Beruflich Dokumente
Kultur Dokumente
effect of fluctuating internal pressures, except for open roofs, in which the value of C C is provided.
The values of C pe (and C C in the open roof case) are determined from the most critical positive
*
and negative peak values irrespective of wind direction. Note that the factor C pi for the effect of
fluctuating internal pressures is not the actual peak internal pressure coefficient C pi but an equivalent
value producing the peak wind force coefficient C C when combined with the peak external pressure
coefficient C pe .
The wind force coefficients and wind pressure coefficients given in this section are all for isolated
buildings and are obtained from the results of wind tunnel experiments. When nearby buildings are
expected to influence the wind forces and pressures, it is necessary to carry out wind tunnel
experiments or other special researches to determine the coefficients12).
Figure A6.2.1 External pressure on a building with a vaulted roof in a wind parallel to the gable
walls
gable wall (wind direction W2 ) it is represented by the rise/depth ratio f / D and the
eaves-height/depth ratio h / D . In both cases, the roof is divided into three zones. However, the zone
definitions vary because of the difference between the flow patterns of the two wind directions. For
wind direction W1 , the definition of zones is similar to that for flat, gable and mono-sloped roofs. For
wind direction W2 , however, the definition is similar to that for spherical domes.
The external pressure coefficient corresponds to the area-averaged value and the design wind load is
assumed constant over each zone. When h / B = 0 and f / B = 0 or when h / D = 0 and f / D = 0 ,
roof level coincides with ground level. The coefficients for these cases, which have no physical
meaning, are provided to make interpolation possible.
The external pressure coefficients on walls are determined in the same way as for buildings with flat,
gable and mono-sloped roofs.
3) Spherical domes
In the same manner as for buildings with vaulted roofs, the external pressure coefficients for
spherical domes are determined from the results of a wind tunnel experiment34). Since the counter lines
of mean pressure coefficients on a spherical dome are almost perpendicular to the wind direction, the
dome surface is divided into four zones ( Ra to Rd ), as shown in Table A6.10, and the external
pressure coefficient C pe for each zone is given by spatially averaging the mean external pressure
coefficient over the zone. The building shape is represented by the rise/span ratio f / D and the
eaves-height/span ratio h / D . The values of C pe for five f / D ratios and three h / D ratios are
provided in Table A6.10. Linear interpolation can be used for values of f / D and h / D other than
shown. Both positive and negative values of C pe are provided for zone Ra . The value for h / D = 0
and f / D = 0 are again provided for interpolation.
The wind force coefficients for walls can be obtained from Table A6.12 by substituting h for H .
internal pressures, whereas one in a side or leeward wall may produce negative internal pressures.
Moreover, the internal pressure fluctuates and its characteristics depend on the relationship between
the size of the openings and the internal volume of the building. In this section, internal pressure
coefficients for buildings without dominant opening are provided based on the results of a series of
computations, in which it is assumed that the internal pressures are significantly influenced by factors
a) and b) mentioned above. That is, the values of Cpi in Table A6.11 are provided based on the
calculations of the mean internal pressures for various building configurations, assuming that the gaps
and openings are uniformly distributed over the external walls and the internal pressure is caused by
external pressures acting at the locations of the gaps and openings.
When the influence of other factors is assumed to be significant, it should be taken into account for
evaluating the internal pressure coefficient. For instance, when the internal volume is divided by
airtight partitions, the influence of factor d) is significant. When powerful air-conditioners are in
operation, the influence of factor e) is significant. In buildings with flexible roofs and/or walls, such as
membrane structures, the influence of factor f) is significant. When glass windows on the windward
face are broken by wind-borne debris in strong winds, the internal pressure is suddenly increased by
winds blowing into the building. This often results in failures of roof structures. In such cases, factor
h) should be considered appropriately.
Figure A6.2.2 Plots of drag coefficient C D on a two-dimensional cylinder with very smooth
surface as a function of Reynolds number Re 36)
(2) Wind force coefficients C R for free roofs with rectangular base
For free roofs where strong wind can flow under the roof, high fluctuating pressures act on both the
top and bottom surfaces. It is reasonable to evaluate the net wind force coefficients directly, not from
the wind pressure coefficients on the top and bottom surfaces, because the correlation between
fluctuating wind pressures on both surfaces is higher than that for enclosed buildings.
The wind force coefficients in Table A6.13 can be used for small-scale buildings, to which the
simplified method (A6.11) is applied, because the coefficients are determined from the results of wind
tunnel experiments on free roofs with H < 10 m. For gable ( > 0 ) and troughed roofs ( < 0 ),
previous studies have shown the most critical peak wind force coefficients on the windward and
leeward areas irrespective of wind direction. Since the tested roof angle is limited to the range of
| | 30 , the provision is also limited to that range.
The wind force coefficients are regulated for a clear flow case where there are no obstructions under
the roof. The flow pattern around a roof is significantly affected by obstructions under it. If there is
any obstruction whose blockage ratio is larger than approximately 50%, the wind pressure on the
bottom surface may increase significantly, resulting in a significant increase in the net wind force on
the roof. In such a case, it is necessary to evaluate the wind force coefficients from wind tunnel
experiments and so on.
(3) Wind force coefficients C D for lattice structures
The size of individual lattice structure members is generally much smaller than the width of the
structure, and they are arranged symmetrically. Therefore, it is assumed that the only wind force acting
on a plane of the structure is drag. Total drag can be estimated as the summation of the drags on each
member of the structure. Since the flow around a member depends only on the characteristics of the
local flow around it, drag is proportional to the velocity pressure at the height of the member. Based on
these features, the following two methods are often used for estimating the wind force on lattice
C6-48 Recommendations for Loads on Buildings
structures. One is to multiply the wind force coefficient, given as a function of the solidity of the
plane, by the projected area of the plane. The other method39) is to sum the wind forces on all members,
which is given by the product of the wind force coefficient C D of each member and its projected
area. For any method, the solidity should be small. In the Recommendations, the former method is
used and the wind force coefficient C D is provided only for 0.6 .
The wind force coefficient is represented as a function of the solidity , the plan of the structure
and the cross section of the member. The solidity is defined as the ratio of the projected area AF
of the plane to the whole plane area A0 = ( Bh) of the structure. The value of is calculated for
each panel of the lattice structure when the wind direction is normal to the plane. In the calculation,
the areas of the leeward lattice members and the appurtenances are not included. The wind forces on
the appurtenances can be estimated from the provision of C D for members (Table A6.16) or from
wind tunnel experiments and they are added to the wind force on the structure.
Table A6.14 provides the wind force coefficients C D for lattice structures with square and
triangular plan shapes, which consist of angles or circular pipes. The wind force coefficient C D for
the triangular shape in plan is the same for the two wind directions shown in the table. When the
members are circular pipes, the wind force coefficients C D for the members are affected by the
Reynolds number. The provisions are based on the value in the subcritical Reynolds number regime. In
strong winds, the value of C D may become smaller than that given in the provisions due to the effect
of the Reynolds number. However, this effect is not considered here.
When the plan of the structure and/or the cross section of the member are different from those in
Table A6.14, the wind loads on the structure can be estimated by using the wind force coefficients of
the members given in Table A6.16 together with the local velocity pressure. However, the solidity
of the structure is required to be less than 0.6.
(4) Wind force coefficients C D for fences on ground
Wind force coefficients C D for fences on the ground are defined as a function of the solidity
in the same manner as those for lattice structures. The value of C D for = 0 in Table A6.15 is
introduced to obtain intermediate values of C D for 0 < < 0.2 . Wind load for a fence can be
calculated according to the simplified procedure using C D and the projected area A, which is defined
as the whole area multiplied by .
(5) Wind force coefficients C for components
Wind force coefficients C for components are determined from wind tunnel experiments with
two-dimensional models in a smooth flow. The values of C can be applied to line-like members less
than approximately 50cm wide, but should not be applied to ordinary buildings. In some cases, the
value of C in the across-wind direction becomes relatively large when the wind direction deviates
only a little from the normal direction. In such cases, two values of C ( 0.6) are provided in Table
A6.16.
Wind force coefficients for components may also be used for calculating the wind loads on lattice
structures, together with the local velocity pressure q Z at height Z of the member under
CHAPTER 6 WIND LOADS C6-49
(2) Peak external pressure coefficient C pe for buildings with rectangular sections and heights less
than or equal to 45 m
1) Buildings with flat, gable and mono-sloped roofs
For estimating peak pressure coefficients for components/cladding of low-rise buildings, the subject
area is assumed to be 1 m2 as a typical value. Positive peak external pressure coefficients are given as
a function of the turbulence intensity, because the pressures depend significantly on the turbulence of
the approach flow. The positive peak external pressure coefficient on a roof is evaluated by using the
positive external pressure coefficient C pe for zone Ru in Table A 6.9(1). If no positive value of
C pe is provided for small roof angles, it is not necessary to evaluate the positive wind pressures.
Negative peak external pressure coefficients in the edge and corner regions are significantly influenced
by vortices related to flow separation at the edge. Negative peak pressure coefficients tend to increase
in magnitude as the turbulence intensity of the approach flow increases. However, the influence of
turbulence on negative peak pressure coefficients is smaller than that on positive peak pressure
coefficients on windward walls. Consequently, the provision of negative peak pressure coefficients is
determined from the values for terrain category IV and are independent of turbulence intensity. High
suctions are induced in the edge and corner regions of walls and roofs, whose widths are affected by
building dimensions such as height and width.
For gable roofs, very high suctions are induced near corners (zone Rb ) when the roof angle is
less than or equal to 10 and in the ridge corner (zones Rb and Rg ) when 20 . For
mono-sloped roofs, very high suctions are induced near the higher eaves corners (zone Rd ); the
suctions are larger and the high suction area is wider than that for gable roofs. Consequently, the peak
external pressure coefficient for zone Rd is larger than that for gable roofs. In such high suction
zones, the wind load can be reduced by using the area reduction factor k C when the subject area AC
of components/cladding is greater than 1 m2 (up to 5 m2).
2) Buildings with vaulted roofs
The peak external pressure coefficients C pe are determined from the results of wind-tunnel
experiments33), focusing on medium-scale buildings in urban areas, in which the h / B1 ratio is varied
from 0 to 0.7 and the f / B1 ratio from 0.1 to 0.4. When the f / B1 ratio is small, the corner and edge
regions of a roof are significantly affected by vortex generation as in the flat roof case. This results in
larger peak suctions in zones R a and Rd . When the f / B1 ratio is relatively large, large peak
suctions are induced in zone Rd for winds nearly perpendicular to the gable edge and in zone Rc
for winds nearly perpendicular to the eaves.
Taking these wind pressure features into account, the roof is divided into several zones and positive
and negative peak external pressure coefficients are provided for these zones, as shown in Table
A6.18(2). When the f / B1 ratio is lower than 0.1, the roof is subjected to higher suctions similar to
gable and mono-sloped roofs. Therefore, it is not necessary to evaluate the positive peak external
pressure coefficients. The values for walls can be determined from Table A6.18(1).
(3) Peak external pressure coefficients C pe for buildings with circular sections
CHAPTER 6 WIND LOADS C6-51
For buildings with circular sections, the maximum positive peak external pressure coefficient occurs
at the stagnation point on the windward face, whereas the maximum negative peak external pressure
coefficient occurs near the point of maximum negative mean external pressure. The vertical
distribution of positive peak pressure coefficients depends strongly on the mean velocity profile of the
approach flow in the same manner as that for buildings with rectangular sections. On the other hand,
negative peak external pressure coefficients are influenced by the aspect ratios H / D and surface
roughness of buildings. The factor k1 considers the effect of aspect ratio, and the factor k 2 the
effect of surface roughness in the transcritical Reynolds number regime. Negative peak external
pressure coefficients become larger in magnitude near the top of the building because of the flow
separation from the top (i.e. end effect). The factor k 3 considers this effect47). The values in Table
A6.19 are applicable to buildings with aspect ratios H / D less than or equal to 8, because the
provision is based on wind tunnel experiments using such models.
Only negative peak pressures are considered for roofs. The values of C pe for domes with
f / D = 0 provided in Table A6.20 can be used.
(4) Peak external pressure coefficients C pe for buildings with circular sections and spherical domes
Peak external pressure coefficients in Table A6.20 are determined from the results of wind tunnel
experiments34). External pressures on domes fluctuate significantly due to the effects of turbulence of
approach flow as well as of vortex generation. Therefore, both positive and negative peak pressure
coefficients are provided. Because the geometry of spherical domes is axisymmetric, they are divided
into three zones ( R a , Rb and Rc ) by coaxial circles. When the rise/span ratio ( f / D) is small,
negative peak external pressures become large in magnitude near the windward edge (zone R a ) due
to the flow separation at the windward edge. On the other hand, when the f / D ratio is large, large
positive peak external pressures are induced near the windward edge due to the direct influence of the
approach flow. Therefore, positive peak external pressure coefficients for zone R a are provided as a
function of the turbulence intensity I uH at the reference height H of the approach flow when
f / D 0.2 .
itself but an equivalent value that provides the actual peak wind force when combined with the peak
external pressure coefficient C pe . The value of CC is evaluated from a series of computations for
the peak wind force coefficients using wind tunnel data on C pe for various building configurations.
The following assumptions are made in the computations:
1) Gaps and openings in the external walls are uniformly distributed, and the internal pressures are
generated from the external pressures at the locations of the gaps and openings.
2) The fluctuating internal and external pressures are independent of each other.
When the building has intentionally designed openings or when glass windows on the windward
face are broken by flying debris, the size of the openings may be very large compared with ordinary
gaps and openings. The values in Table A6.21 cannot be used for such cases. It is necessary to estimate
the peak wind force coefficients appropriately by using the data on the external and internal pressures
obtained from wind tunnel experiments. Some international codes and standards20), 50) provide internal
pressure coefficients for buildings with dominant openings.
Cpi
1.5 1.5 10 -2
recommendation value/test value
1.0 1.0 10 -3
fSCMD(f)
category
category
0.5 II 0.5 10 -4 test
II
III III recommendation
IV IV
0.0 0.0 10 -5 -3
0 1 2 3 0 1 2 3 10 10 -2 10 -1 10 0
side ratio D/B side ratio D/B fB/UH
(a) mean overturning moment (b) rms overturning moment (c) power spectrum density of
coefficient coefficient over turning moment
Figure A6.3.1 Along-wind force in comparison with those obtained from wind tunnel tests
( H / BD = 4 )52)
'
S MD ( f ) is expressed by the following equation.
2
S 'MD ( f ) = m ( f ) S MD ( f ) (A6.3.12)
2
where m ( f ) is mechanical admittance as expressed by the following equation.
2 1
m ( f ) = (A6.3.13)
{
1 ( f / fD ) 2 2
}
+ 4 D2 ( f / f D ) 2
2
The variance of overturning moment due to the load effect by vibration MD is the integral of
2
Eq.(A6.3.12), and the variance consists of back ground component MDQ and resonance component
2
MDR as expressed by the following equation.
2
MD = S ' MD ( f )df MDQ
2 2
+ MDR
0
f D S MD ( f D )
0 0
2 2
= S MD ( f )df + S MD ( f D ) m ( f ) df = MDQ + (A6.3.14)
4 D
In this equation, resonance component is estimated approximately as a response to white noise
S MD ( f D ) .
Therefore, overturning moment for maximum load effect is expressed by following equation.
2 2
M Dmax = M D + g D MDQ + MDR (A6.3.15)
where g D is called peak factor, and is the ratio of maximum fluctuating component to standard
deviation. This is expressed by the following equation, based on the theory of stationary stochastic
process.
0.577
g D = 2 ln( DT ) + 2 ln( DT ) + 1.2 (A6.3.16)
2 ln( DT )
where T is time for evaluation and D is level crossing rate calculated from power spectrum density
as in the following equation.
D =
0 f 2 S ' MD ( f ) df
fD
RD
(A6.3.17)
1 + RD
0 S 'MD ( f )df
Additionally, in some foreign wind loading standards, M Dmax is expressed by the following formula.
In this equation, the background component and the resonance component are distinguished.
M Dmax = M D + g Q2 MDQ
2
+ g R2 MDR
2
(A6.3.18)
where g Q is peak factor of background component (=3.4) and g R is peak factor of resonance
component calculated from Eq.(A6.3.16) as D = f D .
(4) Vertical distribution of equivalent static wind load
In the gust effect factor method, the vertical distribution of wind load is given by mean wind load
multiplied by gust effect factor. This wind load is an approximate value based on the assumption that
vibration mode is close to mean wind load distribution and the building has uniform density. Actually,
the mean, background and resonance components of wind load distribution are different. The mean
component is expressed by Eq.(A6.3.8), and the resonance component is expressed by Eq.(A6.3.3).
Therefore, if the vertical distribution of building mass is remarkably uneven, the resonance component
C6-56 Recommendations for Loads on Buildings
should be estimated carefully. In that case, the distribution of resonance component for the
fundamental vibration mode could be estimated from the following equation.
2 2
WD = W D + WDQ + WDR (A6.3.19)
where
W D = qH CD A
C'g
WDQ = g DQ q H C D A
Cg
A
WDR = a Dmax ( Z )m( Z )
B
where
WD , WDQ , WDR (N): mean, background and resonance component of wind load, respectively
aDmax (cm/s2): maximum acceleration at top of building as defined in A6.10.2
g DQ : peak factor of background component
In this recommendation, it is assumed that the background component has a similar distribution to
mean component. The following methods may also be used.
1) Shear force or overturning moment at a certain building height may be obtained from the integral of
pressure on area over the height20).
2) Load distribution can be defined by LRC formula53).
(5) Example of calculation of gust effect factor
Figure A6.3.2 shows the variation of gust effect factor by terrain category and building height for
H / B = 4 , D / B = 1 and U 0 = 35 m/s. The gust effect factors become large with terrain category and
building height.
3.8
3.6 category
gust effect factor G D
3.4 V
IV
3.2 III
3.0 II
I
2.8
2.6
2.4
2.2
2.0
0 50 100 150 200 250 300
0 50 100 150 200 250 300
height of building (m)
Figure A6.3.2 Variation of gust effect factor with terrain category and building height
A6.3.2 Gust effect factor for roof wind loads on structural frames
Gust effect factor for roof wind loads on structural frames is influenced by external pressure and
internal pressure. It can be assumed that there is no correlation between fluctuation of external
CHAPTER 6 WIND LOADS C6-57
pressure and fluctuation of internal pressure for a building without dominant openings. Furthermore,
Helmholtz resonance, the phenomenon of varying internal pressure at a specific frequency by external
pressure, can be disregarded. Fluctuating internal pressure coefficient is derived from the theory for
buildings with uniform openings54). Therefore, external pressure fluctuation, which is slower than
response time of internal pressure, is transmitted as internal pressure, and it is assumed that quicker
pressure fluctuation is not transmitted as internal pressure. Furthermore, fluctuating internal pressures
act on all parts of a roof simultaneously for more safety. Generally, response time of internal pressure
is long enough, compared with the natural period for the first mode of the roof structure. Therefore,
resonance of the roof structure for internal pressure can be disregarded. Under these conditions, gust
effect factor for roof wind loads is given by the following equation.
2 2 2 2 2
g Re rRe (1 + RRe ) + g Ri rRi rc
GR = 1 (A6.3.21)
1 rc
where g Re and g Ri are peak factors for generalized external pressure and generalized internal
pressure, and these value are g Re = 3.5 , g Ri = 3 from the results of test and measurement. rRe and
rRi are the generalized fluctuating external and internal pressures divided by the generalized mean
wind pressure coefficient. rc is the generalized mean internal pressure divided by the generalized
mean external pressure coefficient. RRe is resonance factor, which is calculated from the
non-dimensional power spectrum density at the frequency of the first mode of the roof and the critical
damping ratio.
wind load
time
Figure A6.3.3 Fluctuation of roof wind loads when wind force coefficient is small
An equation of gust effect factor is expressed for two cases of internal pressure coefficient,
C pi = 0.4 and C pi = 0 , given by Table A6.11. If wind force coefficient is small, roof wind loads act
in the upward direction and in the downward direction as shown in Fig.A6.3.3. When combinations
with other loads are considered, downward wind load can be dominant even if the absolute value is
small. Therefore, downward wind load can be calculated. In Eq.(A6.17), GR for +corresponds to
load in the same direction as given by wind load coefficient, and GR for is opposite. The above is
the same for Eq.(A6.18) and Eq.(A6.19). However, wind force coefficients are given as positive or
negative in A6.2.2, and gust effect factor should be calculated from Eq.(A6.17) with +. Furthermore,
C6-58 Recommendations for Loads on Buildings
the equation, f R 0.57 ( is deformation at center due to weight), can approximately evaluate
the natural frequency for the first mode of the roof beam, and the document55) is useful for estimating
the critical damping ratio, R .
(1) Case for C pi = 0.4
Roof wind loads can be calculated for roof beams parallel to the wind direction and for roof beams
normal to the wind direction.
If external pressure coefficient C pe is 0.4 over the whole subject area as center beam shown in
Fig.A6.3.4(a), the wind force coefficient becomes C R = 0 . In this case, roof wind loads can be
calculated from Eq.(A6.18), which is the product C R G R of wind force coefficient C R and gust
effect factor GR . However, when the wind force coefficient becomes partially C R = 0 as shown in
Fig.A6.3.4(b), the wind loads can be calculated from Eq.(A6.17).
-0.2 -0.4
-1.0 -0.6
external
pressure
coefficient
-0.4
-0.8
internal pressure
-0.4 external
pressure coefficient
coefficient
-0.4
wind force
-0.4 internal
pressure
0 coefficient
+0.2 -0.2
coefficient
beam -0.6
=
0 -0.4
-0.4 wind force
coefficient
beam
beam
beam
wind direction
wind
direction
(a) beams normal to the wind direction (b) beams parallel to the wind direction
Figure A6.3.4 Relation between wind force coefficient and external or internal pressure coefficient
(for C pi = 0.4 )
(2) For C pi = 0
Wind force coefficient is equal to external pressure coefficient for C pi = 0 . In this case, gust effect
factor can be calculated from Eq.(A6.19). The equation considers the mean and fluctuating
components of external pressure, and the fluctuating component of internal pressure.
U H /( f L BD) > 10 , aeroelastic instability may well occur and wind load will need to be calculated
from the wind force and the response in wind tunnel tests.
Along-wind vibration is caused by turbulence in natural wind, but across-wind vibration is caused
by wind turbulence as well as by the vortex in the wake of the building. Although there are many study
examples with regard to the behavior of a vortex in the wake of a building, unclear points remain.
Furthermore, since the behavior is greatly affected by building shape, it is difficult on the whole to
theoretically estimate across-wind vibrations in the same manner as for along-wind vibrations. With
consideration of the first mode, an estimation equation for across-wind load has been derived from
data of across-wind fluctuating overturning moment obtained from wind tunnel tests. Subjects for this
estimation equation are structures with rectangular planes (side ratio D / B = 0.2 ~ 5 ) from which
many experimental data have been obtained. Moreover, by taking into account the fact that
experimental data for buildings with an aspect ratio H / BD exceeding 6 are insufficient, and that
aeroelastic instability easily occurs in these buildings, the scope of application is limited to aspect
ratios of 6 or less.
Furthermore, data of across-wind fluctuating overturning moment for buildings with plane shapes
other than rectangular planes can be obtained from wind tunnel tests. Where it is unnecessary to
consider aeroelastic instability, across-wind wind loads can be calculated using the method indicated
in the recommendations.
A6.4.2 Procedure
(1) Concept of wind load estimation
Since a fundamental mode usually predominates in across-wind vibration, across-wind loads are
calculated using the spectral modal method considering only to the first translational mode, in the
same manner as for along-wind loads. For the non-resonance component, the profile of fluctuating
across-wind force is set to be vertically uniform and the magnitude of the fluctuating wind force is
decided to agree with the fluctuating overturning moment. The resonance component estimates the
inertia force due to vibration and the vertical profile is determined using L in Eq.(A6.33) so as to be
proportioned to the first translational mode.
It is recommended that the critical damping ratio be estimated with reference to Damping in
buildings 7).
(2) Modeling of overturning moment
The overturning moment varies with building shape and wind characteristics, but in the subjective
scope the breadth-depth ratio has the greatest effect on the overturning moment: the effects of other
parameters are slight. Therefore, in the recommendations, the fluctuating overturning moment is set as
a function of only the breadth-depth ratio of a building based on wind tunnel test data 52, 56).
(3) Buildings with circular planes
Across-wind responses of buildings with plane shapes other than rectangular planes can be
estimated with the same concept. This section details buildings with circular planes. The parameter
C6-60 Recommendations for Loads on Buildings
It is recommended that the critical damping ratio be estimated with reference to Damping in
buildings 7).
(2) Modeling of torsional moment
The torsional moment varies according to building shape and wind characteristics, but in respect of
buildings in the subjective scope the breadth-depth ratio exerts the greatest effect on the torsional
moment and the effects of other parameters are slight. Therefore, in the recommendations, the
fluctuating torsional moment is set as a function of only the breadth-depth ratio of a building based on
wind tunnel test data 52, 56).
2I H
BD (1 + RD )
q H C D HB0
x max,Z = g D (A6.6.2)
K 0.95 + +
However, the mean response X Z at height Z is given by:
qH CD H B0 B BH
XZ = 0 (A6.6.3)
K 1 + 2 + 2 + 2 +
where qH , I H are the velocity pressure and the turbulence intensity, respectively, at H height,
and is the exponent of the power law in the wind speed profile. g D , RD and BD are the peak
factor, the resonance factor and the back ground excitation factor, respectively.
Gust effect factor is given by Eq.(A.6.23).
A6.7.2 Vortex induced vibration and resulting wind load on buildings with circular sections
Shear layers separated from windward corners of both sides of buildings roll up alternately to shed
into wake and form Karman vortex streets behind the buildings. According to the alternate shedding,
the periodic fluctuating wind loads act on the buildings in the across-wind direction. When the natural
frequency of the building coincides with the vortex shedding frequency, the vibration of the building
can be resonant with the periodic fluctuating wind loads, causing the building to vibrate at large
amplitude in the across-wind direction. This is vortex-induced vibration, which is a problem for many
structures, particularly chimneys.
The critical wind speed of the resonance is larger than the design wind speed for most buildings, so
these phenomena are not normally important. However, as the critical wind speed is smaller than
CHAPTER 6 WIND LOADS C6-63
design wind speed for very slender buildings with small natural frequency and damping like steel
chimneys, tall buildings and building components, the effect of vortex induced vibration should be
checked carefully in the wind resistance design stage.
A lot of research has been done on vortex-induced vibration and a number of methods have been
developed in the past decade for estimating vibration amplitude and its equivalent static wind loads,
particularly for structures with circular sections. The equivalent wind loads described in the
recommendation are based on the spectral modal method in which the Strouhal number of vortex
shedding is 0.2, and the power spectrum of the fluctuating wind loads depends on the vibration
amplitude6) and the Reynolds number.
The effects of structural density, damping and Reynolds number are included in the resonant wind
force coefficient C r , which is shown in Table A6.2.3 for three categories of Reynolds number region
and for two types of structures with various density and damping. The rows in the table show the
effect of Reynolds number, that is, U r Dm < 3 is the subcritical region, 3 U r Dm < 6 is critical
region and 6 U r Dm is super/trance critical Reynolds number region. s L in Table A6.23
depends on the amplitude at the resonant condition. s L < 0.5 corresponds with the large
amplitude, and s L 0.5 corresponds with the small amplitude.
A6.7.3 Vortex induced vibration and resulting wind load on building components with circular
sections
Occurrence of vortex induced vibration of building components with circular section can be
checked by Eq.(A6.26). Most design wind speeds for components like members of truss towers are
larger than the critical wind speed, so the effect of vortex induced vibration should be checked
carefully. In particular, the vibration amplitude can be very large for components like steel pipes
whose mass and damping are small. The equivalent wind loads described in Eq.(A6.27) are introduced
in the sub-critical Reynolds number region based on wind tunnel tests59). The equation is applicable for
various boundary conditions at the ends of components.
A6.8.2 Combination of horizontal wind loads for buildings not satisfying the conditions of Eq.(6.1)
Buildings not satisfying the conditions of Eq.(6.1) have a small resonance component. For such
cases, it is considered that wind load of times of the windward loads act in the across-wind
direction, as shown in figure 6.8.1. tends to increase with building height according to the stress
analysis for buildings with rectangular columns using wind load from wind tunnel tests. Therefore, an
approximate equation of for an 80m-high building is defined as per the recommendation.
A6.8.3 Combination of horizontal wind loads for buildings satisfying the conditions of Eq.(6.1)
Buildings satisfying the conditions of Eq.(6.1) have a large resonance component. For such cases, it
is assumed that response probability is expressed by a normal distribution. If the overturning moments
in two directions, M x , M y , are expressed by a 2-dimensional normal distribution, the equivalence
line of probability becomes an eliptical line using correlation coefficient of response, , as shown in
Figure A6.8.3. Every point on the eliptical line (solid line) can be considered as a load combination,
but it is not practical to consider a lot of them. Therefore, load combinations can be defined as the
apexes of an octagon enveloping the oval. In other words, y-direction overturning moment M yc ,
which should be combined with maximum x-direction overturning moment M xmax , is defined by the
following equation using mean y-direction overturning moment M y and maximum fluctuating
component of y-direction overturning moment m ymax .
M yc = M y + mymax ( 2 + 2 1 ) (A6.8.1)
Table A6.24 shows the combination of loads according to the upper equation considering following
characteristics of along-wind, across-wind and torsional wind loads.
Co-coherence (correlation coefficient for each frequency) is negligible between along-wind force
and across-wind force, and between along-wind force and torsional wind force. Therefore, = 0
as co-coherence of response is negligible.
Because the co-coherence between across-wind force and torsional wind force is not zero, the
absolute value of the correlation coefficient of response LT , shown in Table A6.25, is defined
by calculation based on wind tunnel tests.
LT is calculated by a statistical analysis method61) under the conditions that the critical damping
CHAPTER 6 WIND LOADS C6-65
ratios for across-wind vibration and torsional vibration are 0.02, and the building has no coupling
vibration mode. Therefore, if the critical damping ratio differs greatly from 0.02 or the buildings
vibration mode is significantly coupled, it is necessary to carry out special research.
My
mx max
point A
M y max
my max M yc
considered point of M y0 m y max ( 2 + 2 1)
combination load my max
My
m y max (1 2 2 )
Mx
Mx M x max
Figure A6.8.3 Schema of load combination in consideration of response correlation
A6.9.2 Procedure
The mode shape correction factor is specified by Eq.(A6.32). This corrects the gust effect factor for
C6-66 Recommendations for Loads on Buildings
1
Z
T = (0.27 + 0.73)
(A6.9.4)
H
In addition, the generalized mass M D , M L and the generalized inertial moment I T of a
building can be calculated according to Eqs.(A6.9.5) and (A6.9.5), respectively.
2
H Z
M D (L ) = 0 mZ
H
dZ (A6.9.5)
2
HZ
IT =
0I Z dZ
H
(A6.9.6)
where mZ and I Z are the mass and the inertial moment at height Z , respectively.
Furthermore, aD is multiplied by the peak factor in the recommended equation for the
acceleration at the top of the building. Because the resonant component is dominant in acceleration,
level crossing rate D for calculating peak factor is approximated by the natural frequency f D .
A.6.11.2 Procedure
The simplified procedures are derived from the results of calculation for buildings with reference
heights of 5 - 15m and projected breadths of 5 - 30m, assuming that the wind directionality factor K D
is 1.0 and the terrain category is III. Therefore, this procedure can be applied to terrain categories IV
and V with some overestimates in wind loads. For terrain categories less than III, the exposure factor
Ce is introduced. When wind speed is expected to increase due to local topography, the wind loads
shall be increased appropriately, for example, by multiplying by the square of the topography factor
Eg .
When groups of two or more tall buildings are constructed in proximity, the fluid flow through the
group may be significantly deformed and have a much more complex nature than is usually
acknowledged, resulting in enhanced dynamic pressures and motions especially on neighboring
downstream structures. Therefore, study of mutual interference among closely-located tall buildings is
an important problems not only in wind resistant structure design but even in minimizing wind-motion
discomfort to building occupants. Wake-induced oscillation in the downstream structure is considered
to be affected by interference from upstream buildings of various sizes placed in various locations and
also by the turbulence of incident flows.
Figure A6.12.1 shows contours of the increase or decrease ratios for the maximum along/across
CHAPTER 6 WIND LOADS C6-69
wind responses of the downstream building exposed to interference from an upstream building at
various locations to those of an isolated building where the maximum responses including mean
deflection are estimated at near the design wind speeds of 4060m/s by a modal-spectrum method
(1,2). The contours are illustrated for an identical pair of square tall buildings with aspect ratio
H / BD = 4 where two coordinate axes are normalized by the non-dimensional distance using the
reference building breadth BD .
The response ratios in the across-wind direction are usually larger than those in the along-wind
direction. Interfering positions producing response ratio contours higher than 1.2 are generally
restricted to regions of 12 BD in the x-direction and 6 BD in the y-direction, whereas interfering
positions higher than 1.1 exceed the regions indicated in the figure.
When the flat terrain subcategories increase from Category II to Category IV, the dynamic responses
of the downstream building are relatively independent of mutual interference effect. This is closely
related to the fact that when turbulence is added to an incident flow, shedding vortices from an
upstream building and the alternately deformed wake surrounding the vortices are not clearly formed
in the wake owing to increased entrainment and diffusive action, and the production of additional
turbulence by the introduction of the upstream building is unlikely because of the sufficiently high
turbulence in the incident flow (3).
y y
6 BD 6 BD
1.1 1.2
4 4
1.1 1.1 1.2
1.3
1.2 1.3
2 2
1.1 1.0
x 1.0 1.0 x 1.2 1.1
12 BD 6 4 2 12 BD 6 4 2 1.3
0.8
(a) Terrain category II, along-wind direction (b) Terrain category II, across-wind direction
1.2
y
6 BD
1.2 1.1
1.2 4
1.2 1.4
1.2
1.1
1.2 2
1.0
1.0
1.0
x 1.1 1.0 1.1
12 BD 6 4 2 0.8
1-year-recurrence wind speed U 1H is used to calculate the acceleration of wind response for the
evaluation of the habitability, defined in Eq.(A6.41).
Figure A6.5 is smoothing of the wind speed map based on the 1-year-recurrence wind speed at the
metrological offices, from which the wind speed U1 at any locations can be estimated. The
1-year-recurrence wind speeds at the metrological offices are established based on the daily-maximum
wind speed data regardless of wind directions collected from 1991 to 2000. On the other hand, because
the wind response characteristic is not the same for the wind direction, the wind speed, which becomes
the same acceleration is also different for the wind direction. Therefore, if the wind direction
characteristic, that is, the frequency of exceedance of each wind speed can be understood, a reasonable
design becomes possible. This wind direction characteristic in the range of the wind speed to evaluate
the habitability is generally clarified.
When the maximum acceleration a max is approximated as a function of wind speed U shown in
Eq.(A6.13.1), the return period t a max for maximum acceleration a max is calculated by
Eq.(A6.13.2). The probability at the right side of Eq.(A6.13.2) is expressed as the total sum of the
occurrence probability of the wind speed in every 16 azimuths shown in Eq.(A6.13.3).
amax = f (U ) (A6.13.1)
1
t a max = (A6.13.2)
1 Fa ( amax )
Fa ( amax ) = pi FU { }
16
f i 1 (amax ) (A6.13.3)
i =1
where
Fa ( a max ) : probability that maximum acceleration does not exceed a max
pi : occurrence frequency for wind direction i
{ }
FU f i 1 (amax ) : probability that the wind speed does not exceed the wind speed that the
maximum acceleration is equal to a max for wind direction i
The occurrence frequency at each wind direction pi , parameters ai and bi in Eq.(A6.13.4),
which are the parameters to calculate the right side of Eq.(A6.13.3), are shown in Table A6.13.1.
These parameters are estimated based on the daily maximum wind speed at 30 cities, with the least
square method applied for the data at Naha where typhoon is dominant, and the Gumbels moment
method for other cities. These parameters ai and bi should be used for the return period less than 1
year.
FU ( U i ) = exp[ exp{ ai (U i bi )}] (A6.13.4)
where
U i : 10-minute mean wind speed at 10m above ground over a flat and open terrain for wind
direction i
ai , bi : parameters estimated based on the daily maximum speed for wind direction i
CHAPTER 6 WIND LOADS C6-71
In addition, the wind direction factor in A6.1.4 should be used for 100-year-recurrence wind
speed, and it is not possible to use it here.
Table A6.13.1 parameters ai , bi and occurrence frequency pi for each wind direction at 30 cities
Asahikawa Sapporo Aomori Akita Sendai
ai bi pi(%) ai bi pi(%) ai bi pi(%) ai bi pi(%) ai bi pi(%)
NNE 0.58 4.26 3.3 1.58 3.59 0.4 1.22 3.57 4.6 0.73 4.79 0.4 0.82 4.40 1.7
NE 0.52 4.32 0.8 1.23 3.76 0.5 0.82 4.03 4.0 0.56 5.88 0.1 0.61 3.72 1.1
ENE 0.54 3.63 0.2 1.30 3.80 1.6 0.76 5.84 3.7 0.73 3.17 0.2 0.56 5.86 0.8
E 1.45 2.28 0.7 0.94 4.93 4.0 0.90 5.46 7.9 0.63 4.77 0.3 0.66 5.09 0.7
ESE 1.05 2.74 0.7 0.72 5.52 6.2 0.60 6.09 1.1 0.65 6.57 7.2 0.74 4.97 0.8
SE 0.76 4.44 6.4 0.59 7.49 8.1 0.64 7.71 0.7 0.63 6.25 17.0 1.14 3.89 16.7
SSE 0.55 5.61 17.1 0.47 8.86 13.5 0.58 4.61 0.5 1.25 4.70 0.2 0.76 4.58 13.3
S 0.54 4.34 3.9 0.43 7.94 3.2 1.58 2.79 0.2 0.72 6.27 0.1 0.75 4.66 6.4
SSW 0.48 6.37 3.3 0.45 7.31 1.8 0.54 5.27 2.8 0.38 8.91 2.2 0.87 5.06 1.8
SW 0.59 6.72 1.2 0.44 7.96 2.1 0.47 6.47 12.6 0.46 7.44 9.9 0.77 5.55 0.9
WSW 0.49 7.58 10.1 0.47 8.41 3.9 0.48 7.56 10.2 0.38 6.98 12.5 0.46 8.02 1.6
W 0.63 6.45 17.6 0.53 8.53 5.1 0.50 9.11 14.0 0.36 7.91 17.7 0.42 8.75 7.7
WNW 0.65 5.80 19.4 0.45 9.28 5.2 0.55 8.43 15.7 0.37 9.68 11.9 0.39 9.42 16.9
NW 0.68 4.78 8.8 0.46 8.63 19.5 0.66 6.00 8.6 0.45 9.56 9.2 0.43 8.62 10.1
NNW 0.86 5.66 4.7 0.59 7.05 23.3 1.00 4.20 6.7 0.60 7.87 3.8 0.56 5.44 7.9
N 0.83 4.92 1.8 0.83 4.78 1.6 0.84 3.49 6.7 0.75 5.86 7.3 0.75 5.17 11.6
Niigata Kanazawa Utsunomiya Maebashi Tokyo
ai bi pi(%) ai bi pi(%) ai bi pi(%) ai bi pi(%) ai bi pi(%)
NNE 1.07 4.61 14.4 0.76 5.11 5.8 0.70 4.47 18.5 0.28 9.56 0.1 0.87 5.46 4.2
NE 1.78 3.66 6.6 0.81 5.38 3.0 0.88 4.43 8.8 0.0 1.04 5.43 6.2
ENE 0.85 3.72 0.3 0.99 5.02 10.5 1.01 4.52 2.3 1.20 4.78 0.1 1.05 5.58 6.6
E 1.24 4.17 0.2 0.93 4.62 9.9 1.13 3.81 3.5 0.71 4.32 1.4 1.10 5.47 3.3
ESE 0.64 7.39 0.2 0.87 3.56 0.9 1.37 3.85 7.1 0.81 5.19 22.7 1.22 5.67 3.6
SE 0.69 8.05 6.6 1.35 3.32 1.2 1.33 3.76 9.2 0.99 4.83 8.7 1.37 6.02 1.9
SSE 0.98 5.69 4.4 2.15 3.26 1.6 1.00 4.26 9.1 1.21 3.84 2.0 0.94 4.99 0.3
S 1.65 4.38 1.7 0.17 4.11 0.5 0.78 4.68 6.0 1.17 3.76 1.2 0.83 6.53 20.2
SSW 1.19 4.78 3.0 0.42 7.62 8.2 0.75 4.48 6.4 0.57 2.88 0.3 0.56 7.61 2.0
SW 0.45 6.84 3.2 0.43 9.16 8.5 0.81 4.12 2.8 0.49 3.30 0.3 0.53 7.80 9.8
WSW 0.40 8.65 14.4 0.45 8.65 9.7 0.68 4.79 1.5 0.50 4.65 1.3 0.64 5.84 0.4
W 0.44 7.29 18.8 0.36 7.49 12.1 0.59 6.99 2.2 0.44 6.78 1.5 0.45 7.83 0.2
WNW 0.38 8.39 7.7 0.37 6.62 9.1 0.53 7.17 3.1 0.34 6.86 3.5 0.50 7.23 0.2
NW 0.48 8.40 6.9 0.44 5.36 7.4 0.47 5.14 1.6 0.45 6.82 26.0 0.45 8.28 4.9
NNW 0.52 7.43 6.7 0.38 5.82 3.7 0.50 5.67 3.6 0.47 8.43 26.7 0.47 7.37 25.8
N 0.66 5.56 4.9 0.66 4.89 7.9 0.58 4.49 14.3 0.51 11.0 4.2 0.64 5.85 10.4
Chiba Yokohama Shizuoka Hamamatsu Nagoya
ai bi pi(%) ai bi pi(%) ai bi pi(%) ai bi pi(%) ai bi pi(%)
NNE 0.73 6.38 6.2 0.58 7.52 1.8 0.83 4.75 2.9 0.80 4.59 0.4 1.10 3.61 1.6
NE 0.89 6.10 6.1 0.81 6.50 0.1 0.77 5.74 9.5 1.25 3.20 3.0 1.80 2.92 0.7
ENE 0.97 5.46 6.7 0.64 7.58 1.4 0.94 5.74 23.7 0.56 6.29 7.1 2.25 2.29 0.8
E 1.02 4.85 2.5 1.04 5.62 9.1 0.88 5.51 1.8 0.59 6.69 7.8 2.46 3.82 0.1
ESE 1.41 4.08 6.9 1.19 5.00 1.9 0.80 4.50 1.8 0.74 6.59 2.5 0.47 6.21 0.4
SE 1.27 4.26 9.9 0.71 5.81 0.9 0.75 3.95 1.3 1.03 5.35 5.5 0.47 6.03 3.8
SSE 0.68 4.96 3.8 0.76 5.48 7.5 0.92 4.96 6.1 0.80 5.06 6.7 0.51 6.54 13.5
S 0.77 4.62 2.2 0.63 5.85 4.2 0.81 5.46 17.6 0.93 4.93 2.5 1.16 4.85 11.0
SSW 0.35 9.90 4.8 0.40 9.60 5.8 0.50 6.50 4.1 0.67 5.94 0.6 1.26 4.67 2.0
SW 0.45 7.69 13.4 0.38 8.74 15.8 0.42 8.63 12.4 0.58 5.77 3.2 1.14 4.78 1.1
WSW 0.74 4.95 8.8 0.40 8.42 3.4 0.57 9.01 4.0 0.68 6.00 13.8 0.88 3.81 1.3
W 0.59 4.84 0.7 0.48 8.68 0.2 0.51 10.1 5.3 0.66 7.30 16.7 0.59 5.61 1.4
WNW 0.42 8.33 0.6 0.65 8.27 0.3 0.39 7.05 3.8 0.49 9.15 23.6 0.70 6.49 18.8
NW 0.46 7.68 7.0 0.36 8.39 0.5 0.55 4.96 1.8 0.39 8.27 5.9 0.53 7.29 19.0
NNW 0.48 6.26 15.1 0.32 6.95 2.5 1.28 4.07 2.9 0.55 4.18 0.5 0.50 5.49 16.2
N 0.61 5.46 5.3 0.46 7.21 44.5 0.59 3.81 1.0 1.69 4.88 0.2 0.89 4.10 8.3
C6-72 Recommendations for Loads on Buildings
100-year-recurrence basic wind speed U 0 and 500-year-recurrence wind speed U 500 based on the
annual maximum wind speed approximated by a Gumbel distribution. The mean value and the
standard deviation of the T -year maximum value can be obtained from these values based on the
method described in chapter 2. A calculated example for the mean value, the standard deviation and
the coefficient of variation of 50-year maximum values is shown in appendix Table 6.6.1. The
difference between U 500 and U 0 is 4m/s and the coefficient of variation is about 0.08 to 0.11 in
most areas other than the Okinawa Islands.
Appendix Table 6.6.1 Mean value, standard deviation and coefficient of variation for 50-year
maximum values of wind speed
50-year maximum value
coefficient of
city U 0 (m/s) U 500 (m/s) standard deviation
mean (m/s) variation
(m/s)
Sapporo 30.5 34.5 30.2 3.2 0.11
Aomori 31.0 35.0 30.7 3.2 0.10
Sendai 30.5 34.5 30.2 3.2 0.11
Niigata 37.0 41.0 36.7 3.2 0.09
Tokyo 36.0 40.0 35.7 3.2 0.09
Nagoya 32.5 36.5 32.2 3.2 0.10
Osaka 34.5 38.5 34.2 3.2 0.09
Hiroshima 30.0 34.0 29.7 3.2 0.11
Kochi 39.0 43.0 38.7 3.2 0.08
Fukuoka 33.5 37.5 33.2 3.2 0.10
Kagoshima 42.0 46.0 41.7 3.2 0.08
speed profile factor EH deviates 25% at H = 5 m, 15% at H = 100 m and 10% at H = 200 m, and
the coefficients of variation can be estimated as half their values as follows;
0.13 at H = 5 m
0.08 at H = 100 m
0.05 at H = 200 m
(5) Wind force coefficient, wind pressure coefficient
The case for a rectangular plan building is introduced here as an example for wind force coefficients
of horizontal wind load for structural frames of a building whose reference height is greater than 45m.
Wind tunnel test results obtained from reference papers and so on vary with aspect ratio and side ratio
of the building, and the wind force coefficients shown in Table A6.8 are their mean. For the vertical
distribution of wind force coefficient, test values at heights from 0.2 H to 0.9 H are mostly within
the range of 10% of these recommendation values. For the overturning moment coefficient at the
building base, most test results are within the range of 20% of these recommendation values. If a
building has a corner recess, the wind force coefficient generally takes a safe value. Therefore, if these
recommendations are adopted for such a building, its design is generally safe.
Horizontal wind force coefficients for structural frames of a rectangular plan building whose
reference height is 45m or less are influenced not only by building shape but also by many other
parameters such as wind characteristics. The values shown in Table A6.9(1) are simplified so that they
represent the results under various conditions. Therefore, their values are 10-30% greater than actual
ones, and 50% greater in some parts. They exceed 30% in part Lb when the roof slope is 30 or less,
but about 10-20% in parts WU and La . Furthermore, they may exceed 30% in part RLb when the
roof slope is less than 30 but about 10-20% in part RU on negative pressure parts and positive
pressure parts.
For the external pressure coefficient C pe , to calculate the roof wind load on structural frames
around the leading edge of the eave, for example, for B / H 6 and D / H > 1 , the spatial mean
value of the test results deviates within the range of 30% of these recommendation values of -1.0.
The positive and negative peak external pressure coefficients of the roof wind load for
components/claddings are determined from the maximum and minimum peak external pressures on
each part of the building for all wind directions. These values vary with wind profile, wind tunnel test
condition (such as sampling frequency, measuring position), side ratio and size reduction rate of the
test model and so on. Their coefficients of variation are about 0.2.
(6) Gust effect factor GD
The parameters that influence the gust effect factor GD of the horizontal wind load for structural
frames, excluding the height and the width of the building, are the natural frequency f D of the first
translational mode in the along-wind direction, the critical damping ratio D of the first translational
mode in along-wind direction, the design wind speed U H , turbulence scale LH , turbulence intensity
I H and the exponent of the power law in the wind speed profile. The influence of these
parameters on the gust effect factor varies with the flat terrain subcategory, the assumed building
C6-76 Recommendations for Loads on Buildings
shape and so on. Here, the reference height H = 80 m, the width B = 40 m, the natural frequency for
the first translational mode f D = 0.5 Hz, the critical damping ratio for the first translational mode
D = 2 %, the basic wind speed U 0 = 39 m/s and the flat terrain subcategory III are assumed. The
increase of the gust effect factor GD when each parameter is increased by 1% individually is
shown in appendix Table 6.6.2.
Appendix Table 6.6.2 Increase of gust effect factor GD when value of each parameter is
increased by 1% individually
parameter increase of gust effect factor GD
natural frequency f D 0.29%
critical damping ratio D 0.16%
design wind speed U H 0.34%
turbulence intensity I H 0.55%
turbulence scale LH 0.07%
exponent of power law 0.02%
For example, if the coefficient of variation of the critical damping ratio is 20%, that for the gust
effect factor caused by the critical damping ratio is estimated as 0.160.20=0.032.
Although the gust effect factor of the roof wind load for structural frames is influenced by various
parameters, the difference between the maximum loading effect for roof structural frames obtained
from these recommendations and the wind tunnel test results is within 15% and mostly around 30%.
(7) Natural frequency and critical damping ratio of first mode
Damping in Buildings7) proposed an estimation formula for the natural frequency and the critical
damping ratio of the first mode. When the dispersion of the values calculated from these proposed
formula is evaluated as the coefficient of variation of the difference between these recommendation
values and the field measurement values, the coefficient of variation of the natural frequency for the
first mode is about 0.1-0.5 for reinforced concrete structures, steel reinforced concrete structures and
steel structures, and that of the critical damping ratio for the first mode is about 0.2 for reinforced
concrete structure and steel reinforced concrete structures, about 0.3 for steel structures.
(8) Turbulence intensity I H
Fig.A6.1.17 compares the turbulence intensities of these recommendations and field measurements.
The coefficient of variation of the difference between these values can be estimated as about 0.2 for
flat terrain subcategory III where many field measurement data have been obtained.
(9) Turbulence scale LH
Fig.A6.1.21 compares the turbulence scales of these recommendations and field measurements. The
coefficient of variation of the difference between these values can be estimated as about 0.5.
CHAPTER 6 WIND LOADS C6-77
Horizontal wind load for structural frames: VWD = V2 + 4VU2H + VC2D + VG2D (Appendix 6.6.2)
where
VWD : coefficient of variation of horizontal wind load for structural frames WD
VWC : coefficient of variation of wind load for components/cladding WC
V : coefficient of variation of air density
VU H : coefficient of variation of design wind speed U H
VCD : coefficient of variation of wind force coefficient C D
VG D : coefficient of variation of gust effect factor GD
VC : coefficient of variation of peak wind force coefficient CC
C
When a building with reference height H = 80 m, width B = 40 m, natural frequency for first
translational mode f D = 0.5 Hz, and critical damping ratio for first translational mode D = 2 % is
constructed in a region of flat terrain subcategory III in each city of appendix Table 6.6.1, the
coefficient of variation VWD can be estimated as around 0.3 to 0.33 for wind load on structural frames
and the coefficient of variation VWC can be estimated as around 0.32 to 0.35 for wind load on
components/claddings.
References
Observation of wind speed profiles in Tokyo city area using doppler soda, Proceedings of 16th
National Symposium on Wind Engineering, pp.13-18, 2000 (in Japanese)
23) Kondo, K., Kawai, H., Kawaguchi, A: Topographic multipliers for mean and fluctuating wind
velocities around up-slope cliffs, Summaries of Technical Papers of Annual Meeting, Architectural
Institute of Japan, pp.105-106, 2001 (in Japanese)
24) Kawai, H., Kondo, K: Topographic multipliers around micro-topography, Summaries of Technical
Papers of Annual Meeting, Architectural Institute of Japan, pp.103-104, 2003 (in Japanese)
25) Tsuchiya, M., Kondo, K., Kawai, H., Sanada, S: Effect of micro-topography on design wind
velocity, Summaries of Technical Papers of Annual Meeting, Architectural Institute of Japan,
pp.119-120, 1999 (in Japanese)
26) Meng, Y., Hibi, K: An experimental study of turbulent boundary layer over steep hills, Proceedings
of 15th National Symposium on Wind Engineering, pp.61-66, 1998
27) Goto, S., Suda, K. Miyashita, K: Profiles of turbulence intensity on the basis of full scale
measurements, Summaries of Technical Papers of Annual Meeting Architectural Institute of Japan
B-1, pp.111-112, 2002 (in Japanese)
28) Eurocode ENV 1991-2-4: 1997
29) Kamei, I. and Maruta, E: Wind Tunnel Test for evaluating wind pressure coefficients of buildings
with a gable roof -Part 2-, Summaries of Technical Papers of Annual Meeting Architectural
Institute of Japan, Structures, 1981, pp.1041-1042 (in Japanese)
30) Kanda, M. and Maruta; E: Study on design wind pressure coefficient of low rise buildings with a
flat roof or a gable roof -Part 3- Averaging wind pressure coefficient and wind direction,
Summaries of Technical Papers of Annual Meeting Architectural Institute of Japan, Structures ,
1992, pp.119-120 (in Japanese)
31) Ueda, H., Tamura, Y. and Fujii; K: Effect of turbulence of approaching wind on mean wind
pressures acting on flat roofs -Part 1- Study on characteristics of wind pressure acting on flat roofs,
Journal of Structural and Construction Engineering, No. 425, pp.91-99, 1991 (in Japanese)
32) Ueda, H., Hagura, H. and Oda, H: Characteristics of stress generated by wind pressures and wind
loads acting on stiff two-dimensional arches supporting a barrel roof, Journal of Structural and
Construction Engineering, AIJ, No. 496pp.29-35, 1997 (in Japanese)
33) Kikuchi, T., Ueda, H. and Hibi, K: Characteristics of wind pressures acting on the curved roofs,
Summaries of Technical Papers of Annual Meeting Architectural Institute of Japan, Structures ,
2003, pp.147-148 (in Japanese)
34) Nogichi, M., Uematsu, Y: Design wind pressure coefficients for spherical domes, Journal of Wind
Engineering, JAWE, No.95, 2003, pp.177-178 (in Japanese)
35) Chino, N. and Okada, H: Wind-induced internal pressures in buildings, Part 1 mean internal
pressures, Journal of Wind Engineering, JAWE, No.56, 1993, pp.11-20 (in Japanese)
36) Schewe, G: On the force fluctuations acting on a circular cylinder in crossflow from subcritical up
to transcritical Rynolds numbers, Journal of Fluid Mechanics, Vol.133, pp.265-285, 1983
C6-80 Recommendations for Loads on Buildings
37) Uematsu, Y., Yamada, M: Aerodynamic forces on circular cylinders of finite height, Journal of
Wind Engineering and Industrial Aerodynamics, Vol.51, pp.249-265, 1994
38) Uematsu, Y: Design wind force coefficients for free-standing canopy roofsJournal of Wind
Engineering, JAWE, No.95, 2003, pp.181-182 (in Japanese)
39) JEC-127, The Institute of Electrical Engineers of Japan 1979 (in Japanese)
40) Nishimura, H: Aerodynamic Characteristics of Shapes yielding Stagnated Flow, GBRC, No.106,
2002, pp.19-24 (in Japanese)
41) Nishimura, H, Asami, Y, Takamori K. and Okeya M: A wind tunnel study of fluctuating pressures
on buildings Part4 Pressure coefficient and drag coefficient, Summaries of Technical Papers of
Annual Meeting Architectural Institute of JAPAN, Structures I, 1992, pp.57-58 (in Japanese)
42) Katagiri, J, Kawabata, S, Niihori, Y, and Nakamura, O: Pressure Characteristics of Rectangular
cylinders with Cut Corner, Summaries of Technical Papers of Annual Meeting Architectural
Institute of Japan, Structures , 1992, pp.47-48 (in Japanese)
43) Ohtake, K: Peak wind pressure coefficients for cladding of a tall building - Part 1 Characteristics
of peak pressure, Summaries of Technical Papers of Annual Meeting Architectural Institute of
Japan, Structures , 2000, pp.193-194 (in Japanese)
44) Ohtake, : Peak wind pressure coefficients for cladding of a tall building - Part 2 Stretch of Peak
Wind Pressure, Summaries of Technical Papers of Annual Meeting Architectural Institute of Japan,
Structures , 2001, pp.143-144 (in Japanese)
45) Maruta, E., Ueda, H. and Kanda, M: Local wind pressure on gable roofs, Summaries of Technical
Papers of Annual Meeting College of Industrial Technology Nihon University, 1991, pp.33-36 (in
Japanese)
46). Uematsu, Y: Peak gust pressures acting on low-rise building roofs, Proceedings of the 8th East
Asia-Pacific Conference on Structural Engineering and Construction, Singapore, 2001
47) Uematsu, Y, Yamada, M: Fluctuating wind pressures on buildings and structures of circular
cross-section at high Reynolds numbers, Proceedings of the 9th International Conference on Wind
Engineering, New Delhi, 1995, pp.358-368
48) Okada, H. and Chino, N: Wind-induced internal pressures in buildings, Part 2 gust response factor
of internal pressure, Journal of Wind Engineering, JAWE, No.58, 1994, pp.43-53 (in Japanese)
49) Chino, N, Okada, H. and Kikitsu, H: On a new way to estimate wind load on cladding considering
correlation between external and internal pressures, Summaries of Technical Papers of Annual
Meeting Architectural Institute of Japan, Structures , 2000, pp.197-198 (in Japanese)
50). International Standard ISO4354, 1997
51) Asami, Y, Nakamura, O: A proposal for alongwind load model, Summaries of Technical Papers of
Annual Meeting, AIJ, Structures I, pp.195-196, 2002 (in Japanese)
52) Asami, Y, Kondo, K, Hibi, K: Experimental research of aerodynamic force on rectangular prism,
Journal of Wind Engineering, JAWE, 91, pp.83-88, 2002 (in Japanese)
53) Holmes, J. D: Effective static load distributions in wind engineering, Journal of Wind Engineering
CHAPTER 6 WIND LOADS C6-81