Fuel tanks, 600-2500 kw

Dual wall, sub-base

Description Features
Cummins Power Generation atmospheric dual wall diesel fuel UL142 Listed - Secondary containment generator
tanks are rectangular steel tanks with a sealed, separately sub-base tank meets UL requirements.
vented, integral fuel containment basin, with drain.
Designed to meet requirements of NFPA -
They are UL Listed as secondary containment generator
NFPA 30, NFPA 37 and NFPA 110.
base tanks and meet the requirements of UL 142. Inner and
outer tanks are pressurized at 3 psi and leak checked to Emergency pressure relief vent cap - Meets or
ensure integrity of weld seams per UL 142 standards prior to exceeds UL requirements - insures adequate venting and
shipment. pressure relief for inner and outer tanks under extreme
Tanks are constructed of heavy gauge steel and include a temperature and emergency conditions.
reinforced steel box channel for generator support. Full Atmospheric vent cap - Accommodates normal
height gussets are provided at generator set mounting holes. venting (oversized 2" vent is raised above the fuel fill).
Tanks are load rated at 5,000 lbs per generator set mounting
point. The design has been tested extensively under Raised fuel fill - Includes lockable flip top to prevent
conditions far in excess of normal use to ensure that it can tampering and/or fuel contamination.
safely support the full weight of the generator set.
Fuel level gauge - Provides direct reading and is top
All tanks are pressure washed with an iron phosphate mounted.
solution and then finished with an acrylic primer and black
enamel paint. The interior is coated with a solvent-based Low fuel level switch - Annunciates a 50% low fuel
rust preventative. level condition at genset control panel and/or optional
remote annunciator.
Tanks with local code approvals share the same construction
features of standard sub-base tanks and are configured with Leak detection switch - Side mounted, annunciates
additional options necessary to meet requirements of city of a contained primary tank fuel leak at genset control
Chicago Department of Inspectional Services, Florida and/or optional remote annunciator.
Department of Environmental Protection (FDEP) or city of
Los Angeles Bureau of Fire Prevention. Modular tank design - Genset support and mounting
design accepts multiple Cummins Power Generation
Reference instruction sheet - G478 for installation gensets within designated genset groupings.
Note: Pre-drilled mounting pads accept Cummins Power Generation
accessories spring vibration isolators (0402-0220, 0402-0222, 0402-
Enclosure compatible - Accepts drop-over weather
0234, 0402-0427, 0402-0431, 0402-0750-01) between tank and genset protective and sound attenuated enclosures.
but will not accept 0402-0690 or 0402-0691 series isolators.
Integral tank lift lugs - Enables a crane to lift an
empty tank, mounted genset and enclosure.
Tank top mounting bracket - Provides mounting
for (optional) pump and control for day tank operation.
Removable end panel/channel - Provides access
to a full width, electrical stub-up area.
2009 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation and Cummins are registered trademarks of Cummins
Inc. Our energy working for you. is a trademark of Cummins Power Generation Inc. Specifications are subject to change without notice.
S-1395d (7/09) Page 1 of 4
Specifications
Kit Full load
159-1512-xx operating Tank Tank dimensions Tank
hours capacity* Length Width Height weight
Model Std Chicago LA FL (60 Hz) Gal (L) In (mm) In (mm) In (mm) Lb (Kg)
DFGB -21 -41 -61 -81 12.4 550 (2082) 200 (5080) 90 (2286) 15 (381) 3875 (1758)
-24 -44 -64 -84 24.9 1100 (4164) 200 (5080) 90 (2286) 27 (686) 4875 (2211)
DFHA -28 -48 -68 -88 13.7 750 (2839) 200 (5080) 90 (2286) 19 (483) 4200 (1905)
-31 -51 -71 -91 27.4 1500 (5678) 200 (5080) 90 (2286) 36 (914) 5650 (2563)
DFHB -28 -48 -68 -88 13.0 750 (2839) 200 (5080) 90 (2286) 19 (483) 4200 (1905)
-31 -51 -71 -91 26.0 1500 (5678) 200 (5080) 90 (2286) 36 (914) 5650 (2563)
DFHC -28 -48 -68 -88 12.5 750 (2839) 200 (5080) 90 (2286) 19 (483) 4200 (1905)
-31 -51 -71 -91 24.9 1500 (5678) 200 (5080) 90 (2286) 36 (914) 5650 (2563)
DFHD -29 -49 -69 -89 12.3 850 (3218) 200 (5080) 90 (2286) 22 (559) 4450 (2019)
-32 -52 -72 -92 24.5 1700 (6435) 220 (5588) 90 (2286) 36 (914) 6000 (2722)
DFLB -33 -53 -73 -93 13.0 1000 (3785) 240 (6096) 112 (2845) 16 (406) 5650 (2563)
-35 -55 -75 -95 25.9 2000 (7571) 240 (6096) 112 (2845) 29 (737) 7075 (3209)
DFLC -33 -53 -73 -93 12.4 1000 (3785) 240 (6096) 112 (2845) 16 (406) 5650 (2563)
-35 -55 -75 -95 24.8 2000 (7571) 240 (6096) 112 (2845) 29 (737) 7075 (3209)
DFLE -34 -54 -74 -94 12.1 1250 (4732) 240 (6096) 112 (2845) 19 (483) 6000 (2722)
-37 -56 -76 -96 24.1 2500 (9464) 240 (6096) 112 (2845) 36 (914) 7850 (3561)
DQCA NA NA NA NA
DQCB NA NA NA NA
DQCC NA NA NA NA
DQFAA 27 47 67 87 13.8 550 (2082) 200 (5080) 90 (2286) 15 (381) 3875 (1758)
32 52 72 92 42.7 1700 (6435) 200 (5080) 90 (2286) 36 (914) 6000 (2272)
DQFAB 27 47 67 87 12.7 550 (2082) 200 (5080) 90 (2286) 15 (381) 3875 (1758)
32 52 72 92 39.4 1700 (6435) 200 (5080) 90 (2286) 36 (914) 6000 (2272)
DQFAC 27 47 67 87 11.6 550 (2082) 200 (5080) 90 (2286) 15 (381) 3875 (1758)
32 52 72 92 35.8 1700 (6435) 200 (5080) 90 (2286) 36 (914) 6000 (2272)
DQFAD 27 47 67 87 10.1 550 (2082) 200 (5080) 90 (2286) 15 (381) 3875 (1758)
32 52 72 92 31.4 1700 (6435) 200 (5080) 90 (2286) 36 (914) 6000 (2272)
DQGAA 33 53 73 93 13.7 1000 (3785) 240 (6096) 112 (2845) 16 (406) 5650 (2563)
36 56 76 96 34.2 2500 (9464) 240 (6096) 112 (2845) 36 (914) 7850 (3561)
DQGAB 33 53 73 93 12.0 1000 (3785) 240 (6096) 112 (2845) 16 (406) 5650 (2563)
36 56 76 96 30.0 2500 (9464) 240 (6096) 112 (2845) 36 (914) 7850 (3561)
DQKAA NA NA NA NA
DQKAB NA NA NA NA
DQKB -37 -57 -77 -97 12.6 1500 (5678) 260 (6604) 120 (3048) 19 (483) 6450 (2926)
-39 -59 -79 -99 25.2 3000 (11356) 260 (6604) 120 (3048) 36 (914) 8450 (3833)
DQKC -38 -58 -78 -98 12.4 1700 (6435) 260 (6604) 120 (3048) 22 (559) 6800 (3084)
-40 -60 -80 -10 24.8 3400 (12870) 285 (7239) 120 (3048) 36 (914) 9075 (4116)
DQKH NA NA NA NA
DQLC NA NA NA NA
* Fuel Capacity listed is usable amount. Initial fill will be approximately 20 gallon more than listed.

Our energy working for you.


www.cumminspower.com
2009 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation and Cummins are registered trademarks of Cummins
Inc. Our energy working for you. is a trademark of Cummins Power Generation Inc. Specifications are subject to change without notice.
S-1395d (7/09) Page 2 of 4
Additional unique features by local
approval
Chicago Florida
City of Chicago approval - Approved by the Florida Department of Environmental Protection
Department of Inspectional Services - Plan No. 0451. approval - Tag No. 2-94-1 for a sub base tank.
Low fuel level switch (95% high and 50%) - Wired to a Tank design meets seismic requirements - When
terminal block for local/remote annunciation within an appropriate vibration isolators are installed beneath the
electrical junction box. tank.
Leak detection switch (top-mount) - Wired to a terminal
block for local/remote annunciation within an electrical Options
junction box.
Fuel transfer control and pump kit - Enables field
No bottom fittings - Meets requirement that all tank
upgrade of standard tank to a day tank.
fittings are to be located above the fuel level of the
tank. Outside venting - Normal atmospheric and emergency
vents must be exhausted out of a building (indoor
Los Angeles applications) at a safe location by a qualified service
Tank approval indicated - Tag No. 2-94-1 for a technician (Florida and Los Angeles approval only).
sub-base tank. Additional options - required when the tank fill location
Tank design meets seismic requirements - When does not allow the fuel level gauge to be supervised
appropriate vibration isolators are installed beneath the (Florida and Los Angeles approval only).
tank.

Our energy working for you.


www.cumminspower.com
2009 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation and Cummins are registered trademarks of Cummins
Inc. Our energy working for you. is a trademark of Cummins Power Generation Inc. Specifications are subject to change without notice.
S-1395d (7/09) Page 3 of 4
Standards and certifications/codes
UL 142 Listed - Cummins Power Generation
dual wall sub-base tanks are UL Listed (File
MH17470) and constructed in accordance with
Underwriters Laboratories Standard UL 142
steel aboveground tanks for flammable and
combustible liquids, as a secondary
containment generator base tank

NFPA - Cummins Power Generation tanks are


built in accordance with all applicable NFPA
codes:
- NFPA 30 - Flammable and Combustible
Liquids code
- NFPA 37 - Standard for Installation and use
of Stationary Combustible Engine and Gas
Turbines
- NFPA 110 - Standard for Emergency and
Standby Power Systems

Chicago Optional city of Chicago local


Local approval - Meets the local code required for
Approval approval by the Chicago Department of
Inspectional Services - Plan No. 0451

L.A.
Optional local approval - Meets the local
Local code required for approval by the city of Los
Approval Angeles Bureau of Fire Prevention

Florida
Optional local approval - Meets the local
Local code required for approval by the Florida
Approval Department of Environmental Protection

ISO9001 - This product was designed and


manufactured in facilities certified to ISO9001

Americas Europe, CIS, Middle East and Africa Asia Pacific


1400 73rd Avenue N.E. Manston Park Columbus Ave. 10 Toh Guan Road #07-01
Minneapolis, MN 55432 USA Manston Ramsgate TT International Tradepark
Phone: 763 574 5000 Kent CT 12 5BF United Kingdom Singapore 608838
Fax: 763 574 5298 Phone 44 1843 255000 Phone 65 6417 2388
Fax 44 1843 255902 Fax 65 6417 2399

Warning: Back feed to a utility system can cause electrocution and/or property damage. Do not connect generator sets to any building
electrical system except through an approved device or after building main switch is open.
Warning: For professional use only. Must be installed by a qualified service technician. Improper installation presents hazards of electrical
shock and improper operation, resulting in severe personal injury and/or property damage.

Our energy working for you.


www.cumminspower.com
2009 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation and Cummins are registered trademarks of Cummins
Inc. Our energy working for you. is a trademark of Cummins Power Generation Inc. Specifications are subject to change without notice.
S-1395d (7/09) Page 4 of 4