Beruflich Dokumente
Kultur Dokumente
PUBLICATION: 17A-04-S
ISSUE No. & DATE: 17 10/09
Registered Company: Thorn Security Ltd. Registered Office: Dunhams Lane Letchworth Garden City Hertfordshire SG6 1BE
MX/MZX
17A-04-S
17 10/09
PAGE 2 of 40
EQUIPMENT: MX/MZX
PUBLICATION:
17A-04-S
ISSUE No. & DATE:
17 10/09
1. GENERAL INFORMATION
WARNING:
This manual is written for firmware Version 17.
ENSURE THAT ANY EXTINGUISHING
As the MX/MZX equipment form a fire control system, SYSTEMS ARE MADE SAFE
the following periodical checks must be carried out in order (SEE 05A-03-S1) BEFORE CARRYING OUT
to comply with the requirements of BS 5839 : Part 1 and THE DESCRIBED PROCEDURES.
marine customer requirements to ensure the continued
correct operation of the system. ANY AUXILIARY DEVICES CONNECTED TO
The following checks and servicing must be carried out: THE SYSTEM MAY OPERATE DURING THE
FOLLOWING PROCEDURES UNLESS
Weekly checks of the controller, one DISABLED. NOTIFY THE CUSTOMER
detector per zone and the fire detection PRIOR TO ANY DISABLEMENT.
sounders.
Three-monthly checks.
Annual visual, fixture security and zone
checks on all units. Note: The EVACUATE or FIRE ALARM, SILENCE,
Three-yearly check of all detectors. RESET, DAY/NIGHT and INVESTIGATE
DELAY keys on the front panel are inoperative
Four-yearly replacement of batteries. until the keyswitch has been turned to the
enable position.
e) Set one device (either a callpoint or detector) g) Visually check the installation to ascertain
from one zone into alarm and check that the whether structural or occupancy changes
system responds as follows: have affected the requirements for the siting
of manual callpoints, detectors, line isolator
The controllers internal buzzer sounds in base, sounders or sounder bases.
a continuous tone.
PAGE 4 of 40
EQUIPMENT: MX/MZX
PUBLICATION:
17A-04-S
ISSUE No. & DATE:
17 10/09
Note: Any changes must be made the subject of a 2.5 THREE-YEARLY CHECKS
report to the Service Department.
In addition to the normal yearly checks, filters of VESDA
Aspirating detectors must be changed.
h) Ensure that a clear space of at least 750 mm
is preserved in all directions below heat and
smoke detectors, that they are correctly sited 2.6 FOUR-YEARLY CHECKS
and that all manual callpoints remain In addition to the normal yearly checks, internal standby
unobstructed and conspicuous. batteries must be renewed.
i) Ensure that no physical obstruction has been
placed in the line-of-sight between flame
detectors and the protected area. CAUTION:
PAGE 6 of 40
MX/MZX
10/09
ALPHANUMERIC KEYPAD
1 2
ABC
3
DEF
First Fire
Zone 002 B002 SCROLL UP
1st Floor Corridoor
Room 117 4 5 6
GHI JKL MNO
Last Fire 002
Fig. 1
Zone 030 B055
4th Floor
Washroom / Window 7 8 9
PQRS TUV WXYZ
General Information
SCROLL DOWN
View More
SOFTKEYS
EQUIPMENT: MX/MZX
PUBLICATION:
17A-04-S
ISSUE No. & DATE:
17 10/09
ALPHANUMERIC
KEYPAD
Main
Main menu
menu 2 3
1
SYSTEM
SYSTEM 1 2 3
11 -- Accept
Accept Events
Events SCROLL * ABC DEF
Wed,
Wed, 01-Mar-08
01-Mar-08 22 -- Actual
Actual Status
Status * ABC DEF
14:15
14:15 33 -- Isolate/De-Isol
(De-) Isolate UP
44 -- Time / Date
Time / Date 4 5 6
Company
Company Name
Name 55 -- Event
Event Log
Log 4 5 6
66 -- View/Print
View/Prn StaData GHI JKL MNO
General
General 77 -- Service
Service GHI JKL MNO
8 - Configuration
99 -- Test
Test Buzzer,
Buzzer, 7 8 9
LED's
LED's Display
Display 7
PQRS TUV8 9
WXYZ
Alarm
Alarm Count:
Count: 0021
0021 PQRS TUV WXYZ
SCROLL
0000 DOWN
Back
Back SounSIL 0
0
F1 F2 F3 F4 F5
F1 F2 F3 F4 F5
SOFTKEYS
GENERAL
GENERAL PROTECTION SOUNDERS
SOUNDERS SIGNALLING PANEL
GENERAL
GENERAL SYSTEM SOUNDERS
SOUNDERS SIGNALLING CONTROLLER
FIRE ACTIVATED ACTIVATED ACTIVATED POWER ON
FIRE
FAULT
PRE ALARM
FAULT
ACTIVATED
FAULT
ACTIVATED
FAULT
POWER ON
MAINS FAULT
FAULT DAY MODE FAULT FAULT MAINS FAULT
DISABLED DISABLED DISABLED DISABLED SYSTEM FAULT
DISABLED STATUS 1 DISABLED DISABLED SYSTEM FAULT
TEST DAY MODE SYSTEM
TEST STATUS 2
ZONE DISPLAY
ZONE DISPLAY
1 11 21 31 41 51 61 71
1 11 21 31 41 51 61 71
2 12 22 32 42 52 62 72
2
3 12
13
22
23
32
33
42
43
52
53
62
63 72
73
3
4 13
14 23
24 33
34 43
44 53
54 63
64 73
74
4
5 14
15
24
25
34
35
44
45
54
55
64
65 74
75
5
6 15
16 25
26 35
36 45
46 55
56 65
66 75
76
6
7 16
17 26
27 36
37 46
47 56
57 66
67 76
77
7
8 17
18 27
28 37
38 47
48 57
58 67
68 77
78
8
9 18
19 28
29 38
39 48
49 58
59 68
69 78
79
9
10 19
20 29
30 39
40 49
50 59
60 69
70 79
80
10 20 30 40 50 60 70 80
I
I
0
0
PAGE 8 of 40
MX/MZX
10/09
1 2 3 1 9
* ABC DEF
2 10
4 5 6 3 11
GHI JKL MNO
4 12
Fig. 3
5 13
7 8 9
PQRS TUV WXYZ 6 14
7 15
0 8 16
F1 F2 F3 F4 F5
SILENCE SILENCE DAY INVESTIGATE
RESET EVACUATE
BUZZER RESOUND NIGHT DELAY
1 2 3
* ABC DEF
4 5 6
GHI JKL MNO
7 8 9
PQRS TUV WXYZ
0 1
F1 F2 F3 F4 F5
ZONE DISPLAY
1 5 9 13 17 21 25 29
2 6 10 14 18 22 26 30
3 7 11 15 19 23 27 31
4 8 12 16 20 24 28 32
Supervisor
Engineer
Engineer
In order to avoid repetition, however, the general procedure Enable
for entering a PASSCODE is described as follows: Key
MAIN MENU ON
3.4 POINT DEFINITIONS Accept Events ON
Real point - A physical input/output point
View Status ON
Pseudo point - A software derived fault number
eg, Communications Fault or Isolate/De-Isolate ON
RAM Fault Time/Date ON
Timer - Point activated by user Set time/Date ON
(MZX CONSYS) configured timer Summer/Winter ON
Configuration ON
Change Text ON
Insert Point ON
Delete Point ON
Modify Point ON
Auto Configure ON
Table. 1 Menu Options and Access Levels
* Key OFF F1 key View
PAGE 10 of 40
EQUIPMENT: MX/MZX
PUBLICATION:
17A-04-S
ISSUE No. & DATE:
17 10/09
Use the F4 Key << and F5 key >> keys to move between
events. Usr F3 Accept to accept an event.
Back
The following type of screen will be displayed: The fifth line shows the Point description (defined at
configuration).
Note: If the panel is in a networked system, the panel The sixth line shows the device type.
number will be shown as in the following
example. Actual Status IP can be in one of the following states:
Normal
View Status Fault
MX Panel
Point Active
Wed, 01-Mar-08
14:15 Panel
PreAlarm
02 Actual Status OP can be in one of the following conditions:
Company Name Loop Point
General
A 001 On
Off
Pulse 1
Pulse 2
Back >> - + Enter Selecting 4 Zone will display the following type of screen:
Loop Point (Addressable Loop) Screen display (the asterisks are not displayed on the
screen).:
Use the +, - and >> keys to select the
required Loop and Point, then press Enter *YES/NO
key.
**NONE /PARTIAL/ALL
RBus Point (Remote Bus)
Use the +, - and >> keys to select the
required RBus, Category and Point, then View Status
press Enter key. MX Panel
Zone 002
Local I/O Point (Field Interface Module) Thu, 26-Jul-07
14:15
South Building
1st Floor Corridoor
Use the +, - and >> keys to select the
required Category and Point, then press Company Name Alarm : NO*
Enter key. Fault : NO*
General Isolate : NONE**
Walk Test : NO*
The following type of screen will be displayed:
View Status
MX Panel _
Point Back +
Thu, 26-Jul-07 Zone 006 A007
14:15
Zone 06 Function Keys F3/F4 will decrement/increment the zone
Company Name Call alarm in room number.
CP 820
General
Description
Input Output Alarm Yes One or more devices of a zone
Normal in Alarm Mode
Fault Yes One or more devices of the
Back zone in Fault Mode
Isolate All All alarm input devices of the
Point Input and Point Output are displayed in the same
format. zone are Isolated
Isolate Partial At least one, but not all alarm
The top line shows the selected option. input devices are Isolated
The second line shows the Zone and Point number of the Walk Test Yes All alarm input devices of the
device. zone in Walk Test
The third line shows the Sector description (defined at
configuration).
The fourth line shows the Zone description (defined at
configuration).
PAGE 12 of 40
EQUIPMENT: MX/MZX
PUBLICATION:
17A-04-S
ISSUE No. & DATE:
17 10/09
Network Status
Non-LED Outputs 9
MX Panel Extinguish Controls (all) F2*
Nodes 0123456789
Wed, 01-Jan-09 0 Mm...... Fault Signalling (all) F3*
14:15 10 ..........
20 .......... Alarm Signalling (all) F4*
Company Name 30 ..........
40 .......... All Sounders F5*
General 50 ..........
60 ..........
70 .......... Note: Other options are available for some of the
80 .......... above:
90 ..........
1) * No extra options.
Back 2) ** The following options are available:
1 - All
See Table 1 for an explanation of the displayed codes. 2- In Fault
3 - Active
4 - Not Normal (either In Fault or Active)
3) *** The following options are available:
1 - All
2 - In Fault
Press 3 from the Main menu. The following screen will be The following screen shows an example detector isolation:
displayed:
Isolate/De-Isolate
Isolate/De-Isolate MX Panel Detectors
MX Panel Wed, 01-Mar-09 Zone 001
1 - Point 14:15
Wed, 01-May-09 2 - Point I/P only Zone 01
14:15 3 - Point O/P only Company Name
4 - By Function
Company Name
General Isolate
General All
In the Customer Operator access levels, only points on the Isola 020 Success :0020
addressable loop can be isolated or de-isolated. Iso.S 004 Matches :0020
Isolations are counted and displayed (eg, Isol 001). If only Back
the input or output of a point is isolated, this is counted as a
All log and LED outputs are as configured but loop and FIM
complete isolation of the point.
outputs are not switched.
PAGE 14 of 40
EQUIPMENT: MX/MZX
PUBLICATION:
17A-04-S
ISSUE No. & DATE:
17 10/09
This is a timed function of one hour, when the time expires Summer/Winter
the mode is automatically ended. The timer can be MX Panel Summertime
extended at any time to the original one hour.
Wed, 01-Jan-09 28-Mar-09 +1h
Local panel only - not available for network. 14:15 28-Mar-10 +1h
28-Mar-11 +1h
Company Name 28-Mar-12 +1h
3.10 TIME/DATE 28-Mar-13 +1h
General 28-Mar-14 +1h
Press 4 from the Main menu. The following type of screen 28-Mar-15 +1h
28-Mar-16 +1h
will be displayed: 28-Mar-17 +1h
28-Mar-18 +1h
Time / Date
MX Panel
1 - Set Time/Date Back Winter
Thu, 26-Jul-07 2 - Summer/Winter
14:15 These screens show the date of change between Summer
Company Name and Winter time and cannot be changed, the information is
configured in MZX CONSYS, use F5 to toggle between
General Winter and Summer.
Dates are not shown on a T2000 Marine panel.
Back
Back >> - + Save
3.11.1 VIEW EVENT LOG
Use the >> key to move the cursor between options, enter This option allows all events in the event log to be viewed or
date and time values via the keypad. printed.
Note: Select option 1 from the Event Log menu, the following
type of screen will be displayed:
1) When a value has been changed, F5 shows
Save, use this key when all editing has been
completed. Event Log
MX Panel
2) Months January to September can also be
entered with the keypad: Thu, 26-Jul-07 Zone 000
14:15 System Zone
1 = January
Company Name TEST FINISHED
...................
9 = September General 04-Feb-02 19:30:00
- Empty -
Information only
3.10.2 SUMMER/WINTER
Press 2 from the Time/Date menu. Select summer, the 0001/0010
following type of screen will be displayed:
Back << << >> >>
2009 Tyco Safety Products PAGE 15 of 40
Registered Company: Thorn Security Ltd. Registered Office: Dunhams Lane Letchworth Garden City Hertfordshire SG6 1BE
MX/MZX
17A-04-S
17 10/09
The latest event is displayed, use the << and >> keys to 3.11.3 FILTER
scroll through the log and the |<< to move to the back of Select option 3 from the Event Log menu, the following
the log or the >>| key to move to the front of the log. type of screen will be displayed:
0001/0010 - The first number is the actual
position in the event log (1 means it displays Event Log
the newest event log entry. The second MX Panel
number displays the number of entries in the
1 - Fire -
Thu, 26-Jul-07 2 - Gas Alert -
event log (max. 3,000). 14:15 3 - Pre Alarm -
4 - Supervisory -
Company Name 5 - Fault -
6 - Isolate -
The newest/last event will be displayed when the Event Log General 7 - Test Mode -
is entered. 8 - Warning -
9 - Information -
PAGE 16 of 40
EQUIPMENT: MX/MZX
PUBLICATION:
17A-04-S
ISSUE No. & DATE:
17 10/09
Select option 2 from the View/Print Status menu, the Back Print
following type of screen will be displayed: Press F5 to print Point Values, values for all devices on the
loop will be printed.
Pts Untested/Failed
MX Panel 3.12.4 VIEW FAULTS
Thu, 26-Jul-07 Total : 004
14:15 Select option 4 from the View/Print Status menu, the
Zone 001 -001 B following type of screen will be displayed:
Company Name Point Text
--------------------
General Zone 001 -002 B View Faults
Point Text MX Panel
Total : 002
Thu, 26-Jul-07
14:15 Zone 000 R10
Zone 000 R12
Company Name
Back Print
General
Note: If the panel is part of a networked system,
another screen is displayed before the above Flt P 002
screen where the panel number may be
selected.
Back Print
Press F5 to print the Untested/Failed points.
Points which are not tested or points which return the wrong Press F5 to print.
condition are then listed.
3.12.5 VIEW LOOP POINT COUNTERS Detected points from left, right and both
sides are equal.
This option is view only. Select option 5 from the View/
Print Status menu, the following screen will be displayed: If all conditions are not satisfied, the ATTENTION screen
will be displayed showing the relevant counters.
Loop Point Counters
MX Panel Loop Point Counters
Panel MX Panel
Thu, 26-Jul-07 02 Counter
14:15 Thu, 26-Jul-07 Loop : A
Loop 14:15 A T T E N T I O N
Company Name A
Company Name Configured : 010
General
General Conf. & Ident: 009
Note: Only the Loop will be shown if the panel is not Configured - the number of points
networked. configured in CONSYS.
Select the required panel (only if the panel is networked) and Conf & Ident - shows how many points are
loop, then press the Enter key. The following message is connected, identified and configured on the
displayed: loop.
Please Wait... Not Conf. - shows how many points were
identified on the loop but not configured in
CONSYS.
for approximately 2 minutes until the count is complete, if
no faults are found, the following type of screen will be
Both Sides/Left Side/Right Side - Shows
how many points on the loop are recognised
displayed: by the panel. Left Side and Right Side is
the count from both sides. Both Sides
Loop Point Counters means the detection of a closed loop
MX Panel
Counter Note: If the value of Conf & Ident is different to the
Thu, 26-Jul-07 Loop : A
14:15 PASSED number of installed devices, multiple reserved
address may be the cause.
Company Name Configured : 010
General 3.12.5.1 DETAILS
Press the Details key (F2), the following type of screen
will be displayed:
PAGE 18 of 40
EQUIPMENT: MX/MZX
PUBLICATION:
17A-04-S
ISSUE No. & DATE:
17 10/09
All 250 addresses may be displayed using the >>) key. 3.12.6 FORCED POINTS
The connection detail of each point is shown by the Select option 6 from the View/Print Status Menu. The
following symbols: following type of screen will be displayed:
o OK: point connected, configured and identified
(eg, point 33 and points 60 to 64) Forced Points
MX Panel Input:
Point was configured (in MZX CONSYS) but Total: 1
c Wed, 01-Jan-99
not connected or identified (eg, point 21)
00:01
Point was not configured but connected (eg, Zone 001 A001
u Company Name CO Device
point 6)
General
Function key F2 scrolls through the loop.
3.12.5.2 SCAN
Press the Scan key (F3), the following type of screen will Back Output Print
be displayed:
Pressing Iso&For (F2) will display the following screen: Select option 1 from the Fire Inputs menu, the following
screen will be displayed:
Active Points
MX Panel Isolated Forced pts Active Fire IPs
Wed, 21-Aug-07 Total : 0 MX Panel
08:01 Panel: 1
Wed, 21-Aug-07 Page : 0/ 0
Company Name 08:01
Company Name
General
General
Back
Back Select option 3 from the Fire Inputs menu, the following
screen will be displayed:
Screens for options 2, 3, 4, 5 and 6 are the same type as for
option 1 Fire Inputs.
Isolated Fire IPs
MX Panel
Panel: 1
3.12.8.1 FIRE INPUTS Wed, 21-Aug-07 Page : 0/ 0
08:01
Select option 1 from the By Function menu, the following
Company Name
screen will be displayed:
General
Fire Inputs
MX Panel
1 - Active
Wed, 21-Aug-07 2 - Fault
08:01 3 - Isolated
Back
Company Name
General
Back
PAGE 20 of 40
EQUIPMENT: MX/MZX
PUBLICATION:
17A-04-S
ISSUE No. & DATE:
17 10/09
Loop
Only with Area as All or Zone.
Walk Test of all loops or of a specific loop (A, B, C, D, E,
F, G or H).
PAGE 22 of 40
EQUIPMENT: MX/MZX
PUBLICATION:
17A-04-S
ISSUE No. & DATE:
17 10/09
CAUTION:
TestZ Number of zones which are in Walk
Test. (The pointer is only counted if all
points of a zone are in Walk Test. If one
THE FINISHING OF A WALK TEST IS ONLY
detector on the zone is switched off, the
POSSIBLE IF ALL POINTS IN THE WALK
TEST ARE INACTIVE. counter is not decreased. In the case of
Walk Test for one point, the counter is
only decreased if that point is the only
point on the zone).
3.13.1.2 SOUNDERS
Select Sounders in the Type field. Press F3 for a display of selected settings.
No results will be shown on the display. The selected Press F2 for details of the Walk Test (see 3.12.5.1, page 16
sounders will be activated in a configuration specified for details).
mode.
Press F5 to end Walk Test.
3.13.1.3 POINT
Select the following settings: CAUTION:
Back
Back Print
To reset the Fire Alarm Cycle Count, proceed as follows: Press F5 to print the Maintenance Request.
Back
PAGE 24 of 40
EQUIPMENT: MX/MZX
PUBLICATION:
17A-04-S
ISSUE No. & DATE:
17 10/09
3.13.2.4 VIEW/RESET SOFTWARE Press 7 from the Maintenance menu. The following type of
INITIALISATION COUNT screen will be displayed:
On options 3 and 6 when the option is Enabled/Disabled the Select the type of point as described in Section 3.7:
word Commissioning will be displayed, even with the
keyswitch turned to the off position. This will only
Loop Point (Addressable Loop)
Use the +, - and >> keys to select the
disappear when the option is re-enabled/re-disabled. required Loop and Point, then press Enter
Pressing F4 (>>) will show further menu points. key.
RBus Point (Remote Bus)
Use the +, - and >> keys to select the
3.13.3.1 FORCE DEVICE OUTPUTS required RBus, Category and Point, then
Press 1 from the Diagnostics menu. press Enter key.
Select the type of point as described in Section 3.7: Local I/O Point (Field Interface Module)
Use the +, - and >> keys to select the
Loop Point (Addressable Loop) required Category and Point, then press
Enter key.
Use the +, - and >> keys to select the
required Loop and Point, then press Enter
key. Force Device Input
MX Panel
RBus Point (Remote Bus)
Wed, 01-Mar-00
Zone 002 B007
1st Floor Corridoor
Use the +, - and >> keys to select the
required RBus, Category and Point, then 14:15 Room 117
801 H
press Enter key. Company Name
Status: Unforced
Local I/O Point (Field Interface Module) General
Use the +, - and >> keys to select the
required Category and Point, then press 1 - Force ON
Enter key.
PAGE 26 of 40
EQUIPMENT: MX/MZX
PUBLICATION:
17A-04-S
ISSUE No. & DATE:
17 10/09
Back Start
Press 4 from the Service Menu, the following screen will be
displayed:
Press F4 to start the device poll, F5 will change to End.
Press F5 to end the device poll. Calibrate DDM800
MX Panel
3.13.3.5 CHANGE ADDRESS Fri, 01-Aug-08 Panel: 01
14:15 Loop: All
When selected, this option allows the address of a device to Point: All
be changed. Company Name
Press 7 from the Diagnostics menu. The following type of General
screen will be displayed:
Change Address
MX Panel
Loop : B Back >> - + Enter
Wed, 01-Mar-00
14:15 Old Address : 017 Select the Panel( if networked), Loop and Point address of
Type : 801H the DDM800 to be calibrated, pressing F5 will store the
Company Name
New Address : 025 returned current value for the DDM800.
General
3.13.5 RESTART SYSTEM
Press 5 from the Service Menu, the following screen will be
displayed:
Back New - + Enter
Restart System
Use the >>, - and + keys to select the options. Press MX Panel
Enter when all options have been selected. Thu, 26-Jan-09
00:01
1 - Restart Panel
CAUTION: Company Name
DO NOT SELECT A NEW ADDRESS THAT IS General
ALREADY BEING USED ON THE LOOP.
Back
Pressing 1 will restart the system.
Back
3.13.6.1 FAST FAULT MODE Back
When selected, this option allows faults to be detected in 5 As Configured - means that the devices will operate as they
seconds. have been programmed in MZX Consys.
Press 1from the Switches menu. The following screen will OFF - regardless of how the devices have been configured
be displayed: in MZX Consys the Fast Logic algorithm is not used.
Back
PAGE 28 of 40
EQUIPMENT: MX/MZX
PUBLICATION:
17A-04-S
ISSUE No. & DATE:
17 10/09
3.13.6.5 DETECTOR POWER UP Configuration changes across a network are possible, but
changes to more than one panel at a time MUST NOT be
Press 4 from the Switches menu. The following screen will attempted within one session. When a panels
be displayed: configuration has been changed, it must be restarted using
menu option 9 Restart.
Detector Power Up Failure to comply with these restrictions may lead to
MX Panel Status: ENABLED unpredictable effects or system instability
Wed, 01-Mar-08
14:15 2 - Disable 3.14.1 CHANGE TEXT
Company Name Press 1 from the Configuration menu. The following
General screen will be displayed:
Change Text
MX Panel 1 - Point Text
Wed, 01-Mar-08 2 - Zone Text
14:15 3 - Sector Text
Back 4 - Panel Text
Company Name 5 - Info Text
This allows the monitoring of detector removal to be
disabled. General
3.14 CONFIGURATION
Press 8 from the Main menu. The following screen will be
displayed: Back
3.14.1.1 POINT TEXT MODIFY
Configuration
MX Panel 1 - Change Text Press 1 from the Change Text menu. The following screen
Wed, 01-Mar-00 2 - Insert Point will be displayed:
14:15 3 - Delete Point
4 - Modify Point
Company Name Point Text Modify
MX Panel
General 7 - Autoconfig.
Wed, 01-Mar-08 Loop : A
9 - Restart 14:15 Point : 001
Company Name
General
Back
Menu option 9 will only be displayed if an action has been
carried out and saved. The relevant action will only be
carried out after the panel has been restarted.
Back >> - + Enter
After an action has been carried out, not all menu options
from the configuration menu are displayed. Select the required loop and point then press Enter. The
following type of screen will be displayed:
RESTRICTIONS ON THE USE OF THE
FOLLOWING OPTIONS
Point Text Modify
When using Configuration menu options 2 to 4, ALWAYS MX Panel
commit configuration changes by using option 9 Restart Zone 255 -007 A
before leaving the panel. Wed, 01-Mar-08 Old text
14:15 Callp. alarm room
Avoid inactivity timeouts. Company Name New text
NEVER use the Back option from the configuration General
menu if option 9 Restart is showing.
If you do not want to commit changes, by using 9 Restart,
option, turn the keyswitch to OFF position to avoid a
timeout situation, do NOT USE the Back option.
Back >> - + Enter
>> - copies the old text to the New text position. 3.14.1.2 ZONE TEXT MODIFY
- moves the cursor back one position. Press 2 from the Configuration menu. The following screen
will be displayed:
+ moves the cursor forward one position.
Modify the old text or insert new text using the
Zone Text Modify
alphanumeric keypad, when finished press Enter. MX Panel
Pressing the scroll up key allows text to be entered in Wed, 01-Mar-08
upper case. 14:15 Zone : 001
Pressing the scroll down key changes to lower case Company Name
text.
General
The message Save Data? appears and the functions change
F4 to Yes and F5 to No. Selecting F5 allows the text
modifications to be changed.
Selecting F4 Yes displays the message:
Please wait..... Back - + Enter
Select the required and press Enter. The following type of
screen will be displayed:
then the following screen is displayed:
Back
Only Change Text and Restart are available allowing
more points to be changed or using Restart to allow the
changes to take effect.
PAGE 30 of 40
EQUIPMENT: MX/MZX
PUBLICATION:
17A-04-S
ISSUE No. & DATE:
17 10/09
Back
Back - + Enter
Back
Back It is now possible to change the text for another Panel.
Selecting F1 Back will display the following screen:
3.14.1.4 PANEL TEXT MODIFY Configuration
Press 4 from the Configuration menu. The following MX Panel 1 - Change Text
screen will be displayed: Wed, 01-Mar-08
14:15
Panel Text Modify Company Name
MX Panel Panel 00 General
Wed, 01-Mar-08 Old Text 9 - Restart
14:15 ADT
Company Name New Text
General
Back
PAGE 32 of 40
EQUIPMENT: MX/MZX
PUBLICATION:
17A-04-S
ISSUE No. & DATE:
17 10/09
Save data? Use the >> key to move between the options, use the +
and - keys to select the type of point and zone number.
Back Yes No
When finished, press Enter, the message Please wait...
3.14.2 INSERT POINT will be displayed then:
WARNING: Configuration
MX Panel
ONLY SUITABLY QUALIFIED PERSONNEL Wed, 01-Mar-00 2 - Insert Point
IN INTRINSICALLY SAFE SYSTEMS MUST 14:15 3 - Delete Point
4 - Modify Point
BE ALLOWED TO INSERT INTRINSICALLY
SAFE EQUIPMENT. Company Name
General 7 - Autoconfig.
9 - Restart
Connect the new device(s) to the addressable loop, when a
fault has been generated, Accept the fault(s).
Press 2 from the Configuration menu. The following screen
will be displayed: Back
Press 9 to complete the configuration or 2 to insert
another point.
Back
Back
Press 9 to complete the configuration or 3 to delete
another point. Press 9 to complete the configuration or 4 to modify
another point.
PAGE 34 of 40
EQUIPMENT: MX/MZX
PUBLICATION:
17A-04-S
ISSUE No. & DATE:
17 10/09
3.14.5 AUTOCONFIGURATION b)
Autoconfiguration
Note: This option should only be used on a new MX Panel
system with an empty configuration and should
not be for additions to the system. Wed, 01-Mar-00 Panel : 01
14:15 Loop : A
Topology : Loop
Company Name Zone : 001
Press 7 from the Configuration menu. The following screen 015 from left
will be displayed: General 015 from right
015 from both
Autoconfiguration
MX Panel
Wed, 01-Mar-00 Panel : 01
14:15 Loop : A Abort Details Enter
Topology : Loop
Company Name Zone : 001 Pressing F2 (Details) will display the following type of
screen (see also Section 3.11.5, View Loop Point Counters):
General
c)
Autoconfiguration
MX Panel
Counter
Back >> - + Enter Loop : A
Wed, 01-Mar-00
14:15 A T T E N T I O N
Panel will only be displayed if it is part of a networked
system. Company Name Configured : 000
Select the panel, Loop, Topology (Loop or Spur) and Zone General
(the Zone number is selected will be allocated to all Unconfigured: 015
devices), then press F5 Enter, the following screen will be
displayed.
Pressing F3 (Scan from step c) will display the following Pressing F2 (Details) will display the following screen:
type of screen:
g)
Result
e) MX Panel
Loop Point Counters View details of
MX Panel Left / Right Scan Wed, 01-Mar-00
Loop : A 14:15 1 - Added point
Wed, 01-Jan-00 Point 0123456789
14:15 0 : ......*... Company Name
10 : ..........
Company Name 20 : .*........ General
30 : ...*...... Flt P 015
General 40 : ..........
50 : ..........
60 : ..........
70 : ..........
80 : ..*.......
90 : .*....*... Back
Back >> Pressing 1 from the alpha numeric keypad will display the
following type of screen:
The stars denote devices that will be configured.
h)
Pressing F2 (>>) will display further point screens. Result
Pressing F5 (Enter from step b) will display the following
MX Panel
Added Points
type of screen: Wed, 01-Mar-00
14:15 Panel : 01
f) Loop : A
LoopScan Company Name Zone : 001
Point : 006
MX Panel Mode : 2
General
Wed, 01-Jan-00 Device Type
14:15 RIM800
Please wait...
Company Name 001/015
General
Back << >> >>|
<<, >> and >>| navigate through the points.
Pressing F5 (Save) from step f) will display the following type
of screen:
Abort
i)
When the Loop Scan has been completed, the following Result
type of screen will be displayed: MX Panel
Wed, 01-Mar-00
Result 14:15
MX Panel Company Name no errors
015 points added
Wed, 01-Mar-00 General 000 points unchanged
14:15 000 pnt. with error
Company Name no errors
015 points added
General 000 points unchanged Save data?
000 pnt. with error
Yes No
Pressing F4 (Yes) will save the configuration. When the save
is complete, the controller will re-initialise.
Abort Details Save
If errors are detected, the following type of screen will be
displayed:
PAGE 36 of 40
EQUIPMENT: MX/MZX
PUBLICATION:
17A-04-S
ISSUE No. & DATE:
17 10/09
8 - Multi-Channel Device
Autoconfiguration There is currently only limited support for Multi-
MX Panel
Channel Devices, any conflict due to a known Multi-
Wed, 01-Mar-00 Points failed Channel Device type will receive this error code. Note
14:15 unless the Device has an entry in the 'Device Uses'
Panel : 00
Company Name Loop : B table, Auto-Configuration will not be aware that it is in
fact a Multi-Channel Device, and Error 4 ('Device Not
General Point : 001 Supported') will be assigned instead.
Device Type: 9 - Change of Device Type Not Allowed
Error : 008
If the Auto-Configuration option 'Only add new' is
Point 001/001 selected, then it is not possible to change the Device
Type of an existing, configured Point.
Back
The following lists the error code descriptions:
3.15 TEST BUZZER/LEDs/DISPLAY
1 - Unknown Error
Selecting option 9 from the Main menu causes the following to
It was determined that there was an Error with the happen for approximately 2 seconds:
associated Point, but it was unable to be classified.
2 - Multiple Devices at Address
The LCD Backlight to extinguish
It was found that more than one Device responded at All LEDs to illuminate
the address specified. Internal buzzer to pulse
3 - Logical Zone Overflow
While adding Points for all the new devices found, WARNING:
thelimit for the maximum number of Points allowed
in a Logical Zone was reached. All new Devices BEFORE LEAVING SITE, ANY FORCED
found after this limit was reached will be assigned INPUT/OUTPUT MUST BE UNFORCED.
this error and will not be added. FAST FAULT, RATE OF RISE PROCESSING
4 - Device Not Supported OR SINGLE DEVICE POLL MODE MUST BE
SET TO THEIR DEFAULT SETTINGS.
For a new Point to be added by Auto-configuration,
any Device found must be allocated an entry in the
'Device Uses Configuration Table'. If a newly
discovered Device does not have such an entry, it will Any non-standard settings will display
be assigned this error code. COMMISSIONING on the bottom line of the LCD.
5 - Device Use Not Supported
For a new Point to be added by Auto-configuration,
any Device found must be allocated both an entry in
the 'Device Uses Configuration Table' and have at
least one 'Use' enabled. If a newly discovered Device
is found in the 'Device Use Table' but does NOT have
the appropriate 'Use' enabled, it will be assigned this
error code.
6 - Invalid Address
A new Device was found to be responding at an
Address not currently valid (e.g. '0')
7 - Too Many Points on Loop
While adding in Points for all the new devices found,
the limit for the maximum number of Points allowed
on a Loop was reached. All new Devices found after
this limit are assigned this error, they will not be
added.
PAGE 38 of 40
EQUIPMENT: MX/MZX
PUBLICATION:
17A-04-S
ISSUE No. & DATE:
17 10/09
XBUS
RBxxX1 - 40 ZONAL x ALARM
RBxxX41 - 80 ZONAL x FAULT
RBxxX81 SIGNALLING ACTIVE
RBxxX82 SIGNALLING FAULT
RBxxX83 SIGNALLING DISABLED
RBxxX84 PROTECTION EQUIPMENT FAULTY
RBxxX85 SOUNDERS ACTIVE
RBxxX86 SOUNDERS FAULT
RBxxX87 SOUNDERS DISABLED
RBxxX88 PROTECTION EQUIPMENT DISABLED
RBxxX89 PROTECTION EQUIPMENT ACTIVE
RBxxX90 DAY MODE ACTIVE
RBxxX91 MAINS FAULT O/P
RBxxX92 LAMP TEST SPECIAL
RBxxX93 FIRE O/P
RBxxX94 FAULT O/P
RBxxX95 DISABLED O/P
RBxxX96 TEST O/P
xx = MPM800 address
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9
Z o n e z z z Stand Alone
Z o n e p p . z z z Network
S e c t s s s Stand Alone
S e c t p p . s s s Network
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9
l n n n Loop Point Standard
l n n n . e e Loop Point Extended
R B r r c n n RBus Points
c n n Main Processor Points
N E T n n n Network Mode
R B u s n n RBus Mode
C O M 1 Device on COM1
C O M 2 Device on COM2
T L I c n n TLI Event
JM/mm
5th October 2009
PAGE 40 of 40