Beruflich Dokumente
Kultur Dokumente
Fans
Reference Guide
ONTARIOrQwER
GENERATION
First Edition, September 1993 Second Edition, October 1997 Third
Edition, August 1999 Fourth Edition, January 2001
Coordinated by:
Scott Rouse, P.Eng., MBA. Ontario Hydro 1997
Revised by:
Richard Okrasa, P. Eng., MBA. Ontario Hydro
Written by:
Ralph G. Culham, P. Eng.
Consulting Engineer
for Technology Services Department, Ontario Hydro, 1993
Neither Ontario Hydro, nor any person acting on its behalf, assumes any liabilities
with respect to the use of, or for damages resulting from the use of, any information,
equipment, product, method or process disclosed in this guide.
Printed in Canada
Copyright 1993, 1997, 1999, 2001 Ontario Power Generation
FANS
Reference Guide
INTRODUCTION ......................................................................................... 1
...................................................................................................................21
Bifurcated Fans ....................................................................................21
Centrifugal Inline Fans ........................................................................21
Centrifugal Roof Exhausters ................................................................25
Utility Fans ..........................................................................................25
Fan Designation and Arrangements ....................................................25
Class Limits for Fans ..............................................................................31
PRINCIPLES OF OPERATION .................................................................... 33
Centrifugal Fans......................................................................................34
Axial Fans ................................................................................................36
FAN PERFORMANCE CURVES.................................................................. 39
FAN LAWS ................................................................................................ 43
Limitations ...............................................................................................43
Compressibility Factor ...........................................................................44
FAN FORMULAE ....................................................................................... 47
Density .....................................................................................................47
Fan Flow Rate..........................................................................................48
Head and Pressure .................................................................................49
Velocity Pressure ....................................................................................49
Total Pressure ..........................................................................................50
Fan-System-Effect Factor .......................................................................50
Fan Power and Efficiency ......................................................................50
Fan Motor Power ....................................................................................52
Example 1 ................................................................................................53
AIR SYSTEMS ........................................................................................... 59
Example 2 ................................................................................................60
FAN AND SYSTEM INTERFACE ................................................................ 65
i
TA B L E OF CO N T E N T S
2
TA B L E OF CO N T E N T S
3
LI S T OF FI G U R E S
iv
LI S T OF FI G U R E S
V
LI S T OF FI G U R E S
vi
LI S T OF TA B L E S
7
LI S T OF TA B L E S
8
CH A P T E R 1
INTRODUCTION
Fans and blowers are the largest single type of user of electricity in
industry. Applications in all industries include: boiler combustion
air supply, dust and exhaust removal (pneumatic conveying), bag
house, sewage aeration, drying, cooling industrial processes, and
ventilation. Issues such as indoor air quality and pollution control
create a continuous demand for well-designed, efficient and
cost-effective ventilation and blower systems.
Selecting the right size and type of fan and blower is fundamental to
an energy-efficient system.
The first step in any fan application is defining the needs of the
system being supplied.
Enhancing the performance of an existing air system with a new,
energy-efficient electronic control system offers significant potential
for energy savings. In some cases, retrofitting with a more efficient
fan or blower and interconnecting ductwork will be the most
appropriate way to reduce energy consumption.
Chapter 1: Introduction 1
This guide contains the information required to select an industrial
or commercial fan and blower system. Supporting handbooks and
reference material are identified in the Bibliography.
Chapter 7 provides the formulae necessary to determine the energy
consumption of a heating and ventilating fan system, particularly
variable-volume fans.
Because the personal computer is a popular design tool, the formulae
in this guide were designed to be used in a spreadsheet program.
Hourly analysis programs determine energy use more accurately,
and some of these programs can be used for system design and
selection.
This guide demonstrates how to use the American Society of
Heating, Refrigerating and Air Conditioning Engineers (ASHRAE)
Modified Bin Method on a spread-sheet program to determine
annual energy consumption when fan power is a function of
outdoor air temperature. This procedure is reasonably accurate
relative to the time required to perform the analysis.
Once the annual energy consumption is determined, a life-cycle
costing analysis of a proposed system can be done. This guide
excludes life-cycle costing techniques as they are well documented
in texts such as the ASHRAE Handbook, 1991 HVAC Applications
Volume.
DEFINITIONS
The gaseous fluid transported by a fan is most often air and/or toxic
fumes, whereas blowers may transport a mixture of particulate and
air.
BLOWER
Similar to a fan, except it can produce a much higher static pressure.
Sometimes higher pressure is achieved by a multistage impeller
arrangement.
Chapter 2: Definitions 3
e flow rate and fan outlet area.
FAN DUTY
The range of operating points, giving the fan inlet volume flow at a
rated fan pressure.
FAN EFFICIENCY
The fan total or mechanical efficiency is defined as the ratio of fan air
power to fan-shaft input power.
SYSTEM CURVE
The set of operating points defined by the duct friction, bends, and
other pressure losses that make up the connected system the fan
must serve.
PERFORMANCE CURVE
The set of operating points defined by a particular fan design, size,
and speed. Where the system and performance curves meet is the
fan's operating point.
Chapter 2: Definitions 5
Fan Total
Pressure Fan
or Performance
Fan Static Curve
System Curve
Pressure
P Operating Point
Volume Flow
V
Figure 1: Operating Point
FAN TYPES
- Axial fans have high volume capability for large duct size
ventilation applications.
CENTRIFUGAL FANS
Centrifugal fans are divided into four main subclassifcations
according to impeller type: airfoil, backward-inclined, radial and
forward-curved.
Figure 3: Airfoil
Backward-inclined
Backward-inclined (BI) or backward curved fans have an impeller
with typically 10 to 16 blades of uniform thickness incllined or
curved away from the direction of rotation.
APPLICATION
In systems that require low-to-high static pressure, specifically in
commercial HVAC systems with moderate flow volume.
Also used in industrial systems that require some tolerance to a
corrosive or erosive environment. They are being used increasingly
in industrial process ventilation with wear liners.
Radial Fans
Radial (R) fans have an impeller wheel of high mechanical strength
with typically six to 10 blades of heavy gauge material radiating out
from the hub.
Forward-curved
Forward-curved (FC) fans have an impeller wheel made of light
gauge material, with typically 24 to 64 shallow blades with both the
heel and the tip curved forward.
Air leaves the blade at a velocity greater than the tip speed, and
primarily kinetic energy is transferred to the air.
These fans are the smallest of the centrifugal type and, for a given
duty, rotate at the slowest speed.
The fan housing is a scroll design similar to the other centrifugal fan
housings, except the tolerance between the inlet cone and the wheel
is not as critical allowing lighter gauge material to be used.
AXIAL FANS
Divided into three subclassifications according to impeller type:
propeller, tubeaxial and vaneaxial.
/
hp
o r o - t ^ o o D *
o
8-
o
/
CD ^ Cfl
o
1
\
1
-
o
4
4
o
( A se
< J i - CD
2
o
C T s u
5 - rge
1
" 5
-
0
0 2 4 6 8 10 12
cfm x 1,000
Tubeaxial
Have an impeller with typically four to eight blades attached to a
hub that is usually less than half the diameter of the wheel.
Direct Drive
horsepower
Ib/cu.ft.)
Vaneaxial
Usually have short AF blades radiating from a hub greater than half
the diameter of the impeller.
Essentially axial fans with a special casing that allow the driving
motor to be removed from the airstream while maintaining a
direct-drive arrangement.
The air discharged radially from the blade tips must turn through 90
degrees to pass through the fan exit, which is in line with the
impeller inlet.
APPLICATION
Commercial applications where high efficiency, low sound levels
and space are prime considerations.
t
Airflow
Belt Drive
Down Discharge Direct Drive
Up Blast
The impeller has an inlet cone that allows mixed flow through the
impeller-blade passages, and air exits radially from the blade tips
through a concentric discharge passage.
Utility Fans
Utility fans are self-contained units consisting of either an FC or BI
irnpeller, a motor, and a direct (or belt-driven) drive.
APPLICATION
Commercial and industrial ventilation applications requiring
low-to-medium air volumes and pressures.
80
60
CD
40 O
TO
20 V)
O
J
oja Id
Arr. 9 motor on casing Arr. 9 motor on inte
h Of
fa
|J
For belt drive. Impeller overhung. Two bearings on internal supports. Motor on casing or on integral base. Drive through belt fairing.
Figure 17:
Arr. 3 SWSI Drive
For belt Arrangements
drive or direct for
Arr. 3 DWDI For belt drive or direct Arr. 4 SWSI For direct drive. Impeller
connection. One bearing
Centrifugal Fans on each side connection. One bearing on each side overhung on prime mover shaft. No
and supported by fan housing. and supported by fan housing. bearings on fan. Prime mover base
mounted or integrally directly connected.
Arr. 7 SWSI For belt drive or direct Arr. 7 DWDI For belt drive or direct
'1
bearings on base.
Arr. 10 SWSI For belt drive. Impeller
overhung, two bearings, with prime mover inside base.
Reprinted with permission from the Air Movement
and Control Association from Publication 201-90.
Arr. 3 SWSI with Inlet Box and Independent Arr. 3 DWDI with Independent Pedestal
Pedestals For belt drive or direct connection fan. For belt drive or direct connection fan. Housing is
Housing is self-supporting. One bearing on each side self-supporting. One bearing on each side supported by
supported by independent pedestals with shaft independant pedestals.
extending through inlet box.
Arr. 3 DWDI with Inlet Box and Independent Pedestals Arr. 3 SWSI with Inlet Box For belt drive or direct
For belt drive or direct connection fan. Housing is connection. Impeller overhung, two bearings on base plus
self-supporting. One bearing on each side supported by exended base for prime mover. Inlet box may be
independent pedestals with shaft extending through inlet self-supporting.
box.
PRINCIPLES OF OPERATION
All fans produce total pressure, which represents the static and
kinetic energy imparted to the air by the impeller.
The rotating blades of the fan impeller convert mechanical energy
into static and kinetic energy by changing the velocity vector of the
incoming air.
Centrifugal fans produce total pressure from the centrifugal force of
the air radiating out between the blade passages and by the kinetic
energy imparted to the air by virtue of its velocity leaving the
impeller.
The absolute velocity vector in the case of centrifugal fans is the sum
of the tangential and radial velocity components.
Axial fans produce total pressure from the change in velocity passing
through the impeller, with none being produced by centrifugal
force.
The absolute velocity vector in the case of axial fans is the sum of the
axial and tangential velocity components.
FAN LAWS
The Fan Laws relate the performance variables for any dynamically
similar series of fans at the same point of rating on the performance
curve.
Fan Law No. 1 governs the effect of changing size, speed or density
on volume flow, pressure and power level.
Fan Law No. 3 governs the effect of changing size, volume flow or
density on speed, pressure and power.
LIMITATIONS
The Fan Laws may be applied to a particular fan to determine the
effect of speed change. However, caution should be exercised since
the Laws apply only when all flow conditions are similar.
COMPRESSIBILITY FACTOR
As air travels through a fan, it is compressed and the outlet volume
will be less than at the inlet. The fan laws as presented in this
chapter do not account for this effect.
For applications where the fan pressure rise is more than 10i Wg., the
chart on the following page may be used as follows:
3. For fan selection only, multiply the required pressure and flow
by the compressibility factor, Kp. The fan input power obtained
using the fan laws for selection must be divided by Kp.
.990
.980
Kp
.970
.960
.950
.940
0 10 20 30 40 50 60 70
Fan Static Pressure Rise - inches W.G.
4 P = QP / (6362 ht)
FAN FORMULAE
1 The SI standard density of 1.20 kg/m3 is not an exact equivalent of the imperial standard density.
Source: Jorgensen, R. (ed.) Fan Engineering 8th ed. Buffalo: NY, Buffalo Forge Company, 1983.
(Ref. A). The SI density derived directly from the imperial equivalent would be a value of
1.2014 kg/m3. Source: Metric Conversion Handbook for Mechanical Engineers in the Building
Industry 2nd ed. Public Works Canada, 1983. (Ref. B)
where
PFi = input power, hp (W)
PMo = motor output power, hp (W)
Q = flow, ft.3/min. (L/s) ht = fan total efficiency,
dimensionless ratio hD = fan drive efficiency,
dimensionless ratio cf = conversion factor, 6349.6
(1,000)
EQUATION 14: The fan motor input power.
PMi = PMo
hM cf
where
PMi = motor input power, kW PMo = motor
output power, hp (W) hM = motor efficiency,
dimensionless ratio cf = conversion factor,
1.3410 ( 1,000)
EXAMPLE 1
A large cafeteria at a manufacturing plant requires an exhaust fan to
ensure proper indoor air quality for the patrons. Positive exhaust is
provided by a belt-driven, 24-in., airfoil, single-width (AFSW)
centrifugal fan with an inlet and outlet area of 4.11 sq.ft. The fan is to
be equipped with a two-speed 1,800/1,200- rpm motor and, on the
high-speed setting, is required to deliver 10,000 cfm of air at 70F at a
static pressure of 2.5 in.Wg. This is identified as operating point A
(see Figure 25). Standard atmospheric conditions are assumed for
this example.
E"
rpm
6600 1605 963 1.8 1003 2.1 1191 3.5 1260 4.2 1329 4.2 1465 6.3
7000 1703 1000 2.0 1040 2.3 1222 3.8 1288 4.4 1353 5.1 1482 6.6
9000 2189 1188 3.2 1223 3.6 1387 5.4 1446 6.2 1503 7.0 1610 8.6
9400 2287 1226 3.5 1260 3.9 1420 5.8 1479 6.6 1534 7.5 1640 9.1
9800 2384 1267 3.8 1301 4.2 1456 62 1512 7.1 1567 8.0 1671 9.6
10200 2481 1310 4.2 1339 4.6 1494 6.7 1546 7.5 1601 8.4 1703 10.2
EQUATION 17: Air volume delivered by the fan on the low speed
setting (rearrange Fan Law No. la).
Q2 = Q1 (N2/N2)
=10,000 x (1,200/1,800)
= 6,666 cfm
EQUATION 18: The corresponding impeller speed.
N2 = N1 (rpm2/rpml)
= 1,429 x 1,200/1,800 =
953 rpm
EQUATION 19: The corresponding static pressure delivered by the
fan (rearrange Fan Law No. 3 b).
AIR SYSTEMS
(Ap2/Ap1) = (Q2/Q1)2
Figure 25 (p.51) shows the characteristic system curve plotted in a
parabolic fashion according to the relationship established in
Equation 20.
The required static pressure of the fan is 2.5 in.Wg at the design flow
rate. This identifies the design operating point A from which the
design curve A is plotted. It is assumed that the fan is plenum
mounted and hence the inlet velocity pressure is
~ 0 Wg, and fan static pressure = pressure rise of 2.5 Wg.
When the fan is set at low speed, from the Fan Laws shown in
Example 1, the flow rate is 6,666 cfm.
This gives a new design point C, from which the dirty maximum
design operating system curve C is plotted (see Figure 27).
FAN SELECTION
The inlet and outlet velocities (V1 and V2) in these equations are taken
to be at the terminals of the fan manufacture's supply, which may
include silencers, inlet boxes, outlet diffusers, etc. The velocities
may not be identical to those in the adjacent ducts.
The most common definition in North America is Fan Static Pressure for
centrifugal fan and Fan Total Pressure for axial flow fans. The Europeans
use Fan Total Pressure almost exclusively for all fans.
With fan selection at point BD2, one fan is under loaded while the
other fan is heavily loaded, and surge can occur in the system.
On any system to the left of point P. The two fans in series combination
will always produce more volume than the parallel configuration.
On any system to the right of point P. Two fans in parallel will
always produce more volume than they will connected in series.
Whenever a second fan is to be added to one existing on a given
system to increase flow, it is advisable to plot pressure volume
curves for both series and parallel connection if maximum possible
flow is desired. The power absorbed by each fan should also be
carefully noted.
FAN NOISE
Fan noise is an important criteria for the proper selection of fan type
and size for an application.
The noise from a fan is predominantly from aerodynamic sources
and includes factors such as lift, rotation, vortex shedding, and
wake.
The noise generated by a fan depends on the fan design, the
volume flow rate, total pressure, and efficiency. This noise is
proportional to the product of the pressure squared and the
flow.
Low outlet velocity does not necessarily relate to lower sound
power, and fan selection should not be based solely on fan tip
speed.
The only valid basis for comparison is the actual sound power
levels generated by the different fan types when they are operating
at the required system flow and pressure.
For constant-volume systems, the recommended practice for a
selected fan type is that the fan size and speed be selected so
operation falls at or near the peak efficiency point of the fan
performance curve.
where
Bf = blade frequency, Hz
N = impeller speed, rpm (r/s)
cf = conversion factor 60 ( 1 )
Table 3: Typical Number of Fan Blades
Impeller
Fan Type Size/Drive No. of Blades
CENTRIFUGAL
Airfoil and Backward-inclined 24 in. and over 10
Under 24 in. 12
Forward-curved 52
Radial 6
AXIAL
Vaneaxial 12
Tubeaxial Belt drive 6
Direct drive 4
Propeller 6
Propeller Cooling
tower All 48 51 58 56 55 52 46 5
Note: These values are the specific power levels radiated from either the inlet or the outlet of
the fan. If the total sound power level being radiated is desired, add 3 db to each of the
above values.
EXAMPLE 3
Equation 11 54 54 54 54 54 54 54
BFI 3
Total dB 90 93 93 89 86 82 74
VIBRATION ISOLATION/
FAN BALANCING
All rotating machinery have critical speeds called resonant
frequencies where excessive vibration can cause damage. It is
necessary to have each fan and foundation installation checked to
avoid these speeds, or correct the fan balance.
Most fans are shipped statically and dynamically balanced but
corrosion, erosion, dust and airborne contaminants collecting on the
impeller may cause imbalance over time.
Therefore, consider fan isolation when designing the installation.
The transmission of vibration to a building structure involves
vibratory force, frequency of vibratory force (disturbing frequency),
natural frequency of isolator and floor, and stiffness of isolator and
floor.
It is important to select vibration isolators to compensate for floor
deflection; and to avoid resonance, the natural frequency of the
isolator should be different to the disturbing frequency.
The degree of fan isolation and balancing depends on the floor span,
and the fan type, size, speed and power.
ELECTRIC MOTOR
FAN DRIVE
The AC electric motor is the main type of prime mover used to drive
fans and there are many types.
FLYWHEEL EFFECT
The time to accelerate a fan to operating speed depends on the
fan/impeller inertia (flywheel effect) and the starting characteristics
of the electric motor.
Shaded pole motors are generally unsuitable for fan drive, because
of their inherent poor starting torque.
DC MOTORS
Sometimes DC motors are preferable for fan drive, particularly in
applications requiring speed modulation.
ENERGY CONSUMPTION
ANALYSIS
EXAMPLE: Building Ventilation
Note: This procedure involves many calculations that are easily done
using a spreadsheet computer program.
It is often necessary to estimate the energy consumption of a fan,
particularly for life-cycle costing. The energy costs are usually
determined for a period of a year.
EQUATION 27: Estimating the energy consumption of a fan
involves integrating the fan shaft input power divided by system
efficiencies over time.
n PFi t(n)
E=I ' x t(n)
1 hDt(n) x hMt(n) x ^Vt(n) x cf where:
E = energy consumption, kWh PFI t(n) =
fan shaft input power for time period, hp (W)
hDt(n) = drive efficiency for time period,
dimensionless ratio
hMt(n) = motor efficiency for time period,
dimensionless ratio
hVt(n) = variable-speed drive efficiency for time period,
dimensionless ratio
PFI c = PFI dx fP
where:
PFI c = corrected fan-shaft input power at design, hp
PFI d = fan input power at design, hp
fP = fan power correction factor
EQUATION 34: Typical fan power correction factor.
fp = 1 + 1.933 994 x exp (0.026 075 x %Qd)
100
where
fp = fan power correction factor, dimensionless ratio %Qd
= %WOcfm at design
EQUATION 35: The fan input power at each load point.
where:
Ppi (n) = fan shaft input power for time period, hp (W)
PFI c = corrected fan input power at design, hp
%hp(n) = percentage fan power for time period, %hp
%hpd = percentage fan power at design, %hp
Pn = actual density at load point, lbm/ft.3 (kg/m3)
pd = design air density used to determine hpd,
lbm/ft.3 (kg/m3)
cf = conversion factor, 1.0 (745.70)
where
LfM = motor load factor, dimensionless ratio
PMo(n) = fan motor output power at load point, hp
PM = nominal nameplate rating of motor, hp
where:
PMi(n) P = fan motor input power at load point, kW =
Fi(n) hD(n) fan-shaft input power at load point, hp (W) =
drive efficiency at load point, dimensionless
ratio
hM(n) = motor efficiency at load point, dimensionless
ratio
cf = conversion factor,1.3410 (1,000)
n
E=X (PMi(n) x t(n))
1
where:
E = energy consumption, kWh
P Mi(n) = fan motor input power for load point, kW
t(n) = time at load point, hours
EQUATION 40: Percentage static pressure at each load point
including the design point.
%sp(n) = a x %Q (n)b
where
%sp(n) = percentage fan static pressure at load point, %sp %Q
(n) = percentage fan flow at load point, %WOcfm a,b =
constants determined from table closest to design WOcfm
EQUATION 41: The fan static pressure at each load point.
Ps(n) = Psd x %sp(n) x pn x cf
%spd ps
where:
where:
NFc = corrected fan speed with VIVs, rpm
NFd = fan speed at design without VIVs, rpm
Nf = fan speed correction factor
Dependent Independent
50 55 60 65
Variable Variable Constant
%hp %Q a 1.015668 1.251667 1.847918 1.915869
%WOcfm
Dependent Independent
Variable Variable
70 75 80 85
Constant
%hp %Q a 2.012019 2.462608 3.751074 2.274535
Elevation, m 176
5.5
Maximum Static Pressure (Ps max) in.Wg From performance curve at 693 rpm
contd
Variables Constants
%hp %Q a 1.847918 Data from Table 7
b 0.055539
c 41.50000
%sp %Q a 0.022564
b 2.000808
CALCULATED PARAMETERS
99.261 Interpolated
Station pressure (Pb), kPa
Summary
In reviewing the output from the spreadsheet program, it is apparent
that the fan operates at a static efficiency of only 16% for over 6,000
hours a year. Therefore, the proposed control scheme and system
arrangement is not very efficient and another scheme should be
considered. Also, the ductwork would have to be doubled in size for
this arrangement, which would add to the installation cost.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
34 25 8 3169.211 0.02051 0.01672 0.0684 100.00 60 81.50 4.11 93.25 73.78 70.13 76.85 0.768 0.935 61.31 491
31 23 42 2810.437 0.01812 0.01477 0.0693 100.00 60 81.50 4.16 93.25 74.73 70.13 77.84 0.778 0.934 62.12 2609
28 21 186 2487.663 0.01599 0.01307 0.0702 100.00 60 81.50 4.21 93.25 75.68 70.13 78.83 0.788 0.934 62.92 11704
25 19 352 2197.793 0.01408 0.01159 0.0711 100.00 60 81.50 4.26 93.25 76.62 70.13 79.81 0.798 0.934 63.72 22428
22 18 742 2064.288 0.01321 0.01155 0.0718 100.00 60 81.50 4.31 93.25 77.40 70.13 80.63 0.806 0.934 64.38 47770
19 15 630 1705.445 0.01087 0.00922 0.0728 100.00 60 81.50 4.37 93.25 78.48 70.13 81.75 0.818 0.934 65.30 41136
16 13 644 1497.808 0.00953 0.00830 0.0737 75.00 45 45.83 2.49 64.00 54.50 43.10 56.77 0.568 0.924 45.83 29515
13 11 969 1312.737 0.00834 0.00752 0.0745 50.00 30 20.36 1.12 51.28 44.18 15.93 46.b2 0.460 0.915 37.50 36337
10 8 588 1072.839 0.00680 0.00598 0.0755 50.00 30 20.36 1.13 51.28 44.76 15.93 46.63 0.466 0.916 37.97 22325
7 5 811 872.485 0.00552 0.00471 0.0765 50.00 30 20.36 1.15 51.28 45.33 15.93 47.22 0.472 0.916 38.43 31167
4 3 621 758.030 0.00479 0.00438 0.0773 50.00 30 20.36 1.16 51.28 45.85 15.93 47.76 0.478 0.917 38.85 24124
1 0 1731 611.212 0.00385 0.00345 0.0783 50.00 30 20.36 1.17 51.28 46.42 15.93 48.35 0.484 0.917 39.31 68045
-2 -5 488 401.763 0.00253 0.00133 0.0794 50.00 30 20.36 1.19 51.28 47.09 15.93 49.05 0.491 0.918 39.85 19449
-5 -7 461 338.193 0.00213 0.00133 0.0803 50.00 30 20.36 1.20 51.28 47.62 15.93 49.60 0.496 0.918 40.28 18569
-8 -10 274 259.902 0.00163 0.00084 0.0813 50.00 30 20.36 1.22 51.28 48.19 15.93 50.20 0.502 0.919 40.75 11165
-11 -13 138 198.518 0.00125 0.00046 0.0823 50.00 30 20.36 1.23 51.28 48.78 15.93 50.81 0.508 0.919 41.22 5688
-14 -16 56 150.676 0.00095 0.00016 0.0833 50.00 30 20.36 1.25 51.28 49.36 15.93 51.42 0.514 0.920 41.69 2335
-17 -19 13 113.618 0.00071 -0.00007 0.0843 50.00 30 20.36 1.26 51.28 49.96 15.93 52.04 0.520 0.920 42.17 548
-20 -22 5 85.096 0.00053 -0.00025 0.0853 50.00 30 20.36 1.28 51.28 50.57 15.93 52.67 0.527 0.921 42.66 213
1 Bin dry-bulb temperature, "C. 11 Fan static pressure, in.Wg; Equation 41.
2 Bin mean coincident wet-bulb temperature, "C. 12 Percent fan power; Equation 32.
3 Bin hours of occurrence, h. 13 Fan-shaft input power, bhp; Equation 35.
4 Saturation pressure, Pa.; Equation A6 and Equation A7, "C. 14 Fan static efficiency, %o; Equation 42.
5 Saturation humidity ratio, dimensionless; Equation A9. 15 Fan motor output power, bhp; Equation 37.
6 Humidity ratio, dimensionless; Equation A11. 16 Motor load factor; dimensionless ratio; Equation 36.
7 Density, Ib/ft.3; Equation A14 and Equation A15 converted to IP units. 17 Motor efficiency; Equation derived from a regression analysis of
8 Load factor derived from example control sequence. Table 8 data (alternatively linear interpolation can be used).
9 Percent fan load; Equation 30. 18 Fan motor input power, kW; Equation 38.
10 Percent fan static pressure; Equation 40. 19 Fan energy consumption, kWh; Equation 27 (product of columns 3 and 18).
APPENDICES
EQUATION A3: The humidity ratio (W) of a given moist air sample
is defmed as the ratio of the mass of water vapour to the mass of dry
air.
W = mw/ma
The saturation humidity ratio (Ws) is the humidity ratio of moist air
saturated with water (or ice) at the same temperature and pressure.
EQUATION A4: Relative humidity (f) is the ratio of the mole fraction
of water vapour in a given moist air sample to the mole fraction in a
saturated air sample at the same temperature and pressure.
f = xw/xws | t,p
EQUATION A5: The dew point temperature (td) is the temperature
of moist air saturated at the same pressure (p) and with the same
humidity ratio (W) as that of the given sample of air. It is defined as
the solution td(p, W) to:
Ws(p,td) = W
The thermodynamic wet-bulb temperature (twb) is the temperature
at which water (liquid or solid), by evaporating into moist air at a
given dry-bulb temperature (t) and humidity ratio (W), can bring air
into saturation adiabatically at the same temperature (twb), while
the pressure (p) is constant.
Density Calculations
The numerical method for calculating the density of moist air is a
multistep process and initially involves determining the water-
vapour saturation pressure. The saturation pressure in SI units
at the wet-bulb temperature is calculated by the following
Hyland and Wexler formulae published in the ASHRAE
Handbook, 1989 Fundamentals Volume.
where:
W = humidity ratio, dimensionless
p = total pressure, lbf/ft.2 (Pa)
p w = partial pressure of water vapour, lbf/ft.2 (Pa)
f = Pw/Pws | t,p
where:
f = relative humidity, dimensionless pw = partial pressure
of water vapour, lbf/ft.2 (Pa)
pws = saturation pressure, lbf/ft.2 (Pa)
p = 1/v
where:
p = density, lbm/ft.3 (kg/m3)
The equation to use to determine density depends on the measured
parameters. Table A2 outlines which equations must be used with
the appropriate parameters.
V-belt Drives
Expressed as a percentage of motor output, these losses diminish
logarithmically as the motor size increases. In addition, there is a
range for each motor size where typically the losses increase as speed
increases. The value of the drive- belt loss can be determined by the
graph in AMCA Publication 203-90, or the mean drive loss can be
determined by the following equations:
EQUATION B6:
cfv =1.0 + (0.203 176 x 1n Nfv)
where:
cfv = variable-torque drive correction factor, dimensionless
ratio
PVo = (E I pf hD)/cf
EQUATION B10: For three - phase power:
C0
e A1 / A2
degree 1.5 2.0 2.5 3.0 3.5 4.0
10 0.51 0.34 0.25 0.21 0.18 0.17
15 0.54 0.36 0.27 0.24 0.22 0.20
C0
e A1 / A2
degree 1.5 2.0 2.5 3.0 3.5 4.0
10 0.54 0.42 0.37 0.34 0.32 0.31
15 0.67 0.58 0.53 0.51 0.50 0.51
20 0.75 0.67 0.65 0.64 0.64 0.65
25 0.80 0.74 0.72 0.70 0.70 0.72
30 0.85 0.78 0.76 0.75 0.75 0.76
C0
e A1 / A2
degree 1.5 2.0 2.5 3.0 3.5 4.0
10 0.05 0.07 0.09 0.10 0.11 0.11
15 0.06 0.09 0.11 0.13 0.13 0.14
C0
e A1 / A2
degree 1.5 2.0 2.5 3.0 3.5 4.0
10 0.08 0.09 0.10 0.10 0.11 0.11
15 0.10 0.11 0.12 0.13 0.14 0.15
C0
e A1/ A2
degree 1.5 2.0 2.5 3.0 3.5 4.0
10 0.05 0.08 0.11 0.13 0.13 0.14
15 0.06 0.10 0.12 0.14 0.15 0.15
C0
e A1 / A2
degree 1.5 2.0 2.5 3.0 3.5 4.0
10 0.11 0.13 0.14 0.14 0.14 0.14
15 0.13 0.15 0.16 0.17 0.18 0.18
20 0.19 0.22 0.24 0.26 0.28 0.30
C0
e A1 / A2
degree 1.5 2.0 2.5 3.0 3.5 4.0
10 0.10 0.18 0.21 0.23 0.24 0.25
From To Multiply by
F C T-C = (tF- 32)/1.8
area
1 in. 2
645.16 mm 2
1 mm 2
0.00155 in. 2
1 ft.2
0.092 903 m 2
1m 2
10.764 ft. 2
mass
1 Ibm 0.453 59 kg 1 kg 2.2046 Ibm
volume
1 ft.3
0.028 317 m 3
1m 3
35.315 ft. 3
1 ft.3
28.317 I 1 0.035 315 ft. 2
1 Ibm/ft. 3
16.018 kg/m 3
1 kg/m 3
0.062 430 Ibm/ft. 3
specific v
ft /Ibm
3
0.062 43 m /kg
3
1 m /kg
3
16.018 ft /Ib.
3
velocity
1 in.Hg (1)
3.376 9 kPa 1 kPa 0.296 12 in.Hg (1)
1 psi = 27.8 in Wg
energy, work
1 Btu 1.055 1 kJ 1 kJ 0.947 85 Btu
1 kWh 3600.0 kJ 1 MJ 0.277 78 kWh
1 ft.lbf 1.355 8 J 1J 0.737 56 ft.lbf
power
1 Btu/h 0.293 07 W 1 kW 3.412 2 MBh (2)
ABBREVIATIONS AND
SYMBOLS
ABBREVIATIONS
A
fan outlet area, ft.2 (m2) blade frequency constant
Bf
system effect coefficient, dimensionless
C
conversion factor
Co
cubic feet Per minute
cf
cubic feet Per second
cfm
fan size or impeller diameter
cfs
energy consumption, kWh
D
fan power correction factor, dimensionless ratio
E
amperage
fP
natural logarithm
I
value for calculating system effect factors specific
In sound power level, dB re 1 pW drive loss, % load
K factor
Kw
LD
lf
Wg = water gauge
Ws = saturation humidity ratio
C = degree Celsius
dB = decibel
F = degree Fahrenheit
g= gram
hp = horsepower
At = temperature difference
hM = motor efficiency, dimensionless ratio
hD = drive efficiency, dimensionless ratio
hV = variable-speed drive efficiency, dimensionless ratio
hs = static efficiency of fan, dimensionless ratio
ht = total efficiency of fan, dimensionless ratio
0 = plane angle
f = relative humidity
w = rotational speed, rad/s
BIBLIOGRAPHY
GLOSSARY
abscissa
horizontal coordinate of a point in a plane Cartesian coordinate
system obtained by measuring parallel to the x-axis. (Compare
ordinate.)
absolute humidity
in a mixture of water vapour and dry air, the mass of water vapour in
a specific volume of the mixture. Compare relative humidity.
absolute (thermodynamic) temperature
temperature as measured above absolute zero.
absolute (dynamic) viscosity
force per unit area required to produce unit relative velocity between
two parallel areas of fluid unit distance apart, also called coefficient
of viscosity.
absolute zero temperature
zero point on an absolute temperature scale.
COMMENTS:
For any changes, additions and/or comments call or
write to:
Scott Rouse
Project Manager Ontario Power
Generation 700 University
Avenue, H15-A6 Toronto,
Ontario M5G 1X6
Telephone (416) 592-8044
Fax (416) 592-4841
E-Mail srouse@ontariopowergeneration.com
Printed on
ONTARIOFuiniER
recycled papers
GENERATION