NOTES:-

1. ALL DIMENSIONS ARE IN MILLI METERS AND LEVELS


# PROVIDE LIGHT WIGHT (FOM WORK) FOR SUNKEN SLABS ARE IN METERS UNLESS OTHERWISE SPECIFIED.

2. ALL DIMENSIONS ARE FROM UNFINISHED

FLOOR LEVEL/ SURFACE.

3. ALL DIMENSIONS SHALL BE CHECKED


1 2 3 4 5 6 7 8 9 10 11 12 13
AND VERIFIED AT SITE.

4. NO DIMENSIONS TO BE SCALED OFF THE DRAWING.


B B B B ONLY WRITTEN DIMENSIONS SHALL BE FOLLOWED.
A A
S2
S2 B S2 B 5. ALL DRAWINGS ARE INTERRELATED AND SHALL
B BE READ IN CONJUNCTION WITH OTHER RELEVANT
B B S3 B B
B
B
S2 6. ANY DISCREPANCY FOUND IN THE DRAWING IS
S2 S2
TO BE IMMEDIATELY CLARIFIED WITH THE ENGINEER
B B B B
C C
OR HIS REPRESENTATIVE AT THE SITE BEFORE

B4 B4 B4 COMMENCEMENT OF RELATED ITEMS OF WORK.


D D

7. CONCRETE FOR STRUCTURAL MEMBERS SHOULD BE

E E
OF GRADE 30 UNLESS OTHERWISE SPECIFIED.
HB1

Y14 @ 10 CC. T&B S5 S5 B5 S4 8. ALL REINFORCEMENTS SHALL BE HIGH YIELD HAVING


#B5 B4
CHARACTERISTIC STRENGTH Fy- 460 N/mm2.

UNLESS OTHERWISE SPECIFIED.


ONLY UP TO G.F. HB3 B5
F F
S1 9. Concrete cover is as follows
B5 B5 B1 S1 B1 S1 B3
Y14 @ 10 CC. T&B

B5
S5 B1 Foundation 50 mm
S1
G G Columns 25 mm
HB3 B5
10. Tie beams and strap beams
B4 SCHEDULE OF BEAMS
S5 B5
HB2

B4
H S5 H
HB1 Y14 @ 10 CC. T&B
TYPE SIZE BOTTOM BARS TOP BARS
SL EXTRA OVER STIRRUPS REMARKS
*B3/B3

UP
STRAIGHT CURTAILED STRAIGHT CONT.SUPPORT
SF 13 12 11 10 9 8 7 6 5 4 3 2 1

B4 S5
SF B1 200X500 2Y14 2Y14 Y8@150 c/c
I SL B3 I
B2 200X500 3Y14 2Y14 2Y14 2Y14 Y8@150 c/c
J B4 HB2 J B3 200X600 3Y16 ------ 4Y16 ------ Y8@150 c/c
B3 S2 B1 S2 B5 B4 200X600 4Y16 2Y16 2Y16 4Y16 Y8@100 c/c
B3 B4 S5 Y14 @ 10 CC. T&B
Y14 @ 10 CC. T&B

K K B5 200X700 4Y18 2Y16 4Y18 4Y16 Y8@100 c/c 2Y16 F.B


B4 HB2 ------ 2Y14 ------ 2Y16 F.B
B 200X500 2Y14 Y8@100 c/c

HB1 600X400 10Y16 ------ 10Y16 ------ Y8 @ 50 c/c 4 LEGGED


Y14 @ 10 CC. T&B B4
B4 B2 B5 B5 HB2 800X400 10Y18 ------ 10Y18 ------ Y10 @ 50 c/c 6 LEGGED
L S4 S5 L
HB3 1000X400 12Y20 ------ 12Y20 ------ Y10 @ 50 c/c 8 LEGGED
Y14 @ 10 CC. T&B

Y14 @ 10 CC. T&B

Y14 @ 10 CC. T&B


Y14 @ 10 CC. T&B

Y14 @ 10 CC. T&B

M M
B5 B5
SCHEDULE OF SLABS

TYPE THICK SHORT BARS LONG BARS REMARKS


S1 14 Y10@150 c/c Y10@150 c/c
S2 16 Y10@150 c/c Y10@150 c/c
1 2 3 4 5 6 7 8 9 10 11 12 13
S3 18 Y10@150 c/c Y10@150 c/c
S4 20 Y10@150 c/c Y10@100 c/c
DIVISION Engineering Consultancy TEL: 968 24533514, FAX No:968 26893133
S5 22 Y12@150 c/c Y10@100 c/c T/B E-Mail: division-om@hotmail.com
web site:www.division-om.com

SF 20 Y16@150 c/c Y16@150 c/c T/B DIVISION BOX No: 26 PC 121 SEEB
SULTANATE OF OMAN

SL 20 Y12@150 c/c Y12@150 c/c T/B

* BEAM @ MID LENDING LVL

#BEAM @CLOSED STIRRUPS