Sie sind auf Seite 1von 25

MidD APS 1500A-230

Inverter Solutions Presentation


MidD APS 1500A-230

MidD_APS 1500A-230-6 SSW MidD_APS 1500A-230-8

11-05-27 Delta Energy Systems 2


MidD_APS 1500A-230-6 SSW

MidD PowerBox , WxHxD: 600mm x 11U x 480mm

Floor, rack-top (ETS/MidD), plinth or wall mounting


(key hole).

6 pcs API 1500A-230 inverters + SSW7500A-230


static switch. One redundant API 1500A-230 module
stand-by.

045 C full power, 4560 C reduced power,


derating -2%/C typically.

AC Power output

208 / 220V / 230 / 240 Vrms, 50/60Hz


configurable.

7.5 kVA/6.0 kW (PF 0.8), 10.5 kVA for 5s

32.5 A nominal, Overload capability 140


%/45.5 A for (5s) .
11-05-27 Delta Energy Systems 3
MidD_APS 1500A-230-6 SSW

19 subrack modules combined in MidD enclosure for


industry standard 600mm wide frame. Optional door
assembly.

LED-Indications:

Input ON, Output ON, Overload / Fault

Output loading, 4 levels: >5%, >30%, >50%, >80%

Insulating cover in front of PDU for protection

Safety: EN 60950 , IP20 protection class

EMC:

Inverters: EN 55022B, EN61000-6-3, EN61000-6-2,


ETS 300 132-2, BTNR 2511 (NEBS)

Static switch: As inverters except immunity;


EN61000-4-3 radiated immunity according to
EN61000-6-1, other immunity standards EN61000-

11-05-27 Delta Energy Systems


6-2 4
MidD_APS 1500A-230-6 SSW

DC power input

6 pcs MCB C40A and 35 sqmm terminal


blocks

One common feed to common rails

One feed for dual shelf to dual connector

Individual feeds to MSBs and terminals

Remote Monitoring with RS-232 bus (D-sub at SSW)

AC-input for SSW 7.5kVA and by-pass switch

208 / 220V / 230 / 240 Vrms, 50/60Hz


configurable

1-phase, MCB 40A C-curve

11-05-27 Delta Energy Systems 5


MidD_APS 1500A-230-6 SSW

AC PDU options

15 x MCB 240A, GE G60 B or C curve

15 x DPN MCB 240A, GE G60 B or C curve

Auxiliary alarm switches with 10 x MCB/DPN

Neutral and PE rails with MCB. PE rail with DPN.

Cover plates

Alarm connections

Fuse alarm (aux)

Inverter alarm: Fault in system summary alarm


(module failure, DC input low, etc)

SSW alarm: Primary supply failure (system with


bypass) or Output ON indication (system without
bypass)

11-05-27 Delta Energy Systems 6


MidD_APS 1500A-230-6 SSW

11-05-27 Delta Energy Systems 7


MidD_APS 1500A-230-6 SSW

11-05-27 Delta Energy Systems 8


MidD_APS 1500A-230-6 SSW

11-05-27 Delta Energy Systems 9


MidD_APS 1500A-230-6 SSW

11-05-27 Delta Energy Systems 10


MidD_APS 1500A-230-8

MidD PowerBox , HxWxD: 11U x 600 x 480 mm

Floor, rack-top (ETS/MidD), plinth or wall mounting (key


hole)

8 pcs API 1500A-230 inverters

AC Power output

208 / 220V / 230 / 240 Vrms, 50/60Hz


configurable

12 kVA/10 kW (PF 0.8), 16.8 kVA for 5s

52 A nominal, Overload capability 140 % (5s) 72.8


A

045 C full power, 4560 C reduced power, derating -


2%/C typically.

11-05-27 Delta Energy Systems 11


MidD_APS 1500A-230-8

19 subrack modules combined in MidD


enclosure for industry standard 600mm wide
frame. Optional door assembly.

LED-Indications:

Input ON, Output ON, Overload / Fault

Output loading, 4 levels: >5%, >30%,


>50%, >80%

Insulating cover in front of PDU for protection

IP20 protection class

Safety: EN 60950

EMC Inverters: EN 55022B, EN61000-6-3,


EN61000-6-2, ETS 300 132-2, BTNR 2511
(NEBS)

11-05-27 Delta Energy Systems 12


MidD_APS 1500A-230-8

DC power input

8 pcs MCB C40A and 35 sqmm terminal blocks

One common feed to common rails

One feed for dual shelf to dual connector

Individual feeds to MSBs and terminals

Remote Monitoring with RS-232 bus (D-sub at front


panel)

11-05-27 Delta Energy Systems 13


MidD_APS 1500A-230-8
Alarm connections

Fuse alarm (aux)

Inverter alarm: Fault in system summary alarm


(module failure, DC input low, etc)

AC PDU options

15 x MCB 240A, GE G60 B or C curve

15 x DPN MCB 240A, GE G60 B or C curve

Auxiliary alarm switches with 10 x MCB/DPN

Neutral and PE rails with MCB. PE rail with DPN.

Cover plates

11-05-27 Delta Energy Systems 14


MidD_APS 1500A-230-8

11-05-27 Delta Energy Systems 15


11-05-27 Delta Energy Systems 16
MidD_APS 1500A-230-8

11-05-27 Delta Energy Systems 17


Inverter API 1500A-230

P/N: TPS1030001A
OPEX & energy saving - high efficiency 90.3 %
High start up current capability start up heavy AC load
Modular 1.5kVA module, scalable up to 30 kVA
Supply all kind of equipment wide power factor supply range
Supply all kind of equipment outstanding dynamic performance
Pure sine wave output, Very low output voltage distortion
Easy installation - Hot pluggable, connectors at the rear
Low audible noise - Fan cooled with speed control
Operating temperature range up to 60 C
IEC / EN 60950
Static switch modules available for complete power solution

11-05-27 Delta Energy Systems 18


DC input specification

48V or 60V nominal battery systems


Input voltage range 40 72 Vdc
Input current 35A max @ 48VDC continuous
50A max (5s), in case of maximum overload on the output
Inrush current 20A max
Input protection Internal fuse

11-05-27 Delta Energy Systems


AC output specification

Nominal system voltage 208 / 220V / 230 / 240 Vrms configurable


130 Vrms factory setting
Nominal system frequency 50 / 60 Hz configurable
50 Hz factory setting
Nominal output power 1500 VA (PF 0.8) / 1200 W
Overload capability 140 % (5s)
Output distortion < 2 % THD resistive load
Crest factor 2.8
Static voltage regulation +/- 3%
Output protection internal fuse
Short circuit protection 12 Arms for 4s then shut down
Startup behavior configurable

11-05-27 Delta Energy Systems


Overload characteristic

11-05-27 Delta Energy Systems


Static Switch SSW 7500A-230
TPS1030002A
7.5 kVA single phase static switch
Remote Monitoring with RS-232 bus (D-sub)
Configurable mains voltages - 208 / 220V / 230 / 240 Vrms
Configurable mains frequencies 50 / 60 Hz
Energy saving OFFLINE mode - minimise total losses on site
For critical mains conditions ONLINE mode
High availability of AC supply Quick detection of AC faults
High availability of AC supply Fast switchover by synchronisation of the
inverter group to the public AC mains
Easy installation - Hot pluggable, connectors at the rear
Low audible noise - Fan cooled with speed control
Operating temperature range up to 60 C
IEC / EN 60950
11-05-27 Delta Energy Systems 22
Static Switch basics

Operating Modes
z OFF Line Mode: Public AC network supplies load
z ON Line Mode: Inverter AC network supplies load
z Operating mode is configurable

Public AC
network

inverter group static switch OFF LINE MODE

DC

Loads
ON LINE MODE
11-05-27 Delta Energy Systems
AC utility input specification

z Nominal utility voltage 208 / 220V / 230 / 240 Vrms


configurable 230Vrms factory setting
z Nominal utility frequency 50 / 60 Hz
configurable - 50 Hz factory setting
z Inbuilt AC overvoltage protection and loss of Neutral protection.

11-05-27 Delta Energy Systems


AC output specification

z Operating modes OFFLINE / ONLINE mode configurable


z Stabilized AC output voltage window configurable
z Stabilized AC output frequency window configurable
z Detection of mains failure 2ms factory setting configurable

11-05-27 Delta Energy Systems

Das könnte Ihnen auch gefallen