Beruflich Dokumente
Kultur Dokumente
TABLE A.2
Areas of groups of standard bars, in 2
Bar No.
Number of Bars
Inch-
Pound Sl 1 2 3 4 5 6 7 8 9 10 11 12
4 13 0.20 0.40 0.60 ,.. 0.80 1.00 1.20 1.40 1.60 1.80 2.00 2.20 2.40
5 16 0.31 0.62 0.93 1.24 1.55 1.86 2.17 2.48 2.79 3.10 3.41 3.72
6 19 0.44 0.88 1.32 1.76 2.20 2.64 3.08 3.52 3.96 4.40 4.84 5.28
7 22 0.60 1.20 1.80 2.40 3.00 3.60 4.20 4.80 5.40 6.00 6.60 7.20
8 25 0.79 1.58 2.37 3.16 3.95 4.74 5.53 6.32 7.11 7.90 8.69 9.48
9 29 1.00 2.00 3.00 4.00 5.00 6.00 7.00 8.00 9.00 10.00 11.00 12.00
10 32 1.27 2.54 3.81 5.08 6.35 7.62 8.89 10.16 11.43 12.70 13.97 15.24
11 36 1.56 3.12 4.68 6.24 7.80 9.36 10.92 12.48 14.04 15.60 17.16 18.72
14 43 2.25 4.50 6.75 9.00 11.25 13.50 15.75 18.00 20.25 22.50 24.75 27.00
18 57 4.00 8.00 12.00 16.00 20.00 24.00 28.00 32.00 36.00 40.00 44.00 48.00
TABLE A.l
Areas of bars in slabs, in 2/ft
Bar No.
Inch-
Spacing, Pound: 3 4 5 6 7 8 9 10 11
in. Sl: 10 13 16 19 22 25 29 32 36
3 0.44 0.78 1.23 1.77 2.40 3.14 4.00 5.06 6.25
3! 0.38 0.67 1.05 1.51 2.06 2.69 3.43 4.34 5.36
4 0.33 0.59 0.92 1.32 1.80 2.36 3.00 3.80 4.68
412 0.29 0.52 0.82 1.18 1.60 2.09 2.67 3.37 4.17
5 0.26 0.47 0.74 1.06 1.44 1.88 2.40 3.04 3.75
s! 0.24 0.43 0.67 0.96 1.31 1.71 2.18 2.76 3.41
6 0.22 0.39 0.61 0.88 1.20 1.57 2.00 2.53 3.12
6! 0.20 0.36 0.57 0.82 1.11 1.45 1.85 2.34 2.89
7 0.19 0.34 0.53 0.76 1.03 1.35 1.71 2.17 2.68
7! 0.18 0.31 0.49 0.71 0.96 1.26 1.60 2.02 2.50
8 0.17 0.29 0.46 0.66 0.90 1.18 1.50 1.89 2.34
9 0.15 0.26 0.41 0.59 0.80 1.05 1.33 1.69 2.08
10 0.13 0.24 0.37 0.53 0.72 0.94 1.20 1.52 1.87
12 0.11 0.20 0.31 0.44 0.60 0.78 1.00 1.27 1.56
Department of Civil Engineering, N-W.F.P UET Peshawar Design of Reinforced Concrete Components of a House
Appendix A
Tables of moment coefficients in slab:
NOTE: Horizontal sides of the figure represent longer side while vertical side represents
shorter side of the slab.
Table A1: Coefficients (Ca, neg) for negative moment in slab along longer direction
m Case1 Case2 Case3 Case4 Case5 Case6 Case7 Case8 Case9
0.50 0.000 0.086 0.000 0.094 0.090 0.097 0.000 0.089 0.088
0.55 0.000 0.084 0.000 0.092 0.089 0.096 0.000 0.085 0.086
0.60 0.000 0.081 0.000 0.089 0.088 0.095 0.000 0.080 0.085
0.65 0.000 0.077 0.000 0.085 0.087 0.093 0.000 0.074 0.083
0.70 0.000 0.074 0.000 0.081 0.086 0.091 0.000 0.068 0.081
0.75 0.000 0.069 0.000 0.076 0.085 0.088 0.000 0.061 0.078
0.80 0.000 0.065 0.000 0.071 0.083 0.086 0.000 0.055 0.075
0.85 0.000 0.060 0.000 0.066 0.082 0.083 0.000 0.049 0.072
0.90 0.000 0.055 0.000 0.060 0.080 0.079 0.000 0.043 0.068
0.95 0.000 0.050 0.000 0.055 0.079 0.075 0.000 0.038 0.065
1.00 0.000 0.045 0.000 0.050 0.075 0.071 0.000 0.033 0.061
Table A2: Coefficients (Cb, neg) for negative moment in slab along shorter direction
m Case1 Case2 Case3 Case4 Case5 Case6 Case7 Case8 Case9
0.50 0.000 0.006 0.022 0.006 0.000 0.000 0.014 0.010 0.003
0.55 0.000 0.007 0.028 0.008 0.000 0.000 0.019 0.014 0.005
0.60 0.000 0.010 0.035 0.011 0.000 0.000 0.024 0.018 0.006
0.65 0.000 0.014 0.043 0.015 0.000 0.000 0.031 0.024 0.008
0.70 0.000 0.017 0.050 0.019 0.000 0.000 0.038 0.029 0.011
0.75 0.000 0.022 0.056 0.024 0.000 0.000 0.044 0.036 0.014
0.80 0.000 0.027 0.061 0.029 0.000 0.000 0.051 0.041 0.017
0.85 0.000 0.031 0.065 0.034 0.000 0.000 0.057 0.046 0.021
0.90 0.000 0.037 0.070 0.040 0.000 0.000 0.062 0.052 0.025
0.95 0.000 0.041 0.072 0.045 0.000 0.000 0.067 0.056 0.029
1.00 0.000 0.045 0.076 0.050 0.000 0.000 0.071 0.061 0.033
Table A3: Coefficients (Ca,pos, dl) for dead load positive moment in slab along longer
direction
m Case1 Case2 Case3 Case4 Case5 Case6 Case7 Case8 Case9
0.50 0.095 0.037 0.080 0.059 0.039 0.061 0.089 0.056 0.023
0.55 0.088 0.035 0.071 0.056 0.038 0.058 0.081 0.052 0.024
0.60 0.081 0.034 0.062 0.053 0.037 0.056 0.073 0.048 0.026
0.65 0.074 0.032 0.054 0.050 0.036 0.054 0.065 0.044 0.028
0.70 0.068 0.030 0.046 0.046 0.035 0.051 0.058 0.040 0.029
0.75 0.061 0.028 0.040 0.043 0.033 0.048 0.051 0.036 0.031
0.80 0.056 0.026 0.034 0.039 0.032 0.045 0.045 0.032 0.029
0.85 0.050 0.024 0.029 0.036 0.310 0.042 0.004 0.029 0.028
0.90 0.045 0.022 0.025 0.033 0.029 0.039 0.035 0.025 0.026
0.95 0.040 0.020 0.021 0.030 0.028 0.036 0.031 0.022 0.024
1.00 0.036 0.018 0.018 0.027 0.027 0.033 0.027 0.020 0.023
Table A4: Coefficients (Cb, dl) for dead load positive moment in slab along shorter direction
m Case1 Case2 Case3 Case4 Case5 Case6 Case7 Case8 Case9
0.50 0.006 0.002 0.007 0.004 0.001 0.003 0.007 0.004 0.002
0.55 0.008 0.003 0.009 0.005 0.002 0.004 0.009 0.005 0.003
0.60 0.010 0.004 0.011 0.007 0.003 0.006 0.012 0.007 0.004
0.65 0.013 0.006 0.014 0.009 0.004 0.007 0.014 0.009 0.005
0.70 0.016 0.007 0.016 0.011 0.005 0.009 0.017 0.011 0.006
0.75 0.019 0.009 0.018 0.013 0.007 0.013 0.020 0.013 0.007
0.80 0.023 0.011 0.020 0.016 0.009 0.015 0.022 0.015 0.010
0.85 0.026 0.012 0.022 0.019 0.011 0.017 0.025 0.017 0.013
0.90 0.029 0.014 0.024 0.022 0.013 0.021 0.028 0.019 0.015
0.95 0.033 0.016 0.025 0.024 0.015 0.024 0.031 0.021 0.017
1.00 0.036 0.018 0.027 0.027 0.018 0.027 0.033 0.023 0.020
Table A5: Coefficients (Ca, ll) for live load positive moment in slab along longer direction
m Case1 Case2 Case3 Case4 Case5 Case6 Case7 Case8 Case9
0.50 0.095 0.066 0.088 0.077 0.067 0.078 0.092 0.076 0.067
0.55 0.088 0.062 0.080 0.072 0.063 0.073 0.085 0.070 0.063
0.60 0.081 0.058 0.071 0.067 0.059 0.068 0.077 0.065 0.059
0.65 0.074 0.053 0.064 0.062 0.055 0.064 0.070 0.059 0.054
0.70 0.068 0.049 0.057 0.057 0.051 0.060 0.063 0.054 0.050
0.75 0.061 0.045 0.051 0.052 0.047 0.055 0.056 0.049 0.046
0.80 0.056 0.041 0.045 0.048 0.044 0.051 0.051 0.044 0.042
0.85 0.050 0.037 0.040 0.043 0.041 0.046 0.045 0.040 0.039
0.90 0.045 0.034 0.035 0.039 0.037 0.042 0.040 0.035 0.036
0.95 0.040 0.030 0.031 0.035 0.034 0.038 0.036 0.031 0.032
1.00 0.036 0.027 0.027 0.032 0.032 0.035 0.032 0.028 0.030
Table A6: Coefficients (Cb, ll) for live load positive moment in slab along shorter direction
m Case1 Case2 Case3 Case4 Case5 Case6 Case7 Case8 Case9
0.50 0.006 0.004 0.007 0.005 0.004 0.005 0.007 0.005 0.004
0.55 0.008 0.006 0.009 0.007 0.005 0.006 0.009 0.007 0.006
0.60 0.010 0.007 0.011 0.009 0.007 0.008 0.011 0.009 0.007
0.65 0.013 0.010 0.014 0.011 0.009 0.010 0.014 0.011 0.009
0.70 0.016 0.012 0.016 0.014 0.011 0.013 0.017 0.014 0.011
0.75 0.019 0.014 0.019 0.016 0.013 0.016 0.020 0.016 0.013
0.80 0.023 0.017 0.022 0.020 0.016 0.019 0.023 0.019 0.017
0.85 0.026 0.019 0.024 0.023 0.019 0.022 0.026 0.022 0.020
0.90 0.029 0.022 0.027 0.026 0.021 0.025 0.029 0.024 0.022
0.95 0.033 0.025 0.029 0.029 0.024 0.029 0.032 0.027 0.025
1.00 0.036 0.027 0.032 0.032 0.027 0.032 0.035 0.030 0.028
TABLE 1.1
Minimum uniformly distributed live loads
Live Load, Live Load,
Occupancy or Use psfa Occupancy or Use psfa
Apartments (see residential) Dining rooms and restaurants 100
Access floor systems Dwellings (see residential)
Office use 50 Fire escapes 100
Computer use 100 On single-family dwellings only 40
Armories and drill rooms 150 Garages (passenger cars only) 40
Assembly areas and theaters Trucks and busesh
Fixed seats (fastened to floor) 60 Grandstands (see stadium and arena bleachers)
Lobbies 100 Gymnasiums, main floors and balconiesc 100
Movable seats 100 Hospitals
Platforms (assembly) 100 Operating rooms, laboratories 60
Stage floors 150 Patient rooms 40
Balconies (exterior) 100 Corridors above first floor 80
On one and two-family residences 60 Hotels (see residential)
only, and not exceeding 100 ft 2 Libraries
Bowling alleys, poolrooms, and similar 75 Reading rooms 60
recreational areas Stack roomsd 150
Catwalks for maintenance access 40 Corridors above first floor 80
Corridors Manufacturing
First floor 100 Light 125
Other floors, same as occupancy Heavy 250
served except as indicated Marquees and canopies 75
Dance halls and ballrooms 100 Office buildings
Decks (patio and roof) File and computer rooms shall be designed for
Same as area served, or for the heavier loads based on anticipated occupancy
type of occupancy accommodated Lobbies and first-floor corridors 100
(continued)
Tabulated live loads cannot always be used. The type of occupancy should be
considered and the probable loads computed as accurately as possible. Warehouses for
heavy storage may be designed for loads as high as 500 psf or more; unusually heavy
operations in manufacturing buildings may require an increase in the 250 psf value
specified in Table 1.1; special provisions must be made for all definitely located heavy
concentrated loads.
Live loads for highway bridges are specified by the American Association of
State Highway and Transportation Officials (AASHTO) in its LRFD Bridge Design
Specifications (Ref. 1.3). For railway bridges, the American Railway Engineering and
Maintenance-of-Way Association (AREMA) has published the Manual of Railway
Engineering (Ref. 1.4), which specifies traffic loads.
Environmental loads consist mainly of snow loads, wind pressure and suction,
earthquake loads (i.e., inertia forces caused by earthquake motions), soil pressures on
subsurface portions of structures, loads from possible ponding of rainwater on flat sur-
faces, and forces caused by temperature differentials. Like live loads, environmental
loads at any given time are uncertain in both magnitude and distribution. Reference 1.1
contains much information on environmental loads, which is often modified locally
depending, for instance, on local climatic or seismic conditions.
Figure 1.13, from the 1972 edition of Ref. 1.1, gives snow loads for the
continental United States and is included here for illustration only. The 2005 edition
MATERIALS 57
TABLE 2.4
Summary of minimum ASTM strength requirements
ASTM Minimum Yield Minimum Tensile
Product Specification Designation Strength, psi (MPa) Strength, psi (MPa)
Reinforcing bars A615 Grade 40 40,000 (280) 60,000 (420)
Grade 60 60,000 (420) 90,000 (620)
Grade 75 75,000 (520) 100,000 (690)
A706 Grade 60 60,000 (420) 80,000 (55Q)a
[78,000 (540) maximum]
A996 Grade 40 40,000 (280) 60,000 (420)
Grade 50 50,000 (350) 80,000 (550)
Grade 60 60,000 (420) 90,000 (620)
A1035 Grade 100 100,000 (690) 150,000 (1030)
Deformed bar mats A184 Same as reinforcing bars
Zinc-coated bars A767 Same as reinforcing bars
Epoxy-coated bars A775, A934 Same as reinforcing bars
Stainless-steel barsh A955 Same as reinforcing bars
Wire
Plain A82 70,000 (480) 80,000 (550)
Deformed A496 75,000 (515) 85,000 (585)
Welded wire reinforcement
Plain A185
Wl.2 and larger 65,000 (450) 75,000 (515)
Smaller than Wl.2 56,000 (385) 70,000 (485)
Deformed A497 70,000 (480) 80,000 (550)
Prestressing tendons
Seven-wire strand A416 Grade 250 212,500 (1465) 250,000 ( 1725)
(stress-relieved)
Grade 250 225,000 (1555) 250,000 ( 1725)
(low-relaxation)
Grade 270 229,500 (1580) 270,000 (1860)
(stress-relieved)
Grade 270 243,000 (1675) 270,000 (1860)
(low-relaxation)
Wire A421 Stress-relieved 199,750 (1375) to 235,000 (1620) to
212,500 (1465)< 250,000 (1725)"
Low-relaxation 211,500 (1455) to 235,000 (1620) to
225,000 (1550)C 250,000 (1725)"
Bars A722 Type I (plain) 127,500 (800) 150,000 (1035)
Type II (deformed) 120,000 (825) 150,000 (1035)
Compacted strandb A779 Type 245 241,900 (1480) 247,000 (1700)
Type 260 228,800 (1575) 263,000 (1810)
Type 270 234,900 (1620) 270,000 (1860)
a But not Jess than 1.25 times the actual yield strength.
b Not listed in ACI 318.
c Minimum strength depends on wire size.
Inch-pound Sl
Grade 60 Grade420
(a)
SI Conversion Factors:
Inch-Pound Units to SI Units
Overall Geometry
Spans 1 ft = 0.3048 m
Displacements 1 in. = 25.4 mm
Surface area 1 ft 2 = 0.0929 m2
Volume 1 ft 3 = 0.0283 m3
1 yd3 = 0.765 m3
Structural Properties
Cross-sectional dimensions 1 in. = 25.4 mm
Area 1 in2 = 645.2 mm2
Section modulus 1 in3 = 16.39 X 103 mm3
Moment of inertia 1 in4 = 0.4162 X 106 mm4
Material Properties
Density 1lb/ft 3 = 16.03 kg/m3
Modulus and stress 1 lb/in 2 = 0.006895 MPa
1 kip/in 2 = 6.895 MPa
Loadings
Concentrated loads 11b = 4.448 N
1 kip = 4.448 kN
Density 11b/ft 3 = 0.1571 kN/m3
Linear loads 1 kip/ft = 14.59 kN/m
Surface loads 11b/ft 2 = 0.0479 kN/m2
1 kip/ft 2 = 47.9 kN/m2
Stress and Moments
Stress 1 1b/in2 = 0.006895 MPa
1 kip/in 2 = 6.895 MPa
Moment or torque 1 ft-lb = 1.356 N-m
1 ft-kip = 1.356 kN-m
785
APPENDIX
Design Aids
TABLE A.1
Designations, diameters, areas, and weights of standard bars
Bar No. Cross-Sectional Nominal Weight,
lnch-Pounda Sib Diameter, in. Area, in 2 lb/ft
3 10 ~ =0.375 0.11 0.376
4 13 &= 0.500 0.20 0.668
5 16 i= 0.625 0.31 1.043
6 19 ~ =0.750 0.44 1.502
7 22 ~ =0.875 0.60 2.044
8 25 I =1.000 0.79 2.670
9 29 1~ =1.128' 1.00 3.400
10 32 1~ =1.270' 1.27 4.303
II 36 1~ =1.410' 1.56 5.313
14 43 I~= 1.693' 2.25 7.650
18 57 2i = 2.257' 4.00 13.600
"Based on the number of eighths of an inch included in the nominal diameter of the bars. The nominal
diameter of a deformed bar is equivalent to the diameter of a plain bar having the same weight per foot as the
deformed bar.
hBar number approximates the number of millimeters included in the nominal diameter of the bar. Bars are
marked with this designation.
'Approximate to nearest kin.
751
REINFORCED CONCRETE
Reinforced Concrete Design Fifth Edition
A Fundamental Approach - Fifth Edition
CHAPTER
FLEXURE IN BEAMS
A. J. Clark School of Engineering Department of Civil and Environmental Engineering
5d
By
SPRING 2004 Dr . Ibrahim. Assakkaf
Introduction
If a beam cross section is limited because of
architectural or other considerations, it may
happen that concrete cannot develop the
compression force required to resist the given
bending moment.
In this case, reinforcing steel bars are added
in the compression zone, resulting in a so-
called doubly reinforced beam, that is one
with compression as well as tension
reinforcement (Figure 21)
1
CHAPTER 5d. FLEXURE IN BEAMS Slide No. 2
b
d
As
h (d d ) d
As
Introduction (contd)
The use of compression reinforcement has
decreased markedly with the use of strength
design methods, which account for the full
strength potential of the concrete on the
compressive side of the neutral axis.
However, there are situations in which
compressive reinforcement is used for
reasons other than strength.
2
CHAPTER 5d. FLEXURE IN BEAMS Slide No. 4
Introduction (contd)
It has been found that the inclusion of some
compression steel has the following
advantages:
It will reduce the long-term deflections of members.
It will set a minimum limit on bending loading
It act as stirrup-support bars continuous through
out the beam span
Introduction (contd)
Another reason for placing reinforcement in
the compression zone is that when beams
span more than two supports (continuous
construction), both positive and negative
moments will exist as shown in Figure 23.
In Figure 23, positive moments exist at A and
C; therefore, the main tensile reinforcement
would be placed in the bottom of the beam.
At B, however, a negative moment exists and
the bottom of the beam is in compression.
The tensile reinforcement, therefore, must be
placed near the top of the beam.
3
CHAPTER 5d. FLEXURE IN BEAMS Slide No. 6
Introduction (contd)
w
A C
B
Moment
+ + +
Diagram - -
4
CHAPTER 5d. FLEXURE IN BEAMS Slide No. 8
5
CHAPTER 5d. FLEXURE IN BEAMS Slide No. 10
N.A
d a
Z1 = d Z2 = d d
2
As T1 = As1 f y
s T2 = As 2 f y
Cross Section Strain at Ultimate Concrete-Steel Steel-Steel
Moment Couple Couple
(a) (b) (c) (d)
6
CHAPTER 5d. FLEXURE IN BEAMS Slide No. 12
M n 2 = T2 Z 2 (36)
7
CHAPTER 5d. FLEXURE IN BEAMS Slide No. 14
N.A
d a
Z1 = d Z2 = d d
2
As T1 = As1 f y
s T2 = As 2 f y
Cross Section Strain at Ultimate Concrete-Steel Steel-Steel
Moment Couple Couple
(a) (b) (c) (d)
M n 2 = As f y (d d ) (37)
The strength of the concrete-steel couple is
given by
M n1 = T1Z1 (38)
8
CHAPTER 5d. FLEXURE IN BEAMS Slide No. 16
M n = M n1 + M n 2
(40)
a
= ( As As ) f y d + As f y (d d )
2
9
CHAPTER 5d. FLEXURE IN BEAMS Slide No. 18
10
CHAPTER 5d. FLEXURE IN BEAMS Slide No. 20
11
CHAPTER 5d. FLEXURE IN BEAMS Slide No. 22
Strain-Compatibility Check
For As to yield, the strain s in the
compression steel should be greater than or
equal to the yield strain of reinforcing steel,
which is fy
s = (44)
Es
The strain s can be calculated from similar
triangles. Referring to Figure 24,
c d d (45)
s = 0.003 = 0.0031
c c
d 0.851 f cd
s = 0.0031 = 0.0031 (46)
c ( )df y
For compression steel to yield, the following
condition must be satisfied:
fy fy
s or s
Es 29 106
12
CHAPTER 5d. FLEXURE IN BEAMS Slide No. 24
or
0.851 f cd fy
1-
( - ) f y d 87,000
0.851 f cd fy
1-
( - ) f y d 87,000
or
0.851 f cd fy
1
( - ) f y d 87,000
or
0.851 f cd f y 87,000
( - ) f y d 87,000
13
CHAPTER 5d. FLEXURE IN BEAMS Slide No. 26
87,000
( - ) 0.851 f c d
87,000 f
(47)
f yd y
14
CHAPTER 5d. FLEXURE IN BEAMS Slide No. 28
f s = Es s = 29 106 s
or (48)
0.851 f cd
f s = 29 106 0.0031
( ) f y d
15
CHAPTER 5d. FLEXURE IN BEAMS Slide No. 30
16
CHAPTER 5d. FLEXURE IN BEAMS Slide No. 32
N.A
d a
Z1 = d Z2 = d d
2
As T1 = As1 f y
s T2 = As 2 f y
Cross Section Strain at Ultimate Concrete-Steel Steel-Steel
Moment Couple Couple
(a) (b) (c) (d)
17
CHAPTER 5d. FLEXURE IN BEAMS Slide No. 34
18
CHAPTER 5d. FLEXURE IN BEAMS Slide No. 36
3 f c 200
min = (57)
fy fy
19
CHAPTER 5d. FLEXURE IN BEAMS Slide No. 38
ENCE 454 Assakkaf
Figure 14. Strain Limit Zones and variation of Strength Reduction Factor
20
CHAPTER 5d. FLEXURE IN BEAMS Slide No. 40
ENCE 454 Assakkaf
21
CHAPTER 5d. FLEXURE IN BEAMS Slide No. 42
ENCE 454 Assakkaf
22
CHAPTER 5d. FLEXURE IN BEAMS Slide No. 44
Example 11 (contd)
Determine the values for As and As:
From Table 6,
As = area of 2 #10 = 2.54 in 2
As = area of 6 #9 = 6.0 in 2
23
CHAPTER 5d. FLEXURE IN BEAMS Slide No. 46
Example 11 (contd)
Table 6. Areas of Multiple of Reinforcing Bars (in2)
Number Bar number
of bars #3 #4 $5 #6 #7 #8 #9 #10 #11
1 0.11 0.20 0.31 0.44 0.60 0.79 1.00 1.27 1.56
2 0.22 0.40 0.62 0.88 1.20 1.58 2.00 2.54 3.12
3 0.33 0.60 0.93 1.32 1.80 2.37 3.00 3.81 4.68
4 0.44 0.80 1.24 1.76 2.40 3.16 4.00 5.08 6.24
5 0.55 1.00 1.55 2.20 3.00 3.95 5.00 6.35 7.80
6 0.66 1.20 1.86 2.64 3.60 4.74 6.00 7.62 9.36
7 0.77 1.40 2.17 3.08 4.20 5.53 7.00 8.89 10.92
8 0.88 1.60 2.48 3.52 4.80 6.32 8.00 10.16 12.48
9 0.99 1.80 2.79 3.96 5.40 7.11 9.00 11.43 14.04
10 1.10 2.00 3.10 4.40 6.00 7.90 10.00 12.70 15.60
Example 11 (contd)
Therefore,
As 2 = As = 2.54 in 2
As1 = As As 2 = 6.0 2.54 = 3.46 in 2
( ) = 0.0273 0.0115 = 0.0158
Check whether compression steel yielded using Eq. 47
87,000
( - ) 0.851 f c d
87,000 f
f yd y
24
CHAPTER 5d. FLEXURE IN BEAMS Slide No. 48
Example 11 (contd)
Therefore,
[( ) = 0.0158] > 0.0146 ductility is OK
Example 11 (contd)
6,050.9
Mn = ft - kips = 504.2 ft - kips
12
25
CHAPTER 5d. FLEXURE IN BEAMS Slide No. 50
Example 12 (contd)
Determine the values for As and As:
From Table 6,
A 5.08
As = area of 4 #10 = 5.08 in 2 , = s = = 0.0173
bd 14(21)
A 1.20
As = area of 2 #7 = 1.20 in 2 , = s = = 0.0041
bd 14(21)
Therefore,
As As = As1 = 5.08 1.20 = 3.88 in 2
( ) = 0.0173 0.0041 = 0.0132
26
CHAPTER 5d. FLEXURE IN BEAMS Slide No. 52
Example 12 (contd)
Table 6. Areas of Multiple of Reinforcing Bars (in2)
Number Bar number
of bars #3 #4 $5 #6 #7 #8 #9 #10 #11
1 0.11 0.20 0.31 0.44 0.60 0.79 1.00 1.27 1.56
2 0.22 0.40 0.62 0.88 1.20 1.58 2.00 2.54 3.12
3 0.33 0.60 0.93 1.32 1.80 2.37 3.00 3.81 4.68
4 0.44 0.80 1.24 1.76 2.40 3.16 4.00 5.08 6.24
5 0.55 1.00 1.55 2.20 3.00 3.95 5.00 6.35 7.80
6 0.66 1.20 1.86 2.64 3.60 4.74 6.00 7.62 9.36
7 0.77 1.40 2.17 3.08 4.20 5.53 7.00 8.89 10.92
8 0.88 1.60 2.48 3.52 4.80 6.32 8.00 10.16 12.48
9 0.99 1.80 2.79 3.96 5.40 7.11 9.00 11.43 14.04
10 1.10 2.00 3.10 4.40 6.00 7.90 10.00 12.70 15.60
Example 12 (contd)
Check whether compression steel yielded using Eq. 47
87,000
( - ) 0.851 f c d
87,000 f
f yd y
27
CHAPTER 5d. FLEXURE IN BEAMS Slide No. 54
Example 12 (contd)
Using Eq. 55 to find c and consequently a:
Example 12 (contd)
The solution to the quadratic equation is as follows:
ax 2 + bx + c = 0
b b 2 4ac
x=
2a
47.6 x 2 200.4 x 261 = 0
(200.4) (200) 2 4(47.6)( 261) 200.4 299.49
x= =
2(47.6) 95.2
x = 1.0409, 5.251
28
CHAPTER 5d. FLEXURE IN BEAMS Slide No. 56
Example 12 (contd)
Check ACI Code Requirements for minimum
steel and strain limits:
3 f c 200
[Actual ( ) = 0.0132] > max , = 0.0035 OK
fy f y
Using either Eq. 58 or 59, gives
c 5.25
= = 0.25 < 0.375 (preferably 0.30) OK
dt 21
or
d 21
t = 0. 003 1 = 0. 003 1 = 0.009 > 0.005 OK
c 5 .25
29
CHAPTER 5d. FLEXURE IN BEAMS Slide No. 58
ENCE 454 Assakkaf
Figure 14. Strain Limit Zones and variation of Strength Reduction Factor
Example 12 (contd)
Since t > 0.005, the strength reduction factor
= 0.9. Therefore, the nominal moment
strength Mn of the beam is computed using
Eqs. 52 and 56 as follows:
0.003(c d ) 0.003(5.25 2.5)
f s = Es = 29 103 = 45.57 ksi
c 5.25
30
Chapter 6.
Compression Reinforcement - Flexural Members
If a beam cross section is limited because of architectural or other considerations, it may hap-
pen that the concrete cannot develop the compression force required to resist the give bending mo-
ment. In this case, reinforcing is added in the compression zone, resulting in a so-called doubly rein-
forced beam, i.e., one with compression as well as tension reinforcement. Compression reinforced
is also used to improve serviceability, improve long term deflections, and to provide support for stir-
rups throughout the beam.
A bs
d-c b h-c b T bs
b s = y
strains stresses forces
From geometry we can find the strain in compression steel at failure as:
s = 0.003 c
c
d (6.1)
d
u = 0.003 0.85f c 0.85f c
Cs
As y a a
c Cc A sf y Cc
d = +
h
As d-c Ts A sf y
T s = (A s A s)f y
b > y
Case I Case II
1c (6.2)
M n = (A s A s) f y (d ) + A s f y (d d)
2
Solve for a:
A s A s (6.4)
a= f
0.85f c b y
b y
Substitute for c from Eq. (6.6) and (6.7) and divide both sides by bd gives:
(A lim
s A s)f y
bd
= 0.85 1 b f c u
u
y
d 1
bd (6.8)
or A lim
s
bd
=
A s
bd
f
+ 0.85 1 c
fy
u
u d
y d
(6.9)
lim = s + 0.85 1
f c
fy
87, 000 d
87, 000 f y d
(6.10)
if
As A s
bd
f
0.85 1 c
fy
87, 000
d
87, 000 f y d
then compression steel
will yield
12
Solution
Equilibrium:
Cs + Cc = Ts
solve for c:
457 228
c = = 5.6 in
40.8 d
0.85f c u = 0.003
check assumption
c s
c d d
s = 0.003 c
5.6 2.5 Ts d-c
= 0.003 = 0.0017
5.6
y
fy 60
s = 0.0017 < = = 0.00207 wrong assumption
Es 29, 000
This means the compression steel does not yield. Therefore, our
initial assumption was wrong. We need to make a new assumption.
check assumption
6.31 2.5
f s = 0.003 29, 000 = 52.5 ksi < f y = 60 ksi
6.31
assumption o.k.
c = 6.31 = 0.284 < 0.375 We are in the tension-controlled section and satisfy
d 22.2
the ACI code requirements.
= 0.9
= 0.75 + ( t 0.002)(50)
0.90
SPIRAL
0.75
0.65
OTHER
Compression Tension
Transition
Controlled Controlled
t = 0.002 t = 0.005
c = 0.600 c = 0.375
dt dt
Take moment about tension reinforcement to determine the nominal moment capacity of the section:
Mn = Cc d 1c
2
+ C (d d)
s
2.5
2 No. 7
As= 1.2 in2
f c = 5, 000 psi 21
14
Solution
As
= = 5.08 = 0.0173
bd 14 21
= 0.0173 0.0041 = 0.0132
A s 1.2
= = = 0.0041
bd 14 21
Check whether the compression steel has yielded, use Eq. (6.10):
?
0.0132 0.85 1
f c
fy
87, 000 d
87, 000 f y d
?
0.0132 0.85 0.80 5
60
87, 000 2.5
87, 000 60000 21
?
0.0132 0.0217
Required M n = 9020 in k
As = ? in 2
Solution 12
use c = 0.375
d
f
= 0.85 1 c c
d fy
5 ksi
= (0.85)(0.80)(0.375) = 0.0213
60 ksi
Maximum As1 for singly reinforced section then is:
22.2 As = ? in 2
As = ? in 2
12
Check whether the compression steel has yielded, use Eq. (6.10):
As A s
bd
f
0.85 1 c
fy
87, 000 d
87, 000 f y d
8 2.37 0.85 0.80 5
22.2 12 60
87, 000
87, 000 60000
2.5
22.2
0.0211 0.206
Check to make sure that the final design will fall under tension-controlled
(A s A s)f y
a=
0.85f cb
(8.002.37)60
a= = 6.62 in
0.85(5)(12)
c = a = 6.62 = 8.28 in
1 0.80
see the following page for the rest of the solution done in a speadsheet.
f c = 4, 000 psi
CIVL 4135
134 Compression Reinforcement
CIVL 4135
135 Compression Reinforcement
CIVL 4135
136 Compression Reinforcement
CIVL 4135
137 Compression Reinforcement
CIVL 4135
138 Compression Reinforcement
CIVL 4135
139 Compression Reinforcement
CIVL 4135
140 Compression Reinforcement
CIVL 4135
141 Compression Reinforcement
CIVL 4135
142 Compression Reinforcement
CIVL 4135
143 Compression Reinforcement
6.9. Example: Design of a member to satisfy a nominal moment capacity.
A doubly reinforced concrete beam section has a maximum effective depth d = 25 in and is subjected
to a total factored moment Mu = 9400 in--kips, including self weight. Design the section and select
the appropriate reinforcement at the tension and the compression faces to carry the required load.
f c = 4, 000 psi
CIVL 4135
144 Compression Reinforcement
CIVL 4135
145 Compression Reinforcement
CIVL 4135
146 Compression Reinforcement
CIVL 4135
147 Compression Reinforcement
Lecture 1 Reinforced Concrete Properties
Reinforced concrete structures are typified by their strength, beauty, bulk and
longevity. It is the material of choice for many structures where these
characteristics are required. Concrete-framed structures have many desirable
advantages over other construction materials including:
Very labor-intensive
Quality control
Formwork
Longer construction schedule due to curing time
Much larger, heavier member sizes (vs. steel-framed)
Poor insulation values
Lecture 1 - Page 1 of 8
Concrete Materials:
Lecture 1 - Page 2 of 8
Reinforced Concrete Properties:
1) Compressive Strength
Lecture 1 - Page 3 of 8
2) Tensile Strength
Concrete is a brittle material and has very small tensile strength (about
10% of fc). It is usually assumed that concrete has zero tensile
strength.
Example:
GIVEN: Concrete with fc = 4000 PSI.
REQUIRED: Determine Econc
= 3,605,000 PSI
Lecture 1 - Page 4 of 8
4) Reinforcing Bars Used to carry ALL of the tension in a concrete
member, as well as helping to carry shear and compression. The steel
uses for bars is typically new billet steel having the usual modulus of
elasticity E = 29,000 KSI. The size of a bar refers to its diameter in
1/8ths. For example a #5 bar is in diameter (see table below). Rebar
should conform to ASTM A615 for deformed (ribbed) bars. Typical
grades of bars include:
Area (in2):
Fy = 60 KSI
"
8
Yield
#4 0.20
#5 5 0.31
Yield point
Fracture "
8
#6 0.44
Strain (in/in) #7 7 0.60
"
Elastic range 8
Stress #8 1 0.79
E
Strain #9 1 1.00
1 "
8
#10 1 1.27
Steel Stress-Strain Curve #11 3 1.56
1 "
8
The following diagram shows the typical markings on a deformed reinforcing bar:
Lecture 1 - Page 5 of 8
Epoxy-coated reinforcing bars are regular bars with a shop-applied
coating of epoxy. Epoxy coated bars conform to ASTM A775. These bars
have exceptional resistance to corrosion and are used in situations where
there is high water/salt exposure (such as road bridge decks, marine
structures, etc.). They are smooth to the touch and usually green in color.
Codes MAY allow the placement of epoxy-coated bars to be closer to the
surface than regular bars because of the increased resistance to
corrosion. This may result in a thinner, lighter concrete beam or slab.
Lecture 1 - Page 6 of 8
Reinforcing bars are placed a certain minimum distance away from the
edge of the member to ensure that it will not be susceptible to water/salt
infusion. This is referred to as cover distance. The cover distance
requirements shown below are obtained from ACI 318-05 Building Code
Requirements for Structural Concrete.
Required
minimum cover
distance Concrete member
Reinforcing bars
Required minimum
cover distance
Lecture 1 - Page 7 of 8
5) Slump Fresh concrete uses a slump test to determine the workability
of the concrete as per ASTM C 143. It is, however, not a very useful
measure of the concretes strength. It is possible to get very workable
concrete with high slump (i.e., very fluid) with the use of
superplasticizers.
Lecture 1 - Page 8 of 8
Lecture 2 Introduction to ACI 318-02
The American Concrete Institute (ACI) is the governing agency for all concrete
construction in the U.S. It was established in 1904 to serve and represent user
interests in the field of concrete. The ACI publishes many different standards,
but the most commonly referenced standard used by architects and engineers is
the ACI 318 Building Code Requirements for Structural Concrete. It is updated
every 7 years and the latest version is ACI 318-02 updated in 2002.
Almost all Building Codes, including the IBC, refer to ACI 318 as the basis for
structural design of concrete members.
Contents:
PART 1GENERAL
Lecture 2 - Page 1 of 9
PART 3CONSTRUCTION REQUIREMENTS
COMMENTARY REFERENCES.................................................................................................318-353
APPENDIXES
Lecture 2 - Page 2 of 9
Analysis and Design General Considerations
Design Basis:
Load Factors:
1) 1.4(D + F)
2) 1.2(D + F + T) + 1.6(L + H) + 0.5(Lr or S or R)
3) 1.2D + 1.6(Lr or S or R) + (1.0L or 0.8W)
4) 1.2D + 1.6W + 1.0L + 0.5(Lr or S or R)
5) 1.2D + 1.0E + 1.0L + 0.2S
6) 0.9D + 1.6W + 1.6H
7) 0.9D + 1.0E + 1.6H
Lecture 2 - Page 3 of 9
Example 1
GIVEN: The interior column of a 2-story concrete-framed building has the
following applied service loads to the 1200 ft2 tributary area as shown:
REQUIRED: Determine the maximum factored load, Pu, at the bottom of the 20
x 20 square column.
Lecture 2 - Page 4 of 9
Step 1 Determine the total service loads on the roof:
Step 3 Determine the total service dead load of the concrete column:
20" 20"
Column dead load, Dcolumn = (
(28 ft ) 150lb / ft
3
)
12 12
= 11,667 lbs.
= 11.7 KIPS
Lecture 2 - Page 5 of 9
Step 4 Sum all service dead loads together:
1) 1.4(D + F)
1.4(351.3) = 491.8 KIPS
Lecture 2 - Page 6 of 9
Example 2
GIVEN: The cantilevered floor balcony beam/slab as shown below. The service
superimposed dead load (not including concrete) = 14 PSF and the
superimposed service live load = 75 PSF.
REQUIRED: Determine the maximum factored moment, Mu on the cantilevered
beam.
wu
14-0
Lecture 2 - Page 7 of 9
Step 1 Determine service dead load, D acting on beam:
5 slab
18
10
8-0 18 5 slab
16-0
Lecture 2 - Page 8 of 9
Step 4 Determine maximum factored moment on beam, Mu:
wu = 1.9 KLF
14-0
0 Kips 0 Kips
Shear Diagram
-26.6 Kips
Area of Triangle
0 Kip-Ft
Moment Diagram
-186.2 Kip-Ft
wu L2
For a cantilevered beam, Mmax = Mu =
2
Mu = -186.2 KIP-FT
Lecture 2 - Page 9 of 9
Lecture 5 T- Beams
Concrete beams are often poured integrally with the slab, forming a much stronger
T shaped beam. These beams are very efficient because the slab portion
carries the compressive loads and the reinforcing bars placed at the bottom of the
stem carry the tension. A T-beam typically has a narrower stem than an ordinary
rectangular beam. These stems are typically spaced from 4-0 apart to more than
12-0. The slab portion above the stem is designed as a one-way slab spanning
between stems (see Lecture 6).
Overhang
width d
bw Clear distance bw
NOTE: Stirrups in T-beam
are required (not shown in
this sketch)
Lecture 5 - Page 1 of 9
Assuming T-beams are symmetrical, the following design dimensions are used:
8hf
(Clear distance)
(Beam span)
b = smaller or
(2 x overhang width) + bw
T-Beam Analysis
T-beams are analyzed similarly to rectangular beams, except the
compression area is a narrow strip usually located in the slab.
a = Effective conc.
compressive b = Effective flange width
thickness
hf
a
Z = (d - ) d
2
Ac = Shaded area
= Effective concrete
compression area As = Total area of
= (a)(b) bw
main tension bars
Lecture 5 - Page 2 of 9
Mu = Usable moment capacity of T-beam
= TZ
where: = 0.9
a
=d-
2
Lecture 5 - Page 3 of 9
Example 1
GIVEN: A commercial building has T-beams spaced 6-6 (center-to-center) with a 4
thick concrete slab as shown in the framing plan and cross-section views below. Use
the following information:
Superimposed service floor dead load (NOT including conc. wt.) = 40 PSF
Superimposed service floor live load = 100 PSF
Concrete fc = 3000 PSI
ASTM A615 Grade 60 bars
REQUIRED:
1) Determine the maximum factored moment, Mmax, on the T-beam.
2) Determine the usable moment capacity, Mu, for the T-beam.
T-beam
6-6
Perimeter girder Column
Typ.
Framing Plan
Lecture 5 - Page 4 of 9
6-6
hf = 4
16
18
2 - #9 bars
8
wu L2
Det. Maximum factored moment, Mmax =
8
Mmax = 95 KIP-FT
Lecture 5 - Page 5 of 9
Step 2 Determine effective concrete slab width b:
b = smaller or
(2 x overhang width) + bw = (2 x 32 + 8) = 72
T
=
0.85 f ' c
120 KIPS
=
0.85(3KSI )
= 47.1 in2
Lecture 5 - Page 6 of 9
Step 4 Determine usable moment capacity, Mu for the T-beam:
47.1in 2
=
60"
a = 0.79
a
=d-
2
0.79"
= 16 -
2
Z = 15.6
Mu = TZ
= 0.9(120 KIPS)(15.6)
= 1685 KIP-IN
Mu = 140.4 KIP-FT
Lecture 5 - Page 7 of 9
Heavily-Reinforced T-Beams
T-beams with a lot of tension reinforcement may have a portion of the effective
concrete area located within the stem as shown below:
hf
d
Z
Ac = Shaded area
= Effective concrete
compression area
bw
As
Similar to ordinary rectangular reinforced concrete beams, the ACI 318 limits
the amount of tension steel in T-beams so that the steel will yield prior to
concrete compression failure. The maximum area of steel, As is shown in the
table below.
Lecture 5 - Page 8 of 9
Example 2
GIVEN: The T-beam from Example 1.
REQUIRED: Determine the maximum area of tension steel permitted, As max:
From Example 1:
Lecture 5 - Page 9 of 9
Lecture 7 Two-Way Slabs
Two-way slabs have tension reinforcing spanning in BOTH directions, and may take
the general form of one of the following:
Lecture 7 Page 1 of 13
The following Table may be used to determine minimum thickness of various two-
way slabs based on deflection:
Flat Plates
Flat plates are the most common type of two-way slab system. It is commonly
used in multi-story construction such as hotels, hospitals, offices and
apartment buildings. It has several advantages:
Easy formwork
Simple bar placement
Low floor-to-floor heights
Lecture 7 Page 2 of 13
The ACI 318 code allows a direct design method that can be used in most
typical situations. However, the following limitations apply:
Design Strips
a) If L1 > L2:
L2 L2
Column
(typ.)
Exterior Column Strip
Interior Column Strip
Interior Column Strip
Middle Strip
Middle Strip
L1
Lecture 7 Page 3 of 13
b) If L2 > L1:
L2 L2
Middle Strip
Middle Strip
L1
1 2 3 4 5
2
wu L2 Ln
Mo = where Ln = clear span (face-to-face of cols.) in the direction of analysis
8
Lecture 7 Page 4 of 13
Bar Placement per ACI 318-02
Lecture 7 Page 5 of 13
Example 1
GIVEN: A two-way flat plate for an office building is shown below. Use the following:
Column dimensions = 20 x 20
Superimposed service floor Dead load = 32 PSF (not including slab weight)
Superimposed service floor Live load = 75 PSF
Concrete fc = 4000 PSI
#4 Grade 60 main tension bars
Concrete cover =
REQUIRED: Use the Direct Design Method to design the two-way slab for the
design strip in the direction shown.
20-0
Ln 20-0
20-0
L2/4 L2/4
Middle strip
= (16 Col. strip) Middle strip
Col. strip = (16 Col. strip)
Design Strip = 16
Lecture 7 Page 6 of 13
Step 1 Determine slab thickness h:
Ln
Since it is a flat plate, from Table above, use h =
30
= 220 = 18.33
220"
h=
30
= 7.333
= 278.4 PSF
= 0.28 KSF
3) Successive span lengths in each direction must not differ by more than
1/3 of the longer span. YES
4) Columns must not be offset by more than 10% of the span (in direction
of offset) from either axis between centerlines of successive columns.
YES
5) Loads must be uniformly distributed, with the unfactored live load not
more than 2 times the unfactored dead load (L/D < 2.0). YES
Lecture 7 Page 7 of 13
Step 4 Determine total factored moment per span, Mo:
2
wu L2 Ln
Mo =
8
Mo = 188 KIP-FT
Step 5 Determine distribution of total factored moment into col. & middle strips:
Step 6 Determine tension steel bars for col. & middle strips:
b = 96
8
d
Lecture 7 Page 8 of 13
Mu 586,800 LB IN
=
bd 2
(0.9)(96" )(7" ) 2
= 138.6 PSI
As
=
bd
As = bd
= (0.0033)(96)(7)
= 2.22 in2
As
Number of bars required =
As _ per _ bar
2.22in 2
=
0.20in 2 _ per _#4 _ bar
Lecture 7 Page 9 of 13
b) Column strip for region 2 :
b = 96
8 d
Mu 699,600 LB IN
=
bd 2
(0.9)(96" )(7" ) 2
= 165.2 PSI
Use = 0.0033
Lecture 7 Page 10 of 13
c) Middle strip for region 2 :
b = 96
8 d
Mu 474,000 LB IN
=
bd 2
(0.9)(96" )(7" ) 2
= 112.0 PSI
Use = 0.0033
Lecture 7 Page 11 of 13
Step 7 Draw Summary Sketch plan view of bars:
8 Thick
concrete slab 20-0
4-0 4-0
16 0
Lecture 7 Page 12 of 13
Example 2
GIVEN: The two-way slab system from Example 1.
REQUIRED: Design the steel tension bars for design strip shown (perpendicular to
those in Example 1).
20-0
Middle strip = 6-0
20-0
Lecture 7 Page 13 of 13
Lecture 11 Development of Reinforcement, Splices, Hooks
Concrete
Rebar
T = Asfy
Ld
The development length is based upon the BOND between the rebar and the
concrete. Factors affecting this bond include the following:
Lecture 11 Page 1 of 9
Determining Ld for Tension Bars:
d b f y
Ld =
25 f ' c
d b f y
Ld =
20 f ' c
where:
db = diameter of bar
= alpha
= Bar location factor
= 1.3 for top reinforcement
= 1.0 for all other locations
= beta
= Coating factor
= 1.5 for epoxy coated bars
= 1.0 for uncoated bars
= lambda
= Lightweight aggregate factor
= 1.3 for lightweight aggregate
= 1.0 for normal weight aggregate
Lecture 11 Page 2 of 9
Example 1
GIVEN: A #6 rebar under tension force. Assume the following conditions:
d b f y
Ld =
25 f ' c
6
" (60,000 PSI )(1.0)(1.0)(1.0)
Ld =
8
25 4000 PSI
Ld = 28.5
Concrete
#6 Rebar
Ld = 28.5
Lecture 11 Page 3 of 9
Assuming normal conditions, the following table may be used to determine
development lengths of bars in tension:
Example 2
GIVEN: The same information as Example 1.
REQUIRED: Using the table above, determine the Ld for a #6 bar.
Lecture 11 Page 4 of 9
Determining Ld for Compression Bars:
= larger of or
Ldc = 0.0003dbfy
Example 3
GIVEN: A #6 bar in compression. Use fc = 4000 PSI and Grade 60 bars.
REQUIRED: Determine the Ldc for the bar.
6
" (60,000 PSI )
= 0.02
db f y 8
Ldc = 0.02 = 14.2 Use
f 'c 4000 PSI
Ldc = Larger of or
6
Ldc = 0.0003dbfy = 0.0003 " (60,000 PSI) = 13.5
8
Ldc = 14.2
Lecture 11 Page 5 of 9
Lap Splices of Bars
Bars are generally fabricated to lengths of about 60-0, but transportation,
workability and other concerns often require bars to be less than about
40-0 long. For long walls, beams, slabs and other situations requiring
long lengths of bars, lap splicing is commonly used. It is good practice to
place laps at regions of small tension, i.e., low moment.
Concrete
Ls
Lecture 11 Page 6 of 9
Hooked and Bent Bars
Hooks are used in concrete members where there is not sufficient straight
length to achieve the full development length Ld.
Ldh = Lhb
Lecture 11 Page 7 of 9
Where: Lhb = Basic development length of hook in tension
db
= 1200
f 'c
= 1.0 unless otherwise specified below:
fy
= if using other than Grade 60 bars
60,000
Re quired _ As
=
Pr ovided _ As
Example 4
GIVEN: A #5 Grade 40 bar is in tension as shown below. Use LIGHTWEIGHT
concrete with fc = 4000 PSI.
REQUIRED: Determine the min. required hook dimensions X, Y and Z.
Z = Ldh
Side cover = 1
Y
End cover = 1 Critical section
X = 12db
5
= 12 "
8
X = 7
Lecture 11 Page 8 of 9
Step 2 Determine dimension Y:
5
= 4 "
8
Y = 2
db
Lhb = 1200
f 'c
5
"
= 1200
8
4000 PSI
= 11.9
Ldh = Lhb
fy 40000 PSI
= = = 0.67
60000 PSI 60000 PSI
Ldh = Lhb
= 11.9(1.0)(1.3)(0.67)
Ldh = 10.4
Lecture 11 Page 9 of 9
Lecture 14 Columns
Concrete Columns:
Lecture 14 Page 1 of 15
Most columns have combined compression and bending. They are
essentially a beam-column. The compression capacity of a reinforced
column is reduced by the bending stresses on the column and vice-versa.
A graph of the axial load capacity of a column vs. the moment capacity of
a typical column is shown below:
Pure bending
Lecture 14 Page 2 of 15
Types of Concrete Columns:
There are two types of reinforced concrete columns tied and spiral
and refer to the type of confining bars used to contain the interior core of
concrete. It has been shown that unconfined concrete core will carry
MUCH LESS load than a confined core as shown below:
Load
Load
Unconfined core
Insufficient ties
Lecture 14 Page 3 of 15
A confined concrete core will carry substantially more load and will NOT
explode outward like the unconfined concrete section will.
Load Load
Minor concrete
spalling, core
remains intact
Confined core
Tied Column:
A Tied concrete column is one in which individual rebar ties are used to
wrap completely around the vertical bars to confine the interior core.
These ties are usually #3 or #4 bars spaced per ACI requirements:
Lecture 14 Page 4 of 15
A typical tied concrete column looks like the following:
Vertical bars (4
minimum)
Tie bars
Tie spacing
Concrete
Lecture 14 Page 5 of 15
Spiral Column:
A spiral column has a single rebar wrapped around the vertical bars in a
spiral and is stronger than a comparable tied column. It is more labor-
intensive to build than a tied column. The ACI requires a minimum of 6
vertical bars, with the same minimum and maximum areas of steel as a
tied column.
Concrete
Pitch =
1 3
Spiral rebar
Spiral columns have greater ductility than a tied column. This means that
a spiral column is capable of sustaining larger strain before failure than a
tied column. For this reason, spiral columns are used in areas with
high seismicity to prevent brittle failures. The stress-strain curve below
shows the relative yield strength of a tied column and a spiral column are
similar, however the strain capacity of the spiral column is much greater
than that of a tied column.
Spiral column
Yield
Fracture
Fracture
Stress
Tied column
Strain
Lecture 14 Page 6 of 15
Column Load Capacity Small eccentricity:
The ratio of applied moment to the applied axial load is its eccentricity. A
small eccentricity e means small moment, where a large eccentricity
means large moment.
e e
Side view of
column
h h
Mu = Pue Mu = Pue
= Small = Large
Lecture 14 Page 7 of 15
1) Tied columns with small eccentricity:
e
Small eccentricity if 0.10
h
= 0.80c[0.85fc(Ag-As)+fyAs]
e
Small eccentricity if 0.10
h
= 0.85c[0.85fc(Ag-As)+fyAs]
Lecture 14 Page 8 of 15
Spiral requirements:
Ag f'
s = 0.45 1 c
Ac fy
4 As (d c d b )
s=
sdc2
Lecture 14 Page 9 of 15
Example 1
GIVEN: A 16 x 16 square tied concrete column has an applied factored axial
load Pu = 300 KIPS and an applied factored moment Mu = 35 KIP-FT. In
addition, use the following:
REQUIRED:
1) Determine the eccentricity e and state whether or not it is considered to
be small eccentricity.
2) Determine the required tie spacing.
3) Determine if the vertical bars are acceptable based on ACI requirements.
4) Determine the usable axial strength of the tied column, Pn, and state
whether or not it is acceptable.
16
16
8 - #7 vertical bars
M u (12" / ft )
Eccentricity e =
Pu
35 KIP FT (12" / ft )
=
300 KIPS
e = 1.4
e/h = 1.4/(16)
e/h = 0.0875 it is small eccentricity
Lecture 14 Page 10 of 15
Step 2 Determine the required tie spacing:
7
16 x Vert. Bar Dia. = 16 " = 14 USE
Tie Spacing = smaller of 8
3
48 x Tie Bar Dia. = 48 " = 18
8
Step 4 - Determine the usable axial strength of the tied column, Pn:
= 0.80c[0.85fc(Ag-As)+fyAs]
Ag = 16 x 16
= 256 in2
Pn = 594 KIPS
Lecture 14 Page 11 of 15
Example 2
GIVEN: A 14 diameter spiral column has a factored axial load Pu = 400 KIPS
and a factored moment = 45 KIP-FT. In addition, use the following:
REQUIRED:
1) Determine the eccentricity e and state whether or not it is considered to
be small eccentricity.
2) Determine the required spiral pitch.
3) Determine the usable axial strength of the spiral column, Pn, and state
whether or not it is acceptable.
Lecture 14 Page 12 of 15
Step 1 Determine eccentricity and whether it is small.
M u (12" / ft )
Eccentricity e =
Pu
45KIP FT (12" / ft )
=
400 KIPS
e = 1.35
e
Small eccentricity if < 0.10
h
e 1.35"
=
h 14"
Ag f'
s = 0.45 1 c
Ac fy Pitch
where: Ag = (Outside _ Dia ) 2
4
= (14" ) 2
4
Ag = 153.9 in2
Ac = (Core _ Dia) 2
4
= (11" ) 2
4
Ac = 95.0 in2
Lecture 14 Page 13 of 15
Ag f'
s = 0.45 1 c
Ac fy
153.9in 2 4 KSI
s = 0.45 2
1
95.0in 60 KSI
s = 0.0186
Pitch = s
4 As (d c d b )
s=
sdc2
3
4(0.11in 2 )(11" " )
s= 8
(0.0186)(11" ) 2
Pitch s = 2.08
Use pitch = 2
Lecture 14 Page 14 of 15
Step 3 - Determine the usable axial strength of the spiral column, Pn:
= 0.85c[0.85fc(Ag-As)+fyAs]
Ag = 153.9 in2
Pn = 513 KIPS
Lecture 14 Page 15 of 15
Lecture 15 Columns (cont.)
In the previous lecture, we talked about columns having small eccentricity (i.e.,
small applied moment). While this may be the case for interior columns with
offsetting moments, the majority of concrete columns do experience applied
moments.
Concrete framed buildings typically have columns that are poured monolithically
with beams and slabs, thus creating a statically-indeterminate frame such as the
one shown below:
The analysis of such a frame is usually quite complex and requires computer
software such as STAAD or approximate analysis methods such as the Portal
Method and others discussed in Structural Theory.
Lecture 15 Page 1 of 12
The compression capacity of a reinforced column is reduced by the bending
stresses on the column and vice-versa. A graph of the axial load capacity of a
column vs. the moment capacity of a typical column is shown below (from
Lecture 14):
Determining points along the curve is quite laborious and typically not done using
hand calculations. Instead, computer programs or design guides are used to
perform column analysis and design.
Below are some Column Interaction Diagrams that are used for column
analysis and design.
Lecture 15 Page 2 of 12
R4-60.75
R = Rectangular cross-section
4 = fc = 4 KSI
60 = Grade 60 vertical bars
75 =
Lecture 15 Page 3 of 12
Circular SPIRAL Column Interaction Diagrams
Lecture 15 Page 4 of 12
Short Column Design:
KL
Short column IF 22
rmin
Lecture 15 Page 5 of 12
Example
GIVEN: A 20 x 20 square interior tied column is shown below. Use concrete f c
= 4000 PSI and 8 - #8 grade 60 vertical bars and #3 ties. Concrete cover = 1 .
All loads are factored and includes beam weight. Assume the beams are fixed
to the columns.
REQUIRED:
1) Determine the applied factored axial load, P u on the middle column. Be
sure to add column weight. Assume the loads from the roof above are
75% of the floor load.
KL
2) Determine the slenderness ratio using K = 0.7 and determine if
rmin
column qualifies as short.
3) Determine total factored moments Mtotal applied to the column.
4) Determine if the column is acceptable based on Column Interaction
Diagram.
22-0 30-0
46 K 46 K
wu = 1.7 KLF wu = 2.5 KLF
Beam 1 Beam 2
14-0
20 x 20 Middle
column
Lecture 15 Page 6 of 12
Step 1 Determine the total factored axial load, Pu on the middle column:
a) Beam 1:
b) Beam 2:
c) Column weight:
20" x 20"
Weight = (1.2) (14'0" )(150 PCF )
144in 2 / ft 2
ACI Dead
Load factor = (1.2)5833 Lbs.
= 7.0 KIPS 75%
KL
Step 2 - Determine the slenderness ratio using K = 0.7:
rmin
KL (0.7)(14'0" x12" / ft )
=
rmin 0.3( 20")
KL
= 19.6
rmin
Lecture 15 Page 7 of 12
Step 3 Determine total factored moment M total applied to the column:
a) Beam 1:
22-0
46 K 46 K
wu = 1.7 KLF
Ln = 20.33
Lecture 15 Page 8 of 12
Unif. Load
Point Loads
= Muniform + Mpoint
= (bPL)unif + (bPL)point
Lecture 15 Page 9 of 12
b) Beam 2:
30-0
wu = 2.5 KLF
Ln = 28.33
= Muniform
= (bPL)unif
= 166.5 Kip-ft
c) Determine Mtotal:
Lecture 15 Page 10 of 12
Step 4 - Determine if the column is acceptable based on Column
Interaction Diagram.
e
a) Determine ratio:
h
e = eccentricity
M total (12" / ft )
=
Pu
e = 6.26
e 6.26"
=
h 20"
e
= 0.31 > 0.10 CANNOT use small eccentricity formula
h
b) Determine :
h = 20
X h X
8 - #8 vertical bars 20
h = 20 (X + X)
= 20 (2.375 + 2.375)
= 15.25
(20) = 15.25
Lecture 15 Page 11 of 12
c) Use Interaction Diagram R4-60.75:
Use g = 0.01
Pn Pu
=
Ag Ag
191.1KIPS
=
20" x 20"
Pn
= 0.48 KSI
Ag
Pn e Pu e
x = x
Ag h Ag h
= (0.48 KSI)(0.31)
Pn e
x = 0.15 KSI
Ag h
As
g =
Ag
2
= 8 _ bars (0 .79in _ per _#8 _ bar ) = 0.016
20" x 20"
Lecture 15 Page 12 of 12
Lecture 19 Wall Footings
All structural load-bearing walls must bear on footings. These footings in turn
distribute the loads to the soil. If the loading on the soil exceeds the soil bearing
capacity, undesirable settlement will occur, resulting in cracked walls, uneven
floors, or potentially structural failure in extreme overloading.
Lecture 19 Page 1 of 10
Wall Footing Requirements:
1) Must distribute the loads evenly to the soil.
2) Bottom of footing must be deeper than the frost penetration or else frost
heave will occur.
3) Must be well-drained to prevent wash-out.
4) Must bear on undisturbed (or engineered) soil.
Lecture 19 Page 2 of 10
Typical Allowable Soil Bearing Values per IBC Table 1804.2
Soil Type: Allowable Soil Bearing (qa)*:
Bedrock 12,000 PSF
Sedimentary and foliated rock 4,000 PSF
Sandy gravel and/or gravel 3,000 PSF
Sand, silty sand, clayey sand, silty gravel, clayey gravel 2,000 PSF
Clay, sandy clay, silty clay, clayey silt, silt, sandy silt 1,500 PSF
Organics, peat, top soil NOT Recommended for use
as footing bearing
* = An increase of one-third is permitted when using alternate load combinations in
IBC Section 1605.3.2 that include wind or earthquake loads.
Example
GIVEN: An 8 wide load-bearing poured-in-place concrete wall is to bear on a
wall footing with the following:
Lecture 19 Page 3 of 10
Step 2 Determine effective soil bearing, qe:
Soil overburden
Finished grade
1-0
qe
qe = 2630 PSF
Lecture 19 Page 4 of 10
Step 3 Determine required width of footing, wf:
qe = 2630 PSF
Footing width = wf
Ptotal
Footing width = wf =
qe
14000 PLF
wf =
2630 PSF
wf = 5.32 feet
Lecture 19 Page 5 of 10
Step 4 Determine soil bearing pressure for strength design, qu:
qu = 3490 PSF
Footing d
thickness
#5 bar
w f Wall _ Width d
Vu = qu
2 2 2
8" 8.69"
5.5' 12" / ft 12" / ft
= 3490 PSF
2 2 2
Vu = 7170 Lbs.
Lecture 19 Page 6 of 10
dmin = Minimum depth to reinforcement based on shear
Vu
=
(0.85)2 f ' c (12" )
7170 Lbs.
=
(0.85)2 3000 PSI (12" )
Point A
qu = 3490 PSF
Isolate footing
overhang and treat Footing width = 5.5 ft.
as if it were a
cantilevered beam
Point A
MA = Moment at point A
Footing _ overhang
= qu(Footing overhang)
2
2.42'
= 3490 PSF(2.42) Overhang
2
MA = 10,219 FT-LB
Lecture 19 Page 7 of 10
Step 7 Determine required tension steel, As in footing:
Mu (10219 Ft Lb)(12" / ft )
=
bd 2
0.9(12" )(8.69" ) 2
= 150.4 PSI
Mu
Use min = 0.0033 since = 150.4 PSI < 190.3 PSI
bd 2
As = bd
= (0.0033)(12)(8.69)
Lecture 19 Page 8 of 10
Step 8 Determine spacing of #5 tension bars:
A _ per _ bar
Spacing = 12" s
As
= 10.9
h = 12
As temp = 0.0018bh
= 0.0018(5.5 x 12/ft)(12)
= 1.43 in2
As
Number of bars =
As _ per _ bar
1.43in 2
=
0.20in 2 _ per _#4 _ bar
= 7.15 bars
Lecture 19 Page 9 of 10
Step 10 Draw Summary Sketch:
8 poured-in-place conc.
wall centered over footing
(dowel bars not shown) Finished grade sloped
away from bldg.
Formed Keyway
3-0 minimum
8 - #4 longitudinal bars
3 conc. cover
12
all around
NOTES:
1) Conc. fc = 3000 PSI. Footing to bear on
2) All bars grade 60
#5 bars @
10 o.c. undisturbed soil
3) Wall reinf. & dowels not shown
4) Allow. Soil bearing = 3000 PSF
5-6
Lecture 19 Page 10 of 10
Lecture 20 Column Footings
All columns must bear on footings. Usually these footings are square or circular
for ease of design and formwork. The same general requirements and design
fundamentals pertain to column footings as for wall footings, i.e.,
Steel column
Lecture 20 Page 1 of 8
Example
GIVEN: A steel column rests on a 10 x 10 steel base plate over a 12 x 12
concrete pier centered over a square footing. Use the following:
REQUIRED: Design the square concrete footing, including all dimensions and
bars. Provide a Summary Sketch showing all information necessary to build it.
Soil overburden
Finished grade
Depth to frost = 4-0
2-9
1-3
qe
qe = 4000 PSF (1.25(150 PCF)) (2.75(100 PCF))
= 3538 PSF
= 3.5 KSF
Lecture 20 Page 2 of 8
Step 3 Determine length & width of footing:
Ptotal
Area of footing =
qe
PDEAD + PLIVE
=
qe
= 62.9 ft2
Use 8-0 x 8-0 square footing Area = 64 ft2 > 62.9 ft2
qu = 4.75 kips/ft2
Lecture 20 Page 3 of 8
Step 5 Determine depth to tension bars d:
#7 bar
Footing d
thickness = 15
Ftg. Width
Footing
thickness = 15
d
d d Ftg. Plan
Pier
2 width 2
bo bo = shear
perimeter
4
bo d
= pier width + 2( )
4 2
11.56"
= 12 + 2( )
2
bo
= 23.56 = 1.96 feet
4
bo = 94.24
Lecture 20 Page 4 of 8
Vu2 = 2-way punching shear
2
b
= qu(Footing area - o )
4
= 285.8 KIPS
= 285,800 Lbs.
Vu 2
=
(0.85)4 f ' c bo
285,800 Lbs.
=
(0.85)4 3000 PSI (94.24" )
dreqd = 16.3
7
= 16.3 + 3 + "
8
= 19.73
Lecture 20 Page 5 of 8
Step 7 Determine moment on footing overhang, Mu:
Footing
overhang Column pier
8-0
qu
3-6 12 3-6
Footing
8-0
overhang
Side View
( Footing _ Overhang ) 2
Mu = (Footing width)(qu)
2
(3.5' ) 2
= (8-0)(4.75KSF)
2
= 232.8 Kip-Ft
Lecture 20 Page 6 of 8
Step 8 Determine area of tension steel As:
Lb Inch
232.8Kip Ft (12000 )
Mu Kip Ft
=
bd 2 1
2
d = 16.56
= 117.9 PSI
As = bd
= (0.0033)(8-0 x 12/ft)(16.56)
As = 5.25 in2
As
Number of bars =
As _ per _ bar
5.25in 2
=
0.60in 2 _ per _#7bar
= 8.75 bars
Lecture 20 Page 7 of 8
Step 10 Draw Summary Sketch:
Steel column on 12 x 12
base plate centered over
footing pier
Finished grade
4-0 minimum
3 conc. cover
20
all around
NOTES: 8-0
1) Conc. fc = 3000 PSI.
2) All bars grade 60
3) Allow. Soil bearing = 4000 PSF
4) Anchor rods not shown for clarity
5) Pier reinf. & dowels not shown for
clarity
Lecture 20 Page 8 of 8
Lecture 21 Load-Bearing Walls
The ACI recognizes the Empirical Design Method for the design of load-
bearing concrete walls having the following limitations:
Load-bearing Wall
Lu
25
2. Minimum wall thickness tw = larger of
4 Interior walls only
7 Exterior walls
tw
3. Applied load eccentricity e (including lateral load moments) <
6
Lecture 21 Page 1 of 7
5. Must have horizontal & vertical reinforcement, with 2 rows of
reinforcing for walls with tw > 10
3tw
18
KL 2
Pn = 0.55f ' c Ag 1 u
32t w
where: = 0.70
Lecture 21 Page 2 of 7
Example
GIVEN: A poured-in-place concrete wall supports W18x35 steel beams spaced
6-0 apart and rests on 10 wide steel bearing plates. Use the following:
Beam end reaction = 22 KIPS Service Dead Load (Not incl. wall wt.)
= 15 KIPS Service Live Load
PDEAD = 22 KIPS
PLIVE = 15 KIPS
Steel beam
Wind = 25 PSF
Lu = 13-0
10 bearing
plate
Wall
Fin. Grade
Slab on grade
Lecture 21 Page 3 of 7
Step 1 Determine Trial thickness of wall, tw:
Lu 13'0" (12" / ft )
= = 6.24
25 25
Minimum wall thickness tw = larger of
4
7 Largest
wL2
Mwind =
8
(25PSFx1'0" )(13' ) 2
=
8
Lecture 21 Page 4 of 7
Step 4 Determine if eccentricity is acceptable for Empirical Design:
e = eccentricity
M
= Service wind load moment
P
3.168Kip Ft (12" / ft )
=
44.8KIPS Service axial load (see
above)
= 0.85 inches
tw
The empirical design method dictates that e <
6
tw
= 1.33 > 0.85 OK to use Empirical Design Method
6
Pu = 1.2(PDEAD) + 1.6(PLIVE)
= 1.2(29.8 KIPS) + 1.6(15 KIPS)
= 59.8 KIPS
= (10)(8)
= 80 in2
Lecture 21 Page 5 of 7
Step 7 Determine design axial strength of wall Pn:
KL 2
Pn = 0.55f ' c Ag 1 u
32t w
(1.0)(13' x12" / ft ) 2
= 0.55(0.70)(4000 PSI )(336in ) 1
2
32(8" )
3tw = 3(8) = 24
Maximum bar spacing = smaller of
or
18 USE
Lecture 21 Page 6 of 7
b) Horizontal bars As = 0.0020(tw)(12)
= 0.0020(8)(12)
= 0.192 in2
= 19.4
19.4
or
or
18 USE
Lecture 21 Page 7 of 7
Page 1 of 16
mhtml:http://faculty.delhi.edu/hultendc/AECT%20250-Lecture%2038.mht 4/18/2008
Page 2 of 16
mhtml:http://faculty.delhi.edu/hultendc/AECT%20250-Lecture%2038.mht 4/18/2008
Page 3 of 16
mhtml:http://faculty.delhi.edu/hultendc/AECT%20250-Lecture%2038.mht 4/18/2008
Page 4 of 16
mhtml:http://faculty.delhi.edu/hultendc/AECT%20250-Lecture%2038.mht 4/18/2008
Page 5 of 16
mhtml:http://faculty.delhi.edu/hultendc/AECT%20250-Lecture%2038.mht 4/18/2008
Page 6 of 16
mhtml:http://faculty.delhi.edu/hultendc/AECT%20250-Lecture%2038.mht 4/18/2008
Page 7 of 16
mhtml:http://faculty.delhi.edu/hultendc/AECT%20250-Lecture%2038.mht 4/18/2008
Page 8 of 16
mhtml:http://faculty.delhi.edu/hultendc/AECT%20250-Lecture%2038.mht 4/18/2008
Page 9 of 16
mhtml:http://faculty.delhi.edu/hultendc/AECT%20250-Lecture%2038.mht 4/18/2008
Page 10 of 16
mhtml:http://faculty.delhi.edu/hultendc/AECT%20250-Lecture%2038.mht 4/18/2008
Page 11 of 16
mhtml:http://faculty.delhi.edu/hultendc/AECT%20250-Lecture%2038.mht 4/18/2008
Page 12 of 16
mhtml:http://faculty.delhi.edu/hultendc/AECT%20250-Lecture%2038.mht 4/18/2008
Page 13 of 16
mhtml:http://faculty.delhi.edu/hultendc/AECT%20250-Lecture%2038.mht 4/18/2008
Page 14 of 16
mhtml:http://faculty.delhi.edu/hultendc/AECT%20250-Lecture%2038.mht 4/18/2008
Page 15 of 16
mhtml:http://faculty.delhi.edu/hultendc/AECT%20250-Lecture%2038.mht 4/18/2008
Page 16 of 16
mhtml:http://faculty.delhi.edu/hultendc/AECT%20250-Lecture%2038.mht 4/18/2008
Lecture 26 Metric
Metric units are used everywhere in the world EXCEPT the USA. It is based on
scientific measurements, not the length of a kings foot or the weight of a chicken.
Lecture 26 Page 1 of 11
Example 1
GIVEN: All road construction projects in New York State have drawings
with metric measurements. All metric drawings always use units of mm
for everything. (Reminder: 1 m = 1000 mm)
REQUIRED: Convert 1500 mm as shown on the drawings into
feet/inch/sixteenths.
1500mm
Number of inches =
25.4mm _ per _ inch
= 59.055118 inches
= 48 + 11.055118
= 4 + 11.055118
= 4 + 11 + (0.055118 x 16th)
0.88
= 4 + 11 +
16ths
1
1500 mm = 4-11 "
16
Example 2
GIVEN: The x-sectional area of a W30x211 steel beam = 62.0 in2.
REQUIRED: Determine the area of the beam in units of mm2.
Lecture 26 Page 2 of 11
Example 3
GIVEN: The tank below.
REQUIRED: How many liters are in the tank?
7-0
Dia. = 18-0
Vol. = (18' ) 2 (7' )
4
= 1781 ft3
Lecture 26 Page 3 of 11
Example 4
GIVEN: An ASTM A325 steel bolt is capable of resisting an allowable
shear stress of 30 kips per square inch (KSI)
REQUIRED: What is the allowable shear stress for the bolt in units of
KPa?
1 Pa = 1 N/m2
1 kPa = 1000 Pa
1 lb = 4.448 N
30000lb
30 KSI =
1in 2
(133440 N )
30 KSI =
(0.00064516mm 2 )
30 KSI = 206,832,414 Pa
Lecture 26 Page 4 of 11
Metric Loads
All metric loads, forces and derivatives of those are in units of Newtons.
Below is a sampling of typical minimum design live loads for buildings:
Material Properties
Material: Unit Weight: Modulus Of Elasticity (E): Yield Stress (fy):
Lb/ft3 kN/m3 Kips/in2 kN/mm2 Kips/in2 N/mm2
Steel A36 490 77.2 29,000 205 36 248
Steel A992 490 77.2 29,000 205 50 345
Aluminum 170 26.7 10,000 70 28 190
Concrete (4000 psi) 150 23.6 3,600 25.4 - -
Wood - SYP 37 5.8 1,600 11.3 6 42
Earth sandy 100 15.7 - - - -
Water 62.4 9.8 - - - -
Lecture 26 Page 5 of 11
Metric Dimensions
All metric dimensions are in units of millimeters. Below are a few
examples of architectural drawings in metric dimensions:
Lecture 26 Page 6 of 11
Lecture 26 Page 7 of 11
Example 5 LRFD Steel Beam Analysis
GIVEN: A simply-supported ASTM A992 steel W18x35 beam is loaded as
shown (all loads are factored and includes beam weight). Assume the
beam is continuously laterally braced.
REQUIRED:
1) Determine the maximum factored moment in units of kN-m.
2) Determine the plastic section modulus, Zx of the beam in units
of mm3.
3) Determine the LRFD design moment of the beam Mn in units of
kN-m.
4) Determine if the beam is adequate in moment.
w = 3 kN/m
11 m
wu L2
Mmax =
8
(3kN / m)(11m) 2
=
8
Step 2 - Determine the plastic section modulus of the beam in units of mm3:
Lecture 26 Page 8 of 11
Step 3 - Determine the LRFD design moment of the beam Mn in units of kN-m:
From LRFD:
See table above
Mn = 0.9FyZx
Zx = 1,089,742 mm3
= 338,360,000 N-mm
kN m
= 338,360,000 N-mm x x
1000 N 1000mm
Mn = 338.4 kN-m
Lecture 26 Page 9 of 11
Example 6 ACI Concrete Beam Analysis
GIVEN: The rectangular concrete beam shown below. All loads are
factored and includes beam weight. Use fc = 25 mPa and 3 20 mm
diameter bars having fy = 400 mPa.
REQUIRED:
1) Determine the ACI 318 factored moment capacity, Mu of the beam in
units of kN-m.
2) Determine the ACI 318 factored moment capacity of the beam in units
of Kip-Feet.
250
350
act f y
Mu = 0.9Asfyd(1 - 0.59 )
f 'c
(20mm) 2
where: As = 3 bars
4
2
= 942.5 mm
As
act =
bd
942.5mm 2
=
(250mm)(350mm)
= 0.0108
Lecture 26 Page 10 of 11
act f y
Mu = 0.9Asfyd(1 - 0.59 )
f 'c
(0.0108)(400 N / mm 2
= 0.9(942.5 mm2)(400 N/mm2)(350 mm)(1 - 0.59 )
25 N / mm 2
= 106,640,000 N-mm
kN m
= 106,640,000 N-mm x x
1000 N 1000mm
Mu = 106.6 kN-m
Kip Feet
Mu = 106.6 kN-m x See conversion
1.3559kN m table above
Mu = 78.6 Kip-Feet
Lecture 26 Page 11 of 11