Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1 Issued: 2016-05-20
Revision: A
ABB 3
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
U12
REG615 INTERCONNECTION PROTECTION RELAY STANDARD
CONFIGURATION
A
94/86 94/86
Time
Authorization
A
O
- Time synchronization: IEEE 1588 v2,
R
L
U12 0. 0 kV
P 0.00 kW
2 3
Q 0.00 kVAr
IL2 0 A
SNTP, IRIG-B
I2> 3Ith>F ARC - User management
46 49F 50L/50NL I ESC Clear
- Web HMI
3 AND
Io
O R
L OR
18
MAP SYNC PQUUB
MAP 25 PQVUB
2RTD
1mA
REMARKS
GUID-608806E0-EC45-49E7-BBBB-3FD20DD5D84C V1 EN
4 ABB
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
94/86 94/86
Authorization
A
- Self-supervision
Master Trip O
- Time synchronization: IEEE 1588 v2,
R
L
U12 0. 0 kV
P 0.00 kW
2 2 2
U/f> 3U< U2> U1< PQM3I PQM3U PQMU
24 27 47O- 47U+ PQM3I PQM3V PQMV
2 6
3U> f>/f<, PQUUB
df/dt
59 PQVUB
81
18
MAP
MAP
2RTD
1mA
Uo REMARKS
GUID-1536B574-54F9-4C47-BD65-175410DFEE46 V2 EN
ABB 5
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
U12
REG615 GENERATOR PROTECTION RELAY STANDARD
CONFIGURATION
D
94/86 94/86
Time
Authorization
Master Trip O
- Time synchronization: IEEE 1588 v2,
R
L
U12 0. 0 kV
P 0.00 kW
IL2 0 A
SNTP, IRIG-B
94/86 - User management
I ESC Clear
- Web HMI
AND
O R
L OR
Io
2
Io> Io>>
67N-1 67N-2
REMARKS
GUID-309F67A9-5199-4215-95A7-7703EE262635 V2 EN
Generator protection with generator differential and directional overcurrent protection and synchro-check D
6 ABB
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
ABB 7
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
8 ABB
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
3. Protection functions and when to disconnect from the grid. The voltage vector shift
The generator protection relay offers protection functionality for protection detects islanding from the grid by measuring
synchronous generators and their prime mover against internal continuously the duration of the voltage cycle and it can be
faults and abnormal conditions of external systems. The main further secured with the provided frequency and voltage based
feature in the standard configuration D is the differential protection. Standard configuration A additionally offers
protection. The main feature in the standard configuration C is directional overcurrent protection, directional earth-fault
the 3rd harmonic-based stator earth-fault protection protection and reverse power and directional overpower
completing the detection coverage with the other earth-fault protection.
protection provided. The generator protection relay also
features reverse power and directional overpower protection The RTD/mA inputs are offered as an option for the default
against delivering excessive power beyond the generator's configuration. They can be used with Multipurpose protection
capacity and against the generator running like a motor. The function for tripping and alarm purposes. Multipurpose
underpower protection protects generators and prime movers protection function uses RTD/mA measuring data or analog
against the effects of very low power outputs. A dedicated values via GOOSE messages.
protection function detects any loss of synchronism (out-of-
Enhanced with optional hardware and software, the relay also
step condition) between the generator and the rest of the power
features three light detection channels for arc fault protection of
system. The generator relay also includes back-up overcurrent
the circuit breaker, busbar and cable compartment of metal-
protection featuring voltage dependent overcurrent and, in the
enclosed indoor switchgear.
standard configuration D, directional overcurrent protection
and, in the standard configuration C, underimpedance The arc-fault protection sensor interface is available on the
protection. Overexcitation protection (U/f) protects the optional communication module. Fast tripping increases staff
generators against excessive flux density. Underexcitation (X<) safety and security and limits material damage in an arc fault
protects the synchronous machine against the underexcitation situation. A binary input and output module can be selected as
or loss of excitation condition. Frequency and voltage based an option - having three high speed binary outputs (HSO) it
protection, thermal overload and unbalance protection are also further decreases the total operate time with typically 4...6 ms
included in both standard configurations C and D intended for compared to the normal power outputs.
generator protection.
The relay for the interconnection point of the power grid and 4. Application
distributed power generation is provided with the standard Standard configuration A is intended to be used in the common
configuration A where the main features are low-voltage ride- point of coupling distributed power generation into the utility
through protection, directional reactive power undervoltage network. It ensures the grid stability and reliability according to
protection (QU) and the voltage vector shift protection. The given grid codes and by determining whether and when to
main features of the interconnection relay can be used to disconnect according to defined settings. A typical application
support utility grid stability and to detect islanding. The example of the distributed power generation is a wind power
protection allows the monitoring of distributed generation plant or a solar power plant but it can also be a combined heat
during low-voltage or fault ride through to determine whether and power or hydroelectric power plant.
ABB 9
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
REG615
3I
Std. conf. A
3U ANSI IEC
25 SYNC
27RT U<RT
Io 32Q, 27 Q>, 3U<
32R/32O P>/Q>
47O-/59 U2>/3U>
47U+/27 U1</3U<
50L/50NL ARC
60 FUSEF
78V VS
81 f</f>, df/dt
G G G G G G
GUID-FC594C90-D99A-4D1B-89FE-089A640794E4 V1 EN
Figure 4. Application example of wind power plant as distributed power generation coupled into the utility network
Standard configuration A is not designed for using all the the Application Configuration tool. In order to ensure the
available functionality content in one relay at the same time. performance of the relay, the user specific configuration load is
Directional earth-fault protection functions must be added with verified with the Application Configuration tool in PCM600.
10 ABB
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
REG615
3I
Std. conf. A
3U ANSI IEC
25 SYNC
27RT U<RT
Io 32Q, 27 Q>, 3U<
32R/32O P>/Q>
47O-/59 U2>/3U>
47U+/27 U1</3U<
50L/50NL ARC
60 FUSEF
78V VS
81 f</f>, df/dt
GUID-B99D5D42-A515-43E9-8F1C-74131A760E33 V1 EN
Figure 5. Application example of combined heat and power/hydro power plant as distributed power generation coupled into the utility network
Standard configurations C and D are intended to be used in independent and redundant protection system can be a
synchronous power generator application where the protection requirement or the protection system as a whole may require
coverage is a generator, field excitation system and primary more than one protection relay in one set-up. Various
mover. A typical application example is parallel connected recognized earthing principles exist and typically earthing
diesel or gas generators with a common step-up transformer selection depends on the complete system requirements where
but it can also be a generator in block connection with a the generator is located. The earth-fault protection depends
transformer. In medium-size power generator applications mainly on the used earthing principle.
ABB 11
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
Uo Uo
3U 3U
Io Io
G G
3I 3I
Io Io
REG615 REG615
Std. conf. C Std. conf. C
ANSI IEC ANSI IEC
40 X< 40 X<
32R/32O P>/Q> 32R/32O P>/Q>
32U P< 32U P<
46M I2>M 46M I2>M
47O-/59 U2>/3U> 47O-/59 U2>/3U>
47U+/27 U1</3U< 47U+/27 U1</3U<
49T/G/C 3Ith>T/G/C 49T/G/C 3Ith>T/G/C
51P-1/51P-2 3I>/3I>> 51P-1/51P-2 3I>/3I>>
51V 3I(U)> 51V 3I(U)>
59G Uo> 59G Uo>
60 FUSEF 60 FUSEF
67N-1/67N-2 Io>/Io>> 67N-1/67N-2 Io>/Io>>
81 f>/f<, df/dt 81 f>/f<, df/dt
GUID-FA8F2E27-11C7-4B88-8865-414DFB0D71F3 V1 EN
Figure 6. Application example for parallel with common step-up transformer connected Diesel/Gas generators protected with standard
configuration C
12 ABB
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
3I
Uo
3U
Io
G
RTD
3I
3I
Io
Uo
REG615 REG615
Std. conf. D Std. conf. C
ANSI IEC ANSI IEC
49T/G/C 3Ith>T/G/C 21G Z<G
51BF/51NBF 3I>/Io>BF 27/59THD dUo>/Uo3H
51P-1/51P-2 3I>/3I>> 32R/32O P>/Q>
51V 3I(U)> 32U P<
59G Uo> 40 X<
60 FUSEF 46M I2>M
67-1/67-2 3I>/3I>> 47O-/59 U2>/3U>
87G 3dI>G 47U+/27 U1</3U<
MAP MAP 49T/G/C 3Ith>T/G/C
51BF/51NBF 3I>/Io>BF
51P-1/51P-2 3I>/3I>>
51V 3I(U)>
60 FUSEF
67N-1/67N-2 Io>/Io>>
81 f>/f<, df/dt
GUID-D955F7DE-7A8E-4C73-BBD9-BD81F95A4414 V1 EN
Figure 7. Medium-sized generator protection application example with standard configuration C and D
In Figure 7 protection is implemented with two REG615 Three-phase directional overcurrent protection, three-phase
generator protection relays. One REG615 takes care of the voltage protection, positive-sequence and negative-sequence
generator protection with 100% stator earth-fault protection voltage protection functions must be added with the
and the other REG615 provides the generator differential Application Configuration tool. In order to ensure the
protection. performance of the relay, the user specific configuration load is
verified with the Application Configuration tool in PCM600.
Standard configuration D is not designed for using all the
available functionality content in one relay at the same time.
ABB 13
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
3I (HV)
3U
Io
Io (HV)
RTD
G
RTD
3I (LV)
3I
Uo
RET615 REG615
Std. conf. A Std. conf. C
ANSI IEC ANSI IEC
51BF/51NBF 3I>/Io>BF 21G Z<G
51P-1/51P-2 3I>/3I>> 24 U/f>
87NL dIoLo> 32R/32O P>/Q>
87T 3dI>T 32U P<
MAP MAP 40 X<
46M I2>M
47O-/59 U2>/3U>
47U+/27 U1</3U<
49T/G/C 3Ith>T/G/C
51BF/51NBF 3I>/Io>BF
51P-1/51P-2 3I>/3I>>
51V 3I(U)>
59G Uo>
60 FUSEF
67N-1/67N-2 Io>/Io>>
81 f>/f<, df/dt
MAP MAP
GUID-B27F8FE3-1001-412B-A46B-7257A90AC757 V1 EN
Figure 8. Medium-sized generator in block connection with a transformer protection application example with standard configuration C and
RET615
In Figure 8 generator protection is implemented with REG615 a transformer. A single-phase voltage transformer is connected
generator protection relay. Transformer protection is to the generator neutral for the residual overvoltage protection.
implemented with the RET615 transformer differential On the terminal side phase-to-earth voltages are connected to
protection relay covering the generator in block connection with the generator protection relay.
14 ABB
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
5. Supported ABB solutions COM600S features a Web browser-based HMI, which provides
The 615 series protection relays together with the Substation a customizable graphical display for visualizing single-line
Management Unit COM600S constitute a genuine IEC 61850 mimic diagrams for switchgear bay solutions. The SLD feature
solution for reliable power distribution in utility and industrial is especially useful when 615 series relays without the optional
power systems. To facilitate the system engineering, ABB's single-line diagram feature are used. The Web HMI of
relays are supplied with connectivity packages. The COM600S also provides an overview of the whole substation,
connectivity packages include a compilation of software and including relay-specific single-line diagrams, which makes
relay-specific information, including single-line diagram information easily accessible. Substation devices and
templates and a full relay data model. The data model includes processes can also be remotely accessed through the Web
event and parameter lists. With the connectivity packages, the HMI, which improves personnel safety.
relays can be readily configured using PCM600 and integrated
with COM600S or the network control and management In addition, COM600S can be used as a local data warehouse
system MicroSCADA Pro. for the substation's technical documentation and for the
network data collected by the devices. The collected network
The 615 series relays offer native support for IEC 61850 Edition data facilitates extensive reporting and analyzing of network
2 also including binary and analog horizontal GOOSE fault situations by using the data historian and event handling
messaging. In addition, process bus with the sending of features of COM600S. The historical data can be used for
sampled values of analog currents and voltages and the accurate monitoring of process and equipment performance,
receiving of sampled values of voltages is supported. using calculations based on both real-time and historical
Compared to traditional hard-wired, inter-device signaling, values. A better understanding of the process dynamics is
peer-to-peer communication over a switched Ethernet LAN achieved by combining time-based process measurements
offers an advanced and versatile platform for power system with production and maintenance events.
protection. Among the distinctive features of the protection
system approach, enabled by the full implementation of the IEC COM600S can also function as a gateway and provide
61850 substation automation standard, are fast seamless connectivity between the substation devices and
communication capability, continuous supervision of the network-level control and management systems, such as
protection and communication system's integrity, and an MicroSCADA Pro and System 800xA.
inherent flexibility regarding reconfiguration and upgrades.This
GOOSE Analyzer interface in COM600S enables the following
protection relay series is able to optimally utilize interoperability
and analyzing the horizontal IEC 61850 application during
provided by the IEC 61850 Edition 2 features.
commissioning and operation at station level. It logs all GOOSE
At substation level, COM600S uses the data content of the bay- events during substation operation to enable improved system
level devices to enhance substation level functionality. supervision.
Product Version
ABB 15
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
ABB
MicroSCADA Pro/
System 800xA
COM600S COM600S
Web HMI Web HMI
GUID-4D002AA0-E35D-4D3F-A157-01F1A3044DDB V4 EN
Figure 9. ABB power system example using Relion relays, COM600S and MicroSCADA Pro/System 800xA
16 ABB
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
the relevant primary devices. Interlocking schemes required by The protection relay has the following power quality monitoring
the application are configured using the signal matrix or the functions.
application configuration functionality of PCM600. Depending
on the standard configuration, the relay also incorporates a Voltage variation
synchrocheck function to ensure that the voltage, phase angle Voltage unbalance
and frequency on either side of an open circuit breaker satisfy Current harmonics
the conditions for safe interconnection of two networks. Voltage harmonics
11. Recorded data block, or by both. The available measurement modes include
The relay has the capacity to store the records of the 128 latest DFT, RMS and peak-to-peak. Fault records store relay
fault events. The records can be used to analyze the power measurement values at the moment when any protection
system events. Each record includes, for example, current, function starts. In addition, the maximum demand current with
voltage and angle values and a time stamp. The fault recording time stamp is separately recorded. The records are stored in
can be triggered by the start or the trip signal of a protection the non-volatile memory.
IEC 61850-8-1
events
WHMI
DNP3
LHMI
(FIFO) 1024
Fault
records
(FIFO) 128
BASIC FUNCTIONS
Fault summary;
Trip timestamp, Function, Currents, Voltages, etc.
Audit
trail
events
(FIFO) 2048
n100
Load profile
record
...7 yrs Historical load data captured at a periodical
time interval (Demand interval 1...180min)
GUID-CDF1DC16-AF90-406F-B21B-EF6C7F60BCCA V1 EN
12. Condition monitoring In addition, the relay includes a runtime counter for monitoring
The condition monitoring functions of the relay constantly of how many hours a protected device has been in operation
monitor the performance and the condition of the circuit thus enabling scheduling of time-based preventive
breaker. The monitoring comprises the spring charging time, maintenance of the device.
SF6 gas pressure, the travel time and the inactivity time of the
circuit breaker.
13. Trip-circuit supervision
The monitoring functions provide operational circuit breaker The trip-circuit supervision continuously monitors the
history data, which can be used for scheduling preventive availability and operability of the trip circuit. It provides open-
circuit breaker maintenance. circuit monitoring both when the circuit breaker is in its closed
and in its open position. It also detects loss of circuit-breaker
control voltage.
18 ABB
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
14. Self-supervision residual current input, three phase-voltage inputs and one
The relays built-in self-supervision system continuously residual voltage input, and one voltage input that is used either
monitors the state of the relay hardware and the operation of for synchro-check or for the 3rd harmonic-based stator earth-
the relay software. Any fault or malfunction detected is used for fault protection depending on the standard configuration.
alerting the operator.
The phase-current inputs are rated 1/5 A. Two optional
A permanent relay fault blocks the protection functions to residual-current inputs are available, that is, 1/5 A or 0.2/1 A.
prevent incorrect operation. The 0.2/1 A input is normally used in applications requiring
sensitive earth-fault protection and featuring core-balance
current transformers. The three phase-voltage inputs and the
15. Fuse failure supervision
residual-voltage input covers the rated voltages 60...210 V.
The fuse failure supervision detects failures between the
Both phase-to-phase voltages and phase-to-earth voltages
voltage measurement circuit and the relay. The failures are
can be connected.
detected either by the negative sequence-based algorithm or
by the delta voltage and delta current algorithm. Upon the The phase-current input 1 A or 5 A, the residual-current input 1
detection of a failure, the fuse failure supervision function A or 5 A, alternatively 0.2 A or 1 A, and the rated voltage of the
activates an alarm and blocks voltage-dependent protection residual voltage input are selected in the relay software. In
functions from unintended operation. addition, the binary input thresholds 16176 V DC are selected
by adjusting the relays parameter settings.
16. Access control
All binary inputs and outputs contacts are freely configurable
To protect the relay from unauthorized access and to maintain
with the signal matrix or application configuration functionality
information integrity, the relay is provided with a four-level, role-
of PCM600.
based authentication system with administrator-programmable
individual passwords for the viewer, operator, engineer and See the Input/output overview table and the terminal diagrams
administrator levels. The access control applies to the local for more information about the inputs and outputs.
HMI, the Web HMI and PCM600.
Optionally, a binary input and output module can be selected. It
has three high speed binary outputs (HSO) and it decreases the
17. Inputs and outputs
total operate time with typically 4...6 ms compared to the
Depending on the standard configuration selected, the relay is
normal power outputs.
equipped either with three or six phase-current inputs and one
ABB 19
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
AG 4 5 16 4 PO + 6 SO - -
AE / AF FC 4 5 16 4 PO + 2 SO - -
+ 3 HSO
A
AD 4 5 12 4 PO + 6 SO 2 1
FE / FF FE 4 5 12 4 PO + 2 SO 2 1
+ 3 HSO
AG 4 5 16 4 PO + 6 SO - -
AE / AF FC 4 5 16 4 PO + 2 SO - -
+ 3 HSO
C
AD 4 5 12 4 PO + 6 SO 2 1
FE / FF FE 4 5 12 4 PO + 2 SO 2 1
+ 3 HSO
AD 7 5 12 4 PO + 6 SO - -
BC / BD FE 7 5 12 4 PO + 2 SO - -
+ 3 HSO
D
BA 7 5 8 4 PO + 6 SO 2 1
BE / BF FD 7 5 8 4 PO + 2 SO 2 1
+ 3 HSO
18. Station communication simultaneous event reporting to five different clients on the
The relay supports a range of communication protocols station bus. The relay can exchange data with other devices
including IEC 61850 Edition 2, IEC 61850-9-2 LE, IEC using the IEC 61850 protocol.
60870-5-103, Modbus and DNP3. Profibus DPV1
The relay can send binary and analog signals to other devices
communication protocol is supported with using the protocol
using the IEC 61850-8-1 GOOSE (Generic Object Oriented
converter SPA-ZC 302. Operational information and controls
Substation Event) profile. Binary GOOSE messaging can, for
are available through these protocols. However, some
example, be employed for protection and interlocking-based
communication functionality, for example, horizontal
protection schemes. The relay meets the GOOSE performance
communication between the relays, is only enabled by the IEC
requirements for tripping applications in distribution
61850 communication protocol.
substations, as defined by the IEC 61850 standard (<10 ms
The IEC 61850 protocol is a core part of the relay as the data exchange between the devices). The relay also supports
protection and control application is fully based on standard the sending and receiving of analog values using GOOSE
modelling. The relay supports Edition 2 and Edition 1 versions messaging. Analog GOOSE messaging enables easy transfer of
of the standard. With Edition 2 support, the relay has the latest analog measurement values over the station bus, thus
functionality modelling for substation applications and the best facilitating for example the sending of measurement values
interoperability for modern substations. It incorporates also the between the relays when controlling parallel running
full support of standard device mode functionality supporting transformers.
different test applications. Control applications can utilize the
The relay also supports IEC 61850 process bus by sending
new safe and advanced station control authority feature.
sampled values of analog currents and voltages and by
The IEC 61850 communication implementation supports receiving sampled values of voltages. With this functionality the
monitoring and control functions. Additionally, parameter galvanic interpanel wiring can be replaced with Ethernet
settings, disturbance recordings and fault records can be communication. The measured values are transferred as
accessed using the IEC 61850 protocol. Disturbance sampled values using IEC 61850-9-2 LE protocol. The intended
recordings are available to any Ethernet-based application in application for sampled values shares the voltages to other 615
the standard COMTRADE file format. The relay supports series relays, having voltage based functions and 9-2 support.
20 ABB
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
615 relays with process bus based applications use IEEE 1588 communication. The network redundancy is based on two
for high accuracy time synchronization. complementary protocols defined in the IEC 62439-3 standard:
PRP and HSR protocols. Both the protocols are able to
For redundant Ethernet communication, the relay offers either overcome a failure of a link or switch with a zero switch-over
two optical or two galvanic Ethernet network interfaces. A third time. In both the protocols, each network node has two
port with galvanic Ethernet network interface is also available. identical Ethernet ports dedicated for one network connection.
The third Ethernet interface provides connectivity for any other The protocols rely on the duplication of all transmitted
Ethernet device to an IEC 61850 station bus inside a switchgear information and provide a zero switch-over time if the links or
bay, for example connection of a Remote I/O. Ethernet network switches fail, thus fulfilling all the stringent real-time
redundancy can be achieved using the high-availability requirements of substation automation.
seamless redundancy (HSR) protocol or the parallel
redundancy protocol (PRP) or a with self-healing ring using In PRP, each network node is attached to two independent
RSTP in managed switches. Ethernet redundancy can be networks operated in parallel. The networks are completely
applied to Ethernet-based IEC 61850, Modbus and DNP3 separated to ensure failure independence and can have
protocols. different topologies. The networks operate in parallel, thus
providing zero-time recovery and continuous checking of
The IEC 61850 standard specifies network redundancy which redundancy to avoid failures.
improves the system availability for the substation
COM600
SCADA
HSR applies the PRP principle of parallel operation to a single sender node discards the frame to avoid loops. The HSR ring
ring. For each message sent, the node sends two frames, one with 615 series relays supports the connection of up to 30
through each port. Both the frames circulate in opposite relays. If more than 30 relays are to be connected, it is
directions over the ring. Every node forwards the frames it recommended to split the network into several rings to
receives from one port to another to reach the next node. When guarantee the performance for real-time applications.
the originating sender node receives the frame it sent, the
ABB 21
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
COM600
Devices not supporting HSR
SCADA
Ethernet switch
The choice between the HSR and PRP redundancy protocols switch-over. The relays in the ring topology act as unmanaged
depends on the required functionality, cost and complexity. switches forwarding unrelated data traffic. The Ethernet ring
solution supports the connection of up to 30 615 series relays.
The self-healing Ethernet ring solution enables a cost-efficient If more than 30 relays are to be connected, it is recommended
communication ring controlled by a managed switch with to split the network into several rings. The self-healing Ethernet
standard Rapid Spanning Tree Protocol (RSTP) support. The ring solution avoids single point of failure concerns and
managed switch controls the consistency of the loop, routes improves the reliability of the communication.
the data and corrects the data flow in case of a communication
22 ABB
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
Client A Client B
Network A
Network B
GUID-AB81C355-EF5D-4658-8AE0-01DC076E519C V4 EN
All communication connectors, except for the front port records are supported. DNP serial and DNP TCP can be used in
connector, are placed on integrated optional communication parallel. If required, both IEC 61850 and DNP protocols can be
modules. The relay can be connected to Ethernet-based run simultaneously.
communication systems via the RJ-45 connector (100Base-TX)
or the fiber optic LC connector (100Base-FX). If connection to 615 series supports Profibus DPV1 with support of SPA-ZC
serial bus is required, the 9-pin RS-485 screw-terminal can be 302 Profibus adapter. If Profibus is required the relay must be
used. An optional serial interface is available for RS-232 ordered with Modbus serial options. Modbus implementation
communication. includes SPA-protocol emulation functionality. This
functionality enables connection to SPA-ZC 302.
Modbus implementation supports RTU, ASCII and TCP modes.
Besides standard Modbus functionality, the relay supports When the relay uses the RS-485 bus for the serial
retrieval of time-stamped events, changing the active setting communication, both two- and four wire connections are
group and uploading of the latest fault records. If a Modbus supported. Termination and pull-up/down resistors can be
TCP connection is used, five clients can be connected to the configured with jumpers on the communication card so external
relay simultaneously. Further, Modbus serial and Modbus TCP resistors are not needed.
can be used in parallel, and if required both IEC 61850 and
The relay supports the following time synchronization methods
Modbus protocols can be run simultaneously.
with a time-stamping resolution of 1 ms.
The IEC 60870-5-103 implementation supports two parallel
Ethernet-based
serial bus connections to two different masters. Besides basic
SNTP (Simple Network Time Protocol)
standard functionality, the relay supports changing of the active
setting group and uploading of disturbance recordings in IEC
60870-5-103 format. Further, IEC 60870-5-103 can be used at With special time synchronization wiring
the same time with the IEC 61850 protocol. IRIG-B (Inter-Range Instrumentation Group - Time Code
Format B)
DNP3 supports both serial and TCP modes for connection up
to five masters. Changing of the active setting and reading fault
ABB 23
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
The relay supports the following high accuracy time Layer 2 mapping
synchronization method with a time-stamping resolution of 4 s Peer to peer delay calculation
required especially in process bus applications. Multicast operation
PTP (IEEE 1588) v2 with Power Profile
Required accuracy of grandmaster clock is +/-1 s. The relay
can work as a master clock per BMC algorithm if the external
The IEEE 1588 support is included in all variants having a grandmaster clock is not available for short term.
redundant Ethernet communication module.
The IEEE 1588 support is included in all variants having a
IEEE 1588 v2 features redundant Ethernet communication module.
Ordinary Clock with Best Master Clock algorithm
One-step Transparent Clock for Ethernet ring topology In addition, the relay supports time synchronization via
1588 v2 Power Profile Modbus, DNP3 and IEC 60870-5-103 serial communication
Receive (slave): 1-step/2-step protocols.
Transmit (master): 1-step
IEC 61850-8-1 - -
IEC 61850-9-2 LE - -
MODBUS RTU/ASCII - -
MODBUS TCP/IP - -
DNP3 (serial) - -
DNP3 TCP/IP - -
IEC 60870-5-103 - -
= Supported
24 ABB
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
Table 6. Dimensions
Description Value
Case 164 mm
Case 160 mm
Nominal auxiliary voltage Un 100, 110, 120, 220, 240 V AC, 50 and 60 Hz 24, 30, 48, 60 V DC
Burden of auxiliary voltage supply under DC <13.0 W (nominal)/<18.0 W (max.) DC <13.0 W (nominal)/<18.0 W (max.)
quiescent (Pq)/operating condition AC <16.0 W (nominal)/<21.0 W (max.)
Ripple in the DC auxiliary voltage Max 15% of the DC value (at frequency of 100 Hz)
Description Value
Continuously 4A 20 A
Voltage withstand:
Continuous 240 V AC
For 10 s 360 V AC
ABB 25
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
Description Value
Description Value
RTD inputs Supported RTD sensors 100 platinum TCR 0.00385 (DIN 43760)
250 platinum TCR 0.00385
100 nickel TCR 0.00618 (DIN 43760)
120 nickel TCR 0.00618
250 nickel TCR 0.00618
10 copper TCR 0.00427
2.0% or 1 1C
10 copper: 2C
Description Value
Breaking capacity when the control-circuit time constant L/R<40 ms 1 A/0.25 A/0.15 A
26 ABB
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
Description Value
Breaking capacity when the control-circuit time constant L/R<40 ms, at 1 A/0.25 A/0.15 A
48/110/220 V DC
Description Value
Breaking capacity when the control-circuit time constant L/R<40 ms, at 5 A/3 A/1 A
48/110/220 V DC (two contacts connected in series)
Description Value
Breaking capacity when the control-circuit time constant L/R<40 ms, at 5 A/3 A/1 A
48/110/220 V DC
ABB 27
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
Description Value
Breaking capacity when the control-circuit time constant L/R <40 ms, at 5 A/3 A/1 A
48/110/220 V DC
Front TCP/IP protocol Standard Ethernet CAT 5 cable with RJ-45 connector 10 MBits/s
Description Value
Modulation Unmodulated
Description Value
Front side IP 54
Description Value
Altitude Up to 2000 m
1) Degradation in MTBF and HMI performance outside the temperature range of -25...+55 C
2) For relays with an LC communication interface the maximum operating temperature is +70 C
28 ABB
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
Contact discharge 8 kV
Air discharge 15 kV
All ports 4 kV
2s 100 A/m
ABB 29
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
Conducted
Radiated
30 ABB
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
Description Reference
LV directive 2006/95/EC
Description Reference
Description
ABB 31
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
Protection functions
Characteristic Value
PHIPTOC:
IFault = 2 set Start value 16 ms 19 ms 23 ms
IFault = 10 set Start value
11 ms 12 ms 14 ms
Operate time accuracy in definite time mode 1.0% of the set value or 20 ms
Operate time accuracy in inverse time mode 5.0% of the theoretical value or 20 ms 3)
1) Set Operate delay time = 0,02 s, Operate curve type = IEC definite time, Measurement mode = default (depends on stage), current before fault = 0.0 In, fn = 50 Hz, fault current in one phase
with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Includes the delay of the heavy-duty output contact
PHIPTOC 20...200000 ms 10
32 ABB
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
Characteristic Value
DPHLPDOC Current:
1.5% of the set value or 0.002 In
Voltage:
1.5% of the set value or 0.002 Un
Phase angle: 2
DPHHPDOC Current:
1.5% of the set value or 0.002 In
(at currents in the range of 0.110 In)
5.0% of the set value
(at currents in the range of 1040 In)
Voltage:
1.5% of the set value or 0.002 Un
Phase angle: 2
Operate time accuracy in definite time mode 1.0% of the set value or 20 ms
Operate time accuracy in inverse time mode 5.0% of the theoretical value or 20 ms3)
1) Measurement mode and Pol quantity = default, current before fault = 0.0 In, voltage before fault = 1.0 Un, fn = 50 Hz, fault current in one phase with nominal frequency injected from
random phase angle, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Maximum Start value = 2.5 In, Start value multiples in range of 1.5...20
ABB 33
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
Characteristic Value
Operation accuracy Depending on the frequency of the measured current and voltage:
fn 2 Hz
Current:
1.5% of the set value or 0.002 In
Voltage:
1.5% of the set value or 0.002 Un
Operate time accuracy in definite time mode 1.0% of the set value or 20 ms
Operate time accuracy in inverse time mode 5.0% of the set value or 20 ms
1) Measurement mode = default, current before fault = 0.0 In, fn = 50 Hz, fault current in one phase with nominal frequency injected from random phase angle, results based on statistical
distribution of 1000 measurements
2) Includes the delay of the signal output contact
34 ABB
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
Characteristic Value
EFIPTOC:
IFault = 2 set Start value 16 ms 19 ms 23 ms
IFault = 10 set Start value 11 ms 12 ms 14 ms
Operate time accuracy in definite time mode 1.0% of the set value or 20 ms
Operate time accuracy in inverse time mode 5.0% of the theoretical value or 20 ms 3)
1) Measurement mode = default (depends on stage), current before fault = 0.0 In, fn = 50 Hz, earth-fault current with nominal frequency injected from random phase angle, results based on
statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Maximum Start value = 2.5 In, Start value multiples in range of 1.5...20
EFIPTOC 20...200000 ms 10
ABB 35
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
Characteristic Value
DEFLPDEF Current:
1.5% of the set value or 0.002 In
Voltage
1.5% of the set value or 0.002 Un
Phase angle:
2
DEFHPDEF Current:
1.5% of the set value or 0.002 In
(at currents in the range of 0.110 In)
5.0% of the set value
(at currents in the range of 1040 In)
Voltage:
1.5% of the set value or 0.002 Un
Phase angle:
2
DEFHPDEF
IFault = 2 set Start value 42 ms 46 ms 49 ms
DEFLPDEF 58 ms 62 ms 66 ms
IFault = 2 set Start value
Operate time accuracy in definite time mode 1.0% of the set value or 20 ms
Operate time accuracy in inverse time mode 5.0% of the theoretical value or 20 ms 3)
1) Set Operate delay time = 0.06 s, Operate curve type = IEC definite time, Measurement mode = default (depends on stage), current before fault = 0.0 In , fn = 50 Hz, earth-fault current with
nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Maximum Start value = 2.5 In, Start value multiples in range of 1.5...20
36 ABB
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
DEFHPDEF 40...200000 ms 10
Characteristic Value
Operation accuracy (Uo criteria with transient protection) Depending on the frequency of the measured current: fn 2 Hz
ABB 37
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
Characteristic Value
Operate time accuracy in definite time mode 1.0% of the set value or 20 ms
Operate time accuracy in inverse time mode 5.0% of the theoretical value or 20 ms 3)
1) Negative sequence current before fault = 0.0, fn = 50 Hz, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Maximum Start value = 2.5 In, Start value multiples in range of 1.5...20
Characteristic Value
Operate time accuracy in definite time mode 1.0% of the set value or 20 ms
Operate time accuracy in inverse time mode 5.0% of the theoretical value or 20 ms3)
1) Negative-sequence current before = 0.0, fn = 50 Hz, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Start value multiples in range of 1.10...5.00
38 ABB
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
Table 42. Negative-sequence overcurrent protection for machines (MNSPTOC) main settings
Operation MNSPTOC 1 = on -
5 = off
Characteristic Value
Operate time accuracy in definite time mode 1.0% of the set value or 20 ms
1) Residual voltage before fault = 0.0 Un , fn = 50 Hz, residual voltage with nominal frequency injected from random phase angle, results based on statistical distribution of 1000
measurements
2) Includes the delay of the signal output contact
ABB 39
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
Characteristic Value
Operate time accuracy in definite time mode 1.0% of the set value or 20 ms
Operate time accuracy in inverse time mode 5.0% of the theoretical value or 20 ms3)
1) Start value = 1.0 Un, Voltage before fault = 1.1 Un, fn = 50 Hz, undervoltage in one phase-to-phase with nominal frequency injected from random phase angle, results based on statistical
distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Minimum Start value = 0.50, Start value multiples in range of 0.90...0.20
Characteristic Value
Operate time accuracy in definite time mode 1.0% of the set value or 20 ms
Operate time accuracy in inverse time mode 5.0% of the theoretical value or 20 ms3)
1) Start value = 1.0 Un, Voltage before fault = 0.9 Un, fn = 50 Hz, overvoltage in one phase-to-phase with nominal frequency injected from random phase angle, results based on statistical
distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Maximum Start value = 1.20 Un, Start value multiples in range of 1.10...2.00
40 ABB
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
Characteristic Value
Operate time accuracy in definite time mode 1.0% of the set value or 20 ms
1) Start value = 1.0 Un, positive-sequence voltage before fault = 1.1 Un, fn = 50 Hz, positive sequence undervoltage with nominal frequency injected from random phase angle, results based
on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
ABB 41
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
Characteristic Value
Operate time accuracy in definite time mode 1.0% of the set value or 20 ms
1) Negative-sequence voltage before fault = 0.0 Un, fn = 50 Hz, negative-sequence overvoltage with nominal frequency injected from random phase angle, results based on statistical
distribution of 1000 measurements
2) Includes the delay of the signal output contact
Characteristic Value
df/dt <120 ms
42 ABB
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
Characteristic Value
Voltage change:
Typically 40 ms
ABB 43
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
Table 57. Three-phase thermal protection for feeders, cables and distribution transformers (T1PTTR)
Characteristic Value
Table 58. Three-phase thermal protection for feeders, cables and distribution transformers (T1PTTR) main settings
Table 59. Three-phase thermal overload protection, two time constants (T2PTTR)
Characteristic Value
Table 60. Three-phase thermal overload protection, two time constants (T2PTTR) main settings
Operation T2PTTR 1 = on -
5 = off
44 ABB
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
Characteristic Value
Characteristic Value
Current measurement:
1.5% of the set value or 0.002 In
Ratio I2f/I1f measurement:
5.0% of the set value
ABB 45
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
Characteristic Value
1) Phase start value = 1.0 In, current before fault = 2.0 set Phase start value, fn = 50 Hz, fault with nominal frequency, results based on statistical distribution of 200 measurements
2) Includes the delay of the heavy-duty output contact
3) Normal power output
4) High-speed output
Characteristic Value
46 ABB
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
Table 69. Stabilized and instantaneous differential protection for machines (MPDIF)
Characteristic Value
Low stage 36 ms 40 ms 42 ms
High stage 18 ms 22 ms 27 ms
Table 70. Stabilized and instantaneous differential protection for machines (MPDIF) main settings
Characteristic Value
ABB 47
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
Table 72. Third harmonic-based stator earth-fault protection (H3EFPSEF) main settings
Characteristic Value
Operation accuracy 1) Depending on the frequency of the measured current and voltage:
fn 2 Hz
48 ABB
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
Characteristic Value
Operation accuracy 1) Depending on the frequency of the measured current and voltage:
f = fn 2 Hz
Characteristic Value
Operation accuracy Depending on the frequency of the measured current and voltage:
f = fn 2 Hz
Retardation time Total retardation time when the impedance returns from the operating
circle <40 ms
ABB 49
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
Characteristic Value
Operation accuracy Depending on the frequency of the measured current and voltage: fn 2
Hz
Characteristic Value
Impedance reach Depending on the frequency of the measured current and voltage: fn 2
Hz
50 ABB
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
ABB 51
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
Interconnection functions
Characteristic Value
Operation accuracy Depending on the frequency of the measured current and voltage:
fn 2 Hz
Reactive power range |PF| <0.71
Power:
3.0% or 0.002 Qn
Voltage:
1.5% of the set value or 0.002 Un
1) Start value = 0.05 Sn, reactive power before fault = 0.8 Start value, reactive power overshoot 2 times, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
Table 85. Directional reactive power undervoltage protection (DQPTUV) main settings
Characteristic Value
1) Tested for Number of Start phases = 1 out of 3, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
52 ABB
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
Characteristic Value
ABB 53
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
54 ABB
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
Characteristic Value
Characteristic Value
ABB 55
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
Control functions
Characteristic Value
Voltage:
3.0% of the set value or 0.01 Un
Frequency:
10 mHz
Phase angle:
3
Operate time accuracy in definite time mode 1.0% of the set value or 20 ms
56 ABB
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
Supervision functions
Characteristic Value
Characteristic Value
Characteristic Value
Operate time1) NPS function UFault = 1.1 set Neg Seq voltage <33 ms
Lev
UFault = 5.0 set Neg Seq voltage <18 ms
Lev
1) Includes the delay of the signal output contact, fn = 50 Hz, fault voltage with nominal frequency injected from random phase angle, results based on statistical distribution of 1000
measurements
Description Value
ABB 57
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
Measurement functions
Characteristic Value
0.5% or 0.002 In
(at currents in the range of 0.01...4.00 In)
Characteristic Value
1.0% or 0.002 In
at currents in the range of 0.01...4.00 In
Characteristic Value
0.5% or 0.002 In
at currents in the range of 0.01...4.00 In
Characteristic Value
0.5% or 0.002 Un
Characteristic Value
0.5% or 0.002 Un
58 ABB
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
Characteristic Value
1.0% or 0.002 Un
Characteristic Value
Description Value
RTD inputs Supported RTD sensors 100 platinum TCR 0.00385 (DIN 43760)
250 platinum TCR 0.00385
100 nickel TCR 0.00618 (DIN 43760)
120 nickel TCR 0.00618
250 nickel TCR 0.00618
10 copper TCR 0.00427
2.0% or 1 1C
10 copper: 2C
Characteristic Value
ABB 59
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
Other functions
Characteristic Value
Characteristic Value
Characteristic Value
60 ABB
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
20. Local HMI default single line diagram. The SLD view can also be accessed
The relay is available with two optional displays, a large one and using the Web browser-based user interface. The default SLD
a small one. The large display is suited for relay installations can be modified according to user requirements by using the
where the front panel user interface is frequently used and a Graphical Display Editor in PCM600. The user can create up to
single line diagram is required. The small display is suited for 10 SLD pages.
remotely controlled substations where the relay is only
occasionally accessed locally via the front panel user interface. The local HMI includes a push button (L/R) for local/remote
operation of the relay. When the relay is in the local mode, it can
Both LCD displays offer front-panel user interface functionality be operated only by using the local front panel user interface.
with menu navigation and menu views. However, the large When the relay is in the remote mode, it can execute
display offers increased front-panel usability with less menu commands sent from a remote location. The relay supports the
scrolling and improved information overview. In addition, the remote selection of local/remote mode via a binary input. This
large display includes a user-configurable single line diagram feature facilitates, for example, the use of an external switch at
(SLD) with position indication for the associated primary the substation to ensure that all relays are in the local mode
equipment. Depending on the chosen standard configuration, during maintenance work and that the circuit breakers cannot
the relay displays the related measuring values, apart from the be operated remotely from the network control center.
IECA070904 V3 EN IECA070901 V3 EN
ABB 61
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
190
6
18
164
177
25
160
160
177
177
230
98
107
48
1 53 133
103
Figure 16. Flush mounting Figure 17. Semi-flush mounting Figure 18. Semi-flush mounting in a 25 tilt
22. Relay case and plug-in unit 23. Selection and ordering data
The relay cases are assigned to a certain type of plug-in unit. Use ABB Library to access the selection and ordering
For safety reasons, the relay cases for current measuring relays information and to generate the order number.
are provided with automatically operating contacts for short-
circuiting the CT secondary circuits when a relay unit is Product Selection Tool (PST), a Next-Generation Order Number
withdrawn from its case. The relay case is further provided with Tool, supports order code creation for ABB Distribution
a mechanical coding system preventing the current measuring Automation IEC products with emphasis on but not exclusively
relay units from being inserted into relay cases intended for for the Relion product family. PST is an easy to use, online tool
voltage measuring relay units. always containing the latest product information. The complete
order code can be created with detailed specification and the
result can be printed and mailed. Registration is required.
62 ABB
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
Mounting bracket for one relay with test switch RTXP in 4U Combiflex (RHGT 19 variant C) 2RCA022642P0001
19 rack mounting kit for one relay and one RTXP18 test switch (the test switch is not included in the delivery) 2RCA021952A0003
19 rack mounting kit for one relay and one RTXP24 test switch (the test switch is not included in the delivery) 2RCA022561A0003
Replacement kit for a Strmberg SP_J40 series relay (cut-out in the center of the installation plate) 2RCA027871A0001
Replacement kit for a Strmberg SP_J40 series relay (cut-out on the left or the right of the installation plate) 2RCA027874A0001
19 rack replacement kit for Strmberg SP_J3/J6 series relays (one cut-out) 2RCA027894A0001
19 rack replacement kit for Strmberg SP_J3/J6 series relays (two cut-outs) 2RCA027897A0001
1) Cannot be used when the protection relay is mounted with the Combiflex 19" equipment frame (2RCA032826A0001)
ABB 63
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
25. Tools (Internet Explorer). For security reasons, the Web HMI is
The protection relay is delivered as a preconfigured unit. The disabled by default but it can be enabled via the local HMI. The
default parameter setting values can be changed from the front- Web HMI functionality can be limited to read-only access.
panel user interface (local HMI), the Web browser-based user
interface (Web HMI) or Protection and Control IED Manager The relay connectivity package is a collection of software and
PCM600 in combination with the relay-specific connectivity specific relay information, which enables system products and
package. tools to connect and interact with the protection relay. The
connectivity packages reduce the risk of errors in system
PCM600 offers extensive relay configuration functions. For integration, minimizing device configuration and setup times.
example, depending on the protection relay, the relay signals, Further, the connectivity packages for protection relays of this
application, graphical display and single-line diagram, and IEC product series include a flexible update tool for adding one
61850 communication, including horizontal GOOSE additional local HMI language to the protection relay. The
communication, can be modified with PCM600. update tool is activated using PCM600, and it enables multiple
updates of the additional HMI language, thus offering flexible
When the Web HMI is used, the protection relay can be means for possible future language updates.
accessed either locally or remotely using a Web browser
Description Version
64 ABB
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
Signal monitoring
Application configuration -
Event viewing
Online monitoring -
= Supported
26. Cyber security and Web HMI use TLS encryption with a minimum of 128 bit key
The relay supports role based user authentication and length protecting the data in transit. In this case the used
authorization. It can store 2048 audit trail events to a non- communication protocols are FTPS and HTTPS. All rear
volatile memory. The non-volatile memory is based on a communication ports and optional protocol services can be
memory type which does not need battery backup or regular deactivated according to the required system setup.
component exchange to maintain the memory storage. FTP
ABB 65
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
GUID-4BA6AD56-1833-4BA6-B3CC-3C44FD9767BF V1 EN
66 ABB
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
GUID-7E974B34-D8B8-4114-A24A-40F38BECF594 V1 EN
ABB 67
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
GUID-6756612D-B6DA-4B52-822D-B2794FADCC23 V1 EN
68 ABB
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
DNV GL has issued an IEC 61850 Edition 1 Certificate Level A1 The latest relevant information on the REG615 protection and
for Relion 615 series. Certificate number: 74105701-OPE/INC control relay is found on the product page. Scroll down the
15-1145. page to find and download the related documentation.
ABB 69
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
Protection
Three-phase directional overcurrent protection, low DPHLPDOC1 3I> -> (1) 67-1 (1)
stage
DPHLPDOC2 3I> -> (2) 67-1 (2)
Three-phase directional overcurrent protection, high DPHHPDOC1 3I>> -> (1) 67-2 (1)
stage
Non-directional earth-fault protection, high stage EFHPTOC1 Io>> (1) 51N-2 (1)
Directional earth-fault protection, low stage DEFLPDEF1 Io> -> (1) 67N-1 (1)
Directional earth-fault protection, high stage DEFHPDEF1 Io>> -> (1) 67N-2 (1)
Transient/intermittent earth-fault protection INTRPTEF1 Io> -> IEF (1) 67NIEF (1)
70 ABB
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
Three-phase thermal protection for feeders, cables T1PTTR1 3Ith>F (1) 49F (1)
and distribution transformers
Three-phase thermal overload protection, two time T2PTTR1 3Ith>T/G/C (1) 49T/G/C (1)
constants
Stabilized and instantaneous differential protection MPDIF1 3dI>G/M (1) 87G/M (1)
for machines
Third harmonic-based stator earth-fault protection H3EFPSEF1 dUo>/Uo3H (1) 27/59THD (1)
ABB 71
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
Interconnection functions
Directional reactive power undervoltage protection DQPTUV1 Q> ->,3U< (1) 32Q,27 (1)
Power quality
Control
Earthing switch control ESXSWI1 I <-> O ESC (1) I <-> O ESC (1)
Runtime counter for machines and devices MDSOPT1 OPTS (1) OPTM (1)
Measurement
72 ABB
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
Sequence current measurement CSMSQI1 I1, I2, I0 (1) I1, I2, I0 (1)
Sequence voltage measurement VSMSQI1 U1, U2, U0 (1) V1, V2, V0 (1)
Other
Minimum pulse timer (2 pcs, second resolution) TPSGAPC1 TPS (1) TPS (1)
Minimum pulse timer (2 pcs, minute resolution) TPMGAPC1 TPM (1) TPM (1)
ABB 73
Generator and Interconnection Protection 1MRS758279 A
REG615
Product version: 5.0 FP1
Generic control point (16 pcs) SPCGAPC1 SPC (1) SPC (1)
74 ABB
75
Contact us