Sie sind auf Seite 1von 14

This article has been accepted for publication in a future issue of this journal, but has not been

fully edited. Content may change prior to final publication.

A Non-Iterative Optimized Algorithm for Shunt


Active Power Filter under Distorted and
Unbalanced Supply Voltages
Parag Kanjiya, Vinod Khadkikar, Member, IEEE and Hatem H. Zeineldin, Member, IEEE,

voltage and current distortion, unbalanced supply voltages,


AbstractIn this paper, a single-step non-iterative optimized excessive neutral current, poor power factor, increased losses
algorithm for a three-phase four-wire (3P4W) shunt active power and reduced overall efficiency.
filter (APF) under distorted and unbalanced supply conditions is Active power filters (APF) are widely used to overcome
proposed. The main objective of the proposed algorithm is to such power quality problems [2-5]. There are two main APF
optimally determine the conductance factors to maximize the
supply side power factor subject to predefined source current control strategies for load compensation when the supply
total harmonic distortion (THD) limits and average power voltages are unbalanced and distorted [6-13]: (1) harmonic
balance constraint. Unlike previous methods, the proposed free (HF) source currents, and (2) unity power factor (UPF)
algorithm is simple and fast as it does not incorporate complex source currents. The HF strategy results in sinusoidal source
iterative optimization techniques (such as, Newton-Raphson and currents [6], while UPF strategy can achieve minimum root
sequential quadratic programming), hence, making it more mean square (rms) source current magnitudes. Additionally,
effective under dynamic load conditions. Moreover, separate
limits on odd and even total harmonic distortion have been the UPF strategy can provide effective damping to avoid any
considered. A mathematical expression for determining the resonance [7-8]. Both HF and UPF control strategies under
optimal conductance factors is derived using the Lagrangian sinusoidal and balanced supply will lead to identical
formulation. The effectiveness of the proposed single-step non- performance. However, when the supply voltages are distorted
iterative optimized algorithm is evaluated through comparison and unbalanced, HF and UPF operation cannot be achieved
with an iterative optimization based control algorithm (OCA) simultaneously. For this reason, previous literature in the area
and then validated using a real-time hardware in the loop (HIL)
experimental system. The real-time experimental results of shunt APF under distorted and unbalanced supply
demonstrate that the proposed method is capable of providing condition, use either HF or UPF control strategy [6-13].
load compensation under steady state and dynamic load Recently, several approaches have been proposed to combine
conditions and thus making it more effective for practical the advantages of both control strategies using non-linear
applications. optimization techniques [15-20].
The optimization based papers on the shunt APF control
Index Terms Active power filter (APF), harmonic
under distorted and unbalanced voltages can be classified into
compensation, unity power factor, power quality, optimized
control. two main categories. In the first category, the distorted and
unbalanced supply voltages of each phase are processed
I. INTRODUCTION through a set of filters (such as, band pass). The filter gains are
optimized considering both voltage THD and voltage
T he increasing demand of the power electronics based non-
linear loads has raised several power quality problems.
The uneven distribution of dynamically changing single phase
unbalance limit constraints to achieve the desired
compensated voltages. These compensated voltages are then
multiplied with constant conductance factors to obtain the
loads give rise to the additional problem of excessive neutral
desired source currents. In [15], the compensated voltage are
current and current unbalance [1]. The combined effects of the
obtained in --0 reference frame, whereas, in [16-18] the
above in todays power distribution system results in increased
compensated voltage are generated in a-b-c stationary
reference frame to avoid the complex transformation from one
Manuscript received May 31, 2012; revised August 2, 2012 and October frame to the other. As stated in [16-18], due to the
19, 2012; accepted November 29, 2012. Copyright (c) 2009 IEEE. Personal computational delay, the studied approach is not suitable for
use of this material is permitted. However, permission to use this material for
any other purposes must be obtained from the IEEE by sending a request to
loads that operate dynamically.
pubs-permission@ieee.org. In the second category, to reduce the complexity and
P. Kanjiya, V. Khadkikar and H. H. Zeineldin are with Masdar Institute of dimensionality of the optimization problem, the authors in
Science and Technology, Abu Dhabi, PO Box 54224, United Arab Emirates
(e-mail: pkanjiya@masdar.ac.ae, vkhadkikar@masdar.ac.ae, hzaineldin
[19-20] formulated the optimization problem considering the
@masdar.ac.ae). conductance factors as variables. The conductance factors for
This research work was supported by Masdar Institute of Science and each harmonic order are optimally determined. These
Technology under MISRG internal grant (Award No. 10PAAA2).

Copyright (c) 2011 IEEE. Personal use is permitted. For any other purposes, permission must be obtained from the IEEE by emailing pubs-permissions@ieee.org.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication.

conductance factors are then multiplied with a balanced set of In [27], a voltage detector approach is given where the sum
supply voltages to obtain desired source currents. In [19], the of all harmonic components are extracted (by subtracting
supply voltages are considered as distorted and balanced. In fundamental positive sequence voltages from measured
[20] to enhance the performance of the system under voltages) to control shunt APF for damping the voltage
unbalanced and distorted voltages, the balanced set of voltages harmonic propagation in distribution systems. The extracted
are extracted using instantaneous symmetrical components voltages by this method contain unbalanced harmonics as it
along with complex Fourier transform. does not extract individual balanced harmonics and cannot be
One of the main disadvantages of all the above mentioned used here directly. To optimally compensate the load currents
optimization based approaches is the use of iterative under unbalanced and distorted supply conditions using shunt
APF, the individual balanced harmonic components are
techniques for solving the optimization problem. The use of an
extracted in [20]. An instantaneous symmetrical component
iterative technique can result in a computational delay, which
theory combined with complex Fourier transform is utilized to
can constraint the applicability of the these control approaches
extract the balanced set of voltages in [20]. This approach is
under dynamic load conditions. As a result, the methods complex and the use of fixed frequency moving average
proposed in [15-20], focused on steady state load technique to carry out integration into the Fourier transform
compensation only. In [22], N. Pogaku and T. Green have may affect the extraction under 1) supply frequency variations
considered only one conductance factor to compute the [22] and 2) presence of inter-harmonics into the supply
reference current for distributed generator inverter controller voltages. A new approach to extract the balanced set of
in a micro-gird application to provide adjustable damping at voltages, utilizing synchronous reference frame (SRF) theory,
harmonic frequencies to mitigate voltage distortion. is proposed in this paper and discussed below.
To overcome the aforementioned challenges, a single-step Let the three distorted and unbalanced supply voltages at
non-iterative optimized control algorithm for shunt APF under the point of common coupling (PCC) be represented as follow,
distorted and unbalanced supply conditions is proposed in this
paper. The algorithm is based on direct calculation of
conductance factors without incorporating any iterative
optimization technique. It is shown that there is no need to
where subscript denotes supply, subscript denotes phase of
compute conductance factors for each harmonic order
the system, denotes harmonic order, denotes the
separately. Three conductance factors (for the fundamental,
maximum harmonic order (the choice of will depend on the
odd and even harmonics) are sufficient to achieve the desired maximum harmonic order to be expected in the supply
performance. Since the algorithm is based on direct voltages and it is selected by the user), denotes rms value of
calculation of conductance factors (only three) without voltage and denotes phase angle. For the harmonic
incorporating any iterative technique, it can effectively work order, the voltages given in (1) can be converted into the SRF
under steady state as well as dynamic load conditions. The using Parks transformation as:
Lagrangian formulation is utilized to develop the proposed
single-step non-iterative approach. Moreover, to extract the
balanced set of voltages from unbalanced and distorted supply
voltages, the novel and simple balanced voltage extractor
based on synchronous reference frame theory is proposed. The where is the fundamental angular frequency of supply
performance of proposed single-step algorithm is evaluated voltages which can be obtained using the phase locked loop
through comparison with the Newton-Raphson based (PLL). , and are the direct and quadrature axis voltage
optimization control approach (OCA). A real-time hardware in components of harmonic voltage. With this approach there
the loop test bed system is developed using OPAL-RT is no need to extract positive, negative and zero sequence
simulator and a digital signal processor (DSP) DS1103 form components separately.
dSPACE to validate the performance of the proposed The components and can be represented as:
algorithm for practical applications. The real-time
experimental results show the compensation effectiveness of
the proposed algorithm, in particularly, under a dynamic load
condition. where and are the DC components corresponding to
the balanced part of the harmonic voltage present in the
II. EXTRACTION OF BALANCED SET OF VOLTAGES FROM supply voltages, while and are the AC components
DISTORTED AND UNBALANCED SUPPLY VOLTAGES USING corresponding to the unbalanced part of harmonics. The
SYNCHRONOUS REFERENCE FRAME THEORY zero sequence component does not contain any information
One of the main objectives of the four leg shunt APF is to about the balanced part of the voltages, hence it is not
achieve balanced source currents by compensating unbalanced considered in (2).
load currents. In order to generate the balanced reference The DC direct and quadrature axis components and
source currents to control shunt APF under distorted and can be obtained after processing and through low pass
unbalanced supply condition, the balanced set of voltages filters (LPFs). The use of LPFs over fixed frequency moving
needs to be extracted. average filters into the proposed SRF theory based extractor

Copyright (c) 2011 IEEE. Personal use is permitted. For any other purposes, permission must be obtained from the IEEE by emailing pubs-permissions@ieee.org.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication.

gives robustness to the extraction against supply frequency THD, minimization of APF kVA rating or maximization of
variations and presence of inter-harmonics. The balanced set source power factor [16], [18]. The most practical objective is
of the supply voltages in the stationary reference frame for the to maximize the source power factor, which consequently
harmonic is then obtained using inverse Parks transform reduces the cost of electricity consumption under power factor
as follows, based tariff (the most commonly used electricity tariff plan for
industrial users). Therefore, the objective chosen here is to
maximize the power factor which can be achieved by
minimizing the square of apparent power calculated using the
extracted balanced set of voltage and the desired source
The above procedure is carried out for . current of any phase [19-20]. Since both the extracted voltages
Finally the three phase balanced set of voltages can be and desired source currents are balanced, the three phase rms
expressed as follows, quantities are equal and thus can be represented as follows,

where the rms value of the balanced order harmonic


Since all the quantities on the right hand side of (5) are voltage of any phase can be computed as follows,
balanced, represents the balanced set of supply voltages
derived from the distorted and unbalanced supply voltages.

III. PROPOSED SINGLE-STEP NON-ITERATIVE OPTIMIZED Using (7), the objective function , which is the square of
ALGORITHM the apparent power of any phase, is given by:
To achieve UPF operation, under distorted and unbalanced
supply conditions, the following conditions should be
satisfied: (1) the source currents should have the same
harmonic content as the supply voltages, and (2) all the phase
currents should be in-phase with their respective phase B. Equality Constraint
voltages. This suggests that in case of UPF operation, the For the desired source currents to be balanced, the three
source current THD should equate to the source voltage THD source currents should supply the demanded average total
value while maintaining in phase relationship with respect to power equally. Therefore, the equality constraint for any phase
the individual phase voltage. Therefore, the source current can be written as:
THD and unbalance factor may not be within the acceptable
limit. By controlling the harmonic ratios and balancing the
average power equally among the three phases, the THD and
source current unbalance factor can be maintained within the
specified limits. For the source current to meet all the above where is the demanded average load power, which is
constraints while maximizing the power factor, the APF computed using instantaneous three-phase source voltages and
control algorithm is formulated as an optimization problem load currents. This instantaneous power is then
where the main variable is the conductance factor for each processed by an LPF to obtain the . is the average
individual harmonic order. Using (5), the desired source power required to overcome the losses in the shunt APF and
currents can be expressed as follows thus to maintain the DC link voltage.
C. Inequality Constraints
The approach discussed, in [19-20], considers one THD
where * denotes the reference or desired quantity. and limit on the source current total harmonic distortion ).
are the conductance factors for the fundamental and nth As per the IEEE Std. 519, limits on the current distortion for
order harmonic components. The values of these conductance individual even harmonics is 25% of the limit on the odd
factors can be controlled to maximize the power factor while harmonics. To address this, different THD limits for the
satisfying the average power balance and THD constraints. current distortion due to odd and even harmonics is considered
Since the same conductance factor value will be applied to in this paper.
each phase to achieve balanced source currents, the The upper bounds on the source current harmonic distortion
optimization problem can be solved and formulated due to odd and even harmonics is denoted as and
considering one phase. The next subsections will highlight the , respectively. The inequality constraints on
proposed problem formulation for determining the optimal current distortion due to odd and even harmonics is given by,
conductance factors.
A. Objective function and,
There are various objectives that can be applied to the shunt
APF problem which include minimization of source currents where,

Copyright (c) 2011 IEEE. Personal use is permitted. For any other purposes, permission must be obtained from the IEEE by emailing pubs-permissions@ieee.org.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication.

and,

The source side power factor is maximum (UPF) when both


the source voltage and current THDs are equal (UPF
operation). Let and be the user defined By applying the Karush Kuhn Tucker (KKT) optimality
(pre-specified) THD limits on the source current harmonic conditions to (19) [25], the following set of equations can be
distortion due to odd and even harmonics respectively. For derived.
cases where the source voltage THDs due to odd and even
harmonics ( and ) are greater than
and respectively, the source current THDs should
be equal to the pre-specified THD values to achieve maximum
power factor. On the other hand, for cases where and
are less than and respectively,
the source current THDs should be equal to the supply voltage
THDs to maximize the source side power factor. This can be
mathematically represented as follows:

and,

For optimality, the source current THDs will always reach


its upper limit as per (15)-(16) and thus the inequality
constraint given in (11)-(12) can be reformulated as an
equality constraint as follows,

and,
From (21) and (22), it can be deduced that the conductance
factors for all odd harmonics as well as for all even harmonics
will be equal and can be represented as follows,
In the following subsection it will be proven that, by
converting the inequality constraints given in (11)-(12) into an
equality constraints as per (17)-(18) (by selecting
according to the condition given in (15)-(16)), By substituting (26)-(27) into (23), (24) and (25), the
the closed form solution of optimum conductance factors is following equations can be derived.
possible without incorporating any iterative optimization
technique. The identification of the optimum source current
THDs to achieve the maximum power factor significantly
reduces the complexity of the problem and thus a simple
single-step non-iterative solution is achievable.
D. Proposed Single-step Non-iterative Solution where,
The optimization problem presented in the previous
subsections is a constrained non-linear optimization problem
where the main variables are the conductance factors. Using
the Lagrangian function, the problem can be transformed into
an unconstrained optimization problem as follows [25], and,

Copyright (c) 2011 IEEE. Personal use is permitted. For any other purposes, permission must be obtained from the IEEE by emailing pubs-permissions@ieee.org.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication.

From (29) and (30), and can be represented in (34) and (35), the optimal conductance factors are determined.
terms of as follows, The flowchart is an integral part of the overall control block of
the APF which is discussed in the next section.
The non-iterative solution of the optimization problem with
constraint on different power quality factors, such as,
distortion factor and K-factor, is also discussed briefly in
Appendix-III.
Furthermore, by substituting (33) and (34) into (28), an START
expression for can be derived as follows,
Get the RMS values of balanced set of
fundamental and harmonic voltages
( , = , , ,)
Get the demanded total average power
( + )
Equations (33), (34) and (35) present a closed form Specify source current THD limit
( _ and _ )
mathematical formula for determining the optimal values for
the conductance factors. By substituting the value of , Calculate Calculate
and from (33), (34) and (35) into (6), the reference source _ _

currents can be re-written as:


N Check Check N
_ < _ _ < _

_ = _ Y Y _ = _

,_ = _ ,_ = _

Equation (36) suggests that the proposed algorithm may


have superior performance compared to algorithms given in Calculate
+
[19-20] due to the direct calculation of conductance factors =
+ ,__
, and using (33), (34) and (35). The
+,__
distinguishing features of the proposed single-step optimized ,_
_ =
_
approach can be summarized as follows: ,_
a- The proposed approach involves only three conductance _ =
_
factors (one for the fundamental and two other for odd
and even harmonics respectively) as opposed to STOP

conductance factors in [19-20]. This will reduce the Fig. 1. Flowchart to determine the conductance factors , and .
complexity of the problem.
Ls iSa iLa
b- The different conductance factors for the odd and even Three-phase
Ls iSb iLb
harmonics facilitates the selection of separate THD limits Loads/
on odd and even harmonics. Ls iSc iLc Several
Single-phase
iSN iLN Loads
c- Mathematical formulas are derived that can calculate the
optimal conductance factors directly and thus avoiding 3P4W
iShN
iSha
iShb
iShc

AC Supply
the use of iterative techniques. The direct calculation of
, and can greatly reduce the computation Lsh
time and thus achieving faster response time when
S1 S3 S5 S7
compared to other methods [19-20].
d- As opposed to previous approaches in [15-20], since the Cdc
proposed method does not involve an iterative approach,
it can be more effective for dynamic load variations.
S6 S2 S4 S8
The flow chart of the proposed single-step non-iterative Shunt Active Power Filter
solution procedure is shown in Fig. 1. The algorithm will start Fig. 2. Four-leg VSI based shunt APF system configuration.
by measuring the source voltage and extracting the rms value
of each balanced harmonic component. This will be used to IV. OVERALL CONTROL BLOCK OF SHUNT APF
determine and . As mentioned previously in
Fig. 2 represents the system under study which consists of
(15) and (16), and will be compared with
an equivalent grid behind an impedance, combined single
and respectively to determine
phase and three phase loads, and the shunt APF. The four leg
and . For cases where is voltage source inverter (VSI) topology is utilized to realize
less than , will be set equal to . 3P4W APF system. The overall control block diagram of the
Otherwise, the value of will be set equal to proposed single-step non-iterative optimized control algorithm
. Similarly, will be selected by comparing to control shunt APF under distorted and unbalanced supply
with . Using the derived formulas in (33), condition is shown in Fig. 3.

Copyright (c) 2011 IEEE. Personal use is permitted. For any other purposes, permission must be obtained from the IEEE by emailing pubs-permissions@ieee.org.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication.

The inputs to the single-step calculation of , and study is carried out under the MATLAB/SIMULINK
block are the specified source current THD limits environment. The simulated test system data is given in
( and ), demanded average total power Appendix-I. The performance of the proposed single-step non-
( ), and rms values of the balanced set of iterative optimized control algorithm is compared and
harmonic voltages ( ). The demanded validated with an iterative optimization based control
instantaneous load power is calculated as, algorithm (OCA) given in [20]. The simulation studies for
both steady-state and dynamic conditions are performed and
discussed below.
The instantaneous power is then process by an LPF to
A. Case 1: Unbalanced supply voltages distorted with odd
obtain the average power To maintain the dc link
harmonics only - steady state load condition.
capacitor voltage constant at a pre-specified value, a small
amount of active power should be drawn from the grid. To In order to test the proposed approach under distorted and
accomplish this, a discrete proportional-integral (PI) controller unbalanced supply voltage condition, the unbalanced three
is used which can be given as follows, phase supply voltages are expressed in Table I.
Fig. 4 shows the simulated results with the proposed single-
step optimized algorithm under steady-state load condition.
The profiles of the distorted-unbalanced supply voltages and
where, the non-linear distorted-unbalanced load currents are given in
where is the measured instantaneous voltage across Fig. 4 (a) and (b). Table-II gives the rms and THD values of
the DC link capacitor processed through the low pass filter, each phase voltage and load current with the source voltage
is the reference DC link voltage and is the sample and load current unbalance (UB) factors. The value of the
number. and are the proportional and integral gain power factor and the source current UB, with APF
compensation, using the proposed and OCA control
respectively of the PI controller. The rms values of the
algorithms are also presented in Table-II.
balanced set of harmonic voltages are calculated as in (8)
The unbalance factor is calculated as follow,
using the extracted balanced set of harmonic voltages in the
synchronous reference frame. After calculating the
conductance factors , and as shown in Fig. 1, the
three phase reference source currents are calculated as in (36).
The reference source neutral current is set equal to zero. These
reference source currents are compared with the actual Table I: Distorted and unbalanced supply voltages (Case 1)
measured currents using the hysteresis current controller Phase-a Phase-b Phase-c
which determine the switching signals for the VSI.

V. SIMULATION RESULTS
To verify the performance of the proposed single-step non-
iterative optimized control algorithm, a detailed simulation

_ _

LPF
1

Single-step
PI calculation _
of
LPF
, _
and
PLL _
Hysteresis
current
controller

abc dq _
LPF
dq abc To gates of IGBTs
of 4-leg VSI

2
abc dq
LPF
dq abc
=
=3,5

=
h
abc dq
LPF =3,5
dq abc

Fig. 3. The overall control block diagram for the proposed non-iterative optimized control of four-leg VSI based shunt APF.

Copyright (c) 2011 IEEE. Personal use is permitted. For any other purposes, permission must be obtained from the IEEE by emailing pubs-permissions@ieee.org.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication.

The extracted balanced set of voltages using the d-q c). The power factor of all phases is measured to be 0.983
transformation method is depicted in Fig. 4 (e). The lagging with respect to extracted balanced set of voltages.
performance of the proposed optimized control algorithm is Note that the slight increase in the actual source current THD
evaluated for the following three conditions: (1) HF (0 % values (greater than specified 5%) is due to the switching
THD) operation, (2) UPF operation and (3) a specified THD operation of VSI.
limit operation.
Fig. 4 (f) gives the compensated source currents when the
APF is controlled under HF condition using the proposed
optimized control. For this case, the THD limits
and are set equal to 0%. The source currents, after
the compensation, are balanced and sinusoidal. As noticed
from Table-II, the THD of the source currents with HF mode
of operation is around 1.7%. The power factors in the HF
mode, measured with respect to unbalanced supply voltages,
are 0.955 lagging (phase-a), 0.905 lagging (phase-b) and
0.884 lagging (phase-c) while, power factor of all phases
measured with respect to extracted balanced set of voltages is
0.969 lagging.
To test the controller performance, the odd and even THD
limits were specified as 100%. As discussed in previous
sections and shown in the flow chart (refer to Fig. 1), the
proposed algorithm compares the specified THD limits
and of 100% with the balanced set of
source voltage THDs, and which in this case
are 24% and 0% respectively. The specified THD limits of
100% are greater than the balanced set of supply voltage
THDs, and therefore, the control algorithm operates in the
UPF mode to achieve the maximum possible power factor
operation. Fig. 4 (g) illustrates the compensated source
currents when the APF system operates in the UPF operation.
The unity power factor with respect to balanced set of voltages
is achieved in this mode of operation with source current THD
close to 24% (equal to balanced set of supply voltage THD Fig. 4. Simulation results under unbalanced supply voltages distorted with odd
value). The power factors of each phase measured with respect harmonics using proposed single-step optimized control algorithm.
to unbalanced supply voltages are given in Table-II.
Finally, the performance of proposed single-step optimized It can be viewed from the above-discussed three modes that
control algorithm is evaluated considering constraints on the compensated source current profile, in the optimized
source current THD levels while maximizing power factor. mode, is in between sinusoidal (HF operation) and balanced
The THD limits of the source currents are specified as 5%. set of supply voltage (UPF) operations. In all the above
Fig. 4 (h) depicts the simulation results under the optimized operating modes, the fourth leg of the shunt APF effectively
mode of operation. From Table-II, the source current THD is compensates the load neutral current (Fig. 4 (c)), and thus
achieved around 5.6% with the source side power factors, reducing the source side neutral current to zero (shown with
measured with respect to unbalanced supply voltages, as 0.967 cyan color in Figs. 4 (f)-(h)).
lagging (phase-a), 0.912 (phase-b) and 0.900 lagging (phase-

Table-II: Performance indices with proposed optimized and OCA approaches (steady-state condition case-1)

rms (pu) Power factor THD (%) UB (%)


Mode Strategy a b c a b c a b c -
Supply voltages
- - 0.667 0.807 0.537 - - - 27.03 21.06 37.24 19.89
Load currents
- - 0.536 0.932 0.608 0.733 0.713 0.917 25.97 17.07 32.93 22.54
HF Proposed 0.597 0.600 0.602 0.955 0.905 0.884 1.70 1.75 1.80 0.44
OCA 0.598 0.601 0.603 0.955 0.905 0.884 1.77 1.81 1.87 0.44
UPF Proposed 0.581 0.584 0.584 0.983 0.915 0.936 23.54 23.57 23.69 0.34
OCA 0.582 0.584 0.585 0.983 0.915 0.936 23.55 23.52 23.69 0.29
Optimized Proposed 0.593 0.594 0.597 0.967 0.912 0.900 5.57 5.67 5.65 0.28
OCA 0.592 0.597 0.597 0.967 0.912 0.900 5.50 5.64 5.70 0.56

Copyright (c) 2011 IEEE. Personal use is permitted. For any other purposes, permission must be obtained from the IEEE by emailing pubs-permissions@ieee.org.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication.

Fig. 5 gives the simulated results for the system under Table-III: Overall comparison between Iterative Newton-Raphson and
Proposed Non-iterative Single-step Optimized Approaches.
consideration, under three operating modes (HF, UPF and
optimized), with an iterative optimization based OCA control Method Newton-Raphson (NR) Proposed
method. The performance indices of the OCA method are also No. of iteration 8 4 2 1
provided in Table-II. As viewed from Figs. 4-5 and Table-II, Time (Second) 0.11 0.07 0.04 1.00E-05
the performance of the proposed single-step optimized Time (cycles) 5.5 3.5 2 Inst.
algorithm is identical to the OCA control method since the Function value 0.088 0.0878 0.0896 0.088
supply voltages are distorted with only odd harmonics and the Eq. constraint Satisfied Satisfied Satisfied Satisfied
THD limit in case of OCA was set same as . The Ineq. constraint Satisfied Unsatisfied Satisfied Satisfied
proposed optimized method, however, requires minimum Minima Optimum Infeasible Feasible Optimum
computational burden compared to the OCA method since the
model relies on only three control variable ( , and )
This demonstrates that the proposed optimized algorithm
and direct computation of the variables without any iterative computes the conductance factors almost instantaneously. The
technique. Table-III gives the comparison between Newton- extremely low computational time makes the proposed
Raphson (NR) based OCA and the proposed single-step method capable of compensating dynamically changing load.
optimized control method. The steady state per unit values The results by the NR method, with a maximum number of
used to determine the conductance factors using both methods iterations set equal to 4 and 2 iterations, are shown in Table-
are given in Appendix-II. III. It can be noticed that despite the reduction in the
computational time the solution is not optimum. Moreover, it
is worthy to note that the execution time and the number of
iterations taken by the NR method to find the optimum value
is highly dependent on the initial guess of the control variables
and in some cases might not guarantee the global optimal
solution. The NR method was run 50 times with a random
initial guesses for all control variables and it was found that
the maximum number of iteration taken was 11 with an
execution time of 7.5 cycles, while the minimum number of
iterations recorded was 3 with an execution time of 2.5 cycles.
The average number of iterations and average execution time
found for 50 runs of NR method was 8 and 5.5 cycles
respectively. It is important to note that the sampling time of
the controller for the shunt APF with the NR method should
be higher than the maximum optimization execution time.
B. Case 2: Unbalanced supply voltages distorted with odd
harmonics only - dynamic load Condition.
The performance of the proposed control algorithm,
considering the distorted and unbalanced supply voltages
given in Table I, during a sudden load change condition is
illustrated in Fig. 6.
To create the dynamic condition, at time t=0.2 sec, the load
is changed from L1 to L1+L2 (Appendix-I) and again brought
back to L1 at time t=0.3 sec. The change in the load current
profile can be viewed from Fig. 6 (b). The compensated
source current profile is shown in Fig. 6 (c). As noticed, the
APF system with the proposed single-step optimized approach
Fig. 5. Simulation results under unbalanced supply voltages distorted with odd
harmonics using OCA control algorithm.
achieves the new steady-state condition within one cycle and
without affecting the APF compensation capability during
The CPU used for this study has core i5 processor with 4 both load increase and decrease. Furthermore, the dc link
GB RAM. For the NR method, the optimization problem with controller, as shown in Fig. 6 (d), effectively regulates the dc
seven conductance factors is formulated and solved using bus voltage at the set reference value.
MATLAB optimization tool box [19-20]. The optimum value Under the same dynamic condition, the performance of
is found to be 0.088 which was reached in 0.11 seconds or 5.5 iterative optimization based OCA method is given in Fig. 7.
cycles (average) utilizing 8 iterations (average) compared to As observed from Fig. 7 (a), the compensated source currents
10 -seconds or almost instantaneous (Inst.) for the proposed are not optimal. In addition, the dc link voltage, shown in Fig.
single-step method. For both cases, 0.11 seconds and 10 - 7 (b), settles at a new operating point, lower than the set
seconds represent the time required to compute the reference value. This is mainly because of the 10 cycles
conductance factors which does not include the time required computational delay (maximum execution time of 7.5 cycles
for the extraction of balanced set of voltages. plus 2.5 cycles safety margin) in calculating the new

Copyright (c) 2011 IEEE. Personal use is permitted. For any other purposes, permission must be obtained from the IEEE by emailing pubs-permissions@ieee.org.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication.

conductance factors. Therefore, for a duration of 10 cycles, the Table-IV: Performance indices with proposed optimized and OCA approaches
(after load change)
OCA based controller tries to compensate the source currents
based on the previously computed conductance factors and Method Proposed OCA
thus the source currents become more distorted and a 5.57 6.83
unbalanced. Table-IV presents the compensated current b 5.67 14.43
THD (%)
THDs, power factors, rms values and UB factors under the c 5.65 15.41
a 0.967 0.947
new operating condition using the proposed optimized and Power
b 0.912 0.914
OCA algorithms. Thus, this dynamic condition demonstrates factor
c 0.900 0.932
the true capability and enhanced performance of the proposed a 0.593 0.556
single-step optimized algorithm over other optimization based rms (pu) b 0.594 0.628
approaches. c 0.597 0.594
UB (%) - 0.28 6.187

Table-V: Distorted and unbalanced supply voltages (Case 3)


Phase-a Phase-b Phase-c

The source current THD limit in case of OCA algorithm is


set equal to 5% while, the THD limits and
) in case of the proposed algorithm are set equal to
4.85% and 1.21% respectively. is set equal to
to comply with IEEE Std. 519. The above limits
for the proposed algorithm are calculated using (41) to
maintain an overall THD limit ( ) of 5%.

The profiles of the supply voltages and load currents are


given in Fig. 8 (a) and (b). The compensated source currents
Fig. 6. Simulation results for dynamic load condition under unbalanced supply
using the proposed algorithm are shown in Fig. 8(c), while,
voltages distorted with odd harmonics using proposed algorithm. Fig. 8(d) depicts the source currents using OCA algorithm.
Note that there is a slight difference in shape of source current
waveforms with proposed and OCA algorithm due to different
odd and even harmonics level in the source currents. The
different performance indices with the proposed algorithm and
OCA algorithm are provided in Table VI. The performance of
the shunt APF with both algorithms is almost identical in
terms of rms value, power factor and THD of the source
currents, the main differences lie in the individual harmonic
distortion (IHD), filters kVA and the K-factor as shown in
Table VI.
The average IHD of three phase source currents for both
algorithms are shown shaded in Table-VI. The IEEE-519
Fig. 7. Simulation results for dynamic load condition under unbalanced supply standard recommends that the individual even and odd
voltages distorted with odd harmonics using an iterative optimization method.
harmonics in the source current should be less than 1% and
4%, respectively, for a system with short circuit ratio less than
C. Case 3: Unbalanced supply voltages distorted with both 20. The 2nd and 4th harmonic in source currents are measured
odd and even harmonics - steady state load condition. to be 2.88% and 2.62% respectively with OCA algorithm
The superiority of the proposed algorithm over the OCA (shown bold) which are above the individual even harmonics
algorithm, in terms of computation time, was highlighted in limit as per IEEE-519. On the other hand, since individual
the previous two cases. To show the advantage of having limits are imposed on odd and even harmonics with the
different THD limits on odd and even harmonics, the proposed method, the measured 2nd and 4th harmonic in source
performance of proposed algorithm is evaluated and compared currents are 0.95% and 0.88% respectively (below limit). The
with the OCA algorithm under unbalanced supply voltages measured odd harmonics (5th and 7th) in source currents are
distorted with both even and odd harmonics (Table-V). within the individual odd harmonics limit as per IEEE-519
with both algorithms. The K-factor of the source current is
slightly higher with the proposed algorithm due to higher

Copyright (c) 2011 IEEE. Personal use is permitted. For any other purposes, permission must be obtained from the IEEE by emailing pubs-permissions@ieee.org.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication.

10

amount of higher order harmonics (5 th and 7th) compared to currents and 1 neutral current) are also taken out from the
the OCA algorithm. It is worthy to note that considering OPAL-RT. An external analog hysteresis current control
different THD limits on odd and even harmonics is one step board is developed to perform the pulse width modulation.
towards the optimized control of shunt APF taking into The actual and reference source current signals are then
account individual harmonic constraints. As seen from the compared and the 8 necessary switching pulses for the shunt
results, the proposed approach improves upon existing inverter are generated. Finally, these 8 switching/gate pluses
methods. Future work would be to implement a non-iterative are transferred to OPAL-RT using digital I/O ports and
approach that considers directly constraints on individual utilized to control the shunt APF inverter in real-time. It
harmonics. should be noted that all the signals are normalized on a 5V
scale (5V=1 pu, base values in Appendix-I). The maximum
limit on the input-output signals for OPARL-RT is 16V and
10V for dSPACE. The sampling times for both OPAL-RT
and DS1103 systems were 20 sec each.
The performance of shunt APF real-time HIL system is
evaluated for both steady state and under dynamic conditions.
Fig. 10 gives the real-time test system results. The source
voltage and load current profiles in steady-state are given in
Fig. 10 (a) and (b), respectively. It is worthy to note that
identical system parameters and load conditions are
considered (same as discussed in the simulation section, case
1 and case 2). The real-time experimental results with the
proposed optimized algorithm for three different modes of
Fig. 8. Simulation results under unbalanced supply voltages distorted with
operation are given in Fig. 10 (c) to 10 (e). As noticed from
both odd and even harmonics using proposed optimized and OCA control the Fig. 10 (c) for the case of HF operation, the source
algorithms. currents are achieved as balanced and sinusoidal. The actual
VI. REAL-TIME HARDWARE IN THE LOOP (HIL) THD values of the source currents are noticed as 3.9%. The
harmonics are mostly due to the sampling time of the OPAL-
IMPLEMENTATION
RT and switching operation of the inverter. Fig. 10 (d) gives
A real-time hardware-in-the-loop (HIL) system is built to the source currents when the optimized algorithm is operated
validate the feasibility of the proposed single-step optimized to achieve maximum power factor at 5% THD limit. In this
approach for practical applications. Fig. 9 illustrates the case, the THD of the source currents are measured to be
developed laboratory experimental setup. The real-time HIL 5.94%. The harmonic spectrum of phase-a supply voltage,
system is composed of an OPAL-RT digital simulator and a load current and source current up to 7 th harmonic during 5%
rapid prototyping digital signal processing (DSP) board from THD limit operation is given in Table-VII. When THD limits
dSPACE, DS1103. The OPAL-RT is a real-time simulation are defined as 100%, the source current profiles are illustrated
platform based on two Intel Xeon QuadCore 2.40 GHz in Fig. 10 (e). In this case, the proposed algorithm determines
processors (total 8 cores or CPUs) working under RT-LAB the maximum THD limits by comparing it with a balanced set
software environment. OPAL-RT is equipped with analog of source voltages ( and ). The
inputs/outputs (16 each) and digital inputs/outputs (32 each). compensated source currents have THD of 24.47%. Note that
The DS1103 has 20 analog to digital converter (ADC) ports, 8 the source currents are identical to the extracted distorted-
digital to analog converter (DAC) ports and 32 digital balanced set of supply voltage profile shown in Fig. 4 (e).
inputs/outputs. As shown in Fig. 9, the OPAL-RT represents The dynamic performance of proposed non-iterative
the power system where all the power circuit components, optimized control algorithm is shown in Fig. 10 (f) to 10 (i).
such as, 3P4W unbalanced distorted source, unbalanced load Initially, the load on the system is three-phase diode bridge
and shunt APF are implemented. The DS1103, on the other rectifier with a resistor. Suddenly, an unbalance load is
hand, represents digital controller for the shunt APF. In an connected to the system. The load current profile due to this
actual practical system, the OPAL-RT will be replaced by the dynamic load change is shown in the Fig. 10 (f). Prior to the
actual power source, load and inverter, whereas, the digital load change, the controller is working under HF mode. As
controller will remain the same. The necessary seven signals seen from the Fig. 10 (g), the shunt APF system together with
(3 supply voltages, 3 load currents and the DC bus voltage) proposed algorithm maintains the desired performance.
are measured and taken out of OPAL-RT through its DAC Additionally, as noticed from the three phase source currents
ports. These real-time signals are available in the in Figs. 10 (h) and 10 (i), the dynamic performance can be
MATLAB/SIMULINK platform on the host computer through achieved in different modes of operation. The load neutral
ADC ports of DS1103 and are utilized to generate reference current compensation during dynamic load change is depicted
source currents based on the proposed control algorithm in Fig. 11. It can be seen that the source neutral current is
(indirect control). For the neutral current compensation, the achieved equal to zero by injecting compensating neutral
source neutral current is directly considered as zero. These current opposite to load neutral current through forth leg of the
generated reference source currents (total 4, 3 for phase shunt APF. This study thus validates that the proposed
currents and 1 for neutral) are taken out of the DSP through optimized control algorithm can perform well under dynamic
DAC ports. The actual source current signals (total 4, 3 phase conditions.

Copyright (c) 2011 IEEE. Personal use is permitted. For any other purposes, permission must be obtained from the IEEE by emailing pubs-permissions@ieee.org.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication.

11

Table VI: Performance indices for the proposed optimized and OCA approaches (steady-state condition case-3)

rms (pu) Power factor THD (%) UB (%) IHD (%) Filters kVA K-factor
Strategy nd th th th
a b c a b c a b c - 2 4 5 7 - -
Supply voltages
- 0.648 0.793 0.511 - - - 11.25 7.98 15.13 21.47 6.09 5.73 5.47 5.20 - -
Load currents
- 0.567 0.936 0.576 0.780 0.693 0.928 21.12 10.25 17.31 18.18 - - - - - -
Source currents
Proposed 0.584 0.586 0.586 0.984 0.922 0.932 5.16 5.24 5.22 0.23 0.95 0.88 3.58 3.27 0.865 1.069
OCA 0.585 0.587 0.588 0.985 0.923 0.933 5.19 5.21 5.23 0.28 2.88 2.62 2.38 2.27 0.894 1.044

Non-linear
Load
DS1103
3P4W System LS h iL (a,b,c) APF Controller
DAC 1-3 ADC 1-3 Implementation
vS (a,b,c)
DAC 4-6 ADC 4-6 on Matlab/
Cdc vd c Simulink
vdc iS (a,b,c,n)
DAC 7 ADC 7
Platform
Actual Reference
DAC 8-11 DAC 1-4
(a,b,c,n) (a,b,c,n) Host PC
Analog
G1 to G8 G1-G8 H.C.
Digital I/O
Opal-RT gate signals H.C.= Hysteresis
dSPACE & PC Interface
Interface
Controller
Fig. 9 Laboratory Real-time Hardware-In-the-Loop (HIL) System Representation.

(a) Source voltages (b) Load currents . (c) Source currents (HF mode)

(d) Source currents (optimized mode) (e) Source currents (UPF mode) (f) Load currents (load change)

(g) Phase-a performance (HF mode- load change) (h) Load currents (HF mode- load change) (i) Source currents (optimized mode- load change)
Fig. 10 Real-time experimental results (scale:- X-axis = 10 m-sec/div, Y-axis = 1 pu/div for all the quantities except for Vdc where Y-axis = 0.2 pu/div

Copyright (c) 2011 IEEE. Personal use is permitted. For any other purposes, permission must be obtained from the IEEE by emailing pubs-permissions@ieee.org.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication.

12

Table VII: Harmonic spectrum of different quantities during 5% THD limit IX. APPENDIX-II
operation.
The steady state per unit values used to determine the
Quantity THD 2nd 3rd 4th 5th 6th 7th conductance factors:
27.03 0.01 0.01 0.01 21.43 0.01 15.22
25.79 0.01 19.12 0.01 05.68 0.02 12.36
05.94 0.00 0.01 0.02 04.25 0.01 03.10
X. APPENDIX-III
OPTIMIZATION PROBLEM FORMULATION AND ITS SOLUTION
WITH ALTERNATE POWER QUALITY CONSTRAINTS
In the previous discussion the optimization problem aiming
at maximizing the power factor subject to the power balance
and THD constraints was introduced. However, there are
various power quality constraints other than THD such as,
distortion factor and K-Factor that are of technical interest in
certain conditions. This section provides a brief discussion on
how to formulate and solve an optimization problem to
compute optimal conductance factors considering distortion
factor and k-factor.
Fig. 11 Real-time experimental results: neutral current compensation
(scale:- X-axis = 10 m-sec/div, Y-axis = 1 pu/div). A. Constraint on Source Current Distortion Factor
The distortion factor (DF) describes how the harmonic
VII. CONCLUSION
distortion of source current affects the effective source power
A single-step non-iterative optimized control algorithm has factor. The current distortion factor ( ) is defined as the
been proposed for three-phase four-wire shunt active power ratio of the fundamental rms current to the total rms current.
filter to achieve an optimum performance between power
factor and THD. The proposed optimized approach is simple
to implement and does not require complex iterative
optimization techniques to determine the conductance factors. The lower the DF, higher the current distortion, therefore,
It is shown mathematically that only three conductance factors the lower bound on the source current DF is considered and
(one for the fundamental and two other for odd and even given as,
harmonics respectively) are sufficient to determine the desired
reference source currents. The proposed algorithm determines
the conductance factors in 10 sec. Because of the smaller As discussed before, to achieve maximum power factor the
computational time, the proposed algorithm performs conductance factors for all the harmonics should be equal and
satisfactory under dynamically changing load conditions here it is denoted as . Using fundamental conductance
(other optimization based approaches are limited to steady- factor and harmonics conductance factor , the constraint
state condition). The performance of proposed algorithm is on source current DF can be rewritten as,
validated by a real-time hardware-in-the-loop experimental
prototype. The satisfactory real-time experimental results for
steady state as well as dynamic condition demonstrate the
feasibility of proposed algorithm for practical implementation. The maximum source side power factor can be achieved
when both the source voltage and current DFs are equal. Let
VIII. APPENDIX-I be the lower bound on DF specified by the user. To
achieve the maximum possible power factor under the
The system data for simulation as well as experimental study. condition where the source voltage DF ( ) is higher than
Base voltage (AC) - 415 V (L-L) , the source current DF should equate to . On the
System Base voltage (DC) - 750 V other hand, when is less than , the source current
Parameter
Base power - 15 kVA DF should equate to to achieve maximum possible
L1 :- 3-phase diode rectifier with 20 power factor satisfying DF constraint. The appropriate value
resistive load of can be selected by comparing the with .
L2 :- phase-a: 0.05+j0.15 pu, With this selected value of , the inequality constraint of
phase-b: 0.05+j0.175 pu and, (43) can be reformulated as equality constraint and expressed
Loads phase-c: 0.025+j0.125 pu as,
Steady state condition: L1 + L2
Dynamic condition: load is changed from
L1 to L1 + L2 and again brought back to L1
DC link capacitor = 2000 F; reference DC
From (44), can be represented in terms of as follows,
APF link voltage = 750 V; filter inductor = 6 mH

Copyright (c) 2011 IEEE. Personal use is permitted. For any other purposes, permission must be obtained from the IEEE by emailing pubs-permissions@ieee.org.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication.

13

Let be the user defined maximum limit on K-factor.


By comparing the with the source voltage K-factor
where, ( ) and following the similar procedure discussed in
previous sub-section the inequality constraint of (50) can be
Using and , the power balance constraint given in converted into equality constraints as follows,
(10) can be rewritten as,

By substituting (45) into (47), an expression to compute From (51), can be represented in terms of as follows,
can be derived as follows,

where,
Equations (45) and (48) present closed form mathematical
expressions to compute the optimal conductance factors which The expression for can be derived by substituting
maximize the source side power factor satisfying power from (52) into the power balance constraint of (47).
balance and DF constraints.

Table VIII: Performance indices achieved for optimization problem with DF
constraint. Equations (52) and (54) present closed form mathematical
expressions to compute the optimal conductance factors,
0.0000 0.6259 0.6259 0.9677 0.9677 which maximize the source side power factor satisfying power
0.9800 0.6348 0.4945 0.9677 0.9800 balance and K-factor constraints.
Using the same steady state per unit values of Appendix-II,
the optimization problem with KF constraint is solved and the
Using the steady state per unit values provided in the
results for equal to 10% and 2% are provided in Table-
Appendix-II, the optimization problem with DF constraint is
solved using (45) and (48). The results achieved with different IX.
values of are tabulated in Table-VIII. First is
Table IX: Performance indices achieved for optimization problem with KF
specified equal to 0%. As discussed above, the proposed constraint.
algorithm compares with to determine . As

seen from the Table-VIII, the specified DF limit of 0% is less 10 0.6259 0.6259 3.0482 3.0482
than , and therefore, the control algorithm chose 2 0.6386 0.4387 3.0482 2.0000
equal to . With this value of , the optimum
conductance factors, which ensure source current DF ( )
XI. REFERENCES
within the limit (equal to ) are computed and provided in
the Table-VIII. The conductance factors and [1] W. Mack Grady, Surya Santoso, Understanding Power System
Harmonics, IEEE Power Eng. Rev., vol.21, no.11, pp.8-11, Nov.
corresponding to equal to 98% is also provided in 2001.
Table-VIII. Note that is higher than in this case, so [2] B. Singh, K. Al-Haddad, A. Chandra, A review of active filters
the control algorithm chose equal to and the for power quality improvement, IEEE Trans. Ind. Electron.,
vol.46, no.5, pp.960-971, Oct 1999.
source current DF ( ) is achieved equal to [3] Yi Tang, Poh Chiang Loh, Peng Wang, Fook Hoong Choo, Feng
Gao, F. Blaabjerg, Generalized Design of High Performance
B. Constraint on Source Current K-Factor Shunt Active Power Filter With Output LCL Filter, IEEE Trans.
Another important power quality factor is the K-factor (KF) Ind. Electron., vol.59, no.3, pp.1443-1452, March 2012.
especially when non-linear load is supplied through [4] M. Angulo, J. Lago, D. Ruiz-Caballero, S. Mussa, M. Heldwein,
Active Power Filter Control Strategy with Implicit Closed Loop
transformer. The K-factor is a weighting of the harmonic Current Control and Resonant Controller, IEEE Trans. Ind.
currents according to their effects on transformer heating, as Electron, vol.PP, no.99, pp.1, 0.
derived from ANSI/IEEE C57.110. The K-factor for current is [5] A. Bhattacharya, C. Chakraborty, A Shunt Active Power Filter
defined as follows, With Enhanced Performance Using ANN-Based Predictive and
Adaptive Controllers, IEEE Trans. Ind. Electron., vol.58, no.2,
pp.421-428, Feb. 2011.
[6] G.W. Chang, Tai-Chang Shee, A novel reference compensation
current strategy for shunt active power filter control, IEEE
Transactions on Power Delivery, vol.19, no.4, pp. 1751- 1758, Oct.
2004.
To limit the transformer heating, the upper bound on K- [7] T.E. Nunez-Zuniga, J.A. Pomilio, Shunt active power filter
factor is given by, synthesizing resistive loads, IEEE Trans. Power Electron., vol.17,
no.2, pp.273-278, Mar 2002.

Copyright (c) 2011 IEEE. Personal use is permitted. For any other purposes, permission must be obtained from the IEEE by emailing pubs-permissions@ieee.org.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication.

14

[8] S.K. Jain, P. Agarwal, H.O. Gupta, A control algorithm for Component Separation of Unbalanced and Distorted Three-Phase
compensation of customer-generated harmonics and reactive Signals, IEEE Trans. Ind. Electron., vol.59, no.10, pp.3847-3859,
power, IEEE Transactions on Power Delivery, vol.19, no.1, pp. Oct. 2012.
357- 366, Jan. 2004. [27] H. Akagi, E. H. Watanabe, M. Aredes, Instantaneous Power
[9] Shyh-Jier Huang, Jinn-Chang Wu, A control algorithm for three- Theory and Applications to Power Conditioning, IEEE Press,
phase three-wired active power filters under nonideal mains Wiley Interscience, 2007.
voltages, IEEE Trans. Power Electron., vol.14, no.4, pp.753-760,
Jul 1999.
[10] Cheng-Che Chen, Yuan-Yih Hsu, A novel approach to the design Parag Kanjiya received his B.E.
of a shunt active filter for an unbalanced three-phase four-wire from the B.V.M. Engineering College,
system under nonsinusoidal conditions , IEEE Trans. Power Sardar Patel University, V.V. Nagar,
Delivery, vol.15, no.4, pp.1258-1264, Oct 2000. India, in 2009 and M. Tech. from the
[11] A. Chandra, B. Singh, B.N. Singh, K. Al-Haddad, An improved Indian Institute of Technology Delhi
control algorithm of shunt active filter for voltage regulation, (IITD), New Delhi, India, in 2011. He
harmonic elimination, power-factor correction, and balancing of was awarded with K.S. Prakasa Rao
nonlinear loads, IEEE Trans. Power Electron., vol.15, no.3,
Memorial Award for getting highest
pp.495-507, May 2000.
C.G.P.A at IITD in August, 2011.
[12] V.M. Moreno, A.P. Lopez, R.I.D. Garcias, Reference current
estimation under distorted line voltage for control of shunt active Since October 2011 he is a
power filters, IEEE Transactions on Power Electronics, vol.19, Research Engineer at Masdar Institute
no.4, pp. 988- 994, July 2004. of Science and Technology, Abu
[13] M. I. M. Montero, E. R. Cadaval, F. B. Gonzalez, Comparison of Dhabi, UAE. His research interests include applications of power
Control Strategies for Shunt Active Power Filters in Three-Phase electronics in distribution systems, power quality enhancement,
Four-Wire Systems, IEEE Transactions on Power Electronics, HVDC, FACTS and power system optimization.
vol.22, no.1, pp.229-236, Jan. 2007.
[14] A.E. Emanuel, Powers in nonsinusoidal situations-a review of
definitions and physical meaning, IEEE Trans. Power Delivery, Vinod Khadkikar (S06-M09)
vol.5, no.3, pp.1377-1389, Jul 1990. received his B.E. from the Government
[15] S.M.-R. Rafiei, H.A. Toliyat, R. Ghazi, T. Gopalarathnam, An College of Engineering, Dr. Babasaheb
optimal and flexible control strategy for active filtering and power Ambedkar Marathwada University,
factor correction under non-sinusoidal line voltages, IEEE Trans. Aurangabad, India, in 2000, M. Tech.
Power Delivery, vol.16, no.2, pp.297-305, Apr 2001. from the Indian Institute of Technology
[16] G.W. Chang, C.M. Yeh, Optimisation-based strategy for shunt
(IITD), New Delhi, India, in 2002 and
active power filter control under non-ideal supply voltages, IEE
Ph.D. degrees in Electrical Engineering
Proceedings - Electric Power Appl., vol.152, no.2, pp. 182- 190, 4
March 2005. from the cole de Technologie
[17] G.W. Chang, Chia-Ming Yeh, Wei-Cheng Chen, Meeting IEEE- Suprieure (E.T.S.), Montral, QC,
519 current harmonics and power factor constraints with a three- Canada, in 2008, all in Electrical
phase three-wire active power filter under distorted source Engineering.
voltages, IEEE Trans. Power Delivery, vol.21, no.3, pp.1648- From December 2008 to March 2010, he was a Postdoctoral
1654, July 2006. Fellow at the University of Western Ontario, London, ON, Canada.
[18] G.W. Chang, A new approach for optimal shunt active power Since April 2010 he has been an Assistant Professor at Masdar
filter control considering alternative performance indices, IEEE Institute of Science and Technology, Abu Dhabi, UAE. From April
Trans. Power Delivery, vol.21, no.1, pp. 406- 413, Jan. 2006 2010 to December 2010, he was a visiting faculty at Massachusetts
[19] S. George, V. Agarwal, A DSP Based Optimal Algorithm for Institute of Technology, Cambridge, MA, USA. His research
Shunt Active Filter Under Nonsinusoidal Supply and Unbalanced interests include applications of power electronics in distribution
Load Conditions, IEEE Trans. Power Electron, vol.22, no.2, systems and renewable energy resources, grid interconnection issues,
pp.593-601, March 2007. power quality enhancement, active power filters and electric vehicles.
[20] K.R. Uyyuru, M.K. Mishra, A. Ghosh, An Optimization-Based
Algorithm for Shunt Active Filter Under Distorted Supply
Voltages, IEEE Trans. Power Electron, vol.24, no.5, pp.1223-
1232, May 2009. Hatem H Zeineldin (M06) received
[21] N. Pogaku and T. C. Green, Harmonic mitigation throughout a the B.Sc. and M.Sc.degrees in electrical
distribution system: a distributed generator-based solution, IEE engineering from Cairo University,
Pro. Gener. Transm. Dsitrib., vol. 153, no.3, pp. 350-358, May Cairo, Egypt, in 1999 and 2002,
2006. respectively. In 2006, he received the
[22] M.T. Chen, Z.M. Yu, Determination of frequency variation effect Ph.D. degree in electrical and computer
on DFT-based algorithms for harmonic and flicker measurements, engineering from the University of
Transmission and Distribution Conference and Exposition, 2003. Waterloo, Waterloo, ON, Canada.
[23] IEEE Recommended Practices and Requirements for Harmonic He worked for Smith and Andersen
Control in Electrical Power Systems, IEEE Standard 519-1992, Electrical Engineering Inc. where he
1993. was involved with projects involving
[24] IEEE Standard Definitions for the Measurement of Electric Power distribution system design, protection,
Quantities Under Sinusoidal, Nonsinusoidal, Balanced, or and distributed generation. He then worked as a Visiting Professor at
Unbalanced Conditions, IEEE Standard 1459-2010 (Revision of
the Massachusetts Institute of Technology (MIT), Cambridge. He is
IEEE Standard 1459-2000), March 19 2010.
an associate professor with Masdar Institute of Science and
[25] A. J. Wood, B. Wollenberg, Power Generation Operation and
Control, Second Edition, Wiley Interscience, 1996.
Technology, Abu Dhabi, UAE and currently a faculty member at
[26] F.A.S. Neves, H.E.P. de Souza, M.C. Cavalcanti, F. Bradaschia, Cairo University in Egypt. His research interests include power
E.J. Bueno, Digital Filters for Fast Harmonic Sequence system protection, distributed generation, and deregulation.

Copyright (c) 2011 IEEE. Personal use is permitted. For any other purposes, permission must be obtained from the IEEE by emailing pubs-permissions@ieee.org.

Das könnte Ihnen auch gefallen