Standard Technical Features of BTG System for Supercritical 660/800 MW Thermal Units

5.4.12 Furnace exit gas temperature (FEGT)

It shall be demonstrated that maximum furnace exit gas temperature (FEGT)


shall be minimum 60 deg C below the minimum initial deformation
temperature (IDT) of ash. A comprehensive thermal performance test (TPT)
shall be conducted for this purpose on one unit. FEGT shall be demonstrated
through such TPT by indirect measurement.

5.4.13 Air heater air in leakage

It shall be demonstrated that the air-heater air-in-leakage after 3000 hours of


steam generator operation does not exceed the specified/ quoted values.

5.4.14 Equipment cooling water system

i) Inlet and outlet temperatures on the primary and secondary side of the
plate type heat exchangers as per design shall be demonstrated at site.
ii) Pressure drop across plate type heat exchanger on primary and secondary
side cooling water circuits shall be demonstrated at site.
iii) Satisfactory operation of primary side DMCCW pumps and secondary
side cooling water pumps (as applicable) without undue noise and
vibration while operating in isolation or in parallel with other pumps
shall be demonstrated at site.

5.4.15 Generator excitation system

The performance of generator excitation system as specified shall be


demonstrated.

5.4.16 Steam condensing plant

i) The value of design condenser pressure, to be measured at 300 mm


above the top row of condenser tubes, shall be demonstrated under VWO
condition, 1% make-up, design CW inlet temp. and CW flow. The
condenser vacuum shall be measured with a vacuum grid utilizing
ASME basket tips.

ii) Temperature of condensate, at outlet of condenser, shall be demonstrated


to be near to saturation temperature corresponding to the condenser
pressure at all loads.

iii) Oxygen content in condensate at hotwell outlet shall not exceed 0.015
cc/litre over 50-100% load range and shall be determined according to
calorimetric Indigo-Carmine method.

iv) Air leakage in the condenser under full load condition shall not exceed
more than 50% of design value taken for sizing the condenser air
evacuation system.