Beruflich Dokumente
Kultur Dokumente
LT W I T H H ONOR
BUI
HAR
T , INC
P I Q UZELL FANU S A
A, OHIO
Index
About Hartzell . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pages 2-3
Hartzell Products
General Ventilation Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 4
Process Ventilation Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 5
Fiberglass Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 6
Heating Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 7
Performance Envelopes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pages 8-9
Engineering Information
Application Data
General Ventilation Fans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 10
Process Ventilation Fans. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 11
Fan Laws and Formulae . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 12
Fans and Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 13
Density, Temperature and Altitude . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 14
Safe Operating Speeds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 15
Useful Engineering Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pages 16-19
Fan Sound . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pages 20-21
Material Corrosion Resistance Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pages 22-23
Research & Development Lab, Piqua, Ohio. Wind Tunnel and Calibration Equipment
Product Concept Standard 210 Laboratory Methods of Testing Fans for Rating and
AMCA Standard 300 Test Code for Sound Rating.
Reliable, efficient performance is the underlying principle of the
product concept of every Hartzell fan that is built. Its principle is Hartzell pioneered the testing of its products in accordance with the
adhered to in the early design and development stages of the AMCA Standard test codes.
prototype and is demonstrated by the special care given to the
development of propeller and wheel patterns in the pattern shop. Manufacturing
Hartzell has over 400,000 square feet of manufacturing space in its
Prototype Development two plant locations.
After completion of the fan pattern, it is taken to the Research & Facilities and capabilites include full metal forming fabrication and
Development Lab for testing and further refinement. welding, a modern foundry and machine shop, and fiberglass mold-
Hartzell laboratory is AMCA* accredited to test for air and sound ing equipment.
performance and is located on the grounds of the main Hartzell Recent equipment modernizations include a foundry mullor,
plant in Piqua, Ohio. machining center and paint line.
In addition to the 12 ft. test chambers capable of 50,000 CFM at up to Our CAD system provides maximum accuracy for manufacturing
24" W.G. pressures, the lab is equipped with precision instruments for purposes.
sound and vibration testing.
Outdoor test stand utilized for fans up to 14 ft. in diameter. Quality
Additional equipment allows for Hartzell to conduct overspeed tests, The quality of Hartzells air moving products is ensured by an in-
check blade movement while fan is rotating, check noise levels, house Quality Assurance Program. Hartzell Fan Inc. has made this
frequencies and vibration stresses. investment in modern, sophisticated engineering methods in order to
provide the best possible quality products for your use.
Certified Fan Ratings *Product laboratory data based on tests in an AMCA Accredited
Hartzell Fan is a charter member of the Air Movement and Control Laboratory are not to be construed as being licensed to bear the
Association International, Inc. (AMCA) which has adopted AMCA AMCA Seal.
Propeller Fans
Propeller fans are designed for general
ventilation, fume removal, cooling, air
supply or exhaust in direct drive and belt
drive arrangements. Standard motors are
totally enclosed air over. See Bulletin A-
109 for details.
Roof Ventilators
All Hartzell ventilators are
designed as packaged units,
ready for installation. Models
available are either direct drive,
belted or belt driven, in hot rolled
steel, galvanized steel or aluminum.
Vaneaxial Blowers
Vaneaxial blowers are designed for
handling relatively clean and corrosive-
free air at static pressures up to 10".
These units can also move large volumes
Belt Drive Vaneaxial Adjustable Pitch Vaneaxial
of air at low pressure, with low speed Direct Drive Vaneaxial Blower Blower VA and VB Blower Direct Drive Series 65
characteristics. Series 53 Series 54 Belt Drive Series 66
Adjustable pitch vaneaxial fans feature Guide vanes insure maximum efficiency Both VA and VB type impellers are a Adjustable pitch vaneaxial fans feature
in converting velocity pressure to static one-piece cast aluminum airfoil design. adjustable pitch blades in both direct
high total efficiency providing a space pressure with minimal turbulence. Both are designed to work efficiently at drive and belt driven units. Sizes 35" to
and energy saving unit that offers a Suitable where conditions are not detri- high static pressures. VA units in sizes 12" 79". CFM from 5900 to 232,500 at free
wide range of performance and quiet mental to operation of totally enclosed to 60" with CFM from 1545 to 104,400 at air. Standard motors on direct drive units
operation. The adjustable pitch vaneaxial air over motor in the air stream. Cast alu- free air. VB units in sizes 18" to 48" with are totally enclosed foot mounted.
blades can be quickly adjusted without minum impellers. Sizes 18" to 42". CFM CFM from 2340 to 46,697 at free air. Both Standard motors on belt driven units are
removing the wheel from the motor shaft. from 4350 to 36,250 at free air. See models have open end drip proof motors open end drip proof out of air stream.
Bulletin A-110 for details. as standard. See Bulletin A-110 for details. See Bulletin A-142 for details.
General Ventilation
Fiberglass Wall Ventilators Series 59 Fiberglass Upblast Roof Ventilator Fiberglass Upblast Roof Ventilator Fiberglass Hooded Roof Ventilator
Direct drive wall ventilator designed for Direct Drive Series 57 Belt Drive Series 37 Belt Drive Series 58
general ventilation where corrosive elements Provides an efficient, yet economical choice Meets the need for a heavy duty, belt drive, Hooded ventilators design provides complete
exist in fume or vapor form. Temperatures for general ventilation of mild corrosive upblast ventilator with motor out of the protection from the elements for exhaust
to 180 with specially insulated motors. atmospheres. Suitable for temperatures up airstream. Ideal for applications where operation. Units belt drive configuration and
Unit constructed of solid fiberglass. Sizes 12" to 180 with specially insulated motors. severe corrosive elements are present. exterior motor mounting makes this the
to 60". Performance from 1,315 to 55,500 Sizes 28" to 60". CFM from 7330 to 50,400 at Available in sizes 12" to 60". Performance logical choice where corrosive elements exist
CFM at free air. Request Bulletin A-137. free air. See Bulletin A-141 for details. ranging from 1260 CFM to 61,765 CFM at and protection from the weather is essential.
free air. See Bulletin A-141 for details. Sizes 12" to 60", with CFM from 1280 to
63,470 at free air. See Bulletin A-141 for details.
Process Ventilation
Fiberglass Duct Fans Fiberglass Duct Axial Fans Fiberglass By-Pass Fan Direct Drive Fiberglass Inline Centrifugal Blowers
Belt Drive Series 34 Belt Drive Series 35 Series 28B and 29B Belt Drive Series 40
Direct Drive Series 28 Direct Drive Series 29 Engineered and built to be used in a variety The inline blower offers straight airflow for
Best suited for applications with low static Designed for maximum efficiency in the static of corrosive applications. Direct drive motor duct installations with the highly efficient,
pressure characteristics where some corrosive pressure range of 1" to 3" at low speeds and out of the airstream. Suitable for temperatures backward curved airfoil-bladed wheel in a vane
elements exist. Sizes 12" to 60". Belt drive low noise. Internal hardware of stainless steel. to 200F with specially insulated motors. 28B equipped tube. Identical inlet and discharge
units have open end motors as standard with Sizes 12" to 60". Belt drive units have open has Type FW low pressure propeller; 29B has dimensions. Compact, efficient low noise
CFM from 1370 to 62,200 at free air. Direct end protected motors as standard. CFM from Type E, medium pressure propeller. Sizes 24" units. Sizes 12" to 60" wheel diameters.
drive units have totally enclosed air over XT 470 to 70,000 at 1" S.P. Direct drive units to 48", with performance ranging from 6012 Performance from 800 to 85,000 CFM. Static
motors as standard with CFM from 1325 to have totally enclosed chemical plant motors CFM to 46,145 CFM at free air. See Bulletin pressures to 12". Request Bulletin A-131.
66,700 at free air. See Bulletin A-139 for details. as standard. CFM from 1204 to 68,950 at A-139 for details.
free air. See Bulletin A-139 for details.
Fiberglass
Air Control
Products
Gas Fired Door Heater Series 79 Model GMP (Propeller Fan) Econo Units Series 78
Unit works whenever door is raised far enough Model GMC (Centrifugal Fan) DWDI BC For supplying tempered make-up air or for total
to trip the switch. Comes equipped with all Model GFC (Centrifugal Fan) DWDI FC fresh air heating systems. Three sizes, 7100 to
standard controls and safety features. Eliminate hot and cold spots, supplying fresh clean air at the right temperature. Direct fired 23,580 CFM at 1/4" est. static pressure. IRI and
Capacities from 700,000 to 990,000 input unit designed to burn either natural or propane gas. Constructed of 16 gauge galvannealed FM control packages available. Standard motor
BTU. Standard motors are totally enclosed steel painted on the outside. Capacities from 300,000 through 10,000,000 BTU/HR at 92F is totally enclosed air over. See Bulletin A-125
air over. See Bulletin A-125 for details. temperature rise. Built to IRI, FM or ANSI Standard Z83.4. All models have OEDP motor in for details.
the airstream. See Bulletin A-125 for details.
Steam Unit Heater Propeller Fan Assembly Series 86 Centrifugal Fan Assembly Series 85 Face and Bypass Assembly
Series 771 1-Row Coils Single package assembly uses lo-noise airfoil Fan wheels are heavy duty industrial forward Series 87 Axial Flow Fan
Series 772 2-Row Coils propeller incorporating full efficiency at slow curved and backward curved type. Capacities Series 88 Centrifugal Fan
Direct drive unit is equipped with high efficiency speeds without excessive noise. Capacities from 8000 to 45,000 CFM. Packaged design Available in two designs utilizing a duct axial
cast aluminum propeller direct connected to a from 6000 to 60,000 CFM. Standard motor is with controls mounted and wired. Standard fan or DWDI forward curved centrifugal fan.
totally enclosed fan duty motor. Capacities open end protected. See Bulletin A-128 for motor is open end protected. See Bulletin Coil slides in and out on rails. Capacities
from 40,300 to 524,000 BTU/HR. See Bulletin details. A-128 for details. from 8000 to 45,000 CFM. Standard motors
A-121 for details. are open end protected. See Bulletin A-128
for details.
Other
Adjustable Pitch Fans Marine and Mine Duty Blowers
All Aluminum Series 90 Adjustable Pitch Reversible Series 90R Series 44 or 44M Duct Axial Fans Series 50 or 50M Vaneaxial Blowers
Blades and hubs of sturdy corrosive resistant Aluminum alloy blades are designed so the Heavy-duty direct drive Duct Axial fans. Direct drive fans in rugged two-piece design.
aluminum alloy castings. Four- and six-blade leading edges and trailing edges of the blades Wheel is one piece, airfoil type with six Housings are heavy gauge welded steel.
assemblies in 4' to 12' sizes. Drop in blade are identical in either direction of rotation. blades, made of aluminum. Sizes 12" through Wheel is one piece, airfoil type with seven
retention, manually adjustable. Right- or left- Blades fit into recessed hub, retained by two 60". Performance from 300 to 91,920 CFM blades made of cast aluminum. Sizes 12"
hand rotation. S.A.E. Grade 5 U bolts per blade. Can be at free air. Static pressures to 3". Guide vanes through 60". Performance from 1,930 to
Also available in threaded blade retention, manually adjusted to meet changes in air can be added for increased performance at 123,000 CFM at free air. Units are designed
Series 89, right- or left-hand rotation. delivery. Sizes 48" to 84" diameter. Four- and 1" to 4" static pressure with the same or less for use in 2" to 5" static pressure. Request
Request Technical Data Sheet. Six-blade design. horsepower. Request Bulletin A-143. Bulletin A-143.
20
HARTZELL FAN, INC.
Performance Envelopes
Axial Flow Fans
18 Standard Air
16 Curves shown are the maximum performance rating for wheel type.
Area below and left of curve is the suggested operating performance range.
14
STATIC PRESSURE (IN W.G.)
12
10
Fixed Pitch
Vaneaxial Fans
4
2
Duct Adjustable Pitch
and Vaneaxial Fans
Tubeaxial
Fans
0
0 40 80 120 160 200 240 280
1000 CFM
50
45
Type AH, MH
HARTZELL FAN, INC.
Performance Envelopes
Type PW, PWR
Centrifugal Fans
40
Standard Air
35
30
STATIC PRESSURE (IN W.G.)
25
20
Type BC/BI DWDI
Type BC SWSI
15
Type BA DWDI
10 Type BA SWSI
0
0 20 40 60 80 100 120 140 160 180 200
1000 CFM
Curves shown are maximum performance rating for wheel type.
Area below and left of curve is the suggested operating performance range.
Fan Discharges
CLOCKWISE
COUNTERCLOCKWISE
E x I x ME x Pf
Useful Fan Application Formulae FOR 1 PHASE MOTORS: BHP OUTPUT =
746
d = 1.322 x PB To plot a system curve where
F + 460 SP1 & CFM1 are known, use the FOR 1 PHASE MOTORS: KW INPUT = E x I x Pf
following formula to find other 1000
FAN AHP = CFM x TP curve points: SYMBOL DEFINITION
6356
A AREA (FT.2)
[ ] 2
SP2 = SP1 CFM2 AHP AIR HORSEPOWER
FAN Eff = AHP = CFM x TP CFM1 a SIDE a OF RECTANGULAR DUCT
BHP 6356 x BHP b SIDE b OF RECTANGULAR DUCT
To determine round duct equiva- BHP BRAKE HORSEPOWER
CFM x SP CFM AIR VOLUME FLOW (FT.3/MIN)
SE = lent of rectangular duct for same
6356 x BHP friction loss and volumetric d AIR DENSITY (LB./FT.3)
DR DIAMETER OF ROUND DUCT
capacity:
VP = [ ] [
FPM
4005
2
=
CFM
A x 4005 ] 2
8 (ab)5
E
Eff
F
VOLTS
FAN EFFICIENCY (DECIMAL)
TEMPERATURE (DEGREES FAHRENHEIT)
DR = 1.265 (a + b)2 I AMPS
TP = SP + VP Kw KILOWATTS
ME MOTOR EFFICIENCY (DECIMAL)
FAN BHP = CFM x TP = CFM x SP PB BAROMETRIC PRESSURE (INCHES MERCURY)
6356 x EffT 6356 x EffS Pf POWER FACTOR
SE STATIC EFFICIENCY
E x I x ME x Pf x 1.732
FOR 3 PHASE MOTORS: BHP OUTPUT = SP STATIC PRESSURE (INCHES WG)
746 TP TOTAL PRESSURE (INCHES WG)
FOR 3 PHASE MOTORS: KW INPUT = E x I x Pf x 1.732 VP VELOCITY PRESSURE (INCHES WG)
1000 V VELOCITY (FT./MIN)
12
vLa = Average velocity across the width of the spread.
W = Maximum width in feet of airstream perpendicular to axis of
rotation of the fan. L feet from the fan (feet per minute).
vmax= Maximum velocity L feet from the fan (feet per minute).
L = Distance from fan in feet.
d = Fan diameter in inches. CFM = Free Air Delivery of fan.
NOTE: These formulae are applicable only to fans with a seal ring configuration. For general stamped blade circulation fans, a factor of 50%
of calculated value should be used.
BHP
6 3205 RPM
pressure. Static pressure is read on the vertical axis on the left-hand 13
2
2976 RPM
side of the plot. Static pressure for fans is measured in terms of inches 5
RADIAL
D
12
11
water gauge (in W.G.) C
10 2518 RPM
2747 RPM
1
9 2289 RPM
Suppose you have a Series A46_ _ _ 166DA_ _ _ STOPK3 duct fan 4 8 2060 RPM
1831 RPM
and you know that it is operating at 3205 RPM. You need to supply 7 1602 RPM
0
3500 CFM with this fan and you need to know the fans static pressure 3
capability, the brake horsepower required, as well as the efficiency of SP vs CFM
2 Tip Speed in 1000s
the fan. of Ft./Min.
2 14
Go to example fan curve and read 3500 CFM (Point ) on the System 13
Curve A 12
horizontal axis. Move vertically upward along the 3500 CFM line until B 11
1 10
you intersect the SP vs. CFM curve for 3205 RPM (Point ). At this 7 8
9
20 22 25
18
27
47
29
76
32
05
160 183 60 89 RP RP
intersection move horizontally to the static pressure axis and read 2R
PM
1R
PM RP
M 1 PM
R RP
M
RP
M M M
0
2.15 in. W.G. static pressure. 0 5 10 15 20 25 30 35 40 45 50 60
Now, going back to the 3500 CFM line, continue to move vertically CFM (k100)
until you intersect the BHP vs. CFM curve for 3205 RPM (Point ). At
This is the operating RPM for this fan at the specified performance
Suppose you need 2750 CFM at 1.5" SP. Using the fan curve shown,
point.
you can see that this point (indicated as A) falls between 2518 and
2747 RPM. Going to the BHP curves, you can see that the BHP will Following the 2625 CFM line up to the BHP curves, we see that we
be between 1.4 BHP and 1.8 BHP. The motor HP needed may be 112 intersect the 2518 RPM curve at 1.4 BHP. Again, using the fan laws
or it may be 2 (Point B). we find:
Algebraically rearranging the fan laws to show:
[ ] [ ]
3 3
BHP2 = BHP1 RPM2 2638 = 1.61 (BHP).
= 1.4
RPM1 2518
[ ]
2
SP2 = CFM2 x SP1
CFM1
To obtain 2750 CFM at 1.5" SP, you would have to operate this fan at
you may calculate a system curve based on 2750 CFM and 1.5" SP 2638 RPM and would use 1.61 BHP. You would need a 2 HP motor
(Point A). This system curve crosses the 2518 curve at 2625 CFM. with a 1.0 service factor or a 112 HP motor with a 1.15 service factor.
The 2 HP model code would be 46-16DJ3.
Temperature/Altitude Applications
When a fan operates in standard ambient conditions, it is Correction factors for temperatures and altitudes are provided in
handling air generally at 70F, 29.92 in. Hg barometric pressure, Table 1 and Table 2. When a fan operates at other than standard
weighing 0.075 lbs./cu. ft. Where the fan operates at other than standard ambient conditions, the correction factors in Table 1 and Table 2 will
ambient conditions (temperature, altitude, or both) correction factors be required to correct static pressure and horsepower.
must be applied to the fan performance for proper fan selection. In
addition, the standard construction of the fan may have to be
modified. See the section on Safe Operating Speeds.
Table 1 Temperature Correction Factors
Temp. -25 0 25 50 70 100 150 200 250 300 350 400 450 500 550 600 650 700 750 800
(F)
Factor 0.82 0.87 0.91 0.96 1.00 1.06 1.15 1.25 1.34 1.43 1.53 1.62 1.72 1.81 1.91 2.00 2.09 2.19 2.29 2.38
Above table has inverted values. Actual density ratio is the reciprocal of the above values.
At sea level, at 70F.
For corrections involving both temperature and altitude, correction factors should be multiplied.
Example: 175F at 7000 ft.
Temperature factor 1.15 x altitude factor 1.30 = 1.50 combined correction factor.
Diameter of Pipe 30 45
4" 3' 5'
6" 5' 7' D" R/D = 1.5 R/D = 2.0"
8" 7' 11' D h = 12 D h = 34 D h=D 4' 6' 4'
10" 9' 14' 12" 44' 11' 6' 6" 12' 7'
12" 11' 17' 16" 62' 15' 9' 8" 15' 10'
14" 13' 21' 18" 71' 18' 10' 10" 20' 14'
16" 16' 25' 20" 80' 20' 11' 12" 25' 17'
18" 18' 28' 24" 92' 24' 13' 14" 30' 21'
20" 20' 32' 28" 115' 28' 16' 16" 36' 24'
24" 24' 37' 32" 137' 33' 19' 18" 41' 28'
28" 28' 46' 36" 159' 39' 22' 20" 46' 32'
30" 31' 49' 40" 177' 44' 25' 24" 57' 40'
32" 33' 53' 44" 196' 49' 28' 28" 68' 47'
48" 215' 54' 32' 30" 74' 51'
32" 80' 54'
Rectangular Equivalents of Round Ducts 36" 93' 64'
40" 105' 72'
From ASHVE Guide
42" 111' 76'
Used by permission.
44" 118' 81'
48" 130' 89'
Smooth, Unflanged
well 5 cone, 15 13
rounded per side
Flanged Unflanged
cone, 15 7 pipe 90
per side
Flanged Two-cone,
pipe 50 45 & 15 6
per side
DR = 1.265 (a + b)2
Applications
As mentioned previously, the dBA weighting is a convenient single We can only publish such a dBA rating with an accuracy of 3 dB,
number rating for judging the loudness of a sound. dBAs, however, though. We have no knowledge of the acoustical environment in which
are not practical when comparing two or more noise sources. First, the fan will be installed (a must if one really wishes to accurately
they are relevant only to the environment where they are measured. approximate the level) and offer our rating only as an in-field approxi-
Second, since dBAa are derived from logarithms, noise that appears mation. Hartzell engineering will continue to accurately measure the
twice as loud as another is not twice as many dBAs. To solve this sound output of our fans and to provide guidelines for controlling fan
dilemma, a difference loudness rating was developed. Called sone, it noise. Accurate sound power levels are a must for the sound engineer
is the linear rating, i.e., a noise that appears twice as loud as another to work with.
is twice as many sones as the other noise. It is then possible to compare Sound originates from two basic sources: direct radiation and reflected
any fan to another. See AMCA bulletins 300, 301, and 302 for tech- radiation. We have all removed furniture from a room that we wished
niques using sones. to paint and noticed the acoustical change. Echoes appear when we
Hartzell has in the past released dBA ratings of fans. A fan is almost speak; the room seems to be more alive. This is because we have
always installed in some degree of reverberant field (an environment removed acoustic absorbers (rugs, drapes, furniture, etc.). This is a
where reflections are possible). This rating could in reality (upon good example of the effect of a noise source in an acoustic environment.
installation of the fan) be conservative (low). In fact, there can be as
much as 4 dB difference in a rating between a soft room (much
acoustic absorption) and a hard room (reverberant)! These ratings are
calculated assuming that sound radiated from both the discharge and
upstream opening of the fan contributes to the noise heard.
Stainless Steel
Stainless Steel
Stainless Steel
Epoxy (300F)
Epoxy (300F)
Zinc (150F)
Zinc (150F)
Hetron 693
Hetron 693
Ashland F.
Ashland F.
Aluminum
Aluminum
Reichhold
Reichhold
Neoprene
Neoprene
Inorganic
Inorganic
Coal Tar
Coal Tar
Carbon
Carbon
Epoxy
Epoxy
Monel
Monel
250F
250F
Steel
510A
Steel
510A
6694
6694
Dow
Dow
304
316
304
316
Stainless Steel
Stainless Steel
Stainless Steel
Stainless Steel
Epoxy (300F)
Epoxy (300F)
Zinc (150F)
Zinc (150F)
Hetron 693
Hetron 693
Ashland F.
Ashland F.
Aluminum
Aluminum
Reichhold
Reichhold
Neoprene
Neoprene
Inorganic
Inorganic
Coal Tar
Coal Tar
Carbon
Carbon
Epoxy
Epoxy
Monel
Monel
250F
250F
Steel
510A
Steel
510A
6694
6694
Dow
Dow
304
316
304
316
Chlorobenzene G G G F G NR NR NR NR F F Potassium Chloride F G G G F G 200 240 210 G
Chromic Acid, to 5% F F G NR NR NR 100 110 150 NR NR NR Potassium Cyanide NR G G G F G NR G
Citric Acid F G G NR F G *200 *220 *210 F NR G Potassium G G G F F G 200 220 210 F NR
Copper Acetate NR G G NR NR F 180 220 F Dichromate
Copper Chloride NR NR NR NR NR G *250 *220 *220 G Potassium G G G F G 200 220 210 G
Ferricyanide
Copper Cyanide NR G G NR NR G 90 220S 210 G
Potassium G G G F F G 220 210 G
Copper Nitrate NR G G NR NR G 140 220 210 F Ferrocyanide
Copper Sulfate NR G G NR NR G 250 240 210 F Potassium
Detergents G F F G F 120 170 150 G G NR G G G G G NR 120S 150S G NR G
Hydroxide, to 25%
Ethyl Chloride F G G NR F NR 90 NR G F Potassium
Ethylene Chloride F G G NR NR NR NR G F NR NR NR NR G
Hypochlorite
Ferric Nitrate NR G G NR G 170 220 210 F Potassium Nitrate G G G G F G 200 220 210 G
Ferric Sulphate NR F F NR F G 200 220 210 F Potassium G G G G F 150 210 210 F G(5)
Ferrous Sulphate G F G NR F G 220 220 210 F Permanganate
Fluoboric Acid NR NR F NR G 90S 220S 210S F Potassium Sulphate F G G G G G 200 240 210 G
Formalin Pyrogallic Acid G G G G F F
G G G G G NR 100 110 150 F NR G
Formaldehyde Salt Spray F G G NR G G 200 210 G G G
Formic Acid, to 10% F G G NR F G 200 150 180 F NR Silver Bromide NR F G F G
Furfural to 10% G G G G F F NR 170 NR F NR Silver Nitrate NR G G NR NR G 200 220 210 G
Gallic Acid G G G NR F F F Sodium Acetate G G G F G F 150 220 210 G NR
Gasoline G G G G G F 110 120 G G G Sodium Bisulfate F G G NR F F 200 220 210 G
Hydrobromic Acid, NR NR NR NR NR NR *160 *170 *180 F NR Sodium Borate F G G F F F 170 220 210 G NR
to 25% Sodium Carbonate,
Hydrochloric Acid, NR G G G G G 90S 200S 180S G NR
NR NR NR NR F G *230 *210 210S F NR G to 35%
to 15% Sodium Chlorate F G G F G G 90 210 210 G NR
Hypochlorus Acid NR NR NR NR 90 110 F Sodium Chloride F F G F G G 200 240 180 G(30) NR G
Hydrocyanic Acid, G G G F G 200 170 210 F Sodium Citrate NR G G 180 G
to 10% Sodium Dichromate G G F 160 220 210 F NR
Hydrofluosilicic NR NR NR F F *100S *150S *180S F Sodium Ferricyanide G G G F 220 220 210 G
Acid, to 10%
Sodium Fluoride F G G NR G NR 180S 180S G
Hydrofluoric Acid, NR NR NR NR G G ^100 ^150 ^150 F NR
to 10% Sodium Hydroxide, NR G G G G G NR 160S 180S G NR G
to 10%
Hydrogen Peroxide, G G G NR F F 120 100 150 G NR G
to 30% Sodium Hypochlorite, NR F F NR NR G NR 125S 180S G NR G(5)
to 15%
Hydrogen Sulfide, G F G G NR G 250 240 180 F NR G
to 5% Sodium Hyposulfite NR G G F 210 G
Lactic Acid F F G NR NR G *200 *220 *210 F NR Sodium Nitrate G G G G F F 220 220 210 G
Magnesium Sodium Nitrite G G G F 220 G
F G G F G 160 210 180 G Sodium Perchlorate,
Carbonate G G G NR
Magnesium Chloride NR F G F G G 220 240 210 G NR to 10%
Magnesium Nitrate G G G F G 160 220 210 G Sodium Peroxide F G G F F G F
Magnesium Sodium Phosphate NR G G G F 180 210 G G(10)
NR NR NR F Sodium Salicylate NR G G
Oxychloride
Maleic Acid G G G G F NR 210 F Sodium Silicate F G G G F G 160S 210S G NR
Manganese Sodium Sulfate F G G G G G 180 240 210 F NR
F G G F G
Carbonate Sodium Sulfite F G G F G 180 220 210 F NR
Mercurous Nitrate NR G G NR F Sodium Sulfide NR G G G F G 90S 220 210 G NR
Methyl Ethyl Ketone, G G G G NR NR 80 NR F G F Stannic Chloride NR NR NR NR NR F *180 *220 *210 NR
to 10% Stannous Chloride NR F F NR F G *200 *220 *210 F
Methylene Chloride NR G G G F NR NR NR G F Steam Vapor G G G G G G 180 210 180 G
Naphtha G G G G F NR 200 210 180 G G G Stearic Acid G G G F F F 200 220 210 G NR
Napthalensulfonic NR NR NR NR NR Strontium Hydroxide NR G G G
Acid Strontium Nitrate NR G G G F
Nickel Chloride NR F F NR F F 220 220 210 G Sulfur Dioxide Gas G G G G NR G 200 250 210 NR NR
Nickel Nitrate NR G G NR NR 220 220 210 F Sulfuric Acid, to 25% NR NR NR NR F G *200 *220 *210 F NR G
Nickel Sulphate NR F F NR F G 220 220 210 G Sulfurous Acid,
Nitric Acid, to 5% NR G G NR NR F 200 170 150 F NR F to 10% F F F NR NR NR 90 110 120 F NR
Nitrous Acid F G G NR NR 90 F Tannic Acid F G G F F G 200 220 210 G(50) NR G
Oleic Acid G G G F G F 200 220 210 G NR Tartaric Acid F G G NR F G 220 220 210 G NR
Oxalic Acid, to 10% NR G G NR F F *220 *220 120 G NR G(20) Trichlorethylene F G G G G NR NR 130 NR NR F
Perchloric Acid, NR NR NR F H/D 150 150 F NR Water (Moisture) G G G NR G G 180 210 200 G G G
to 10%** Xylol-Toluol G G G G NR 90 80 80 G G G
Phenol, to 10% G G G NR F NR 80 NR G(10) F Zinc Chloride NR G G NR F G *200 *220 *210 G
Phosphoric Acid, NR G G NR F F *220 *210 *210 F NR NR Zinc Cyanide (Moist) NR G G 150 F
to 10%
Zinc Nitrate F G G 180 220 210 G
Phosphoric G G G F F
Anhydride Zinc Sulfate F G G NR F G 200 220 210 F
Picric Acid, to 10% G G G NR NR G 100 170 NR NR KEY: G = Good F = Fair NR = Not Recommended
Potassium Bromide F G G NR F G 170 210 G = Unknown S = Synthetic Veil Required
* Special shaft and hardware required. H/D = Suitable For Hood & Duct Applications At Ambient Conditions Only
** Special design considerations (explosive environment), contact factory.
*** Temperature values shown for fiberglass resins are for immersion or condensate contact applications.
^ Do not use HartKoate. Special shaft and hardware required, contact factory. For environments not shown, or when temperatures exceed the
maximum listed, contact factory. Do not use HartKoate (Alum. Oxide) with Hydrofluoric acid.
Where temperature values are shown, resin is suitable for hood and duct type applications for the full operating temperature range of the product.
See product specifications for materials of construction and maximum operating temperature limits.
Concentrations are considered to be 100%, except when indicated by (%).