Digital Energy

Multilin

L90 Line Differential Relay

Agenda

1
AGENDA
Introduction

Product overview

Installation

Percent Current Differential

Lab: setting up 87L

Grouped elements

Control elements

Monitoring & Metering

Introduction

2
Introduction

Transmission Line Protection Considerations


1) Reliability: has two aspects:
Dependability: the degree of certainty that the relay will operate
correctly.
Security: the relay will not operate incorrectly
2) Speed: Very high power during fault conditions: delays translate into
increased damage: faster protection tends to compromise relay system
security and selectivity.
3) Sensitivity: The minimum operating quantities allows the relay to detect
an abnormal condition. High-impedance ground faults,voltage unbalance
and high source- to- line impedance ratio affect the sensitivity
4) Selectivity: or coordination: ability of the relay system to minimize
outages as a result of a fault by operating as fast as possible within their
primary zone.
5) Simplicity and ergonomics: simple to apply and to obtain maximum
protection for the minimum cost in one box
Terms: Coordination, Unit Protection/None Unit Protection, Primary/Back up

Introduction

Transmission Line Protection Considerations


High voltage transmission lines have extremely high level of fault current and
low impedance characteristics. Over current protection can not be as fast as its
needed.
Solutions:
Current Differential:
Unit Protection
Measure the current phasors at both ends of the line. If you have a line fault
there will be a difference in the current magnitude at each end and/or a change
in current phase angle with respect to applied voltage.
Distance or (Impedance):
None Unit Protection
Impedance known as Distance: The distance relay operates by using both
voltage and current to determine if a fault is in a relays zone of protection. At
time of fault Current increases and voltage decreases which translates into a
change in impedance.

3
Introduction

Current differential highlights

Communication link

1. 2 relays are required


2. Digital communication channel 64 kbps is
required.

Product overview

4
L90 Current Differential Relay:
Features
Protection:
Segregated Line current differential (87L)
87L Trip logic
Phase/Neutral/Ground TOCs
Phase/Neutral/Ground IOCs
Negative sequence TOC
Negative sequence IOC
Phase directional OCs
Neutral and negative sequence directional OC
Phase under- and overvoltage
3-zone distance back-up with power swing detect,
load encroachment, POTT and line pickup

L90 Current Differential Relay:


Features
Control:
Breaker Failure (phase/neutral amps)
Synchrocheck & Autoreclosure
Direct messaging (8 extra inter-relay DTT bits exchanged)
UR Metering:
Fault Locator
Oscillography
Event Recorder
Data Logger
Phasors / true RMS / active, reactive and apparent power, power
factor
87L Metering:
actual differential current
local and remote phasors
communication channel status

5
L90 Current Differential Relay:
Features

52

79 3V_0
M onitoring CLOSE TRIP

50DD 50P(2) 50_2(2) 51P(2) 51_2(2) 50BF(2) 87L 21P 67P(2) 68 78 50N(2) 51N(2) 67N/ G 21G

Data From/ To Remote End Transducer


(via Dedicated Communications) FlexElement
TM
M etering Inputs 59P

27P(2)

50G(2) 51G(2)
59N

59X 27X

25(2)

L90 Line Differential Relay


831706AS.CDR

L90 Current Differential Relay:


Line Current Differential
Improved operation of the line current differential (87L)
element:
Dynamic Restraint increasing security without jeopardizing
sensitivity
Line Charging Current Compensation to increase sensitivity
Self-synchronization
Channel Asymmetry Compensation to compensate for
asymmetrical channel delay on multiplexed channels
CT Saturation Detection
Zero sequence current removal for applications on lines with
a tapped transformers with a primary wye neutral grounded.
Relay ID for secure applications on higher order
communication systems.

6
L90 Current Differential Relay:
Line Current Differential

L90 can be applied


on both 2-terminal
and 3-terminal
apllications:
hardware and
firmware are the
same.

L90 Current Differential Relay:


Installation

Direct point-to-point Fiber


(up to 100Km)

(64Kbps)

- G.703 - G.703
- RS422 OR - RS422
Via SONET system telecom multiplexer
(GEs FSC)

(155Mbps)
FSC FSC
(SONET) (SONET)

7
Installation

L90 Current Differential Relay:


Installation
CHANNEL COMMUNICATION OPTIONS

8
L90 Current Differential Relay:
Installation
DIRECT FIBER

FIBER - LED & ELED LASER FIBER MODULES


TRANSMITTERS WARNING: When using a 1300/1550 nm
The above figure shows the 2-Terminal LASER Interface, attenuators may be
configuration for the 7A, 7B, & 7C fiber- necessary to ensure that you do not exceed
only modules. Maximum Optical Input Power (-14 dBm) to
the receiver.

L90 Current Differential Relay:


Installation
DIRECT FIBER

9
L90 Current Differential Relay:
Installation
DIRECT FIBER OPTICAL POWER BUDGET

L90 Current Differential Relay:


Installation
G.703 CO-DIRECTIONAL INTERFACE

Typical pin interconnection between two G.703 interfaces back-to-


back.

10
L90 Current Differential Relay:
Installation
G.703 INTERFACE

G.703 module dip switches..

L90 Current Differential Relay:


Installation
G.703 INTERFACE

Connection to higher order system

G.703 Timing Selection

11
L90 Current Differential Relay:
Installation
G.703 INTERFACE

Minimum Remote Loopback Test mode data processing

L90 Current Differential Relay:


Installation
G.703 INTERFACE

Dual Loopback Test mode data processing

12
L90 Current Differential Relay:
Installation
G.703 INTERFACE

Back to Back: Correct

Internal Timing mode Loop Timing mode


(S1=Off, S5=On, S6=Off) (S1=Off, S5=Off, S6=Off)

Back to Back : Will work but not ideal.

Internal Timing mode Loop Timing mode (factory


(S1=Off, S5=On, S6=Off) default for connections to
higher order system
(S1=On, S5=Off, S6=Off)

L90 Current Differential Relay:


Installation
G.703 INTERFACE

Point to Point using Modems (for example RAD modem):


Rad Modem Rad Modem

Octet Timing Loop Timing Loop Timing Octet Timing


Disabled mode mode Disabled
Loop Timing Internal
mode
Only one clock per system
generated by right L90.

13
L90 Current Differential Relay:
Installation
G.703 INTERFACE

Connection via multiplexers (higher order system):

Octet Timing Octet Timing


enabled
Multiplexer Multiplexer enabled
Loop Timing Loop Timing
mode mode

The multiplexer provides the clock for all relays: again, one clock per
system:

L90 Current Differential Relay:


Installation
RS.422 INTERFACE

Typical pin interconnection between two RS422 interfaces

14
L90 Current Differential Relay:
Installation
RS.422 INTERFACE

RS422 - Two Channel Applications via


Multiplexers

TIMING CONFIGURATION FOR RS422 2 CHANNEL - 3 TERMINAL APPLICATION


Data Module 1 provides timing to the L90 RS422 interface via the ST(A) and ST(B) outputs. Data
Module 1 also provides timing to Data Module 2 TT(A) and TT(B) inputs via the ST(A) and AT(B)
outputs.
Note: The Data Module Pin Numbers, in the figure above, have been omitted since they may vary
depending on the manufacturer.

L90 Current Differential Relay:


Installation
RS422 INTERFACE
Clock and Data Transitions

Tx Clock

Tx Data

15
L90 Current Differential Relay:
Installation
MIXED INTERFACES

RS422 & FIBER INTERFACE CONFIGURATION

WARNING: When using a 1300 nm LASER Interface, attenuators may be


necessary to ensure that you do not exceed Maximum Optical Input Power
(-14 dBm) to the receiver.

L90 Current Differential Relay:


Installation
IEEE fiber C37.94 INTERFACE

The IEEE C37.94 Standard defines a point to point optical link for
synchronous data between a multiplexer and a teleprotection
device.
Designed to interface with IEEE C37.94 compliant digital multiplexer
and/or an IEEE C37.94 compliant interface converter for use with
L90.

Connected directly to
MUX

Connected to MUX
via converter

16
L90 Current Differential Relay:
Installation
IEEE fiber C37.94 INTERFACE

For the Internal Timing Mode, the system clock is generated


internally; therefore, the timing switch selection should be Internal
Timing for Relay 1 and Loop Timed for Relay 2. There must be only
one timing source configured.
For the Looped Timing Mode, the system clock is derived from the
received line signal; therefore, the timing selection should be in
Loop Timing Mode for connections to higher order systems.

L90 Current Differential Relay:


Installation
COMMS CHANNEL TESTING
Local Loopback Test Mode Transmitted
data blocked
G7X

Local relay
G7R

17
L90 Current Differential Relay:
Installation
COMMS CHANNEL TESTING
Received data
Remote Loopback Test echoed back.

G7R G7X
Remote
Local relay
G7X G7R
relay

L90 Current Differential Relay:


Installation
COMMS CHANNEL ON-LINE DIAGNOSTICS

Current comms status is available History of comms disturbances is logged


in Actual Values. into event recorder.

18
L90 Current Differential Relay:
Installation
COMMS CHANNEL ON-LINE DIAGNOSTICS

MAJOR COMMS ALARMS MINOR COMMS ALARMS


1. 87L DIFF CH1/2 FAIL 1. 87L DIFF CH1/2 CRCFAIL
2. 87L DIFF PFLL FAIL 2. 87L DIFF CH1/2 LOSTPKT
3. 87L DIFF CH1/2 ID FAIL 3. 87L DIFF TIME CHANGED
4. 87L DIFF ASYM DETECTED
5. 87L DIFF 1/2 ASYM MAX
87L DIFF BLOCKED 6. 87L DIFF GPS1/2 FAIL

L90 Current Differential Relay:


Installation
COMMS CHANNEL ON-LINE DIAGNOSTICS
CHANNEL ID FAIL
1. Each packet carries relay
ID number per channel
2. Each received packet is
compared with ID
programmed L90 Power
System menu.
3. 0 means NO Channel ID
check is required (for
direct fibers).

Protection against:
1. Inadvertent loopback
2. Inadvertent connection to a
wrong L90 relay.

19
Percent Current Differential

L90 Current Differential Function


ACTUAL VALUES SETTING
VAG To Remote Relays
L90 POWER SYSTEM channel 1 & 2
VBG XC0 & XC1:
VCG
Compute Charging
SETTING Current
DATA FROM RUN
LOCAL END FLEXLOGIC OPERANDS
CURRENT DIFF OR
SOURCE: Charging Current RUN IA
Compute 87L DIFF OP
IA IA 2 @Timestamp Process IA Phasors
& Variance IB
IB IB @Timestamp
2
Phasors IB
87L DIFF OP A
Computations IC (Local)
IC IC @Timestamp
2
IC

87L DIFF OP B
SETTING
L90 POWER SYSTEM 87L DIFF OP C
NUM. OF TERMINALS: AND SETTINGS
3 = 1 87L DIFF RECVD DTT A
CURRENT DIFF
OR PICKUP:
SETTING
AND CURRENT DIFF 87L DIFF RECVD DTT B
L90 POWER SYSTEM OR RESTRAINT 1:
NUM. OF CHANNELS:
SETTING CURRENT DIFF 87L DIFF RECVD DTT C
2 = 1 AND RESTRAINT 2:
CURRENT DIFF
TAP 1: CURRENT DIFF 87L DIFF PFLL FAIL
DATA FROM
REMOTE 1 BREAK PT:
OR RUN
Channel 1 OK=1 AND 87L DIFF CH1 FAIL
2
Channel 1 ID Fail IA Operate
Compute IA >1
IA 2 @Timestamp Phasors IA Restraint
2 87L DIFF CH2 FAIL
IB 2 @Timestamp & Variance IB
IC2 @Timestamp (Remote 1)
IC 87L DIFF CH1 LOSTPKT
2
DTT PHASE A AND IB Operate
>1
DTT PHASE B AND IB Restraint
2 87L DIFF CH2 LOSTPKT
SETTING
DTT PHASE C AND
CURRENT DIFF
AND 87L DIFF CH1 CRCFAIL
TAP 2: 2
DATA FROM IC Operate
REMOTE 2 OR >1
RUN 2 87L DIFF CH2 CRCFAIL
IC Restraint
Channel 2 OK=1
Channel 2 ID Fail Compute IA
AND
87L DIFF CH1 ID FAIL
IA 2 @Timestamp Phasors RUN
& Variance IB
IB 2 @Timestamp (Remote 2) 87L DIFF CH2 ID FAIL
IC @Timestamp
2 IC
AND
DTT PHASE A OR
AND
87L BLOCKED
DTT PHASE B AND
OR
DTT PHASE C AND AND
87L DIFF KEY DTT
OR
AND

AND
OR

OR

FLEXLOGIC OPERAND AND


STUB BUS OP
To Remote Relays
channel 1 & 2
AND
OR
SETTING

CURRENT DIFF
DTT: AND OR
Enabled=1

SETTING
AND
CURRENT DIFF OR
KEY DTT:
827056A9.CDR
Off

20
L90 Current Differential Relay:
Operate Current Traditional Restraint Method

K2

K1

Restraint Current

Traditional method is STATIC


Compromise between Sensitivity and Security

L90 Current Differential Relay:


Dynamic Restraint

Dynamic restraint uses an estimate of a


measurement error to dynamically increase the
restraint
On-line estimation of an error is possible owing to
digital measuring techniques
In digital relaying to measure means to calculate or
to estimate a given signal feature such as magnitude
from the raw samples of the signal waveform

21
L90 Current Differential Relay:
Digital Phasor Measurement

The L90 measures the current phasors (magnitude


and phase angle) as follows:

1. digital pre-filtering is applied to remove the


decaying dc component and a great deal of high
frequency distortions
2. the line charging current is estimated and used
to compensate the differential signal
3. full-cycle Fourier algorithm is used to estimate
the magnitude and phase angle of the
fundamental frequency (50 or 60Hz) signal

L90 Current Differential Relay:


Digital Phasor Measurement
Sliding Data Window
32 samples for 32 samples for
Transmission Transmission of
of one phaselet next phaselet

windo present
w time

time time

waveform magnitude

22
L90 Current Differential Relay:
Digital Phasor Measurement
Sliding Data Window
32 samples for 32 samples for
Transmission Transmission of
of one phaselet next phaselet

windo present
w time

time time

waveform magnitude

L90 Current Differential Relay:


Phasor Goodness of Fit

A sum of squared differences between the actual


waveform and an ideal sinusoid over last window is a
measure of a goodness of fit (a measurement error)

window

time

23
L90 Current Differential Relay:
Phasor Goodness of Fit

The goodness of fit is an accuracy index for the digital


measurement
The goodness of fit reflects inaccuracy due to:
transients
CT saturation
inrush currents and other signal distortions
electrical noise
The goodness of fit is used by the L90 to alter the
traditional restraint signal (dynamic restraint)

L90 Current Differential Relay:


Operate-Restraint Regions
ILOC local current
IREM remote end current
Imaginary (ILOC/IREM)

OPERATE

OPERATE

RESTRAINT Real (ILOC/IREM)

OPERATE

OPERATE

24
L90 Current Differential Relay:
Dynamic Restraint
Dynamic restraint signal =
Traditional restraint signal + Error factor
Imaginary (ILOC/IREM)

OPERATE

Error factor is high

Real (ILOC/IREM)
REST.

Error factor is low

L90 Current Differential Relay:


Charge Current Compensation

The L90 calculates the instantaneous values of the


line charging current using the instantaneous values
of the terminal voltage and shunt parameters of the
line
The calculated charging current is subtracted from
the actually measured terminal current
The compensation reduces the spurious differential
current and allows for more sensitive settings

25
L90 Current Differential Relay:
Charge Current Compensation

The compensating algorithm:


is accurate over wide range of frequencies
works with shunt reactors installed on the line
works in steady state and during transients
works with both wye- and delta-connected VTs
(for delta VTs the accuracy of compensation is
limited)

L90 Current Differential Relay:


Effect of Compensation
Local and remote voltages
Voltage, V
200

150

100

50
Time of
0
energization
-50

-100
Time of out of zone fault

-150

-200
0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18
time, sec

26
L90 Current Differential Relay:
Effect of Compensation
Traditional and compensated differential
currents (waveforms)
Current, A
0.3
Actual none compensated
current
0.25

0.2
Theoretical compensated
current
0.15

0.1

0.05
Time of
0
energization
-0.05

-0.1

-0.15

-0.2
0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18

time, sec

L90 Current Differential Relay:


Effect of Compensation

Traditional and compensated differential


currents (magnitudes)
Current, A
0.08
Actual none compensated
0.07 current after filtering and
Fourier algorithm
0.06

0.05

0.04
Actual compensated current
0.03 after filtering and fourier
algorithm
0.02

0.01

0
0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18

time, sec

27
L90 Current Differential Relay:
Self-Synchronization

RELAY 1 RELAY 2

Forward t0
travel tf
time t1 Relay
ping-pong
turn-around
t2 time
Return tr
travel t3
time

t3 t0 t2 t1
t f tr
2

L90 Current Differential Relay:


Ping-Pong (example)
Relay 1 Relay 2
Send start bit 0 Initial clocks mismatch=1.4ms or 30
Store T1i-3=0
Communication path Send start bit
0 Store T2i-3=0
8.33 ms
Capture T2i-2=2.3
5.1 2.3
Capture T1i-2=5.1
8.33 ms

Send T1i-2=5.1 8.33

8.33 Send T2i-2=2.3

8.33 ms Store T1i-2=5.1


13.43
10.53
Store T2i-2=2.3
8.33 ms

Send T1i-1=16.66 16.66

16.66 Send T2i-1=16.66


8.33 ms
Store T1i-1=8.33
21.76 Capture T2i=18.96
Store T2i-1=16.66 18.96
Capture T1i=21.76
T2i-3=0 a2=5.1-0=5.1
T1i-2=5.1 b2=18.96-16.66=2.3
T1i-3=0 a1=2.3-0=2.3 T1i-1=16.66 2=(5.1-2.3)/2=
T2i-2=2.3 b1=21.76-16.66=5.1 T2i=18.96 = +1.4ms (behind)
T2i-1=16.66 1=(2.3-5.1)/2=
T1i=21.76 = -1.4ms (ahead)
Speed up

Slow down
30
0

t1 t2

28
L90 Current Differential Relay:
Ping-Pong (example continued)
Relay 1 Relay 2
33.32
Store T1i-3=33.32
33.32
Store T2i-3=33.32
8.52 ms
Capture T2i-2=35.62
38.28
35.62
Capture T1i-2=38.28
8.14 ms

41.55
Send T1i-2=38.28 41.55
Send T2i-2=35.62

8.52 ms
Store T1i-2=38.28
Store T2i-2=35.62
8.14 ms

Send T1i-1=50.00 50.00 49.93


Send T2i-1=49.93

8.52 ms 53.16
54.03
Store T1i-1=50.00
Store T2i-1=49.93 Capture T2i=53.16
Capture T1i=54.03
8.14 ms

T2i-3=33.32 a2=38.28-33.32=4.96
T1i-3=33.32 a1=35.62-33.32=2.3 T1i-2=38.28 b2=53.16-50.00=3.16
T2i-2=35.62 b1=54.03-49.93=4.1 T1i-1=50.00 2=(4.96-3.16)/2=
T2i-1=49.93 1=(2.3-4.1)/2= T2i=53.16 = +0.9ms (behind)
T1i=54.03 = -0.9ms (ahead)

Speed up
Slow down
0
19.5
30
t1 t2

L90 Current Differential Relay:


Digital Flywheel


Virtual Shaft

clock 1 clock 2

If communications is lost, sample clocks continue


to free wheel
Long term accuracy is only a function of the base
crystal stability

29
L90 Current Differential Relay:
Peer-to-Peer Operation

Each relay has sufficient information to make an independent


decision
Communication redundancy
L90-1 L90-2

L90-3

L90 Current Differential Relay:


Master-Slave Operation

At least one relay has sufficient information to make an


independent decision
The deciding relay(s) sends a transfer-trip command to all other
relays

L90-1 L90-2

L90-3 Data (currents)


Transfer Trip

30
L90 Current Differential Relay:
Zero-sequence Current Removal
The L90 protection system could be applied to lines with tapped
transformer(s) even if the latter has its windings connected in a grounded
wye on the line side and the transformer(s) currents are not measured by
the L90 protection system..

L90-1 L90-2
I_0

L90 Current Differential Relay:


CT Saturation Detection
Current differential protection is inherently dependent on adequate CT
performance at all terminals of the protected line especially during
external faults. CT saturation, particularly if happens at one terminal of
the line only, introduces a spurious differential current that may cause the
differential protection to misoperate.

31
L90 Current Differential Relay:
Breaker-and-a-half
The L90 has
advantages on
systems with breaker-
and-a-half or ring bus
configurations. In these
applications, each of
the two three-phase
sets of individual
phase currents (one
associated with each
breaker) can be used
as an input to a
breaker failure
element.

L90 Current Differential Relay:


Breaker-and-a-half

Benefits:
For restraint forming, maximum of 2 (or more currents is
used). Conventional sum might not provide enough
restraint.

CTs matching is done


internally, different CT
ratios possible
Current are available
individually for BF,
metering etc

32
L90 Current Differential Relay:
Breaker-and-a-half

Distributed bus
differential
Up to 4 CTs can be
processed
individually and
summed up with
L90. For application
where buses are
located remotely,
this is beneficial as
CT leads dont allow
applying bus
differential.

L90 Current Differential Relay:


Channel asymmetry

ADM-2 ADM-3

RELAY 1 RELAY 2
Rx Tx
ADM-1 ADM-4
Tx Rx

On SONET/SDH system, transmit and receive channel


delays can be different. Normally, Tx_delay=Rx_delay.
If one path is broken, it can be re-routed to another
physical fiber, resulting in Tx_delayRx_delay.

33
L90 Current Differential Relay:
Channel asymmetry
Difference in transmit-receive paths is causing
incorrect synchronization between relays as ping-
pong is operating based on assumption that transmit-
receive delays are the equal.
That results in apparent differential current,
proportional to the value of the channel asymmetry.
If currents and channel asymmetry are high enough,
relay misoperates.
IDIFF
IA IB

Half of the channel


asymmetry in
electrical degrees

L90 Current Differential Relay:


Channel asymmetry
L90 can cope with channel asymmetry as high as up
to 10 ms using GPS signal.
No additional input is required-GPS clock is
connected to the regular IRIG-B UR input, providing
accurate clock to both events time-stamping and
channel asymmetry compensation algorithm.

ADM-2 ADM-3

GPS clock GPS clock

Rx Tx
ADM-1 ADM-4
Tx Rx
RELAY 1 RELAY 2

34
L90 Current Differential Relay:
Channel asymmetry
FLEXLOGIC OPERAND
IRIG-B FAILURE
To Remote Relays
SETTINGS Channels 1 and 2
L90 POWER SYSTEM: 87L GPS Status Fail

OR
BLOCK GPS TIME REF:
Off = 0
REAL TIME CLOCK:
IRIG-B SIGNAL TYPE
None = 0
L90 POWER SYSTEM:
CHNL ASYM COMP: GPS COMPENSATION

Off = 0 RUN

DATA FROM REM OTE Use Calculated

OR
TERM INAL 1 Correction, Establish and
87L Ch 1 Status (OK=1) Update Memory

AND

OR
87L GPS 1 Status (OK=1) Use Memorized
Correction
FLEXLOGIC OPERAND
DATA FROM REM OTE
87L DIFF GPS FAIL

OR
TERM INAL 21
87L Ch 2 Status (OK=1) SETTINGS
AND
87L GPS 2 Status (OK=1) L90 POWER SYSTEM:
MAX CHNL ASYMMETRY:
L90 POWER SYSTEM:
FLEXLOGIC OPERAND ROUND TRIP TIME
87L DIFF GPS 1 FAIL CHANGE:

AND
RUN FLEXLOGIC OPERAND
87L DIFF 1 MAX ASYM
ACTUAL VALUES | Ch1 Assymetry | > MAX
Ch1 Assymtery
RUN
FLEXLOGIC OPERAND
ACTUAL VALUES |Ch1 T-Time New - 87L DIFF 1 TIME CHNG
Ch1 Round Trip Time Ch1 T-TIME Old| > CHANGE

GPS function FLEXLOGIC OPERAND


87L DIFF GPS 2 FAIL

AND
RUN
FLEXLOGIC OPERAND
ACTUAL VALUES | Ch2 Assymetry | > MAX 87L DIFF 2 MAX ASYM
Ch2 Assymtery
RUN
FLEXLOGIC OPERAND
ACTUAL VALUES |Ch2 T-Time New -
87L DIFF 2 TIME CHNG
Ch2 Round Trip Time Ch2 T-TIME Old| > CHANGE

L90 Current Differential Relay:


Channel asymmetry
Important consideration is fallback mode if GPS signal is
lost: for example, relay can be programmed to continue
to provide sensitive differential function using memorized
value of last measured channel asymmetry until step
change in the communications path is detected.

35
L90 Current Differential Relay:
Channel asymmetry

Asymmetry-disabled
(about 3 ms of
asymmetry present)

Diff. Current
high

Asymmetry-enabled
(about 3 ms of
asymmetry present)
Diff. Current
low

L90 Current Differential Relay:


Channel asymmetry

Its beneficial to monitor


differential current to
raise an alarm if it
becomes relatively high.
This can happen due to
asymmetry is present,
problems in CT
secondary. Flexelements
are used for that.

36
L90 Current Differential Relay:
Synchronization

f System f
RELAY 1 + Frequency + RELAY 2

_ _
Compute Compute
Frequency Frequency
f f1 Deviation f1 f2 Deviation f f2

+ +
+ Phase Frequency Phase Frequency +
Loop Filter Loop Filter
+ +

1 2

(2 1)/2 Ping-Pong time stamps Ping-Pong (2 1)/2


Phase Phase
Deviation Deviation

(2 1)/2 GPS time stamps GPS (2 1)/2


Phase Phase
Deviation Deviation

GPS GPS
Clock Clock

Overall Relays synchronization


diagram

L90 Current Differential Relay:


Synchronization

37
L90 Current Differential Relay:
Frequency Tracking
1. It is important for current differential to track the
frequency to fit exactly 64 samples within one power
cycle and to provide synchronized sampling at each
L90 relay.
2. L90 starts tracking the frequency if current at any
terminal is above 0.125 pu
3. L90 tracks the frequency from positive- sequence
current from all terminals.
4. If positive-sequence current is below 0.125 pu, all
relays track to nominal frequency, 50 Hz or 60 Hz.
5. Tracking frequency is displayed in Actual
Values\Metering menu.

L90 Current Differential Relay:


Benefits

Increased Sensitivity without sacrificing Security:


Fast operation (11.5 cycles)
Lower restraint settings / higher sensitivity
Charging current compensation
Unique precise synchronization with frequency tracking
Channel Asymmetry Compensation
CT saturation detection
Dynamic restraint ensures security during noise, harmonics,
CT saturation or transient conditions
Reduced CT requirements
Direct messaging
Increased redundancy due to master-master configuration
Reliable CRC-32 communication packet protection against
noise
Breaker-and-a half applications

38
Lab: setting up 87L

L90 Current Differential Relay:


Lab 1: Setting up 87L

Test Set 1 Test Set 2

Direct point-to-point Fiber


Rx Tx
(64Kbps)
Tx Rx

39
L90 Current Differential Relay:
Lab 1: Setting up 87L

L90 system is
chosen

Charging current
enabled/disabled

Channel ID
enabled/disabled

Channel ID
enabled/disabled

L90 Power System menu.

L90 Current Differential Relay:


Lab 1: Setting up 87L

87L enabled

Source chosen

Pickup

CT Tap

87L Current Differential menu.

40
L90 Current Differential Relay:
Lab 1: Setting up 87L

Slope 1

Slope 2

DTT

External DTT

87L Current Differential menu.

L90 Current Differential Relay:


Lab 1: Setting up 87L

1000/1 2000/5

Rx Tx
(64Kbps)
Tx Rx

L90 can accommodate CT ratios mismatch


up to 5 times even if CTs secondary
nominal current is different.

41
L90 Current Differential Relay:
Lab 1: Setting up 87L

Restraint 2

Current Differential major


settings

Restraint 1

Pickup

Breakpoint
(200% of I nominal)

L90 Current Differential Relay:


Lab 1: Setting up 50DD

This portion of logic will not


reset for a continuous
disturbance.

Disturbance Detector-logic
diagram

42
L90 Current Differential Relay:
Lab 1: Setting up 50DD

Disturbance Detector-elements menu

L90 Current Differential Relay:


Lab 1 Comms Channel Check

Channel Status menu-


Actual
Values\Statis\Channel Tests

43
L90 Current Differential Relay:
Lab 1: Faults Simulation
Test Set 87L should
operate at the
current

Rx Direct point-to-point Fiber Tx


(64Kbps)
Tx Rx

Test Set 87L should


NOT operate

Rx Direct point-to-point Fiber Tx


(64Kbps)
Tx Rx

L90 Current Differential Relay:


Lab 1: 87L Characteristics Check
Test Set 1 Test Set 2

Direct point-to-point Fiber


Rx Tx
(64Kbps)
Tx Rx

Operate /
Restraint
Characteristics

44
L90 Current Differential Relay:
Lab 1: 87L Characteristics Check

User 87L settings

Operate current
Restraint current

Relays response

Injected currents

L90 Current Differential Relay:


SETTING

87L TRIP FUNCTION:


87L Trip element
Disable=0
Enable=1

SETTING SETTING

87L TRIP SOURCE: 87L TRIP SEAL-IN PICKUP:

IA IA > PICKUP
IB IB > PICKUP
IC IC > PICKUP

SETTING

87L TRIP SEAL-IN:

Enable=1
AND
FLEXLOGIC OPERAND
FLEXLOGIC OPERAND
OR 87L TRIP OP A
87L DIFF OP A AND

87L and DTT FLEXLOGIC OPERAND


OR

are OR-ed 87L RECVD DTT A

AND
FLEXLOGIC OPERAND
FLEXLOGIC OPERAND
OR 87L TRIP OP B
87L DIFF OP B AND

OR
FLEXLOGIC OPERAND
87L RECVD DTT B

AND
FLEXLOGIC OPERAND
FLEXLOGIC OPERAND
Mode is hosen: 87L DIFF OP C AND
OR 87L TRIP OP C

OR FLEXLOGIC OPERAND
FLEXLOGIC OPERAND
OR 87L TRIP OP
1P or 3P 87L RECVD DTT C
OR
SETTING

87L TRIP M ODE:

1-Pole=0
3-Pole=1
AND
SETTING
AND
87L TRIP SUPV:

50DD SV 0 OR
AND OR
50

Supervising AND

element 50DD SETTING

87L TRIP FORCE 3- :


OR
OR

87L Trip Logic


Off=0 AND
OR
FLEXLOGIC OPERAND
OPEN POLE OP

45
L90 Current Differential Relay:
SETTING

87L TRIP FUNCTION:


87L Trip element
Disable=0
Enable=1
Seal-in outputs if
SETTING SETTING

87L TRIP SOURCE:

IA
87L TRIP SEAL-IN PICKUP:

IA > PICKUP
desirable Outputs per
IB
IC
IB > PICKUP
IC > PICKUP
phase or 3-phase
SETTING

87L TRIP SEAL-IN:

Enable=1
AND
FLEXLOGIC OPERAND
FLEXLOGIC OPERAND
OR 87L TRIP OP A
87L DIFF OP A AND

OR
FLEXLOGIC OPERAND
87L RECVD DTT A

AND
FLEXLOGIC OPERAND
FLEXLOGIC OPERAND
OR 87L TRIP OP B
87L DIFF OP B AND

OR
FLEXLOGIC OPERAND
87L RECVD DTT B

AND
FLEXLOGIC OPERAND
FLEXLOGIC OPERAND
OR 87L TRIP OP C
87L DIFF OP C AND

OR FLEXLOGIC OPERAND
FLEXLOGIC OPERAND
OR 87L TRIP OP
87L RECVD DTT C
OR
SETTING

87L TRIP M ODE:


Logic to detect
1-Pole=0
3-Pole=1 multi-phase
SETTING
AND
evolving and
AND
Open Pole 87L TRIP SUPV: sequential faults
forces 3P trip 50DD SV AND OR
0
50
OR

if another
fault occurs AND

during open
SETTING

87L TRIP FORCE 3- :


OR
OR

87L Trip Logic


pole Off=0 AND

conditions FLEXLOGIC OPERAND


OPEN POLE OP
OR

Grouped elements

46
L90 Current Differential Relay:
Grouped elements

L90 Current Differential Relay:


Grouped: Stub bus

Line disconnect
switch 52b contact

IOC trigger

47
L90 Current Differential Relay:
Grouped: Stub bus

Stub Bus Line


zone

Breaker Breaker

+ IOC

L90 Current Differential Relay:


Grouped: Distance

L90 phase and ground distance is the same as D60 elements.

48
L90 Current Differential Relay:
Grouped: Distance

L90 backup distance is complimented by line pickup, power swing


detection, POTT and load encroachment.

L90 Current Differential Relay:


Grouped: Breaker Failure

49
L90 Current Differential Relay:
Grouped: Breaker Failure

3- Pole Breaker Failure

L90 Current Differential Relay:


Grouped: Breaker Failure

3- Pole Breaker Failure

50
L90 Current Differential Relay:
Grouped: Breaker Failure

3- Pole Breaker Failure

L90 Current Differential Relay:


Grouped: Breaker Failure

3- Pole Breaker Failure

51
L90 Current Differential Relay:
Grouped: Breaker Failure

1- Pole Breaker Failure

L90 Current Differential Relay:


Grouped: Breaker Failure

1- Pole Breaker Failure

52
L90 Current Differential Relay:
Grouped: Open Pole Detector

Control elements

53
L90 Current Differential Relay:
Control Elements

Control elements
available in L90

L90 Current Differential Relay:


Control: Synchrocheck

Synchrocheck
Logic

54
L90 Current Differential Relay:
Control: Synchrocheck

3-phase
line VT

1-phase
bus VT

Time that the two


voltages remain within
the admissible angle
difference

L90 Current Differential Relay:


Control: AutoReclose

AutoReclose sequence

55
L90 Current Differential Relay:
SETTING

AR FUNCTION:
Control: AutoReclose
Enable=1
Disable=0
D60 Relay Only
FLEXLOGIC OPERAND
LINE PICKUP OP
AND FLEXLOGIC OPERANDS
AR ENABLED
SETTING AR DISABLED
OR
AR INITIATE
AR BLOCK:
(To page 2, Reset AR TRANSFER TIM ER)
Off = 0
FLEXLOGIC OPERAND
SETTING AR RIP

AR BKR MAN CLOSE: SETTING AND 0.5 cycle To: AR FORCE 3P TRIP

AR BLK TIME UPON MAN (Evolving fault)


Off = 0 CLS :
OR
BKR MANUAL CLOSE:
0
(From sheet 3)
FLEXLOGIC OPERAND
AND
SETTING AR 1-P RIP
LO
AR 1P INIT: SETTING
SETTING
AR EXTEND DEAD TIME
Off = 0
AR 1-P DEAD TIM E: 1:
OR
FLEXLOGIC OPERAND OR Off = 0
D60 Relay Only From Trip Output

TRIP 1-POLE AND 0


OR
SETTING
SETTING OR
AR DEAD TIME 1
FLEXLOGIC OPERAND
EXTENSION:
AR 3P INIT: AR 3-P/1 RIP
OR AND
Off = 0 0
SETTING
FLEXLOGIC OPERAND OR
AR 3-P DEAD TIM E 1:
TRIP AR INIT 3-POLE
OR
OR AND
SETTING 0

AR 3P TD INIT:

Off = 0

SETTING

BKR ONE POLE OPEN: CLOSE (to page 2)


OR
Off = 0
OR
From sheet 3

BKR ONE POLE OPEN

SETTING

BKR 3 POLE OPEN: FLEXLOGIC OPERAND


Off = 0 AR 3-P/2 RIP
OR

BKR 3 POLE OPEN SETTING


OR
RESET AND AR 3-P DEAD TIME 2:
CLOSE BKR1 OR BKR2
OR 0
FLEXLOGIC OPERAND
OR AND
From Sheet 2

AR SHOT COUNT>0

SETTING FLEXLOGIC OPERAND


BKR FAIL TO RECLS AR INCOM PLETE SEQ
AR PAUSE
(from sheet 2)

Off = 0 827089AD.CDR

SHOT COUNT = MAX AND

SETTING
AND
AR M0DE: FLEXLOGIC OPERAND
AND AR LO
1 Pole SETTING
3 Pole - A AR INCOMPLETE SEQ.
OR
3 Pole -B TIMER: OR
1 & 3 Pole
OR 0

AutoReclose
D60 Relay Only From Phase Selector AND
FLEXLOGIC OPERAND
AND OR
PHASE SELECT MULTI-P
0
SETTING 5ms
AND
OR
AR MULTI-P FAULT:

Off = 0

SETTING
OR
FLEXLOGIC OPERAND
AR FORCE 3P TRIP
RESET (to sheet 2)
logic
AR RESET: Evolving fault
OR AR DISABLED
Off = 0
FLEXLOGIC OPERAND
OR AR ZONE 1 EXTENT

L90 Current Differential Relay:


AND
AND
Control: AutoReclose
OR

OR

AND

AND
LO
To sheet 3 AND
AND

OR LO 2ms
AND
OR
AND

AND

OR

OR AND

S
Latch
OR R

RESET

LO

AND

LO

AND

2ms

BKR CLOSED (from page 3)


OR
827090A9.CDR

AND
AND
OR

AutoReclose
logic

56
L90 Current Differential Relay:
Control: AutoReclose

This piece of the AR is


reading status of
breaker(s) and feeds
main AR logic to
proceed action further
accordingly number of
breakers, mode chosen
and sequence chosen.

AutoReclose
logic

L90 Current Differential Relay:


Control: AutoReclose
AutoReclosure Function Breaker Function
Breakers are set in
System Setup\
Breakers

AR is set per users


requirements (reads
breakers status
automatically) LEDs are needed to
know AR ststus

LEDs

57
L90 Current Differential Relay:
Control: CT Fail Detector

CT Fail Detector is designed to detect


failures in CT secondary circuitry

L90 Current Differential Relay:


Control: VT Fuse Fail

58
L90 Current Differential Relay:
Control: POTT

POTT scheme requires 1-bit


comms channel, for example
PLC.

L90 Current Differential Relay:


Direct Inputs and Outputs
Line 1
B5 C60 3
Ethernet

Ethernet
B1 B3

Line 2
L90 1 L90 2

Substation 1
B2 B4

Substation
L90 1-2 LAN 2

59
L90 Current Differential Relay:
Direct Inputs and Outputs
Default
means state
when
channel is Direct
broken Outputs are
assigned with
Flexlogic
operands

This is active
in 3-terminal
only

L90 Current Differential Relay:


Direct Inputs and Outputs

Channel status
controls either
Direct Input is read
from the received
data or set to
default

60
L90 Current Differential Relay:
Direct Inputs and Outputs
Example

Local Relay Remote Relay

Breaker Fail is
assigned to Direct
Output 1-1

Direct Input 1-1 (BF


at remote S/S) is
assigned to a trip
gate.

Monitoring & Metering

61
L90 Current Differential Relay:
Metering: 87L

L90 Current Differential Relay:


Oscillography: 87L analogs

62
Overall L90 functional diagram

L90 test program is available on GE Multilin web site

63
Thank you.