1 General ................................................................................................................................................. 5
Forward ......................................................................................................................................... 5
Acceptance Criteria (for Plate & Shaft Modification Analysis Report) ..................................... 14
Geometry..................................................................................................................................... 15
Mesh ............................................................................................................................................ 15
Crack Location ............................................................................................................................ 16
Stress ........................................................................................................................................... 17
Shear ........................................................................................................................................... 18
Deflection .................................................................................................................................... 19
4 Step-2- Manual Calculation for Bending & Companied Stress for Damper vane .............................. 20
5 Step-3- FEA Calculation for Bending & Companied Stress for Damper vane ................................... 24
Conclusion .................................................................................................................................. 47
1 General
Forward
Purpose of this Strength Calculation & Damaged Case Study report is to know the Strength for
Damper Valve Blade have adequate strength to support for Air Control Operation,
This Report Contains 4 Steps which are following below
1. Step-1-Crack Study for Exiting Blade.
Crack Study for Exiting Blade will explain the in detail of Vane cracked location, using FEA
Method
2. Step-2-Manual Calculation Bending & Companied Stress for New Damper vane
Manual Calculation for Bending & Companied Stress for Damper vane, use to cross check the
FEA calculation report
3. Step-3-FEA Calculation Bending & Companied Stress for New Damper vane
FEA Calculation for Bending & Companied Stress for Damper vane, use to cross check the
Manual calculation report
Reference Documents
V-2158-050-4-903-(Test Report For Fan performance Test)
6937-201-(Detail Of Damper Valve)
Power Plant Engineering-Black & Veatch 5th Edition
Material Used
For this structural Analysis all the material used
Housing (Outside & Inside) : SS 304 Material
Blade & Shaft : SS316 Material
Bush : Teflon
Material Properties
ANSYS Default material Settings for stainless steel
Geometry Model.
Please refer drawing No: 6937-201-Rev-C (Detail of Damper Valve)
Analysis Setup
2.3.1 Setting
Fixed Boundary
Fixed Boundary
Step-5 for Housing & Support
Fixed Boundary
Fixed Boundary
Applied Load Detail
= 0.004578 MPa
Max Allowable Bending Stress 60% of Yield Strength =207 N/mm * 60 % =124.2 N/mm (MPa)
Max Allowable Combined Stress 60% of Yield Strength =207 N/mm * 60 % =124.2 N/mm (MPa)
Max Deflection = length /360 (Refer Deflection Calculation in Step-2)
For Housing & Support
Mesh
Crack Location
Applied Pressure
Applied Boundary
Stress
Equivalent Stress
Max Shear Stress
Total Deflection
8 Result & Conclusion
Result Table
1. Step-1-Table_1Crack Study for Exiting Blade.
Allowable
Description Analysis Result Remark Reference Image
Stress
Max Bending Stress 123 24.802 Pass 5.4 Max Bending Stress
Max Companied Stress 123 24.802 Pass 5.5 Max Companied Stress
Deflection 1.47 ~0 .01 0.464 ~ 0.05 Pass 5.3 Total Deflection
4. Step-4-Table_4 FEA Calculation Bending & Companied Stress for New Damper vane
Modal Analysis
Analysis Reference Image
Description Allowable Stress Remark
Result
For Shape Mode
24.696 at As advised by SRC 6.2 Modal Max Deflection
Max Deflection In-between 0 Hz
to 100 Hz
91.625 Hz Max up to 100 Hz at 91.625 Hz
Max Stress 393.17is 6.1 Modal Equivalent
Max Stress 123 110.13 inside the place this will Stress at 91.625 Hz
be removed in welding
Harmonic Analysis
6.3Harmonic Max
Deflection at 10 Hz 1.47 0.4769 Acceptable
Deflection at 10 Hz
6.4 Harmonic Max
Stress at 10 Hz 123 7.0063 Acceptable
Equivalent Stress at 10 Hz
6.5 Harmonic Max
Deflection at 20 Hz 1.47 0.50354 Acceptable
Deflection at 20 Hz
6.6 Harmonic Max
Stress at 20 Hz 123 7.3977 Acceptable
Equivalent Stress at 20 Hz
6.7 Harmonic Max
Deflection at 30 Hz 1.47 0.55522 Acceptable
Deflection at 30 Hz
6.8 Harmonic Max
Stress at 30 Hz 123 8.157 Acceptable
Equivalent Stress at 30 Hz
6.9 Harmonic Max
Deflection at 40 Hz 1.47 0.64839 Acceptable
Deflection at 40 Hz
6.10 Harmonic Max
Stress at 40 Hz 123 9.52258 Acceptable
Equivalent Stress at 40 Hz
6.11 Harmonic Max
Deflection at 50 Hz 1.47 0.82678 Acceptable
Deflection at 50 Hz
6.12 Harmonic Max
Stress at 50 Hz 123 12.14164 Acceptable
Equivalent Stress at 50 Hz
6.13 Harmonic Max
Deflection at 60 Hz 1.47 1.2456 Acceptable
Deflection at 60 Hz
6.14 Harmonic Max
Stress at 60 Hz 123 18.3 Acceptable
Equivalent Stress at 60 Hz
6.15 Harmonic Max
Deflection at 70 Hz 1.47 3.1039 Shall be advise by SRC
Deflection at 70 Hz
6.16 Harmonic Max
Stress at 70 Hz 123 45.601 Acceptable
Equivalent Stress at 70 Hz
6.17 Harmonic Max
Deflection at 80 Hz 1.47 4.3026 Shall be advise by SRC
Deflection at 80 Hz
6.18 Harmonic Max
Stress at 80 Hz 123 63.2111 Acceptable
Equivalent Stress at 80 Hz
6.19 Harmonic Max
Deflection at 90 Hz 1.47 1.1615 Acceptable
Deflection at 90 Hz
6.20 Harmonic Max
Stress at 90 Hz 123 17.064 Acceptable
Equivalent Stress at 90 Hz
6.21 Harmonic Max
Deflection at 100 Hz 1.47 0.63962 Acceptable
Deflection at 100 Hz
6.22 Harmonic Max
Stress at 100 Hz 123 9.3968 Acceptable
Equivalent Stress at 100 Hz
Conclusion
From Setp-1- Table_1 all the stress & Deflection if higher than the allowable limit and more than
the ultimate / point of rupture , so blade will be crack or broken , therefore this blade / damper vane
have no adequate strength to support for air controlled operation
From Step-2-Table_2 & Step-3-Table_3 all the stress with in the allowable limit and comparison
Between Manual Calculation and FEA Calculation similar equal, so the new Damper vane /Blade have
adequate strength to support for Air Control Operation,
Step-4-Table_4 Deflection at 70 Hz & 80 Hz is higher than 50 % & 75 % higher than the allowable
limit, if we change the Round bar size also the deflection is same, & this deflection is not permanent
deflection because the stress is within the limit, SRC shall be advise accordingly.
From Step-5-Table_5 all the stress & Deflection are within the allowable limit, so the Housing
and Support have adequate strength to support damper Vane/Blade