15 10 NC 15 10 NC 15
0 0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave band center frequency(Hz) Octave band center frequency(Hz) Octave band center frequency(Hz)
VRF-PRC006-EN 23
3 4 way cassette
3-5. Temperature and air flow distribution
4TVC0009B100NB
(1) Cooling air velocity distribution Discharge angle :
YU^
O_U`P
0.8m/s 0.9m/s
(2.62ft/s)
0.2m/s (2.95ft/s)
(0.66ft/s) 0.7m/s
(2.30ft/s)
0.1m/s
0.6m/s (0.33ft/s) Y
O]U]P
(1.97ft/s)
0.5m/s
(1.64ft/s)
X
0.4m/s OZUZP
(1.31ft/s) 0.1m/s
(0.33ft/s)
0.3m/s
0.1m/s
0.2m/s (0.98ft/s)
0.3m/s (0.33ft/s)
(0.66ft/s)
(0.98ft/s)
YU\ Y X X Y YU\
O_UYP O]U]P OZUZP OZUZP O]U]P O_UYP
YU^
O_U`P
23
23 17 (73.4)
(73.4 ) (62.6)
17.5
(63.5)
18 22 Y
(64.4) (71.6) O]U]P
18.5
(65.3)
22
(71.6) 22
21.5 (71.6)
X
(70.7 ) 19.5 OZUZP
(67.1)
21
21 (69.8)
(69.8)
20.5
(68.9 )
20.5
(68.9)
YU\ Y X X Y YU\
O_UYP O]U]P OZUZP OZUZP O]U]P O_UYP
24 VRF-PRC006-EN
4TVC0009B100NB
(3) Heating air velocity distribution Discharge angle :
YU^
O_U`P
1.3m/s
0.14m/s (4.27fit/s)
(0.46fit/s) 1.1m/s
(3.61fit/s) 0.28m/s 1m/s
(0.92fit/s) (3.28fit/s) Y
0.85m/s O]U]P
(2.79fit/s)
0.7m/s
Indoor units
(2.30fit/s) 0.14m/s
(0.46fit/s)
0.14m/s
0.57m/s (0.46fit/s)
(1.87fit/s)
0.42m/s
(1.38fit/s)
X
OZUZP
0.28m/s
(0.92fit/s)
0.14m/s
(0.46fit/s)
0.14m/s
(1.31fit/s)
YU\ Y X X Y YU\
O_UYP O]U]P OZUZP OZUZP O]U]P O_UYP
YU^
O_U`P
28.5
(83.3)29.4 29.4
(84.9)
35.5 (84.9)
34.5 (95.9)
(94.1)
33.6
(92.5)
Y
O]U]P
32.8
(91.8)
32
30 29.4 (89.6)
(86) 30 (84.9)
(86)
31 28.5
(83.3)
(87.8)
32 32 X
(89.6) (89.6) OZUZP
27.6
(81.7)
26.7
(80.1)
YU\ Y X X Y YU\
O_UYP O]U]P OZUZP OZUZP O]U]P O_UYP
VRF-PRC006-EN 25
3 4 way cassette
4TVC0018B100NB
(1) Cooling air velocity distribution
YU^
O_U`P
0.3m/s 1m/s
(0.98fit/s)
(3.98fit/s)
0.9m/s
(2.95fit/s) 0.2m/s
(0.66fit/s) 0.7m/s
(2.30fit/s)
Y
0.6m/s 0.1m/s O]U]P
(1.97fit/s) 0.33fit/s)
0.1m/s
0.5m/s (0.33fit/s)
(1.64fit/s)
X
OZUZP
0.3m/s
0.2m/s (0.98fit/s)
0.2m/s
(0.66fit/s) 0.1m/s 0.1m/s (0.66fit/s)
(0.33fit/s) (0.33fit/s)
YU^\ Y X X Y YU^\
17
17.5
(62.6) 24
(63.6) 23 (75.2)
(73.4) 18
23 (64.4)
(73.4) 18.5 Y
O]U]P
(65.3)
22
(71.6)
19.5
(67.1) 22
(71.6)
21.5
(70.7)
X
OZUZP
21 21
(69.8) (69.8)
20.5 20.5
(68.9) (68.9)
YU^\ Y X X Y YU^\
26 VRF-PRC006-EN
4TVC0018B100NB
(3) Heating air velocity distribution Discharge angle :
YU^
0.14m/s O_U`P
(0.46fit/s)
0.14m/s
(0.46fit/s) 0.42m/s
1.6m/s
(5..25fit/s)
(1.38fit/s) 1.4m/s 0.14m/s
0.14m/s 0.28m/s (4.59fit/s)
(0.46fit/s)
(0.92fit/s)
(0.46fit/s) 1.1m/s
(3.61fit/s)
Y
1m/s O]U]P
Indoor units
0.14m/s (3.28fit/s)
(0.46fit/s)
0.85m/s
(2.79fit/s) 0.28m/s
(0.92fit/s)
0.28m/s
(0.92fit/s)
0.7m/s
(2.30fit/s)
0.57m/s 0.42m/s X
(1.87fit/s) (1.38fit/s)
OZUZP
0.28m/s
(0.92fit/s)
0.14m/s
0.14m/s (0.46fit/s)
(0.46fit/s)
YU^\ Y X X Y YU^\
YU^
O_U`P
40.6
(105.1)
35.3 35.3
(95.5)
(95.5 ) Y
39.8 34.6 O]U]P
(103.6)
(94.3)
36.8
(98.2)
39 36.1
(102.2 )
38.3 33.8 (97.0 )
(100.9) (92.8)
37.6
(99.7 )
X
39 OZUZP
(102.2)
33
(91.4)
32.3
30.7 31.5 (90.1) 30.7
(87.3) (87.3 )
(88.7)
30 30
YU^\ (86)Y X X Y (86 ) YU^\
VRF-PRC006-EN 27
3 4 way cassette
4TVC0024B100NB
(1) Cooling air velocity distribution
YU^
O_U`P
0.9m/s 1m//s
(2.95fit/s) (3.28fit/s)
Y
0.8m/s O]U]P
0.7m/s (2.62fit/s)
(2.30fit/s)
0.5m/s
(1.64fit/s)
X
0.1m/s 0.2m/s OZUZP
(0.33fit/s) (0.66fit/s)
0.1m/s
0.2m/s (0.33fit/s)
(0.66fit/s)
0.3m/s 0.3m/s
(0.98fit/s) (0.98fit/s)
ZUX Z Y X X Y Z ZUX
YU^
O_U`P
24
(75.2)
17.5
(63.5) 23
18 (73.4)
(64.4) Y
18.5 O]U]P
(65.3)
22
(71.6)
22 19
(71.6)
(66.2)
21
(69.8) X
OZUZP
20
(68) 21
21
(69.8) 20
(68)
ZUX Z Y X X Y Z ZUX
28 VRF-PRC006-EN
4TVC0024B100NB
(3) Heating air velocity distribution Discharge angle :
YU^
0.28m/s 0.28m/s
O_U`P
(0.92fit/s)
(0.92fit/s)
0.14m/s 0.42m/s 0.14m/s
(0.46fit/s) (0.46fit/s)
(1.38fit/s)
0.28m/s 1.4m/s
(4.59fit/s)
(0.92fit/s)
1.3m/s Y
(4.27fit/s) O]U]P
1.1m/s
Indoor units
0.14m/s
(0.46fit/s) (3.61fit/s) 0.14m/s
(0.46fit/s)
1m/s
(3.28fit/s)
0.28m/s 0.85m/s
(0.92fit/s) (2.79fit/s)
0.7m/s X
(2.30fit/s) OZUZP
0.57m/s
(1.87fit/s)
0.42m/s
(1.38fit/s)
0.14m/s 0.14m/s
(0.46fit/s)
(0.46fit/s)
ZUX Z Y X X Y Z ZUX
YU^
O_U`P
34.5 34.5
(94.1) 42
41.5 33.7 (107.6)
(94.1)
(106.7) 40.8
(92.7) (105.4)
33.7 33.7
(92.7) (92.7)
40 Y
(104) O]U]P
34.5 34.5
(94.1)
(94.1)
39.3
(102.7)
33 33 35.3
35.3 (91.4) (91.4) (95.5)
(95.5)
38.5 X
(101.3) OZUZP
32.3 32.3
(90.1) (90.1)
31.6 31.6
(88.9) (88.9)
30.8 30.8
(87.4) (87.9)
ZUX Z
30
Y X Y Z ZUX
VRF-PRC006-EN 29
3 4 way cassette
4TVC0030B100NB
(1) Cooling air velocity distribution
Discharge angle : 45
2.7m
0.6m/s
(8.9 ft)
0.4m/s 0.4m/s
(1.31ft/s) (1.97ft/s) (1.31ft/s)
0.8m/s 0.2m/s 0.6m/s
(2.62ft/s) (0.66ft/s) (1.97ft/s)
Ceiling heigt
0.2m/s
2m
(0.66ft/s) (6.6 ft)
0.2m/s 0.2m/s
(0.66ft/s) (0.66ft/s) 0.2m/s
0.2m/s (0.66ft/s)
(0.66ft/s)
0.6m/s 1m
(1.97ft/s)
0.6m/s
(3.3 ft)
(1.97ft/s) 0.2m/s
0.2m/s (0.66ft/s)
0.2m/s
0.4m/s 0.2m/s (0.66ft/s) (0.66ft/s) 0.4m/s
(1.31ft/s) (0.66ft/s) (1.31ft/s)
4m 3m 2m 1m 0m 1m 2m 3m 4m
(13.1 ft) (9.8 ft) (6.6 ft) (3.3 ft) (0 ft) (3.3 ft) (6.6 ft) (9.8 ft) (13.1 ft)
Floor distance
(71.6F) 2m
(6.6 ft)
20
(68.0F)
22
22 (71.6F) 20
(68.0F)
(71.6F) 1m
22
(71.6F) (3.3 ft)
22 22
22 (71.6F) 21
(71.6F) (71.6F) (69.8F)
21 21
(69.8F) (69.8F)
4m 3m 2m 1m 0m 1m 2m 3m 4m
(13.1 ft) (9.8 ft) (6.6 ft) (3.3 ft) (0 ft) (3.3 ft) (6.6 ft) (9.8 ft) (13.1 ft)
Floor distance
(1.31ft/s)
0.6m/s 2m
0.4m/s (1.97ft/s)
(1.31ft/s) (6.6 ft)
0.4m/s 0.2m/s
(1.31ft/s) (0.66ft/s)
0.4m/s 0.2m/s
(1.31ft/s) (0.66ft/s) 1m
(3.3 ft)
4m 3m 2m 1m 0m 1m 2m 3m 4m
(13.1 ft) (9.8 ft) (6.6 ft) (3.3 ft) (0 ft) (3.3 ft) (6.6 ft) (9.8 ft) (13.1 ft)
Floor distance
(87.8F)
2m
30
31
(87.8F) (86F) (6.6 ft)
26
26 (78.8F)
(78.8F) 25
31 (77.0F)
27 (87.8F)
(80.6F) 24 1m
(75.2F) (3.3 ft)
23
(73.4F)
21 22 22 21 21
(69.8F) (71.6F) (71.6F) (69.8F) (69.8F)
4m 3m 2m 1m 0m 1m 2m 3m 4m
(13.1 ft) (9.8 ft) (6.6 ft) (3.3 ft) (0 ft) (3.3 ft) (6.6 ft) (9.8 ft) (13.1 ft)
Floor distance
30 VRF-PRC006-EN
4TVC0036B100NB
(1) Cooling air velocity distribution
Discharge angle : 45
1.0m/s
2.7m
(3.28ft/s) (8.9 ft)
0.4m/s
(1.31ft/s) 0.4m/s 1.0m/s
(1.31ft/s) (3.28ft/s)
0.2m/s 2m
(6.6 ft)
Ceiling heigt
(0.66ft/s)
1.2m/s 0.2m/s 0.4m/s
0.4m/s (3.94ft/s) (0.66ft/s) (1.31ft/s)
(1.31ft/s) 1.2m/s
(3.94ft/s)
0.6m/s 0.6m/s
1.0m/s
(1.97ft/s)
(3.28ft/s) (1.97ft/s) 1m
0.6m/s
0.2m/s (3.3 ft)
(0.66ft/s) 0.2m/s
(1.97ft/s)
(0.66ft/s)
Indoor units
0.2m/s 0.6m/s
(0.66ft/s) 0.2m/s 0.4m/s
0.6m/s 0.2m/s (1.31ft/s) (1.97ft/s)
(1.97ft/s) (0.66ft/s) (0.66ft/s)
4m 3m 2m 1m 0m 1m 2m 3m 4m
(13.1 ft) (9.8 ft) (6.6 ft) (3.3 ft) (0 ft) (3.3 ft) (6.6 ft) (9.8 ft) (13.1 ft)
Floor distance
(71.6F) 2m
22 (6.6 ft)
(71.6F)
21
(69.8F)
22
(71.6F) 22
1m
21
(69.8F) 21
(71.6F) (3.3 ft)
(69.8F) 21
22 (69.8F)
21 22 (71.6F) 21
(69.8F) (71.6F) (69.8F)
4m 3m 2m 1m 0m 1m 2m 3m 4m
(13.1 ft) (9.8 ft) (6.6 ft) (3.3 ft) (0 ft) (3.3 ft) (6.6 ft) (9.8 ft) (13.1 ft)
Floor distance
(0.66ft/s)
0.4m/s 1.0m/s 0.4m/s
(1.31ft/s) (3.28ft/s) (1.31ft/s)
0.4m/s
(1.31ft/s) 1.0m/s
1.0m/s (3.28ft/s) 0.4m/s
(3.28ft/s)
0.2m/s
(0.66ft/s)
(1.31ft/s) 1m
(3.3 ft)
0.4m/s
(1.31ft/s)
0.2m/s 0.2m/s
0.2m/s (0.66ft/s) 0.2m/s
(0.66ft/s) (0.66ft/s)
(0.66ft/s)
4m 3m 2m 1m 0m 1m 2m 3m 4m
(13.1 ft) (9.8 ft) (6.6 ft) (3.3 ft) (0 ft) (3.3 ft) (6.6 ft) (9.8 ft) (13.1 ft)
Floor distance
29 27
(84.2F) (80.6F) 2m
(6.6 ft)
Ceiling heigt
33
(91.4F)
26
31
(78.8F) 1m
31 (87.8F) (3.3 ft)
(87.8F) 29 28
25 (84.2F) (82.4F)
25 29 (77.0F)
(84.2F) 25 25
(77.0F) (77.0F) 25
(77.0F) (77.0F)
4m 3m 2m 1m 0m 1m 2m 3m 4m
(13.1 ft) (9.8 ft) (6.6 ft) (3.3 ft) (0 ft) (3.3 ft) (6.6 ft) (9.8 ft) (13.1 ft)
Floor distance
VRF-PRC006-EN 31
3 4 way cassette
4TVC0048B100NB
Cooling air velocity distribution
Discharge angle : 45
2.7m
0.6m/s 0.2m/s (8.9 ft)
0.4m/s (1.97ft/s) (0.66ft/s)
(1.31ft/s) 0.4m/s
(1.31ft/s)
0.2m/s
Ceiling heigt
(0.66ft/s)
0.4m/s 2m
(1.31ft/s)
0.6m/s 1.4m/s
(6.6 ft)
1.4m/s
(1.97ft/s) (4.59ft/s) (4.59ft/s)
1.4m/s 1.2m/s
0.8m/s (4.59ft/s) 0.2m/s (3.94ft/s)
(2.62ft/s) (0.66ft/s) 0.2m/s
(0.66ft/s)
1m
(3.3 ft)
0.2m/s 0.8m/s
0.8m/s 0.2m/s (2.62ft/s)
(2.62ft/s) (0.66ft/s) (0.66ft/s)
0.2m/s 0.2m/s 0.6m/s
(0.66ft/s) (0.66ft/s) (1.97ft/s)
4m 3m 2m 1m 0m 1m 2m 3m 4m
(13.1 ft) (9.8 ft) (6.6 ft) (3.3 ft) (0 ft) (3.3 ft) (6.6 ft) (9.8 ft) (13.1 ft)
Floor distance
21 20
(69.8F) (68.0F)
(69.8F) 2m
(6.6 ft)
20 20
(68.0F) 18.0 (68.0F)
20
(68.0F) 19
(66.2F)
1m
20
(68.0F)
(3.3 ft)
20 20
(68.0F) (68.0F)
20 20
(68.0F) (68.0F)
4m 3m 2m 1m 0m 1m 2m 3m 4m
(13.1 ft) (9.8 ft) (6.6 ft) (3.3 ft) (0 ft) (3.3 ft) (6.6 ft) (9.8 ft) (13.1 ft)
Floor distance
(1.31ft/s)
(0.66ft/s) 0.8m/s 2m
(2.62ft/s)
0.4m/s (6.6 ft)
(1.31ft/s)
0.4m/s 1.2m/s
(1.31ft/s) 0.2m/s 0.2m/s (3.94ft/s)
(0.66ft/s) (0.66ft/s)
0.8m/s
(2.62ft/s) 1m
0.6m/s (3.3 ft)
(1.97ft/s)
0.2m/s
(0.66ft/s) 0.6m/s
0.2m/s 0.2m/s 0.2m/s (1.97ft/s)
(0.66ft/s) (0.66ft/s) (0.66ft/s)
4m 3m 2m 1m 0m 1m 2m 3m 4m
(13.1 ft) (9.8 ft) (6.6 ft) (3.3 ft) (0 ft) (3.3 ft) (6.6 ft) (9.8 ft) (13.1 ft)
Floor distance
31 32
(87.8F) (89.6F)
Ceiling heigt
33
(91.4F)
31
(87.8F)
2m
(6.6 ft)
34
34 (93.2F)
(93.2F)
27
(80.6F)
1m
27
34 29 (80.6F) 34 (3.3 ft)
(93.2F) (93.2F)
(84.2F) 27 33
(80.6F) (91.4F)
27
(80.6F)
4m 3m 2m 1m 0m 1m 2m 3m 4m
(13.1 ft) (9.8 ft) (6.6 ft) (3.3 ft) (0 ft) (3.3 ft) (6.6 ft) (9.8 ft) (13.1 ft)
Floor distance
32 VRF-PRC006-EN
14 Slim duct
4-1. Specifications
Technical specifications
Model Name 4TVL0007B100NB 4TVL0009B100NB 4TVL0012B100NB 4TVL0018B100NB
Indoor units
Heating 0.32 0.40 0.51 0.94
Type (Qty.) - Sirocco Fan Sirocco Fan Sirocco Fan Sirocco Fan
Motor
Output (Each) W 40 x 1 50 x 1 60 x 1 100 x 1
Fan Airflow Rate H/M/L CFM 282/247/212 318/282/247 353/300/247 547/495/441
External Static
Min/Std/Max in. WG 0.00/0.08/0.16 0.00/0.08/0.16 0.00/0.08/0.16 0.00/0.08/0.16
Pressure
Additional Drain Pump3 Max. Lifting Height inches 29.5 29.5 29.5 29.5
Features Displacement Gal/Hr. 6.25 6.25 6.25 6.25
Air Filter - Washable Filter Washable Filter Washable Filter Washable Filter
1. Nominal capacity based on 25 ft. of equivalent refrigerant piping with 0 ft. level difference.
- Cooling: Indoor temperature 80F DB, 67F WB/Outdoor temperature 95F DB, 75F WB
- Heating: Indoor temperature 70F DB, 60F WB/Outdoor temperature 47F DB, 43F WB
2. Sound pressure was acquired in a dead room. Actual noise level may be different depending on installation conditions.
3. Internally installed drain pump must be ordered separately
4. Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.
VRF-PRC006-EN 33
4 Slim duct
Technical specifications
Type (Qty.) - Sirocco Fan Sirocco Fan Sirocco Fan Sirocco Fan
Motor
Output (Each) W 110 x 1 80 x 1 100 x 1 160 x 1
Fan Airflow Rate H/M/L CFM 582/530/477 880/810/705 950/880/810 1,235/1,165/1,060
External Static
Min/Std/Max in. WG 0.00/0.08/0.16 0.00/0.14/0.28 0.00/0.14/0.28 0.00/0.14/0.28
Pressure
Shipping Dimensions (WxHxD) inches 53 3/16 x 11 x 28 62 x 14 9/16 x 32 7/8 62 x 14 9/16 x 32 7/8 62 x 14 9/16 x 32 7/8
Additional Drain Pump3 Max. Lifting Height inches 29.5 29.5 29.5 29.5
Features Displacement Gal/Hr. 6.25 6.25 6.25 6.25
Air Filter - Washable Filter Washable Filter Washable Filter Washable Filter
1. Nominal capacity based on 25 ft. of equivalent refrigerant piping with 0 ft. level difference.
- Cooling: Indoor temperature 80F DB, 67F WB/Outdoor temperature 95F DB, 75F WB
- Heating: Indoor temperature 70F DB, 60F WB/Outdoor temperature 47F DB, 43F WB
2. Sound pressure was acquired in a dead room. Actual noise level may be different depending on installation conditions.
3. Internally installed drain pump must be ordered separately
4. Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.
34 VRF-PRC006-EN
4-2. Dimensional drawing
4TVL0007B1-TVL0012B100NB
Unit : mm(inch)
12(4/8) 3x256(10-1/8)=768(30-1/4)
71(2-3/4) 100(4) 10(3/8)
6
Suction
Indoor units
7
938(36-7/8) 600(23-5/8)
900(35-3/8)
477(18-3/4)
600(23-5/8)
8x100(3-7/8)=800(31-1/2) Suspension bolts(M8~M10) X 4EA
73(2-7/8) 55(2-1/8)
199(7-7/8)
152(6)
100(4)
146(5-3/4)
116(4-5/8)
182(7-1/8)
OD31(1-1/4)
32(1-1/4)
246(9-5/8)
5
333(13-1/8) 3
Description
No. Name
7.5 MBH 9.5 MBH 12.0 MBH
1 Liquid pipe connection 6.35(1/4") Flare
2 Gas pipe connection 12.70(1/2") Flare
3 Drain pipe connection without optional drain pump kits VP25 (OD 32, ID 25) / VP25 (OD 1 1/4", ID 1")
4 Drain pipe connection with optional drain pump kits VP25 (OD 32, ID 25) / VP25 (OD 1 1/4", ID 1")
5 Control unit -
6 Conduit for power supply & communication wiring -
7 Return air side -
8 Air outlet duct flange -
VRF-PRC006-EN 35
4 Slim duct
4TVL0018B1-TVL0024B100NB
Unit : mm(inch)
13(1/2) 3x322(12-5/8)=966(38)
71(2-3/4) 100(4) 10(3/8)
Suction 6
1100(43-1/4) 600(23-5/8)
7
505(19-7/8)
600(23-5/8)
10x100(3-7/8)=1000(39-3/8) Suspension bolts(M8~M10) X 4EA
8 1060(41-3/4)
Duct flange connection bolts(M4) X 26EA
Discharge
18(3/4)
1 2 4
73(2-7/8) 55(2-1/8)
199(7-7/8)
100(4)
152(6)
146(5-3/4)
116(4-5/8)
182(7-1/8)
31(1-1/4)
OD32(1-1/4)
246(9-5/8) 5
3
333(13-1/8)
Description
No. Name
18.0 MBH 24.0 MBH
1 Liquid pipe connection 6.35(1/4") Flare 9.52(3/8") Flare
2 Gas pipe connection 12.70(1/2") Flare 15.88(5/8") Flare
3 Drain pipe connection without optional drain pump kits VP25 (OD 32, ID 25) / VP25 (OD 1 1/4", ID 1")
4 Drain pipe connection with optional drain pump kits VP25 (OD 32, ID 25) / VP25 (OD 1 1/4", ID 1")
5 Control unit -
6 Conduit for power supply & communication wiring -
7 Return air side -
8 Air outlet duct flange -
36 VRF-PRC006-EN
4TVL0030B1-TVL0048B100NB
Unit : mm(inch)
10(3/8)
16(5/8) 4x290(11-3/8)=1160(45-5/8)
88(3-1/2)=
83(3-1/4) 176(6-7/8)
2(1/16)x
Indoor units
Suction 6
1338(52-5/8)
1300(51-1/8) 600(23-5/8)
690(27-1/8)
477(18-3/4)
8
1260(49-5/8) Duct flange connection bolts(M4) X 32EA
Discharge
248(9-3/4) 18(3/4)
1 2 4
73(2-7/8) 55(2-1/8)
2(1/16)x100(4)=200(7-7/8)
295(11-5/8)
146(5-3/4)
116(4-5/8)
182(7-1/8)
OD32(1-1/4)
29(1-1/8)
246(9-5/8) 3 5
333(13-1/8)
Description
No. Name
30.0 MBH 36.0 MBH 48.0 MBH
1 Liquid pipe connection 9.52(3/8") Flare
2 Gas pipe connection 15.88(5/8") Flare
3 Drain pipe connection without optional drain pump kits VP25 (OD 32, ID 25) / VP25 (OD 1 1/4", ID 1")
4 Drain pipe connection with optional drain pump kits VP25 (OD 32, ID 25) / VP25 (OD 1 1/4", ID 1")
5 Control unit -
6 Conduit for power supply & communication wiring -
7 Return air side -
8 Air outlet duct flange -
VRF-PRC006-EN 37
4 Slim duct
4-3. Electrical wiring diagram
4TVL0007B1-TVL0024B100NB
38 VRF-PRC006-EN
4TVL0030B1-TVL0048B100NB
Indoor units
VRF-PRC006-EN 39
4 Slim duct
4-4. Sound pressure level
Operation sound level
Unit : dB(A)
Model High Low Model High Low
4TVL0007B100NB 26 21 4TVL0024B100NB 38 33
4TVL0009B100NB 27 23 4TVL0030B100NB 37 34
4TVL0012B100NB 29 27 4TVL0036B100NB 37 34
4TVL0018B100NB 36 31 4TVL0048B100NB 39 36
Note
These operation values were obtained in an anechoic room. Sound pressure level will vary depending on a
range of factors such as the construction of the particular room where the equipment is installed.
Operation sound level may differ depending on operation and ambient conditions.
2) NC curves
(1) 4TVL0007B100NB (2) 4TVL0009B100NB
45 45
NC 45 NC 45
40 40
NC 40 NC 40
Sound pressure level (dB)
35 HIGH 35 HIGH
NC 35 NC 35
30 30 LOW
LOW
NC 30 NC 30
25 25
20 NC 25 20 NC 25
15 NC 20 15 NC 20
10 NC 15 10 NC 15
5 5
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
45 45
NC 45 NC 45
40 40 HIGH
HIGH
NC 40 LOW NC 40
Sound pressure level (dB)
35 35
LOW NC 35 NC 35
30 30
NC 30 NC 30
25 25
20 NC 25 20 NC 25
15 NC 20 15 NC 20
10 NC 15 10 NC 15
5 5
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
40 VRF-PRC006-EN
NC curves
(5) 4TVL0024B100NB (6) 4TVL0030B100NB
45 45
NC 45 NC 45
40 40
NC 40 NC 40
HIGH
Sound pressure level (dB)
NC 35 NC 35
30 30 LOW
LOW
NC 30 NC 30
25 25
NC 25 NC 25
Indoor units
20 20
15 NC 20 15 NC 20
10 NC 15 10 NC 15
5 5
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
45 45
NC 45 NC 45
40 40
NC 40 HIGH NC 40
Sound pressure level (dB)
35 HIGH 35
NC 35 LOW NC 35
30 LOW
30
NC 30 NC 30
25 25
20 NC 25 20 NC 25
15 NC 20 15 NC 20
10 NC 15 10 NC 15
5 5
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
VRF-PRC006-EN 41
4 Slim duct
4-5. Recommended operation range
Adjust option code according to the actual installation condition (external static pressure).
0 0 0 0 0 0 0 0 0
4 5 6 7 8 9 5 6 7 8 9 10 6 7 8 9 10 11
(141) (177) (212) (247) (282) (318) (177) (212) (247) (282) (318) (353) (212) (247) (282) (318) (353) (388)
Air Flow Rate : CMM(CFM) Air Flow Rate : CMM(CFM) Air Flow Rate : CMM(CFM)
L(23) H(31)
9.8 1.0 0.04
4.9 0.5 0.02 4.9 0.5 0.02
0 0 0 0 0 0 0 0 0
11.5 12.5 13.5 14.5 15.5 16.5 12 13 14 15 16 17 18 19.8 21.4 23 24.6 26.2 27.8 29.4 31 32.6
(406) (441) (477) (512) (547) (582) (424) (459) (494) (530) (565) (600) (635) (699) (755) (812) (868) (925) (981) (1038) (1094) (1151)
Air Flow Rate : CMM(CFM) Air Flow Rate : CMM(CFM) Air Flow Rate : CMM(CFM)
Note
E SP = External Static Pressure
The
graphs display the available external static pressure range of installed indoor units. Therefore, they do not
reflect the actual change of external static pressure and airflow rate according to adjusted airflow (High-Mid-Low) of
installed indoor units.
42 VRF-PRC006-EN
Adjust option code according to the actual installation condition (external static pressure).
Indoor units
L(24) H(34) L(27) H(38)
29.4 3.0 0.12 29.4 3.0 0.12
0 0 0 0 0 0
20 22.5 24 26.5 29 31.5 34 36.5 25.8 27 29.2 31.4 33.6 35.8 38 40.2
(706) (794) (847) (935) (1024) (1112) (1200) (1288) (911) (953) (1031) (1108) (1186) (1264) (1341) (1419)
Air Flow Rate : CMM(CFM) Air Flow Rate : CMM(CFM)
Note
ESP = External Static Pressure
The graphs display the available external static pressure range of installed indoor units. Therefore, they do not
reflect the actual change of external static pressure and airflow rate according to adjusted airflow (High-Mid-Low) of
installed indoor units.
VRF-PRC006-EN 43
5 MSP (Middle static pressure) duct
5-1. Specifications
Technical specifications
Model Name 4TVD0018B100NB 4TVD0024B100NB 4TVD0030B100NB
Shipping Dimensions (WxHxD) inches 46 1/16 x 13 3/8 x 23 7/16 46 1/16 x 13 3/8 x 23 7/16 55 15/16 x 15 3/4 x 23 7/16
Additional Drain Pump3 Max. Lifting Height inches 29.5 29.5 29.5
Features Displacement Gal/Hr. 6.25 6.25 6.25
1. Nominal capacity based on 25 ft. of equivalent refrigerant piping with 0 ft. level difference.
- Cooling: Indoor temperature 80F DB, 67F WB/Outdoor temperature 95F DB, 75F WB
- Heating: Indoor temperature 70F DB, 60F WB/Outdoor temperature 47F DB, 43F WB
2. Sound pressure was acquired in a dead room. Actual noise level may be different depending on installation conditions.
3. Internally installed drain pump must be ordered separately
4. Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.
44 VRF-PRC006-EN
Technical specifications
Model Name 4TVD0036B100NB 4TVD0048B100NB
Indoor units
Heating 1.60 2.45
Shipping Dimensions (WxHxD) inches 55 15/16 x 15 3/4 x 23 7/16 57 5/16 x 17 1/8 x 30 5/8
1. Nominal capacity based on 25 ft. of equivalent refrigerant piping with 0 ft. level difference.
- Cooling: Indoor temperature 80F DB, 67F WB/Outdoor temperature 95F DB, 75F WB
- Heating: Indoor temperature 70F DB, 60F WB/Outdoor temperature 47F DB, 43F WB
2. Sound pressure was acquired in a dead room. Actual noise level may be different depending on installation conditions.
3. Internally installed drain pump must be ordered separately
4. Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.
VRF-PRC006-EN 45
5 MSP (Middle static pressure) duct
5-2. Dimensional drawing
4TVD0018B1-TVD0024B100NB Unit: mm(inch)
77(3) 12(0.5)
117(4.6)
7 6
Suction
397(15.6) Suspension position
480(18.9)
480(18.9)
135(5.3) x 5(0.2) = 675(26.6) 600(23.6)
Discharge
185(7.3)
90(3.5)
260(10.2)
76(3)
4 3 132(5.2)
5 139(5.5)
Description
No. Name
18MBH 24MBH
1 Liquid pipe connection 6.35(1/4") Flare 9.52(3/8") Flare
2 Gas pipe connection 12.70(1/2") Flare 15.88(5/8") Flare
3 Drain pipe connection without optional drain pump kits VP25 (OD 32, ID 25) / VP25 (OD 1 1/4", ID 1")
4 Drain pipe connection with optional drain pump kits VP25 (OD 32, ID 25) / VP25 (OD 1 1/4", ID 1")
5 Control unit -
6 Conduit for power supply & communication wiring -
7 Return air side -
8 Air outlet duct flange -
46 VRF-PRC006-EN
4TVD0030B1-TVD0036B1NB Unit: mm(inch)
Indoor units
7 6
Suction
397(15-5/8) Suspension position
480(18-7/8)
222(8-6/8)
87(3-3/8)
600(23-5/8)
6x135(5-3/8)=810(31-7/8)
902(35-1/2) Air outlet duct flange
Suspension bolts(M8~M10) X 4EA
1150(45-1/4)
1186(46-3/4) Suspension position
Duct flange connection bolts(M4) X 18EA
8 Discharge
Air outlet flange
125(4-7/8)
320(12-5/8)
229(9)
157(6-1/8)
121(4-3/4)
107(4-1/4)
27(1-1/8)
77(3)
5 132(5-1/4)
3 144(5-5/8)
Description
No. Name
30.0 MBH 36.0 MBH
1 Liquid pipe connection 9.52(3/8") Flare
2 Gas pipe connection 15.88(5/8") Flare
3 Drain pipe connection without optional drain pump kits VP25 (OD 32, ID 25) / VP25 (OD 1 1/4", ID 1")
4 Drain pipe connection with optional drain pump kits VP25 (OD 32, ID 25) / VP25 (OD 1 1/4", ID 1")
5 Control unit -
6 Conduit for power supply & communication wiring -
7 Return air side -
8 Air outlet duct flange -
VRF-PRC006-EN 47
5 MSP (Middle static pressure) duct
5-3. Dimensional drawing
4TVD0048B100NB Unit: mm(inch)
6
7 Suction
534(21) Suspension position
650(25-5/8)
86(3-3/8) 222(8-3/4)
6x150(5-7/8)=900(35-3/8)
1000(39-3/8) Air outlet duct flange
1200(47-1/4) Suspension bolts(M8~M10) X 4EA
1236(48-5/8) Suspension position
80(3-1/8)
5 3
170(6-3/4)
244(9-5/8)
299(11-3/4)
Description
No. Name
48.0 MBH
1 Liquid pipe connection 9.52(3/8") Flare
2 Gas pipe connection 15.88(5/8") Flare
3 Drain pipe connection without optional drain pump kits VP25 (OD 32, ID 25) / VP25 (OD 1 1/4", ID 1")
4 Drain pipe connection with optional drain pump kits VP25 (OD 32, ID 25) / VP25 (OD 1 1/4", ID 1")
5 Control unit -
6 Conduit for power supply & communication wiring -
7 Return air side -
8 Air outlet duct flange -
48 VRF-PRC006-EN
5-4. Electrical wiring diagram
Indoor units
VRF-PRC006-EN 49
5 MSP (Middle static pressure) duct
5-5. Sound pressure level
Operation sound level
Unit : dB(A)
Model High Low
4TVD0018B100NB 35 31
4TVD0024B100NB 39 31
4TVD0030B100NB 40 34
4TVD0036B100NB 41 38
4TVD0048B100NB 42 36
Note
These operation values were obtained in an anechoic room. Sound pressure level will vary depending on a range
of factors such as the construction of the particular room where the equipment is installed.
Operation sound level may differ depending on operation and ambient conditions.
2) NC curves
(1) 4TVD0018B100NB (2) 4TVD0024B100NB
45 45
NC 45 NC 45
40 40
NC 40 NC 40
Sound pressure level (dB)
35 35 HIGH
HIGH NC 35 NC 35
30 30
NC 30 LOW NC 30
LOW
25 25
20 NC 25 20 NC 25
15 NC 20 15 NC 20
10 NC 15 10 NC 15
5 5
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
60 60
HIGH
50 50
Sound pressure level (dB)
LOW
NC 45 NC 45
40 40
HIGH NC 40 NC 40
NC 35 NC 35
30 30
NC 30 NC 30
LOW
20 NC 25 20 NC 25
NC 20 NC 20
10 NC 15 10 NC 15
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
50 VRF-PRC006-EN
(5) 4TVD0048B100NB
60
HIGH
50
Sound pressure level (dB)
LOW NC 45
40
NC 40
NC 35
30
NC 30
Indoor units
20 NC 25
NC 20
10 NC 15
0
63 125 250 500 1000 2000 4000 8000
VRF-PRC006-EN 51
5 MSP (Middle static pressure) duct
5-6. Recommended operation range
Adjust option code according to the actual installation condition (external static pressure).
39.2 4.0 L(11.5) H(14.5) 0.16 39.2 4.0 L(15.5) H(18.5) 0.16 98.1 10.0 0.39
19.6 2.0 0.08 19.6 2.0 0.08 78.5 8.0 L(20) H(25) 0.31
78.5 8.0 L(23) H(27) 0.31 78.5 8.0 L(30) H(35) 0.31
Note
ESP = External Static Pressure
The graphs display the available external static pressure range of installed indoor units. Therefore, they do not
reflect the actual change of external static pressure and airflow rate according to adjusted airflow (High-Mid-Low) of
installed indoor units.
52 VRF-PRC006-EN
16 HSP (High static pressure) duct
6-1. Specifications
Technical specifications
Model Name 4TVA0036B100NB 4TVA0048B100NB 4TVA0076B100NB 4TVA0096B100NB
Indoor units
Type (Qty.) - Sirocco Fan Sirocco Fan Sirocco Fan Sirocco Fan
Motor
Output (Each) W 183 x 2 183 x 2 400 x 1 400 x 1
Fan Airflow Rate H/M/L CFM 989/880/777 1,377/1,183/989 2,048/1,835/1,660 2,543/2,295/2,047
Shipping Dimensions 58 1/4 x 16 9/16 x 31 1/8 58 1/4 x 16 9/16 x 31 1/8 59 5/16 x 22 x 45 1/2 59 5/16 x 22 x 45 1/2
inches
(WxHxD)
Air Filter - Washable Filter Washable Filter Washable Filter Washable Filter
1. Nominal capacity based on 25 ft. of equivalent refrigerant piping with 0 ft. level difference.
- Cooling: Indoor temperature 80F DB, 67F WB/Outdoor temperature 95F DB, 75F WB
- Heating: Indoor temperature 70F DB, 60F WB/Outdoor temperature 47F DB, 43F WB
2. Sound pressure was acquired in a dead room. Actual noise level may be different depending on installation conditions.
3. Internally installed drain pump must be ordered separately
4. Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.
VRF-PRC006-EN 53
6 HSP (High static pressure) duct
6-2. Dimensional drawing
4TVA0036B1-TVA0048B100NB Unit : mm(inch)
6
7 Suction
534(21) Suspension position
650(25-5/8)
86(3-3/8) 222(8-3/4)
6x150(5-7/8)=900(35-3/8)
1000(39-3/8) Air outlet duct flange
1200(47-1/4) Suspension bolts(M8~M10) X 4EA
1236(48-5/8) Suspension position
80(3-1/8)
5 3
170(6-3/4)
244(9-5/8)
299(11-3/4)
Description
No. Name
36.0 / 48.0 MBH
1 Liquid pipe connection 9.52(3/8") Flare
2 Gas pipe connection 15.88(5/8") Flare
3 Drain pipe connection without optional drain pump kits VP25 (OD 32, ID 25) / VP25 (OD 1 1/4", ID 1")
4 Drain pipe connection with optional drain pump kits VP25 (OD 32, ID 25) / VP25 (OD 1 1/4", ID 1")
5 Control unit -
6 Conduit for power supply & communication wiring -
7 Return air side -
8 Air outlet duct flange -
54 VRF-PRC006-EN
4TVA0076B1-TVA0096B100NB Unit : mm(inch)
Indoor units
914(36) Suspension position
1040(40.9)
385(15.2)
OD 32(1.3)
35(1.4)
209(8.2)
236(9.3)
Discharge side Suction side 29(1.1)
5 1 2 3 4
VRF-PRC006-EN 55
6 HSP (High static pressure) duct
6-3. Electrical wiring diagram
4TVA0036-0096B100NB
56 VRF-PRC006-EN
6-4. Sound pressure level
Operation sound level
Unit : dB(A)
Model High Low
4TVA0036B100NB 40 37
4TVA0048B100NB 44 40
4TVA0076B100NB 45 41
4TVA0096B100NB 48 43
Indoor units
Note
T
hese operation values were obtained in an anechoic room. Sound pressure level will vary depending on a range
of factors such as the construction of the particular room where the equipment is installed.
O
peration sound level may differ depending on operation and ambient conditions.
NC curves
(1) 4TVA0036B100NB (2) 4TVA0048B100NB
60 60 HIGH
HIGH
LOW
50 LOW
50
Sound pressure level (dB)
NC 45 NC 45
40 40
NC 40 NC 40
NC 35 NC 35
30 30
NC 30 NC 30
20 NC 25 20 NC 25
NC 20 NC 20
10 NC 15 10 NC 15
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
90 90
80 80
Sound pressure level (dB)
70 NC 70 70 NC 70
HIGH
HIGH
60 60
NC 60 NC 60
LOW
LOW
50 50
NC 50 NC 50
40 40
NC 40 NC 40
30 30
NC 30 NC 30
20 20
NC 20 NC 20
10 10
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
VRF-PRC006-EN 57
6 HSP (High static pressure) duct
6-5. Recommended operation range
Adjust option code according to the actual installation condition (external static pressure).
0 0 0 0 0 0 0 0 0
19 21 23 25 27 29 31 33 24 26 28 30 32 34 36 38 40 42 44 44 46 48 50 52 54 56 58 60 62 64
(671) (741) (812) (883) (953) (1024) (1094) (1165) (847) (918) (988) (1059) (1130) (1200) (1271) (1341) (1412) (1483) (1553) (1553)(1624) (1694) (1765) (1836) (1906) (1977) (2047) (2118) (2189) (2259)
Air Flow Rate : CMM(CFM) Air Flow Rate : CMM(CFM) Air Flow Rate : CMM(CFM)
(4) 4TVA0096B100NB
294.2 30.0 1.18
0 0 0
50 54 58 62 66 70 74 76 80
(1765) (1906) (2047) (2189) (2330) (2471) (2612) (2683) (2824)
Air Flow Rate : CMM(CFM)
External Static
Option code
Pressure (in H20)
0.20 011054-195407-231C1C-331110
0.40 011054-195429-231C1C-331110
0.59 011054-19545B-231C1C-331110
0.79 011054-19549E-231C1C-331110
0.98 011054-1955D1-231C1C-331110
1.10 011054-1955F3-231C1C-331110
Note
ESP = External Static Pressure
The graphs display the available external static pressure range of installed indoor units. Therefore, they do not
reflect the actual change of external static pressure and airflow rate according to adjusted airflow (High-Mid-Low) of
installed indoor units.
58 VRF-PRC006-EN
17 Ceiling Suspended (Floor)
7-1. Specifications
Technical specifications
Model Name 4TVX0018B100NB 4TVX0024B100NB
Indoor units
Type (Qty.) - Sirocco Fan Sirocco Fan
Motor
Output (Each) W 25 x 1 35 x 1
Fan
Airflow Rate H/M/L Cfm 495/460/420 635/580/530
Shipping Dimensions (WxHxD) inches 42 1/2 x 28 3/4 x 11 13/16 42 1/2 x 28 3/4 x 11 13/16
1. Nominal capacity based on 25 ft. of equivalent refrigerant piping with 0 ft. level difference.
- Cooling: Indoor temperature 80F DB, 67F WB/Outdoor temperature 95F DB, 75F WB
- Heating: Indoor temperature 70F DB, 60F WB/Outdoor temperature 47F DB, 43F WB
2. Sound pressure was acquired in a dead room. Actual noise level may be different depending on installation conditions.
3. EEV kit to be ordered separately, see application guide on page 74.
4. Condensate pump, if necessary, to be field supplied
5. Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.
VRF-PRC006-EN 59
7 Ceiling Suspended (Floor)
7-2. Dimensional drawing
Unit: mm(inch)
6
1000(39.4)
650(25.6)
253(10)
868(34.2)
200(7.9)
5
3
11(0.4)
22(0
.9)
197(7.8)
2 1
Description
No. Name
18.0 MBH 24.0 MBH
1 Liquid pipe connection 6.35(1/4") Flare 9.52(3/8") Flare
2 Gas pipe connection 12.70(1/2") Flare 15.88(5/8") Flare
3 Drain pipe connection ID18 Hose/ID11/16" Hose
4 Conduit for power supply & communication wiring -
5 Air inlet grille -
6 Air outlet louver -
60 VRF-PRC006-EN
7-3. Electrical wiring diagram
Indoor units
VRF-PRC006-EN 61
7 Ceiling Suspended (Floor)
7-4. Sound pressure level
Operation sound level
Unit : dB(A)
Model High Low
1m 1m 4TVX0018B100NB 40 34
1m
4TVX0024B100NB 44 40
Microphone 1m
Microphone
Note
These operation values were obtained in an anechoic room. Sound pressure level will vary depending on a range
Microphone
of factors such as the construction of the particular room where the equipment is installed.
Operation sound level may differ depending on operation and ambient conditions.
1m
1m
2) NC curves
(1) 4TVX0018B100NB (2) 4TVX0024B100NB
60 60
50 50
Sound pressure level (dB)
NC 45 NC 45
40 40
NC 40 NC 40
HIGH NC 35 HIGH NC 35
30 30
NC 30 NC 30
20 LOW NC 25 20 LOW NC 25
NC 20 NC 20
10 NC 15 10 NC 15
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
62 VRF-PRC006-EN
7-5. Temperature and air flow distribution
4TVX0018-0024B100NB (Floor installation)
(1) Cooling air velocity distribution Discharge angle : 36
3m
(9.8 ft)
0.2m/s
Ceiling height
(0.66ft/s) 2m
(6.6 ft)
0.4m/s
(1.31ft/s)
1m
0.6m/s (3.3 ft)
Indoor units
(1.97ft/s)
0m 1m 2m 3m 4m 5m 6m 7m 8m
(0 ft) (3.3 ft) (6.6 ft) (9.8 ft) (13.1 ft) (16.4 ft) (19.7 ft) (23.0 ft) (26.2 ft)
Floor distance
2m
25 (6.6 ft)
(77.0F)
24
22 23 (75.2F)
(71.6F) (73.4F)
21
24
1m
(69.8F)
(75.2F) (3.3 ft)
25
(77.0F)
0m 1m 2m 3m 4m 5m 6m 7m 8m
(0 ft) (3.3 ft) (6.6 ft) (9.8 ft) (13.1 ft) (16.4 ft) (19.7 ft) (23.0 ft) (26.2 ft)
Floor distance
0.2m/s 2m
(0.66ft/s)
1.2m/s
(6.6 ft)
(3.94ft/s)
1m
(3.3 ft)
0m 1m 2m 3m 4m 5m 6m 7m 8m
(0 ft) (3.3 ft) (6.6 ft) (9.8 ft) (13.1 ft) (16.4 ft) (19.7 ft) (23.0 ft) (26.2 ft)
Floor distance
(84.2F)
2m
27
31
29 (80.6F) (6.6 ft)
(84.2F)
(87.8F)
25
(77.0F)
1m
23
(73.4F) (3.3 ft)
21
(69.8F)
0m 1m 2m 3m 4m 5m 6m 7m 8m
(0 ft) (3.3 ft) (6.6 ft) (9.8 ft) (13.1 ft) (16.4 ft) (19.7 ft) (23.0 ft) (26.2 ft)
Floor distance
VRF-PRC006-EN 63
8 Ceiling Suspended (Floor)
2m
(6.6 ft)
0.2m/s
(0.66ft/s)
1m
0.4m/s
(1.31ft/s)
(3.3 ft)
0.2m/s
(0.66ft/s) 0.6m/s
(1.97ft/s)
0m 1m 2m 3m 4m 5m 6m 7m 8m
(0 ft) (3.3 ft) (6.6 ft) (9.8 ft) (13.1 ft) (16.4 ft) (19.7 ft) (23.0 ft) (26.2 ft)
Floor distance
21
(69.8F)
2m
24 (6.6 ft)
(75.2F)
24
(75.2F)
1m
(3.3 ft)
23 23
(73.4F) (73.4F)
0m 1m 2m 3m 4m 5m 6m 7m 8m
(0 ft) (3.3 ft) (6.6 ft) (9.8 ft) (13.1 ft) (16.4 ft) (19.7 ft) (23.0 ft) (26.2 ft)
Floor distance
0.4m/s 2m
(1.31ft/s)
1.0m/s (6.6 ft)
(3.28ft/s)
0.8m/s
(2.62ft/s)
0.6m/s
0.4m/s
(1.97ft/s)
(1.31ft/s) 1m
(3.3 ft)
0.2m/s
(0.66ft/s)
0m 1m 2m 3m 4m 5m 6m 7m 8m
(0 ft) (3.3 ft) (6.6 ft) (9.8 ft) (13.1 ft) (16.4 ft) (19.7 ft) (23.0 ft) (26.2 ft)
Floor distance
33 2m
(91.4F)
(6.6 ft)
31 25
(87.8F) (77.0F)
27
(80.6F)
1m
23 (3.3 ft)
(73.4F)
21
(69.8F) 21
(69.8F)
0m 1m 2m 3m 4m 5m 6m 7m 8m
(0 ft) (3.3 ft) (6.6 ft) (9.8 ft) (13.1 ft) (16.4 ft) (19.7 ft) (23.0 ft) (26.2 ft)
Floor distance
64 VRF-PRC006-EN
18 High Wall
8-1. Specifications
Technical specifications
Model Name 4TVW0007B100NB 4TVW0009B100NB 4TVW0012B100NB
Indoor units
Type (Qty.) - Crossflow Fan Crossflow Fan Crossflow Fan
Motor
Output (Each) W 23 x 1 23 x 1 23 x 1
Fan Airflow Rate H/M/L Cfm 275/240/200 290/255/215 325/295/255
External Static
Min/Std/Max In. Wg - - -
Pressure
Shipping Dimensions (WxHxD) inches 35 1/2 x 13 7/8 x 10 3/8 35 1/2 x 13 7/8 x 10 3/8 35 1/2 x 13 7/8 x 10 3/8
Additional Features Air Filter - Washable Filter Washable Filter Washable Filter
1. Nominal capacity based on 25 ft. of equivalent refrigerant piping with 0 ft. level difference.
- Cooling: Indoor temperature 80F DB, 67F WB/Outdoor temperature 95F DB, 75F WB
- Heating: Indoor temperature 70F DB, 60F WB/Outdoor temperature 47F DB, 43F WB
2. Sound pressure was acquired in a dead room. Actual noise level may be different depending on installation conditions.
3. EEV kit to be ordered separately, see application guide on page 74.
4. Condensate pump, if necessary, to be field supplied
5. Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.
VRF-PRC006-EN 65
8 High Wall
Technical specifications
Model Name 4TVW0018B100NB 4TVW0020B100NB 4TVW0024B100NB
External Static
Min/Std/Max In. Wg - - -
Pressure
Shipping Dimensions (WxHxD) inches 44 3/4 x 14 7/8 x 11 7/8 44 3/4 x 14 7/8 x 11 7/8 44 3/4 x 14 7/8 x 11 7/8
Additional Features Air Filter - Washable Filter Washable Filter Washable Filter
1. Nominal capacity based on 25 ft. of equivalent refrigerant piping with 0 ft. level difference.
- Cooling: Indoor temperature 80F DB, 67F WB/Outdoor temperature 95F DB, 75F WB
- Heating: Indoor temperature 70F DB, 60F WB/Outdoor temperature 47F DB, 43F WB
2. Sound pressure was acquired in a dead room. Actual noise level may be different depending on installation conditions.
3. EEV kit to be ordered separately, see application guide on page 74.
4. Condensate pump, if necessary, to be field supplied
5. Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.
66 VRF-PRC006-EN
8-2. Dimensional drawing
4TVW0007-0012B100NB Unit:mm(inch)
Indoor units
5
285(11-1/4)
6
825(32-1/2) 189(7 1/2)
1 3
2
Description
No. Name
7.5 MBH 9.5 MBH 12.0 MBH
1 Liquid pipe connection 6.35 (1/4") Flare
2 Gas pipe connection 12.70 (1/2") Flare
3 Drain pipe connection ID 18 hose / ID 11/16" hose
4 Conduit for power supply & communication wiring -
5 Air inlet grille -
6 Air outlet louver -
VRF-PRC006-EN 67
8 High Wall
298(11-3/4)
1065(41-7/8) 6 218(8-5/8)
3
2 1
Description
No. Name
18.0 MBH 20.0 MBH 23.2 MBH
1 Liquid pipe connection 6.35 (1/4") Flare 9.52 (3/8") Flare
2 Gas pipe connection 12.70 (1/2") Flare 15.88 (5/8") Flare
3 Drain pipe connection ID 18 hose / ID 11/16" hose
4 Conduit for power supply & communication wiring -
5 Air inlet grille -
6 Air outlet louver -
68 VRF-PRC006-EN
8-3. Electrical wiring diagram
Indoor units
VRF-PRC006-EN 69
8 High Wall
8-4. Sound pressure level
Operation sound level
Unit : dB(A)
Note
These operation values were obtained in an anechoic room. Sound pressure level will vary depending on a range
of factors such as the construction of the particular room where the equipment is installed.
Operation sound level may differ depending on operation and ambient conditions.
NC curves
(1) 4TVW0007B100NB (2) 4TVW0009B100NB
45 45
NC 45 NC 45
40 40
NC 40 NC 40
Sound pressure level (dB)
35 35
HIGH NC 35 HIGH NC 35
30 30
LOW LOW
NC 30 NC 30
25 25
20 NC 25 20 NC 25
15 NC 20 15 NC 20
10 NC 15 10 NC 15
5 5
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
45 60
NC 45
40
50 HIGH
HIGH NC 40
Sound pressure level (dB)
35
LOW NC 35 NC 45
30 40 LOW
NC 40
NC 30
25
NC 35
30
20 NC 25 NC 30
15 NC 20 NC 25
20
NC 20
10 NC 15
10 NC 15
5
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
70 VRF-PRC006-EN
NC curves
(5) 4TVW0020B100NB (6) 4TVW0024B100NB
60
55
50 HIGH HIGH
Sound pressure level (dB)
NC 35 35 NC 35
30
Indoor units
NC 30 NC 30
NC 25 25 NC 25
20
NC 20 NC 20
10 NC 15 15 NC 15
0 5
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
VRF-PRC006-EN 71
8 High Wall
8-5. Temperature and air flow distribution
4TVW0007-0012B100NB
(1) Cooling air velocity distribution Discharge angle : 60
3m
(9.8 ft)
Ceiling height
2m
(6.6 ft)
1.4m/s
(4.59ft/s)
1m
1.2m/s
(3.94ft/s) (3.3 ft)
0.2m/s 1.0m/s
(0.66ft/s) (3.28ft/s) 0.6m/s 0.4m/s 0.2m/s
(1.97ft/s) (1.31ft/s) (0.66ft/s)
0.8m/s
0.6m/s (2.62ft/s)
(1.97ft/s)
0m 1m 2m 3m 4m 5m 6m 7m 8m
(0 ft) (3.3 ft) (6.6 ft) (9.8 ft) (13.1 ft) (16.4 ft) (19.7 ft) (23.0 ft) (26.2 ft)
Floor distance
2m
(6.6 ft)
26
23 (78.8F)
(73.4F)
1m
(3.3 ft)
25
24 (77.0F)
25 (75.2F)
(77.0F)
0m 1m 2m 3m 4m 5m 6m 7m 8m
(0 ft) (3.3 ft) (6.6 ft) (9.8 ft) (13.1 ft) (16.4 ft) (19.7 ft) (23.0 ft) (26.2 ft)
Floor distance
0.4m/s
(1.31ft/s) 2m
(6.6 ft)
1.8m/s
(5.90ft/s)
0.2m/s
1.2m/s
(3.94ft/s) 0.4m/s
(0.66ft/s) 1m
1.0m/s 0.6m/s
(1.97ft/s)
(1.31ft/s) (3.3 ft)
(3.28ft/s)
0.8m/s
(2.62ft/s)
0m 1m 2m 3m 4m 5m 6m 7m 8m
(0 ft) (3.3 ft) (6.6 ft) (9.8 ft) (13.1 ft) (16.4 ft) (19.7 ft) (23.0 ft) (26.2 ft)
Floor distance
2m
25
(77.0F)
(6.6 ft)
23
25 (73.4F)
27 (77.0F)
31
(87.8F)
(80.6F) 1m
21
(69.8F)
(3.3 ft)
29
(84.2F)
0m 1m 2m 3m 4m 5m 6m 7m 8m
(0 ft) (3.3 ft) (6.6 ft) (9.8 ft) (13.1 ft) (16.4 ft) (19.7 ft) (23.0 ft) (26.2 ft)
Floor distance
72 VRF-PRC006-EN
4TVW0018-0024B100NB
(1) Cooling air velocity distribution Discharge angle : 60
3m
(9.8 ft)
Ceiling height
2m
(6.6 ft)
1.4m/s
(4.59ft/s)
1m
1.2m/s (3.3 ft)
Indoor units
(3.94ft/s)
0.4m/s
1.0m/s 0.8m/s (1.31ft/s)
(3.28ft/s) (2.62ft/s) 0.6m/s
(1.97ft/s)
0m 1m 2m 3m 4m 5m 6m 7m 8m
(0 ft) (3.3 ft) (6.6 ft) (9.8 ft) (13.1 ft) (16.4 ft) (19.7 ft) (23.0 ft) (26.2 ft)
Floor distance
25
(77.0F)
Ceiling height
2m
24
(75.2F) (6.6 ft)
23
(73.4F)
1m
22
(71.6F) (3.3 ft)
23 22
(73.4F) (71.6F)
0m 1m 2m 3m 4m 5m 6m 7m 8m
(0 ft) (3.3 ft) (6.6 ft) (9.8 ft) (13.1 ft) (16.4 ft) (19.7 ft) (23.0 ft) (26.2 ft)
Floor distance
(1.97ft/s) 2m
(6.6 ft)
1.2m/s 1m
(3.94ft/s)
1.0m/s
0.2m/s
(0.66ft/s)
(3.3 ft)
(3.28ft/s)
0.8m/s
(2.62ft/s)
0m 1m 2m 3m 4m 5m 6m 7m 8m
(0 ft) (3.3 ft) (6.6 ft) (9.8 ft) (13.1 ft) (16.4 ft) (19.7 ft) (23.0 ft) (26.2 ft)
Floor distance
27
2m
(80.6F) (6.6 ft)
27
(80.6F)
1m
25 (3.3 ft)
29 (77.0F)
(84.2F)
29 31 23
(84.2F) (87.8F) (73.4F)
0m 1m 2m 3m 4m 5m 6m 7m 8m
(0 ft) (3.3 ft) (6.6 ft) (9.8 ft) (13.1 ft) (16.4 ft) (19.7 ft) (23.0 ft) (26.2 ft)
Floor distance
VRF-PRC006-EN 73
EEV Kit Application Table
Indoor unit type and combinations
4TVW0018B100NB
4TVW0020B100NB
4TVW0007B100NB
4TVW0024B100NB
EEV KIT 4TVW0009B100NB
4TVW0012B100NB
4TVX0018B100NB
4TVX0024B100NB
4EEVEVA24SA000 Any 1 N/A
Single room application
4EEVEVA32SA000 N/A Any 1
4EEVXDA24K132A Any 1 Plus Any 1
Note: Cassette and concealed (fan coil) type indoor units come with a factory installed and cannot be installed with the above
EEV kits.
74 VRF-PRC006-EN
Variable Refrigerant Flow (VRF) Multi-Split AC and HP
AHRI Standard 1230
Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in
creating and sustaining safe, comfortable and energy efficient environments, Trane offers a broad portfolio of advanced
controls and HVAC systems, comprehensive building services, and parts. For more information, visit www.Trane.com.
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.