Volume 2Commercial Distribution CA08100003EMarch 2016 www.eaton.com V2-T6-1
6.1 Low Voltage Busway
Pow-R-Way III
Contents
6 Pow-R-Way III Busway
Description Page
6 Pow-R-Way III Busway
Features, Benefits and Functions . . . . . . . . . . V2-T6-12
6 Standards and Certifications . . . . . . . . . . . . . . V2-T6-13
Product Support. . . . . . . . . . . . . . . . . . . . . . . . V2-T6-13
6 Catalog Number Selection . . . . . . . . . . . . . . . . V2-T6-14
Product Selection. . . . . . . . . . . . . . . . . . . . . . . V2-T6-15
6 Technical Data and Specifications . . . . . . . . . . V2-T6-19
6
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . V2-T6-23
6
6
6
6
6 Pow-R-Way III Busway
6 Product Description
6
6
6
Plug-In Unit
6
6
6
V2-T6-4 Volume 2Commercial Distribution CA08100003EMarch 2016 www.eaton.com
Low Voltage Busway
Pow-R-Way III
6.1
Traditional Indoor and Corner Joint Elbows Special Angle Elbows Tees
Outdoor Elbows The Pow-R-Way III corner Special angle elbows are A tee is a busway fitting 6
Elbows are used to make joint elbow can be installed traditional elbows that allow suitable for connection in
90 changes in the direction in areas where a traditional the direction of the busway three directions. 6
of busway runs. The four 90 turn could never have runs to change at angles
types that are available are
forward, rearward, upward
been accomplished before. greater than 90. They allow 6
easy routing through non-
Pow-R-Way III corner
and downward.
joint elbows can solve any
traditional corridors. The
four types offered are
6
serious pathway problem forward, rearward,
and contribute to successful upward and downward. 6
layouts with minimal space
requirements. The corner joint
elbow is UL listed for indoor
6
applications only and
is also certified for seismic 6
withstand capability to
worst-case, Zone 4 levels. 6
6
6
6
6
6
6
6
6
6
6
For Indoor Use Only
6
6
6
6
6
6
6
6
6
6
6
6
Volume 2Commercial Distribution CA08100003EMarch 2016 www.eaton.com V2-T6-5
6.1 Low Voltage Busway
Pow-R-Way III
6
6
6
6
6
V2-T6-6 Volume 2Commercial Distribution CA08100003EMarch 2016 www.eaton.com
Low Voltage Busway
Pow-R-Way III
6.1
Transformer Flange Connections Three-Phase Transformer Taps In-Line Power Takeoff Unprotected PTO
Transformer flange Three-phase transformer Main Circuit Breaker PTO The in-line PTO with no 6
connections are used taps are used when making The in-line main circuit main device shown in figure
when making a connection connections to a three- breaker PTO shown in figure to the left comes with 6
to a dry-type substation phase transformer. The bus to the left is available with 1200 A horizontal cross bus
transformer. Transformer extensions do not include trip ratings from 300 A up to as standard. This device is
intended for use with six or
6
flange connections include drilling or lugs. 1200 A; using L-, M- and
flexible connectors between
the transformer low
N-Frame circuit breakers.
This device is indoor rated
fewer meter sockets, or as
local code permits. 6
voltage spades and the
Pow-R-Way III flange
and may be sprinkler-proofed
upon request. 6
busbars.
6
6
6
6
6
6
6
Main Fusible Switch PTO
Offsets
An offset is used to avoid
6
The in-line main fusible
switch PTO shown in figure
obstacles and to conform
to the buildings structure. 6
to the left is available with It is two elbows fabricated
400, 600 and 800 A switches;
using Class T fuses.
into a single fitting for use 6
where space restrictions
Single-Phase Transformer Taps This device is indoor rated
only. The switch handle is
prohibit the use of two 6
Single-phase transformer standard 90 elbows.
mounted in front, eliminating
taps arrangements are used
for connections to three
interference with the meter 6
sockets and the need for
single-phase transformers.
The bus extensions do not
spacers between the main 6
device and the meter stack.
include drilling or lugs.
It comes with a hinged door,
giving easy access to the
6
fuses mounted below the
main switch. 6
6
6
6
6
6
6
6
6
6
6
Volume 2Commercial Distribution CA08100003EMarch 2016 www.eaton.com V2-T6-7
6.1 Low Voltage Busway
Pow-R-Way III
Pow-R-Way III Adapters Power Where You Need it! Schools and Laboratories Single Receptacle Plug-In Unit
6 A complete line of adapters As a leader in providing quality, Pow-R-Way III receptacle These units are configured
are available to enable the robust, cutting-edge electrical plugs offer safe power to order based upon the
6 user to add to existing old-line distribution equipment, Eaton access for instrumentation type and size of receptacle
Westinghouse or obsolete understands the importance and other lab equipment at ordered, and offer the
6 Cutler-Hammer bus runs of providing usable power the point of use. following features:
with the Pow-R-Way III access in a variety of Machine Shops One single or duplex
6
design. The specific applications. Eatons Pow-R- Pow-R-Way III busway and
Westinghouse product lines Way III busway continues to receptacle. Straight blade
receptacle plugs offer quick or twist lock, 530 A
6 are low impedance busway,
current-limiting busway, Pow-
offer electrical distribution
solutions that are flexible and
power connection for shop
equipment and make it easy
240 V maximum,
R-Way and Pow-R-Way II. without limitations, and are single-phase
6 The obsolete Cutler-Hammer energy efficient, saving time
to change shop layouts as
demands change.
Type CH single-pole or
designs are CP2, CP3 and and money. two-pole circuit breaker
6 CP4 Safetybus.
Pow-R-Way III Receptacle
Light Industrial protection
Pow-R-Way III busway Receptacles can be fix-
The adapters allow the
6 incorporation of present-
Plug-In Units
Eaton now offers a full line
and receptacle plugs help
make manufacturing and
mounted or cord-mounted
day technologies, available Cord lengths are 125 feet
of receptacle plug-in units assembly lines more flexible.
6 in Pow-R-Way III plug-in for use on Pow-R-Way III Receptacle plugs bring easy
in 1-foot increments
units, into existing busway busway. Pow-R-Way III power access for tools and
6 systems. State-of-the-art
features such as energy
receptacle plug-in units come equipment being used on
fully assembled and wired, the lines.
6 monitoring, transient voltage
surge suppression and
reducing installation time.
They are UL listed and offer For application and layout
coordination/communication assistance, and for additional
6 capabilities can all be added
a complementary line of
accessories. Eatons unique information, please contact
to existing distribution design makes them the your local Eaton sales office
6 systems without having to
upgrade and replace entire
most flexible receptacle or Eaton authorized
units in the industry. distributor.
6 runs of busway.
Data CentersData racks Fused Duplex Receptacle Fix-Mounted Single Receptacle
Special adapters to continue to process more Plug-In Unit
6 competitive busway products information at higher speeds These units allow you
are also available. Please with constantly changing to quickly add standard
6 contact the Greenwood
factory for information.
demands. Pow-R-Way III receptacle power and come
receptacle plugs offer the with the following features:
6 highest ampere ratings in
the industry. Busway and
Two fix-mounted
NEMA 5-20R or L5-20R
6 receptacle plugs above
the data racks provide faster duplex receptacles
installation, faster connectivity, Fuse protection for each
6 easier rack changes and duplex receptacle
Cord-Mounted Single Receptacle
upgrades, and will run cooler 120 V maximum,
6 than traditional cable methods. single-phase
RetailAs retail
6 environments change
meeting customer demands,
6 Pow-R-Way III busway and
receptacle plugs help make
6 floor layout and display
changes easier. Receptacle
6 plugs allow for easy power
access, eliminating costly
conduit and cable work.
6
Fix-Mounted Duplex Receptacle
6
6
6
6
6
V2-T6-8 Volume 2Commercial Distribution CA08100003EMarch 2016 www.eaton.com
Low Voltage Busway
Pow-R-Way III
6.1
Quad Receptacle Plug-In Unit SPD Plug-In Devices Not all SPD units on the It offers a centralized
These units are configured The Pow-R-Way III plug-in market have filtering alternative to individually 6
to order based upon the device product offering capabilities. The benefits of mounted wattmeters, watt-
quantity, type and size of includes a surge protective combining SPD and filtering hour meters and watt-demand 6
receptacles ordered. Any device (SPD) that is ideal for are reduced MOV stress, meters. Key advantages
combination of receptacles busway fed distribution resulting in a longer life cycle,
lower let-through voltage,
include unmatched savings
in space, lower installation
6
can be ordered and offer the systems. A transient voltage
following features: is a random, high-energy,
short duration electrical
better noise attenuation
levels and increased
costs, and the capability to
communicate data readings in 6
Two to four receptacles. anomaly. These high-energy reliability. a variety of ways. IQ Energy
Any combination and surges can disrupt, damage
Without protection devices,
Sentinels with built-in CTs 6
size of standard NEMA or destroy sensitive and communication capability
configured receptacles microprocessor-based
electronic-based loads and
microprocessors are not
have the added benefit of 6
240 V maximum, equipment. Eaton has overall system accuracy.
provided with the noise- and
three-phase developed the SPD family
of products to ensure that
disturbance-free power that
The Energy Sentinel mounts
on the load side of Eaton
6
Type CH single-pole, two- they require. Because
6
pole or three-pole circuit quality power is supplied F-, J- and K-Frame breakers
microprocessors are now within the bus plug enclosure.
breaker protection to commercial, industrial,
common in those facilities, The Energy Sentinel is also
medical and institutional
Receptacles can be fix-
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
V2-T6-10 Volume 2Commercial Distribution CA08100003EMarch 2016 www.eaton.com
Low Voltage Busway
Pow-R-Way III
6.1
Pow-R-Way III Express Bus Fittings and Accessories
Eaton continues to be a How the Program Works Corner Joint Elbows End cable tap boxes are 6
leader in providing service By using the form provided, When it comes to bends available for all ratings in the
and product solutions to its its quick and as easy as and turns in a bus run, the Express Bus program. One 6
customers. When you need a 1-2-3. Pow-R-Way III corner joint horizontal hanger will be
complete run of busway fast
1. Write in the catalog
is the most compact elbow
in the industry. Given the
included for every 10 feet of 6
to get critical electrical loads busway. Please specify
numbers and quantities
running or meet time-
sensitive deadlines, Express of the pieces needed.
complexity of todays
industrial and commercial
flatwise or edgewise.
6
Bus is the solution. distribution systems and the
2. Write in and extend the
pricing. Obtain net need to coordinate layouts 6
Product Offering with HVAC, plumbing and
multipliers from your
Indoor plug-in busway:
local sales office. lighting requirements, 6
8002500 A copper and space quickly becomes
8002000 A aluminum 3. Fax in the order sheet
with a copy of your
a critical factor. 6
Indoor feeder busway:
The Pow-R-Way III corner
8002500 A copper and
8002000 A aluminum
purchase order.
joint elbow can be installed 6
Once received, your order will in areas where traditional Corner Joint Elbows
Corner joints: be entered in the system and
shipped within 5 to 10
90-degree elbows could
never have been
6
Forward (right)
Rearward (left) working days based upon the
number of pieces ordered.
accomplished before.
6
Upward Due to its compact design,
Downward Feeder and plug-in indoor the corner joint also allows 6
Tap boxes: busway with copper for layouts that provide
End tap box
conductors are available in
10-feet and 6-feet lengths.
optimum utilization of space.
Critical section length that
6
Plug-in tap box They can be used would normally be required
Bus plugs: interchangeably without the for a traditional elbow leg 6
Fusible use of special adapters or length can now be dedicated Plug-In and Feeder Busway
Circuit breaker special splice plates, provided to maximizing usable plug-in 6
they are the same current section length.
Accessories:
6
Wall/floor flange
Hangers
with a lightweight and seismic certified and exceeds 6
rugged, two-piece all- the requirements of both the
Program Highlights aluminum extruded housing, UBC and CBC (Zone 4). The 6
Eaton will ship 12 total pieces which is rated as a 50% corner joint is UL listed for Pow-R-Bridge Assembly
of busway in 5 working days
or 24 total pieces in 10
ground path. indoor applications.
6
Copper busbars for plug-in
working days after receipt of
released order. Total pieces
applications have full-sized 6
conductor tabs welded to
are inclusive of end tap boxes
and corner joints.
their side edges to form the
plug-in contact surfaces. Tabs
6
For pricing, special requests
or needs, please contact your
are the same exact thickness
as the conductors and are 6
fully rated up to 800 A.
local Eaton sale office.
6
Plug-in units and additional
hangers are stocked and
available in the warehouse.
6
6
Corner Joint Elbows
6
6
6
6
6
6
Volume 2Commercial Distribution CA08100003EMarch 2016 www.eaton.com V2-T6-11
6.1 Low Voltage Busway
Pow-R-Way III
6 IBP = PRW
BP = Old line
(Ex. FD, JDC, KDB) Three-Pole Only Trip Rating
(Ex. 015, 060, 150, 400)
G = 50% internal
I = Isolated ground (PRWIII only)
N2 = 200% neutral (PRWIII only)
ZN = Low Z (old line only)
6
Fusible Unit
6
P3F 3 6 4 R G N H
6
6
Bus Style Mounting Options for
P3F = PRWIII Three-Pole Only Neutral Option P3F (30200 A Only)
ITAP = PRW Voltage N = 100% neutral H = Horizontal
6 TAP = Old line 6 = 600 V
2 = 240 V
Amps Fuse Clips N2 = 200% neutral (PRWIII only)
ZN = Low Z (old line only)
V = Vertical
1 = 30 H, J, or R 600 A
6 2 = 60
3 = 100
T or L for 800 A
Ground Option
4 = 200
6 5 = 400
6 = 600
G = 50%
I = Isolated (PRWIII only)
7 = 800
6
6 SPD Series Bus Plug
6 Surge Rating
(kA/Phase)
Voltage Code
208Y = 208Y/120 V (4W + G) Option Code
50 200 400Y = 400Y/230 V (4W + G) 1 = BasicDual-colored LED per phase to indicate protection status of the N-G mode on units
6 80 250 480Y = 480Y/277 V (4W + G)
600Y = 600Y/347 V (4W + G)
with a neutral wire, single-colored LED to indicate the lack of a neutral wire connection on
100 300 systems with a neutral wire.
6 120 400 240D = 240 Delta (3W + G) 2 = StandardDual-colored LED per phase to indicate protection status of the N-G mode on
160 480D = 240 Delta (3W + G) units with a neutral wire, single-colored LED to indicate the lack of a neutral wire connection
600D = 240 Delta (4W + G) on systems with a neutral wire, audible alarm with silence button and Form C relay contact.
6 3 = Standard + Surge CounterDual-colored LED per phase to indicate protection status of the
N-G mode on units with a neutral wire, single-colored LED to indicate the lack of a neutral
wire connection on systems with a neutral wire, audible alarm with silence button, Form C
6 relay contact, EMI/RFI filtering providing up to 50 dB of noise attenuation from 10 kHz to
100 MHz and surge counter with reset button.
6
6 NEMA Receptacle Configuration
L 5 15 R
6
6 Blade
Blank = Straight blade Voltage Amps
Receptacle Type
R = Receptacle
6 L = Locking blade 1
2
= 125 V, two-pole, two-wire
= 250 V, two-pole, two-wire
11 = 250 V, three-pole, three-wire
14 = 25/250 V, three-pole, four-wire
15
20
40
50
C = Cord receptacle
6 Notes
H clips are standard for PRW and old line unless specified by adding R in catalog number.
6 Please call Greenwood low voltage busway department for help in assigning a catalog number for a specific application.
Do not leave spaces between characters. Example: P3BFD3100N; ITAP361N.
6 All plug-in units come fully assembled.
Breaker Frame
Ampere
Rating
Plug-In Enclosure
Catalog Number 1
100% Neutral Stab
Catalog Number
Ground Stab
Catalog Number
Ground Stab
Catalog Number
200% Neutral Stab
Catalog Number
6
ED, EDH, EHD, EDC,
FDB, FD, HFD, FDC
10225 P3BFD P3FDN100 P3FG100 P3FDI100 P3FD2N100 6
P3FDN225 P3FDI225 P3FD2N225
Horizontal Install JDB, JD, HJD, JDC 70250 P3BJD P3JDN150 P3JDI150 P3JD2N150 6
(Rear View)
P3JDN250 P3JDG250 P3JDI250 P3JD2N250
KDB, KD, DK, HKD, KDC 100400 P3BKD P3KDN400 P3KDG400 P3KDI400 P3KD2N400
6
LDB, LD, HLD, LDC 300600 P3BLD P3MDN800 P3MDG800 P3MDI800
6
MDL, HMDL 400800 P3BMD P3MDN800 P3MDG800 P3MDI800
ND, HND, NDC 400800 P3BND P3NDN800 P3NDG800 P3NDI800 6
FB TRI-PAC 15100 P3BFBP P3FBPN100 P3FBPG100 P3BFBPI100
LA TRI-PAC 75400 P3BLAP P3LAPN400 P3LAPG400 P3LAPI400 6
6
NB TRI-PAC 500800 P3BNBP P3NBPN800 P3NBPG800 P3BNBPI800
2 2 2 2
30 (Vertical) P3F361RGV P3F321RGV
6 60 (Horizontal) P3F362RGH P3F322RGH 2 2 2 2
6
2 2 2 2
60 (Vertical) P3F362RGV P3F322RGV
2 2 2 2
100 (Horizontal) P3F363RGH P3F323RGH
2 2 2 2
200 (Horizontal) P3F364RGH P3F324RGH
6 200 (Vertical) P3F364RGV P3F324RGV 2 2 2 2
Fuses are not included Plug-in unit, neutral and If J-Fuse clips are required,
6 Mechanical lugs are ground are ordered and replace R in the catalog
provided. Compression shipped assembled number with a J
6 lugs are available for Note: See Page V2-T6-14 for
plug assembled style number
(30600 A, 600 V only)
fusible plug-in units rated 800 A, 600 V also available
6 at 400 A and above. If
compression lugs are
configuration.
Housing ground connection
with L-Fuse clips; replace
T in the catalog number
6 required, the cable size
must be specified
supplied as standard at no
additional charge
with L
as standard
6
Pow-R-Way III Plug Special Industry Fusible Plug-In Units
6 (Rear View)
Enclosure 50% Internal 50% Isolated Terminal Kit Compression Lugs
6
Ampere 600 V 100% Neutral Stab Ground Stab Ground Stab Number Wire Catalog
Rating Catalog Number Catalog Number Catalog Number Catalog Number Per Phase Size Number
30 P3F361H 3 3 3 1 1#12 to #10 CTK30SC
6 60 P3F362H 3 3 3 1 1#8 CTK60SC
6 100 P3F363H 3
3
3
3
3
3
1 1#4 CTK100SC
200 P3F364H 1 12/0 CTK200BSC
6 Notes
1 H and V do not denote mounting orientation of the bus plug. Horizontal (H) and Vertical (V) refer to the orientation of the bus system that the plug
6
6
6
V2-T6-16 Volume 2Commercial Distribution CA08100003EMarch 2016 www.eaton.com
Low Voltage Busway
Pow-R-Way III
6.1
Special Plug-In Units
6
Plug-In Cable Tap Box Units 6
Plug-in Cable Tap Box
Ampere 600 V Enclosure 100% Neutral Stab 50% Internal Ground Stab 50% Isolated Ground Stab 6
Rating Catalog Number Catalog Number Catalog Number Catalog Number
200 P3PTB200 P3PTBN200 P3PTBG200 P3PTBI200 6
400 P3PTB400 P3PTBN400 P3PTBG400 P3PTBI400
600 P3PTB600 P3PTBN600 P3PTBG600 P3PTBI600 6
800 P3PTB800 P3PTBN800 P3PTBG800 P3PTBI800
6
Mechanical lugs are
provided. If compression 6
lugs are required, the cable
size must be specified
6
Plug-In Combination Starters and Contactors (Non-Reversing, Three-Pole)
6
NEMA
Size
Freedom Starter
Fusible Circuit Breaker
Freedom Contact
Fusible Circuit Breaker
Advantage Starter
Fusible Circuit Breaker
Advantage Contact
Fusible Circuit Breaker
6
0 P3FSTR0F P3BSTR0F P3FCON0F P3BCON0F P3FSTR0A P3BSTR0A P3FCON0A P3BCON0A 6
1 P3FSTR1F P3BSTR1F P3FCON1F P3BCON1F P3FSTR1A P3BSTR1A P3FCON1A P3BCON1A
2 P3FSTR2F P3BSTR2F P3FCON2F P3BCON2F P3FSTR2A P3BSTR2A P3FCON2A P3BCON2A 6
6
3 P3FSTR3F P3BSTR3F P3FCON3F P3BCON3F P3FSTR3A P3BSTR3A P3FCON3A P3BCON3A
4 P3FSTR4F P3BSTR4F P3FCON4F P3BCON4F P3FSTR4A P3BSTR4A P3FCON4A P3BCON4A
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
Volume 2Commercial Distribution CA08100003EMarch 2016 www.eaton.com V2-T6-17
6.1 Low Voltage Busway
Pow-R-Way III
Bolt-On Units
6
6 Circuit Breaker Bolt-On Units
6
Breaker Ampere Bolt-On Enclosure 100% Neutral Stab 50% Internal Ground Stab 50% Isolated Ground Stab
Frame Rating Catalog Number Catalog Number Catalog Number Catalog Number
EHD, FDB, FD, HFD, FDC 15225 P3BFDBO P3FDNBO P3FDGBO P3FDIBO
6 JDB, JD, HJD, JDC 70250 P3BJDBO P3FJDNBO P3JDGBO P3JDIBO
6 100
200
P3F363BO
P3F364BO
P3FN100BO
P3FN250BO
P3FG100BO
P3FG250BO
P3FI100BO
P3FI250BO
6
1200 P3F369BO P3FN1200BO P3FG1200BO P3FI1200BO
6 Maximum Voltage
600
Catalog Number
P3GND
6
6
6
6
6
6
6
6
V2-T6-18 Volume 2Commercial Distribution CA08100003EMarch 2016 www.eaton.com
Low Voltage Busway
Pow-R-Way III
6.1
Technical Data and Specifications
6
Ratings Construction B. Busbars shall be Housing
A. The busway shall A. The busway and insulated over their A. The busway housing shall 6
be Eatons type associated fittings shall entire length, except at be a two-piece design
Pow-R-Way III: [three- consist of [aluminum] joints and contact
surfaces, with a UL-
fabricated from extruded 6
phase, three-wire] [three- [copper] conductors aluminum. The two-piece
phase, three-wire with
50% housing ground
totally enclosed in a two-
piece extruded aluminum
listed insulating material
consisting of epoxy
housing shall be bolted
together along the
6
applied by fluidized bed
and/or 50% internal
ground] [three-phase,
housing. Outdoor feeder,
indoor feeder and indoor process. Tape or heat-
bottom flange. The
busway enclosure finish 6
three-wire with 50% plug-in busway shall be shrink sleeve insulation, shall be ANSI 61 gray
housing ground and/or interchangeable at the or any other method of baked epoxy powder 6
50% isolated ground] same rating without the insulation that can allow paint applied by an
three-phase, four-wire use of adapters or air gaps or insulation
breakdown, shall not
electrostatic process. 6
with 100% neutral] special splice plates.
B. Outdoor feeder busway
[three-phase, four-wire
with 100% neutral, 50%
Fittingssuch as
elbows, tees, flanges,
be acceptable.
housing shall be identical 6
C. The busway shall be to indoor feeder busway
housing and/or 50% etc.shall be identical
internal ground] [three- for use with both the
capable of carrying rated
current continuously
housings, and shall be 6
phase, four-wire with plug-in and feeder types UL listed for outdoor use.
100% neutral, 50% of busway. The busway
without exceeding a
temperature rise of 55 C Plug-In Busway
6
housing and/or 50% shall be capable of being based on a 40 C ambient.
isolated ground] [three-
phase, four-wire with
mounted flatwise,
edgewise or vertically
A. Where required, busway
shall be of the plug-in
6
Bus Joints type. Plug-in busway
200% neutral] [three-
phase, four-wire with
without derating. The
busway shall consist of
A. Each busway section shall be available in 6
200% neutral, 50% shall be furnished standard 2-, 4-, 6-, 8-
standard 10 ft (3 m)
housing ground, and/or sections with special complete with joint
hardware and covers.
and 10-foot lengths, 6
50% internal ground] sections and fittings with plug-in openings
[three-phase, four-wire provided to suit the
The busway joints shall
be a single-bolt, non-
provided on both sides
of the busway sections
6
with 200% neutral, 50% installation. Horizontal
rotating, removable
housing ground, and/or
50% isolated ground]
runs shall be suitable for
hanging on 10 ft (3 m)
bridge design. All bridge
on 2 ft (0.6 m) centers.
Plug-in covers shall 6
joints shall be furnished prevent dirt and debris
with voltage and current
ratings as indicated on
maximum centers.
Vertical runs shall be
with torque-indicating from entering contact 6
the contract drawings. double-head joint bolts plug-in openings in the
suitable for mounting on
B. The busway shall have
16 ft (4 m) maximum and Belleville washers.
The bridge joint shall
busway. The design shall 6
centers. Provide one allow for 10 hinged cover
a minimum of 6-cycle
short-circuit rating of
hanger for every 10 ft
utilize a captive nut
retainer on the opposite
outlets per 10 ft (3 m) of
plug-in length. Covers
6
(3 m) of horizontally
85 kA rms symmetrical side of the torque
for ratings through
mounted duct. On
vertical runs, provide indicating bolt. The
for plug-in openings
shall have a positive 6
800 A, 100 kA rms bridge joint design shall screw close feature
one adjustable hanger
symmetrical for ratings per floor.
ensure proper installation and provisions for the 6
through 1350 A, 125 kA without the use of a installation of power
rms symmetrical for
ratings through 1600 A,
Bus torque wrench, and
provide visual indication
company seals. The
contact surfaces for
6
A. Busbars shall be that the joint is properly
150 kA rms symmetrical
for ratings through
fabricated from high torqued. Each busway
bus plug stabs shall be
silver-plated of the same
6
strength, [57% joint shall allow for
2500 A, and 200 kA rms material, thickness and
symmetrical for ratings
conductivity aluminum]
[99% conductivity
a minimum length rating as the stab bars. 6
through 5000 A. adjustment of The stabs shall be
copper] and suitably
plated at all electrical
0.5 inches (12.7 mm).
De-energization of
welded to the busbars. 6
contact surfaces. A standard housing
busway shall not be
required for safe testing
ground connection
shall be supplied in each
6
of joint tightness. plug-in opening. Positive
mechanical guides for 6
plug-in units shall be
provided at each plug-in 6
opening to facilitate unit
alignment and prevent 6
improper installation.
6
6
Volume 2Commercial Distribution CA08100003EMarch 2016 www.eaton.com V2-T6-19
6.1 Low Voltage Busway
Pow-R-Way III
6
stabs make contact with Standard 489. It shall be 1600 125,000
the busbars. All plug-in possible to increase the
units shall be equipped 2000 150,000
6
interrupting rating of a
with a defeatable breaker plug-in device 2500 150,000
interlock to prevent the having ampere ratings
6
3200 200,000
cover from being opened through 400 A up to
while the switch is in the 4000 200,000
100 kAIC at 480 Vac and
6 ON position and prevent
accidental closing of the
200 kAIC at 240 Vac by
changing out the circuit
5000 200,000
6 4000 200,000
5000
6
6
6
6
6
6
6
6
V2-T6-20 Volume 2Commercial Distribution CA08100003EMarch 2016 www.eaton.com
Low Voltage Busway
Pow-R-Way III
6.1
Pow-R-Way III Plug-In Busway Pow-R-Way III Feeder Busway
2255000 A copper 2255000 A copper 6
2254000 A aluminum 2254000 A aluminum
6
Straight sections of plug-in busway are made only in 24-inch Straight sections of feeder busway can be supplied in
(609.6 mm) incremental lengths with a maximum length of
10 ft (3 m). Page V2-T6-25 depicts the configuration of plug-in
any length, at 1/8-inch (3.2 mm) increments, from a
16-inch (406.4 mm) minimum to a 10 ft (3 m) maximum.
6
busway and Pow-R-Bridge for the available ampere ratings. See
table below for reference to the proper configuration. Available
Page V2-T6-25 illustrates the configuration of feeder busway and
Pow-R-Bridge for the available ampere ratings. See table below 6
in indoor and sprinkler-proof ratings. for reference to the proper configuration.
6
Configuration Feeder Busway Configuration
Ampere Rating Ampere Rating
6
6
UL 857 IEC 439 Configuration UL 857 IEC 439 Configuration
Cu Al Cu (see Page V2-T6-25) Cu Al Cu (see Page V2-T6-25)
225 225 225 A 225 225 225 A
6
400 400 400 A 400 400 400 A
600 630 630 A 600 600 630 A 6
800 800 1000 A 800 800 1000 A
1000 1000 1200 A 1000 1000 1200 A 6
6
1200 1200 1400 A 1200 1200 1400 A
1350 1350 1550 A 1350 1350 1550 A
1600 1800 A 1600 1800 A
6
2000 2250 A 2000 2250 A
1600 B 1600 B 6
2500 2000 3000 B 2500 2000 3000 B
3200 3800 C 3200 3800 C 6
4000
2500
3200
4500
C
D
4000
2500
3200
4500
C
D
6
5000 4000 5800 D 5000 4000 5800 D 6
Each section will include one factory-installed Pow-R-Bridge
mounted to the left end of the busway (with the T to the top, 6
IEC 60529 IP Ratings when viewing the bus from the F side). Each Pow-R-Bridge
IEC 529
IP Rating Busway Type
will have a T label, which must always match the T 6
orientation of the busway. Available in indoor, sprinkler-proof
IP2X Pow-R-Way III plug-in busway; plug-in outlet protects against access
to live parts
and outdoor ratings. See IEC 60529 IP Ratings table to the left
for details.
6
IP40 Pow-R-Way III indoor plug-in and feeder busway 6
IP55 Pow-R-Way III sprinkler-proof plug-in busway
IP66 Pow-R-Way III outdoor feeder busway 6
6
IEC 60529 Degrees of Protection
IEC 529 6
IP Rating Description
IP40 Protection against access to hazardous parts with a wire or solid foreign 6
object 1 mm diameter. No protection against water.
IP55 Protection against access to hazardous parts with a wire and dust shall 6
not penetrate in quantity to interfere with satisfactory operation or impair
safety. Protects against water jets.
6
IP66 Protection against access to hazardous parts with a wire and dust shall
not penetrate in quantity to interfere with satisfactory operation or impair
safety. Protects against powerful water jets. 6
6
6
6
Volume 2Commercial Distribution CA08100003EMarch 2016 www.eaton.com V2-T6-21
6.1 Low Voltage Busway
Pow-R-Way III
6 110150
1560
18
65
14
35
14
18
FDB
FD
70100
110150
65
65
ELHFD
ELHFD
6
15100 200 150 FCL
Integrally Fused, Current-Limiting Circuit Breaker
100225 65 ED
Interrupting Rating (kA Symmetrical)
6 100225 100 EDH Ampere
Rating 240 Vac 480 Vac 600 Vac
Breaker
Type
100225 200 EDC
6 70225 65 35 18 JD, JDB
15100
125225
200
200
200
200
200
200
FB-P
LA-P
250 65 35 18 JD, JDB
6 70225 100 65 25 HJD
250400 200 200 200 LA-P
400600 200 200 200 NB-P
6 250
70225
100
200
65
100
25
35
HJD
JDC
700800 200 200 200 NB-P
6
400800 65 50 25 MDL 800 100 250 200 500 250 500
400800 100 65 35 HMDL
6 400800 65 50 25 ND
400800 100 65 35 HND
6 400800 200 100 50 NDC
6001200 65 50 25 ND
6 6001200 100 65 35 HND
6
V2-T6-22 Volume 2Commercial Distribution CA08100003EMarch 2016 www.eaton.com
Low Voltage Busway
Pow-R-Way III
6.1
Dimensions
Approximate Dimensions in Inches (mm) 6
Busbar and Housing 6
Three-Wire with No Neutral 6
Wire Designation and Housing Size
Ampere Rating Phase Bar Size
Bar
Per 50% Integral Housing Ground 3WH 50% Internal Ground Bus 3WHG 50% Internal Isolated Ground 3WI 6
Cu Al Depth Width Phase Width Height Width Height Width Height Figure 1
225 225 0.25 (6.4) 1.62 (41.1) 1 4.75 (120.7) 4.38 (111.3) 4.75 (120.7) 4.50 (114.3) 4.75 (120.7) 4.55 (115.6) A
6
400 400 0.25 (6.4) 1.62 (41.1) 1 4.75 (120.7) 4.38 (111.3) 4.75 (120.7) 4.50 (114.3) 4.75 (120.7) 4.55 (115.6) A
6
600 0.25 (6.4) 1.62 (41.1) 1 4.75 (120.7) 4.38 (111.3) 4.75 (120.7) 4.50 (114.3) 4.75 (120.7) 4.55 (115.6) A
800 600 0.25 (6.4) 1.62 (41.1) 1 4.75 (120.7) 4.38 (111.3) 4.75 (120.7) 4.50 (114.3) 4.75 (120.7) 4.55 (115.6) A 6
1000 0.25 (6.4) 2.25 (57.2) 1 5.38 (136.7) 4.38 (111.3) 5.38 (136.7) 4.50 (114.3) 5.38 (136.7) 4.55 (115.6) A
1200 800 0.25 (6.4) 2.75 (70.0) 1 5.88 (149.4) 4.38 (111.3) 5.88 (149.4) 4.50 (114.3) 5.88 (149.4) 4.55 (115.6) A 6
6
1350 1000 0.25 (6.4) 3.25 (82.3) 1 6.38 (162.10) 4.38 (111.3) 6.38 (162.1) 4.50 (114.3) 6.38 (162.10) 4.55 (115.6) A
1600 1200 0.25 (6.4) 4.25 (108.0) 1 7.38 (187.5) 4.38 (111.3) 7.38 (187.5) 4.50 (114.3) 7.38 (187.5) 4.55 (115.6) A
2000 1350 0.25 (6.4) 5.50 (139.7) 1 8.64 (219.5) 4.38 (111.3) 8.64 (219.5) 4.50 (114.3) 8.64 (219.5) 4.55 (115.6) A
6
1600 0.25 (6.4) 6.25 (158.8) 1 9.40 (238.8) 4.38 (111.3) 9.40 (238.8) 4.50 (114.3) 9.40 (238.8) 4.55 (115.6) A
2500 2000 0.25 (6.4) 8.00 (203.2) 1 11.17 (283.7) 4.38 (111.3) 11.17 (283.7) 4.50 (114.3) 11.17 (283.7) 4.55 (115.6) A 6
3200 0.25 (6.4) 4.25 (108.0) 2 16.14 (410.0) 4.38 (111.3) 16.14 (410.0) 4.50 (114.3) 16.14 (410.0) 4.55 (115.6) B
4000 2500 0.25 (6.4) 5.50 (139.7) 2 18.64 (473.5) 4.38 (111.3) 18.64 (473.5) 4.50 (114.3) 18.64 (473.5) 4.55 (115.6) B 6
5000
3200
4000
0.25 (6.4)
0.25 (6.4)
6.25 (158.8)
8.00 (203.2)
2
2
20.16 (512.0)
23.70 (602.0)
4.38 (111.3)
4.38 (111.3)
20.16 (512.0)
23.70 (602.0)
4.50 (114.3)
4.50 (114.3)
20.16 (512.0)
23.70 (602.0)
4.55 (115.6)
4.55 (115.6)
B
B
6
6
Four-Wire with 100% Neutral
6
Phase and Neutral Wire Designation and Housing Size
Bar
Ampere Rating Bar Size Per 50% Integral Housing Ground 4WH 50% Internal Ground 4WHG 50% Internal Isolated Ground 4WI 6
Cu Al Depth Width Phase Width Height Width Height Width Height Figure 1
225 225 0.25 (6.4) 1.62 (41.1) 1 4.75 (120.7) 4.38 (111.3) 4.75 (120.7) 4.50 (114.3) 4.75 (120.7) 4.55 (115.6) A 6
400 400 0.25 (6.4) 1.62 (41.1) 1 4.75 (120.7) 4.38 (111.3) 4.75 (120.7) 4.50 (114.3) 4.75 (120.7) 4.55 (115.6) A
600 0.25 (6.4) 1.62 (41.1) 1 4.75 (120.7) 4.38 (111.3) 4.75 (120.7) 4.50 (114.3) 4.75 (120.7) 4.55 (115.6) A 6
800
1000
600
0.25 (6.4)
0.25 (6.4)
1.62 (41.1)
2.25 (57.2)
1
1
4.75 (120.7)
5.38 (111.3)
4.38 (111.3)
4.38 (111.3)
4.75 (120.7)
5.38 (111.3)
4.50 (114.3)
4.50 (114.3)
4.75 (120.7)
5.38 (111.3)
4.55 (115.6)
4.55 (115.6)
A
A
6
1200 800 0.25 (6.4) 2.75 (70.0) 1 5.88 (149.4) 4.38 (111.3) 5.88 (149.4) 4.50 (114.3) 5.88 (149.4) 4.55 (115.6) A 6
1350 1000 0.25 (6.4) 3.25 (82.3) 1 6.38 (162.1) 4.38 (111.3) 6.38 (162.1) 4.50 (114.3) 6.38 (162.1) 4.55 (115.6) A
1600 1200 0.25 (6.4) 4.25 (108.0) 1 7.38 (187.5) 4.38 (111.3) 7.38 (187.5) 4.50 (114.3) 7.38 (187.5) 4.55 (115.6) A 6
2000 1350 0.25 (6.4) 5.50 (139.7) 1 8.64 (219.5) 4.38 (111.3) 8.64 (219.5) 4.50 (114.3) 8.64 (219.5) 4.55 (115.6) A
1600 0.25 (6.4) 6.25 (158.8) 1 9.40 (238.8) 4.38 (111.3) 9.40 (238.8) 4.50 (114.3) 9.40 (238.8) 4.55 (115.6) A
6
2500 2000 0.25 (6.4) 8.00 (203.2) 1 11.17 (283.7) 4.38 (111.3) 11.17 (283.7) 4.50 (114.3) 11.17 (283.7) 4.55 (115.6) A
6
3200 0.25 (6.4) 4.25 (108.0) 2 16.14 (410.0) 4.38 (111.3) 16.14 (410.0) 4.50 (114.3) 16.14 (410.0) 4.55 (115.6) B
4000 2500 0.25 (6.4) 5.50 (139.7) 2 18.64 (473.5) 4.38 (111.3) 18.64 (473.5) 4.50 (114.3) 18.64 (473.5) 4.55 (115.6) B 6
3200 0.25 (6.4) 6.25 (158.8) 2 20.16 (512.0) 4.38 (111.3) 20.16 (512.0) 4.50 (114.3) 20.16 (512.0) 4.55 (115.6) B
5000 4000 0.25 (6.4) 8.00 (203.2) 2 23.70 (602.0) 4.38 (111.3) 23.70 (602.0) 4.50 (114.3) 23.70 (602.0) 4.55 (115.6) B 6
Note
1 Refer to drawing on Page V2-T6-24.
6
6
6
6
6
Volume 2Commercial Distribution CA08100003EMarch 2016 www.eaton.com V2-T6-23
6.1 Low Voltage Busway
Pow-R-Way III
6
Phase Bar Size Wire Designation and Housing Size
Neutral Bar is Bar
Ampere Rating 0.5 (12.7) x Width Shown Per 50% Integral Housing Ground 4WNH 50% Internal Ground Bus 4WNG 50% Internal Isolated Ground 4WNI
6 Cu Al Depth Width Phase Width Height Width Height Width Height Figure
225 225 0.25 (6.4) 1.62 (41.1) 1 4.75 (120.7) 4.92 (125.0) 4.75 (120.7) 5.05 (128.3) 4.75 (120.7) 5.10 (129.5) A
6 400 400 0.25 (6.4) 1.62 (41.1) 1 4.75 (120.7) 4.92 (125.0) 4.75 (120.7) 5.05 (128.3) 4.75 (120.7) 5.10 (129.5) A
6
600 0.25 (6.4) 1.62 (41.1) 1 4.75 (120.7) 4.92 (125.0) 4.75 (120.7) 5.05 (128.3) 4.75 (120.7) 5.10 (129.5) A
800 600 0.25 (6.4) 1.62 (41.1) 1 4.75 (120.7) 4.92 (125.0) 4.75 (120.7) 5.05 (128.3) 4.75 (120.7) 5.10 (129.5) A
6 1000 0.25 (6.4) 20.25 (57.2) 1 5.38 (136.7) 4.92 (125.0) 5.38 (136.7) 5.05 (128.3) 5.38 (136.7) 5.10 (129.5) A
1200 800 0.25 (6.4) 2.75 (70.0) 1 5.88 (149.4) 4.92 (125.0) 5.88 (149.4) 5.05 (128.3) 5.88 (149.4) 5.10 (129.5) A
6 1350 1000 0.25 (6.4) 30.25 (82.3) 1 6.38 (162.1) 4.92 (125.0) 6.38 (162.1) 5.05 (128.3) 6.38 (162.1) 5.10 (129.5) A
1600 1200 0.25 (6.4) 40.25 (108.0) 1 7.38 (187.5) 4.92 (125.0) 7.38 (187.5) 5.05 (128.3) 7.38 (187.5) 5.10 (129.5) A
6 2000 1350 0.25 (6.4) 5.50 (139.7) 1 8.64 (219.5) 4.92 (125.0) 8.64 (219.5) 5.05 (128.3) 8.64 (219.5) 5.10 (129.5) A
6
2500
1600
2000
0.25 (6.4)
0.25 (6.4)
60.25 (158.8) 1
8.00 (203.2) 1
9.40 (238.8)
11.17 (283.7)
4.92 (125.0)
4.92 (125.0)
9.40 (238.8)
11.17 (283.7)
5.05 (128.3)
5.05 (128.3)
9.40 (238.8)
11.17 (283.7)
5.10 (129.5)
5.10 (129.5)
A
A
6 3200 0.25 (6.4) 40.25 (108.0) 2 16.14 (410.0) 4.92 (125.0) 16.14 (410.0) 5.05 (128.3) 16.14 (410.0) 5.10 (129.5) B
4000 2500 0.25 (6.4) 5.50 (139.7) 2 18.64 (473.5) 4.92 (125.0) 18.64 (473.5) 5.05 (128.3) 18.64 (473.5) 5.10 (129.5) B
6 3200 0.25 (6.4) 60.25 (158.8) 2 20.16 (512.0) 4.92 (125.0) 20.16 (512.0) 5.05 (128.3) 20.16 (512.0) 5.10 (129.5) B
6
5000 4000 0.25 (6.4) 8.00 (203.2) 2 23.70 (602.0) 4.92 (125.0) 23.70 (602.0) 5.05 (128.3) 23.70 (602.0) 5.10 (129.5) B
Height C
N
Height
B
C
B
C
N N
6
6
Figure A
Figure B
6 2252000 A Aluminum
2252500 A Copper
25004000 A Aluminum
32005000 A Copper
6
6
6
6
6
6
6
6
6
6
V2-T6-24 Volume 2Commercial Distribution CA08100003EMarch 2016 www.eaton.com
Low Voltage Busway
Pow-R-Way III
6.1
Approximate Dimensions in Inches (mm)
6
Plug-In Busway Feeder Busway
CL 12.00 24.00 Spacing 12.00 CL CL CL 6
(304.8) (609.6) (304.8)
CL CL
T T 6
T T
F Configuration A Top View
1 Bar Per Phase
F 6
F Configuration A Top View F
1 Bar Per Phase
6
CL CL CL CL
24.00 Spacing CL CL
12.00
(304.8) (609.6)
12.00
(304.8) 6
T T
6
T T
F F
6
Configuration B Top View
F Configuration B Top View
1 Bar Per Phase
F 1 Bar Per Phase
6
6
CL 12.00 24.00 Spacing 12.00 CL CL CL
(304.8) (609.6) (304.8)
CL CL
6
T T 6
T T
F Configuration C Top View F
2 Bars Per Phase
6
F Configuration C Top View F
2 Bars Per Phase
CL CL 6
CL CL C
12.00 24.00 Spacing L 12.00
(304.8) (609.6) (304.8) 6
6
6
6
T T
T T
F
Configuration D Top View
F
6
2 Bars Per Phase
F F
Configuration D Top View
2 Bars Per Phase CL CL
6
16.00 Minimum
CL
12.00 24.00 Spacing 12.00
(406.4)
6
(304.8) (609.6) (304.8) T T
CL CL
T
F
T
F
F F
6
Front View 6
Front View
6
The table below illustrates the quantity of plug-in openings per
side that are available per standard section. 6
Number of Plug-In Openings 6
Number of Plug-In Openings
Duct Length Front Back 6
24.00 (609.6) 1 1
48.00 (1219.2) 2 2 6
72.00 (1828.8)
96.00 (2438.4)
3
4
3
4
6
120.00 (3048.0) 5 5 6
Volume 2Commercial Distribution CA08100003EMarch 2016 www.eaton.com V2-T6-25
6.1 Low Voltage Busway
Pow-R-Way III
6
6
6 8.61
(218.7)
6
6
6
6
Single Receptacle Unit
6 10.21
(259.3)
6
6 6.86
(174.2)
6 8.61
(218.7)
6
6 10.21
(259.3)
6
6
6
6
6
6
6
6
6
6
6
6
6
6
V2-T6-26 Volume 2Commercial Distribution CA08100003EMarch 2016 www.eaton.com
Low Voltage Busway
Pow-R-Way III
6.1
Approximate Dimensions in Inches (mm)
6
Plug-In UnitsPhysical Data
Bus Plugs 6
A B
ON
6
6
Guide Pin
C
ON
6
OFF
ON
OFF
OFF
Plug-In
Handle C
L
C
L C
L Clamp
6
E F Plug-In Opening
6
Opening and Guide
D and B
Plug-In Units
Dimensions Approx. 6
Max. Max. Mechanical Terminal Weights
Plug-In Unit Amperes Vac A B C D E F Wire Range Per Phase (mm2) Lbs (kg) 6
Circuit Breaker Plug-In Units
P3BFD 225 600 21.20 (538.5) 12.36 (314.0) 5.43 (138.0) 4.00 (101.6) 6.25 (158.8) 6.06 (153.7) 100A(1) #141/0 (2.550) 25 (11.3) 6
(E- & F-Frame) 150A(1) #44/0 (2595)
P3BJD
(J-Frame)
250 600 23.26 (590.8) 12.36 (314.0) 6.97 (177.0) 4.00 (101.6) 10.44 (265.2) 6.06 (153.7) 250A(1) #14350 kcmil (25185)
225A(1) 3350 kcmil (35185)
47 (21.3) 6
P3BKD
(K-Frame)
400 600 34.41 (874.0) 13.29 (337.6) 7.79 (197.9) 4.00 (101.6) 12.56 (319.0) 6.64 (168.7) 350A(1) 250500 kcmil (120240)
400A(2) 3/0250 kcmil (45120)
53 (24.0)
6
P3BLD
(L-Frame)
600 600 41.91 (1064.5) 19.65 (499.1) 10.15 (257.8) 4.00 (101.6) 17.38 (441.5) 9.83 (249.7) 400A(1) 4/0600 kcmil (120300)
600A(2) 400500 kcmil (185240)
75 (34.0)
6
P3BMDL 800 600 45.89 (1165.6) 19.65 (499.1) 10.15 (257.8) 4.00 (101.6) 17.38 (441.5) 9.83 (249.7) 600A(2) #1500 kcmil (50240) 136 (61.7)
(MDL-Frame) 800A(2) 500750 kcmil (300400) 6
P3BND 800 600 45.98 (1167.9) 19.65 (499.1) 10.15 (257.8) 4.00 (101.6) 17.38 (441.5) 9.83 (249.7) 700A(2) # 1500 kcmil (50240) 138 (62.6)
(N-Fame) 800A(3) 3/0400 kcmil (95185) 6
P3BLAP 400 600 45.89 (1165.6) 19.65 (499.1) 10.15 (257.8) 4.00 (101.6) 13.80 (350.5) 9.83 (249.7) 225A(1) #6350 kcmil (16185) 96 (43.5)
(TRI-PAC) 400A(1) #4250 kcmil and
(1) 3/0600 kcmil (25120 and 95300) 6
6
P3BLCL 400 600 41.86 (1063.2) 19.65 (499.1) 10.15 (257.8) 4.00 (101.6) 13.80 (350.5) 9.83 (249.7) (1) #4250 kcmil (25120) and 88 (39.9)
(1) 3/0600 kcmil (95300)
Fusible Plug-In Units
P3F321RGH 30 240 14.72 (373.9) 13.92 (353.7) 8.46 (214.8) 3.85 (97.7) 7.95 (202.0) 5.66 (143.7) Cu (1) #14#3 (2.535) 32 (14.5) 6
6
P3F321RGV 30 240 15.85 (402.5) 14.03 (356.3) 8.46 (214.8) 3.85 (97.7) 6.72 (170.6) 5.66 (143.7) Al (1) #12#2 (3.235) 32 (14.5)
P3F361RGH 30 600 14.72 (373.9) 13.92 (353.7) 8.46 (214.8) 3.85 (97.7) 7.95 (202.0) 5.66 (143.7) Cu (1) #14#3 (2.535) 32 (14.5)
P3F361RGV
P3F322RGH
30
60
600
240
15.85 (402.5)
14.88 (377.9)
14.03 (356.3)
17.92 (455.3)
8.46 (214.8)
8.37 (212.5)
3.85 (97.7)
3.85 (97.7)
6.72 (170.6)
11.95 (303.6)
5.66 (143.7)
5.66 (143.7)
Al (1) #12#2 (3.235)
Cu (1) #14#3 (2.535)
32 (14.5)
40 (18.1)
6
P3F322RGV
P3F362RGH
60
60
240
600
19.85 (504.1)
14.88 (377.9)
14.16 (359.6)
17.92 (455.3)
8.37 (212.5)
8.37 (212.5)
3.85 (97.7)
3.85 (97.7)
6.84 (173.8)
11.95 (303.6)
5.66 (143.7)
5.66 (143.7)
Al (1) #12#2 (3.235)
Cu (1) #141/0 (2.550)
40 (18.1)
40 (18.1)
6
P3F362RGV
P3F323RGH
60
100
600
240
19.85 (504.1)
14.88 (377.9)
14.16 (359.6)
17.92 (455.3)
8.37 (212.5)
8.37 (212.5)
3.85 (97.7)
3.85 (97.7)
6.84 (173.8)
11.95 (303.6)
5.66 (143.7)
5.66 (143.7)
Al (1) #121/0 (3.250)
Cu (1) #141/0 (2.550)
40 (18.1)
40 (18.1)
6
P3F323RGV 100 240 19.85 (504.1) 14.16 (359.6) 8.37 (212.5) 3.85 (97.7) 6.84 (173.8) 5.66 (143.7) Al (1) #121/0 (3.250) 40 (18.1) 6
P3F363RGH 100 600 14.88 (377.9) 17.92 (455.3) 8.37 (212.5) 3.85 (97.7) 11.95 (303.6) 5.66 (143.7) Cu (1) #4250 kcmil (25120) 40 (18.1)
P3F363RGV 100 600 19.85 (504.1) 14.16 (359.6) 8.37 (212.5) 3.85 (97.7) 6.84 (173.8) 5.66 (143.7) Al (1) #4250 kcmil (25120) 40 (18.1) 6
P3F324RGH 200 240 17.42 (442.5) 21.98 (558.3) 8.52 (216.3) 3.85 (97.7) 15.44 (392.1) 6.80 (172.8) Cu (1) #4250 kcmil (25120) 56 (25.4)
P3F324RGV 200 240 23.80 (604.5) 16.64 (422.8) 8.52 (216.3) 3.85 (97.7) 8.26 (209.8) 6.80 (172.8) Al (1) #4250 kcmil (25120) 56 (25.4) 6
P3F364RGH 200 600 17.42 (442.5) 21.98 (558.3) 8.52 (216.3) 3.85 (97.7) 15.44 (392.1) 6.80 (172.8) Cu (1) #4600 kcmil (25300) 56 (25.4)
P3F364RGV 200 600 23.80 (604.5) 16.64 (422.8) 8.52 (216.3) 3.85 (97.7) 8.26 (209.8) 6.80 (172.8) Al (1) #4600 kcmil (25300) 56 (25.4) 6
P3F325R 400 240 48.85 (1242.1) 21.22 (539.0) 10.07 (255.8) 4.00 (101.6) 10.69 (271.5) 10.69 (271.5) Cu/Al (1) 250750 kcmil (127380) 77 (34.9)
P3F365R 400 600 48.85 (1242.1) 21.22 (539.0) 10.07 (255.8) 4.00 (101.6) 10.69 (271.5) 10.69 (271.5) Cu/Al (1) 250750 kcmil (127380) 77 (34.9) 6
P3F365HR 400 600 23.59 (599.2) 21.22 (539.0) 21.00 (533.4) 4.00 (101.6) 10.69 (271.5) 10.69 (271.5) Cu/Al (2) 3/0250 kcmil (85127) 81 (36.7)
P3F326R 600 240 48.90 (1242.1) 26.31 (668.3) 10.59 (270.0) 4.00 (101.6) 13.16 (334.3) 13.16 (334.3) Cu/Al (2) #2600 kcmil (35300) 82 (37.1) 6
P3F366R 600 600 48.90 (1242.1) 26.31 (668.3) 10.59 (270.0) 4.00 (101.6) 13.16 (334.3) 13.16 (334.3) Cu/Al (3) #2600 kcmil (25300) 82 (37.1)
P3F327R 800 240 48.90 (1242.1) 26.31 (668.3) 10.59 (270.0) 4.00 (101.6) 13.16 (334.3) 13.16 (334.3) Cu/Al (3) #2600 kcmil (25300) 108 (49.0) 6
6
P3F367R 800 600 48.90 (1242.1) 26.31 (668.3) 10.59 (270.0) 4.00 (101.6) 13.16 (334.3) 13.16 (334.3) Cu/Al (3) #2600 kcmil (25300) 108 (49.0)
Contents
6 Pow-R-Flex Busway
Description Page
6 Pow-R-Flex Busway
Features, Benefits and Functions . . . . . . . . . . V2-T6-32
6 Standards and Certifications . . . . . . . . . . . . . . V2-T6-33
Product Support. . . . . . . . . . . . . . . . . . . . . . . . V2-T6-33
6 Catalog Number Selection . . . . . . . . . . . . . . . . V2-T6-36
Technical Data and Specifications . . . . . . . . . . V2-T6-38
6 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . V2-T6-41
6
6
6
6
6
6 Pow-R-Flex Busway
6 Product Description
6
6 Assembled Plug-In Section
Joint End
6
V2-T6-28 Volume 2Commercial Distribution CA08100003EMarch 2016 www.eaton.com
Low Voltage Busway
Pow-R-Flex
6.2
Bus Plugs for Any Application High 3-Cycle Short-Circuit A Full Line of Fittings to Meet
Pow-R-Flex plug-in protective Ratings Optimize Coordination Any Routing Requirement 6
devices have been designed Between Busway and Power Pow-R-Flex Busway offers
to meet any low ampere
Equipment and Meet High
Quality Standards fittings to meet any need or 6
application. Standard circuit application. End cable tap
breaker plugs are available in All ratings of Pow-R-Flex have
been tested to 3-cycle
boxes, elbows, and end
closers are all available for the
6
a traditional cable out style.
standards and have achieved
Additionally, customized
receptacle plugs are available a minimum rating of 22 kA
most common runs. For more
complex runs, equipment
Forward Offset 6
with receptacle or connector and a maximum rating of flanges, offsets, phase
options to meet any 42 kA rms symmetrical. transpositions, and tees are 6
requirement. These plugs available to accommodate
come with one to four any routing requirement. 6
devices feeding separate
receptacles in an enclosure.
Pow-R-Flex plugs and
6
connectors can be ordered
in a variety of combinations, 6
cord lengths, and short
circuit ratings. 6
Straight Lengths
6
Standard Switchboard Flange
6
End Cable Tap Box
6
6
6
6
6
Breaker Plug
6
Short-Circuit Ratings Joint Cover Assembly
Three-Cycle rms
Symmetrical 6
Plug-In
Short-
Feeder
Short- 6
Ampere Circuit Circuit
Rating Rating Rating 6
Aluminum
150 22,000 22,000 6
6
225 35,000 35,000
300 35,000 35,000
400 42,000 42,000
6
Copper
225 22,000 22,000 6
400 35,000 35,000
500 42,000 42,000 6
600 42,000 42,000
6
6
6
6
6
Volume 2Commercial Distribution CA08100003EMarch 2016 www.eaton.com V2-T6-29
6.2 Low Voltage Busway
Pow-R-Flex
6 Ground
A 50% integral housing
6 ground is provided as
standard. The housing ground
can be used in combination
6 with the internal ground or
the isolated ground to
6 achieve a 100% ground Wall Flanges
rating. Wall flanges fit around the
6 busway and are designed to
close off the wall gap opening
6 around the busway, made to
allow the busway to pass
through a wall Wall flanges
6 are primarily for cosmetic
purposes and do not provide
6 any type of vapor or fire
barrier.
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
V2-T6-30 Volume 2Commercial Distribution CA08100003EMarch 2016 www.eaton.com
Low Voltage Busway
Pow-R-Flex
6.2
Cable Tap Boxes Standard Flanges Expansion Joints Phase Transpositions
There are two types of cable Flanges provide a direct Expansion joints Phase transposition fittings 6
tap boxes: end and center. connection to low voltage accommodate the expansion are used in applications
End cable tap boxes are used switchgear, switchboards, and contraction of busbars where a phase rotation is 6
to feed power to a run of motor control centers and with respect to the enclosure. needed due to a change in
busway with cable and other apparatus. Cutout They compensate for the phasing from the source 6
conduit or where loads dimensions and drilling plans difference in the coefficient equipment to the load
served by busway are
connected without the need
are provided with the
customer drawings, and it is
of expansion of the aluminum
housing and the copper or
equipment. There are two
types of phase transpositions:
6
of overcurrent protection. 90 degree and 180 degree
6
the responsibility of the aluminum busbars. Expansion
There are two designs for switchgear manufacturer to joints must be used wherever in both types; all conductors
end cable tap boxes. One is provide the opening, flange a run of busway crosses an are transposed.
for a left-hand orientation and drillings, connecting hardware expansion joint of a building. 6
one for a right-hand and bus risers in their They should also be installed
orientation. The two separate
designs allow for the bus to
equipment. For proper
coordination between
in the center of extremely
long straight runs of busway;
6
be mounted flush against the
wall no matter which
busway and other equipment,
detailed drawings, including
one every 300 ft (91 m) for
copper or one every 225 ft 6
direction your busway is switchgear orientation, must (68 m) for aluminum.
running. Center cable tap accompany the order. A 6
boxes are used to center feed standard flange can be
a run of busway with cable supplied to the left or right of 6
and conduit or where loads a section, as required.
served by the busway are
connected without the need
6
of overcurrent protection.
Advanced metering options 6
are also available.
6
6
VaporFire Barriers 6
Vaporfire barriers hold a
two-hour fire rating and are 6
used to seal the busway
internally for penetrations
through walls, floors, and
6
other fire-rated penetrations,
preventing the passage of 6
flame, noxious gas, smoke,
and moisture. The exact 6
location of the wall is required
to properly position the 6
barrier within the busway run.
6
6
6
6
6
6
6
6
6
6
Volume 2Commercial Distribution CA08100003EMarch 2016 www.eaton.com V2-T6-31
6.2 Low Voltage Busway
Pow-R-Flex
provides a busway system and outdoor feeder busway package and torque layout and allows for minor
that can be used over a broad available in any length in indicating bolt gives a last-minute modifications
6 spectrum of industrial, 1/2-inch (12.8 mm) rugged, yet flexible and during installation
commercial and institutional increments from a 24-inch easy-to-install connection Advanced system tools
6 applications worldwide. (609.6 mm) minimum to a
10-foot (3 m) maximum.
3-cycle short- including Bid Manager
programs provide quick
circuit ratings optimize
6 Standard plug-in units and
a full line of receptacle
coordination between
busway and power
and accurate product
information
plug-in units are available
6 with fusible or circuit
equipment
This world-class product
breaker overcurrent
6 protection. Surge design and manufacturing
meets the requirements of
Protection Devices (SPD)
NEMA, CSA, Seismic and
6
are also available
Plug-In Units
ISO and IEEE
Plug-in busway design and
6 A full family of busway
plug-in units is available. an enhanced bus plug-in
Standard plug-in units unit facilitates installation
6 include fusible or circuit and improves safety
breaker protection. Surge Flexible ground and neutral
6 Protection Devices (SPD) options provide solutions
for any application problem
and a full line of receptacle
6 plug-in units are available A full family of plug-in
units is available for every
6
power need
Advanced bus plugs
6 provide protection,
communication and
coordination capabilities
6
6
6
6
6
6
6
6
6
6
V2-T6-32 Volume 2Commercial Distribution CA08100003EMarch 2016 www.eaton.com
Low Voltage Busway
Pow-R-Flex
6.2
Standards and Certifications Product Support
Pow-R-Flex meets the Busway product and Additional Information
6
requirements of NEMA, application support is Product Brochure:
6
Power Where You Need it! Plug-In Unit Overcurrent Pow-R-Flex Receptacle
6 As a leader in providing quality, Protective Devices Plug-In Units
robust, cutting-edge electrical General Information Eaton now offers a full line
6 distribution equipment, Eaton A variety of plug-in units have of receptacle plug-in units
understands the importance been designed for the Pow-R- for use on Pow-R-Flex
6 of providing usable power Flex low-ampere busway to
meet multiple applications
busway. Pow-R-Flex
receptacle plug-in units are
access in a variety of
6 applications. Eatons Pow-R-
Flex busway continues to offer
and a variety of installation
conditions. Plug-in unit
non-serviceable plugs. This
means they come fully
devices provide easy and assembled and wired,
6 electrical distribution solutions
that are flexible and without flexible access to a buildings reducing installation time.
limitations, and are energy electrical power system, They are UL listed and offer
6 efficient, saving time and while providing safe a complementary line of
money. overcurrent protection to accessories. Eatons unique
6 equipment and wiring. design makes them the
most flexible receptacle
All Pow-R-Flex plug-in units
6 are designed with the safety
units in the industry.
of the installer and user as Data CentersData racks
6 the key criteria. The following
safety features are standard
continue to process more
information at higher speeds
6 for all fusible and molded-
case circuit breaker plug-in
with constantly changing
demands. Pow-R-Flex
units: receptacle plugs offer the
6 highest short-circuit ratings
Each plug-in unit ground in the industry. Busway and
6 stab makes positive
contact with the busway
receptacle plugs above
the data racks provide faster
ground (integral or internal)
6 before the phase or neutral
installation, faster connectivity,
easier rack changes and
stabs contact the busbars
6 Plug-in unit molded guide
upgrades, and will run cooler
than traditional cable methods.
tabs are provided in the
6 stab support base. These RetailAs retail
environments change
ensure proper phase
6 alignment and open the
busway outlet shutter
meeting customer demands,
Pow-R-Flex busway and
receptacle plugs help make
6
mechanism
Line-side barriers are floor layout and display
changes easier. Receptacle
6 provided over the line-side
terminal to help prevent plugs allow for easy power
accidental contact with access, eliminating costly
6 line-side connections conduit and cable work.
Each plug-in unit has Schools and Laboratories
6 mounting flanges, which Pow-R-Flex receptacle plugs
help protect the stab-base offer safe power access for
6 assembly and have captive
hardware that bolt the unit
instrumentation and other lab
equipment at the point of use.
6 securely to the busway
6
6
6
6
6
6
6
6
V2-T6-34 Volume 2Commercial Distribution CA08100003EMarch 2016 www.eaton.com
Low Voltage Busway
Pow-R-Flex
6.2
Single Receptacle Unit Double Receptacle Unit Quad Receptacle Units
(600 V Maximum) (600 V Maximum) (600 V Maximum) 6
The single receptacle unit The double receptacle unit The quad receptacle unit
shown in below is configured shown below is configured to shown below is configured to 6
to order based upon the order based upon the order based upon the
receptacle type and rating.
These units are three-phase
receptacle type and rating.
These units are three-phase
receptacle type and rating.
These units are three-phase
6
and can service single- or
three-phase loads up to 600 V
and can service single- or
three-phase loads up to 600 V
and can service single- or
three-phase loads up to 600 V 6
maximum (120 V, 240 V, 400 V, maximum (120 V, 240 V, 400 V, maximum (120 V, 240 V, 400 V,
480 V, 600 V, 208Y/120 V, 480 V, 600 V, 208Y/120 V, 480 V, 600 V, 208Y/120 V, 6
400/230 V, 480/277 V, 600/ 400/230 V, 480/277 V, 600/ 400/230 V, 480/277 V, 600/
347 V). Type F-Frame bolt-on 347 V). Type F-Frame bolt-on 347 V). Type F-Frame bolt-on 6
molded-case circuit breakers molded-case circuit breakers molded-case circuit breakers
are used in single-pole, two-
pole, or three-pole
are used in single-pole, two-
pole, or three-pole
are used in single-pole, two-
pole, or three-pole
6
configurations. Single and
double receptacle plugs are
configurations. Single and
double receptacle plugs are
configurations. Each unit
comes with up to four 6
also available in our mini plug also available in our mini plug receptacles, with the
design, which utilizes either a design, which utilizes either a breakers sized per the 6
GHC circuit breaker or a CCP GHC circuit breaker or a CCP receptacle rating. Each
fusible switch in a smaller fusible switch in a smaller receptacle can be fixed 6
enclosure. Each unit comes enclosure. Each unit comes mounted to the front of the
with one receptacle, with the
breaker sized per the
with two receptacles, with
the breakers sized per the
enclosure or cable-mounted
to a cord drop coming out of
6
receptacle rating. Each receptacle rating. Each the bottom of the enclosure.
receptacle can be fixed- receptacle is cable mounted See below. Cord drop lengths 6
mounted to the front of the to a cord drop coming out of may be 115 ft in 1-ft
enclosure or cable-mounted the bottom of the enclosure. increments. Consult NEC 6
to a cord drop coming out of See below. Cord drop lengths Sections 368, 400 and 645 for
the bottom of the enclosure.
See below. Cord drop lengths
may be 115 ft in 1-ft
increments. Consult NEC
cord drop applications. 6
may be 115 ft in 1-ft
increments.
Sections 368, 400 and 645 for
cord drop applications. 6
Consult NEC Sections 368, 6
400 and 645 for cord drop
applications.
6
6
6
Quad Receptacle Unit
(Cord Mounted) 6
Double Receptacle Unit
(Enclosure Mounted)
6
6
Single Receptacle Unit
(Enclosure Mounted)
6
6
6
6
6
Double Receptacle Unit
(Cord Mounted)
6
6
SPD Series Bus Plug
6
LABSPD 250 480Y 2 C
6
6
Fixeddo not change Fixeddo not change
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
V2-T6-36 Volume 2Commercial Distribution CA08100003EMarch 2016 www.eaton.com
Low Voltage Busway
Pow-R-Flex
6.2
Plug-In Cable Outlet Details Plug-In Cable Tap Box
6
Safety shutter
A B 6
6
C
6
Ground stab contact
6
Plug-in Cable Tap Boxes
Plug-in cable tap boxes are
used to back feed power to a
overcurrent protection. Plug-
in cable tap boxes fit into any
6
run-off busway, or where
equipment served by the
plug-in provision on a plug-in
type busway. See below.
Plug-In Cable Tap Box Dimensions 6
busway is connected without Catalog
Number A B C
6
Plug-In Cable Tap Box Details LAPTB100MG 9.33 (236.9) 18.21 (462.5) 8.18 (207.8)
Catalog Ampere Mechanical Lugs Mechanical Lugs LAPTB100MGN 9.33 (236.9) 18.21 (462.5) 8.18 (207.8) 6
Number Rating (Metric) (Standard) LAPTB200MG 9.33 (236.9) 18.21 (462.5) 8.18 (207.8)
LAPTB100MG 100 #63/0 4.1110.40 mm LAPTB200MGN 9.33 (236.9) 18.21 (462.5) 8.18 (207.8) 6
LAPTB100MGN 100 #63/0 4.1110.40 mm
LAPTB200MG 200 #63/0 4.1110.40 mm Plug-In Cable Tap Box Details
6
LAPTB200MGN 200 #63/0 4.1110.40 mm Stab Base
6
6
6
6
6
6
6
6
6
6
6
6
6
Volume 2Commercial Distribution CA08100003EMarch 2016 www.eaton.com V2-T6-37
6.2 Low Voltage Busway
Pow-R-Flex
6
6
6
6
V2-T6-38 Volume 2Commercial Distribution CA08100003EMarch 2016 www.eaton.com
Low Voltage Busway
Pow-R-Flex
6.2
Circuit Breaker Type Plug-In Plug-In Devices with C. Receptacle type plugs Surge Protective Devices
Devices Receptacles shall have fused or circuit A. Provide surge protective 6
A. Where required, plug-in A. Where required, plug-in breaker over-current devices as specified in
units of the types and units of the types and protection. Circuit Section 16671A. 6
ratings indicated on the ratings indicated on the breakers shall be plug-on
plans and specifications
shall be supplied. Plug-in
plans and specifications
shall be supplied.
or bolt-on type with an
interrupting rating of
End Cap Tap Boxes 6
A. End cable tap boxes shall
units shall be
mechanically interlocked
Plug-in units shall be
mechanically interlocked
10 kA or 22 kA three-
phase at 240 V, 25 kA
be configured to accept
up to (2) 350 kcmil cables
6
with the busway housing with the busway housing single-phase at 240 V,
to prevent their to prevent their 10 kA at 400 V and 480 V
per phase and shall
conform to UL 857 and 6
installation or removal installation or removal and 10 kA at 600 V. NEC standards for wire
while the switch is in the while the switch is in the Fused switches will have bend space. Left and 6
ON position. The ON position. The an interrupting rating that right side removable
enclosure of any plug-in
unit shall make positive
enclosure of any plug-in
unit shall make positive
matches that of the
busway it is attached to,
covers shall be provided 6
for easy cable access.
and shall limit the let-
ground connection to the
duct housing before the
ground connection to the
duct housing before the through current from the
Lug access covers shall
be provided for easy
6
stabs make contact with stabs make contact with plug through the
the busbars. All plug-in the busbars. All plug-in receptacle to less than
access to cable
termination lugs. Cable 6
units shall be equipped units shall be equipped 10 kA IR. All fault current tab boxes shall be
with an interlock that can with an interlock that can ratings shall be
symmetrical rms
mountable against a wall 6
be defeated to prevent be defeated to prevent without causing the
the cover from being
opened while the switch
the cover from being
opened while the switch
amperes. Circuit
breakers and fusible
busway to be offset from 6
the wall.
is in the ON position and is in the ON position and switches shall be from
to prevent accidental to prevent accidental the same manufacturer B. End cable tap boxes shall 6
closing of the switch closing of the switch as the busway. allow for CTs to be
while the cover is open. while the cover is open. Receptacles shall be UL mounted within the tap 6
The plugs shall be The plugs shall be listed, any standard box for metering.
provided with a means
for padlocking the cover
provided with a means
for padlocking the cover
NEMA configuration and
either bolted to the
6
closed and padlocking
the disconnect device in
closed and padlocking
the disconnect device in
enclosure or affixed to an
electrical cord dropped 6
the OFF position. The the OFF position. The down from the
operating handle and operating handle and enclosure. Cord drops 6
mechanism shall remain mechanism shall remain shall use UL listed strain
in control of the in control of the relief devices. 6
disconnect device at all disconnect device at all Receptacle type plugs
times, permitting its easy
operation from the floor
times, permitting its easy
operation from the floor
shall come fully
assembled and wired
6
from the manufacturer.
by means of a hook stick
or chain. All plug-in units
by means of a hook stick
or chain. All plug-in units Field kits for drop cords 6
shall be interchangeable shall be interchangeable and receptacles shall not
without alteration or without alteration or be acceptable. For fault 6
modification of plug-in modification of plug-in current ratings above
duct. duct. 22 kA at 240 V or 10 kA
at 400 V and/or 480 V,
6
B. All plug-in unit types and B. All plug-in unit types and
ratings must be fully ratings must be fully
the connector/receptacle
and breaker combination 6
interchangeable for use interchangeable for use must be tested to UL
on all busway ampere on all busway ampere 231 and UL approved. 6
ratings. ratings.
C. Circuit breaker-type plugs 6
shall have an interrupting
rating as shown in the 6
contract documents, and
shall meet all
requirements of UL
6
Standard 489. All breaker
plug-in devices shall be 6
from the same
manufacturer as the 6
busway.
6
6
Volume 2Commercial Distribution CA08100003EMarch 2016 www.eaton.com V2-T6-39
6.2 Low Voltage Busway
Pow-R-Flex
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
V2-T6-40 Volume 2Commercial Distribution CA08100003EMarch 2016 www.eaton.com
Low Voltage Busway
Pow-R-Flex
6.2
Dimensions
Approximate Dimensions in Inches (mm) 6
Busbar and Housing 6
6
Physical DimensionsWidth x Height
Ampere Rating Phase Conductor Ground Conductor Housing Enclosure
Aluminum
150 0.28 x 0.50 (7.1 x 12.7) 0.20 x 1.75 (5.1 x 44.5) 3.60 x 8.30 (91.4 x 210.6)
6
225
300
0.28 x 1.25 (7.1 x 31.8)
0.28 x 1.25 (7.1 x 31.8)
0.20 x 1.75 (5.1 x 44.5)
0.20 x 1.75 (5.1 x 44.5)
3.60 x 8.30 (91.4 x 210.6)
3.60 x 8.30 (91.4 x 210.6)
6
400
Copper
0.28 x 1.75 (7.1 x 44.5) 0.20 x 1.75 (5.1 x 44.5) 3.60 x 8.30 (91.4 x 210.6)
6
225
400
0.28 x 0.50 (7.1 x 12.7)
0.28 x 1.25 (7.1 x 31.8)
0.20 x 1.75 (5.1 x 44.5)
0.20 x 1.75 (5.1 x 44.5)
3.60 x 8.30 (91.4 x 210.6)
3.60 x 8.30 (91.4 x 210.6)
6
500
600
0.28 x 1.75 (7.1 x 44.5)
0.28 x 1.75 (7.1 x 44.5)
0.20 x 1.75 (5.1 x 44.5)
0.20 x 1.75 (5.1 x 44.5)
3.60 x 8.30 (91.4 x 210.6)
3.60 x 8.30 (91.4 x 210.6)
6
6
Oversized Neutral Ratings
6
Ampere Rating Neutral Size D x W Neutral Rating
Aluminum 6
150
225
0.28 x 1.75 (7.1 x 44.5)
0.28 x 1.75 (7.1 x 44.5)
250%
150%
6
300 0.28 x 1.75 (7.1 x 44.5) 150% 6
400 0.28 x 1.75 (7.1 x 44.5) 100%
Copper 6
225 0.28 x 1.75 (7.1 x 44.5) 250%
400 0.28 x 1.75 (7.1 x 44.5) 150%
6
500 0.28 x 1.75 (7.1 x 44.5) 100%
6
600 0.28 x 1.75 (7.1 x 44.5) 100%
6
Conductor Dimensions
6
3.60
3.60
(91.4) 3.60
(91.4) 6
(91.4)
1.25
(31.7) 1.75
6
0.50
6
8.30 (44.4)
(12.7)
(210.8) 8.30
8.30 (210.8)
(210.8) 6
6
6
6
6
6
6
6
6
Volume 2Commercial Distribution CA08100003EMarch 2016 www.eaton.com V2-T6-41
6.2 Low Voltage Busway
Pow-R-Flex
6 12.00
(304.8)
6 24.00
CL
24.00
Spacing
6 (609.6)
Minimum
(609.6)
6 CL 12.00
(304.8)
CL
6
CL
6
6 Front View
Front View
6
6 Single Receptacle Mini Plug Unit
6
6
6 4.90 0.69
6 (124.5)
4.00
(17.5)
6
(101.6)
5.50
6 (139.7)
5.25
(133.4)
6
6
6
6
7.40
6 (187.9)
6
6
6
6
6
6
6
6
V2-T6-42 Volume 2Commercial Distribution CA08100003EMarch 2016 www.eaton.com
Low Voltage Busway
Pow-R-Flex
6.2
Approximate Dimensions in Inches (mm)
6
Double Receptacle Mini Plug Unit
6
6
6
6
6
8.25
(209.6) 6
6
6
6
6
11.79
(299.5) 6
6
6
6
6
4.90
0.69
(17.5) 6
(124.5)
4.00
6
6
(101.6)
8.25
(209.6)
6
6
6
6
6
6
6
6
6
6
6
Volume 2Commercial Distribution CA08100003EMarch 2016 www.eaton.com V2-T6-43
6.2 Low Voltage Busway
Pow-R-Flex
6 CCP switch
CCP switch
400
480
7.50 (190.5)
7.50 (190.5)
8.60 (218.4)
8.60 (218.4)
4.00 (101.6)
4.00 (101.6) 277 V
grounded
Two-pole, L7-15R L720R L730R
6
three-wire,
Double GHC 480 11.80 (299.7) 8.75 (222.3) 4.00 (101.6) grounded
FD 400 11.00 (279.4) 12.00 (304.8) 6.40 (162.6) 480 V Two-pole, L820R L830R
6 FD 480 11.00 (279.4) 12.00 (304.8) 6.40 (162.6) three-wire,
grounded
6
CCP switch 400 11.80 (299.7) 8.75 (222.3) 4.00 (101.6)
Three 250 V Three-pole, L1520R L1530R CS8364 4
CCP switch 480 11.80 (299.7) 8.75 (222.3) 4.00 (101.6) four-wire,
FD 400 20.50 (520.7) 11.30 (287.0) 7.10 (180.3) 208/120 V Three-pole, L2120R L2130R
five-wire,
6 FD 480 20.50 (520.7) 11.30 (287.0) 7.10 (180.3) grounded
480/277 V Three-pole, L2220R L2230R
6 Receptacle Unit Short-Circuit Withstand Rating five-wire,
grounded
(rms Symmetrical)
6 Plug-In Breaker
Unit Type Type 240 V 400 V 480 V Pin and Sleeve Connectors (UL and IEC 309)
6 Single GHC 10,000 A 10,000 A 10,000 A Phase Voltage Configuration 15 A 20 A 30 A 50 A 60 A
6 Double GHC
FD 1
10,000 A
22,000 A
10,000 A
10,000 A
10,000 A
10,000 A
250 V Two-pole,
three-wire,
P620C P630C P660C
grounded
6 CCP switch 2 42,000 A 42,000 A 42,000 A
277 V Two-pole, P720C P730C P760C
Quad FD 1 22,000 A 10,000 A 10,000 A three-wire,
6 grounded
Three- 250 V Three-pole, P1520C P1530C P1560C
6 NEMA Receptacle Configurations four-wire,
grounded
6 277 V Two-pole,
three-wire,
715R 720R 3 Available in a duplex configuration.
4 California standard receptacles.
grounded
6 Three 250 V Three-pole, 1515R 1520R 1530R
For other receptacle options, contact the factory.
480/277 V receptacles may be applied at 400/230 V.
four-wire,
6 grounded
6
6
6
6
V2-T6-44 Volume 2Commercial Distribution CA08100003EMarch 2016 www.eaton.com
Low Voltage Busway
Pow-R-Flex
6.2
Approximate Dimensions in Inches (mm)
6
Plug-In UnitsPhysical Data
Bus Plugs Breaker Plug-In Unit Dimensions 6
Plug-In Maximum Maximum
Unit Amperes Voltage A B C D E 6
LABFD 225 600 18.00 10.80 8.17 5.97 4.80
A B
(F-Frame) (457.2) (274.3) (207.5) (151.6) (121.9) 6
LABJD 250 600 18.56 10.80 9.08 5.97 4.61
C (J-Frame) (471.4) (274.3) (230.6) (151.6) (117.1) 6
D
Breaker Plug-In Unit Physical Data 6
E Plug-In Mechanical Approximate
Unit Terminals Weight Lb 6
LABFD (F-Frame) Cu/Al-(1)#44/0 25
LABJD (J-Frame) Cu/Al-(1)#14350 kcmil 40 6
Breaker
Neutral
6
6
6
6
6
Ground
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
Volume 2Commercial Distribution CA08100003EMarch 2016 www.eaton.com V2-T6-45
6.3 Low Voltage Busway
100A Busway
Contents
6 Bus Plug Receptacle
Description Page
6 100 A Busway
Options and Accessories . . . . . . . . . . . . . . . . . V2-T6-47
6 Technical Data and Specifications . . . . . . . . . . . V2-T6-48
6
6
6
6
6
6
6
6 100 A Busway
6 Product Description Product Selection
6 Three-phase, three-wire;
three-phase, four-wire; and
Copper (Includes 50% Internal Ground Bar)
10 ft (3 m) CST13G CST14G CST13NG
6 single-phase, three-wire
applications 5 ft (1.5 m) CST135G CST145G CST13N5G
6
3 ft (0.9 m) CST133G CST143G CST13N3G
Application Description
2 ft (0.6 m) CST132G CST142G CST13N2G
Eaton 100 A busway is
6 an alternative to cable in 1 ft (0.3 m) CST131G CST141G CST13N1G
supplying small blocks Elbows 10 x 10 in (254.0 x 254.0 mm)
6 of power for the normal
commercial and industrial
Forward CFE13G CFE14G CFE13NG
6 Type
Three- or Four-Wire
Catalog Number
Ground (If Required)
Catalog Number
6
6
6
6
6
V2-T6-46 Volume 2Commercial Distribution CA08100003EMarch 2016 www.eaton.com
Low Voltage Busway
100A Busway
6.3
Fusible Plug-In Units
Voltage Ampere Fusible Enclosure Ground (If Required)
6
Rating Rating Catalog Number Catalog Number
240 30 FAN321 PIGS100
6
240 60 FAN322 PIGS100
6
240 100 FAN323 PIGS100
600 30 FAN361 PIGS100 6
600 60 FAN362 PIGS100
600 100 FAN363 PIGS100 6
6
Circuit Breakers for Plug-In Units
Circuit Breaker Receptacle Ground External Handle (Required
6
Breaker Ampere Enclosure Enclosure (If Required) for Hook-Stick Operation)
Frame Rating Catalog Number Catalog Number Catalog Number Catalog Number 6
QUICKLAG, HQP 1550 PINQP LCNQP PIGS100 HMQP
FD, EHD, FDB 15100 PINFD LCNFD PIGS100 HMFD 6
6
Options and Accessories
6
100A Busway Plug-In Units External Handle Accessories Hangers
Plug-in units for 100 A busway Operating Mechanism Catalog 6
are available with or without An external operating Item Number
overcurrent protection. All plug- mechanism is attached on
top of the breaker switch for
End closer EC1 6
in units include a neutral stab
6
and are suitable for three- hookstick or chain operation. Outlet cover OC1
phase, three-wire, and three- This is available for all Edgewise hanger EH1
circuit breakers.
phase, four-wire applications. C clamp hanger FH1
C ClampFH1 6
The PINQP circuit breaker Receptacle Enclosures Slip-on wall flange WF1
enclosures and the LCNQP
and LCNFD receptacle
The receptacle enclosures Note 6
(loadcenters) include space The above items can be used with or without Angle
enclosures are all suitable
for single-phase, three-wire
for three breaker poles and ground, three-wire or four-wire. Iron 6
provisions for one, two or
applications. Ground
stabs are available for
three conventional, single-
gang outlets, and blank
Accessories
6
field installation. CL Joint
6
covers to fill unused spaces.
Include neutral stab. Do not
Fusible Units
include breakers, outlets
Fusible units are available
for 30, 60 and 100 A service
or wiring. 4.00
(101.6)
Wall Mounted
6
for 240 or 600 V. The enclosure, circuit breaker
(if required) and ground 6
Circuit Breaker Units are ordered separately
If you are using circuit and shipped unassembled. 6
breaker units, the load must If the unit is to be factory
be distributed evenly among assembled, please indicate 6
A, B and C phases. To on the order, add 15% to End ClosersEC1
accomplish this, distribute the total price, and allow
additional time for shipment. Outlet Cover
6
the load evenly among EdgewiseEH1
6
single-, two- and three-pole For circuit breaker selection,
breakers. Available are see Page V2-T6-22.
QUICKLAGHQP circuit
breaker units for 50A240V 6
maximum service, EHD,
FDB and FD circuit breakers 6
for 100 A to 600 V maximum
service. 6
Replacement Outlet CoverOC1
6
Edge Mounted
6
Volume 2Commercial Distribution CA08100003EMarch 2016 www.eaton.com V2-T6-47
6.3 Low Voltage Busway
100A Busway
6 6.00
(152.4)
26.25
(666.8)
26.25
(666.8)
26.25
(666.8)
26.25
(666.8)
9.00
(228.6)
3.50
(88.9)
Busbar Size:
0.281 (7.1) Dia.
1.75
(44.4)
6 120.00
(3048.0)
CL Joint Joint CL
6 10.00 (254.0) x 10.00 (254.0) 10.00 (254.0) x 10.00 (254.0) 10.00 (254.0) x 10.00 (254.0) 10.00 (254.0) x 10.00 (254.0)
6
CL Joint "
10
6 10" 10"
"
"
10
10
6 CL Joint 10
"
"
10
6 CL Joint
CL Joint
6 "
10
6
Forward Elbow Rearward Elbow Upward Elbow Downward Elbow
6
6
6
6
6
6
6
6
6
6
V2-T6-48 Volume 2Commercial Distribution CA08100003EMarch 2016 www.eaton.com