E - 2101159

FOR VIETNAM
Son La Substation

Instruction Manual
For 300 MVA
Power Transformer
CHANGZHOU TOSHIBA JOB. No. E053ABCE054ABC

Please read this manual before using the equipment.


Please keep the manual safe at your hand after reading.

Please read this manual before using the equipment


DEC2015

CHANGZHOU TOSHIBA TRANSFORMER CO.,LTD.

CHANGZHOU TOSHIBA TRANSFORMER CO.,LTD 2009


All Right Reserved
2 of 24
E -2101159


CHANGZHOU TOSHIBA TRANSFORMER CO.,LTD.
Add: 86Long Jiang Middle road, Changzhou, Jiangsu
Http://www.cz-toshiba.com
Tel: +86-519-83256056
Fax: +86-519-83256002
Postcode: 213012
3 of 24
E - 2101159

Table of Contents

1. Introduction 5
2. Precautions for Safety 5
3. Overview13
3.1 Construction and Name of Components 13
3.2 List of Accessories 13
3.3 Instructions and Drawings 15
3.3.1 Outline and Nameplate 15
3.3.2 Instructions 15
3.3.3 Drawings 16
3.3.4 Assembly Drawings 20
3.3.5 Special Tools 20
4. Action when Protection Circuit Operates 21
4.1 When Light Fault Protection Circuit operates 21
4.2 When Heavy Fault Protection Circuit operates 22
5. Technical Specification of Transformer 23
5.1 Quantity 23
5.2 Type 23
5.3 Rated Power for Each Winding 23
5.4 Rated Voltage for Each Winding 23
5.5 Frequency23
5.6 Connection 23
5.7 HV Winding Connections 24
5.8 Transformer Serial Number 24
5.9 Standard 24
4 of 24
E -2101159

This Page Intentionally Left Blank


5 of 24
E - 2101159

1. Introduction
This manual is written to ensure safe handling of the Power Transformer.
Before maintenance, be certain to read this manual for proper use of the equipment. This manual
should be kept near the equipment so it can be readily referenced.

2. Precautions for Safety


Signs and messages in this manual and on the equipment body are important for management,
operation, maintenance and inspection. They are given to avoid possible injuries and damages as
well as to ensure correct handling of the equipment. The following signs and short messages
should thoroughly be understood before reading this manual. It is advised that you also read the
instruction manuals of related equipment and components.

IMPORTANT MESSAGES
Read this manual and follow its instructions. Signal words such as DANGER, WARNING, two kinds of CAUTION,
and NOTE, will be followed by important safety information that must be carefully reviewed.
Indicates an imminently hazardous situation, which will result in death or serious injury if
! DANGER you do not follow instructions.

Indicates an imminently hazardous situation, which could result in death or serious injury
! WARNING if you do not follow instructions.

Indicates an imminently hazardous situation, which if not avoided, may result in minor
! CAUTION injury or moderate injury.

Indicates an imminently hazardous situation, which if not avoided, may result in property
CAUTION damage.

Give you helpful information.


NOTE
6 of 24
E -2101159

APPLICATION

This equipment is designed for power transformer. Never use this for other purposes.

WARRANTY AND LIMITATION OF LIABILITY

CHANGZHOU TOSHIBA has no obligation to compensate for any damages, including collateral damages,
caused by abnormal conditions or failures of this equipment and connected devices.

QUALIFIED OPERATORS ONLY

This instruction manual is written for chief electric engineers of your company and competent persons authorized
by the chief electric engineers ( * ) .
For operation, maintenance and inspection, this instruction manual and other manuals of the associated devices
and components shall be read and understood. Workers shall follow the directions of the chief electric
engineers.

* Authorized people mean electric engineers who have received education offered by ChangZhou Toshiba.

WARNING LABEL

(1) To ensure safety, all the warning labels shall be read and understood.
(2) Warning labels shall be kept in such a condition that they can be easily seen. They shall never be
contaminated, removed or blocked from view by cover.
7 of 24
E - 2101159

! DANGER

Do not remove caps and covers of circuit sections fixed with bolts and
screws.
Touching the inside of these circuits may result in electric shock or deteriorate the performance of moisture-proof
seal, causing malfunction.

Do not remove the cap of the bushing test terminal or the cover of the
voltage measuring terminal.
This may generate a high voltage, causing electric shock or deteriorate the performance of moisture-proof seal,
causing malfunction.

Do not allow persons or objects to get close to the bushing in the air while
power is on.
A high voltage may cause electric shock. Before getting close to the bushing in the air, stop the operation of the
circuit, use a detector to make sure power to the line conductor connected to the bushing terminal is shut down and
ground the line conductor.
Before entering into the tank, make sure there is air inside. Also take
appropriate measures such as ventilation to secure air during work.
Failing to do so may cause suffocation or death due to oxygen deficiency, etc.
When the heavy fault protection circuit operates, immediately stop the
operations of the transformer and accessories.
Continuing their operations may expand fire, burns, injury or malfunction. After the transformer and accessories are
stopped, Contact ChangZhou Toshiba.

When an accident occurs inside the transformer, do not get close to the
transformer.
Explosion might occur.
Leakage of high temperature insulating oil or discomposed gas may cause fire, burns or suffocation.
Immediately stop operation and contact ChangZhou Toshiba.
During operation or immediately after operation of the transformer is
stopped , do not climb up a ladder or mount on the transformer.
If you touch the high temperature section, you may be shocked and stumble or fall, resulting in injury.
Before climbing up the ladder, stop the operation of the transformer.
When you climb up the ladder or you work on top of the transformer, take measures to prevent falling
(use of safety belts, etc.).
8 of 24
E -2101159

! WARNING

Do not disassemble or modify the equipment.

This may cause fire, electric shock or injury, or cause malfunction or deteriorate performance.
Do not use the transformer and accessories in a manner other than that
specified in the product specification.

This may cause fire, electric shock or injury, or cause malfunction or deteriorate performance.
For repair, special inspection , replacement of parts or transportation ,
contact ChangZhou Toshiba.
These operations require high-level expertise and special equipment. These operations carried out by persons other
than Toshiba personnel may result in fire, electric shock or injury, or cause malfunction or deteriorate performance.
Periodic inspection should be carried out by electrical technicians
appointed by the employer.
Performing wrong inspection may result in fire, electric shock or injury, or cause malfunction or deteriorate
performance.
Before starting periodic inspection, stop the operations of the transformer
and accessories.

Starting periodic inspection without stopping the transformer and accessories may result in electric shock or injury.
Do not carry out periodic inspection when it is raining or snowing or windy.

This may result in injury or malfunction.


Before starting operation or inspection, make sure the equipment is grounded.

Failing to ground the equipment may result in ground fault, fire or electric shock in the event of malfunction.
Do not peep into the pressure-relief device and oil release pipe.

Doing so when high-temperature insulating oil or decomposed gas comes out may result in loss of sight, burns, etc.
Do not step onto or catch your foot on accessories, piping or cables.

This may cause you to stumble or fall, resulting in injury or damage or malfunction of the equipment.
Do not leave open the secondary circuit of the current transformer.

A high voltage may be generated during operation, causing electric shock or malfunction.
When separating the current transformer from the circuit, short all the terminals and ground one end.
9 of 24
E - 2101159

! WARNING

Do not remove the cap or cover of the terminal box.

Touching the interior of the terminal box may result in electric shock or deteriorate the performance of the
moisture-proof seal, resulting in malfunction.
Do not allow fire to get close to insulating oil.
This may cause ignition, fire or burns.
Do not use fire around the transformer.
When insulating oil or decomposed gas leaks in the event of malfunction, this may cause ignition, explosion, fire,
burns or injury. Moreover, when the transformer is operating with load, decomposed gas is always coming out of the
dehydrating breather for the tap changer, and this may cause ignition, explosion resulting in fire, bums or injury.
When working at a high place, provide stable scaffolding and use falling
prevention equipment.
Failing to do so may cause stumbling or falling, resulting in injury.
When disposing of insulating oil, dispose of it as industrial waste.
Failing to dispose of insulating oil as industrial waste may result in environment pollution or fire.
When disposing of the transformer and accessories, dispose of them as
industrial waste.

The transformer and accessories contain inflammable objects such as insulating oil, springs and edged metal
objects, etc. Failing to dispose of them as industrial waste may result in environment pollution, fire, explosion, burns
or injury.
When handling chemical substances such as oil seal, silicon compound,
etc., use them after taking safety measures compliant with MSDS.

Failing to do so may cause environment pollution, fire, explosion or injury.


Do not touch the circuit sections inside the collective terminal box.
This may result in electric shock.
Before touching the circuit sections, turn off power to the circuit sections and check that power is shut down using a
detector. When the transformer is in operation, keep the door closed.
10 of 24
E -2101159

! CAUTION

Do not loosen bolts that form oil tightness.


This may cause high temperature insulating oil to flow out, resulting in burns or cause a drop of oil level, resulting in
malfunction or deterioration of performance or cause discharge of insulating oil, resulting in environment pollution.
Do not touch the electric heater inside the collective terminal box.

This may result in burns.


while the transformer is in operation or immediately after the transformer is
stopped, do not touch the transformer tank, cooling equipment, oil pipe, oil
filter unit, conservator, bushing, etc.
These parts are hot and may cause burns.
When opening the cover of the tank, make sure the pressure in the tank is
equal to the atmospheric pressure.

If the pressure in the tank is not equal to the atmospheric pressure, the inner pressure may cause the cover to fly,
resulting in injury.
Do not touch the cooling fan.

This may cause injury. The cooling fan may rotate without warning.

NOTE

Provide a protection device for the main circuit .


When the Voltage and current of the main circuit exceed specified values due to lighting or switching of the circuit,
the main circuit without a protection device may malfunction.
Protection device: Arrester, capacitor, etc. suited to main circuit.
Carry out periodic inspection.
Failing to perform periodic inspection may prevent abnormalities from being detected early, resulting in malfunction
or deterioration of performance.
Do not operate the transformer beyond rated values ( current , voltage ,
temperature .

This may cause malfunction. (Rated value: See ratings, rating name plates and specifications.)
11 of 24
E - 2101159

NOTE

While the transformer is in operation , do not stop all cooling equipment.

This may cause a temperature rise of the transformer, resulting in malfunction.


During normal operation , do not operate valves of the oil system.
This may prevent insulating oil from flowing normally, causing the temperature of the transformer to rise, resulting in
malfunction.
If the valves are operated for periodic inspection , etc., return the valves to their original conditions when the
inspection is finished.
Do not give any shock to bushing.

This may cause damage, resulting in malfunction.


When wires are disconnected, reconnect them before starting the operation.

Operating the transformer with wires disconnected or misconnected may cause malfunction.
During operation, do not operate handle operation mechanism of the
no-voltage tap changer.
While the transformer is in operation or immediately after the transformer is
stopped, do not operate the handle of the no-voltage tap changer. operate
the handle of the no-voltage tap changer only when the oil temperature falls
to 60 or below.
Operating the handle of the no-voltage tap changer at 60 or above may cause the operation of contact of the
no-voltage tap changer to loose smoothness, causing unexpected damage.
Close the door securely.

Letting rain, dust, etc. enter the box may cause malfunction.
When abnormalities occur during operation or abnormalities are detected
during inspection, contact ChangZhou Toshiba.

[Items to be informed] : Type, number ( described on name plate ), serial number of transformer ( described on name
plate of transformer ), details of abnormalities ( state, parts, be specific ) and others (line name , phase, situation of
peripheral devices before and after abnormalities occurred, etc.)
12 of 24
E -2101159

Read Safety Signs


(1) Check all safety signs attaches on the equipment.
If some of them are found missing, please inform to ChangZhou Toshiba.

(2) To avoid injury, you must read and follow all the safety signs.

(3) Keep the safety signs visible and in good shape.


Do not remove or cover any safety signs.
13 of 24
E - 2101159

3. Overview

3.1 Construction and Name of Components

For the external construction and the names of components of the transformer, see the drawing
shown in the outline of Outline of 180/240/300MVA Transformer, attached to this document.
For the construction and names of components of the accessories, see their respective instruction
manuals.

3.2 List of Accessories


This transformer comes with the following accessories. With reference to the Outline of 300MVA
Transformer, attached to this document, check their mounting positions and carefully read their
respective instruction manuals.

Accessory Type Note


H.V. Bushing ETA-550/1600-3 Shenyang Trench
Neutral Bushing ETA-120/1600-3 Shenyang Trench
M.V. Bushing ETA-252/3150-3 Shenyang Trench
L.V. Bushing BFW-40.5/4000-4 Nanjing Zhida
On-load Tap-Changer VRFI2602Y-362D-10193W MR
Motor Driven Mechanism ED100S MR
Radiators PC3200-35/520TH Changeshu Youbang
Conservator for Main Tank OH-D ChangZhou Toshiba
Dehydrating Breather for Main Tank XS2-9 ChangZhou Huari
Dehydrating Breather for OLTC XS2-1 ChangZhou Huari
Oil Level Gauge for Main Tank 170 Fukuda Instrument
Oil Level Gauge for OLTC 170 Fukuda Instrument
Oil Temperature Indicator MT-ST160F MESSKO
Winding Temperature Indicator MT-STW160WF2 MESSKO
Buchholz Relay for Main Tank 10 EMB
Rapid Pressure Rise Relay OV-22 Fukuda Instrument
Pressure Relief Device for Main Tank 208-60F QualiTROL
Pressure Relief Device for OLTC 213-001 QualiTROL
14 of 24
E -2101159

Accessory Type Note


Butterfly Valve BM-80, BM-160 Zhejiang ERG
Ball Valve DN25DN50DN80 Liang Zheng Valve
Gate Valve DN50DN125 Liang Zheng Valve
Cooling Fans DBF-6.3-H10 Weihai Creditfan
15 of 24
E - 2101159

3.3 Instructions and Drawings

3.3.1 Outline and Nameplate


Outline of 300MVA Transformer T-2207563
Nameplate T-2207537
3.3.2 Instructions
Maintenance Instruction
Maintenance of Generator Transformer E-2002256
Measurement of Insulation Resistance E-2002257
Oil Tests E-2002258
Installation Instruction
Power Transformer for 250MVA Installation Manual E-2101160
Permissible Exposed Time of Core and Coils E-2002259
Internal Work of Transformer E-2002260
On-site Inspection for Rubber Gasket E-2002261
Storing of Transformer E-2002262
Long-Term Storage of Transformer E-2002263
Requirements for Vacuum Oil Filling E-2002264
Type OH-D Oil Preservation System E-2002265
Insulation of Shielded Joint E-2002270
Cooling System
Radiators E-2002387
Cooling Fans E-2100715
Bushing
Epoxy Resin Impregnated Paper Condenser Oil-Air Bushing Instruction Manual E-2101161
Oil-Immersed Flanged Type Bushing E-2002385
Tap Changer
Motor-Driver Unit ED BA 138/06
Protective Relay BA 059/08
On-load Tap-Changer 4349307/00 EN
Sudden Oil Pressure Relay for OLTC BA 296/01
16 of 24
E -2101159

Accessories
Dehydrating Breather for Main Tank/OLTC E-2002389
Oil Level Gauge for Main Tank/OLTC E-2002267
Oil Temperature Indicator E-2002233
Winding Temperature Indicator E-2002234
Buchholz Relay E-2002215
Pressure Relief Valve for Main tank/OLTC E-2002222
Butterfly Valve E-2100168
Gate Valve E-2100724
Ball Valve E-2100167

3.3.3 Drawings
General
Outline of 300MVA Transformer T-2207563
Shipping Dimensions of 300MVA Transformer M-2208743
Base of 300MVA Transformer P-2203457
Nameplate T-2207537
Oil Level Curve M-2209162

Transformer Phase Control Cubicle Drawing Contents M-2208471


Transformer Phase Control Cubicle List of Device(1) M-2208472
Transformer Phase Control Cubicle List of Device(2) M-2208473
Transformer Phase Control Cubicle List of Device(3) M-2208474
Transformer Phase Control Cubicle Outline Drawing(1) M-2208475
Transformer Phase Control Cubicle Outline Drawing(2) M-2208476
Transformer Phase Control Cubicle Principle Drawing(1) M-2208477
Transformer Phase Control Cubicle Principle Drawing(2) M-2208478
Transformer Phase Control Cubicle Principle Drawing(3) M-2208479
Transformer Phase Control Cubicle Principle Drawing(4) M-2208480
Transformer Phase Control Cubicle Principle Drawing(5) M-2208481
Transformer Phase Control Cubicle Principle Drawing(6) M-2208482
Transformer Phase Control Cubicle Principle Drawing(7) M-2208483
Transformer Phase Control Cubicle Principle Drawing(8) M-2208484
17 of 24
E - 2101159

Transformer Phase Control Cubicle Principle Drawing(9) M-2208485


Transformer Phase Control Cubicle Principle Drawing(10) M-2208486
Transformer Phase Control Cubicle Principle Drawing(11) M-2208487
Transformer Phase Control Cubicle Principle Drawing(12) M-2208488
Transformer Phase Control Cubicle Principle Drawing(13) M-2208489
Transformer Phase Control Cubicle Terminal Block Connection(1) M-2208490
Transformer Phase Control Cubicle Terminal Block Connection(2) M-2208491
Transformer Terminal Cubicle Drawing Contents M-2208722
Transformer Terminal Cubicle List of Device M-2208723
Transformer Terminal Cubicle Outline Drawing(1) M-2208724
Transformer Terminal Cubicle Outline Drawing(2) M-2208725
Transformer Terminal Cubicle Principle Drawing(1) M-2208726
Transformer Terminal Cubicle Principle Drawing(2) M-2208727
Transformer Terminal Cubicle Principle Drawing(3) M-2208728
Transformer Terminal Cubicle Principle Drawing(4) M-2208729
Transformer Terminal Cubicle Principle Drawing(5) M-2208730
Transformer Terminal Cubicle Terminal Block Connection M-2208731
Transformer Terminal Cubicle Legend Plate M-2208732
Transformer OLTC Motor Drive Unit Drawing Contents M-2208890
Transformer OLTC Motor Unit Motor Heater and Lighting M-2208891
Transformer OLTC Motor Unit Control Circuit M-2208892
Transformer OLTC Motor Unit Control Circuit M-2208893
Transformer OLTC Motor Unit Control and Potential Terminals M-2208894
Transformer OLTC Motor Unit Indication Circuits M-2208895
Transformer OLTC Motor Unit Indication Circuits M-2208896
Transformer OLTC Motor Unit Remote Position Indication M-2208897
Transformer OLTC Motor Unit Remote Position Indication M-2208898
Transformer OLTC Motor Unit Terminal and the Equipment List M-2208899
Transformer OLTC Motor Unit the Equipment List M-2208900
Transformer OLTC Motor Unit the Equipment List M-2208901
Transformer Common Control Cubicle Drawing Contents M-2208958
Transformer Common Control Cubicle List of Device M-2208959
Transformer Common Control Cubicle Outline Drawing M-2208960
18 of 24
E -2101159

Transformer Common Control Cubicle Internal(Front View) M-2208961


Transformer Common Control Cubicle Annunciator Panel M-2208962
Transformer Common Control Cubicle Main Power Supply Circuit M-2208963
Transformer Common Control Cubicle Aux Power Supply Circuit M-2208964
Transformer Common Control Cubicle DC Power Supply Circuit M-2208965
Transformer Common Control Cubicle Dual Power Switching Circuit M-2208966
Transformer Common Control Cubicle Annunciator(1) M-2208967
Transformer Common Control Cubicle Annunciator(2) M-2208968
Transformer Common Control Cubicle Annunciator(3) M-2208969
Transformer Common Control Cubicle Annunciator(4) M-2208970
Transformer Common Control Cubicle Annunciator(5) M-2208971
Transformer Common Control Cubicle Annunciator(6) M-2208972
Transformer Common Control Cubicle Annunciator(7) M-2208973
Transformer Common Control Cubicle Annunciator(8) M-2208974
Transformer Common Control Cubicle Connect to Phase Control Cubicle*A M-2208975
Transformer Common Control Cubicle Connect to Phase Control Cubicle*B M-2208976
Transformer Common Control Cubicle Connect to Phase Control Cubicle*C M-2208977
Transformer Common Control Cubicle Connect to Terminal Cubicle*A(1) M-2208978
Transformer Common Control Cubicle Connect to Terminal Cubicle*A(2) M-2208979
Transformer Common Control Cubicle Connect to Terminal Cubicle*A(3) M-2208980
Transformer Common Control Cubicle Connect to Terminal Cubicle*B(1) M-2208981
Transformer Common Control Cubicle Connect to Terminal Cubicle*B(2) M-2208982
Transformer Common Control Cubicle Connect to Terminal Cubicle*B(3) M-2208983
Transformer Common Control Cubicle Connect to Terminal Cubicle*C(1) M-2208984
Transformer Common Control Cubicle Connect to Terminal Cubicle*C(2) M-2208985
Transformer Common Control Cubicle Connect to Terminal Cubicle*C(3) M-2208986
Transformer Common Control Cubicle Connect to Terminal Cubicle*A(CT) M-2208987
Transformer Common Control Cubicle Connect to Terminal Cubicle*B(CT) M-2208988
Transformer Common Control Cubicle Connect to Terminal Cubicle*B(CT) M-2208989
Transformer Common Control Cubicle Terminal Block Connection(1) M-2208990
Transformer Common Control Cubicle Terminal Block Connection(2) M-2208991
Transformer Common Control Cubicle Terminal Block Connection(3) M-2208992
Transformer Common Control Cubicle Terminal Block Connection(4) M-2208993
19 of 24
E - 2101159

Transformer Common Control Cubicle Terminal Block Connection(5) M-2208994


Transformer Common Control Cubicle Terminal Block Connection(6) M-2208995
Transformer Common Control Cubicle Connect to OLTC *A M-2208996
Transformer Common Control Cubicle Connect to OLTC *B M-2208997
Transformer Common Control Cubicle Connect to OLTC *C M-2209050
Transformer Common Control Cubicle Terminal Block Connection(7) M-2209051

Bushing and Terminal


Outline of HV Bushing M-2208829
Outline of Neutral Bushing M-2208831
Outline of MV Bushing M-2208830
Outline of LV Bushing M-2208848
Outline of Earthing Bushing K-2210028

Cooling System
Outline of Radiator M-2208821
Outline of Cooling Fan M-2208822

Accessories
Dehydrating Breather for OLTC M-2208808
Dehydrating Breather for Main Tank M-2208809
Outline of Butterfly Valve(BM-50) M-2208827
Outline of Butterfly Valve(BM-80) M-2208810
Outline of Butterfly Valve(BM-160) M-2208811
Oil Level Gauge for Main Tank M-2208812
Oil Level Gauge for Main OLTC M-2208813
Outline of Ball Valve M-2208819
Outline of Oil Thermometer M-2208823
Outline of Winding Thermometer M-2208824
Buchholz Relay with Gas Receiver M-2208825
Pressure Relief Device for Main Tank M-2208826
Suddenly Oil Pressure Relay M-2208828
20 of 24
E -2101159

Pressure Relief Device for OLTC M-2209015


Sudden Oil Pressure Relay for OLTC K-2210088
Outline of Gate Valve M-2208902
Outline of Terminal Connections M-2208903

3.3.4 Assembly Drawings


Internal Assembly
BCT Terminal Mark T-2207749
Internal Assembly T-2207750

External Assembly
Core and Clamp Grounding Assembly M-2209100
Pressure Relief Device Assembly M-2209101
Valve Arrangement M-2209000
Tank Assembly T-2207720
Radiator Assembly T-2207721
Pipe Assembly T-2207722
Conservator Assembly T-2207723
External Assembly T-2207724
Cable List(5-1) T-2207730
Cable List(5-2) T-2209119
Cable List(5-3) T-2209120
Cable List(5-4) T-2209121
Cable List(5-5) T-2209122
Cable Tray Assembly T-2207731
Wiring T-2207732

3.3.5 Special Tools


Accessories List M-2209161
21 of 24
E - 2101159

4. Action when Protection Circuit Operates


Refer to the drawing M-2208471 Transformer Phase Control Cubicle Drawing Cotents.
Alarm = Light Fault.
Trip = Heavy Fault.

4.1 When Light Fault Protection Circuit operates

When the light fault protection circuit operates, check the following items and contact
ChangZhou Toshiba.

[Check items when light fault protection circuit operates]


Serial number of transformer
Date/time of occurrence of irregularity
Name of light fault protection circuit that operated (See the following table)
Irregular situation
Operation situation when irregularity occurred
Operation situation of cooling equipment

Immediate Action
Description Probable Cause Consequences Countermeasures
To Be Taken
Winding Temperature . Reduce the load
High (100) . Examine the cooling
. Operating at overload Alarm on
Oil Temperature High System
. Cooling system fault DCS (SOE)
(85) . Temperature Follow CTCs
And
surveillance Instruction
Cooler Control
Buchholz Relay . Gas accumulation . Gas release
Cubicle (Local)
Operation ( For Main
Tank & Cable Box )
22 of 24
E -2101159

4.2 When Heavy Fault Protection Circuit operates

! DANGER

When the heavy fault protection circuit operates, immediately stop the
operations of the transformer and accessories.
Continuing their operations may expand fire, burns, injury or malfunction. After the transformer and accessories are
stopped, contact ChangZhou Toshiba.

When an accident occurs inside the transformer, do not get close to the
transformer.
Explosion might occur.
Leakage of high temperature insulating oil or discomposed gas may cause fire, burns or suffocation.
Immediately stop operation and contact ChangZhou Toshiba.

When the heavy fault protection circuit operates, immediately stop the operations of the
transformer and accessories, check the following items and contact ChangZhou Toshiba.

[Check items when heavy fault protection circuit operates]


Serial number of transformer
Date/time of occurrence of irregularity
Name of heavy fault protection circuit that operated (See the following table)
Irregular situation
Operation situation when irregularity occurred
Operation situation of cooling equipment

Heavy Fault Immediate Action


Probable Cause Consequences Countermeasures
Description To Be Taken
Buchholz Relay GT Trip (via 86GT)
Contact with
Operation (For Main Tank And
CHANGZHOU
& Cable Box) Plant Shutdown
TOSHIBA
Oil Temperature High An heavy accident
TRANSFORMER Follow CTCs
(95) has occurred inside Alarm on
(CTC) Instruction
the transformer DCS (SOE)
Winding Temperature High And
Tel:
(115) Cooler Control
+86-519-83256056
Cubicle (Local)
23 of 24
E - 2101159

5. Technical Specification of Transformer

5.1 Quantity
6 pieces

5.2 Type
Outdoor
Oil-immersed
Single Phase
ONAN/ONAF1/ONAF2
Connection SymbolYNa0d11

5.3 Rated Power for Each Winding


HV 180/240/300MVA
MV 180/240/300MVA
LV 36/48/60MVA

5.4 Rated Voltage for Each Winding


HV 500kV
MV 225kV
LV 35kV

5.5 Frequency
50Hz

5.6 Connection
HV Winding Wye
MV Winding Wye
LV Winding Delta
24 of 24
E -2101159

5.7 HV Winding Connections


HV WINDING CONNECTION
BETWEEN VOLTS AMPS TAP CHANGER
TERMINALS (kV) (A) POS. CONNECTION
550/3 945 1 M-T1
543.8/3 956 2 M-T2
537.5/3 967 3 M-T3
531.3/3 978 4 M-T4
525/3 990 5 M-T5
518.8/3 1002 6 M-T6
512.5/3 1014 7 M-T7 P0-P1
506.3/3 1026 8 M-T8
9A M-T9
A B C 500/3 1039 (9B) M-T0
(9C) M-T1
493.8/3 1052 10 M-T2
487.5/3 1066 11 M-T3
481.33 1080 12 M-T4 P0-P2
475/3 1094 13 M-T5
468.8/3 1108 14 M-T6
462.5/3 1124 15 M-T7
456.3/3 1139 16 M-T8
450/3 1155 17 M-T9

5.8 Transformer Serial Number


No.1 Transformer C2015084
No.2 Transformer C2015085
No.3 Transformer C2015086
No.4 Transformer C2015088
No.5 Transformer C2015089
No.6 Transformer C2015090
5.9 Standard
IEC 60076