INSTRUCTIONS
DELUXE 36
MANUFACTURED HOME
FIREPLACES
36" Wood Burning Fireplaces
P/N 800,019M REV. B 04/2002
MODELS
BM36HC BM36HCD
This installation manual will enable you to obtain a safe, efficient and
dependable installation of your fireplace system. Please read and under-
stand these instructions before beginning your installation.
*Construction Materials:
framing materials paneling
particle board flooring
Figure 1 millboard dry wall
plywood etc.
9 "
(244 mm)
36"
(914 mm)
37"
(940 mm)
1 " Metal Safety Strips 20 "
27 " (513 mm)
(708 mm)
2"
(51 mm)
Figure 7 3 "
(84 mm)
7 "
(183 mm)
40"
(1016 mm)
Blocking 42"
(1067 mm)
Front
Figure 8
9 "
Step 3. Refer to fireplace drawings and speci- Combustion (251 mm)
Air Inlet
fications on pages 6 and 7 for framing dimen-
sions and details. Frame appliance enclosure as Gas Line 32"
Access (813 mm)
illustrated in Figures 10 through 13 on page 7. 37" Gas Line
(940 mm) Access
The header may rest on the top metal spacers, 1" 40"
(25 mm) (1016 mm)
but must not be notched to fit around them. 42"
(1067 mm)
Consult all local codes. Top View
Figure 9
Header
E 70" 1778 mm
F 35" 889 mm
A
G 20 " 524 mm Rough
E
Framing Face
B H 19 " 498 mm (Unfinished Shown)
Corner Installation
J 49 " 1257 mm
A
Figure 13
Fireplace Framing
Note: All framing dimensions calcu-
lated for 1/2" dry wall at the fireplace
face. If sheathing the chase or finish-
Figure 10 ing with other thickness materials,
calculations will need to be made.
Flue Type A B B
G
A
FTF8 Vertical 14 " 14 "
Ceiling Framing
A (368 mm) (368 mm)
Rough
Framing Face Figure 14
Inside Chase (Unfinished Shown) FTF8 Offset 30 14 " 25"
(368 mm) (635 mm)
Figure 11
Figure 19
14" Min.
Note: The nailing tabs and the area directly
behind the nailing tabs are exempt from the
Figure 17 Thimble
clearances described on page 5. Maintain at FM8-AT1
least 1/2" clearance from the firebox wrapper to
Step 3. Position appropriate thimble/firestop
the framing at the closest point of contact, Pitched Roof
spacer combination at ceiling and nail tempo-
directly adjacent to the flange.
rarily with two (2) 8d nails or equivalent fasten- Outer Pipe Of
Chimney
ers (see Figures 19,20 and 21 ). Use one fastener Note: Trim Thimble/
INSTALLING THE CHIMNEY SYSTEM on opposite sides to hold thimble/firestop spacer
Extension To Desired Length
And Pitch At The Rood Line
combination in position. Nail permanently, us- Thimble
14" Min.
Step 1. Before continuing, check the operation ing at least two (2) more fasteners, after chimney Extension
of the damper, as described on page 4, (refer to sections have been assembled through the
F8-TE26
13"
Figure 2 ). thimble/firestop spacer combination and after Thimble
any necessary adjustments have been made. FM8-AT1
Step 2. Using standard construction framing Firestop spacer must be secured by at least four
techniques, construct opening for chimney route (4) fasteners when completely installed. Pitched Roof
up through the ceiling(s) and roof or through an
outside chase. Note: If there is a room above ceiling level, Outer Pipe Of
14" Min. Chimney
firestop spacer must be installed on the bottom
Framing must maintain adequate minimum air side of the ceiling. If an attic is above ceiling level, Thimble
FM8-AT1
space clearance at all times. firestop thimble must be installed on the bottom
side of ceiling joist (Figure 18 ).
CAUTION: ALLOW MINIMUM 1" CHIMNEY
Bow Roof
AIR SPACE TO FRAMING MEMBERS THROUGH- Room Above
OUT CHIMNEY INSTALLATION. A MINIMUM 1"
AIR SPACE MUST BE MAINTAINED FROM ALL Figure 20
INSULATION AND BUILDING MATERIALS EX-
TENDING FOR ANY CONTINUOUS LENGTH SUR- WARNING: DO NOT ALLOW INSULATING
ROUNDING THE CHIMNEY. MATERIALS TO BE BLOWN INTO THE
SPACE INSIDE THE THIMBLE AND THE
Reference Figures 14 and 15 and their charts CHIMNEY. TO DO SO COULD RESULT IN
Firestop Spacer
for framing dimensions at Ceilings and Roofs.
A FIRE HAZARD.
Figure 18
Figure 21
Figure 28
2' Min.
Step 9. FTF locking bands, Model FLB, may be
required if the chimney extends too high above 3'
Min
the roof flashing. As a general rule, if the 10' 3'
chimney extends more than 6' above the roof Min
flashing, the use of locking bands is advisable
to strengthen the chimney assembly. Align
the locking band at the chimney joint. Locking
bands wrap around pipe joints equally cover-
ing the joints of both pipe sections. Use the nut
provided and TIGHTEN snugly. Do not over-
tighten as this might damage the chimney
section (refer to Figure 23 ).
Figure 31
all pre-selected components (fireplace and length of chimney used between elbows can-
chimney components from total desired not exceed 20' (see Figure 34 ). Example: If C1
Return
height.) = 10' then C2 cannot exceed 10'. Elbow
20'
Reference Vertical Elevation Chart and deter- If an offset exceeds 6' in length, each chimney Max.
mine the number of chimney sections (quan- joint beyond the first 6' of offset to the return
tity and length) required. elbow, must be secured by a No. 8 x " sheet B1
metal screw located at the underside of the Stabilizer
30 when passing through the floor or ceiling Figure 36 ). Be sure to drill only through the
area. Use the F8FS30-2 firestop spacer as shown outer chimney casting. Do not puncture the
in Figure 32. Support the chimney at floor or inner flue.
ceiling penetration with a FTF8 stabilizer if
distance of chimney below ceiling is 10' or
more. Maintain 2" minimum air space to com-
bustibles from chimney sections. The chimney Figure 33
must pass vertically through the attic space.
C2 (Inches) (Inches) Elbow Set Stabilizer 12" 18" 36" 48" (mm) (mm)
B2
4 15 1 0 0 0 0 0 102 400
9 24 1 0 1 0 0 0 229 622
A1
12 29 1 0 0 1 0 0 305 756
14 33 1 0 2 0 0 0 362 851
17 38 1 0 1 1 0 0 438 978
20 43 1 0 0 2 0 0 514 1111
B1
21 45 1 0 0 0 1 0 533 1149
C1
22 47 1 0 2 1 0 0 565 1207
25 52 1 0 1 2 0 0 641 1334
26 54 1 0 1 0 1 0 667 1378
27 55 1 0 0 0 0 1 686 1416
28 57 1 0 0 3 0 0 718 1467
29 59 1 0 0 1 1 0 743 1505
31 63 1 0 2 0 1 0 794 1600
32 64 1 0 1 0 0 1 819 1638
34 68 1 0 1 1 1 0 870 1734
A2 35 69 1 0 0 1 0 1 895 1772
37 73 1 0 0 2 1 0 946 1861
38 75 1 0 0 0 2 0 972 1905
C2 39 77 1 0 2 1 1 0 997 1956
B2
41 80 1 0 1 4 0 0 1054 2045
43 83 1 0 1 0 2 0 1099 2127
A1
44 85 1 0 0 0 1 1 1124 2165
45 87 1 0 0 3 1 0 1149 2223
46 89 1 0 0 1 2 0 1175 2261
48 91 1 0 2 0 2 0 1226 2324
B1
49 94 1 0 1 0 1 1 1251 2394
C1
50 95 1 0 0 0 0 2 1276 2432
51 97 1 0 1 1 2 0 1302 2483
54 103 1 0 0 2 2 0 1378 2616
55 104 1 0 1 0 0 2 1403 2654
56 106 1 0 2 1 2 0 1435 2705
58 109 1 0 0 1 0 2 1480 2788
62 116 1 1 1 0 3 0 1588 2965
65 122 1 1 0 1 3 0 1664 3099
67 125 1 1 2 0 3 0 1721 3188
Figure 34 69 128 1 1 0 0 1 2 1765 3270
70 130 1 1 1 1 3 0 1797 3321
73 136 1 1 0 2 3 0 1873 3454
75 139 1 1 0 0 0 3 1918 3531
79 146 1 1 1 0 4 0 2026 3715
80 148 1 1 1 0 0 3 2051 3759
Joints 82 151 1 1 0 1 4 0 2102 3848
83 153 1 1 0 1 0 3 2121 3886
st At
Chimney
nt ired
6'
Section
Joi qu
Pa
4'
r y Re
Eve ews
et Scr
ffs
'o n
t6 dI
fO
6'
r F qu
Fo Re
nts ws
Joi Scre
No
Figure 35
FTF8-30 Offset Elbow* B Step 2. Center inner slip section into inner flue
pipe-slip down.
A
Step 3. Center outer-locking section over outer
chimney pipe. Push down until locking joint has
firmly engaged. GROUND
WIRE
COVER PLATE
House Wiring Must Be Secured Replace Cover Plate
Step 4. Pull up slightly on return elbow to With The Appropriate Electrical After Electrical
Connector To The Fireplace Hook-Up
ensure locking joint has firmly engaged. Convenience Outlet Wiring
Figure 37
INSTALLING OFFSETS
Desired r value of listed Min. thickness If it is desired to elevate a marble hearth exten-
Required = material (per inch)x of Listed sion to a level of 5" or more above the floor
Thickness r value of desired Material surface. What combination of noncombustible
material (per inch) materials can be used to accomplish this?
Answer using r = 0.51 x 1" = .051 = " Using " of mortar to set the brick, R for the 3 "
" thickness Micore will be required. mortar is calculated as follows:
Combustible
Materials
Allowed In Fireplace
Shaded Area
Safe Zone
7" 1" 0-6/12 63L38 F8F6
Flashing 6/12-12/12 63L39 F8F12
45
12"
Min. Distance To
7" Protected Side Wall
Thimble Extension 26" 91L46 F8-TE26
Min. Distance To
12" Unprotected Side Wall
Figure 48
Stabilizer 63L25 FTF8-S4
INSTALLATION COMPONENTS
63L10 FTF8-12
63L13 FTF8-18
63L14 FTF8-36
Chimney Section 63L15 FTF8-48
Locking Band 63L60 FLB Forced Air Blower Kit 36L32 BFK36
Shipping Weight 175 lbs.
LHP