Sie sind auf Seite 1von 40

Deep Vacuum Principles and

Application
Introduction


Deep Vacuum Method of evacuation is the
only method to use to be sure the system is
thoroughly dry and free of non-condensibles
and leaks.


Callbacks waste time, money, and damage
your reputation in the customer s eye.
Measuring Evacuation:
Microns or Inches?

Micron is a unit of measurement
starting from a perfect vacuum (no
pressure) that is expressed in
linear increments.


One inch= 25,4000 microns thus
one micron= 1/25,400 of an inch.


When discussing vacuum in terms of
microns, this refers to total
ABSOLUTE pressure as opposed to
GAUGE pressure.
Microns versus Inches

Microns are more accurate unit of measure.


Starting from the same measuring point each time
(theoretical perfect vacuum).


Bourdon tube type gauge (analog manifold gauges)
cannot read fractions.


Bourdon tubes use atmospheric pressure as
reference point which is under constant change
throughout the day.
Deep Vacuum readings via
micron gauges are critical
for High SEER systems.
Vacuum Pump and How to
Select the Pump
The first mistake usually made
in selecting a pump:

The larger the pump, the


faster I can do the job

Pump Capacity has very little


to do with evacuation time in
refrigeration systems. Let s
review the reasons why:
Bigger isn t always Better

Refrigeration systems are constructed of several feet
of small diameter tubing.


These small tubes also have return bends and metering
devices that offer restriction during evacuation.


Add to that, service valves have 1/4 male flare ports
with only 3/16 orifices.


The only way to get more flow through a given orifice is
to increase the pressure across that orifice.


A vacuum pump DOES NOT create pressure that
increases flow
Remember these two
basic principles:
1. A vacuum pump creates a void toward which
the system pressure flows.

2. As pressure decreases in the system during


evacuation, flow also decreases. Therefore, it is
IMPOSSIBLE to increase the pressure or flow
through a gauge port with a larger pump.

Pumps in the 1.5 to 10 CFM class are adequate to handle
99% of air conditioning and refrigeration work.


CFM rule of thumb: CFM squared = maximum system
tonnage. Thus a 7 CFM pump is rated for 49 tons; a 3
CFM pump is rated for 9 tons.


Depending on the system line sizes of large-tonnage
systems, it is better to put two smaller, easily handled
pumps, at different locations.


This will overcome some of the pressure drop problems and
actually be faster than a single, large pump.
Vacuum Pump Construction

Rotary-vane deep vacuum pumps are best suited for
air conditioning and refrigeration service.


Piston-type pumps, due to the clearance necessary
between piston and head, are incapable of producing
deep vacuum.


Single-stage compressors, similar to hermetic
compressors, will not evacuate a system into a
micron range nor condense any moisture vapor in
the system.

Two stage pumps have the ability to produce consistently lower
pressures and are efficient at removing moisture vapor.


The pump should have a blank-off valve or attach an external
blank-off valve in order to perform isolation tests (pressure rise)
required in deep vacuum procedures.


The gas ballast should be on all pumps used in refrigeration. At
the start of evacuation, water vapor is quickly removed. If a
system is laden with moisture, the oil gets contaminated fast.


The gas ballast is a fine metering device connected to the second
stage of the pump that allows a small amount of relatively dry,
ambient air in to help prevent moisture vapor from condensing in
the oil.
Summary of Pump Needs

Two-stage, Rotary Vane


1.5 to 10 CFM with blank-off valve (or purchase external one)
and gas ballast (needed for refrigeration)


Systems are evacuated to 300-400 microns, so pump should be
able to produce a vacuum in the low micron range with a safety
factor of at least 25 microns total absolute.


Lightweight and rugged construction. This is a large dollar
purchase so invest in this product. You can buy a pump that is
not repairable and buy a new one every time something breaks,
or spend a little more money and have a pump that will last
through the years.
JB Eliminator VS. Platinum
PLATINUM

Micron Rating 15


Warranty 24 month


100% Made in the USA


100% Field Repairable


1/2 Exhaust
ELIMINATOR

2 stage direct drive, 1/2 HP 1725

Micron Rating 25 RPM motor

Warranty 24 month

GAS BALLAST

100% Made in the USA


100% Field Repairable
BLANK OFF ISOLATION VALVE
LIFT RING

3/8 Exhaust

Finned Aluminum Housing (reduces

2 stage direct drive, 1/2 HP heat)
1725 RPM motor
Digital Micron/
Vacuum Gauges
Tells you positively that the
system is noncondensible and
leak free.

Calibrated in microns of
mercury.

Evacuation is complete when a


system holds at 500 microns.

A compound gauge only indicates a vacuum is being produced. A


micron gauge is the only device that accurately reads the vacuum
pressure needed for deep vacuum.
How the micron gauge works

Heat sensing device, whereby the sensing
element is mechanically connected to the
system, generates heat.


The rate at which this heat is carried off
changes as the surrounding gases and vapors
are removed.


The output of the sensing element (either a
thermocouple or thermistor) changes as the
heat dissipation rate changes.
Micron Gauge: Selection and
Accuracy


Most important: RANGE


If a micron gauge s range is only 50 to 1,000
microns, you will not be able to determine
whether you are pumping against a leak or
against moisture. Need one with a range of
at least 50 to 9,000.

Next important: ACCURACY

Affected by two factors, extreme temperatures and
sensor contamination.


Vacuum sensor is calibrated on air. If refrigerant gas or
oil is drawn into the sensor, an erroneous reading will
occur.


Any oil entering into the vacuum sensor via the hose will
also affect accuracy. Improper shut down of the pump
after evacuation or power loss will suck back oil and
contaminate the hose.


A hose used for charging or testing will contain droplets
of system oil spurted into the hose when the Schrader
valve is open. If same hose is used for hook-up, oil will
collect in the gauge sensor. Use a dedicated hose with
o-ring for evacuation.

JB s DV-22 and Supernova DV-40 reference AVERAGE
accuracy readings. Between 250 and 6000 microns,
the units are +/- 10% AVERAGE accuracy.


Means if you take the reading on these units against
the MKS Baratron master gauge at each increment
displayed on the units, the readings are +/- 10% the
average.


Small differences in ranges are not significant:
Micron Range Micron Difference
60-100 10-20
200-350 30-40
500-700 50-60
900-1500 80-100
2500-4000 200-300
Evacuating through a
Gauge Manifold

Evacuate through a gauge manifold, ONLY IF, it is
an o-ring sealed, piston construction (all of JB s
manifolds are manufactured this way). Any other
type leak under vacuum.


Evaluate the center port. In order to handle the
full capacity of both the high and low sides, the
center intake should have a double-size flow path
throughout its length.
Leak-Proof Hook-Up

Deep vacuum has its own unique properties that require a
leak-free design- not just the manifold but all
components.


The only connecting lines that are absolutely vacuum
tight are soft copper tubing or flexible metal hose.


Charging and testing hose are designed for pressure
therefore, permeation still exists.


When checking pressure rise, the atmosphere will
permeate to the lower pressure in the hoses and the
micron reading will slowly rise.
Other Areas of Leaking
Gasket seal in the valve and hose
couplers is another source of leakage.

Seal is designed for charging and will


not give a perfect seal required in
deep vacuum service.

O-ring seals form around any


irregularities in the flare fitting.

When coupler is screwed down, the


result is a metal-to-metal seat and
the o-ring lays around the lip of the
flare to give a positive seal.
Connecting Lines

Summary of the hook-up:


Gauge manifold with two
1/4 I.D. connecting lines
to the system and a 3/8
connection to the pump via
line or fittings.
Note About Line Size

Much has been said about line size, which would
lead you to believe that the bigger the line
used to connect, the faster the job will be.


TRUE, except for the compressor s service
valves orifice is 3/16


Therefore, we only need to keep the connecting
lines I.D. larger than 3/16


This is one of the limiting time factors in
evacuation.
Time Savers

Evacuation should always be done from both
the low and high sides of the system.


Saves as much as 3/4 of the time when
evacuating from only one side


Short connecting lines will save some time,
but not nearly what is sometimes stated. In
relation to the lengths of tubing in the
system, we add very little restriction via
connecting lines.
Before You Start

Always a good idea to attach a micron gauge
to the vacuum pump to make sure the pump
pulls down to at least 50 microns.


If it doesn t, your pump oil is contaminated
and should be changed.


Do not shut off the blank-off valve on the
pump and expect the gauge to hold a
vacuum as the gauge will fall back to
atmosphere. (The sensor in the gauge is too
close to the pump and does not have time to
equalize).
Best Leak-Proof Micron
Gauge Hook-Up

JB s test unit, DV-29
creates a closed system
and eliminates any leakage
under vacuum.


The DV-29 consists of: 10
flexible metal line with o-ring
quick couplers, 90 deg. male
flare with 1/4 o-ring quick
coupler, ball valve with o-ring
quick coupler, and a valve
assembly with 1/4 male flare
connections

When designing your hook-up system, choose from the following
hoses, valve and couplers designed for leak-proof service in a
deep vacuum environment:


1/4 or 3/8 metal hose with o-ring couplers hooked up through
the manifold, pump, and micron gauge.


Quick coupler tee with o-ring seal. Most accurate readings are
obtained at compressor s high or low sides, use this
arrangement to tee off the gauge.


Ball valve with o-ring quick coupler to valve off gauge before
charging. Depending on the gauge, the sensors of the
electronic gauge will not take pressure beyond 1 to 100 lbs.
Depending on the hook-up, use this arrangement with a metal
hose or coupler.
Dispelling the Argument of No Deep
Vacuum on Heat Pumps
The word sublimation , the ability of moisture to
go directly from a solid ice to a vapor without
passing through a liquid state, is commonly used
in vacuum. This phenomenon is observed when
wash is hung out in the winter and freezes solid.
Still, in time, it dries due to sublimation. If lines
are in a cold ambient, it is possible to have ice in
the system. It will be removed during
evacuation. Of course, the addition of heat
(heat gun only) at these cold spots speeds up the
job.
Pressure Rise Test


The only difference between deep vacuum
and the methods used in the past is that we
can measure what we have done.


This is done through the pressure rise test.
Performing Pressure Rise Test

Using DV-29, Blank-off the high and low side
ball valves attached to the system.


Using general hook-up method, this includes
copper tubing or metal hose to the high and
low side, close blank-off valve on pump.
This will isolate the gauge from the pump.


Wait 5 to no more than 20 minutes to allow
system pressure to equalize. The reading
will be very close to what you actually have
in the system.
Interpreting the
Reading

A rapid rise during this
test to atmospheric
pressure indicates a
leak.


Slower rise to around
1500 microns indicates
moisture is present.


Under 500 microns,
evacuation is complete.

There are many recommendations regarding
evacuation levels, some which state
Evacuate system to below 200 microns .
This should NOT be considered. Note that
the word system is used here because it is
possible to evacuate piping or some
component other than the compressor to
below this level.


Refrigeration oil has a vapor pressure and,
by going below 200 microns, you will de-gas
particles of the refrigeration oil. Be aware
that if you change the makeup of the oil, it
will no longer be a true lubricating oil.
Evacuation brings out
the worst in a system
Remember that hydrofluoric and hydrochloric
acids (and moisture) can and do collect in oil.
They effectively destroy pull down and act as an
abrasive. If let sitting idle in a pump, they will
rust and corrode internal surfaces. Deep vacuum
needs a fill or two for EVERY job.
CHANGE YOUR OIL!!!

In order for your pump to pull a near perfect


vacuum, oil must be clean and moisture-free
throughout evacuation. Take a few minutes
during and after each job to drain, flush, and
refill. Doing so will keep your pump running at
peak performance and maintenance-free for
years.
An Ounce of Prevention
Always store your vacuum equipment plugged or
capped to prevent contamination due to
condensation and dirt. Because a slight cut or
dirt in the o-ring seals can cause leaks, the
mating flare fittings faces should be wiped and
checked for damage before hook up. Vacuum
pump oil makes a fine lubricant at these
connections.
Charging Methods
Charging by Superheat Method
Residential A/C or refrigeration systems equipped with TXV and
receiver, cap tube or metering device. Contact OEM for Superheat
Value.

Charging by Subcooling Method


Contact OEM for Subcool Value. Average subcool value is between
10 to 12 degrees F.
Testing Methods
Testing for charge by
Subcooling Method

Testing for charge by


Superheat Method
Cross Reference of Vacuum Measurements: Boiling
Temperatures of Water at Converted Pressures
For Questions or Further
Technical Assistance
please visit our website
www.jbind.com or call
our Technical Support
line at 800-323-0811

Das könnte Ihnen auch gefallen