Project : Golar Hilli FLNG Project

Location : HVAC System for Laboratory


Title : Condensate Drain Amount, Line Size & Trap Estimation
Date : 24 / 07 / 2017
Condensate Drain Amount, Line Size & Trap Estimation

1. Type of AHU : Constant Air Volume with Draw Through Type


Blower Fan
2. Fan Total Pressure : 1,460 Pa 5.84 in - W.C
3. External Static Pressure : 450 Pa 1.80 in - W.C
4. Fan Inlet Pressure : 750 Pa 3.00 in - W.C
5. Fan Outlet Pressure : 520 Pa 2.08 in - W.C

Cooling Coil
6. Volumetric Air Flow through Coil : 1,440 m3 / hr
7. Air Velocity through Coil : 1.00 m/s < 2.0 m/s ( w/o Mist Eliminator )
o
8. Inlet Air Properties : 40.00 C 33.43 g / ( kg-dry air )
o
9. Outlet Air Properties : 14.00 C 9.67 g / ( kg-dry air )
10. Condensate Drain Amount : 41.60 kg / hr ( Dehumidifying Capacity )
11. Condensate Drain Amount : 42.00 kg / hr ( From Coil Manufacturer )
3
12. Density of Water : 1,000 kg / m

Fig. 1 - Trap for Draw Through Unit Fig. 2 - Trap for Blow Through Unit
( During Fan Off Cycle ) ( During Fan Off Cycle )

Condensate Drain Line & Trap 1 ( Draw Through Arrangement ) ( Fig. 1 )


13. Velocity of Condensate Water : 0.15 m/s
14. Diameter of Condensate Pipe : 25 mm
15. Required Height ( H ) : 105.00 mm = 4.00 in

16. Drain Pipe & Trap Material : TBA


17. Insulation Material : Armaflex
18. Jaketting Material : TBA