Cooling Water Temperature to Generated Power Efficiency

Since 1st of August, weather still hot, but the generated power efficiency (EFF.) value
is slightly increase which compare with July, after some analysis by collected data, we
can found that the under the same environment temperature, the cooling water

temperature was 1 degree lower, please refer to Figure 1.

39
June
38 July
August
37
Cooling Water Temperature

36

35

34

33

32

31

30

29
20 22 24 26 28 30 32 34
Environment Temperature

Figure 1

Furthermore, we looking into more detail on the relation between EFF. And cooling
water temperature, we can found that the lower temperature of cooling water, the
higher EFF. we got, please refer to Figure 2., under the same environment
temperature, the green spot(August) are the highest compare with June and July,
(some purple spots at top is because low environment temperature.
After compare the parameter from collected data, we can found that the major root
cause might be from cooling water flow and pressure, please refer to Figure 3.
200
June
July
195
August

190

185
EFF.

180

175

170

165
29 30 31 32 33 34 35 36 37 38 39
Cooling Water Temperature

Figure 2

Figure 3
Test Plan
To verify the cooling water temperature between cooling water flow and pressure.
Furthermore, check the efficiency in different cooling water temperature.

Cooling water flow 220T/H 250T/H 300T/H


Cooling water pressure
Cooling water temperature
EFF.