Power Capacitors

Single Phase Power Capacitors

Single - Phase High voltage


Capacitors 50 Hz / 60 Hz
From 2.4 kV To 20.70 kV

Maximum valtage 20.70 kV

Maximum output 750 kVAr

All Polypropylene (APP) film dilectric

Ultra Low Losses

Indoor or Outdoor
application upto 96 kVBIL

Superior electrical performance

Improved tank rupture characteristics.

Shreem - Type-S 13 all film capacitors (fig-1)


features the latest designed, manufactured and Shreem single - phase, all - film capacitors. (fig. 1)
tested to meet or exceed the requirements of
applicable IEC & IS standard.
Their low cost per kVAr makes these capacitors
a simple, economical source of reactive power
on electric power systems for,
Improving power factor
Reducing line losses
Decreasing voltage drop Ratings
Power capacitors can be installed
singly or in factory - assembled Shreem Capacitors are rated in continuous kVAr, voltage and
switched or unswitched banks in
Frequency for operating within the - 20o to + 50 o C ambient
Pole mounting racks temperature range. Designed to produce not less than
Substation blocks
rated kVAr at rated voltage and frequency, they are subjected to
Metal enclosures
all applicable IEC/IS standard dielectric tests. Single - phase 50 -
through 750 kVAr capacitors will operate safely at 135 % of kVAr
rating. The 35% above name plate value includes,
Capacitor Application

Capacitor application requires an evaluation of


kVAr caused by excess voltage at rated frequency
the power system to determine.
kVAr added by the harmonic voltage superimposed on the
The kVAr needs power frequency voltage.
The most effective location kVAr attributable to manufacturing tolerance.
The necessary protection
In general capacitors are installed The maximum recommended working voltage of capacitor is
110% of rated voltage. Shreem capacitors include a
At the substation : To supply the system
var needs most effectively. safety factor that permits them to tolerate without damage
momentary over voltages caused by switching or load changes.
At the near the load center : To obtain the
optimum var supply and voltage Capacitor - rated frequency is 50 Hz, kVAr output varies directly
correction. as the ratio applied frequency to rated frequency. Capacitors
designed to operate at other frequencies are also available.
At the end of the line : To achieve maximum
voltage correction.
Single Phase Power Capacitors

External fuse
Construction Features

Capacitors are protected by internal element fuses or by


A B
Internal discharge external unit fuse (Fig.2)
Internal discharge resistor

Internal element fuse resistor


High grade steel tank with epoxy light gray finish for
resistant to severely corrosive atmospheres

Wet process - porcelain bushing glazed for high strength,


Capacitor element

durability and hermetically sealed to the capacitor tank.

Internal discharge resistors that reduce terminal voltage at


50 Volts or less within ten minutes after capacitor has been
disconnected.

Stainless Steel - nameplate containing required IS data.


A. Capacitor with internal element fuses
B. Capacitor with external fuse

Fig. 2
Present k Desired
power factor power factor
Capacitor Bank-Sizing
0.40 2.3
2.2 1.00
A capacitive kVAr required for improvement of power
2.1
factor at a given load can be made from the nomogram
1.9
in Fig.3. However, in most cases the capacitor bank 0.45
1.8
rating has to be carefully selected after due consider- 1.7
ation of rated voltage of the system, system over- 1.6
0.50 1.5
voltages, harmonics in the system, rating of series 1.4
reactor if any, etc. Besides the correct sizing of the 1.3
0.55 1.2 0.95
capacitor bank, the reliability also depends on the right 1.1
selection of associated equipment such as the circuit 1.0
0.60 0.9
breaker, series reactor, protective relays, etc.
0.8
0.90
Above all, it is essential to check that the capacitor 0.65
0.7
0.6
installation will not cause dangerous stress to the
0.5
user's system due to resonance. 0.70 0.4
0.3
0.85
0.75 0.2
NOMOGRAM 0.1
A nomogram is used for calculating the necessary 0.80 0
0.80
capacitor power rating Q (kVAr), required to improve
0.85
the power factor of a load P (kW).
Q =kxP 0.90
c 0.75

Example :
What is the capacitor power rating required to
increase the power factor of an installation from 0.65 Fig. 3 Nomogram
to 0.97 if the load P is 1500 kW ?
From the nomogram K = 0.92 and hence
Q = 0.92 x 1500 = 1350 kVAr
c
Single Phase Power Capacitors

0.05 " 0.5-13UNC 9.05"

0.5-13UNC

D
D

C + 1"
C+1"
B

B
A

A
13.70 " E 3.70 "

17.6 " 17.6 "

NAME PLATE

0.472" X 0.71" SLOT


3.15 "

15.63 " 15.63 "

"A" BUSHING BILL


95 KV 125 KV 150 KV 200 KV
BUSH CREEP (INCHES) 15.00 17.71 21.65 29.5
DIM. "D" (INCHES) 8.07 10.31 10.39 14.17
DIM. "C" (INCHES) 15.95 18.18 18.27 22.00
BUSHING SELECTION

Weights & Dimensions


Wt. : 50 kVAR Wt. : 100 kVAR
Unit Voltage Dimensions (Inches) Unit Voltage Dimensions (Inches)
kV A B C D E kV A B B D E

2.4 5.12 3.94 10.63 8.07 5.83 2.4 8.27 7.87 14.57 8.07 5.83
4.8 5.12 3.94 10.63 8.07 5.83 4.8 8.27 7.87 14.57 8.07 5.83
7.2 5.12 3.94 10.63 8.07 5.83 7.2 8.27 7.87 14.57 8.07 5.83
7.62 4.73 3.94 10.63 8.07 5.83 7.62 8.27 7.87 14.57 8.07 5.83
13.28 5.12 3.94 10.63 8.07 5.83 13.28 8.27 7.87 14.57 8.07 5.83
19.92 5.32 3.94 10.63 8.07 5.83 19.92 9.05 7.87 14.57 8.07 5.83

Wt. : 150 kVAR Wt. : 200 kVAR


Unit Voltage Dimensions (Inches) Unit Voltage Dimensions (Inches)
kV A B C D E kV A B C D E

2.4 10.83 8.62 15.31 8.07 5.83 2.4 14.37 7.12 13.82 8.07 5.83
4.8 10.43 8.62 15.31 8.07 5.83 4.8 14.37 7.12 13.82 8.07 5.83
7.2 11.81 8.62 15.31 8.07 5.83 7.2 13.98 7.12 13.82 8.07 5.83
7.62 10.63 8.62 15.31 8.07 5.83 7.62 13.98 7.12 13.82 8.07 5.83
13.28 12.60 8.62 15.31 8.07 5.83 13.28 14.17 7.12 13.82 8.07 5.83
19.92 12.20 8.62 15.31 8.07 5.83 19.92 15.75 7.12 13.82 8.07 5.83

Wt. : 300 kVAR Wt. : 400 kVAR


Unit Voltage Dimensions (Inches) Unit Voltage Dimensions (Inches)
kV A B C D E kV A B C D E

2.4 19.29 8.62 15.31 8.07 5.83 2.4 24.80 13.38 20.08 8.07 5.83
4.8 19.29 8.62 15.31 8.07 5.83 4.8 24.80 13.38 20.08 8.07 5.83
7.2 19.68 8.62 15.31 8.07 5.83 7.2 25.20 13.38 20.08 8.07 5.83
7.62 18.90 8.62 15.31 8.07 5.83 7.62 24.21 13.38 20.08 8.07 5.83
13.28 20.47 8.62 15.31 8.07 5.83 13.28 25.98 13.38 20.08 8.07 5.83
19.92 21.06 7.75 16.57 10.20 5.83 19.92 26.18 12.52 21.34 10.20 5.83

Wt. : 500 kVAR Wt. : 600 kVAR


Unit Voltage Dimensions (Inches) Unit Voltage Dimensions (Inches)
kV A B C D E kV A B C D E

2.4 32.68 7.87 14.57 8.07 5.83 2.4 38.19 7.87 14.57 8.07 5.83
4.8 32.68 7.87 14.57 8.07 5.83 4.8 38.19 7.87 14.57 8.07 5.83
7.2 32.68 7.87 14.57 8.07 5.83 7.2 39.37 7.87 14.57 8.07 5.83
7.62 31.89 7.87 14.57 8.07 5.83 7.62 38.19 7.87 14.57 8.07 5.83
13.28 31.89 7.87 14.57 8.07 5.83 13.28 38.19 7.87 14.57 8.07 5.83
19.92 36.22 7.87 16.57 10.20 5.83 19.92 43.70 7.87 16.57 10.20 5.83
Production Graph ( in MVAR )
Single Phase Power Capacitors

4000

2900 2400
2700
2200

2016

2000 2001 2002 2003 2004 2005