Kuwait Oil Company Doc. No.

: IA-27542-000-E-019
(K.S.C.) Job No. : G05021

DATA SHEETS
FOR
Tank Gauging & Management System

PROJECT : CRUDE EXPORT FACILITIES AT NTF, STF AND MAA

LOCATION : AL AHMADI, KUWAIT

COMPANY : KUWAIT OIL COMPANY (K.S.C)

CONTRACT NO. : 27542

For Construction
0 Jul. 24, 2006 S. C. Chang S.I. Kim K.T. Kim
(27542/KH/T/5180)
B Apr. 18, 2006 For Approval S. C. Chang T.S. Kim K.T. Kim
A Feb. 20, 2006 For Approval S. C. Chang T.S. Kim K.T. Kim
REV DATE DESCRIPTION PREPARED CHECKED APPROVED

IA-27542-000-E-019-rev0.doc
Data Sheet For DOC. NO. : IA-27542-000-E-019
JOB NO. : G05021
Tank Gauging & REV. NO. :0
Management System PAGE : 2 of 3

REVISION LOG

REV. REVISED
REV. DATE REVISION DESCRIPTION
NO. PAGE
A Feb.20, 2006 For Approval
B Apr.18, 2006 Revised as per 27542/KH/T/0493
0 Jul. 24, 2006 For Construction (27542/KH/T/5180)

IA-27542-000-E-019-rev0.doc
Data Sheet For DOC. NO. : IA-27542-000-E-019
JOB NO. : G05021
Tank Gauging & REV. NO. :0
Management System PAGE : 3 of 3

ATTACHMENT #1

Data Sheets

(IA-27542-000-E-019)

IA-27542-000-E-019-rev0.doc
LEVEL INSTRUMENTS SHEET 1 OF 23
KUWAIT OIL (RADAR TYPE)
COMPANY NO. BY DATE REVISION DATA SHEET. NO. REV.
(K.S.C) A K.N.Kim 19 Feb. 2006 FOR APPROVAL IA-27542-000-E-019 0
B K.N.Kim 18 Apr. 2006 FOR APPROVAL CONTRACT ISSUE DATE
0 S.C.CHANG 24 Jul. 2006 FOR CONSTRUCTION G05021 24 Jul. 2006
REQ. P.O.

BY CHKD APPR.
S.C.C T.S.KIM K.T.KIM
1 Tag No. 270-LT-70 (Note 1) 270-LT-71 (Note 1) 270-LT-72 (Note 1)
2 Quantity 1 1 1
GENERAL 3 Service Heavy Crude Oil Tank Heavy Crude Oil Tank Heavy Crude Oil Tank
4 Tank Type Floating Roof Tank Floating Roof Tank Floating Roof Tank
5 Tank No. 270-TK-70 270-TK-71 270-TK-72
6 P&ID No. (BB-27542-) 270-B-009 (1/2) 270-B-009 (2/2) 270-B-010 (1/2)
7 Nace (MR0175) for all wetted part Yes Yes Yes
8 Area Classification Zone 1, Group IIA,IIB, T3 Zone 1, Group IIA,IIB, T3 Zone 1, Group IIA,IIB, T3
9 Pressure Max/nor. (bar g) ATM/ATM ATM/ATM ATM/ATM
PROCESS 10 Temperature Nor./Max/Design () 15.6/55/93 15.6/55/93 15.6/55/93
CONDITION 11 Viscosity (Cp) /base @ 127.5 / 60 deg F 127.5 / 60 deg F 127.5 / 60 deg F
12 Density (kg/m3) 923 923 923
13 Mounting type Inclined Inclined Inclined
14 Process Connection 8" 300# RF 8" 300# RF 8" 300# RF
15 Measuring Range (mm) 18,000 18,000 18,000
TANK 16 Antenna Type STILL PIPE ARRAY STILL PIPE ARRAY STILL PIPE ARRAY
CONNECTION 17 Propagation mode LOW LOSS MODE LOW LOSS MODE LOW LOSS MODE
18 Antenna Size by Vendor by Vendor by Vendor
19 Antenna surfaces by Vendor by Vendor by Vendor
20 Material by Vendor by Vendor by Vendor
21 Certification IEC 60529 IEC 60529 IEC 60529
22 Mounting ON TANK CONNECTION ON TANK CONNECTION ON TANK CONNECTION
23 Measuring Type RADAR RADAR RADAR
24 Measurement Principle by Vendor by Vendor by Vendor
25 Internal reference by Vendor by Vendor by Vendor
RADAR 26 Material Epoxy Painted Alum. Epoxy Painted Alum. Epoxy Painted Alum.
TRANSMITTER 27 Output Signal Multi-drop Field Bus Multi-drop Field Bus Multi-drop Field Bus
HEAD 28 Power Supply 110V AC, 50Hz 110V AC, 50Hz 110V AC, 50Hz
29 Electrical Connection M20 X 1.5 mm M20 X 1.5 mm M20 X 1.5 mm
30 Lightning protection Yes Yes Yes
31 Enclosure Class IP 65 IP 65 IP 65
32 Instrument accuracy 0.5 mm 0.5 mm 0.5 mm
33 Accuracy approvals OIML R85 OIML R85 OIML R85
34 Configuration IC-27542-000-E-002-1,2,3IC-27542-000-E-002-1,2,3IC-27542-000-E-002-1,2,3
35 Type Multi-functional Indicating Multi-functional Indicating Multi-functional Indicating
36 Display LCD type or eq. LCD type or eq. LCD type or eq.
SDAU 37 Cable Connection by Vendor by Vendor by Vendor
/Display 38 Wiring by Vendor by Vendor by Vendor
39 Sun-shade Yes Yes Yes
40 Enclosure Class IP 65 IP 65 IP 65
41 Type Qt'y (Point) 3 wire PT100 14 3 wire PT100 14 3 wire PT100 14
42 Over all length (mm) 18,000 18,000 18,000
43 Certification IEC IEC IEC
44 Connection Size & Rating 3" 300# RF 3" 300# RF 3" 300# RF
COMBINED 45 Electrical Connection M20 X 1.5 mm M20 X 1.5 mm M20 X 1.5 mm
TEMPERATURE 46 Measuring Range () Vendor STD Vendor STD Vendor STD
& OIL/WATER 47 Accuracy () 0.17 0.17 0.17
SENSOR 48 Bulb Material 316 SS 316 SS 316 SS
49 Bulb Diameter by Vendor by Vendor by Vendor
50 Mounting 3" Stilling Well 3" Stilling Well 3" Stilling Well
51 Output Direct conn. to RADAR Direct conn. to RADAR Direct conn. to RADAR
52 Combined Oil/Water Level Sensor Yes Yes Yes
53 - Sensor Type Microwave Probe Microwave Probe Microwave Probe
54 - Measuring Range (mm) 0 - 500 from the BTM 0 - 500 from the BTM 0 - 500 from the BTM
55 Stilling Well by Others by Others by Others
OPTION 56 Pressure Sensor Input Yes Yes Yes

57 Manufacturer Saab Rosemount Saab Rosemount Saab Rosemount


58 Model Number REX RTG 3950 REX RTG 3950 REX RTG 3950
Notes :
1. Each Instrument shall have an SS Tag Plate containing Tag No., Model No., Size, Rating, etc., securely fastened to the instrument.
2. Vendor shall provide the following items as per MR-27542-000-E-004 as a minimum;
FBM(Field Bus Modem), FCU (Field Communication Unit), Calibration Kits, Local Control Cabinets, Redundant Communication FO HART
modem for AMS, Interface module with DCS/Console, Interconnection Cables etc.
LEVEL INSTRUMENTS SHEET 2 OF 23
KUWAIT OIL (RADAR TYPE)
COMPANY NO. BY DATE REVISION DATA SHEET. NO. REV.
(K.S.C) A K.N.Kim 19 Feb. 2006 FOR APPROVAL IA-27542-000-E-019 0
B K.N.Kim 18 Apr. 2006 FOR APPROVAL CONTRACT ISSUE DATE
0 S.C.CHANG 24 Jul. 2006 FOR CONSTRUCTION G05021 24 Jul. 2006
REQ. P.O.

BY CHKD APPR.
S.C.C T.S.KIM K.T.KIM
1 Tag No. 270-LT-73 (Note 1) 270-LT-74 (Note 1) 270-LT-75 (Note 1)
2 Quantity 1 1 1
GENERAL 3 Service Heavy Crude Oil Tank Heavy Crude Oil Tank Heavy Crude Oil Tank
4 Tank Type Floating Roof Tank Floating Roof Tank Floating Roof Tank
5 Tank No. 270-TK-73 270-TK-74 270-TK-75
6 P&ID No. (BB-27542-) 270-B-010 (2/2) 270-B-011 (1/2) 270-B-011 (2/2)
7 Nace (MR0175) for all wetted part Yes Yes Yes
8 Area Classification Zone 1, Group IIA,IIB, T3 Zone 1, Group IIA,IIB, T3 Zone 1, Group IIA,IIB, T3
9 Pressure Max/nor. (bar g) ATM/ATM ATM/ATM ATM/ATM
PROCESS 10 Temperature Nor./Max/Design () 15.6/55/93 15.6/55/93 15.6/55/93
CONDITION 11 Viscosity (Cp) /base @ 127.5 / 60 deg F 127.5 / 60 deg F 127.5 / 60 deg F
12 Density (kg/m3) 923 923 923
13 Mounting type Inclined Inclined Inclined
14 Process Connection 8" 300# RF 8" 300# RF 8" 300# RF
15 Measuring Range (mm) 18,000 18,000 18,000
TANK 16 Antenna Type STILL PIPE ARRAY STILL PIPE ARRAY STILL PIPE ARRAY
CONNECTION 17 Propagation mode LOW LOSS MODE LOW LOSS MODE LOW LOSS MODE
18 Antenna Size by Vendor by Vendor by Vendor
19 Antenna surfaces by Vendor by Vendor by Vendor
20 Material by Vendor by Vendor by Vendor
21 Certification IEC 60529 IEC 60529 IEC 60529
22 Mounting ON TANK CONNECTION ON TANK CONNECTION ON TANK CONNECTION
23 Measuring Type RADAR RADAR RADAR
24 Measurement Principle by Vendor by Vendor by Vendor
25 Internal reference by Vendor by Vendor by Vendor
RADAR 26 Material Epoxy Painted Alum. Epoxy Painted Alum. Epoxy Painted Alum.
TRANSMITTER 27 Output Signal Multi-drop Field Bus Multi-drop Field Bus Multi-drop Field Bus
HEAD 28 Power Supply 110V AC, 50Hz 110V AC, 50Hz 110V AC, 50Hz
29 Electrical Connection M20 X 1.5 mm M20 X 1.5 mm M20 X 1.5 mm
30 Lightning protection Yes Yes Yes
31 Enclosure Class IP 65 IP 65 IP 65
32 Instrument accuracy 0.5 mm 0.5 mm 0.5 mm
33 Accuracy approvals OIML R85 OIML R85 OIML R85
34 Configuration IC-27542-000-E-002-1,2,3IC-27542-000-E-002-1,2,3IC-27542-000-E-002-1,2,3
35 Type Multi-functional Indicating Multi-functional Indicating Multi-functional Indicating
36 Display LCD type or eq. LCD type or eq. LCD type or eq.
SDAU 37 Cable Connection by Vendor by Vendor by Vendor
/Display 38 Wiring by Vendor by Vendor by Vendor
39 Sun-shade Yes Yes Yes
40 Enclosure Class IP 65 IP 65 IP 65
41 Type Qt'y (Point) 3 wire PT100 14 3 wire PT100 14 3 wire PT100 14
42 Over all length (mm) 18,000 18,000 18,000
43 Certification IEC IEC IEC
44 Connection Size & Rating 3" 300# RF 3" 300# RF 3" 300# RF
COMBINED 45 Electrical Connection M20 X 1.5 mm M20 X 1.5 mm M20 X 1.5 mm
TEMPERATURE 46 Measuring Range () Vendor STD Vendor STD Vendor STD
& OIL/WATER 47 Accuracy () 0.17 0.17 0.17
SENSOR 48 Bulb Material 316 SS 316 SS 316 SS
49 Bulb Diameter by Vendor by Vendor by Vendor
50 Mounting 3" Stilling Well 3" Stilling Well 3" Stilling Well
51 Output Direct conn. to RADAR Direct conn. to RADAR Direct conn. to RADAR
52 Combined Oil/Water Level Sensor Yes Yes Yes
53 - Sensor Type Microwave Probe Microwave Probe Microwave Probe
54 - Measuring Range (mm) 0 - 500 from the BTM 0 - 500 from the BTM 0 - 500 from the BTM
55 Stilling Well by Others by Others by Others
OPTION 56 Pressure Sensor Input Yes Yes Yes

57 Manufacturer Saab Rosemount Saab Rosemount Saab Rosemount


58 Model Number REX RTG 3950 REX RTG 3950 REX RTG 3950
Notes :
1. Each Instrument shall have an SS Tag Plate containing Tag No., Model No., Size, Rating, etc., securely fastened to the instrument.
2. Vendor shall provide the following items as per MR-27542-000-E-004 as a minimum;
FBM(Field Bus Modem), FCU (Field Communication Unit), Calibration Kits, Local Control Cabinets, Redundant Communication FO HART
modem for AMS, Interface module with DCS/Console, Interconnection Cables etc.
LEVEL INSTRUMENTS SHEET 3 OF 23
KUWAIT OIL (RADAR TYPE)
COMPANY NO. BY DATE REVISION DATA SHEET. NO. REV.
(K.S.C) A K.N.Kim 19 Feb. 2006 FOR APPROVAL IA-27542-000-E-019 0
B K.N.Kim 18 Apr. 2006 FOR APPROVAL CONTRACT ISSUE DATE
0 S.C.CHANG 24 Jul. 2006 FOR CONSTRUCTION G05021 24 Jul. 2006
REQ. P.O.

BY CHKD APPR.
S.C.C T.S.KIM K.T.KIM
1 Tag No. 270-LT-76 (Note 1) 270-LT-77 (Note 1) 270-LT-78 (Note 1)
2 Quantity 1 1 1
GENERAL 3 Service Crude Oil Tank Crude Oil Tank Crude Oil Tank
4 Tank Type Floating Roof Tank Floating Roof Tank Floating Roof Tank
5 Tank No. 270-TK-76 270-TK-77 270-TK-78
6 P&ID No. (BB-27542-) 270-B-012 (1/2) 270-B-012 (2/2) 270-B-013 (1/2)
7 Nace (MR0175) for all wetted part Yes Yes Yes
8 Area Classification Zone 1, Group IIA,IIB, T3 Zone 1, Group IIA,IIB, T3 Zone 1, Group IIA,IIB, T3
9 Pressure Max/nor. (bar g) ATM/ATM ATM/ATM ATM/ATM
PROCESS 10 Temperature Nor./Max/Design () 15.6/55/93 15.6/55/93 15.6/55/93
CONDITION 11 Viscosity (Cp) /base @ 18.8 / 60 deg F 18.8 / 60 deg F 18.8 / 60 deg F
12 Density (kg/m3) 882 882 882
13 Mounting type Inclined Inclined Inclined
14 Process Connection 8" 300# RF 8" 300# RF 8" 300# RF
15 Measuring Range (mm) 18,000 18,000 18,000
TANK 16 Antenna Type STILL PIPE ARRAY STILL PIPE ARRAY STILL PIPE ARRAY
CONNECTION 17 Propagation mode LOW LOSS MODE LOW LOSS MODE LOW LOSS MODE
18 Antenna Size by Vendor by Vendor by Vendor
19 Antenna surfaces by Vendor by Vendor by Vendor
20 Material by Vendor by Vendor by Vendor
21 Certification IEC 60529 IEC 60529 IEC 60529
22 Mounting ON TANK CONNECTION ON TANK CONNECTION ON TANK CONNECTION
23 Measuring Type RADAR RADAR RADAR
24 Measurement Principle by Vendor by Vendor by Vendor
25 Internal reference by Vendor by Vendor by Vendor
RADAR 26 Material Epoxy Painted Alum. Epoxy Painted Alum. Epoxy Painted Alum.
TRANSMITTER 27 Output Signal Multi-drop Field Bus Multi-drop Field Bus Multi-drop Field Bus
HEAD 28 Power Supply 110V AC, 50Hz 110V AC, 50Hz 110V AC, 50Hz
29 Electrical Connection M20 X 1.5 mm M20 X 1.5 mm M20 X 1.5 mm
30 Lightning protection Yes Yes Yes
31 Enclosure Class IP 65 IP 65 IP 65
32 Instrument accuracy 0.5 mm 0.5 mm 0.5 mm
33 Accuracy approvals OIML R85 OIML R85 OIML R85
34 Configuration IC-27542-000-E-002-1,2,3IC-27542-000-E-002-1,2,3IC-27542-000-E-002-1,2,3
35 Type Multi-functional Indicating Multi-functional Indicating Multi-functional Indicating
36 Display LCD type or eq. LCD type or eq. LCD type or eq.
SDAU 37 Cable Connection by Vendor by Vendor by Vendor
/Display 38 Wiring by Vendor by Vendor by Vendor
39 Sun-shade Yes Yes Yes
40 Enclosure Class IP 65 IP 65 IP 65
41 Type Qt'y (Point) 3 wire PT100 14 3 wire PT100 14 3 wire PT100 14
42 Over all length (mm) 18,000 18,000 18,000
43 Certification IEC IEC IEC
44 Connection Size & Rating 3" 300# RF 3" 300# RF 3" 300# RF
COMBINED 45 Electrical Connection M20 X 1.5 mm M20 X 1.5 mm M20 X 1.5 mm
TEMPERATURE 46 Measuring Range () Vendor STD Vendor STD Vendor STD
& OIL/WATER 47 Accuracy () 0.17 0.17 0.17
SENSOR 48 Bulb Material 316 SS 316 SS 316 SS
49 Bulb Diameter by Vendor by Vendor by Vendor
50 Mounting 3" Stilling Well 3" Stilling Well 3" Stilling Well
51 Output Direct conn. to RADAR Direct conn. to RADAR Direct conn. to RADAR
52 Combined Oil/Water Level Sensor Yes Yes Yes
53 - Sensor Type Microwave Probe Microwave Probe Microwave Probe
54 - Measuring Range (mm) 0 - 500 from the BTM 0 - 500 from the BTM 0 - 500 from the BTM
55 Stilling Well by Others by Others by Others
OPTION 56 Pressure Sensor Input Yes Yes Yes

57 Manufacturer Saab Rosemount Saab Rosemount Saab Rosemount


58 Model Number REX RTG 3950 REX RTG 3950 REX RTG 3950
Notes :
1. Each Instrument shall have an SS Tag Plate containing Tag No., Model No., Size, Rating, etc., securely fastened to the instrument.
2. Vendor shall provide the following items as per MR-27542-000-E-004 as a minimum;
FBM(Field Bus Modem), FCU (Field Communication Unit), Calibration Kits, Local Control Cabinets, Redundant Communication FO HART
modem for AMS, Interface module with DCS/Console, Interconnection Cables etc.
LEVEL INSTRUMENTS SHEET 4 OF 23
KUWAIT OIL (RADAR TYPE)
COMPANY NO. BY DATE REVISION DATA SHEET. NO. REV.
(K.S.C) A K.N.Kim 19 Feb. 2006 FOR APPROVAL IA-27542-000-E-019 0
B K.N.Kim 18 Apr. 2006 FOR APPROVAL CONTRACT ISSUE DATE
0 S.C.CHANG 24 Jul. 2006 FOR CONSTRUCTION G05021 24 Jul. 2006
REQ. P.O.

BY CHKD APPR.
S.C.C T.S.KIM K.T.KIM
1 Tag No. 270-LT-79 (Note 1) 270-LT-80 (Note 1) 270-LT-81 (Note 1)
2 Quantity 1 1 1
GENERAL 3 Service Crude Oil Tank Crude Oil Tank Crude Oil Tank
4 Tank Type Floating Roof Tank Floating Roof Tank Floating Roof Tank
5 Tank No. 270-TK-79 270-TK-80 270-TK-81
6 P&ID No. (BB-27542-) 270-B-013 (2/2) 270-B-014 (1/1) 270-B-015 (1/2)
7 Nace (MR0175) for all wetted part Yes Yes Yes
8 Area Classification Zone 1, Group IIA,IIB, T3 Zone 1, Group IIA,IIB, T3 Zone 1, Group IIA,IIB, T3
9 Pressure Max/nor. (bar g) ATM/ATM ATM/ATM ATM/ATM
PROCESS 10 Temperature Nor./Max/Design () 15.6/55/93 15.6/55/93 15.6/55/93
CONDITION 11 Viscosity (Cp) /base @ 18.8 / 60 deg F 18.8 / 60 deg F 18.8 / 60 deg F
12 Density (kg/m3) 882 882 882
13 Mounting type Inclined Inclined Inclined
14 Process Connection 8" 300# RF 8" 300# RF 8" 300# RF
15 Measuring Range (mm) 18,000 18,000 18,000
TANK 16 Antenna Type STILL PIPE ARRAY STILL PIPE ARRAY STILL PIPE ARRAY
CONNECTION 17 Propagation mode LOW LOSS MODE LOW LOSS MODE LOW LOSS MODE
18 Antenna Size by Vendor by Vendor by Vendor
19 Antenna surfaces by Vendor by Vendor by Vendor
20 Material by Vendor by Vendor by Vendor
21 Certification IEC 60529 IEC 60529 IEC 60529
22 Mounting ON TANK CONNECTION ON TANK CONNECTION ON TANK CONNECTION
23 Measuring Type RADAR RADAR RADAR
24 Measurement Principle by Vendor by Vendor by Vendor
25 Internal reference by Vendor by Vendor by Vendor
RADAR 26 Material Epoxy Painted Alum. Epoxy Painted Alum. Epoxy Painted Alum.
TRANSMITTER 27 Output Signal Multi-drop Field Bus Multi-drop Field Bus Multi-drop Field Bus
HEAD 28 Power Supply 110V AC, 50Hz 110V AC, 50Hz 110V AC, 50Hz
29 Electrical Connection M20 X 1.5 mm M20 X 1.5 mm M20 X 1.5 mm
30 Lightning protection Yes Yes Yes
31 Enclosure Class IP 65 IP 65 IP 65
32 Instrument accuracy 0.5 mm 0.5 mm 0.5 mm
33 Accuracy approvals OIML R85 OIML R85 OIML R85
34 Configuration IC-27542-000-E-002-1,2,3IC-27542-000-E-002-1,2,3IC-27542-000-E-002-1,2,3
35 Type Multi-functional Indicating Multi-functional Indicating Multi-functional Indicating
36 Display LCD type or eq. LCD type or eq. LCD type or eq.
SDAU 37 Cable Connection by Vendor by Vendor by Vendor
/Display 38 Wiring by Vendor by Vendor by Vendor
39 Sun-shade Yes Yes Yes
40 Enclosure Class IP 65 IP 65 IP 65
41 Type Qt'y (Point) 3 wire PT100 14 3 wire PT100 14 3 wire PT100 14
42 Over all length (mm) 18,000 18,000 18,000
43 Certification IEC IEC IEC
44 Connection Size & Rating 3" 300# RF 3" 300# RF 3" 300# RF
COMBINED 45 Electrical Connection M20 X 1.5 mm M20 X 1.5 mm M20 X 1.5 mm
TEMPERATURE 46 Measuring Range () Vendor STD Vendor STD Vendor STD
& OIL/WATER 47 Accuracy () 0.17 0.17 0.17
SENSOR 48 Bulb Material 316 SS 316 SS 316 SS
49 Bulb Diameter by Vendor by Vendor by Vendor
50 Mounting 3" Stilling Well 3" Stilling Well 3" Stilling Well
51 Output Direct conn. to RADAR Direct conn. to RADAR Direct conn. to RADAR
52 Combined Oil/Water Level Sensor Yes Yes Yes
53 - Sensor Type Microwave Probe Microwave Probe Microwave Probe
54 - Measuring Range (mm) 0 - 500 from the BTM 0 - 500 from the BTM 0 - 500 from the BTM
55 Stilling Well by Others by Others by Others
OPTION 56 Pressure Sensor Input Yes Yes Yes

57 Manufacturer Saab Rosemount Saab Rosemount Saab Rosemount


58 Model Number REX RTG 3950 REX RTG 3950 REX RTG 3950
Notes :
1. Each Instrument shall have an SS Tag Plate containing Tag No., Model No., Size, Rating, etc., securely fastened to the instrument.
2. Vendor shall provide the following items as per MR-27542-000-E-004 as a minimum;
FBM(Field Bus Modem), FCU (Field Communication Unit), Calibration Kits, Local Control Cabinets, Redundant Communication FO HART
modem for AMS, Interface module with DCS/Console, Interconnection Cables etc.
LEVEL INSTRUMENTS SHEET 5 OF 23
KUWAIT OIL (RADAR TYPE)
COMPANY NO. BY DATE REVISION DATA SHEET. NO. REV.
(K.S.C) A K.N.Kim 19 Feb. 2006 FOR APPROVAL IA-27542-000-E-019 0
B K.N.Kim 18 Apr. 2006 FOR APPROVAL CONTRACT ISSUE DATE
0 S.C.CHANG 24 Jul. 2006 FOR CONSTRUCTION G05021 24 Jul. 2006
REQ. P.O.

BY CHKD APPR.
S.C.C T.S.KIM K.T.KIM
1 Tag No. 270-LT-82 (Note 1) 270-LT-83 (Note 1) 270-LT-84 (Note 1)
2 Quantity 1 1 1
GENERAL 3 Service Crude Oil Tank Crude Oil Tank Crude Oil Tank
4 Tank Type Floating Roof Tank Floating Roof Tank Floating Roof Tank
5 Tank No. 270-TK-82 270-TK-83 270-TK-84
6 P&ID No. (BB-27542-) 270-B-015 (2/2) 270-B-016 (1/2) 270-B-016 (2/2)
7 Nace for all wetted part Yes Yes Yes
8 Area Classification Zone 1, Group IIA,IIB, T3 Zone 1, Group IIA,IIB, T3 Zone 1, Group IIA,IIB, T3
9 Pressure Max/nor. (bar g) ATM/ATM ATM/ATM ATM/ATM
PROCESS 10 Temperature Nor./Max/Design () 15.6/55/93 15.6/55/93 15.6/55/93
CONDITION 11 Viscosity (Cp) /base @ 18.8 / 60 deg F 18.8 / 60 deg F 18.8 / 60 deg F
12 Density (kg/m3) 882 882 882
13 Mounting type Inclined Inclined Inclined
14 Process Connection 8" 300# RF 8" 300# RF 8" 300# RF
15 Measuring Range (mm) 18,000 18,000 18,000
TANK 16 Antenna Type STILL PIPE ARRAY STILL PIPE ARRAY STILL PIPE ARRAY
CONNECTION 17 Propagation mode LOW LOSS MODE LOW LOSS MODE LOW LOSS MODE
18 Antenna Size by Vendor by Vendor by Vendor
19 Antenna surfaces by Vendor by Vendor by Vendor
20 Material by Vendor by Vendor by Vendor
21 Certification IEC 60529 IEC 60529 IEC 60529
22 Mounting ON TANK CONNECTION ON TANK CONNECTION ON TANK CONNECTION
23 Measuring Type RADAR RADAR RADAR
24 Measurement Principle by Vendor by Vendor by Vendor
25 Internal reference by Vendor by Vendor by Vendor
RADAR 26 Material Epoxy Painted Alum. Epoxy Painted Alum. Epoxy Painted Alum.
TRANSMITTER 27 Output Signal Multi-drop Field Bus Multi-drop Field Bus Multi-drop Field Bus
HEAD 28 Power Supply 110V AC, 50Hz 110V AC, 50Hz 110V AC, 50Hz
29 Electrical Connection M20 X 1.5 mm M20 X 1.5 mm M20 X 1.5 mm
30 Lightning protection Yes Yes Yes
31 Enclosure Class IP 65 IP 65 IP 65
32 Instrument accuracy 0.5 mm 0.5 mm 0.5 mm
33 Accuracy approvals OIML R85 OIML R85 OIML R85
34 Configuration IC-27542-000-E-002-1,2,3IC-27542-000-E-002-1,2,3IC-27542-000-E-002-1,2,3
35 Type Multi-functional Indicating Multi-functional Indicating Multi-functional Indicating
36 Display LCD type or eq. LCD type or eq. LCD type or eq.
SDAU 37 Cable Connection by Vendor by Vendor by Vendor
/Display 38 Wiring by Vendor by Vendor by Vendor
39 Sun-shade Yes Yes Yes
40 Enclosure Class IP 65 IP 65 IP 65
41 Type Qt'y (Point) 3 wire PT100 14 3 wire PT100 14 3 wire PT100 14
42 Over all length (mm) 18,000 18,000 18,000
43 Certification IEC IEC IEC
44 Connection Size & Rating 3" 300# RF 3" 300# RF 3" 300# RF
COMBINED 45 Electrical Connection M20 X 1.5 mm M20 X 1.5 mm M20 X 1.5 mm
TEMPERATURE 46 Measuring Range () Vendor STD Vendor STD Vendor STD
& OIL/WATER 47 Accuracy () 0.17 0.17 0.17
SENSOR 48 Bulb Material 316 SS 316 SS 316 SS
49 Bulb Diameter by Vendor by Vendor by Vendor
50 Mounting 3" Stilling Well 3" Stilling Well 3" Stilling Well
51 Output Direct conn. to RADAR Direct conn. to RADAR Direct conn. to RADAR
52 Combined Oil/Water Level Sensor Yes Yes Yes
53 - Sensor Type Microwave Probe Microwave Probe Microwave Probe
54 - Measuring Range (mm) 0 - 500 from the BTM 0 - 500 from the BTM 0 - 500 from the BTM
55 Stilling Well by Others by Others by Others
OPTION 56 Pressure Sensor Input Yes Yes Yes

57 Manufacturer Saab Rosemount Saab Rosemount Saab Rosemount


58 Model Number REX RTG 3950 REX RTG 3950 REX RTG 3950
Notes :
1. Each Instrument shall have an SS Tag Plate containing Tag No., Model No., Size, Rating, etc., securely fastened to the instrument.
2. Vendor shall provide the following items as per MR-27542-000-E-004 as a minimum;
FBM(Field Bus Modem), FCU (Field Communication Unit), Calibration Kits, Local Control Cabinets, Redundant Communication FO HART
modem for AMS, Interface module with DCS/Console, Interconnection Cables etc.
LEVEL INSTRUMENTS SHEET 6 OF 23
KUWAIT OIL (RADAR TYPE)
COMPANY NO. BY DATE REVISION DATA SHEET. NO. REV.
(K.S.C) A K.N.Kim 19 Feb. 2006 FOR APPROVAL IA-27542-000-E-019 0
B K.N.Kim 18 Apr. 2006 FOR APPROVAL CONTRACT ISSUE DATE
0 S.C.CHANG 24 Jul. 2006 FOR CONSTRUCTION G05021 24 Jul. 2006
REQ. P.O.

BY CHKD APPR.
S.C.C T.S.KIM K.T.KIM
1 Tag No. 270-LT-36 (Note 1) 270-LT-37 (Note 1) 270-LT-38 (Note 1)
2 Quantity 1 1 1
GENERAL 3 Service Crude Oil Tank Crude Oil Tank Crude Oil Tank
4 Tank Type Floating Roof Tank Floating Roof Tank Floating Roof Tank
5 Tank No. 270-TK-36 270-TK-37 270-TK-38
6 P&ID No. (BB-27542-) Note 2 Note 2 Note 2
7 Nace (MR0175) for all wetted part Yes Yes Yes
8 Area Classification Zone 1, Group IIA,IIB, T3 Zone 1, Group IIA,IIB, T3 Zone 1, Group IIA,IIB, T3
9 Pressure Max/nor. (bar g) ATM/ATM ATM/ATM ATM/ATM
PROCESS 10 Temperature Nor./Max/Design () 15.6/55/93 15.6/55/93 15.6/55/93
CONDITION 11 Viscosity (Cp) /base @ 18.8 / 60 deg F 18.8 / 60 deg F 18.8 / 60 deg F
12 Density (kg/m3) Note 2 Note 2 Note 2
13 Mounting type Inclined Inclined Inclined
14 Process Connection Note 2 Note 2 Note 2
15 Measuring Range (mm) Note 2 Note 2 Note 2
TANK 16 Antenna Type STILL PIPE ARRAY STILL PIPE ARRAY STILL PIPE ARRAY
CONNECTION 17 Propagation mode LOW LOSS MODE LOW LOSS MODE LOW LOSS MODE
18 Antenna Size by Vendor by Vendor by Vendor
19 Antenna surfaces by Vendor by Vendor by Vendor
20 Material by Vendor by Vendor by Vendor
21 Certification IEC 60529 IEC 60529 IEC 60529
22 Mounting ON TANK CONNECTION ON TANK CONNECTION ON TANK CONNECTION
23 Measuring Type RADAR RADAR RADAR
24 Measurement Principle by Vendor by Vendor by Vendor
25 Internal reference by Vendor by Vendor by Vendor
RADAR 26 Material Epoxy Painted Alum. Epoxy Painted Alum. Epoxy Painted Alum.
TRANSMITTER 27 Output Signal Multi-drop Field Bus Multi-drop Field Bus Multi-drop Field Bus
HEAD 28 Power Supply 110V AC, 50Hz 110V AC, 50Hz 110V AC, 50Hz
29 Electrical Connection M20 X 1.5 mm M20 X 1.5 mm M20 X 1.5 mm
30 Lightning protection Yes Yes Yes
31 Enclosure Class IP 65 IP 65 IP 65
32 Instrument accuracy 0.5 mm 0.5 mm 0.5 mm
33 Accuracy approvals OIML R85 OIML R85 OIML R85
34 Configuration IC-27542-000-E-002-1,2,3IC-27542-000-E-002-1,2,3IC-27542-000-E-002-1,2,3
35 Type Multi-functional Indicating Multi-functional Indicating Multi-functional Indicating
36 Display LCD type or eq. LCD type or eq. LCD type or eq.
SDAU 37 Cable Connection by Vendor by Vendor by Vendor
/Display 38 Wiring by Vendor by Vendor by Vendor
39 Sun-shade Yes Yes Yes
40 Enclosure Class IP 65 IP 65 IP 65
41 Type Qt'y (Point) 3 wire PT100 14 3 wire PT100 14 3 wire PT100 14
42 Over all length (mm) Note 2 Note 2 Note 2
43 Certification IEC IEC IEC
44 Connection Size & Rating Note 2 Note 2 Note 2
COMBINED 45 Electrical Connection M20 X 1.5 mm M20 X 1.5 mm M20 X 1.5 mm
TEMPERATURE 46 Measuring Range () Vendor STD Vendor STD Vendor STD
& OIL/WATER 47 Accuracy () 0.17 0.17 0.17
SENSOR 48 Bulb Material 316 SS 316 SS 316 SS
49 Bulb Diameter by Vendor by Vendor by Vendor
50 Mounting Note 2 Note 2 Note 2
51 Output Direct conn. to RADAR Direct conn. to RADAR Direct conn. to RADAR
52 Combined Oil/Water Level Sensor Yes Yes Yes
53 - Sensor Type Microwave Probe Microwave Probe Microwave Probe
54 - Measuring Range (mm) 0 - 500 from the BTM 0 - 500 from the BTM 0 - 500 from the BTM
55 Stilling Well None None None
OPTION 56 Pressure Sensor Input Yes Yes Yes

57 Manufacturer Saab Rosemount Saab Rosemount Saab Rosemount


58 Model Number REX RTG 3950 REX RTG 3950 REX RTG 3950
Notes :
1. Each Instrument shall have an SS Tag Plate containing Tag No., Model No., Size, Rating, etc., securely fastened to the instrument.
2. To be informed later.
3. Vendor shall provide the following items as per MR-27542-000-E-004 as a minimum;
FBM(Field Bus Modem), FCU (Field Communication Unit), Calibration Kits, Local Control Cabinets, Redundant Communication FO HART
modem for AMS, Interface module with DCS/Console, Interconnection Cables etc.
LEVEL INSTRUMENTS SHEET 7 OF 23
KUWAIT OIL (RADAR TYPE)
COMPANY NO. BY DATE REVISION DATA SHEET. NO. REV.
(K.S.C) A K.N.Kim 19 Feb. 2006 FOR APPROVAL IA-27542-000-E-019 0
B K.N.Kim 18 Apr. 2006 FOR APPROVAL CONTRACT ISSUE DATE
0 S.C.CHANG 24 Jul. 2006 FOR CONSTRUCTION G05021 24 Jul. 2006
REQ. P.O.

BY CHKD APPR.
S.C.C T.S.KIM K.T.KIM
1 Tag No. 270-LT-39 (Note 1) 270-LT-40 (Note 1) 270-LT-41 (Note 1)
2 Quantity 1 1 1
GENERAL 3 Service Crude Oil Tank Crude Oil Tank Crude Oil Tank
4 Tank Type Floating Roof Tank Floating Roof Tank Floating Roof Tank
5 Tank No. 270-TK-39 270-TK-40 270-TK-41
6 P&ID No. (BB-27542-) Note 2 Note 2 Note 2
7 Nace (MR0175) for all wetted part Yes Yes Yes
8 Area Classification Zone 1, Group IIA,IIB, T3 Zone 1, Group IIA,IIB, T3 Zone 1, Group IIA,IIB, T3
9 Pressure Max/nor. (bar g) ATM/ATM ATM/ATM ATM/ATM
PROCESS 10 Temperature Nor./Max/Design () 15.6/55/93 15.6/55/93 15.6/55/93
CONDITION 11 Viscosity (Cp) /base @ 18.8 / 60 deg F 18.8 / 60 deg F 18.8 / 60 deg F
12 Density (kg/m3) Note 2 Note 2 Note 2
13 Mounting type Inclined Inclined Inclined
14 Process Connection Note 2 Note 2 Note 2
15 Measuring Range (mm) Note 2 Note 2 Note 2
TANK 16 Antenna Type STILL PIPE ARRAY STILL PIPE ARRAY STILL PIPE ARRAY
CONNECTION 17 Propagation mode LOW LOSS MODE LOW LOSS MODE LOW LOSS MODE
18 Antenna Size by Vendor by Vendor by Vendor
19 Antenna surfaces by Vendor by Vendor by Vendor
20 Material by Vendor by Vendor by Vendor
21 Certification IEC 60529 IEC 60529 IEC 60529
22 Mounting ON TANK CONNECTION ON TANK CONNECTION ON TANK CONNECTION
23 Measuring Type RADAR RADAR RADAR
24 Measurement Principle by Vendor by Vendor by Vendor
25 Internal reference by Vendor by Vendor by Vendor
RADAR 26 Material Epoxy Painted Alum. Epoxy Painted Alum. Epoxy Painted Alum.
TRANSMITTER 27 Output Signal Multi-drop Field Bus Multi-drop Field Bus Multi-drop Field Bus
HEAD 28 Power Supply 110V AC, 50Hz 110V AC, 50Hz 110V AC, 50Hz
29 Electrical Connection M20 X 1.5 mm M20 X 1.5 mm M20 X 1.5 mm
30 Lightning protection Yes Yes Yes
31 Enclosure Class IP 65 IP 65 IP 65
32 Instrument accuracy 0.5 mm 0.5 mm 0.5 mm
33 Accuracy approvals OIML R85 OIML R85 OIML R85
34 Configuration IC-27542-000-E-002-1,2,3IC-27542-000-E-002-1,2,3IC-27542-000-E-002-1,2,3
35 Type Multi-functional Indicating Multi-functional Indicating Multi-functional Indicating
36 Display LCD type or eq. LCD type or eq. LCD type or eq.
SDAU 37 Cable Connection by Vendor by Vendor by Vendor
/Display 38 Wiring by Vendor by Vendor by Vendor
39 Sun-shade Yes Yes Yes
40 Enclosure Class IP 65 IP 65 IP 65
41 Type Qt'y (Point) 3 wire PT100 14 3 wire PT100 14 3 wire PT100 14
42 Over all length (mm) Note 2 Note 2 Note 2
43 Certification IEC IEC IEC
44 Connection Size & Rating Note 2 Note 2 Note 2
COMBINED 45 Electrical Connection M20 X 1.5 mm M20 X 1.5 mm M20 X 1.5 mm
TEMPERATURE 46 Measuring Range () Vendor STD Vendor STD Vendor STD
& OIL/WATER 47 Accuracy () 0.17 0.17 0.17
SENSOR 48 Bulb Material 316 SS 316 SS 316 SS
49 Bulb Diameter by Vendor by Vendor by Vendor
50 Mounting Note 2 Note 2 Note 2
51 Output Direct conn. to RADAR Direct conn. to RADAR Direct conn. to RADAR
52 Combined Oil/Water Level Sensor Yes Yes Yes
53 - Sensor Type Microwave Probe Microwave Probe Microwave Probe
54 - Measuring Range (mm) 0 - 500 from the BTM 0 - 500 from the BTM 0 - 500 from the BTM
55 Stilling Well None None None
OPTION 56 Pressure Sensor Input Yes Yes Yes

57 Manufacturer Saab Rosemount Saab Rosemount Saab Rosemount


58 Model Number REX RTG 3950 REX RTG 3950 REX RTG 3950
Notes :
1. Each Instrument shall have an SS Tag Plate containing Tag No., Model No., Size, Rating, etc., securely fastened to the instrument.
2. To be informed later.
3. Vendor shall provide the following items as per MR-27542-000-E-004 as a minimum;
FBM(Field Bus Modem), FCU (Field Communication Unit), Calibration Kits, Local Control Cabinets, Redundant Communication FO HART
modem for AMS, Interface module with DCS/Console, Interconnection Cables etc.
LEVEL INSTRUMENTS SHEET 8 OF 23
KUWAIT OIL (RADAR TYPE)
COMPANY NO. BY DATE REVISION DATA SHEET. NO. REV.
(K.S.C) A K.N.Kim 19 Feb. 2006 FOR APPROVAL IA-27542-000-E-019 0
B K.N.Kim 18 Apr. 2006 FOR APPROVAL CONTRACT ISSUE DATE
0 S.C.CHANG 24 Jul. 2006 FOR CONSTRUCTION G05021 24 Jul. 2006
REQ. P.O.

BY CHKD APPR.
S.C.C T.S.KIM K.T.KIM
1 Tag No. 270-LT-42 (Note 1) 270-LT-43 (Note 1) 270-LT-51 (Note 1)
2 Quantity 1 1 1
GENERAL 3 Service Crude Oil Tank Crude Oil Tank Crude Oil Tank
4 Tank Type Floating Roof Tank Floating Roof Tank Floating Roof Tank
5 Tank No. 270-TK-42 270-TK-43 270-TK-51
6 P&ID No. (BB-27542-) Note 2 Note 2 Note 2
7 Nace (MR0175) for all wetted part Yes Yes Yes
8 Area Classification Zone 1, Group IIA,IIB, T3 Zone 1, Group IIA,IIB, T3 Zone 1, Group IIA,IIB, T3
9 Pressure Max/nor. (bar g) ATM/ATM ATM/ATM ATM/ATM
PROCESS 10 Temperature Nor./Max/Design () 15.6/55/93 15.6/55/93 15.6/55/93
CONDITION 11 Viscosity (Cp) /base @ 18.8 / 60 deg F 18.8 / 60 deg F 18.8 / 60 deg F
12 Density (kg/m3) Note 2 Note 2 Note 2
13 Mounting type Inclined Inclined Inclined
14 Process Connection Note 2 Note 2 Note 2
15 Measuring Range (mm) Note 2 Note 2 Note 2
TANK 16 Antenna Type STILL PIPE ARRAY STILL PIPE ARRAY STILL PIPE ARRAY
CONNECTION 17 Propagation mode LOW LOSS MODE LOW LOSS MODE LOW LOSS MODE
18 Antenna Size by Vendor by Vendor by Vendor
19 Antenna surfaces by Vendor by Vendor by Vendor
20 Material by Vendor by Vendor by Vendor
21 Certification IEC 60529 IEC 60529 IEC 60529
22 Mounting ON TANK CONNECTION ON TANK CONNECTION ON TANK CONNECTION
23 Measuring Type RADAR RADAR RADAR
24 Measurement Principle by Vendor by Vendor by Vendor
25 Internal reference by Vendor by Vendor by Vendor
RADAR 26 Material Epoxy Painted Alum. Epoxy Painted Alum. Epoxy Painted Alum.
TRANSMITTER 27 Output Signal Multi-drop Field Bus Multi-drop Field Bus Multi-drop Field Bus
HEAD 28 Power Supply 110V AC, 50Hz 110V AC, 50Hz 110V AC, 50Hz
29 Electrical Connection M20 X 1.5 mm M20 X 1.5 mm M20 X 1.5 mm
30 Lightning protection Yes Yes Yes
31 Enclosure Class IP 65 IP 65 IP 65
32 Instrument accuracy 0.5 mm 0.5 mm 0.5 mm
33 Accuracy approvals OIML R85 OIML R85 OIML R85
34 Configuration IC-27542-000-E-002-1,2,3IC-27542-000-E-002-1,2,3IC-27542-000-E-002-1,2,3
35 Type Multi-functional Indicating Multi-functional Indicating Multi-functional Indicating
36 Display LCD type or eq. LCD type or eq. LCD type or eq.
SDAU 37 Cable Connection by Vendor by Vendor by Vendor
/Display 38 Wiring by Vendor by Vendor by Vendor
39 Sun-shade Yes Yes Yes
40 Enclosure Class IP 65 IP 65 IP 65
41 Type Qt'y (Point) 3 wire PT100 14 3 wire PT100 14 3 wire PT100 14
42 Over all length (mm) Note 2 Note 2 Note 2
43 Certification IEC IEC IEC
44 Connection Size & Rating Note 2 Note 2 Note 2
COMBINED 45 Electrical Connection M20 X 1.5 mm M20 X 1.5 mm M20 X 1.5 mm
TEMPERATURE 46 Measuring Range () Vendor STD Vendor STD Vendor STD
& OIL/WATER 47 Accuracy () 0.17 0.17 0.17
SENSOR 48 Bulb Material 316 SS 316 SS 316 SS
49 Bulb Diameter by Vendor by Vendor by Vendor
50 Mounting Note 2 Note 2 Note 2
51 Output Direct conn. to RADAR Direct conn. to RADAR Direct conn. to RADAR
52 Combined Oil/Water Level Sensor Yes Yes Yes
53 - Sensor Type Microwave Probe Microwave Probe Microwave Probe
54 - Measuring Range (mm) 0 - 500 from the BTM 0 - 500 from the BTM 0 - 500 from the BTM
55 Stilling Well None None None
OPTION 56 Pressure Sensor Input Yes Yes Yes

57 Manufacturer Saab Rosemount Saab Rosemount Saab Rosemount


58 Model Number REX RTG 3950 REX RTG 3950 REX RTG 3950
Notes :
1. Each Instrument shall have an SS Tag Plate containing Tag No., Model No., Size, Rating, etc., securely fastened to the instrument.
2. To be informed later.
3. Vendor shall provide the following items as per MR-27542-000-E-004 as a minimum;
FBM(Field Bus Modem), FCU (Field Communication Unit), Calibration Kits, Local Control Cabinets, Redundant Communication FO HART
modem for AMS, Interface module with DCS/Console, Interconnection Cables etc.
LEVEL INSTRUMENTS SHEET 9 OF 23
KUWAIT OIL (RADAR TYPE)
COMPANY NO. BY DATE REVISION DATA SHEET. NO. REV.
(K.S.C) A K.N.Kim 19 Feb. 2006 FOR APPROVAL IA-27542-000-E-019 0
B K.N.Kim 18 Apr. 2006 FOR APPROVAL CONTRACT ISSUE DATE
0 S.C.CHANG 24 Jul. 2006 FOR CONSTRUCTION G05021 24 Jul. 2006
REQ. P.O.

BY CHKD APPR.
S.C.C T.S.KIM K.T.KIM
1 Tag No. 270-LT-52 (Note 1) 270-LT-53 (Note 1) 270-LT-54 (Note 1)
2 Quantity 1 1 1
GENERAL 3 Service Crude Oil Tank Crude Oil Tank Crude Oil Tank
4 Tank Type Floating Roof Tank Floating Roof Tank Floating Roof Tank
5 Tank No. 270-TK-52 270-TK-53 270-TK-54
6 P&ID No. (BB-27542-) Note 2 Note 2 Note 2
7 Nace (MR0175) for all wetted part Yes Yes Yes
8 Area Classification Zone 1, Group IIA,IIB, T3 Zone 1, Group IIA,IIB, T3 Zone 1, Group IIA,IIB, T3
9 Pressure Max/nor. (bar g) ATM/ATM ATM/ATM ATM/ATM
PROCESS 10 Temperature Nor./Max/Design () 15.6/55/93 15.6/55/93 15.6/55/93
CONDITION 11 Viscosity (Cp) /base @ 18.8 / 60 deg F 18.8 / 60 deg F 18.8 / 60 deg F
12 Density (kg/m3) Note 2 Note 2 Note 2
13 Mounting type Inclined Inclined Inclined
14 Process Connection Note 2 Note 2 Note 2
15 Measuring Range (mm) Note 2 Note 2 Note 2
TANK 16 Antenna Type STILL PIPE ARRAY STILL PIPE ARRAY STILL PIPE ARRAY
CONNECTION 17 Propagation mode LOW LOSS MODE LOW LOSS MODE LOW LOSS MODE
18 Antenna Size by Vendor by Vendor by Vendor
19 Antenna surfaces by Vendor by Vendor by Vendor
20 Material by Vendor by Vendor by Vendor
21 Certification IEC 60529 IEC 60529 IEC 60529
22 Mounting ON TANK CONNECTION ON TANK CONNECTION ON TANK CONNECTION
23 Measuring Type RADAR RADAR RADAR
24 Measurement Principle by Vendor by Vendor by Vendor
25 Internal reference by Vendor by Vendor by Vendor
RADAR 26 Material Epoxy Painted Alum. Epoxy Painted Alum. Epoxy Painted Alum.
TRANSMITTER 27 Output Signal Multi-drop Field Bus Multi-drop Field Bus Multi-drop Field Bus
HEAD 28 Power Supply 110V AC, 50Hz 110V AC, 50Hz 110V AC, 50Hz
29 Electrical Connection M20 X 1.5 mm M20 X 1.5 mm M20 X 1.5 mm
30 Lightning protection Yes Yes Yes
31 Enclosure Class IP 65 IP 65 IP 65
32 Instrument accuracy 0.5 mm 0.5 mm 0.5 mm
33 Accuracy approvals OIML R85 OIML R85 OIML R85
34 Configuration IC-27542-000-E-002-1,2,3IC-27542-000-E-002-1,2,3IC-27542-000-E-002-1,2,3
35 Type Multi-functional Indicating Multi-functional Indicating Multi-functional Indicating
36 Display LCD type or eq. LCD type or eq. LCD type or eq.
SDAU 37 Cable Connection by Vendor by Vendor by Vendor
/Display 38 Wiring by Vendor by Vendor by Vendor
39 Sun-shade Yes Yes Yes
40 Enclosure Class IP 65 IP 65 IP 65
41 Type Qt'y (Point) 3 wire PT100 14 3 wire PT100 14 3 wire PT100 14
42 Over all length (mm) Note 2 Note 2 Note 2
43 Certification IEC IEC IEC
44 Connection Size & Rating Note 2 Note 2 Note 2
COMBINED 45 Electrical Connection M20 X 1.5 mm M20 X 1.5 mm M20 X 1.5 mm
TEMPERATURE 46 Measuring Range () Vendor STD Vendor STD Vendor STD
& OIL/WATER 47 Accuracy () 0.17 0.17 0.17
SENSOR 48 Bulb Material 316 SS 316 SS 316 SS
49 Bulb Diameter by Vendor by Vendor by Vendor
50 Mounting Note 2 Note 2 Note 2
51 Output Direct conn. to RADAR Direct conn. to RADAR Direct conn. to RADAR
52 Combined Oil/Water Level Sensor Yes Yes Yes
53 - Sensor Type Microwave Probe Microwave Probe Microwave Probe
54 - Measuring Range (mm) 0 - 500 from the BTM 0 - 500 from the BTM 0 - 500 from the BTM
55 Stilling Well None None None
OPTION 56 Pressure Sensor Input Yes Yes Yes

57 Manufacturer Saab Rosemount Saab Rosemount Saab Rosemount


58 Model Number REX RTG 3950 REX RTG 3950 REX RTG 3950
Notes :
1. Each Instrument shall have an SS Tag Plate containing Tag No., Model No., Size, Rating, etc., securely fastened to the instrument.
2. To be informed later.
3. Vendor shall provide the following items as per MR-27542-000-E-004 as a minimum;
FBM(Field Bus Modem), FCU (Field Communication Unit), Calibration Kits, Local Control Cabinets, Redundant Communication FO HART
modem for AMS, Interface module with DCS/Console, Interconnection Cables etc.
LEVEL INSTRUMENTS SHEET 10 OF 23
KUWAIT OIL (RADAR TYPE)
COMPANY NO. BY DATE REVISION DATA SHEET. NO. REV.
(K.S.C) A K.N.Kim 19 Feb. 2006 FOR APPROVAL IA-27542-000-E-019 0
B K.N.Kim 18 Apr. 2006 FOR APPROVAL CONTRACT ISSUE DATE
0 S.C.CHANG 24 Jul. 2006 FOR CONSTRUCTION G05021 24 Jul. 2006
REQ. P.O.

BY CHKD APPR.
S.C.C T.S.KIM K.T.KIM
1 Tag No. 270-LT-55 (Note 1) 270-LT-56 (Note 1) 270-LT-57 (Note 1)
2 Quantity 1 1 1
GENERAL 3 Service Crude Oil Tank Crude Oil Tank Crude Oil Tank
4 Tank Type Floating Roof Tank Floating Roof Tank Floating Roof Tank
5 Tank No. 270-TK-55 270-TK-56 270-TK-57
6 P&ID No. (BB-27542-) Note 2 Note 2 Note 2
7 Nace (MR0175) for all wetted part Yes Yes Yes
8 Area Classification Zone 1, Group IIA,IIB, T3 Zone 1, Group IIA,IIB, T3 Zone 1, Group IIA,IIB, T3
9 Pressure Max/nor. (bar g) ATM/ATM ATM/ATM ATM/ATM
PROCESS 10 Temperature Nor./Max/Design () 15.6/55/93 15.6/55/93 15.6/55/93
CONDITION 11 Viscosity (Cp) /base @ 18.8 / 60 deg F 18.8 / 60 deg F 18.8 / 60 deg F
12 Density (kg/m3) Note 2 Note 2 Note 2
13 Mounting type Inclined Inclined Inclined
14 Process Connection Note 2 Note 2 Note 2
15 Measuring Range (mm) Note 2 Note 2 Note 2
TANK 16 Antenna Type STILL PIPE ARRAY STILL PIPE ARRAY STILL PIPE ARRAY
CONNECTION 17 Propagation mode LOW LOSS MODE LOW LOSS MODE LOW LOSS MODE
18 Antenna Size by Vendor by Vendor by Vendor
19 Antenna surfaces by Vendor by Vendor by Vendor
20 Material by Vendor by Vendor by Vendor
21 Certification IEC 60529 IEC 60529 IEC 60529
22 Mounting ON TANK CONNECTION ON TANK CONNECTION ON TANK CONNECTION
23 Measuring Type RADAR RADAR RADAR
24 Measurement Principle by Vendor by Vendor by Vendor
25 Internal reference by Vendor by Vendor by Vendor
RADAR 26 Material Epoxy Painted Alum. Epoxy Painted Alum. Epoxy Painted Alum.
TRANSMITTER 27 Output Signal Multi-drop Field Bus Multi-drop Field Bus Multi-drop Field Bus
HEAD 28 Power Supply 110V AC, 50Hz 110V AC, 50Hz 110V AC, 50Hz
29 Electrical Connection M20 X 1.5 mm M20 X 1.5 mm M20 X 1.5 mm
30 Lightning protection Yes Yes Yes
31 Enclosure Class IP 65 IP 65 IP 65
32 Instrument accuracy 0.5 mm 0.5 mm 0.5 mm
33 Accuracy approvals OIML R85 OIML R85 OIML R85
34 Configuration IC-27542-000-E-002-1,2,3IC-27542-000-E-002-1,2,3IC-27542-000-E-002-1,2,3
35 Type Multi-functional Indicating Multi-functional Indicating Multi-functional Indicating
36 Display LCD type or eq. LCD type or eq. LCD type or eq.
SDAU 37 Cable Connection by Vendor by Vendor by Vendor
/Display 38 Wiring by Vendor by Vendor by Vendor
39 Sun-shade Yes Yes Yes
40 Enclosure Class IP 65 IP 65 IP 65
41 Type Qt'y (Point) 3 wire PT100 14 3 wire PT100 14 3 wire PT100 14
42 Over all length (mm) Note 2 Note 2 Note 2
43 Certification IEC IEC IEC
44 Connection Size & Rating Note 2 Note 2 Note 2
COMBINED 45 Electrical Connection M20 X 1.5 mm M20 X 1.5 mm M20 X 1.5 mm
TEMPERATURE 46 Measuring Range () Vendor STD Vendor STD Vendor STD
& OIL/WATER 47 Accuracy () 0.17 0.17 0.17
SENSOR 48 Bulb Material 316 SS 316 SS 316 SS
49 Bulb Diameter by Vendor by Vendor by Vendor
50 Mounting Note 2 Note 2 Note 2
51 Output Direct conn. to RADAR Direct conn. to RADAR Direct conn. to RADAR
52 Combined Oil/Water Level Sensor Yes Yes Yes
53 - Sensor Type Microwave Probe Microwave Probe Microwave Probe
54 - Measuring Range (mm) 0 - 500 from the BTM 0 - 500 from the BTM 0 - 500 from the BTM
55 Stilling Well None None None
OPTION 56 Pressure Sensor Input Yes Yes Yes

57 Manufacturer Saab Rosemount Saab Rosemount Saab Rosemount


58 Model Number REX RTG 3950 REX RTG 3950 REX RTG 3950
Notes :
1. Each Instrument shall have an SS Tag Plate containing Tag No., Model No., Size, Rating, etc., securely fastened to the instrument.
2. To be informed later.
3. Vendor shall provide the following items as per MR-27542-000-E-004 as a minimum;
FBM(Field Bus Modem), FCU (Field Communication Unit), Calibration Kits, Local Control Cabinets, Redundant Communication FO HART
modem for AMS, Interface module with DCS/Console, Interconnection Cables etc.
LEVEL INSTRUMENTS SHEET 11 OF 23
KUWAIT OIL (RADAR TYPE)
COMPANY NO. BY DATE REVISION DATA SHEET. NO. REV.
(K.S.C) A K.N.Kim 19 Feb. 2006 FOR APPROVAL IA-27542-000-E-019 0
B K.N.Kim 18 Apr. 2006 FOR APPROVAL CONTRACT ISSUE DATE
0 S.C.CHANG 24 Jul. 2006 FOR CONSTRUCTION G05021 24 Jul. 2006
REQ. P.O.

BY CHKD APPR.
S.C.C T.S.KIM K.T.KIM
1 Tag No. 270-LT-58 (Note 1) 270-LT-59 (Note 1)
2 Quantity 1 1
GENERAL 3 Service Crude Oil Tank Crude Oil Tank
4 Tank Type Floating Roof Tank Floating Roof Tank
5 Tank No. 270-TK-58 270-TK-59
6 P&ID No. (BB-27542-) Note 2 Note 2
7 Nace (MR0175) for all wetted part Yes Yes
8 Area Classification Zone 1, Group IIA,IIB, T3 Zone 1, Group IIA,IIB, T3
9 Pressure Max/nor. (bar g) ATM/ATM ATM/ATM
PROCESS 10 Temperature Nor./Max/Design () 15.6/55/93 15.6/55/93
CONDITION 11 Viscosity (Cp) /base @ 18.8 / 60 deg F 18.8 / 60 deg F
12 Density (kg/m3) Note 2 Note 2
13 Mounting type Inclined Inclined
14 Process Connection Note 2 Note 2
15 Measuring Range (mm) Note 2 Note 2
TANK 16 Antenna Type STILL PIPE ARRAY STILL PIPE ARRAY
CONNECTION 17 Propagation mode LOW LOSS MODE LOW LOSS MODE
18 Antenna Size by Vendor by Vendor
19 Antenna surfaces by Vendor by Vendor
20 Material by Vendor by Vendor
21 Certification IEC 60529 IEC 60529
22 Mounting ON TANK CONNECTION ON TANK CONNECTION
23 Measuring Type RADAR RADAR
24 Measurement Principle by Vendor by Vendor
25 Internal reference by Vendor by Vendor
RADAR 26 Material Epoxy Painted Alum. Epoxy Painted Alum.
TRANSMITTER 27 Output Signal Multi-drop Field Bus Multi-drop Field Bus
HEAD 28 Power Supply 110V AC, 50Hz 110V AC, 50Hz
29 Electrical Connection M20 X 1.5 mm M20 X 1.5 mm
30 Lightning protection Yes Yes
31 Enclosure Class IP 65 IP 65
32 Instrument accuracy 0.5 mm 0.5 mm
33 Accuracy approvals OIML R85 OIML R85
34 Configuration IC-27542-000-E-002-1,2,3IC-27542-000-E-002-1,2,3
35 Type Multi-functional Indicating Multi-functional Indicating
36 Display LCD type or eq. LCD type or eq.
SDAU 37 Cable Connection by Vendor by Vendor
/Display 38 Wiring by Vendor by Vendor
39 Sun-shade Yes Yes
40 Enclosure Class IP 65 IP 65
41 Type Qt'y (Point) 3 wire PT100 14 3 wire PT100 14
42 Over all length (mm) Note 2 Note 2
43 Certification IEC IEC
44 Connection Size & Rating Note 2 Note 2
COMBINED 45 Electrical Connection M20 X 1.5 mm M20 X 1.5 mm
TEMPERATURE 46 Measuring Range () Vendor STD Vendor STD
& OIL/WATER 47 Accuracy () 0.17 0.17
SENSOR 48 Bulb Material 316 SS 316 SS
49 Bulb Diameter by Vendor by Vendor
50 Mounting Note 2 Note 2
51 Output Direct conn. to RADAR Direct conn. to RADAR
52 Combined Oil/Water Level Sensor Yes Yes
53 - Sensor Type Microwave Probe Microwave Probe
54 - Measuring Range (mm) 0 - 500 from the BTM 0 - 500 from the BTM
55 Stilling Well None None
OPTION 56 Pressure Sensor Input Yes Yes

57 Manufacturer Saab Rosemount Saab Rosemount


58 Model Number REX RTG 3950 REX RTG 3950
Notes :
1. Each Instrument shall have an SS Tag Plate containing Tag No., Model No., Size, Rating, etc., securely fastened to the instrument.
2. To be informed later.
3. Vendor shall provide the following items as per MR-27542-000-E-004 as a minimum;
FBM(Field Bus Modem), FCU (Field Communication Unit), Calibration Kits, Local Control Cabinets, Redundant Communication FO HART
modem for AMS, Interface module with DCS/Console, Interconnection Cables etc.
LEVEL INSTRUMENTS SHEET 12 OF 23
KUWAIT OIL (RADAR TYPE)
COMPANY NO. BY DATE REVISION DATA SHEET. NO. REV.
(K.S.C) A K.N.Kim 19 Feb. 2006 FOR APPROVAL IA-27542-000-E-019 0
B K.N.Kim 18 Apr. 2006 FOR APPROVAL CONTRACT ISSUE DATE
0 S.C.CHANG 24 Jul. 2006 FOR CONSTRUCTION G05021 24 Jul. 2006
REQ. P.O.

BY CHKD APPR.
S.C.C T.S.KIM K.T.KIM
1 Tag No. 279-LT-66 (Note 1) 279-LT-67 (Note 1) 279-LT-68 (Note 1)
2 Quantity 1 1 1
GENERAL 3 Service Crude Oil Tank Crude Oil Tank Crude Oil Tank
4 Tank Type Floating Roof Tank Floating Roof Tank Floating Roof Tank
5 Tank No. 279-TK-66 279-TK-67 279-TK-68
6 P&ID No. (BB-27542-) 279-B-003 (1/2) 279-B-003 (2/2) 279-B-004 (1/2)
7 Nace (MR0175) for all wetted part Yes Yes Yes
8 Area Classification Zone 1, Group IIA,IIB, T3 Zone 1, Group IIA,IIB, T3 Zone 1, Group IIA,IIB, T3
9 Pressure Max/nor. (bar g) ATM/ATM ATM/ATM ATM/ATM
PROCESS 10 Temperature Nor./Max/Design () 15.6/55/93 15.6/55/93 15.6/55/93
CONDITION 11 Viscosity (Cp) /base @ 18.8 / 60 deg F 18.8 / 60 deg F 18.8 / 60 deg F
12 Density (kg/m3) 882 882 882
13 Mounting type Inclined Inclined Inclined
14 Process Connection 8" 300# RF 8" 300# RF 8" 300# RF
15 Measuring Range (mm) 18,000 18,000 18,000
TANK 16 Antenna Type STILL PIPE ARRAY STILL PIPE ARRAY STILL PIPE ARRAY
CONNECTION 17 Propagation mode LOW LOSS MODE LOW LOSS MODE LOW LOSS MODE
18 Antenna Size by Vendor by Vendor by Vendor
19 Antenna surfaces by Vendor by Vendor by Vendor
20 Material by Vendor by Vendor by Vendor
21 Certification IEC 60529 IEC 60529 IEC 60529
22 Mounting ON TANK CONNECTION ON TANK CONNECTION ON TANK CONNECTION
23 Measuring Type RADAR RADAR RADAR
24 Measurement Principle by Vendor by Vendor by Vendor
25 Internal reference by Vendor by Vendor by Vendor
RADAR 26 Material Epoxy Painted Alum. Epoxy Painted Alum. Epoxy Painted Alum.
TRANSMITTER 27 Output Signal Multi-drop Field Bus Multi-drop Field Bus Multi-drop Field Bus
HEAD 28 Power Supply 110V AC, 50Hz 110V AC, 50Hz 110V AC, 50Hz
29 Electrical Connection M20 X 1.5 mm M20 X 1.5 mm M20 X 1.5 mm
30 Lightning protection Yes Yes Yes
31 Enclosure Class IP 65 IP 65 IP 65
32 Instrument accuracy 0.5 mm 0.5 mm 0.5 mm
33 Accuracy approvals OIML R85 OIML R85 OIML R85
34 Configuration IC-27542-000-E-002-1,2,3IC-27542-000-E-002-1,2,3IC-27542-000-E-002-1,2,3
35 Type Multi-functional Indicating Multi-functional Indicating Multi-functional Indicating
36 Display LCD type or eq. LCD type or eq. LCD type or eq.
SDAU 37 Cable Connection by Vendor by Vendor by Vendor
/Display 38 Wiring by Vendor by Vendor by Vendor
39 Sun-shade Yes Yes Yes
40 Enclosure Class IP 65 IP 65 IP 65
41 Type Qt'y (Point) 3 wire PT100 14 3 wire PT100 14 3 wire PT100 14
42 Over all length (mm) 18,000 18,000 18,000
43 Certification IEC IEC IEC
44 Connection Size & Rating 3" 300# RF 3" 300# RF 3" 300# RF
COMBINED 45 Electrical Connection M20 X 1.5 mm M20 X 1.5 mm M20 X 1.5 mm
TEMPERATURE 46 Measuring Range () Vendor STD Vendor STD Vendor STD
& OIL/WATER 47 Accuracy () 0.17 0.17 0.17
SENSOR 48 Bulb Material 316 SS 316 SS 316 SS
49 Bulb Diameter by Vendor by Vendor by Vendor
50 Mounting 3" Stilling Well 3" Stilling Well 3" Stilling Well
51 Output Direct conn. to RADAR Direct conn. to RADAR Direct conn. to RADAR
52 Combined Oil/Water Level Sensor Yes Yes Yes
53 - Sensor Type Microwave Probe Microwave Probe Microwave Probe
54 - Measuring Range (mm) 0 - 500 from the BTM 0 - 500 from the BTM 0 - 500 from the BTM
55 Stilling Well by Others by Others by Others
OPTION 56 Pressure Sensor Input Yes Yes Yes

57 Manufacturer Saab Rosemount Saab Rosemount Saab Rosemount


58 Model Number REX RTG 3950 REX RTG 3950 REX RTG 3950
Notes :
1. Each Instrument shall have an SS Tag Plate containing Tag No., Model No., Size, Rating, etc., securely fastened to the instrument.
2. Vendor shall provide the following items as per MR-27542-000-E-004 as a minimum;
FBM(Field Bus Modem), FCU (Field Communication Unit), Calibration Kits, Local Control Cabinets, Redundant Communication FO HART
modem for AMS, Interface module with DCS/Console, Interconnection Cables etc.
LEVEL INSTRUMENTS SHEET 13 OF 23
KUWAIT OIL (RADAR TYPE)
COMPANY NO. BY DATE REVISION DATA SHEET. NO. REV.
(K.S.C) A K.N.Kim 19 Feb. 2006 FOR APPROVAL IA-27542-000-E-019 0
B K.N.Kim 18 Apr. 2006 FOR APPROVAL CONTRACT ISSUE DATE
0 S.C.CHANG 24 Jul. 2006 FOR CONSTRUCTION G05021 24 Jul. 2006
REQ. P.O.

BY CHKD APPR.
S.C.C T.S.KIM K.T.KIM
1 Tag No. 279-LT-69 (Note 1) 279-LT-10 (Note 1) 279-LT-11 (Note 1)
2 Quantity 1 1 1
GENERAL 3 Service Crude Oil Tank Crude Oil Tank Crude Oil Tank
4 Tank Type Floating Roof Tank Floating Roof Tank Floating Roof Tank
5 Tank No. 279-TK-69 279-TK-10 279-TK-11
6 P&ID No. (BB-27542-) 279-B-004 (2/2) Note 2 Note 2
7 Nace (MR0175) for all wetted part Yes Yes Yes
8 Area Classification Zone 1, Group IIA,IIB, T3 Zone 1, Group IIA,IIB, T3 Zone 1, Group IIA,IIB, T3
9 Pressure Max/nor. (bar g) ATM/ATM ATM/ATM ATM/ATM
PROCESS 10 Temperature Nor./Max/Design () 15.6/55/93 15.6/55/93 15.6/55/93
CONDITION 11 Viscosity (Cp) /base @ 18.8 / 60 deg F 18.8 / 60 deg F 18.8 / 60 deg F
12 Density (kg/m3) 882 Note 2 Note 2
13 Mounting type Inclined Inclined Inclined
14 Process Connection 8" 300# RF Note 2 Note 2
15 Measuring Range (mm) 18,000 Note 2 Note 2
TANK 16 Antenna Type STILL PIPE ARRAY STILL PIPE ARRAY STILL PIPE ARRAY
CONNECTION 17 Propagation mode LOW LOSS MODE LOW LOSS MODE LOW LOSS MODE
18 Antenna Size by Vendor by Vendor by Vendor
19 Antenna surfaces by Vendor by Vendor by Vendor
20 Material by Vendor by Vendor by Vendor
21 Certification IEC 60529 IEC 60529 IEC 60529
22 Mounting ON TANK CONNECTION ON TANK CONNECTION ON TANK CONNECTION
23 Measuring Type RADAR RADAR RADAR
24 Measurement Principle by Vendor by Vendor by Vendor
25 Internal reference by Vendor by Vendor by Vendor
RADAR 26 Material Epoxy Painted Alum. Epoxy Painted Alum. Epoxy Painted Alum.
TRANSMITTER 27 Output Signal Multi-drop Field Bus Multi-drop Field Bus Multi-drop Field Bus
HEAD 28 Power Supply 110V AC, 50Hz 110V AC, 50Hz 110V AC, 50Hz
29 Electrical Connection M20 X 1.5 mm M20 X 1.5 mm M20 X 1.5 mm
30 Lightning protection Yes Yes Yes
31 Enclosure Class IP 65 IP 65 IP 65
32 Instrument accuracy 0.5 mm 0.5 mm 0.5 mm
33 Accuracy approvals OIML R85 OIML R85 OIML R85
34 Configuration IC-27542-000-E-002-1,2,3IC-27542-000-E-002-1,2,3IC-27542-000-E-002-1,2,3
35 Type Multi-functional Indicating Multi-functional Indicating Multi-functional Indicating
36 Display LCD type or eq. LCD type or eq. LCD type or eq.
SDAU 37 Cable Connection by Vendor by Vendor by Vendor
/Display 38 Wiring by Vendor by Vendor by Vendor
39 Sun-shade Yes Yes Yes
40 Enclosure Class IP 65 IP 65 IP 65
41 Type Qt'y (Point) 3 wire PT100 14 3 wire PT100 14 3 wire PT100 14
42 Over all length (mm) 18,000 Note 2 Note 2
43 Certification IEC IEC IEC
44 Connection Size & Rating 3" 300# RF Note 2 Note 2
COMBINED 45 Electrical Connection M20 X 1.5 mm M20 X 1.5 mm M20 X 1.5 mm
TEMPERATURE 46 Measuring Range () Vendor STD Vendor STD Vendor STD
& OIL/WATER 47 Accuracy () 0.17 0.17 0.17
SENSOR 48 Bulb Material 316 SS 316 SS 316 SS
49 Bulb Diameter by Vendor by Vendor by Vendor
50 Mounting 3" Stilling Well Note 2 Note 2
51 Output Direct conn. to RADAR Direct conn. to RADAR Direct conn. to RADAR
52 Combined Oil/Water Level Sensor Yes Yes Yes
53 - Sensor Type Microwave Probe Microwave Probe Microwave Probe
54 - Measuring Range (mm) 0 - 500 from the BTM 0 - 500 from the BTM 0 - 500 from the BTM
55 Stilling Well by Others None None
OPTION 56 Pressure Sensor Input Yes Yes Yes

57 Manufacturer Saab Rosemount Saab Rosemount Saab Rosemount


58 Model Number REX RTG 3950 REX RTG 3950 REX RTG 3950
Notes :
1. Each Instrument shall have an SS Tag Plate containing Tag No., Model No., Size, Rating, etc., securely fastened to the instrument.
2. To be informed later.
3. Vendor shall provide the following items as per MR-27542-000-E-004 as a minimum;
FBM(Field Bus Modem), FCU (Field Communication Unit), Calibration Kits, Local Control Cabinets, Redundant Communication FO HART
modem for AMS, Interface module with DCS/Console, Interconnection Cables etc.
LEVEL INSTRUMENTS SHEET 14 OF 23
KUWAIT OIL (RADAR TYPE)
COMPANY NO. BY DATE REVISION DATA SHEET. NO. REV.
(K.S.C) A K.N.Kim 19 Feb. 2006 FOR APPROVAL IA-27542-000-E-019 0
B K.N.Kim 18 Apr. 2006 FOR APPROVAL CONTRACT ISSUE DATE
0 S.C.CHANG 24 Jul. 2006 FOR CONSTRUCTION G05021 24 Jul. 2006
REQ. P.O.

BY CHKD APPR.
S.C.C T.S.KIM K.T.KIM
1 Tag No. 279-LT-12 (Note 1) 279-LT-13 (Note 1) 279-LT-14 (Note 1)
2 Quantity 1 1 1
GENERAL 3 Service Crude Oil Tank Crude Oil Tank Crude Oil Tank
4 Tank Type Floating Roof Tank Floating Roof Tank Floating Roof Tank
5 Tank No. 279-TK-12 279-TK-13 279-TK-14
6 P&ID No. (BB-27542-) Note 2 Note 2 Note 2
7 Nace (MR0175) for all wetted part Yes Yes Yes
8 Area Classification Zone 1, Group IIA,IIB, T3 Zone 1, Group IIA,IIB, T3 Zone 1, Group IIA,IIB, T3
9 Pressure Max/nor. (bar g) ATM/ATM ATM/ATM ATM/ATM
PROCESS 10 Temperature Nor./Max/Design () 15.6/55/93 15.6/55/93 15.6/55/93
CONDITION 11 Viscosity (Cp) /base @ 18.8 / 60 deg F 18.8 / 60 deg F 18.8 / 60 deg F
12 Density (kg/m3) Note 2 Note 2 Note 2
13 Mounting type Inclined Inclined Inclined
14 Process Connection Note 2 Note 2 Note 2
15 Measuring Range (mm) Note 2 Note 2 Note 2
TANK 16 Antenna Type STILL PIPE ARRAY STILL PIPE ARRAY STILL PIPE ARRAY
CONNECTION 17 Propagation mode LOW LOSS MODE LOW LOSS MODE LOW LOSS MODE
18 Antenna Size by Vendor by Vendor by Vendor
19 Antenna surfaces by Vendor by Vendor by Vendor
20 Material by Vendor by Vendor by Vendor
21 Certification IEC 60529 IEC 60529 IEC 60529
22 Mounting ON TANK CONNECTION ON TANK CONNECTION ON TANK CONNECTION
23 Measuring Type RADAR RADAR RADAR
24 Measurement Principle by Vendor by Vendor by Vendor
25 Internal reference by Vendor by Vendor by Vendor
RADAR 26 Material Epoxy Painted Alum. Epoxy Painted Alum. Epoxy Painted Alum.
TRANSMITTER 27 Output Signal Multi-drop Field Bus Multi-drop Field Bus Multi-drop Field Bus
HEAD 28 Power Supply 110V AC, 50Hz 110V AC, 50Hz 110V AC, 50Hz
29 Electrical Connection M20 X 1.5 mm M20 X 1.5 mm M20 X 1.5 mm
30 Lightning protection Yes Yes Yes
31 Enclosure Class IP 65 IP 65 IP 65
32 Instrument accuracy 0.5 mm 0.5 mm 0.5 mm
33 Accuracy approvals OIML R85 OIML R85 OIML R85
34 Configuration IC-27542-000-E-002-1,2,3IC-27542-000-E-002-1,2,3IC-27542-000-E-002-1,2,3
35 Type Multi-functional Indicating Multi-functional Indicating Multi-functional Indicating
36 Display LCD type or eq. LCD type or eq. LCD type or eq.
SDAU 37 Cable Connection by Vendor by Vendor by Vendor
/Display 38 Wiring by Vendor by Vendor by Vendor
39 Sun-shade Yes Yes Yes
40 Enclosure Class IP 65 IP 65 IP 65
41 Type Qt'y (Point) 3 wire PT100 14 3 wire PT100 14 3 wire PT100 14
42 Over all length (mm) Note 2 Note 2 Note 2
43 Certification IEC IEC IEC
44 Connection Size & Rating Note 2 Note 2 Note 2
COMBINED 45 Electrical Connection M20 X 1.5 mm M20 X 1.5 mm M20 X 1.5 mm
TEMPERATURE 46 Measuring Range () Vendor STD Vendor STD Vendor STD
& OIL/WATER 47 Accuracy () 0.17 0.17 0.17
SENSOR 48 Bulb Material 316 SS 316 SS 316 SS
49 Bulb Diameter by Vendor by Vendor by Vendor
50 Mounting Note 2 Note 2 Note 2
51 Output Direct conn. to RADAR Direct conn. to RADAR Direct conn. to RADAR
52 Combined Oil/Water Level Sensor Yes Yes Yes
53 - Sensor Type Microwave Probe Microwave Probe Microwave Probe
54 - Measuring Range (mm) 0 - 500 from the BTM 0 - 500 from the BTM 0 - 500 from the BTM
55 Stilling Well None None None
OPTION 56 Pressure Sensor Input Yes Yes Yes

57 Manufacturer Saab Rosemount Saab Rosemount Saab Rosemount


58 Model Number REX RTG 3950 REX RTG 3950 REX RTG 3950
Notes :
1. Each Instrument shall have an SS Tag Plate containing Tag No., Model No., Size, Rating, etc., securely fastened to the instrument.
2. To be informed later.
3. Vendor shall provide the following items as per MR-27542-000-E-004 as a minimum;
FBM(Field Bus Modem), FCU (Field Communication Unit), Calibration Kits, Local Control Cabinets, Redundant Communication FO HART
modem for AMS, Interface module with DCS/Console, Interconnection Cables etc.
LEVEL INSTRUMENTS SHEET 15 OF 23
KUWAIT OIL (RADAR TYPE)
COMPANY NO. BY DATE REVISION DATA SHEET. NO. REV.
(K.S.C) A K.N.Kim 19 Feb. 2006 FOR APPROVAL IA-27542-000-E-019 0
B K.N.Kim 18 Apr. 2006 FOR APPROVAL CONTRACT ISSUE DATE
0 S.C.CHANG 24 Jul. 2006 FOR CONSTRUCTION G05021 24 Jul. 2006
REQ. P.O.

BY CHKD APPR.
S.C.C T.S.KIM K.T.KIM
1 Tag No. 279-LT-15 (Note 1) 279-LT-16 (Note 1) 279-LT-17 (Note 1)
2 Quantity 1 1 1
GENERAL 3 Service Crude Oil Tank Crude Oil Tank Crude Oil Tank
4 Tank Type Floating Roof Tank Floating Roof Tank Floating Roof Tank
5 Tank No. 279-TK-15 279-TK-16 279-TK-17
6 P&ID No. (BB-27542-) Note 2 Note 2 Note 2
7 Nace (MR0175) for all wetted part Yes Yes Yes
8 Area Classification Zone 1, Group IIA,IIB, T3 Zone 1, Group IIA,IIB, T3 Zone 1, Group IIA,IIB, T3
9 Pressure Max/nor. (bar g) ATM/ATM ATM/ATM ATM/ATM
PROCESS 10 Temperature Nor./Max/Design () 15.6/55/93 15.6/55/93 15.6/55/93
CONDITION 11 Viscosity (Cp) /base @ 18.8 / 60 deg F 18.8 / 60 deg F 18.8 / 60 deg F
12 Density (kg/m3) Note 2 Note 2 Note 2
13 Mounting type Inclined Inclined Inclined
14 Process Connection Note 2 Note 2 Note 2
15 Measuring Range (mm) Note 2 Note 2 Note 2
TANK 16 Antenna Type STILL PIPE ARRAY STILL PIPE ARRAY STILL PIPE ARRAY
CONNECTION 17 Propagation mode LOW LOSS MODE LOW LOSS MODE LOW LOSS MODE
18 Antenna Size by Vendor by Vendor by Vendor
19 Antenna surfaces by Vendor by Vendor by Vendor
20 Material by Vendor by Vendor by Vendor
21 Certification IEC 60529 IEC 60529 IEC 60529
22 Mounting ON TANK CONNECTION ON TANK CONNECTION ON TANK CONNECTION
23 Measuring Type RADAR RADAR RADAR
24 Measurement Principle by Vendor by Vendor by Vendor
25 Internal reference by Vendor by Vendor by Vendor
RADAR 26 Material Epoxy Painted Alum. Epoxy Painted Alum. Epoxy Painted Alum.
TRANSMITTER 27 Output Signal Multi-drop Field Bus Multi-drop Field Bus Multi-drop Field Bus
HEAD 28 Power Supply 110V AC, 50Hz 110V AC, 50Hz 110V AC, 50Hz
29 Electrical Connection M20 X 1.5 mm M20 X 1.5 mm M20 X 1.5 mm
30 Lightning protection Yes Yes Yes
31 Enclosure Class IP 65 IP 65 IP 65
32 Instrument accuracy 0.5 mm 0.5 mm 0.5 mm
33 Accuracy approvals OIML R85 OIML R85 OIML R85
34 Configuration IC-27542-000-E-002-1,2,3IC-27542-000-E-002-1,2,3IC-27542-000-E-002-1,2,3
35 Type Multi-functional Indicating Multi-functional Indicating Multi-functional Indicating
36 Display LCD type or eq. LCD type or eq. LCD type or eq.
SDAU 37 Cable Connection by Vendor by Vendor by Vendor
/Display 38 Wiring by Vendor by Vendor by Vendor
39 Sun-shade Yes Yes Yes
40 Enclosure Class IP 65 IP 65 IP 65
41 Type Qt'y (Point) 3 wire PT100 14 3 wire PT100 14 3 wire PT100 14
42 Over all length (mm) Note 2 Note 2 Note 2
43 Certification IEC IEC IEC
44 Connection Size & Rating Note 2 Note 2 Note 2
COMBINED 45 Electrical Connection M20 X 1.5 mm M20 X 1.5 mm M20 X 1.5 mm
TEMPERATURE 46 Measuring Range () Vendor STD Vendor STD Vendor STD
& OIL/WATER 47 Accuracy () 0.17 0.17 0.17
SENSOR 48 Bulb Material 316 SS 316 SS 316 SS
49 Bulb Diameter by Vendor by Vendor by Vendor
50 Mounting Note 2 Note 2 Note 2
51 Output Direct conn. to RADAR Direct conn. to RADAR Direct conn. to RADAR
52 Combined Oil/Water Level Sensor Yes Yes Yes
53 - Sensor Type Microwave Probe Microwave Probe Microwave Probe
54 - Measuring Range (mm) 0 - 500 from the BTM 0 - 500 from the BTM 0 - 500 from the BTM
55 Stilling Well None None None
OPTION 56 Pressure Sensor Input Yes Yes Yes

57 Manufacturer Saab Rosemount Saab Rosemount Saab Rosemount


58 Model Number REX RTG 3950 REX RTG 3950 REX RTG 3950
Notes :
1. Each Instrument shall have an SS Tag Plate containing Tag No., Model No., Size, Rating, etc., securely fastened to the instrument.
2. To be informed later.
3. Vendor shall provide the following items as per MR-27542-000-E-004 as a minimum;
FBM(Field Bus Modem), FCU (Field Communication Unit), Calibration Kits, Local Control Cabinets, Redundant Communication FO HART
modem for AMS, Interface module with DCS/Console, Interconnection Cables etc.
LEVEL INSTRUMENTS SHEET 16 OF 23
KUWAIT OIL (RADAR TYPE)
COMPANY NO. BY DATE REVISION DATA SHEET. NO. REV.
(K.S.C) A K.N.Kim 19 Feb. 2006 FOR APPROVAL IA-27542-000-E-019 0
B K.N.Kim 18 Apr. 2006 FOR APPROVAL CONTRACT ISSUE DATE
0 S.C.CHANG 24 Jul. 2006 FOR CONSTRUCTION G05021 24 Jul. 2006
REQ. P.O.

BY CHKD APPR.
S.C.C T.S.KIM K.T.KIM
1 Tag No. 279-LT-18 (Note 1) 279-LT-19 (Note 1) 279-LT-20 (Note 1)
2 Quantity 1 1 1
GENERAL 3 Service Crude Oil Tank Crude Oil Tank Crude Oil Tank
4 Tank Type Floating Roof Tank Floating Roof Tank Floating Roof Tank
5 Tank No. 279-TK-18 279-TK-19 279-TK-20
6 P&ID No. (BB-27542-) Note 2 Note 2 Note 2
7 Nace (MR0175) for all wetted part Yes Yes Yes
8 Area Classification Zone 1, Group IIA,IIB, T3 Zone 1, Group IIA,IIB, T3 Zone 1, Group IIA,IIB, T3
9 Pressure Max/nor. (bar g) ATM/ATM ATM/ATM ATM/ATM
PROCESS 10 Temperature Nor./Max/Design () 15.6/55/93 15.6/55/93 15.6/55/93
CONDITION 11 Viscosity (Cp) /base @ 18.8 / 60 deg F 18.8 / 60 deg F 18.8 / 60 deg F
12 Density (kg/m3) Note 2 Note 2 Note 2
13 Mounting type Inclined Inclined Inclined
14 Process Connection Note 2 Note 2 Note 2
15 Measuring Range (mm) Note 2 Note 2 Note 2
TANK 16 Antenna Type STILL PIPE ARRAY STILL PIPE ARRAY STILL PIPE ARRAY
CONNECTION 17 Propagation mode LOW LOSS MODE LOW LOSS MODE LOW LOSS MODE
18 Antenna Size by Vendor by Vendor by Vendor
19 Antenna surfaces by Vendor by Vendor by Vendor
20 Material by Vendor by Vendor by Vendor
21 Certification IEC 60529 IEC 60529 IEC 60529
22 Mounting ON TANK CONNECTION ON TANK CONNECTION ON TANK CONNECTION
23 Measuring Type RADAR RADAR RADAR
24 Measurement Principle by Vendor by Vendor by Vendor
25 Internal reference by Vendor by Vendor by Vendor
RADAR 26 Material Epoxy Painted Alum. Epoxy Painted Alum. Epoxy Painted Alum.
TRANSMITTER 27 Output Signal Multi-drop Field Bus Multi-drop Field Bus Multi-drop Field Bus
HEAD 28 Power Supply 110V AC, 50Hz 110V AC, 50Hz 110V AC, 50Hz
29 Electrical Connection M20 X 1.5 mm M20 X 1.5 mm M20 X 1.5 mm
30 Lightning protection Yes Yes Yes
31 Enclosure Class IP 65 IP 65 IP 65
32 Instrument accuracy 0.5 mm 0.5 mm 0.5 mm
33 Accuracy approvals OIML R85 OIML R85 OIML R85
34 Configuration IC-27542-000-E-002-1,2,3IC-27542-000-E-002-1,2,3IC-27542-000-E-002-1,2,3
35 Type Multi-functional Indicating Multi-functional Indicating Multi-functional Indicating
36 Display LCD type or eq. LCD type or eq. LCD type or eq.
SDAU 37 Cable Connection by Vendor by Vendor by Vendor
/Display 38 Wiring by Vendor by Vendor by Vendor
39 Sun-shade Yes Yes Yes
40 Enclosure Class IP 65 IP 65 IP 65
41 Type Qt'y (Point) 3 wire PT100 14 3 wire PT100 14 3 wire PT100 14
42 Over all length (mm) Note 2 Note 2 Note 2
43 Certification IEC IEC IEC
44 Connection Size & Rating Note 2 Note 2 Note 2
COMBINED 45 Electrical Connection M20 X 1.5 mm M20 X 1.5 mm M20 X 1.5 mm
TEMPERATURE 46 Measuring Range () Vendor STD Vendor STD Vendor STD
& OIL/WATER 47 Accuracy () 0.17 0.17 0.17
SENSOR 48 Bulb Material 316 SS 316 SS 316 SS
49 Bulb Diameter by Vendor by Vendor by Vendor
50 Mounting Note 2 Note 2 Note 2
51 Output Direct conn. to RADAR Direct conn. to RADAR Direct conn. to RADAR
52 Combined Oil/Water Level Sensor Yes Yes Yes
53 - Sensor Type Microwave Probe Microwave Probe Microwave Probe
54 - Measuring Range (mm) 0 - 500 from the BTM 0 - 500 from the BTM 0 - 500 from the BTM
55 Stilling Well None None None
OPTION 56 Pressure Sensor Input Yes Yes Yes

57 Manufacturer Saab Rosemount Saab Rosemount Saab Rosemount


58 Model Number REX RTG 3950 REX RTG 3950 REX RTG 3950
Notes :
1. Each Instrument shall have an SS Tag Plate containing Tag No., Model No., Size, Rating, etc., securely fastened to the instrument.
2. To be informed later.
3. Vendor shall provide the following items as per MR-27542-000-E-004 as a minimum;
FBM(Field Bus Modem), FCU (Field Communication Unit), Calibration Kits, Local Control Cabinets, Redundant Communication FO HART
modem for AMS, Interface module with DCS/Console, Interconnection Cables etc.
LEVEL INSTRUMENTS SHEET 17 OF 23
KUWAIT OIL (RADAR TYPE)
COMPANY NO. BY DATE REVISION DATA SHEET. NO. REV.
(K.S.C) A K.N.Kim 19 Feb. 2006 FOR APPROVAL IA-27542-000-E-019 0
B K.N.Kim 18 Apr. 2006 FOR APPROVAL CONTRACT ISSUE DATE
0 S.C.CHANG 24 Jul. 2006 FOR CONSTRUCTION G05021 24 Jul. 2006
REQ. P.O.

BY CHKD APPR.
S.C.C T.S.KIM K.T.KIM
1 Tag No. 279-LT-21 (Note 1) 279-LT-22 (Note 1) 279-LT-23 (Note 1)
2 Quantity 1 1 1
GENERAL 3 Service Crude Oil Tank Crude Oil Tank Crude Oil Tank
4 Tank Type Floating Roof Tank Floating Roof Tank Floating Roof Tank
5 Tank No. 279-TK-21 279-TK-22 279-TK-23
6 P&ID No. (BB-27542-) Note 2 Note 2 Note 2
7 Nace (MR0175) for all wetted part Yes Yes Yes
8 Area Classification Zone 1, Group IIA,IIB, T3 Zone 1, Group IIA,IIB, T3 Zone 1, Group IIA,IIB, T3
9 Pressure Max/nor. (bar g) ATM/ATM ATM/ATM ATM/ATM
PROCESS 10 Temperature Nor./Max/Design () 15.6/55/93 15.6/55/93 15.6/55/93
CONDITION 11 Viscosity (Cp) /base @ 18.8 / 60 deg F 18.8 / 60 deg F 18.8 / 60 deg F
12 Density (kg/m3) Note 2 Note 2 Note 2
13 Mounting type Inclined Inclined Inclined
14 Process Connection Note 2 Note 2 Note 2
15 Measuring Range (mm) Note 2 Note 2 Note 2
TANK 16 Antenna Type STILL PIPE ARRAY STILL PIPE ARRAY STILL PIPE ARRAY
CONNECTION 17 Propagation mode LOW LOSS MODE LOW LOSS MODE LOW LOSS MODE
18 Antenna Size by Vendor by Vendor by Vendor
19 Antenna surfaces by Vendor by Vendor by Vendor
20 Material by Vendor by Vendor by Vendor
21 Certification IEC 60529 IEC 60529 IEC 60529
22 Mounting ON TANK CONNECTION ON TANK CONNECTION ON TANK CONNECTION
23 Measuring Type RADAR RADAR RADAR
24 Measurement Principle by Vendor by Vendor by Vendor
25 Internal reference by Vendor by Vendor by Vendor
RADAR 26 Material Epoxy Painted Alum. Epoxy Painted Alum. Epoxy Painted Alum.
TRANSMITTER 27 Output Signal Multi-drop Field Bus Multi-drop Field Bus Multi-drop Field Bus
HEAD 28 Power Supply 110V AC, 50Hz 110V AC, 50Hz 110V AC, 50Hz
29 Electrical Connection M20 X 1.5 mm M20 X 1.5 mm M20 X 1.5 mm
30 Lightning protection Yes Yes Yes
31 Enclosure Class IP 65 IP 65 IP 65
32 Instrument accuracy 0.5 mm 0.5 mm 0.5 mm
33 Accuracy approvals OIML R85 OIML R85 OIML R85
34 Configuration IC-27542-000-E-002-1,2,3IC-27542-000-E-002-1,2,3IC-27542-000-E-002-1,2,3
35 Type Multi-functional Indicating Multi-functional Indicating Multi-functional Indicating
36 Display LCD type or eq. LCD type or eq. LCD type or eq.
SDAU 37 Cable Connection by Vendor by Vendor by Vendor
/Display 38 Wiring by Vendor by Vendor by Vendor
39 Sun-shade Yes Yes Yes
40 Enclosure Class IP 65 IP 65 IP 65
41 Type Qt'y (Point) 3 wire PT100 14 3 wire PT100 14 3 wire PT100 14
42 Over all length (mm) Note 2 Note 2 Note 2
43 Certification IEC IEC IEC
44 Connection Size & Rating Note 2 Note 2 Note 2
COMBINED 45 Electrical Connection M20 X 1.5 mm M20 X 1.5 mm M20 X 1.5 mm
TEMPERATURE 46 Measuring Range () Vendor STD Vendor STD Vendor STD
& OIL/WATER 47 Accuracy () 0.17 0.17 0.17
SENSOR 48 Bulb Material 316 SS 316 SS 316 SS
49 Bulb Diameter by Vendor by Vendor by Vendor
50 Mounting Note 2 Note 2 Note 2
51 Output Direct conn. to RADAR Direct conn. to RADAR Direct conn. to RADAR
52 Combined Oil/Water Level Sensor Yes Yes Yes
53 - Sensor Type Microwave Probe Microwave Probe Microwave Probe
54 - Measuring Range (mm) 0 - 500 from the BTM 0 - 500 from the BTM 0 - 500 from the BTM
55 Stilling Well None None None
OPTION 56 Pressure Sensor Input Yes Yes Yes

57 Manufacturer Saab Rosemount Saab Rosemount Saab Rosemount


58 Model Number REX RTG 3950 REX RTG 3950 REX RTG 3950
Notes :
1. Each Instrument shall have an SS Tag Plate containing Tag No., Model No., Size, Rating, etc., securely fastened to the instrument.
2. To be informed later.
3. Vendor shall provide the following items as per MR-27542-000-E-004 as a minimum;
FBM(Field Bus Modem), FCU (Field Communication Unit), Calibration Kits, Local Control Cabinets, Redundant Communication FO HART
modem for AMS, Interface module with DCS/Console, Interconnection Cables etc.
LEVEL INSTRUMENTS SHEET 18 OF 23
KUWAIT OIL (RADAR TYPE)
COMPANY NO. BY DATE REVISION DATA SHEET. NO. REV.
(K.S.C) A K.N.Kim 19 Feb. 2006 FOR APPROVAL IA-27542-000-E-019 0
B K.N.Kim 18 Apr. 2006 FOR APPROVAL CONTRACT ISSUE DATE
0 S.C.CHANG 24 Jul. 2006 FOR CONSTRUCTION G05021 24 Jul. 2006
REQ. P.O.

BY CHKD APPR.
S.C.C T.S.KIM K.T.KIM
1 Tag No. 279-LT-24 (Note 1) 279-LT-25 (Note 1) 279-LT-26 (Note 1)
2 Quantity 1 1 1
GENERAL 3 Service Crude Oil Tank Crude Oil Tank Crude Oil Tank
4 Tank Type Floating Roof Tank Floating Roof Tank Floating Roof Tank
5 Tank No. 279-TK-24 279-TK-25 279-TK-26
6 P&ID No. (BB-27542-) Note 2 Note 2 Note 2
7 Nace (MR0175) for all wetted part Yes Yes Yes
8 Area Classification Zone 1, Group IIA,IIB, T3 Zone 1, Group IIA,IIB, T3 Zone 1, Group IIA,IIB, T3
9 Pressure Max/nor. (bar g) ATM/ATM ATM/ATM ATM/ATM
PROCESS 10 Temperature Nor./Max/Design () 15.6/55/93 15.6/55/93 15.6/55/93
CONDITION 11 Viscosity (Cp) /base @ 18.8 / 60 deg F 18.8 / 60 deg F 18.8 / 60 deg F
12 Density (kg/m3) Note 2 Note 2 Note 2
13 Mounting type Inclined Inclined Inclined
14 Process Connection Note 2 Note 2 Note 2
15 Measuring Range (mm) Note 2 Note 2 Note 2
TANK 16 Antenna Type STILL PIPE ARRAY STILL PIPE ARRAY STILL PIPE ARRAY
CONNECTION 17 Propagation mode LOW LOSS MODE LOW LOSS MODE LOW LOSS MODE
18 Antenna Size by Vendor by Vendor by Vendor
19 Antenna surfaces by Vendor by Vendor by Vendor
20 Material by Vendor by Vendor by Vendor
21 Certification IEC 60529 IEC 60529 IEC 60529
22 Mounting ON TANK CONNECTION ON TANK CONNECTION ON TANK CONNECTION
23 Measuring Type RADAR RADAR RADAR
24 Measurement Principle by Vendor by Vendor by Vendor
25 Internal reference by Vendor by Vendor by Vendor
RADAR 26 Material Epoxy Painted Alum. Epoxy Painted Alum. Epoxy Painted Alum.
TRANSMITTER 27 Output Signal Multi-drop Field Bus Multi-drop Field Bus Multi-drop Field Bus
HEAD 28 Power Supply 110V AC, 50Hz 110V AC, 50Hz 110V AC, 50Hz
29 Electrical Connection M20 X 1.5 mm M20 X 1.5 mm M20 X 1.5 mm
30 Lightning protection Yes Yes Yes
31 Enclosure Class IP 65 IP 65 IP 65
32 Instrument accuracy 0.5 mm 0.5 mm 0.5 mm
33 Accuracy approvals OIML R85 OIML R85 OIML R85
34 Configuration IC-27542-000-E-002-1,2,3IC-27542-000-E-002-1,2,3IC-27542-000-E-002-1,2,3
35 Type Multi-functional Indicating Multi-functional Indicating Multi-functional Indicating
36 Display LCD type or eq. LCD type or eq. LCD type or eq.
SDAU 37 Cable Connection by Vendor by Vendor by Vendor
/Display 38 Wiring by Vendor by Vendor by Vendor
39 Sun-shade Yes Yes Yes
40 Enclosure Class IP 65 IP 65 IP 65
41 Type Qt'y (Point) 3 wire PT100 14 3 wire PT100 14 3 wire PT100 14
42 Over all length (mm) Note 2 Note 2 Note 2
43 Certification IEC IEC IEC
44 Connection Size & Rating Note 2 Note 2 Note 2
COMBINED 45 Electrical Connection M20 X 1.5 mm M20 X 1.5 mm M20 X 1.5 mm
TEMPERATURE 46 Measuring Range () Vendor STD Vendor STD Vendor STD
& OIL/WATER 47 Accuracy () 0.17 0.17 0.17
SENSOR 48 Bulb Material 316 SS 316 SS 316 SS
49 Bulb Diameter by Vendor by Vendor by Vendor
50 Mounting Note 2 Note 2 Note 2
51 Output Direct conn. to RADAR Direct conn. to RADAR Direct conn. to RADAR
52 Combined Oil/Water Level Sensor Yes Yes Yes
53 - Sensor Type Microwave Probe Microwave Probe Microwave Probe
54 - Measuring Range (mm) 0 - 500 from the BTM 0 - 500 from the BTM 0 - 500 from the BTM
55 Stilling Well None None None
OPTION 56 Pressure Sensor Input Yes Yes Yes

57 Manufacturer Saab Rosemount Saab Rosemount Saab Rosemount


58 Model Number REX RTG 3950 REX RTG 3950 REX RTG 3950
Notes :
1. Each Instrument shall have an SS Tag Plate containing Tag No., Model No., Size, Rating, etc., securely fastened to the instrument.
2. To be informed later.
3. Vendor shall provide the following items as per MR-27542-000-E-004 as a minimum;
FBM(Field Bus Modem), FCU (Field Communication Unit), Calibration Kits, Local Control Cabinets, Redundant Communication FO HART
modem for AMS, Interface module with DCS/Console, Interconnection Cables etc.
LEVEL INSTRUMENTS SHEET 19 OF 23
KUWAIT OIL (RADAR TYPE)
COMPANY NO. BY DATE REVISION DATA SHEET. NO. REV.
(K.S.C) A K.N.Kim 19 Feb. 2006 FOR APPROVAL IA-27542-000-E-019 0
B K.N.Kim 18 Apr. 2006 FOR APPROVAL CONTRACT ISSUE DATE
0 S.C.CHANG 24 Jul. 2006 FOR CONSTRUCTION G05021 24 Jul. 2006
REQ. P.O.

BY CHKD APPR.
S.C.C T.S.KIM K.T.KIM
1 Tag No. 279-LT-27 (Note 1) 279-LT-28 (Note 1) 279-LT-29 (Note 1)
2 Quantity 1 1 1
GENERAL 3 Service Crude Oil Tank Crude Oil Tank Crude Oil Tank
4 Tank Type Floating Roof Tank Floating Roof Tank Floating Roof Tank
5 Tank No. 279-TK-27 279-TK-28 279-TK-29
6 P&ID No. (BB-27542-) Note 2 Note 2 Note 2
7 Nace (MR0175) for all wetted part Yes Yes Yes
8 Area Classification Zone 1, Group IIA,IIB, T3 Zone 1, Group IIA,IIB, T3 Zone 1, Group IIA,IIB, T3
9 Pressure Max/nor. (bar g) ATM/ATM ATM/ATM ATM/ATM
PROCESS 10 Temperature Nor./Max/Design () 15.6/55/93 15.6/55/93 15.6/55/93
CONDITION 11 Viscosity (Cp) /base @ 18.8 / 60 deg F 18.8 / 60 deg F 18.8 / 60 deg F
12 Density (kg/m3) Note 2 Note 2 Note 2
13 Mounting type Inclined Inclined Inclined
14 Process Connection Note 2 Note 2 Note 2
15 Measuring Range (mm) Note 2 Note 2 Note 2
TANK 16 Antenna Type STILL PIPE ARRAY STILL PIPE ARRAY STILL PIPE ARRAY
CONNECTION 17 Propagation mode LOW LOSS MODE LOW LOSS MODE LOW LOSS MODE
18 Antenna Size by Vendor by Vendor by Vendor
19 Antenna surfaces by Vendor by Vendor by Vendor
20 Material by Vendor by Vendor by Vendor
21 Certification IEC 60529 IEC 60529 IEC 60529
22 Mounting ON TANK CONNECTION ON TANK CONNECTION ON TANK CONNECTION
23 Measuring Type RADAR RADAR RADAR
24 Measurement Principle by Vendor by Vendor by Vendor
25 Internal reference by Vendor by Vendor by Vendor
RADAR 26 Material Epoxy Painted Alum. Epoxy Painted Alum. Epoxy Painted Alum.
TRANSMITTER 27 Output Signal Multi-drop Field Bus Multi-drop Field Bus Multi-drop Field Bus
HEAD 28 Power Supply 110V AC, 50Hz 110V AC, 50Hz 110V AC, 50Hz
29 Electrical Connection M20 X 1.5 mm M20 X 1.5 mm M20 X 1.5 mm
30 Lightning protection Yes Yes Yes
31 Enclosure Class IP 65 IP 65 IP 65
32 Instrument accuracy 0.5 mm 0.5 mm 0.5 mm
33 Accuracy approvals OIML R85 OIML R85 OIML R85
34 Configuration IC-27542-000-E-002-1,2,3IC-27542-000-E-002-1,2,3IC-27542-000-E-002-1,2,3
35 Type Multi-functional Indicating Multi-functional Indicating Multi-functional Indicating
36 Display LCD type or eq. LCD type or eq. LCD type or eq.
SDAU 37 Cable Connection by Vendor by Vendor by Vendor
/Display 38 Wiring by Vendor by Vendor by Vendor
39 Sun-shade Yes Yes Yes
40 Enclosure Class IP 65 IP 65 IP 65
41 Type Qt'y (Point) 3 wire PT100 14 3 wire PT100 14 3 wire PT100 14
42 Over all length (mm) Note 2 Note 2 Note 2
43 Certification IEC IEC IEC
44 Connection Size & Rating Note 2 Note 2 Note 2
COMBINED 45 Electrical Connection M20 X 1.5 mm M20 X 1.5 mm M20 X 1.5 mm
TEMPERATURE 46 Measuring Range () Vendor STD Vendor STD Vendor STD
& OIL/WATER 47 Accuracy () 0.17 0.17 0.17
SENSOR 48 Bulb Material 316 SS 316 SS 316 SS
49 Bulb Diameter by Vendor by Vendor by Vendor
50 Mounting Note 2 Note 2 Note 2
51 Output Direct conn. to RADAR Direct conn. to RADAR Direct conn. to RADAR
52 Combined Oil/Water Level Sensor Yes Yes Yes
53 - Sensor Type Microwave Probe Microwave Probe Microwave Probe
54 - Measuring Range (mm) 0 - 500 from the BTM 0 - 500 from the BTM 0 - 500 from the BTM
55 Stilling Well None None None
OPTION 56 Pressure Sensor Input Yes Yes Yes

57 Manufacturer Saab Rosemount Saab Rosemount Saab Rosemount


58 Model Number REX RTG 3950 REX RTG 3950 REX RTG 3950
Notes :
1. Each Instrument shall have an SS Tag Plate containing Tag No., Model No., Size, Rating, etc., securely fastened to the instrument.
2. To be informed later.
3. Vendor shall provide the following items as per MR-27542-000-E-004 as a minimum;
FBM(Field Bus Modem), FCU (Field Communication Unit), Calibration Kits, Local Control Cabinets, Redundant Communication FO HART
modem for AMS, Interface module with DCS/Console, Interconnection Cables etc.
LEVEL INSTRUMENTS SHEET 20 OF 23
KUWAIT OIL (RADAR TYPE)
COMPANY NO. BY DATE REVISION DATA SHEET. NO. REV.
(K.S.C) A K.N.Kim 19 Feb. 2006 FOR APPROVAL IA-27542-000-E-019 0
B K.N.Kim 18 Apr. 2006 FOR APPROVAL CONTRACT ISSUE DATE
0 S.C.CHANG 24 Jul. 2006 FOR CONSTRUCTION G05021 24 Jul. 2006
REQ. P.O.

BY CHKD APPR.
S.C.C T.S.KIM K.T.KIM
1 Tag No. 279-LT-30 (Note 1) 279-LT-31 (Note 1) 279-LT-32 (Note 1)
2 Quantity 1 1 1
GENERAL 3 Service Crude Oil Tank Crude Oil Tank Crude Oil Tank
4 Tank Type Floating Roof Tank Floating Roof Tank Floating Roof Tank
5 Tank No. 279-TK-30 279-TK-31 279-TK-32
6 P&ID No. (BB-27542-) Note 2 Note 2 Note 2
7 Nace (MR0175) for all wetted part Yes Yes Yes
8 Area Classification Zone 1, Group IIA,IIB, T3 Zone 1, Group IIA,IIB, T3 Zone 1, Group IIA,IIB, T3
9 Pressure Max/nor. (bar g) ATM/ATM ATM/ATM ATM/ATM
PROCESS 10 Temperature Nor./Max/Design () 15.6/55/93 15.6/55/93 15.6/55/93
CONDITION 11 Viscosity (Cp) /base @ 18.8 / 60 deg F 18.8 / 60 deg F 18.8 / 60 deg F
12 Density (kg/m3) Note 2 Note 2 Note 2
13 Mounting type Inclined Inclined Inclined
14 Process Connection Note 2 Note 2 Note 2
15 Measuring Range (mm) Note 2 Note 2 Note 2
TANK 16 Antenna Type STILL PIPE ARRAY STILL PIPE ARRAY STILL PIPE ARRAY
CONNECTION 17 Propagation mode LOW LOSS MODE LOW LOSS MODE LOW LOSS MODE
18 Antenna Size by Vendor by Vendor by Vendor
19 Antenna surfaces by Vendor by Vendor by Vendor
20 Material by Vendor by Vendor by Vendor
21 Certification IEC 60529 IEC 60529 IEC 60529
22 Mounting ON TANK CONNECTION ON TANK CONNECTION ON TANK CONNECTION
23 Measuring Type RADAR RADAR RADAR
24 Measurement Principle by Vendor by Vendor by Vendor
25 Internal reference by Vendor by Vendor by Vendor
RADAR 26 Material Epoxy Painted Alum. Epoxy Painted Alum. Epoxy Painted Alum.
TRANSMITTER 27 Output Signal Multi-drop Field Bus Multi-drop Field Bus Multi-drop Field Bus
HEAD 28 Power Supply 110V AC, 50Hz 110V AC, 50Hz 110V AC, 50Hz
29 Electrical Connection M20 X 1.5 mm M20 X 1.5 mm M20 X 1.5 mm
30 Lightning protection Yes Yes Yes
31 Enclosure Class IP 65 IP 65 IP 65
32 Instrument accuracy 0.5 mm 0.5 mm 0.5 mm
33 Accuracy approvals OIML R85 OIML R85 OIML R85
34 Configuration IC-27542-000-E-002-1,2,3IC-27542-000-E-002-1,2,3IC-27542-000-E-002-1,2,3
35 Type Multi-functional Indicating Multi-functional Indicating Multi-functional Indicating
36 Display LCD type or eq. LCD type or eq. LCD type or eq.
SDAU 37 Cable Connection by Vendor by Vendor by Vendor
/Display 38 Wiring by Vendor by Vendor by Vendor
39 Sun-shade Yes Yes Yes
40 Enclosure Class IP 65 IP 65 IP 65
41 Type Qt'y (Point) 3 wire PT100 14 3 wire PT100 14 3 wire PT100 14
42 Over all length (mm) Note 2 Note 2 Note 2
43 Certification IEC IEC IEC
44 Connection Size & Rating Note 2 Note 2 Note 2
COMBINED 45 Electrical Connection M20 X 1.5 mm M20 X 1.5 mm M20 X 1.5 mm
TEMPERATURE 46 Measuring Range () Vendor STD Vendor STD Vendor STD
& OIL/WATER 47 Accuracy () 0.17 0.17 0.17
SENSOR 48 Bulb Material 316 SS 316 SS 316 SS
49 Bulb Diameter by Vendor by Vendor by Vendor
50 Mounting Note 2 Note 2 Note 2
51 Output Direct conn. to RADAR Direct conn. to RADAR Direct conn. to RADAR
52 Combined Oil/Water Level Sensor Yes Yes Yes
53 - Sensor Type Microwave Probe Microwave Probe Microwave Probe
54 - Measuring Range (mm) 0 - 500 from the BTM 0 - 500 from the BTM 0 - 500 from the BTM
55 Stilling Well None None None
OPTION 56 Pressure Sensor Input Yes Yes Yes

57 Manufacturer Saab Rosemount Saab Rosemount Saab Rosemount


58 Model Number REX RTG 3950 REX RTG 3950 REX RTG 3950
Notes :
1. Each Instrument shall have an SS Tag Plate containing Tag No., Model No., Size, Rating, etc., securely fastened to the instrument.
2. To be informed later.
3. Vendor shall provide the following items as per MR-27542-000-E-004 as a minimum;
FBM(Field Bus Modem), FCU (Field Communication Unit), Calibration Kits, Local Control Cabinets, Redundant Communication FO HART
modem for AMS, Interface module with DCS/Console, Interconnection Cables etc.
LEVEL INSTRUMENTS SHEET 21 OF 23
KUWAIT OIL (RADAR TYPE)
COMPANY NO. BY DATE REVISION DATA SHEET. NO. REV.
(K.S.C) A K.N.Kim 19 Feb. 2006 FOR APPROVAL IA-27542-000-E-019 0
B K.N.Kim 18 Apr. 2006 FOR APPROVAL CONTRACT ISSUE DATE
0 S.C.CHANG 24 Jul. 2006 FOR CONSTRUCTION G05021 24 Jul. 2006
REQ. P.O.

BY CHKD APPR.
S.C.C T.S.KIM K.T.KIM
1 Tag No. 279-LT-33 (Note 1) 279-LT-34 (Note 1) 279-LT-35 (Note 1)
2 Quantity 1 1 1
GENERAL 3 Service Crude Oil Tank Crude Oil Tank Crude Oil Tank
4 Tank Type Floating Roof Tank Floating Roof Tank Floating Roof Tank
5 Tank No. 279-TK-33 279-TK-34 279-TK-35
6 P&ID No. (BB-27542-) Note 2 Note 2 Note 2
7 Nace (MR0175) for all wetted part Yes Yes Yes
8 Area Classification Zone 1, Group IIA,IIB, T3 Zone 1, Group IIA,IIB, T3 Zone 1, Group IIA,IIB, T3
9 Pressure Max/nor. (bar g) ATM/ATM ATM/ATM ATM/ATM
PROCESS 10 Temperature Nor./Max/Design () 15.6/55/93 15.6/55/93 15.6/55/93
CONDITION 11 Viscosity (Cp) /base @ 18.8 / 60 deg F 18.8 / 60 deg F 18.8 / 60 deg F
12 Density (kg/m3) Note 2 Note 2 Note 2
13 Mounting type Inclined Inclined Inclined
14 Process Connection Note 2 Note 2 Note 2
15 Measuring Range (mm) Note 2 Note 2 Note 2
TANK 16 Antenna Type STILL PIPE ARRAY STILL PIPE ARRAY STILL PIPE ARRAY
CONNECTION 17 Propagation mode LOW LOSS MODE LOW LOSS MODE LOW LOSS MODE
18 Antenna Size by Vendor by Vendor by Vendor
19 Antenna surfaces by Vendor by Vendor by Vendor
20 Material by Vendor by Vendor by Vendor
21 Certification IEC 60529 IEC 60529 IEC 60529
22 Mounting ON TANK CONNECTION ON TANK CONNECTION ON TANK CONNECTION
23 Measuring Type RADAR RADAR RADAR
24 Measurement Principle by Vendor by Vendor by Vendor
25 Internal reference by Vendor by Vendor by Vendor
RADAR 26 Material Epoxy Painted Alum. Epoxy Painted Alum. Epoxy Painted Alum.
TRANSMITTER 27 Output Signal Multi-drop Field Bus Multi-drop Field Bus Multi-drop Field Bus
HEAD 28 Power Supply 110V AC, 50Hz 110V AC, 50Hz 110V AC, 50Hz
29 Electrical Connection M20 X 1.5 mm M20 X 1.5 mm M20 X 1.5 mm
30 Lightning protection Yes Yes Yes
31 Enclosure Class IP 65 IP 65 IP 65
32 Instrument accuracy 0.5 mm 0.5 mm 0.5 mm
33 Accuracy approvals OIML R85 OIML R85 OIML R85
34 Configuration IC-27542-000-E-002-1,2,3IC-27542-000-E-002-1,2,3IC-27542-000-E-002-1,2,3
35 Type Multi-functional Indicating Multi-functional Indicating Multi-functional Indicating
36 Display LCD type or eq. LCD type or eq. LCD type or eq.
SDAU 37 Cable Connection by Vendor by Vendor by Vendor
/Display 38 Wiring by Vendor by Vendor by Vendor
39 Sun-shade Yes Yes Yes
40 Enclosure Class IP 65 IP 65 IP 65
41 Type Qt'y (Point) 3 wire PT100 14 3 wire PT100 14 3 wire PT100 14
42 Over all length (mm) Note 2 Note 2 Note 2
43 Certification IEC IEC IEC
44 Connection Size & Rating Note 2 Note 2 Note 2
COMBINED 45 Electrical Connection M20 X 1.5 mm M20 X 1.5 mm M20 X 1.5 mm
TEMPERATURE 46 Measuring Range () Vendor STD Vendor STD Vendor STD
& OIL/WATER 47 Accuracy () 0.17 0.17 0.17
SENSOR 48 Bulb Material 316 SS 316 SS 316 SS
49 Bulb Diameter by Vendor by Vendor by Vendor
50 Mounting Note 2 Note 2 Note 2
51 Output Direct conn. to RADAR Direct conn. to RADAR Direct conn. to RADAR
52 Combined Oil/Water Level Sensor Yes Yes Yes
53 - Sensor Type Microwave Probe Microwave Probe Microwave Probe
54 - Measuring Range (mm) 0 - 500 from the BTM 0 - 500 from the BTM 0 - 500 from the BTM
55 Stilling Well None None None
OPTION 56 Pressure Sensor Input Yes Yes Yes

57 Manufacturer Saab Rosemount Saab Rosemount Saab Rosemount


58 Model Number REX RTG 3950 REX RTG 3950 REX RTG 3950
Notes :
1. Each Instrument shall have an SS Tag Plate containing Tag No., Model No., Size, Rating, etc., securely fastened to the instrument.
2. To be informed later.
3. Vendor shall provide the following items as per MR-27542-000-E-004 as a minimum;
FBM(Field Bus Modem), FCU (Field Communication Unit), Calibration Kits, Local Control Cabinets, Redundant Communication FO HART
modem for AMS, Interface module with DCS/Console, Interconnection Cables etc.
LEVEL INSTRUMENTS SHEET 22 OF 23
KUWAIT OIL (RADAR TYPE)
COMPANY NO. BY DATE REVISION DATA SHEET. NO. REV.
(K.S.C) A K.N.Kim 19 Feb. 2006 FOR APPROVAL IA-27542-000-E-019 0
B K.N.Kim 18 Apr. 2006 FOR APPROVAL CONTRACT ISSUE DATE
0 S.C.CHANG 24 Jul. 2006 FOR CONSTRUCTION G05021 24 Jul. 2006
REQ. P.O.

BY CHKD APPR.
S.C.C T.S.KIM K.T.KIM
1 Tag No. 279-LT-60 (Note 1) 279-LT-61 (Note 1) 279-LT-62 (Note 1)
2 Quantity 1 1 1
GENERAL 3 Service Crude Oil Tank Crude Oil Tank Crude Oil Tank
4 Tank Type Floating Roof Tank Floating Roof Tank Floating Roof Tank
5 Tank No. 279-TK-60 279-TK-61 279-TK-62
6 P&ID No. (BB-27542-) Note 2 Note 2 Note 2
7 Nace (MR0175) for all wetted part Yes Yes Yes
8 Area Classification Zone 1, Group IIA,IIB, T3 Zone 1, Group IIA,IIB, T3 Zone 1, Group IIA,IIB, T3
9 Pressure Max/nor. (bar g) ATM/ATM ATM/ATM ATM/ATM
PROCESS 10 Temperature Nor./Max/Design () 15.6/55/93 15.6/55/93 15.6/55/93
CONDITION 11 Viscosity (Cp) /base @ 18.8 / 60 deg F 18.8 / 60 deg F 18.8 / 60 deg F
12 Density (kg/m3) Note 2 Note 2 Note 2
13 Mounting type Inclined Inclined Inclined
14 Process Connection Note 2 Note 2 Note 2
15 Measuring Range (mm) Note 2 Note 2 Note 2
TANK 16 Antenna Type STILL PIPE ARRAY STILL PIPE ARRAY STILL PIPE ARRAY
CONNECTION 17 Propagation mode LOW LOSS MODE LOW LOSS MODE LOW LOSS MODE
18 Antenna Size by Vendor by Vendor by Vendor
19 Antenna surfaces by Vendor by Vendor by Vendor
20 Material by Vendor by Vendor by Vendor
21 Certification IEC 60529 IEC 60529 IEC 60529
22 Mounting ON TANK CONNECTION ON TANK CONNECTION ON TANK CONNECTION
23 Measuring Type RADAR RADAR RADAR
24 Measurement Principle by Vendor by Vendor by Vendor
25 Internal reference by Vendor by Vendor by Vendor
RADAR 26 Material Epoxy Painted Alum. Epoxy Painted Alum. Epoxy Painted Alum.
TRANSMITTER 27 Output Signal Multi-drop Field Bus Multi-drop Field Bus Multi-drop Field Bus
HEAD 28 Power Supply 110V AC, 50Hz 110V AC, 50Hz 110V AC, 50Hz
29 Electrical Connection M20 X 1.5 mm M20 X 1.5 mm M20 X 1.5 mm
30 Lightning protection Yes Yes Yes
31 Enclosure Class IP 65 IP 65 IP 65
32 Instrument accuracy 0.5 mm 0.5 mm 0.5 mm
33 Accuracy approvals OIML R85 OIML R85 OIML R85
34 Configuration IC-27542-000-E-002-1,2,3IC-27542-000-E-002-1,2,3IC-27542-000-E-002-1,2,3
35 Type Multi-functional Indicating Multi-functional Indicating Multi-functional Indicating
36 Display LCD type or eq. LCD type or eq. LCD type or eq.
SDAU 37 Cable Connection by Vendor by Vendor by Vendor
/Display 38 Wiring by Vendor by Vendor by Vendor
39 Sun-shade Yes Yes Yes
40 Enclosure Class IP 65 IP 65 IP 65
41 Type Qt'y (Point) 3 wire PT100 14 3 wire PT100 14 3 wire PT100 14
42 Over all length (mm) Note 2 Note 2 Note 2
43 Certification IEC IEC IEC
44 Connection Size & Rating Note 2 Note 2 Note 2
COMBINED 45 Electrical Connection M20 X 1.5 mm M20 X 1.5 mm M20 X 1.5 mm
TEMPERATURE 46 Measuring Range () Vendor STD Vendor STD Vendor STD
& OIL/WATER 47 Accuracy () 0.17 0.17 0.17
SENSOR 48 Bulb Material 316 SS 316 SS 316 SS
49 Bulb Diameter by Vendor by Vendor by Vendor
50 Mounting Note 2 Note 2 Note 2
51 Output Direct conn. to RADAR Direct conn. to RADAR Direct conn. to RADAR
52 Combined Oil/Water Level Sensor Yes Yes Yes
53 - Sensor Type Microwave Probe Microwave Probe Microwave Probe
54 - Measuring Range (mm) 0 - 500 from the BTM 0 - 500 from the BTM 0 - 500 from the BTM
55 Stilling Well None None None
OPTION 56 Pressure Sensor Input Yes Yes Yes

57 Manufacturer Saab Rosemount Saab Rosemount Saab Rosemount


58 Model Number REX RTG 3950 REX RTG 3950 REX RTG 3950
Notes :
1. Each Instrument shall have an SS Tag Plate containing Tag No., Model No., Size, Rating, etc., securely fastened to the instrument.
2. To be informed later.
3. Vendor shall provide the following items as per MR-27542-000-E-004 as a minimum;
FBM(Field Bus Modem), FCU (Field Communication Unit), Calibration Kits, Local Control Cabinets, Redundant Communication FO HART
modem for AMS, Interface module with DCS/Console, Interconnection Cables etc.
LEVEL INSTRUMENTS SHEET 23 OF 23
KUWAIT OIL (RADAR TYPE)
COMPANY NO. BY DATE REVISION DATA SHEET. NO. REV.
(K.S.C) A K.N.Kim 19 Feb. 2006 FOR APPROVAL IA-27542-000-E-019 0
B K.N.Kim 18 Apr. 2006 FOR APPROVAL CONTRACT ISSUE DATE
0 S.C.CHANG 24 Jul. 2006 FOR CONSTRUCTION G05021 24 Jul. 2006
REQ. P.O.

BY CHKD APPR.
S.C.C T.S.KIM K.T.KIM
1 Tag No. 279-LT-63 (Note 1) 279-LT-64 (Note 1) 279-LT-65 (Note 1)
2 Quantity 1 1 1
GENERAL 3 Service Crude Oil Tank Crude Oil Tank Crude Oil Tank
4 Tank Type Floating Roof Tank Floating Roof Tank Floating Roof Tank
5 Tank No. 279-TK-63 279-TK-64 279-TK-65
6 P&ID No. (BB-27542-) Note 2 Note 2 Note 2
7 Nace (MR0175) for all wetted part Yes Yes Yes
8 Area Classification Zone 1, Group IIA,IIB, T3 Zone 1, Group IIA,IIB, T3 Zone 1, Group IIA,IIB, T3
9 Pressure Max/nor. (bar g) ATM/ATM ATM/ATM ATM/ATM
PROCESS 10 Temperature Nor./Max/Design () 15.6/55/93 15.6/55/93 15.6/55/93
CONDITION 11 Viscosity (Cp) /base @ 18.8 / 60 deg F 18.8 / 60 deg F 18.8 / 60 deg F
12 Density (kg/m3) Note 2 Note 2 Note 2
13 Mounting type Inclined Inclined Inclined
14 Process Connection Note 2 Note 2 Note 2
15 Measuring Range (mm) Note 2 Note 2 Note 2
TANK 16 Antenna Type STILL PIPE ARRAY STILL PIPE ARRAY STILL PIPE ARRAY
CONNECTION 17 Propagation mode LOW LOSS MODE LOW LOSS MODE LOW LOSS MODE
18 Antenna Size by Vendor by Vendor by Vendor
19 Antenna surfaces by Vendor by Vendor by Vendor
20 Material by Vendor by Vendor by Vendor
21 Certification IEC 60529 IEC 60529 IEC 60529
22 Mounting ON TANK CONNECTION ON TANK CONNECTION ON TANK CONNECTION
23 Measuring Type RADAR RADAR RADAR
24 Measurement Principle by Vendor by Vendor by Vendor
25 Internal reference by Vendor by Vendor by Vendor
RADAR 26 Material Epoxy Painted Alum. Epoxy Painted Alum. Epoxy Painted Alum.
TRANSMITTER 27 Output Signal Multi-drop Field Bus Multi-drop Field Bus Multi-drop Field Bus
HEAD 28 Power Supply 110V AC, 50Hz 110V AC, 50Hz 110V AC, 50Hz
29 Electrical Connection M20 X 1.5 mm M20 X 1.5 mm M20 X 1.5 mm
30 Lightning protection Yes Yes Yes
31 Enclosure Class IP 65 IP 65 IP 65
32 Instrument accuracy 0.5 mm 0.5 mm 0.5 mm
33 Accuracy approvals OIML R85 OIML R85 OIML R85
34 Configuration IC-27542-000-E-002-1,2,3IC-27542-000-E-002-1,2,3IC-27542-000-E-002-1,2,3
35 Type Multi-functional Indicating Multi-functional Indicating Multi-functional Indicating
36 Display LCD type or eq. LCD type or eq. LCD type or eq.
SDAU 37 Cable Connection by Vendor by Vendor by Vendor
/Display 38 Wiring by Vendor by Vendor by Vendor
39 Sun-shade Yes Yes Yes
40 Enclosure Class IP 65 IP 65 IP 65
41 Type Qt'y (Point) 3 wire PT100 14 3 wire PT100 14 3 wire PT100 14
42 Over all length (mm) Note 2 Note 2 Note 2
43 Certification IEC IEC IEC
44 Connection Size & Rating Note 2 Note 2 Note 2
COMBINED 45 Electrical Connection M20 X 1.5 mm M20 X 1.5 mm M20 X 1.5 mm
TEMPERATURE 46 Measuring Range () Vendor STD Vendor STD Vendor STD
& OIL/WATER 47 Accuracy () 0.17 0.17 0.17
SENSOR 48 Bulb Material 316 SS 316 SS 316 SS
49 Bulb Diameter by Vendor by Vendor by Vendor
50 Mounting Note 2 Note 2 Note 2
51 Output Direct conn. to RADAR Direct conn. to RADAR Direct conn. to RADAR
52 Combined Oil/Water Level Sensor Yes Yes Yes
53 - Sensor Type Microwave Probe Microwave Probe Microwave Probe
54 - Measuring Range (mm) 0 - 500 from the BTM 0 - 500 from the BTM 0 - 500 from the BTM
55 Stilling Well None None None
OPTION 56 Pressure Sensor Input Yes Yes Yes

57 Manufacturer Saab Rosemount Saab Rosemount Saab Rosemount


58 Model Number REX RTG 3950 REX RTG 3950 REX RTG 3950
Notes :
1. Each Instrument shall have an SS Tag Plate containing Tag No., Model No., Size, Rating, etc., securely fastened to the instrument.
2. To be informed later.
3. Vendor shall provide the following items as per MR-27542-000-E-004 as a minimum;
FBM(Field Bus Modem), FCU (Field Communication Unit), Calibration Kits, Local Control Cabinets, Redundant Communication FO HART
modem for AMS, Interface module with DCS/Console, Interconnection Cables etc.

Das könnte Ihnen auch gefallen