AIR COOLED SPLIT TYPE AIR CONDITIONERS

Series

PE
MECHANICAL SPECIFICATIONS
1. General 3. Outdoor Units (Condensing Units)
All units consist of a ceiling-concealed indoor unit (evaporating unit), an Casing
outdoor unit (condensing unit) and awall-mounted remote control switch All condensing units casing is 0.8mm thick steel with exterior surfaces
and are factory-assembled and fully charged with R-22. They are also coated with polyester resincoating
tested and checked under astrict quality control system in the factory. The
units can be easily connected together with refrigerant pipe and the Compressor
control switch can be wired in lhe 'feld. They are designed to operate at All condensing units have high e(iciency type, hermetic, line-starting
outdoor ambient temperature as high as 52C DB (125F). compressors. Compressors are equipped with an internal thermostat.
overcurrent relay, high and low pressure switches.
2. Indoor Units (Evaporating units)
Casing Condenser Coil
All panels are made of 1mm thick galvanized steel, and are insulated by Condenser Coils are made of 9.52mm OD, 0.35mm thick sea11less
10mmthick, 40kg/m3 glass w~ol witha protective 'flm of PVC. copper tubes mechanically bonded to 0.12mm thick aluminium 'ins. ~c:"
coil is leak-tested at a pressure of 33kg/cm 2 at the factory. Tr::, ~--:
Drain Pan provided with strainers attached to the capillary tubes to further eris_= ~
Each unit has a 1mm thick steel drain pan coated withepoxy resin enamel clean system.
and is insulated with 10mm thick polyurethane foam. It has a 34mm OD
maledrain connection. Condenser Fan
A weather proof squirrel-cage induction motor is used to drive the
Evaporator Coils condenser fan witha Iight plastic propeller fan designed to reduce energy
Coils are made of 9.52mm OD and 0.35mm thick seamless copper tubing requirement which ensures quiet operation.
mechanically bonded to 0.12mm thick aluminium 'ins and are factory leak
tested at a pressure of 28kg/cm2. Room Thermostat
All units have awall-mounted electroniccontrol switch with leatures such
Evaporator Fans as an on-off switch, room temperature control thermostat and indication
Direct-driven, forward curved, centrifugal-type fans are used to deliver an pilot lamps.
accurate air low at a low noiselevel. Fan-driving components are mounted
on rubber pad isolators to reduce noise andvibration.

TYPICAL INSTALLATION EXAMPLE

-2-
STANDARD & OPTIONAL ACCESSORIES

~ PE-3E PE-4E PE-SE PE-6E PE-6G PE-8G PE-lOG PE- 12G PE-16C PE-20G

AIR FILTER 0 0 0 0 0 0 0 0 0 0

ANT I PHASE PROTECTOR . X X X X X X X X

ANTI RECYCLE TIMER X X X X X X X X X X

ROOM THERMOSTAT X X X X X X X X X X

COMP. CONTACTOR X X X X X X X X X X

EVAP.FAN CONTACTOR X X X X X X X X X X

EXPAN.CAP lLLA RY TUB E X X X X X X X X X X

HIGH-PRESSURE SWITCH X X X X X X X X X X

LOW-PRESSU RE SW ITCH X X X X X X X X X X

MOUNTING BRACKETS X X X X X X X X X X

OVER CURRENT RELAY X X X X X X X X X X

SUPPLY DUCT FLANGE X X X X X X X X X X

SUCT.&DISCH.STOP VALVE X X X X X X X X X X

SELF DIAGONASIS CO T.SYSTEM X X X X X X X X X X

INTERNAL THERMOSTAT X X X X X X X X X X

CRANK CASE HEATER X X . . . X X X X X

X : STANDARD ACCESSORTES, 0 : OPTTONALACCESSORIES, - : NOT AVAILABLE

MA DELUXE REMOTE CONTROLLER PAR-21MAA


Unit:mm
Dot liquid - crystal display is applied
Symbols, Japanese, Chinese, English, Germany, Spanish, Russian, Italian, French display can be selected freely.

130 46

Front View Side View Rear View

Function:
I.ON/OFF. 6.Auto Off Timer.
2.Cool/Dry/Fan. ? .Operation locking function.
3 .Self Diagnostic Function. 8.Weekly Timer.
4.Return Air Temp. sensor. 9.Real Time Clock.
5.Auto Recovery Function. 10.Multy language display

3-
SPECIFICATIONS

Item Model PE-3E PE-4E PE-SE PE-6E PE-6G


Function Coolin2
Kcal/h 6700/ 6100/ 5712 9100/ 8000/7594 11200/ 10200/941 l 14000/ 12700/ 11925 I 5120/ 13400/ 12900
*I.Capacity NOM/NET-1/NET-2 BTU/h 26800/24400/22680 36400/32000/30150 44800/40800/3 7360 56000/50800/4 7000 60000/ 53000/ 51000
Waus 7800/71 50/ 667 1 I 0600/93 75/ 8868 13000/1 1955/10988 163 00/ 14885/13482 17600/15600/ 15000
Sensible Heat Factor SBF 0.72 0.76 0.84 0.78 0.82
Total lnput NOM (NET) *2 kW 3.41 (3 .96) 3.59 (4. 16) 4.94 (5.06) 5.93 (6.03) 5.98 (7, I 0)
Power Supply Ph-Hz-V 1-50-220(240)
input kW 0.25 0.32 0.87 0.87 0.87
Running Current A 1.07 J.39 4.0 4.0 4.0
Starling Current A 2.60 2.60 6 .1 6.1 6.1
External Finish GALVANIZED SHEETS
Evaporator ALUMfNUM CROSS FfN
Fan(Drive) x No. CENTRIFUGAL DJR.ECTD.RJVEX I
f- Fan Motor Output
;z kW 0.2 0.3 0.46 0.46 0.46
:::> Air Flow (low- High) CMM(CFM) 19-22 (67 1-777) 27-34 (935- 1200) 34-45 ( I 200- I 600) 40-50 (1412- 1765) 44-55 (1550-1940)
c.::
0 External Static Pressure mmAq (Pa) 5 (50) 10 ( 100) 10 ( 100)
0 Operation Control & Thermostat
0 WIRED REMOTE CONTROL
25 Noise Level (Low -High) *3 dB (A) 46-48 45-49 45-49
Cond.Dra in Conn. O.D 111111 (in) 32 (I) male
Widtb mm (in) 785 (31-0) 1055 (4 1-J /2) 1180 (46-1 /2) 1180 (46-3116)
Dimensions Depth mm (in) 690 (27-1/ 6) 690 (27-1 /6) 634 (24-3/ 8) 634 (24-3/8)
Height mm(in) 428 (16-7/8) 428 (16-7/ 8) 400 0 5-5/16) 400 (15-5/ 16)
Weight kg (lbs) 46 (101) 5 8 (120) 56 (124) 5 6 (124) 59 (130)

Model Name PU-3 PU-4 PU-5 PU-6


Power Supply Ph-I-lz-V 1-50-220(240) 3-50-380(4 15)
Input kW 3.3 '1 3.61 4.19 5 .1 6
Running C01,-ent A 14.4 16.7 6.86 8.45
Starting Ctm-ent A 93 80 64 68
External Finish MUNSELL 3Y7.8/J . I
Refrigerant Control CAPILLA.RV T UBE
f-
z::, Compressor
Motor Output
ROTARY HER.i\1ETICALLY CLOSED SCROLL
kW 2.2 2.7 3.5 4.2
ex:
0 Starter Type LINE START
0
0 Protection Devices *4(V) *4(Y)
5
0
Crank Case Heater *5 kW 0.032 -
Condenser ALUMINUM CROSS F IN
Fan (Drive) PROPELLER-DIRECT DRIVE
Fan Motor Output x No kW 0.085x l 0.065x 2 0.l x2
Air flow CMM (CFM) 50 ( 1765) 95 (3352) JOO (3530)
Noise Level *3 dB(A) 52 54 55 56
Width mm (in) 870 (34-1 /4 ) 870 (34- 1/4) 970 (38-3/16)
Dimensions Depth mm (i n) 320 (12-5/8) 320 {12-5/8) 370 {14-9/ 16)
Height mm (in) 850 (33-1/2) 1258 (49-1/2) 1258 (49-1/2)
Weight kg (lbs) 73 (161) 94 (207) [19 (262) 120 (265)
0 Refrigerant R-22
25 Charge FACTORY PRECHARGED
e::
0.. Liquid mm (in)
Pipe Size O.D '"6 9.52 (3/8)
f-
z Gas mm (i n) 15.87 (5/8) I 19.05 (3/4)
~
w Cormection Method lndoor LTQ / GAS FLARE
0 Outdoor LIQ I GAS FLARE
o2
J.t-. Difference between the Height max.M 30
~ Indoor & Outdoor Unit Length mnx .M 50

Note:
* A ll machines indicate readings at (JlS 8616), Indoor: D.B. 27 C(80 F),W.B.19C (66F) & Outdoor: D.B. 35C(95 F),W.B.24C (75F).
* !.Nominal Capacity Based on = Indoor: D.B. 27 C(80 F),W.B.19.5C (67F) O utdoor: D.B. 35C(95 F).
NetCapacity-1 Based on = Indoor: D.B. 27 C(80 F),W.B. 19.5C (67F) Outdoor: D.B. 46C( l l5 F).
Net Capacity-2 Based on = Indoor: D.B. 24C(76 F),W.B. 17.0C (63F) O utdoor: D.B. 46C(l 15 F).
* 2.Total Input Nominal based on : 1Ph-50Hz-220V&3Ph-50Hz-380V at an ambient temperature of35C (95 F) D.B.
Total lnput Net based on : 1Ph-50Hz-240V&3Ph-50Hz-4 15Y at an ambient temperature of 46C ( 11 5 F) D.B.
* 3. oise level is meas ured in an unacoustic room based on JIS condition.
* 4.Thermal Relay, Thermal switch, HP & LP switch, Anti phase protector,lnternal them1ostat(V- l Ph,Y-3Ph) and Fuse.
* 5.Capacity of crank case heater (kW) based on 220 volts.
* 6.Both refrigerant pipe should be insulated seperately.
* ?.Guaranteed operation up to 52C outdoor temperature. -4-
SPECIFICATIONS

Item Model PE-8G PE-lOG PE-12G PE-16G PE-20G


Function Cooling
Kcal/h 20200/17900/ l 7200 25200/22500/2 1500 28900/25700/24500 40400/3 5800/34 l 00 50400/44900/42900
"' ! .Capacity NOM/NET- l/NET-2 BTU/h 80000/7 l 000/68000 l 00000/ 89000/ 85000 114500/ J02000/97000 l 60000/ )42000/135000 200000/1 78000/17 0000
Watts 23500/20800/20000 29400/26500/25000 33600/29900128500 46900/41700/39600 58700/52200/49900
Sensible Heat Factor SHF 0.74 0.75 0.74 0.69 0.69
Total Input NOM (N ET) *2 kW 7.65(8.91) 10.25(1 1.94) 11.37(1 3.25) 14. 85( 17.30) 2 1. 1(24.60)
Power Supply Ph-Hz-V 3-50-380(4 l 5)
Input kW 1.00 1.12 1.22 1.55 2.84
Running Current A 1.8 2.0 2.3 3.8 5.4
Starting Current A s.o 5.0 6.4 8.5 10.0
External Fi nish GALVANIZED SHEETS
Evaporator ALUM INUM C ROSS FJN
Fan Drive x No. CENT RJFUGAL DIRECT DRJVE X 2
f- Fan Motor Otttpot kW 0.75 0.75 0.77 1.3 1.8
~
i:,:::
Air Flow (low- High) CMM(CFM) 52-65 (1836-2300) 64-80 (2260-2830) 72-90 (2540-3 180) 120 (4240) 160 (5650)
0 External Static Pressure mmAq ( Pa) I O( 100) IS (1 50)
0
Operation Control & Thermostat
~
WIRED REMOTE CONTROL
Noise Level (Low -High) *3 dB (A) 45-49 46-50 48-5 1 52 53
Cond.Drain Coo n. O.D mm(in) 25 ( l) male
Width nu n (in) 1400 (55-1 / 8) 1600 (63- 0) 1947 (76 - 5/8)
Dimensions Depth mm(in) 634 (24-3/ 8) 634 (24-3/8) 764 (30- 1/ 16)
Height mm (in) 40 0 (15-5/1 6) 400 (lS-5/ 16 ) 595 (23-7/16)
We ight kg ( lbs) 70 (154) 77 (169) 130 (286) )33 (293)

Model Name PU-8 .P U-10 PU-1.2 PU-8 x 2 PU-10 x 2


Power Supply Ph-Hz-V 3-50-380(4 1S)
Input kW 6.65 9.1 3 10. 15 6.65 X 2 9.13 X 2
Running Current A 13.0 16.6 17.9 13.0 x 2 !6.6 x 2
Starting Current A 95 125 118 108 141.6
External Finish MUNSELL 3Y7.8/ l . l
Refrigerant. Control CAPl LLARY TUBE
E-<
Compressor
Motor Output kW
HERMETICALLY C LOSED SCROLL

i:,,: 5.6 7.5 8.6 5.6X2 7.5X2


0 Starter 1ype LINE START
0
0 Protection Devices *4
5
0
Crank Case Heater "'5 kW 0.09 0.09X 2
Condenser ALUMINUM CROSS FIN
Fan (Drive) PROPELLER-DIRECT DRIVE
Fan Motor Output x No kW 0. 15 X2 (0.15 X 2)X2
Air Flow CMM (CFM) 160 (5650) 160 (5650) X 2
Noise Level *3 dB (A) 66 66 / uo it
Width mm (in) 1047 (41 -1/4) 1047 (41- 1/4) / unit
Dimensions Depth mm (in) 547 (2 1- 1/2) 547 (21- 1/2) / unit
Height mm (in) 1480 (58 -5/1 6) 1480 (58-5/16) / unit
Weight kg (lbs) 197 (433) 206 (453) 208 (458) 197 (433) / unit 206 ( 453) / uni t
0 Refrigerant R-22
~ Charge FACTORY PRECHARGED
t:>..
0::: Liquid mm (in) 15.88 (5/ 8)
E-< Pipe Size 0 .D * 6
Gas
~
mm(in) 28.6 ( 1-1 / 8)
Indoor UQ / GAS BRAZE
w Connection Method
0 Outdoor LIQ / GAS FLARE
i:2
>-L< Difference between the Height max.M 30
w Indoor & Outdoor Un it Length
....c,,'. max.M 50

Note:
* AH machines indicate readings at (JIS 86 l 6), Indoor: D.B. 27 C(80 F),W.B. l 9C (66F) & Outdoor: D.B. 35C(95 F),W.B.24C (75F).
* I .Nominal Capacity Based on Indoor: D.B. 27 C(80 F),W.B. l 9.5C (67F) Outdoor: D.B. 35C(95 F).
Net Capacity-I Base_d on Indoor: D.B. 27 C(80 F),W.B. I 9.5C (67F) Outdoor: D.B. 46C( I I 5 F).
Net Capacity-2 Based on Indoor: D.B. 24 C(76 F),W.B. l 7.0C (63F) Outdoor: D.B. 46C(J l5 F).
"' 2.Total Input ominal based on :!Ph-50Hz-220V&3Ph-50Hz-380Vat an ambient temperature of35C (95 F) D.B.
Total Input Net based on : I Ph-50Hz-240V &3Ph-50Hz-4 l 5V at an ambient temperature of 46C (115 F) D.B.
* 3.Noise level is measured in an unacoustic room based on HS condition.
* 4.Them1al Relay, Thennal switch, HP & LP switch, Anti phase protector,Internal thermostat and Fuse.
* 5.Capacity of crank case heater (kW) based on 220 volts
* 6.Both refrigerant pipe should be insulated seperately.
* 7.Guaranteed operation up to 52C outdoor temperature.
-5-
]
INDOOR UNIT Unit : mm (inch)

PE-3E 600(24)

Rolrigoranl-ppe flare<! oonnecUon 09.52 (318) - - -- ',-r.---a::- -- - - ----, <if ,nnl


Refrigerant-pipe flared connection 0 15.88 (518)
~g Fl-"-
,ooJJ'~------~
----~rr!:Elaa====''~

SeMCe panel (Indoor coil thermistor) ---/,~ ~ =

Room tomp,uature thermistol' 510(201/8)


418(161/2) 10(3/8)
Air intake duct flange
(23l8) 20(13116"'
) ++-- 33_9-'-
(1_3_-318
---'-
) ---l
175 60 265(101/2)

690(273/16)

For ait outtc1duct con.nec1ion


(12- 03 ( 1/8) hales)

600(24)
PE-4E __ I I
"'?i ~
---
980 389/16)
11
I~ _g_ J
Drainage p'pe conooctioo R1 (ma.I~)
lo ....
~
Aerrigerantpipe flared oonnectlon 09.52 (318) 0
O>
w

j [:
RoM9eran1-plpe flared connection 019.05 (314) - ---!ll:rn
~
"'
.,-'!'.
~::::
Room temperature thermistor
795(31S,'16) 35 re~g 418(16112) 10(3/8)
Air intake duct flange 20(13116) 339(13318)
1 I X6,5{=715)

++++++++++

~
8
+ "'
e ~
20 ":- 0
960(27-3116)
~
For air outtet duct connection
(24 03 (1/8) holes)
i Sl
0
!:?

7X65(=455)

1 315ll6)
9 361/4
500(1911/16) ,,,,----, Mounting Plate
w
-1-- -1--- - - - - - - - - -- I - - ~ ~
rn-========;;;;,i- , - -t!:l.

-6-
Unit : mm (inch)
INDOOR UNIT
PE-SE & GE
34(1-1 1132")
"
121.13?1 6X130(:780 [30-231.32'[) 51 (2-1132")

Re!um air
dud flange

Codroloox

Rwber oosh<Remote
ixrtrollermrJ) 108014217/32"1

Rubber bush 14-~3.1 Holes


(CAJ!doortril
coonectoo wiring)

Rubber tush 4- ~12Holes

t <Powerwpply
~iling> <For hanijng boh M10>
[Fiel:l!l.!ll)lyJ

l
11 80146-1S/311
1120(44118'1
40 (1-19/32"1 1040[40-31132"J 40(1-19/32'1
I
'

-~-
361 114-7132'( 500[191 1/lS'j I 119

.....
~
=
' (7-1/16']

---~
~!
'!:!
i ~i"'
- -~
-_
1064 [4129/32'1

Rehi'J,r'dll riJ1e (L~uid)


~9.52(3/Sflare)

PE-6G
_124.
<A<)Cessory> 51 6X130(:1&1)
Pipe oovcr , 2pcs.
(For dew oondonsation prevention of Aelumair
local piping and unit connection.) duct flange
Rernole controller 1pc.

20-~3Holes

Rubber bush (Remote


control.er wiring) 1080

t Rubber bush 14 1P3.1Holes


l (Outooorun11
oonneclion wiring)

~
Rubberbu$h 4- ~12 Holes
<Power supply
wifinQ)
!:~~:. 56 , 11 , 3X130(a300) I~ ( For hanging boll M10)
{Field supply)

1180
1120
40 I 1040 I 40
Refrigeranl pip,e - - - - , 361 500 I 1)9
qi 19.05 (3/4 ttore) '
I - --
' I l
=
!i!
Return air '- I 11
~

::
1064

Refrigtuan.t pipe Otain R1


~9.52 (3/8 flare}

- 7-
Unit : mm (inch)
INDOOR UNIT
PE-8G

<Accessory> 1102
Pipe cover .. .. 2pcs. 8x130(=1040)
(For dew condensation prevention of
local piping and unit connection.) Return air
Remote controller .. .. 1pc. duct flange

24-lhHoles
Control box
Rubber bush ( Remote
controller wiring )
"'
~ -~-+_.,.__ _ _ _ __ __ 1_3_00_ _ _ __ _ _ _ _ _ _ ~
-
Rubber bush
(Ou1door unit 22. 1.13, 1 Holes
connection wiring )

Rubber bu
(Power supply
w iring) Supply air 441 2 Holes
duct flange
7x130(=910) ( Fo r hanging bolt M 10 )
[Field supply]

Return air
1400
Refrigerant pipe 1340
~25.4 (1 braze) 40 1260 40
I I
155 1000 I 105

--~ -== ~

_.__
'=
.1 I I I "'
"'
::
Refrigerant pipe Drain Rt
~ 15.88 (5/8 braze) 1284

PE-10G & 12G

<Accessory> 1302
Pipe cover .. 2pcs. 9X130(=1 170)
(For dew condensation prevention of
local piping and unit connection.) Return air
Remote controller 1pc. duct flange

Control box
Rubber bush ( Remote
controller wiring )
~ -~-+,_,.__ __ _ __ _ _ _ _1
_soo
____________......,2_0
Rubber bush
(Outdoor unit
connection wiring ) 22- 93.1 Holes

Rubber bush
( Power supply
w iring )
Supply air
duct flange
130 I e
4.912 Holes
45, , 7x130(=910) _ 45 ( For hanging bolt MlO )
-;>!,-,',.._---
1 1 --~-~----...,_,..,,_
~ (Field supply]

1600
1s-l
Refrigerant pipe 40 1460 40
\128.6 (1-1 /8 braze) ~
I
- I

255 1000 205


=l=~==:::-1:.l---;;;r.r- --,-:--, I I

--~ =
I -~
.,, O>

Return air Supply air g

= I I I 1.
N

Refrigerant pipe Drain Al


-'--

1484
-
<Pt5 .88 (5/8 braze)

-8-
;I :r: 7'

"'O -
mZ
,C
.... 0
<Accessory>
Pipe cover .... .. .. .. ........ . -4pcs. 1618 cno
C)::c
(For dew condensation prevention o f 12X130.(=1560:
local piping and unit connection.) 120c
Return air I\) z
Remote controller ... .. ....... ... ..1pc.
; .;. , + .;. ~ duct flange o_
C) --t
<')
0
N

+I---+
Control box

II-Id 1840 ~II 20 ~


Rubber bush Rubber bush
<P9wer supply <Remote controller .,..,1,
wInng> wiri ng> 24 - \13.1 HOLES '<t

Rubber bu'sh + +

~ I.
<Outdoor unit
connection wiring> 4 -i 15 HOLES
Supp ly air <For hanging bolt M12
duct ffange 42.5,11. 8X130(=1040) 4:5
[Field supply]

<.O
Refrigerant pipe
: i/>28.6 (1-1/8 braze)
(2 places ('1 part)]
. \
Refrigerant pipe 764
~15.88 (5/8 braze) 1947
664 50
(2 places ('2 part)] 1880
10 40 1800 ..J 1_40
I
395 1125 280

co
~ co
~

q q U}

Return air Supply air :R ~


<')

m~t;?ii - - -1 - -
.It ~
Ii
~ ,.,,;;,;;,;;,~'! N'

Drain R1 39 700 ,I I
1824
-.,
N
C
::::)
;:;:

3
3
~

sC')
2
Unit mm (inch)
OUTDOOR UNIT
PU-3

Outctoor Unit-necessary surround ng clearance

~
185 185
(7-91321_ 500(19-11/16) 5'9/32)
Ou1ooor un,1,necessary surrounc,ng Clearance
(Concef\ttated u"lstallaton) The upper s.de must be c:pen. {>As intake ! I _ Note Alow ade,qvat&

-1O - -I ~
'
u~r clearance

~
~k For 10 units 0< less I I 1OOQ
Airovtle1

ce

Handle
10rmov>ng

~ Side au 1

Ae31 Ires
ttJ air,ntake Handle tor movi

I
I
?}l \I 00
- T;J Rear pcp1ng hole
(1elrigerant,dra1nage
andwnng)
Knock out hO,e
tor tr o o t ~
{relngeranl.dra.nage ." ~/~
and w,nng) -9<'0 ,f!,'7 I . I
8onom
PI n g , , , ,I . ~;
2-u-...peo , I-"'
';~
!t/7
__i__l J.-
" //.
i i gl ~ //,
not<heo : . ! 1 .; 1 Standa<d bOl1 length
\ hOles : I 8 ~
--
12
lI -=i.. Ft cx,tnghtoip1ngholes
~-+- deta,I f,gures

PU-4

Outdoor Uni1-necessa,y surround "0 ctoara.nce Outooor urwi~necessaiy surrounding clearance


(Concentrated ins1aAatlon}
The upper side mus1te open,
185
(7-9/32)
185
(7-9132) ~~lowadequat
+1Q.

~
~ ._.,pef c!~arance
Front opening

c:>
Airinlake
Few 10unitsorl8:SS 1000

Terminal block tor er Une

~~~ ==*==~==W/''------1 (Gtol#ld lesminal)

Side airintake

Handle

~
Rear fres
~ air intake

tT
'1
~
5 . ~ --
Rear l)Qing hole

- 10 -
Unit : mm (inch}
OUTDOOR UNIT
PU-5 & 6
Outdool' Unit-Nocessary surrounding clearance Outdoor Unrt-Nece&sary surrouf\ding ctearan.ce
(~ntrated Installation)
~
The upper side mus1be open.
185 Note:Allow adequate
(7-9132) 10 upper clearance

Side air intake


Handle
for moving

Rear tres
~ air inlake
Handle foe movi

t-~
I
~
-
~- ~ --
Rear pipino hole

l~ Standal'd bOlt l&ngth

F, on1 right piping ho(es-


detail figu:res

PU-8, 10 & 12

1047
<AccessorY>
Conduit mouting plate 108.5 830 108.5
(Painted the same color as the unit body)
a)e271pc.
b)e34 ............... , pc. """'
(') ~ I {l,Airinlet 1
Tapping screw 4512 4pcs.
Connection pipe l pc. -e . I l
Packlng ....... ..................................... ,pc
,._.,, Q
;:i; fg I I Air
Note 1. It is possible to change to 027 or 034 by inlet
selecting the conduit mounting plate a,b. I I

.,~ J
M ~ {), Air outlet
4-100 20 Holes
<formotlllJOg
anchorbo'I MS>
(F,eld supply)

Koock out hole


Piesstxegauge
(For option)

Relrige,ant pipe
:015.88(518 fare)
Rehige1ant pipe
PUSYAKD
PUH-8YKA
:025.4 1111ange)
PIJ10,12'i'AKD
PIJH lOYKA
:028.6 (1-118 flange)
Comection ppe./l p'. -~
(Accesso,y> ELL
For the power For the indoor unit
supply wiring connection w11ing

- 11 -
Precautions/recommendations concerning the installation and operation of Mitsubishi Electric Aircondltloners.

When used in rooms with high ceilings, it is recommended that a ceiling fan or circulator be installed to improve air circulation and temperature vatiations within the room.
The remote-control circuits under microprocessor control remain on at all times whether the air conditioner is not in operation. Fore more economical operation, it is
recommended that the main power switch be turned off when the air conditioner(s) is not used for long periods.
Avoid exposure to high-frequency waves as this may cause the microprocessor to malfunction.
Rated noise levels were derived from tests in an anechoic test room. Noise levels may therefore be greater depending on the surroundings, application, and/or manner ot
installation.
Avoid using air conditioners in rooms with high humidity because exessive condensation will OCCtJr as lhe air cools.
To avoid tire hazards, do not use air conditioners in areas where inflammable gases are present.
Odours for buildings, cosmetics, perspiration, tigarette smoke, etc., may accumulate in the heat exchanger and emanate from the air conditioner. This is not indicative of
mechanical trouble.

The Air Conditioning & Refrigeration Systems Works acquired ISO 9001 certification under Series
9000 of the International Standard Organ ization (ISO) based on a review of Quality management for
the production of refrigeration and air conditioning equipment.

ISO Authorization System


The ISO 9000 series is a plant authorizati.on system relating to quality management as stipulated by
the ISO. ISO 9001 certifies quality management based on th e "design, development, production,
CC3 installation and auxiliary services" for products built at an authorized plant.
FM33568 / ISO 9001 ;2000

The Air Conditioning & Refrigeration Systems Works acquired environmental management system

'
standard ISO 14001 certification.

The ISO 14000 series is a set of standards applying to environmental protection set by the
UKAS
ENVIRONMENTAL International Standard Organization (ISO).
MANAGEMENT
051

J... MITSUBISHI ELECTRIC CORPORATION


http ://Global.Mitsubishi Electric .corn/
New publication effe<:tive June 201 O