TESTING AND INSPECTION INTERVALS FOR ELECTRICAL EQUIPMENT (EXTRACTED FROM AS3760 - 2003)
Interval between inspection and tests
Class of equipment Residual Current Devices (RCDs) Operating time Type of Push-button test and push-button environment Class I Class II by user test and/or equipment (protectively (double earthed) insulated) Cord sets Portable Fixed Portable Fixed and (a) power (b) (c) (d) (e) (f) (g) boards (h) 1 Factories, workshops, places of Daily, or work or repair, before every 12 manufacturing, 6 months 12 months use, 6 months 12 months 6 months months assembly, whichever is maintenance or the longer fabrication 2 Environment where the equipment or supply flexible cord is subject to flexing in 12 12 months 12 months 3 months 6 months 12 months 12 months normal use OR is months open to abuse OR is in a hostile environment 3 Environment where the equipment or supply cord is NOT subject to flexing in 5 years 5 years 3 months 6 months 2 years 2 years 5 years normal use and is NOT open to abuse and is NOT in a hostile environment 4 Residential type areas of hotels, residential institutions, motels, 2 years 2 years 6 months 6 months 2 years 2years 2 years boarding houses, halls, hostels accommodation houses, and the like 5 Equipment used for commercial 6 months 12 months 3 months N/A 12 months N/A 12 months cleaning 6 Hire Equipment: Including push-button Prior to Prior to hire test by hirer prior to N/A N/A hire Inspection hire 12 3 months N/A 3 months 3 months Test and tag months 7 Repaired, serviced After repair or service which could affect electrical safety, or on reintroduction to and second-hand service. equipment